63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

135
British Electricity International Modern Power Station Practice Third Edition incorporating Modern Power System Practice TURBINES, GENERATORS AND ASSOCIATED PLANT. Volume C Only Ch 6: The Generator

description

CEGB manual

Transcript of 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Page 1: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

British Electricity International

Modern Power Station Practice Third Edition incorporating Modern Power System Practice

TURBINES, GENERATORS AND ASSOCIATED PLANT. Volume C Only Ch 6: The Generator

Page 2: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

.!

British Electricity International .· .·•· ·

. Modern ..... Power Station ··

Practice Third Edition incorporating Modern Power System Practice

TURBINES, GENERATORS AND

ASSOCIATED PLANT. , Volume· c ....

8~rgamon Press · '~i' ..

home
Sticky Note
Unmarked set by home
Page 3: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

MODERN POWER STATION PRACTICE

Third Edition

Incorporating Modern Power System Practice

British Electricity International, London

·volume C

Turbines, Generators and Associated Plant

PERGAMON PRESS OXFORD . NEW YORK . SEOUL . TOKYO

Page 4: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

' -..ain Editorial PaneJ

: w Littler, BSc, PhD, ARCS, CPhys, FlnstP, CEng. FlEE (Chairman)

~ ::-:"essor E. J. Davies, DSc, PhD, CEng, FlEE

- E Johnson

= ( rkbyf BSc/ CEng, MIMechE, AMIEE

= 3 Myerscough, CEng, FIMechE, FINucE

" ••.right, MSc, ARCST, CEng, FlEE, FIMechE, FlnstE, FBlM

Volume Consulting Editor 7 =-:"'essor E. J. Davies, DSc, PhD, CEng, FlEE

Volume Advisory Editor = Hambling, CEng, MlMechE

Authors :- ::::~--s 1 & 2 G. F. Hunt, BSc(Eng), CEng, MIEE

_ -::::~" 3 M. Douglass, CEng, MIMechE

-~--"" 4 A. R. Woodward, BSc(Eng) D. L. Howard, BSc, CEng, MIMechE E. F. C. Andrews, CEng, MlMechE, ABTC

-- :::::;" 5 B. J. Beecher, BSc, CEng, MlMechE

- -::::~" 6 ffi J. J. Arnold, BSc, CEng, MIEE J. R. Capener, BSc, CEng, MIEE

Series Production

=;;s:_"::;es and ::-:-:·ration

P. M. Reynolds

H. E. Johnson

T. A. Dolling J. R. Jackson

Page 5: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

U.K.

U.S.A.

SEOUL

JAPAN

Pergamon Press pic., Headington Hill Hall, Oxford OX3 OBW, England

Pergamon Press, Inc., (395, Saw Mill River Road,) Elmsford, New York 10523, U.S.A.

Pergamon Press Korea, KPO Box 315, Seoul 110-603, Korea

Pergamon Press, 8th Floor, Matsuoka Central Building, 1-7-1 Nishi-Shinjuku, Shinjuku-ku, Tokyo 160, Japan

Copyright © 1991 British Electricity International Ltd All Rights Reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means: electronic, electrostatic, magnetic tape, mechanical, photocopying, recording or otherwise, without permission in writing from the copy­right holder.

First edition 1963

Second edition 1971

Third edition 1991

Library of Congress Cataloging in Publication Data Modern power station practice: incorporating modern power system practice/ British Electricity International.-3rd ed. p. em. Includes index. 1. Electric power-plants. I. British Electricity Inter­national. TK1191.M49 1990 62.31 '21 - dc20 90-43748

British Library Cataloguing in Publication Data

British Electricity International Modern power station practice.- 3rd. ed. 1. Electric power-plants. Design and construction I. Title II. Central Electricity Generating Board 621.3121.

ISBN 0-08-040510-X (12 Volume Set) ISBN 0-08-040513-4 (Volume C)

Printed in the Republic of Singapo;e by Singapore National Printers Ltd

Page 6: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

CoLOUR PLATEs

FOREWORD

PREFACE

CoNTENTs oF ALL VoLUMEs

Contents

Chapter 1 The steam turbine

Chapter 2 Turbine plant systems

Chapter 3 Feedwater heating systems

Chapter 4 Condensers, pumps and cooling water plant

Chapter 5 Hydraulic turbines

Chapter 6 The generator

INDEX

VI

Vll

ix

XI

1

124

241

323

422

446

563

Page 7: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

(

Foreword

G. A. W. Blackman, CBE, FEng Chairman, Central Electricity Generating Board

and Chairman, British Electricity International Ltd

FoR oVER THIRTY YEARS, since its formation in 1958, the Central Electricity Generating Board (CEGB) has been at the forefront of technological advances in the design, construction, operation, and maintenance of power plant and transmission systems. During this time capacity increased almost fivefold, involving the introduction of thermal and nuclear generating units of 500 MW and 660 MW, to supply one of the largest integrated power systems in the world. In fulfilling its statutory responsibility to ensure continuity of a safe and economic supply of electricity, the CEGB built up a powerful engineering and scientific capability, and accumulated a wealth of experience in the operation and maintenance of power plant and systems. With the privatisation of the CEGB this experience and capability is being carried forward by its four successor companies National Power, PowerGen, Nuclear Electric and National Grid.

