72.5 KV Catalog

download 72.5 KV Catalog

of 15

Transcript of 72.5 KV Catalog

  • 8/2/2019 72.5 KV Catalog

    1/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    1

    1 .General 1.1.1 LW30-72.5 Outdoor HV SF6 Circuit Breaker

    is of 3-phase, AC, 60Hz high-voltage switchgear,

    used for the control and protection of 72.5kV

    power distribution and transmission system, aswell as being used as the network interconnected

    circuit breaker and in the places switching

    capacitor bank.

    1.1 LW30-72.5 60Hz 72.5kV

    1.2 The LW30-72.5breaker is incorporated withCT26 spring operating mechanism.

    Self-energized arc control principle is adopted.

    The breaker has won a national patent which No.

    is ZL01 2 62031.9.

    1.2 LW30-72.5+ CT26ZL01 2 62031.9

    1.3 The breaker conforms to IEC62271-100:2001and GB1984-2003 about high-voltage alternating

    current circuit breakers.

    1.3 GB1984-2003 IEC62271-100:2001100

    1.4 Main characteristics

    The breaker provides the following advantages:

    Self-energized arc control principle, excellent

    breaking capacity; short arcing time, long

    electrical life, low operation noise; Adopting SF6

    as the insulating medium, no danger of fire and

    explosion, could be used for the population dense

    area; Spring operating mechanism is incorporated

    to provide simple and compact structure, safe and

    reliable operation.

    1.4 : SF6

    1.5 Working conditions

    1.5.1 Ambient temperature: -30+40(-40+40 for special order)

    1.5.2 Altitude: 2500m1.5.3 Air humidity

    Relative humidity at average per day: 95%Relative humidity at average per month: 90%1.5.4 Max. wind velocity: 35m/s

    1.5.5 Thickness of the ice covered: 10mm

    1.5.6 Seismic intensity:Horizontal acceleration: 0.3gVertical acceleration: 0.15g

    1.5 1.5.1 -30+40

    -40+401.5.2 2500m1.5.3 95%

    90%251.5.4 700Pa1.5.5 10mm1.5.6 0.3g

    0.15g

  • 8/2/2019 72.5 KV Catalog

    2/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    2

    1.5.7 Sunshine intensity: 0.1w/cm2

    (at wind velocity of 0.5m/s)

    1.5.8 Max. daily temperature rise: 251.5.9 Symmetrical Creepage distance: 31mm/kV

    1.5.10 Keep the breaker away from places withcombustible, explosive, corrosive materials

    and violent vibrations.

    1.5.7 0.1W/cm2( 0.5m/s)

    1.5.8 251.5.9 31mm/kV1.5.10

    2. Main technical parameters 2.2.1 Main technical data of the breaker are shown

    in table 1.

    2.1 1

    Table 1 1No. Name Unit LW30-72.51

    Rated voltage kV 72.52

    Rated current A 31503

    Rated short-circuit breaking current(Ie) kA 40 31.54

    Rated short-circuit making current (peak) kA 100 805 Rated short-time withstand current(4s) kA 40 31.56

    Rated peak withstand current kA 100 807

    Short-line fault breaking current kA Ie90 Ie758

    Out-of-phase breaking current kA Ie259

    Rated pressure of SF6 gas

    SF620 MPa 0.5 0.3810

    Alarm pressure of SF6 gas20 MPa 0.45 0.3411

    lock pressure of SF6 gas20 MPa 0.4 0.312

    Rated line-charging breaking current A 50

    13

    Rated lightning impulse withstand voltagePhase-to-phase or phase-to-earth kV 350Across open contacts kV 410

