7.
7.5.52
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
Vertically laid panels require a structure to provide
support for the panel self weight and also resist wind
pressure and suction loads. The main frame structure
shown is a typical arrangement. The load span of the
panels depends on structural / static requirements,
which is specifi c for each project.
External Corner Detail Cill Drip Detail
Construction Method – Vertically Laid Panels
7.
7.5.53
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
Main frame grid
Due to load span table
Secondary steel post
External Corner Detail Cill Drip Detail
Horizontally laid panels require a structure to
provide support for the panel self weight and also
resist wind pressure and suction loads. The main
frame structure shown is a typical arrangement. The
load span of the panels depends on structural / static
requirements, which is specifi c for each project.
Construction Method – Horizontally Laid Panels
7.
7.5.54
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
a a 40
04
P
22
P
17
P
04
P
17
P
21
P
26
P
175a
K
21
P
26
P
or
Steel structure
Site applied rigid
urethane board
Concrete structure
04
P
08
P
214
K
143
K
04
P
16
P
17
P
10
aa
D
at 300 mm
10
02
P
214
K
08
P
08
P
134
K
02
P
16
P
17
P
aa
D
at 300 mm
at 300 mm
Panel to Panel Junction (vertical)
Secret fi xed option Through fi xed option
Note:
a according to structural / static requirements
Note:
a according to structural / static requirements
Panel to Panel Junction Top hat (horizontal)
7.
7.5.55
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
03
Z
04
P
07
P
182
K
08
P
183
K
04
P
17
P
D
10
a
D
at 500 mm
at 500 mm
Site applied insulation
16
P
04
P
214
K
08
P
134
K
04
P
08
P
17
P
D
a
D
10
at 300 mm
at 300 mm
Site applied insulation
Horizontal Panel to Vertical Panel Junction
Vertical Panel to Horizontal Panel Junction
Note:
a according to structural / static requirements
Note:
a according to structural / static requirements
7.
7.5.56
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
14
P
02
P
08
P
118
K
222
K
02
P
08
P
14
P 50
at 300 mm at 300 mm
Site applied insulation
07
P
118
K
07
P 70~90
a a
D
04
P
08
P
26
P
178
K
08
P
04
P
50
26
P
Site applied insulation
at 300 mm at 300 mm
Expansion Joint (vertical)
Expansion Joint (horizontal)
Note:
a according to structural / static requirements
This joint allows for up to 20 mm expansion. In other cases solve according concrete situation.
7.
7.5.57
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
02
P
08
P
07
P
07
P
02
P
08
P
14
P
14
P
146
K
146
K
a
at 300 mm at 300 mmPE tube
14
P
14
P
07
P
07
P
02p
P 08
P
147
K
08
P
02
P
118
K
a a
50
D
TF
D
FR
Site applied insulation
at 300 mm at 300 mm
Expansion Joint
Note:
a according to structural / static requirements
Transition Between Types of Panel (TF / FR)
Note:
a according to structural / static requirements
7.
7.5.58
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
07
P
07
P
31
P
31
P
152
K
152
K
at 300 mmat 300 mm
at 300 mm at 300 mm
Site applied insulation
02
P
155
K
07
P
155
K
05
Z
D
50
70
at 300 mm
Neutral silicone sealant
as required
Butyrub building cement
Panel Head Junction (Vertically Laid Panels)
Floor Slab Junction (Vertically Laid Panels)
7.
7.5.59
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
07
P
14
P
08
P
166
K
02
P
187
K
08
P
14
P
07
P
D
D
Direction of lay
at 300 mm
at 300 mm
Site applied insulation
04
P
08
P
07
P
14
P
106
K
159
K
14
P
07
P
08
P
04
P
D
a
D
a
at 300 mm
at 300 mmSite applied insulation Direction of lay
External Corner (vertical)
External Corner (horizontal)
Note:
a according to structural / static requirements
7.