At the heart of the CEGB's success has been an awareness of the need to sustain and improve the skills and knowledge of its engineering and technical staff. This was achieved through formal and on-job training, aided by a series of textbooks covering the theory and practice for the whole range of technology to be found on a modern power station. A second edition of the series, known as Modern Power Station Practice, was produced in the early 1970s, and it was sold throughout the world to provide electricity undertakings, engineers and students with an account of the CEGB's practices and hard-won experience. The edition had substantial worldwide sales and achieved recognition as the authoritative reference work on power generation.

A completely revised and enlarged (third) edition has now been produced which updates the relevant information in the earlier edition together with a comprehensive account of the solutions to the many engineering and environmental challenges encountered, and which puts on record the achievements of the CEGB during its lifetime as one of the world's leading public electricity utilities.

In producing this third edition, the opportunity has been taken to restructure the information in the original eight volumes to provide a more logical and detailed exposition of the technical content. The series has also been extended to include three new volumes on 'Sta~ion Commissioning', 'EHV Transmission' and 'System Operation'. Each of the eleven subject volumes had an Advisory Editor for the technical validation of the many contributions by individual authors, all of whom are recognised as authorities in their particular field of technology.

All subject volumes carry their own index and a twelfth volume provides a consolidated index for the series overall. Particular attention has been paid to the production of draft material, with text refined through a number of technical and language editorial stages and complemented by a large number of high quality illustrations. The result is a high standard of presentation designed to appeal to a wide international readership.

It is with much pleasure therefore that I introduce this new series, which has been attributed to British Electricity International on behalf of the CEGB and its successor companies. I have been closely associated with its production and have no doubt that it will be invaluable to engineers worldwide who are engaged in the design, construction, commissioning, operation and maintenance of modern power stations and systems.

March 1990 ~.

Page 8: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Preface

The increase in generating capacity of the Central Electricity Generating Board (CEGB) during the last thirty years has involved the introduction· of new 500 MW and 660 MW turbine-generator plant for a variety of operational duties from base load to that of flexible two-shift operation. These plants have been installed in nuclear, coal and oil fired. power stations.

The early operational experience of the 500 MW units provided important data for the design development of the 660 MW turbine-generator plant. These latter machines benefited from the high quality approach to the design of major components by UK manufacturers using their developed analysis techniques in the areas of aerodynamics and stress analysis. The soundness of this approach has been demonstrated by the improved reliability and performance of the later plants.

The Third Edition of Modern Power. Station Practice gives a detailed account of ex­perience obtain<:d in the development, design, manufacture, operation and testing of large turbine-generators in the last twenty years. The practice of testing and evaluation of modern plant has proceeded as before; the advance in analytical and computational techniques has however meant that the application of this experience to future design and operation of large turbine-generator plant is of greater benefit than ever before.

One of the major tasks of the Turbine-generator Plant Branch in the CEGB was to secure the development of Turbine-generators and their associated Plants to meet the needs of the CEGB with due regard to economics, performance and reliability. As Head of the Branch for some years I have felt privileged to have been asked to edit Volume C.

The authors of this volume have wide experience of the plant engineering field and all are authorities in their particular field of Technology. I would like to record my sincere thanks to these colleagues who have produced Volume C. They have undertaken the task with an enthusiasm derived from the knowledge that this work will' be of the greatest assistance to engineers in this field of technology worldwide.

P. HAMBLING

Advisory Editor - Volume C

-

Page 9: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

.... -------------------------------------------------------------- ~ ----

Contents of All Volumes

Volume A - Station Planning and Design Power station siting and site layout Station design and layout Civil engineering and building works

Volume B - Boilers and Ancillary Plant Furnace design, gas side characteristics and combustion equipment Boiler unit - thermal and pressure parts design Ancillary plant and fittings Dust extraction, draught systems and flue gas desulphurisation

Volume C - Turbines, Generators and Associated Plant

The steam turbine Turbine plant systems Feedwater heating systems Condensers, pumps and cooling water plant Hydraulic turbines The generator

Y olume D '"'-- Electrical Systems and Equipment Electrical system design Electrical system analysis Transformers Generator main connections Switchgear and control gear Cabling .\Iotors Telecommunications Emergency sqpply equipment .\1echanical plant electrical services Protection Synchronising

Y olume E - Chemistry and Metallurgy Chemistry Fuel and oil Corrosion: feed and boiler water \\- ater treatment plant and cooling water systems ?!ant cleaning and inspection \letallurgy i.:J.:roduction to metallurgy \1aterials behaviour :'\on-ferrous metals and alloys :'\on-metallic materials \ 1aterials selection

vi

Page 10: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Contents of All Volumes

Welding processes Non-destructive testing ' Defect analysis and life assessment Environmental effects

Volume F - Control and Instrumentation Introduction Automatic control Automation, protection and interlocks and manual controls Boiler and turbine instrumentation and actuators Electrical instruments and metering Central control rooms On-line computer systems Control and instrumentation system considerations

Volume G - Station Operation and Maintenance Introduction Power plant operation Performance and operation of generators The planning" and management of work Power plant maintenance Safety Plant performance and performance monitoring

Volume H - Station Commissioning Introduction Principles of commissioning Common equipment and station plant commissioning Boiler pre-steam to set commissioning Turbine-generator/feedheating systems pre-steam to set commissioning Unit commissioning and post-commissioning activities

