5
=(Lm+L2)/R2 NEMA MG1 Definition of Toc
description
Bus
Transcript of 65820162963 Nema Mg1 Fast Bus Transfer Info r3
![Page 1: 65820162963 Nema Mg1 Fast Bus Transfer Info r3](https://reader035.fdocuments.us/reader035/viewer/2022080223/55cf92a9550346f57b987bd5/html5/thumbnails/1.jpg)
=(Lm+L2)/R2
NEMA MG1 Definition of Toc
![Page 2: 65820162963 Nema Mg1 Fast Bus Transfer Info r3](https://reader035.fdocuments.us/reader035/viewer/2022080223/55cf92a9550346f57b987bd5/html5/thumbnails/2.jpg)
NEMA MG1 Requires 2 * Toc prior to Reclosing
![Page 3: 65820162963 Nema Mg1 Fast Bus Transfer Info r3](https://reader035.fdocuments.us/reader035/viewer/2022080223/55cf92a9550346f57b987bd5/html5/thumbnails/3.jpg)
Remainder of NEMA MG1 20.24
![Page 4: 65820162963 Nema Mg1 Fast Bus Transfer Info r3](https://reader035.fdocuments.us/reader035/viewer/2022080223/55cf92a9550346f57b987bd5/html5/thumbnails/4.jpg)
Time Constant Estimation ECW Vent Fan ~ 0.36 seconds (see next slide).
![Page 5: 65820162963 Nema Mg1 Fast Bus Transfer Info r3](https://reader035.fdocuments.us/reader035/viewer/2022080223/55cf92a9550346f57b987bd5/html5/thumbnails/5.jpg)
Time Constant Calculation
• Ifinal = Io *exp(-t/Tau)
• -ln (Ifinal/Io) = t/tau
• ln(I0/Ifinal) = t/tau
• tau = t/ln(I0/Ifinal)
• Tau = 0.24/ln(2) = 0.36 sec
• Minimum off-time = 1.5*0.36sec = 0.52 sec