7.5.60
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
12
R
08
P
07
P
14
P
118
K
14
P
07
P
08
P
02
P
191
K
02
P
04
P
A
B
C
R
at 300 mm
at 300 mm
Direction of lay
Site applied insulation
External Curved Corner (vertical)
Note:
Panel R12, max. length 8,000 mm
Amin
, Cmin
= 60 mm
A + B + C = max. module 1,000 mm
α = 80 ̊–175 ̊
Rmin
= D
profi lation to be discussed
7.
7.5.61
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
08
P
26
P
08
P
17
P
04
P
164
K
17
P
12
R
R
A
B
C
17
P
06
P
04
P
17
P
08
P
164
K
26
P
08
P
a
a
at 300 mm
at 300 mm
at 300 mm
at 500 mm
at 300 mm
Site applied insulation
Site applied insulation
Note:
a according to structural / static requirements
Panel R12, max. length 8,000 mm
Amin
, Cmin
= 60 mm
A + B + C = max. module 1,000 mm
α = 80 ̊–175 ̊
Rmin
= D
profi lation to be discussed
External Curved Corner (horizontal)
7.
7.5.62
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
08
P
14
P
02
P
191
K
118
K
02
P
14
P
08
P
11
R
07
P
04
P
A
B Direction of lay
at 300 mm
at 300 mm
Site applied insulation
External Cranked Corner (vertical)
Note:
Panel R11, max. length 8,000 mm
Amin
, Bmin
= 250 mm
A + B = module 1,000 mm
α = 80 ̊–175 ̊
profi lation to be discussed
7.
7.5.63
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
08
P
185
K
08
P
a a
17
P
04
P
17
P
15
R
A
B
α
17
P
04
P
185
K
26
P
04
P
17
P
a a
26
P
26
P
08
P
at 300 mm
at 300 mm
at 300 mm
Site applied insulation
Site applied insulation
External Cranked Corner (horizontal)
Note:
a according to structural / static requirements
Panel R15, maximum length of an unsupported arm of single cranked wall panel is 1,000 mm. For longer cranks
additional steelwork is required.
Amin
, Bmin
= 250 mm
Amax
= 1,500 mm
Bmax
= 4,500 mm
α = 90 ̊–180 ̊
module 1,000 mm
profi lation to be discussed
7.
7.5.64
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
17
P
04
P
26
P
185
K
04
P
26
P
17
P
16
R
a a
α
A
B
C
β
17
P
04
P
185
K
26
P
04
P
17
P
a a
08
P
08
P
at 300 mm
at 300 mm
Site applied insulation
Site applied insulation
External Chamfered Corner (horizontal)
Note:
a according to structural / static requirements
Panel R16, maximum length of an unsupported arm of double cranked wall panel is1,000 mm. For longer
cranks additional steelwork is required.
Amin
, Cmin
= 250 mm
Amax
, Cmax
= 1,500 mm
Bmax
= 3,000 mm
α, β = 90 ̊–180 ̊
module 1,000 mm
7.
7.5.65
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
159
K
14
P
09
P
08
P
113
K
02
P
14
P
09
P
D
D
Direction of lay
Direction of lay
at 300 mm
Site applied insulation
159
K
04
P
14
P
09
P
106
K
08
P
14
P
09
P
a
a
D
D
at 300 mm
Internal Corner (vertical)
Internal Corner (horizontal)
Note:
a according to structural / static requirements
7.
7.5.66
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
184
K
04
P
03
Z
18
P
16
P
D
10
min
. 10
0 m
m
at 500 mm
04
P
17
P
08
P
214
K
184
K
18
P
a
D
10
min
. 100 m
mat 300 mm
Concrete Wall Cill (vertical)
Concrete Wall Cill (horizontal)
Note:
a according to structural / static requirements
7.
7.5.67
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
07
P
07
P
23
P
∅d
Dia
met
er –
d
Site applied flashing
Tubing sleeve
Piping
Site applied insulation (fire
rated if hot exhaust)
Wall Pipe Extractor Flue
Note:
Complete installation contents:
– passage piping packing
– sealing material
– necessary quantity of fasteners
Piping sleeves for better additional sealing of passages can be ordered according to diameter of piping.
See to the section of the Accessories or contact Kingspan Technical Service Department for range of piping
sleeves.