  • 8/2/2019 72.5 KV Catalog

    3/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    3

    14

    1 min. power frequency withstand voltage

    Phase-to-phase or phase-to-earth

    kV 160Across open contacts

    kV 20215

    Rated operating sequence

    O-0.3s-CO-180s-CO16

    Radio interference level

    uV 50017

    Close time

    ms 951518

    Open time

    ms 33719 Total breaking time ms 6020

    Opening asynchronism among phases

    ms 321

    Closing asynchronism among phases

    ms 522

    First-pole-to-clear factor

    1.523

    Resistance of main circuit

    60

    24

    Accumulative breaking times under

    rated short-circuit breaking current

    times 20

    25Mechanical duration

    times 1000026

    SF6 gas leakage

    SF6 /year 127

    moisture content of SF6 gas(20)SF6(20) v/v 15010-6

    28 Weight of SF6 gas for one set CB SF6 kg 12 1029

    Temperature class

    -30+40 -40+4030

    Weight of one CB

    kg 108831

    Heater voltage

    V AC220

  • 8/2/2019 72.5 KV Catalog

    4/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    4

    3. Structure and working principle 3. 3.1 The three phases that are separated share one

    common support and one CT26 spring operating

    mechanism. The output bent arm of the mechanism

    is connected with the circuit breaker through the rod.

    The circuit breaker is composed by the interrupter,

    pedestal, support and mechanism operating box. See

    the details in fig1.

    3.1 CT26 1

    3.1.1 Interrupter

    The interrupter adopts self-energizing theory. It

    is the most important part of the circuit breaker

    and is consist of the fixing contact support, fixed

    contact, fixed arcing contact, moving contact,

    moving contact support, moving arcing contact,

    gas cylinder, nozzle and middle contact. The fixed

    contact is fixed on the upper connection board.

    The fixed contact support is filled with F-03

    absorbent. The moving contact is fixed on the

    lower connection board and is connected with the

    wheel box through the insulating rod. See the

    details in fig2.

    3.1.1 F-03 2

    3.1.2 Connection board (terminal.)

    The connection board divides into the upper connection

    board and the lower connection board. One connection

    board has two terminals. Connection should be made

    according to requirements. The connection board is

    made of aluminum cast with silver. Dimension of the

    connection hole is shown in fig.3.

    3.1.2 3

    3.1.3 Post bushing

    The post bushing, under the interrupter, acts as a

    support to the interrupter and the insulation to

    the earth. It has high intensity and excellent air

    tightness.

    3.1.3

    3.1.4 Wheel box

    The wheel box, under the post bushing, delivers

    the motion of the operating mechanism into gas

    department to open or close the circuit breaker.

    The type O shaped seal ring enclosed the SF6

    gas in the wheel box. There are automatic cutout

    valves on the side of wheel box. These valves are

    3.1.4 OSF6

  • 8/2/2019 72.5 KV Catalog

    5/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    5

    sealed when the connecting pipe is unconnected.

    The thimbles in the connecting pipes will open

    the valves to guarantee that the three gas

    departments are connected when the connecting

    pipes are connected.

    3.1.5 Pedestal

    The pedestal props the circuit breaker and

    connects with the operating mechanism. It

    carries operating load of the circuit breaker. A

    gas density-pressure gauge is installed under the

    pedestal to monitor the SF6 gas pressure.

    3.1.5 SF6 SF6

    3.1.6 Mechanism operating box

    The Mechanism operating box that is fixed on the

    pedestal is enclosed with CT26 spring operating

    mechanism and secondary control panel. The

    output bent arm of the mechanism is connected

    with the bent arm of the wheel box under the

    middle phase through the rod. There are two40incoming holes at the bottom of the operating

    box.

    3.1.6 8 M16 CT2640

    3.2 Working principles 3.2 3.2.1 Working principle of interrupter

    It is of the self-energized arc-distinguishing principle.

    When breaking small inductive and capacitive

    current or rated current, the gas pressure in the

    cylinder and that out of the cylinder differs due

    to the mechanical motion of the moving contact,

    which distinguishes arcing.

    When breaking short-circuit current, arc is

    burning between the moving arc contact and the

    fixed arc contact, and SF6 gas in the cylinder is

    expanded, which increases the difference of the

    gas pressure in the cylinder and that out of the

    cylinder. Arcing is distinguished when current is

    over zero.