Volume J - Nuclear Power Generation Nuclear physics and basic technology Nuclear power station design Nuclear power station operation Nuclear safety

Volume K- EHV Transmission Transmission planning and development Transmission network design Overhead line design Cable design Switching station design and equipment Transformer and reactor design Reactive compensation plant HVDC transmission plant design Insulation co-ordination and surge protection Interference Power system protection and automatic switching Telecommunications for power system management Transmission operation and maintenance

:c

---

Page 11: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

,....-------------------~- -~-

Volume L - System Oper,ation

System operation in England, and Wales Operational planning - demand and generation Operational planning - power system Operational procedures - philosophy, principles and outline contents

Control in real time System control structure, supporting services and staffing

Volume M - Index Complete contents of all volumes Cumulative index

Contents of All Volumes

-

Page 12: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

xiv

Evan John Davies Emeritus Professor of Electrical and Electronic Engineering at Aston University in Birmingham, died on 14 April 1991.

John was an engineer, an intellectual and a respected author in his own right. It was this rare combination of talents that he brought to Modern Power Station Practice as Consulting

Editor of seven volumes and, in so doing, bequeathed a legacy from which practising and future engineers will

continue to benefit for many years.

! 1

Page 13: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

1.

l

1

~!i ,.

CHAPTER 6

The generator

Introduction

1.1 Types of generator 1.2 Historical background 1.3 Stnndards and specifications

2 Synchronou:; generator theory

2.1 Electromagnetic induction

3

2.2 Speed, frequency and pole-pairs 2.3 Load, rating and power factor 2.4 MMF, flux an.d magnetic circuit 2.5 Rotating phasors 2.6 Phasor diagrams 2.6.1 Rated voltage, no stator current, open-circuit

conditions 2.6.2 Rated voltage, rated stator current and rated power

factor 2.7 Torque 2.8 Three-phase windings 2.9 Harmonics: distributed and chorded winding

Turbine-generator components: the rotor

3.1 Rotor body and shaft 3.2 Rotor winding 3.3 Rotor end rings 3.4 Wedges and dampers 3.5 Sliprings, brushgear and shaft earthing 3.6 Fans 3.7 Rotor threading and alignment 3.8 Vibration 3.9 Bearings and seals 3.10 Size and weight

4 Turbine-generator components: the stator

4.1 Stator core 4.2 Core frame 4.3 Stator winding 4.4 End winding support 4.5 Electrical connections and terminals 4.6 Stator winding cooling components 4.7 Hydrogen cooling components 4.8 Stator casing

5 Cooling systems

5.1 Hydrogen cooling 5.2 Hydrogen cooling system 5.3 Shaft seals and seal oil system 5.3.1 Thrust type seal 5.3.2 Journal type seal 5.3.3 Seal oil system 5.4 Stator winding water cooling system 5.5 Other cooling systems

6 Excitation

6.1 Exciters 6.1.1 Historical review 6.1.2 AC excitation systems 6.1.3 Exciter transient performance 6.1.4 The pilot exciter 6.1 .5 The main exciter 6.1.6 Exciter performance testing 6. 1. 7 Pilot exciter protection

446

6.1.8 Main exciter protection 6.2 Brushless excitation systems 6.2.1 System description 8. 2 2 The rotating armature rna in exciter 6.::.:> Telemetry systum 6.2.4 Instrument slipnngs 6.2.5 Rotating rectifier protection 6.3 Static rectifier excitation equipment 6.3.1 Introduction 6.3.2 General description of static diode rectifier equipment 6.3.3 Rectifier protection 6.3.4 Static thyristor rectifier schemes 6.4 The voltage regulator 6.4.1 Historical review 6.4.2 System description 6.4.3 The regulator 6.4.4 Auto follow-up circuit 6.4.5 Manual follow-up 6.4.6 Balance meter 6.4.7 AVR protection 6.4.8 Thyristor converter protection 6.4.9 Fuse failure detection unit 6.4.10 The digital AVR 6.5 Excitation control 6.5.1 Rotor current limiter 6.5.2 MVAr limiter 6.5.3 Overfluxing limit 6.5.4 Speed reference controller 6.6 The power system stabiliser 6.6.1 Basic concepts , 6.6.2 Characteristics of GEP 6.6.3 System modes of oscrllation 6.6.4 Principles of PSS operation 6.6.5 The choice of stabiliser signal 6. 7 Excitation system analysis 6. 7.1 Frequency response analysis 6. 7.2 State variable analysis 6.7.3 Large signal performance investigations

7 Generator operation

7.1 Running-up to speed 7.2 Open-circuit conditions and synchronising 7.3 The application of load 7.4 Steady state stability 7. 5 Capability chart 7.6 Steady short-circuit conditions, short-circuit ratio 7.7 Synchronous compensation 7.8 Losses efficiency and temperature 7.9 Electrically unbalanced conditions 7.10 Transient conditions 7.11 Neutral earthing 7.12 Shutting down

8 Mechanical considerations

8.1 Rotor torque 8.2 Stress due to centrifugal force 8.3 Alternating stresses, fretting and fatigue 8.4 'Slip-stick' of rotor windings 8 ,, r·Joise