7.
7.5.68
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
07
P
223
K
143
K
21
P
04
P
16
P
40
a
10–
15
D
10
Site applied insulation
Window frame
17
P
07
P
224
K
04
P
08
P
183
K
211
K
08
P
21
P
35–
40
a
20
D
Site applied insulation
Window frame
adjust the flashing to
the window frame
at 200 mm
at 500 mm
Plastic Window – recessed (vertical) – Head
Plastic Window – recessed (vertical) – Cill
Note:
The fl ashing K211 adjusts according to the window frame.
a according to structural / static requirements
Note:
a according to structural / static requirements
7.
7.5.69
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
04
P
16
P
143
K
a
10
–1
5
D
10
Site applied insulation
Window frame
Note:
a according to structural / static requirements
17
P
08
P
02
P
219
K
21
P
07
P
223
K
40
D
10–15
at 300 mm
Site applied insulation
Window frame
Plastic Window – recessed (vertical) – Jamb
Plastic Window – coplanar (vertical) – Head
7.
7.5.70
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
08
P
21
P
02
P
228
K
21
P
08
P
17
P
D
10–15
at 200 mm at 200 mm
Window frame
Site applied
insulation
17
P
04
P
151
K
08
P
21
P
D
a
at 200 mm
Neutral silicone sealant
Window frame Site applied insulation
Note:
a according to structural / static requirements
Plastic Window – coplanar (vertical) – Cill
Plastic Window – coplanar (vertical) – Jamb
7.
7.5.71
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
04
P
04
P
02
P
a
Aluminium Window – vertical (coplanar)
Head
Cill
Jamb
Note:
a according to structural / static requirements
7.
7.5.72
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
04
P
16
P
157
K
08
P
158
K
197
K
07
P
09
P
d
a
D X
at 300 mm
min
. 10 m
m
Site applied insulation Site applied rigid urethane board Segment of overhead door
17
P
08
P
02
P
07
P
197
K
09
P
218
K
d
D
X
at 300 mm
Site applied rigid
urethane board
Segment of overhead door
Roller Shutter Door (vertical) – Head
Roller Shutter Door (vertical) – Jamb
Note:
a according to structural / static requirements
X specify dimension to defi ne fl ashing K158
Note:
a according to structural / static requirements
X specify dimension to defi ne fl ashing K218
7.
7.5.73
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
223
K
07
P
16
P
143
K
21
P
02
P
160
K
08
P
D
10
–1
5
40
1
0
at 1,000 mm
at 300 mm
Site applied insulation
Window frame
07
P
223
K
21
P
04
P
198
K
182
K
07
P
03
Z
16
P
15
60
D
10
at 500 mm
2× at 500 mm
Site applied insulation
Window frame
Plastic Window – recessed (horizontal) – Head
Plastic Window – recessed (horizontal) – Head (cut end)
7.
7.5.74
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
07
P
224
K
17
P
02
P
08
P
183
K
211
K
08
P
21
P
D
20
35
–4
0
at 200 mm
at 500 mm
at 1,000 mm
adjust the flashing to
the window frame
Site applied insulation
Window frame
07
P
224
K
17
P
04
P
08
P
230
K
08
P
21
P
D
20
35–
40
at 200 mm
at 300 mmat 1,000 mm
adjust the flashing to
the window frame
Site applied insulation
Window frame
Plastic Window – recessed (horizontal) – Cill
Plastic Window – recessed (horizontal) – Cill (cut end)
7.
7.5.75
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
143
K
16
P
02
P
160
K
08
P
10
–1
5
D
10
at 300 mm
at 1,000 mm
Site applied insulation
Window frame
17
P
04
P
08
P
144
K
21
P
07
P
223
K
40
D
a
10–15
at 300 mm
Window frame
Site applied insulation
Plastic Window – recessed (horizontal) – Jamb
Plastic Window – coplanar (horizontal) – Head
Note:
a according to structural / static requirements
7.