    3.2.1

    SF6

    3.2.2 Spring operating mechanism 3.2.2 The structure and the action principle are shown in fig.4. 4

  • 8/2/2019 72.5 KV Catalog

    6/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    6

    3.2.2.1 Charging motor 3.2.2.1It adopts HDZ electromotor that can use DC or

    AC power. The main data are shown in table.3.

    HDZ 3.

    Table3 3Rated operating voltage V

    V DC: 220 AC:220Rated current of the motor A

    A 2.8Range of the normal operating voltage

    85%~110% rated operating voltage

    85%110%Charging time at rated operating voltage sS Less than 15

    Power of the charging motor

    600W

    3.2.2.2 Closing electromagnet 3.2.2.2It adopts solenoid type electromagnet. The main

    data are shown in table.4. 4

    Table4 4Rated operating voltage VV -110 -220Rated operating current AA 3.3 2.3

    Resistance of the coil (20) 20 33 94

    Range of the normal operating voltage 85%~110% rated operating voltage85%110% 3.2.2.3 Opening electromagnet 3.2.2.3It adopts solenoid type electromagnet. The main

    data are shown in table.5.

    5

    Table5 5Rated operating voltage VV -110 -220

  • 8/2/2019 72.5 KV Catalog

    7/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    7

    Rated operating current AA 5.8 2.8Resistance of the coil (20)

    20 19 78

    Range of the normal operating voltage65%~120% rated operating voltage; no opening in

    continuous 3 operations at less than 30% rated voltage65%120% 30% 3

    3.2.2.4 Auxiliary switch

    F9-28I type auxiliary switch that has 14 couple of

    N/O contacts and 14 couple of N/C contacts is

    adopted. The continuous current of the contact is

    not less than 10A.

    3.2.2.4 F9-28 14 14 10A

    3.2.2.5 Travel switch has a couple of N/O contact

    and a couple of N/C contact. The continuous

    current of the contact is not less than 5A.

    3.2.2.5 5A

    3.2.2.6 The continuous current of the connection

    terminal is not less than 30A.

    3.2.2.6 30A

    3.2.2.7 Electric principle and wiring of the circuit

    breaker are shown in fig11 and fig 11.1.

    3.2.2.7 1111.1(

    3.2.2.8 Charging of the operating mechanism

    Closing spring is at uncompressed station. Theratchet pawl shaft(6) is connected with the

    electromotor by gears. See the details in fig 4(A).

    3.2.2.8 (1)(6) 4(A)

    When charging, the electromotor forces the

    ratchet shaft (6) to rotate clockwise; the two

    ratchet pawls(5) on the ratchet shaft push the

    ratchet wheel(3) to rotate counter clockwise

    alternately to drive the dowel and rod on ratchet

    wheel to compress the closing spring; the closing

    spring drives the ratchet wheel to turn counter

    clockwise about 2when the dowel reaches the lefttop point, and the charging holding dowel(4) onthe ratchet wheel is buttoned by the holding

    detent(15) to finish charging. The electromotor is

    cut off and the ratchet pawl departs from the

    ratchet wheel at this time.

    (6) (5)(3) 2 (4) (15)

    3.2.2.9 Closing operation

    The closing spring is charged when the breaker is

    at opening state. See the details in Fig 4(B).

    3.2.2.9 4B

  • 8/2/2019 72.5 KV Catalog

    8/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    8

    When the mechanism receives the closing order, the

    closing coil is to be electrified and the attraction of

    the moving iron core of the closing electromagnet

    drives the closing conduct rod to strike the closing

    detent (13) to rotate counter-clockwise and releasesthe energy holding detent (15). Then, the closing

    spring drives the ratchet to rotate clockwise with

    high speed, and the cam(18)that is coaxial with the

    ratchet beats the roller on the large bent arm(8)to

    force the output bent arm (7) to move upward and

    complete closing. At that time, the opening spring is

    compressed to store energy to prepare for the

    opening operation.

    (13)(15) (3) (18)(8) (7) (16)

    The closing operation can also be realized by attacking

    the conduit of closing electromagnet by hand.

