    PartNo.797961.G

    0

    05/2006Technicalinforma

    tionissubjecttochangewithoutnotice!

    Dieselstrae 2, D-41469 Neuss Phone: +49 (0) 21 37 / 17-0 Internet: Email:Fax: +49 (0) 21 37 / 17-286 www.novar.de [email protected]

    Novar GmbH a Honeywell Company

    Fernkorngasse 10, A-1100 Wien Phone: +43 (0) 1 / 6 00 60 30 Internet: Email:Fax: +43 (0) 1 / 6 00 60 30-900 www.novar.at [email protected]

    Novar Austria GmbH

    Type: O TD TM

    Part No.: 802371 802271 802171

    Operating voltage: 8 - 42 V DC 8 - 42 V DC 8 - 42 V DC

    Quiescent current at UN approx.: 50 A 40 A 40 A

    Max. area to be monitored: 110 m2 30 m2 30 m2

    Max. height to be monitored: 12 m 7.5 m 7.5 m

    Application temperature: -20 C to +72 C -20 C to +50 C -20 C to +50 C

    Response temperature (1C /min): - +54 C to +65 C +54 C to +65 C

    VdS - No.: G 204060 G 204059 G 204058

    General technical data:

    Rated voltage: 19 V DC

    Storage temperature: -25C to +75C

    Type of protection : IP 42

    Material: ABS

    Colour: white, similar RAL 9010

    Weight: approx. 110 g

    Dimensions w/o base ( x H): 117 x 49 mm

    Dimensions base included ( x H: 117 x 62 mm

    Ordering data: Part No.

    (O) Optical detector IQ8Quad 802371

    (TD) Rate-of-rise detector IQ8Quad 802271

    (TM) Fixed heat detector IQ8Quad 802171

    Standard detector base 805590

    Detector base with relay contact 805591

    Flush mount housing for detector base 805571

    Label plate for detector base 805576

    IP protection for detector base 805570Further information is provided in our fire alarm catalogue.

    Technical Data:

    Input

    Output Output

    esserbus transponder

    IQ8Control M

    Powered loopIQ8Alarm

    Detector with base

    117

    62

    Schematic loop diagram: Dimensions (mm):