9 Electrical and electromagnetic aspects

9.1 Flux distribution on load

Page 14: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

9.2 Control and calculation of reactances 9.3 The cause and eff~ct of harmonics 9.4 Magnetic pull 9.5 Shaft voltage and residual magnetism 9.6 Field suppression 9.7 Voltage in the rotor winding 9.8 Stator winding insulation

1 0 Operational measurement, control, monitoring and protection

10.1 Routine instrumentation 10.1.1 Temperature 10.1.2 Pressure 10.1.3 Flow 1 0.1.4 Condition monitoring 10.1.5 Electrical 10.1.6 Vibration 10.2 Logging and display 10.3 Control 10.4 On-load monitoring, detection and diagnosis 10.4. 1 Air gap flux coil 10.4.2 Core or condition monitor 10.4.3 Insulation discharge 10.4.4 Rotor winding earth fault indication 10.4.5 Shaft current insulation integrity 10.4.6 Stator winding water analysis

1 Introduction

1.1 Types of generator The CEGB transmission systertl operates at a fre­quency of 50 Hz: so do all the: generators connected synchronously to iL The larger _generators ate almost all directly driven by steam turbines rotating at 3000 r/min; a few operate at 1500 r/min.

These high speed generators are commonly known as turbine-generators, or cylindrical rotor generators; in this chapter, such machines are implied unless otherwise stated.

The CEGB has for many years standardised on generating units of 500 and 660 MW electrical output_ At these ratings, there have been six different designs of generator, each design incorporating minor changes as time progressed. However, they are all sufficiently similar for a generalised description to be applicable. Where a design departs radically from that being de­scribed, this will be noted (see Fig 6.1).

The bulk of this chapter deals with generators of this size; the theory applies to all synchronous gen­erators. Brief descriptions of other types of generator in use on the CEGB system will be found at the end of this chapter.

1.2 Historical background fhe advantages of AC over DC as a means of elec­tricity distribution were established towards the end

Introduction

10.5 Protection 10.5.1 Class 1 trips 10.5.2 Class 2 trips

11 Maintenance, testing and diagnosis

11 .1 Maintenance and tests during operation 11.2 Maintenance and tests when shut down for a short

outage 11 .3 Maintenance during a longer outage 11 .4 Maintenance and tests with the machine dismantled 11.5 Reassembly 11.6 Diagnosis

12 Future developments

12.1 Extension of present designs 12.2 Extension of water cooling 12.3 Slotless generators 12.4 Superconducting generators 12.5 <\uxiliary systems

13 Other types of generator

13. I i urbine-tyre 0er1etatorc· .. ,f :,>wer rating 13.2 Water turbine d'riven salient pcie synchronous generators 13.2.1 Excitation and control 13.2.2 Other features 13.3 Diesel engine driven salient-pole generators 13.4 Induction generators

of the 19th century, and the rapid growth of AC systems led to a demand for AC generators. At first, these were slow speed machines driven by recipro­cating engines but, by 1900, generators driven directly by high speed steam turbines were being introduced .in what are recognisably the forerunners of modern :machines, the benefits being principally in the prime :mover.

The early, turbine-gel).erators were made both in vertical and horizontal shaft configurations. The ver­tical shaft design required a large thrust bearing, and was quickly abandoned. The development of hori­zontal shaft machines was rapid; unit outputs had risen from a few hundred kW to 20 MW by 1912 (see Fig 6.2).

The rate of increase in output slowed subsequently, but unit outputs had risen to 50 MW by the 1930s. The 60 Hz frequency standardised in the USA re­quired the speed of American two-pole generators to be 3600 r /min, and the losses caused by air friction at this speed made the much-less-dense gas hydrogen attractive as a cooling medium. In the UK, hydrogen cooling was used on 3000 r /min units of 50 MW and above from about 1950.

Later, the search for increasingly effective means of heat (loss) removal led first to the use of hydrogen at higher pressure, then insulating oil, and finally, pioneered in the UK, water in direct contact with the winding conductors. By these means, generators with the increasing outputs demanded were able to be manufactured, transported and installed in a power station as single units, which was both economically and operationally attractive (see Fig 6.3).

447

Page 15: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

..,. ..,. CXl

STATOR WINDING STATOR ENDWINDING 'N'TER INLET MANIFOLD SUPPORT BRACKET RETAINING RING

GENERATOR-lURE,:,;.: HALF COUPLIN .•

~TOR WINDING I I ATER OU.TLET CORE ENDPLATE_ 1 .COR. E BAR

E HOSES~ MANIFO\~ I / d-·OliGJJ i

~-~-~

r 1 ~~; --~!!!IIUII_Ik ~~'

FLANGE CONNECTIONS . -~ -- --- •. ~----- -~~~-, . - GAS SEAL

TO CONDENSATE SYSTEM ' . __ / •

FLANGE CONNECTIONS TO STATOR WINDING WATER SYSTEM

STATOR INNER FRAME

Ftc;_ 6.1 Sectional view of a 660 !'v!W generator

~CURRENT TRANSFORMERS

STATOR CAGED CORE

(·.···-] ~ ~--- _j

J_______, ·'-~

TERMINAL BUSHINGS NEUTRAL

STATOR END CONNECTORS

STATOR ENDWINDING

TERMINAL BUSHING MAIN

--1 ::r <D

<0 <D ::l <D iil .... 0 ...,

n ::r w

"0

~ (J)

Page 16: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Introduction

FIG. 6.2 20 MW air cooled generator

Both the pace of development and the rate of increase in unit output has slowed markedly in re­cent years, as greater emphasis has been placed on the reliability achieved by proven designs, and on the advantages of interchangeability of major plant components.