    After finishing the closing operation, motor begins to

    store energy for the closing spring again. The state of

    the mechanism at this time is shown in Fig 4C.

    4C

    3.2.2.10 Opening operation

    Both of the closing spring and opening spring are

    charged when the breaker is at closing state.

    3.2.2.10 (1)(16) 4(C)

    When the mechanism receives the opening demand,

    opening coil is to be electrified and the attraction of

    the moving iron core of opening electromagnet drives

    the opening conducted rod to strike the opening detent

    (10) to revolve counter clockwise and releases the

    closing holding detent (9).The opening spring drives

    the bent arm to turn clockwise to force the main part

    of the breaker to complete opening operation and the

    large bent arm to move downward to press down the

    closing holding detent to make the mechanism at the

    opening state, see the details in Fig4 (B).

    (10) (9) (16)(8) (9) 4(b)

    The opening can also be competed by attacking

    the conduit of opening electromagnet by hand.

    3.2.2.11 Bound-resistant device

    This mechanism is equipped with mechanical

    bound-resistant device. Electrical bound-resistant

    3.2.2.11

  • 8/2/2019 72.5 KV Catalog

    9/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    9

    device is also on requirement. 3.2.3 The circuit breaker is designed with SF6

    density-controller gauge with automatic monitor

    function to the temperature compensation. Thegauge can not only display the pressure of SF6

    gas but also amend the affect of pressure

    difference arising from temperature change. The

    gauge will send out alarm signal when the

    pressure of gas in circuit breaker is lower than

    the alarm value. The gauge will send out locking

    signal when the pressure of gas in circuit breaker

    is lower than the locking value.

    3.2.3 SF6 SF6 20

    4. Packing, transportation, check before

    acceptance and storage

    4.

    4.1 Packing, transportation: The CB is disjointed

    to pack and transport. The accompanying

    documents should be delivered to the user by the

    transporting unit. The gas compartments are

    filled with SF6 gas (0.05Mpa). The main body of

    the circuit breaker is at closing state; the

    mechanism is at opening state and uncharged.

    The packages are forbidden to be overturned,

    inverted, impacted.

    4.1 : 0.05MPa()SF6

    4.2 Check before acceptance

    As the circuit breaker arrived, users should

    check the accompanying documents first. Then

    open the packages with the transporter and

    check the circuit breaker and accessory

    according to the packing list. Please contact the

    manufacturer in time if you have any question.

    Pay attention to the bushing of the circuit

    breaker when you open the packages.

    4.2

    4.3 Storage: The circuit breaker should be stored

    at drying ventilated house without pollution, if it

    wont be installed at once. If it wont be installedfor a long term, periodical check is necessary.

    4.3

  • 8/2/2019 72.5 KV Catalog

    10/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    10

    5. Installation and examining before

    operation

    5.

    5.1 Foundation

    The foundation dimension is shown in fig.8. The

    height difference between the two sides of the

    foundation should be within 2mm. The upward

    dynamic loading is 20kN and downward dynamic

    loading is 20kN.

    5.1 8 2mm 20kN 20kN

    5.2 Install the circuit breaker under the guidance

    of manufacturers personnel(s).

    5.2

    5.3 Inflating:

    5.3.1 The following procedure must be observed.

    A. Lay the SF6 gas bottle on the ground, and

    connect the pipeline to the decompression valve.

    It is shown in fig.7.

    B. Open the valve of gas bottle, then open the

    pressure reduction valve to make the pressure at

    low pressure side be 0.02~0.04MPa for 5-10

    seconds to wash the pipeline.

    C. Connect the pipeline to the automatic cutout

    valve of drive box, then open the pressure

    reduction valve slowly. The pressure difference

    between pressure reduction valve and the circuit

    breaker will not higher than 0.05MPa. When the

    gas pressure of circuit breaker is near to the

    rated value, inflating slowly to prevent too high

    pressure.

    D. Close the pressure reduction valve when the

    pressure is equal to the rated filling pressure.

    5.3 5.3.1 a. 7b. 0.02-0.04MPa 5-10 c. A 0.05MPad.

