797961_G0
Transcript of 797961_G0
-
8/3/2019 797961_G0
1/2
-
8/3/2019 797961_G0
2/2
PartNo.797961.G
0
05/2006Technicalinforma
tionissubjecttochangewithoutnotice!
Dieselstrae 2, D-41469 Neuss Phone: +49 (0) 21 37 / 17-0 Internet: Email:Fax: +49 (0) 21 37 / 17-286 www.novar.de [email protected]
Novar GmbH a Honeywell Company
Fernkorngasse 10, A-1100 Wien Phone: +43 (0) 1 / 6 00 60 30 Internet: Email:Fax: +43 (0) 1 / 6 00 60 30-900 www.novar.at [email protected]
Novar Austria GmbH
Type: O TD TM
Part No.: 802371 802271 802171
Operating voltage: 8 - 42 V DC 8 - 42 V DC 8 - 42 V DC
Quiescent current at UN approx.: 50 A 40 A 40 A
Max. area to be monitored: 110 m2 30 m2 30 m2
Max. height to be monitored: 12 m 7.5 m 7.5 m
Application temperature: -20 C to +72 C -20 C to +50 C -20 C to +50 C
Response temperature (1C /min): - +54 C to +65 C +54 C to +65 C
VdS - No.: G 204060 G 204059 G 204058
General technical data:
Rated voltage: 19 V DC
Storage temperature: -25C to +75C
Type of protection : IP 42
Material: ABS
Colour: white, similar RAL 9010
Weight: approx. 110 g
Dimensions w/o base ( x H): 117 x 49 mm
Dimensions base included ( x H: 117 x 62 mm
Ordering data: Part No.
(O) Optical detector IQ8Quad 802371
(TD) Rate-of-rise detector IQ8Quad 802271
(TM) Fixed heat detector IQ8Quad 802171
Standard detector base 805590
Detector base with relay contact 805591
Flush mount housing for detector base 805571
Label plate for detector base 805576
IP protection for detector base 805570Further information is provided in our fire alarm catalogue.
Technical Data:
Input
Output Output
esserbus transponder
IQ8Control M
Powered loopIQ8Alarm
Detector with base
117
62
Schematic loop diagram: Dimensions (mm):