1.3 Standards and specifications The British Standard covering generators is BS5000, which refers to many parts of BS4999. The corre­sponding international standard is IEC 34. Standards specific for turbine-generators are BS5000 Part 2 and IEC 34 Part 3. These standards specify acceptable characteristics, values of temperature, vibration, noise, phase unbalance, harmonic content, excitation control limits and tolerances, and test conditions, e.g., high voltage test levels.

Other parameters, such as hydraulic pressure and dielectric loss test values, are specified in various CEGB Standards.

Specific requirements for a new generator are con­tained within its own specification, which covers items peculiar to its location or duty, for example, tem­perature of cooling water, power factor and reactances. Where necessary, these requirements may differ from those in the appropriate Standard. The expected op­erational life is quoted in the specification; this is currently 200 000 hours, with 104 start/stop cycles. These values are used in design calculations, e.g., crack growth rate by fatigue.

The following Standards are relevant:

IEC 34-1: Rotating electrical machines - rating and performance.

IEC 34-2: Rotating electrical machines - methods for determining losses and efficiency from tests.

449

Page 17: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

2.5

2.0

WEIGHT/RATING kg/kVA

1.5

1.0

1930 1940 1950

Chapter 6

YEAR

1960 1970 1 980 1990

IN SERVICE

M w M SUPERCONDUCTING

DIRECT GAS OR LIQUID COOLING OF STATOR AND DIRECT ROTOR COOLING

0.5 , LIQUID COOLING OF STATOR AND ROTOR ~

SUPERCONDUCTING ~-ROTOR ~

10 20 50 100 200 500 1000 2000 5000

MVA RATING

FIG. 6.3 Development of generator size, weight and cooling arrangements

IEC 34-3: Ratings and characteristics of 3-phase 50 Hz turbine type machines.

IEC 34-4: Methods for determining synchronous machine quan­

tities from tests.

IEC 34-6: Methods of cooling rotating machinery.

BS4999: General requirements for rotating electrical machines.

BS4999 Part 106: Classification of methods of cooling.

BS4999 Part 101: Specification for rating and performance.

BS4999 Part 142: Mechanical performance - vibration.

BS4999 Part 109: Noise levels.

BS5000: Specification for rotating electrical machines of particular types or for particular applications.

BS5000 Part 2: Turbine type machines.

BS27 57: Classification of insulating materials for electrical machinery.

BS5500: Specification for unfired fusion welded pressure vessels.

BS601: Steel sheets for magnetic circuits of power electrical apparatus.

BS1433: Copper for electrical purposes: rod and bar.

BS3906: Electrolytic CO!'(lpressed hydrogen.

ES1 Standard 44-7: Testing the insulation system of bars.

450

2 Synchronous generator theory Some basic principles of theory and design are es­tablished in this section in order that the descriptive matter in later sections may be more easily understood.

2.1 Electromagnetic induction In a synchronous generator with the rotor running at constant speed, the instantaneous voltage induced in a stator conductor is proportional to the magnetic flux density experienced by the conductor.

where e

dB

cit

f

k

dB e k- £

dt

instantaneous voltage induced along the length of the conductor, V

rate of change of magnetic flux density, tesla/s

length of conductor exposed to the flux, m

constant

In order to operate synchronously with the inter­connected AC transmis'i'):l system, the generated voltage is required to vary sinusoidally. The magnetic

Page 18: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

flux density experienced by the stator conductors must therefore also vary sinusoidally. This is achieved by arranging, on the rotor, excitation coils which produce a flux whose density varies approximately sinusoidally around the circumference.

As the rotor rotates inside the stator bore, a con­ductor fixed in the stator will be subjected to an approximately sinusoidally varying magnetic flux den­sity, and will have an approximately sinusoidal voltage generated along its length (Fig 6.4). The magnitude of the flux density, which determines the magnitude of the generated voltage, can be changed by varying the direct current supplied to the excitation coils on the rotor.

2.2 Speed, frequency and pole-pairs The relationship between speed, number of pole­pairs and the frequency of the generated voltage is:

f = pn

where f frequency, Hz

n rotational speed, r/s

p number of pole-pairs

Cylindrical rotor 50 Hz generators have two poles and operate at 3000 r/min, or less commonly four

CONDUCTOR IN STATOR

Synchronous generator theory

poles operating at 1500 r/min. Salient-pole generators usually have more than four poles, for example, the Dinorwig hydraulic turbine-generators have 12 poles and operate at 500 r/min. Generators producing other frequencies are used for special purposes; those whose output is rectified for use as an excitation supply commonly operate at 150 Hz or 400 Hz.

2.3 Load, rating and power factor Root-mean-square (RMS) values of alternating volt­ages and currents are implied in this chapter, unless specifically noted otherwise.

A single AC generator supplying a load has its voltage/ current relationship dictated by the nature of that load. For any load which is not purely resistive, the sinusoidal voltage and current will not be m phase.