    5.3.2 Adopting the leak hunting device with

    sensitivity grade 10-6

    to all the sealing planes after

    the breaker is filled to the rated voltage. There

    should be no leaking. Contact the manufacturer

    immediately upon finding leaking.

    5.3.2 10-6

    5.3.3 Moisture Check 5.3.3 SF6

  • 8/2/2019 72.5 KV Catalog

    11/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    11

    Users should check moisture in 24 hours after

    inflating. The measured values should be in accordance

    with fig9 about the moisture content-temperature curve.

    24 95.3.4 manual charging of the mechanism is shown

    in fig.10. The circuit breaker could be adjusted

    thrown into operation when is filled with SF6 gas.

    Power must be cut off.

    5.3.4 10

    5.4 Checkup before operation

    5.4.1 Leakage Detect

    Adopting the SF6 detector with flexibility not

    lower than 10-6

    to check the flange linking planes

    and the connectors of the linking pipe in 24 hours

    at the finish of gas filling.

    5.4 5.4.1 10-6atmm3/s 24

    5.4.2 Moisture Measuring

    Connecting the needled-shaped pressure reduction

    valve to the self-sealing valve to control the gas flow.

    Then using micro-moisture detecting instrument to

    measure the moisture which should be within 15010-6(v/v) at 20 at checkup and 30010-6 (v/v) at 20during operation.

    5.4.2 5.3.3 9 150L/L20300L/L20

    5.4.3 Main-circuit resistance measuring

    DC pressure deduction method is adopted. measure the

    main-circuit resistance which should be within 60ubetween the upper and the lower connection boards

    when connecting with 100A DC current at close state.

    5.4.3 100A 60

    5.4.4 Insulation Checkup

    a. There should be no flash and abnormal noise

    when applying power frequency voltage to the

    main circuit.

    b. There should be no penetrationflash andother abnormal situation when applying 2000V of

    power frequency voltage to the secondary circuit

    for 1 minute, excluding the relay coil motor.

    5.4.4a.

    b. 2000V-1min

    5.4.5 Measuring the opening and closing

    synchronism and time under the rated operating

    voltage.

    5.4.5 ,

    5.5 D04 moisture-resistant glum should be

    smeared between the mechanical box and the

    5.5 DO4

  • 8/2/2019 72.5 KV Catalog

    12/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    12

    transition support. DO45.6 Connection of the Primary bus bar of the

    Main Circuit and the Earthing Line

    5.6

    5.6.1 The incoming line and the outgoing line ofthe primary bus bar should be connected to the

    upper and lower connection boards respectively.

    The dimension of the open hole on the connection

    board is shown in Fig3. The connection board

    should be wiped with the white cloth submerged

    with alcohol, while emery cloth is forbidden,

    before connecting.

    5.6.1 3

    5.6.2 The earthing line should be connected to the

    earthing bolt (with earthing symbol) on the

    support.

    5.6.2

    5.7 Connection of the Secondary Circuit

    Taking off the rubber glove under the mechanical

    box and mounting with GBL connector which is

    to be penetrated with incoming cable and

    phase-to phase cable. Fig11 11.1 show thesecondary connection. The lead area should be

    within 2.5 mm2.

    5.7 11 11.1

    5.8 Then it is the time to throw the breaker into

    operation as soon as cleaning the site.

    5.8

    6. Maintenance and repair 6.6.1 Daily Maintenance

    Do the following work one time every week:

    a. observing and recording the gas pressure to see

    whether it is normal

    b. observing and the close and open indication

    positions

    c. observing the internal part of the breaker to

    make sure there are no abnormal noise and over

    heating

    d. observing the motion of the mechanism to

    make sure they are normal

    e. checking the fixed nuts to make sure their

    6.1 SF6a.b.c.d.

    e.

  • 8/2/2019 72.5 KV Catalog

    13/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    13

    fixedness.

    6.2 annual check of circuit breaker

    Short-time power cut and cut-down of the control

    power should be guaranteed during annual

    maintenance.