7.5.76
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
04
P
154
K
08
P
21
P
08
P
17
P
D
a
10–15 at 200 mmat 200 mm
Window frame
Site applied insulation
17
P
02
P
151
K
08
P
21
P
D
at 200 mm
at 1,000 mm
Neutral silicone sealant
Window frame Site applied insulation
Plastic Window – coplanar (horizontal) – Cill
Plastic Window – coplanar (horizontal) – Jamb
Note:
a according to structural / static requirements
7.
7.5.77
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
08
P
160
K
02
P
at 300 mm
08
P
160
K
02
P
at 300 mm
02
P
Aluminium Window – coplanar (horizontal)
Head
Cill
Jamb
7.
7.5.78
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
08
P
157
K
214
K
08
P
160
K
02
P
16
P
158
K
197
K
07
P
09
P
D X
d
10
at 300 mm
at 300 mm
Site applied insulation Site applied rigid urethane board Segment of overhead door
08
P
04
P
17
P
165
K
09
P
197
K
07
P
X D
a d
at 300 mm
Site applied rigid
urethane board
Segment of overhead door
Roller Shutter Door (horizontal) – Head
Roller Shutter Door (horizontal) – Jamb
Note:
X specify dimension to defi ne fl ashing K158
Note:
a according to structural / static requirements
X specify dimension to defi ne fl ashing K165
7.
7.5.79
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
31
P
106
K
14
P
31
P
02
P
220
K
08
P
07
P
at 300 mm
at 300 mm at 300 mm at 300 mm
Site applied insulation
18
P
221
K
02
P
08
P
31
P
106
K
14
P
07
P
D
at 500 mmPlaster
Direction of lay
at 300 mmSite applied
insulation
Butyrub building
cement
Wall Junction (vertical)
Wall Junction (vertical)
7.
7.5.80
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
31
P
106
K
08
P
04
P
14
P
07
P
a
at 300 mm at 300 mm
at 300 mm
Site applied insulation
18
P
219
K
02
P
08
P
17
P
a
D
at 300 mmButyrub building cement
Wall Junction (vertical)
Note:
a according to structural / static requirements
Note:
a according to
structural / static requirements
Wall Junction (horizontal)
7.
7.5.81
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
18
P
194
K
08
P
04
P
31
P
106
K
14
P
07
P
a
at 300 mm
at 300 mm
Site applied insulation Butyrub building cement
Plaster
18
P
144
K
08
P
04
P
17
P
D
a
at 300 mm
Butyrub building
cement
Plaster
Wall Junction (horizontal)
Wall Junction (horizontal)
Note:
a according to
structural / static requirements
Note:
a according to
structural / static requirements
7.
7.5.82
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
04
P
17
P
157
K
08
P
21
P
04
P
09
P
07
P
07
Z
08
Z
07
Z
07
P
09
P
17
P
D
D
a a
10
at 300 mm
Louvre Head & Cill (vertical)
Note:
a according to structural / static
requirements
When panels are site cut for fi tting the
louvre systems, the panel joint above the
louvre head has to be sealed to prevent
water ingress – neutral silicone sealant.
02
P
17
P
09
P
07
P
07
Z
08
Z
07
Z
07
P
09
P
17
P
02
P
21
P
08
P
08
P
21
P
D
at 300 mm at 300 mm
Louvre Jamb (vertical)
7.
7.5.83
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Wall Panels
160
K
02
P
21
P
08
P
156
K
08
P
160
K
08
P
17
P
09
P
07
P
07
Z
08
Z
07
Z
07
P
09
P
17
P
02
P
D
D
at 300 mm
at 300 mm
at 300 mm
Drip flashing glued onto panel and
sealed with neutral silicone sealant
04
P
17
P
09
P
07
P
07
Z
08
Z
07
Z
07
P
09
P
17
P
04
P
21
P
08
P
08
P
21
P
D
a a
at 300 mm at 300 mm
Louvre Head & Cill (horizontal)
Louvre Jamb (horizontal)
Note:
When panels are site cut for fi tting the
louvre systems, the panel joint above the
louvre head has to be sealed to prevent
water ingress – neutral silicone sealant.
Note:
a according to structural / static requirements