The rated output of a single-phase generator is the product of its rated voltage and its rated current, expressed in volt-amps, kVA or MVA. The rated power is the rated output times the rated power factor, expressed in watts, kW or MW.

The rated power of a three-phase generator is three times rated phase voltage times rated phase current times power factor. Virtually all CEGB generators have their three phases connected in star, so that:

line voltage and line current

-J3 x phase voltage phase current.

. 0~----------------------~----------------------r-

MAGNETIC FLUX PRODUCED BY

ROTOR WINDINGS

-V

FIG. 6.4 Production of sinusoidal voltage

451

Page 19: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

The MV A rating is then:

.J3 x rarectiine-~x rated line current x 10- 6

The MW rating i\ then: rated MW A X rated power

factoc. \

I The present CEGB 'ating for large turbine-generators is:

660 MW, 0.85 pc\wer factor lagging, 23 500 V, 3-phase, 50 Hz I

The MV A rating islherefore 660/0.85 and the rated line c rrent is:

776 MVA

776 X 106

/3x1~ 19 076 A

The output is specified as a maximum continuous rating (MCR), which implies no guaranteed sustained overload capacity. The standards specify very short term overcurrent capability, and acceptable variations in voltage and frequency. Some sustained overload capability may be possible by operating at a hydrogen pressure greater than the rated value, by agreement.

Although operation at 0.85 power factor (lagging) is specified, generators on the CEGB network gen­erally operate at power factors of 0.9 or higher, and this allows operation at higher than rated MW if this is available from the turbine, up to the limit of rated MVA (see Fig 6.5).

2.4 MMF, flux and magnetic circuit Direct current circulating in coils wound into the rotor poles, causes them to act as electromagnets,

452

OPERATION ABOVE RATED MW PERMISSIBLE IN THESE AREAS

MW

LEADING LAGGING

MVAR

NOMINAL RATED MW

MCR POINT

0.85 POWER FACTOR LAGGING

F!G. 6.5 Operation at high MW and power factor

Chapter 6

which provide a source of magneto-motive force (MMF); the 'driving force' behind the magnetic flux . The value of MMF depends on the maximum flux density required at the stator conductors to produce the required voltage and on the reluctance of the magnetic circuit. The magnetic circuit consists of paths of low reluctance in the iron of the rotor and stator, with an air gap of high reluctance between them. The air gap reluctance is effectively constant, but that of the iron paths increases at high values of magnetic flux density, when the iron becomes magnetically saturated.

2.5 Rotating phasors A sinusoidally-varying voltage has an instantaneous value v at time t expressed by:

where V

f

v = V sin (27rf)t

maximum value of v

frequency in Hz

The same relationship can be derived by rotating a phasor of constant magnitude V at a constant speed (Fig 6.6). At time t, when the phasor is at an angle e to the horizontal axis, v = v sin e, i.e.' the pro­jection of V on to the vertical axis.

In a synchronous machine, all the sinusoidally­varying quantities (voltage, current, etc.) can be re­presented by phasors rotating together at synchronous speed. The rotating phasor diagram can be thought of as a snapshot of a set of phasors which all rotate together while maintaining the relationships to each other.

In a three-phase machine, with balanced electrical output, conditions in one phase are repeated exactly in the other two, with time delays of 11(3f) and 2/ (3f). For clarity, one phase is chosen, and its phasors are taken as representative of the phase quantities for all the other phases in a diagram of rotating phasors.

2.6 Phasor diagrams

2.6.1 Rated voltage, no stator current, open­circuit conditions Let a phase voltage be represented by the phasor V (Fig 6. 7). Since it is the rate of change of flux density which produces V, the phasor for flux den­sity, B, is drawn 90° out-of-phase with V. The MMF, F, producing this flux density is in phase with B.

Page 20: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

I

I

I

I

I

I ------.. -----... i

PHASEC

\ \ \ \ \ \ \PHASE B

\ \

INSTANTANEOUS VOLTAGE

v

v

0.005

I I

I I

I /

FIG. 6.6 Rotating phasors

Vbf

Synchronous generator theory

v = Vsin (21rf) t = Vsin 9

I

.... -,. /''

/ PHASE B

0.015

8,------------------------------+--------~~~ b = Bsm (100n) t

v = Vs1n (100nj t

v

0

FIG. 6.7 Phasors for open-circuit conditions

453

Page 21: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

2.6.2 Rated voltage, rated stator current and rated power factor ' If the power factor is 'expressed as cos ¢, ¢ is the angle between the voltage and current phasors, as shown in Fig 6.8 for a lagging power factor.

Current circulating in the stator winding results in voltage drops: IR due to the winding resistance R, in phase with I, and IXe due to the winding 'leakage reactance', Xe, lagging I by 90°. R is negligibly small, and the resistive voltage drop is neglected henceforth.

An 'internal' voltage E must be generated in the winding such that after subtracting (phasorially) the leakage-reactance drop, the rated voltage V is pro­duced at the terminals.

In order to generate E, flux density Be and MMF Fe are required, such that the voltage, flux and MMF phasor triangles are all similar. The physical meaning of this is discussed later.

Current in the three-phase stator winding produces its own MMF, Fd, which acts in the same direction as Fxe· An MMF, F, must be provided, such that, when the Fd component is subtracted vectorially, the resultant is Fe. This is achieved by increasing the rotor winding current and by the rotor moving ahead of its open-circuit alignment, by the 'load angle', o, as shown.