    6.2

    6.2.1 Clean the dirts on the surface of the porcelain.

    6.2.2 Measure the micro-water content of the gas in

    the breaker, and make a record.

    6.2.3 Check the fixed nuts to make sure their

    fixedness.

    6.2.4 Check the upper and lower connection boards to

    see whether there are overheating and color changed,

    if do, using abrasive that is less than 250# to wipe the

    boards then fixing the primary bus bar again.

    6.2.5 The above procedure of the annual maintenance

    could be done simultaneously and have no order.

    6.2.1 6.2.2 6.2.3 6.2.4 250#6.2.5

    6.3 supply the gas

    If the density-pressure meter sends out an alarm

    single during operation, gas should be supplied

    during operation.

    6.3

    6.4 notes during check and repair 6.4 6.4.1 Closing or opening is forbidden when the

    breaker is at vacuum state to avoid damaging the

    parts of arc control device.

    6.4.1

    6.4.2 Lubricate the driving bent arm the rolling

    parts.

    6.4.2

    6.4.3 Release the spring energy during examining

    and repairing the mechanism. The way to release

    energy is: do one cycle closing and opening

    operation with power off.

    6.4.3

    7. Repair parts, special tools and accessories 7.7.1 repair parts

    The repair parts were provided by the

    manufacturer on users order. Table 6(1)62andtable 7 show the spare parts to be selected. The

    7.1 6162 7

  • 8/2/2019 72.5 KV Catalog

    14/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    14

    quantity regulated in the table in only for reference. Table6(1) 6(1)

    No.Code No.

    Name and specification

    Quantity

    Remark

    1 5TK.177.007GGas-filling pipe

    1

    It should be connected with

    pressure reduction valve in one end

    and self-sealing valve in the other

    end when filling gas to the breaker

    2 5TK.253.027Special spanner1

    1 1For manual charging

    3 5TK.177.007

    Connector for measuring

    moisture

    1

    One end should be connected tocircuit beaker and the other should

    be connected to the cone-shaped

    pressure reduction valve.

    Table6(2) 6(2)No. Code No. Name and specification Quantity Remark1

    D04 water resistant glueD04FQ 2 Apply it on the water-resistant place2

    7501 vacuum silicon grease

    7501 1 Used for the gas seal gasket3

    M2060 bolt ,flat washer andflexible washer

    M2060 12 of eachUsed for the protection cover

    of the support7.2 Spare parts providing according to the

    contract

    7.2

    Table 7 7No. Type designate Name Quantity1 5TK.520.051.34 Opening and closing coils One for each1 HDZ-26005A

    Motor 13 TZ7311

    Travel switch 14 3TH30 22-1XM4 DC contactor 1

  • 8/2/2019 72.5 KV Catalog

    15/15

    LW30-72.5 Outdoor HV SF6 Circuit Breaker

    15

    7.3 Accessories providing according to the

    contract7.3

    No.

    Type designate

    Name

    Quantity

    Remark

    1 LF-1

    SF6 detector 1 For detecting leakage2 DWS-

    moisture measuring instrument

    matched with cone-shaped pressure

    reduction valve1

    For measuring moisture3

    SF6 gas

    SF6 1 bottle For filling and evacuating4 YQY-07

    Oxygen pressure reduction valve 1 For filling and evacuating5 2X-4

    Vacuum pump 1For pumping

    during maintenance8. Notice for Order

    Please specify the following items when ordering.

    a. type designate of the breaker and the mechanism

    b. ratings including voltage, current, breaking

    current and so on

    c. ambient temperature

    d. closing and opening operating voltage of the

    operating mechanism, and the working voltage of

    the charging motor

    e. outgoing direction of the bus bar terminals

    f. spare parts, auxiliaries, abbreviation, code No,

    Quantity

    8.a.b.()c.d.e.f.

    9. Documents accompanying the machine

    a. one copy of packing listb. one copy of qualification certificate

    c. one copy of manual instruction.

    9. a.b.c.

    10. Drawings

    See the drawings of Fig1 through Fig 12 in the

    Appendix.

    10. 1 12