This demagnetising effect of the stator winding current is known as armature reaction, and can be seen from the diagram to be similar in effect (though much larger in magnitude) to that of the leakage

Be

Chapter 6

reactance. The term synchronous reactance (Xd + Xe) is used to express this effect, the IXd drop being added to the IXe drop in the diagrams.

As the lagging power factor of the load worsens, i.e., cos¢ is smaller and¢ larger, the required MMF, F, increases, i.e., more current is required in the rotor winding (Fig 6.9 (a}}. Conversely, if the lagging power factor increases or goes beyond unity into the leading regime, the rotor current must be reduced (Fig 6.9 (b)).

2.7 Torque The mechanical torque provided by the prime mover is balanced by an electromagnetic torque caused by the interaction of the magnetic flux and the current flowing in the stator windings.

IXd

The rotor shaft must be designed to transmit rated torque, and the stator must be able to withstand a similar torque reaction. In practice, the design must cope with the very much higher torques produced during certain fault conditions.

2.8 Three-phase windings The voltages and currents produced in each phase must be identical, apart from their phase displace-

Fd

MMF PH~.SORS ROTATED BACK THROUGH 90 TO SHOW

SIMILARITY OF TRIANGLE TO VOLTAGE PHASORS

FIG. 6.8 Phasor diagram for load conditions

454

Page 22: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

PROPORTIONAL TO F

IXd

Ia) Lagg1ng current: Exc1tat10n current on load lS proportional to F

PROPORTIONAL TOF

Synchronous generator theory

(b) Leading curr,ent Rotor angle h larqer load excttatron current smaller

IXd

v

FIG. 6.9 Phasor diagrams for lagging and leading loads

ments, in order to avoid the damaging effects of · unbalance.

In this and the next section, a complete two-pole generator is considered, for simplicity. In a machine with 2n poles, a two-pole segment is exactly repeated n times, and can be considered as electromagnetically equivalent to a two-pole machine.

An economic design of stator winding has many conductors connected in series, so the individual con­ductor voltages are additive. Each 'go' conductor is connected to a 'return' conductor, acted on by the pole of opposite polarity, and thence to a third con­ductor adjacent to the first, and so on through the phase. The 'return' conductors are disposed in a layer displaced radially from the 'go' conductor, both in the slots and in the end region.

The usual and most economic arrangement is for the winding ·of one phase to occupy one-sixth of the circumference, with a parallel section of the same phase occupying the position diametrical~y opposite (see Fig 6.10).

2.9 Harmonics: distributed and chorded winding A cylindrical rotor generator has a circular rotor

profile which cannot be shaped to produce a sin­usoidal flux density variation (as can, approximately, a salient pole on a multi-polar slow speed generator). The flux density variation in a turbine-generator is of a stepped rectangular form (Fig 6.11), which con­tains a fundamental with odd harmonics of significant amplitude. The voltage induced in a single stator con­ductor would contain similar unacceptable harmonic components.

In a series-connected winding occupying several adjacent slots in the stator, the voltage induced in one conductor will be displaced from that induced in its neighbour by the electrical angle subtended by the two slots, a in Fig 6.12. The sum of n such voltages is V + 2Vcos a + 2Vcos 2a + ... + 2Vcos (n - 1 )a if n is odd, or, 2Vcos a/2 + 2Vcos 3a/2 + ... 2V cos (2n - 1 )a, if n is even. The ratio of this to n V is the distribution factor Kd ( < 1).

The effect of distribution on the third harmonic voltage is to triple the effective angle, so that the s.ummated voltage is:

V 3 + 2V 3 cos 3a + 2V 3 cos 6a + etc.

and the resultant third harmonic voltage is very much reduced. A similar argument applies even more effec­tively to harmonics of higher order.

455

Page 23: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

STATOR CONDUCTORS NEAREST TO BORE

/ PHASE C

"SPACES FOR PARALLELED

PHASE A WINDING

CONNECTION OF PHASES

FIG. 6.10 Arrangement of stator conductors

P~.ASE 8 WINDING

SPACE

A somewhat similar effect is produced by the common practice of chording, or short-pitching. Here the return conductor is at an angle less than I80° from its connected conductors. If {3 is the angle by which this falls short of I80° (Fig 6.I3):

the ratio (I - cos{3)12 is the pitch factor, KP (<I)

Hence, in the usual distributed short-pitched winding, the generated voltage is n VKctKp, the harmonic con­tent is acceptably small, and the stepped rectangular flux density wave generates a substantially sinusoidal voltage of fundamental frequency.

456

Chapter 6

3 Turbine-generator components: the rotor The rotor must carry the excitation winding, provide a low reluctance path for the magnetic flux, and transfer the rated torque from the turbine to the electromagnetic reaction at the air gap. Steel is the only material which meets these requirements economically. A single steel forging is used, from which the central cylindrical body and its supporting shafts are machined.

3.1 Rotor body and shaft -The high rotational speed produces large centrifugal forces in the rotor body, and a high-strength steel is necessary. Typical alloying constituents are:

2.50Jo nickel 0.250Jo carbon

I.2 OJo chrome 0.2 OJo silicon

0. 60Jo manganese 0.1 OJo vanadium

0.50Jo molybdenum

The steel is vacuum-degassed, which minimises the possibility of hydrogen-initiated cracking, and the forging is hardened by reheating and quenching under closely controlled conditions. Rough machining is followed by a stress-relieving heat treatment.

Mechanical properties as high as 800 MN/m2 at 0.20Jo proof stress, with 940 MN/m2 ultimate tensile strength, are obtained in forgings for the largest ratings. A reduction in area of 400Jo, elongation 15 OJo, Charpy V-notch impact level of 40 Joules, and a fracture-appearance transition temperature of 20°C, are typical of this material, though specified pro­perties are allowed to differ at different parts of the forging and in different test piece orientations. Stresses in a rotor at 3000 r/min limit the practicable diameter to about 1150 mm.

The rotor is examined ultrasonically from the sur­face at various stages, and any significant defects are reported. These are most likely to occur near the cylindrical axis, and may be cleared by machining a central axial hole, not usually larger than 100 mm diameter, through all or part of the rotor. The critical defect size is established from considerations of crack growth by fatigue, recognising that there will be- a small, but significant, once-per-revolution alternating bending stress superimposed on the steady stress.

Magnetic permeability tests are carried out at flux ·densities up to 2.2 tesla, i.e., well into magnetic saturation.

The rough-turned forging is further turned by the generator manufacturer. The winding slots are then cut, using accurately indexed milling cutters working at a controlled cut rate to minimise residual surface stresses (see Fig 6.I4).

Page 24: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

l

'

I " ·'

FUNDAMENTAL

DEVELOPED VIEW SHOWING STEPPED MMF WAVE AND FUNDAMENTAL SINE WAVE

Turbine-generator components: the rotor

MMF DUE TO COIL

FIG. 6.11 The stepped magneto motive force wave

The shape and size of the winding slots are deter­mined by an optmisation process, taking into account the following factors, and considering a radial cir­cumferential section:

• The more ampere-turns the rotor can carry, the smaller the generator. Together with the need for

keeping a low current density to minimise the loss and temperature, as much of the area as possible must be allocated to the winding copper.

• The winding insulation must be mechanically strong to withstand centrifugal and bending stresses, and stable to withstand load cycling. Adequate electrical

457

Page 25: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

·~·-·

l ··~· 4.'. "-I~ i

The generator

SLOT n

SLOT:

Chapter 6

v

THE EFFECT ON THE FUNDAMENTAL VOLTAGES

THE EFFECT ON THE THIRD HARMONIC VOLTAGES

FIG. 6.12 The effect of distributing the stator winding over several slots

tracking distances from the winding to the rotor body must be provided, since the winding is in direct contact with the ventilating gas, and dirt and oil may collect on insulation surfaces. The insulation must therefore be more substantial than the operating voltage of about 600 V would require in other applications.

• Passages for an appropriate flow of cooling gas must be· provided in the winding copper section, and also in the steel body section in some designs, to ensure that the specified temperature rise is not exceeded.

• The magnetic flux in the rotor is unidirectional and normally substantially constant, so there is no loss due to magnetic hysteresis or eddy currents, but there must be an adequate magnetic section particularly in the area of the winding slots. A high degree of saturation in the teeth would result in unacceptably high excitation requirements and losses.

458

• The whole centrifugal force of the slot contents, the retaining wedge and the tooth is resisted by the narrowest section of the tooth, normally the tooth root. There must be an adequate safety margin between the maximum tooth stress at overspeed and the proof stress of the steel.

The optimisation of these conflicting requirements has led, in the latest designs, to a departure from parallel-sided slots to slots of trapezoidal section (Fig 6.15).

The winding slots are cut in diametrically opposite pairs, equally pitched over about two-thirds of the periphery, leaving the pole faces without winding slots. The resulting difference in stiffness in the two per­pendicular axes would produce a twice-per-revolution vibration; this is avoided by cutting equalising slots in the pole faces (Fig 6.16). These are either similar to the winding slots and are subsequently filled with short steel blocks to restore the magnetic properties, or slits cut with a large diameter cutter in the radial

Page 26: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

/

/ /

-~ /

Turbine-generator components: the rotor

Jrl

vs

EFFECT ON FUNDAMENTAL VOLTAGE

EFFECT ON THIRD HARMONIC

VOLTAGE

EFFECT ON FIFTH HARMONIC

VOLTAGE

FIG. 6. I 3 The effect of shurt-pi1ching the stator winding

circumferential plane, at intervals axially along the pole faces.

During a three-phase sudden short-circut at the generator terminals, torque peaks of four to five times full-load torque are experienced between the LP turbine and generator shafts. The generator rotor shaft and coupling at the turbine end must be designed to withstand this peak torque with an adequate safety margin. The coupling is usually shrunk on and keyed or dowelled, and has oil-injection grooves for removal. A proportion of the coupling bolts are fitted, the others have a clearance to the coupling holes.

Journal and journal-type shaft seal surfaces are ground and polished to a high degree of circularity. Overall, good surface finishes and absence of sharp blemishes are called for. Radii are made as large as practicable to minimise stress concentrations.

3.2 Rotor winding Winding coils are assembled into pairs of rotor slots symmetrically disposed about the pole axis, but in opposite senses in the two poles, i.e., clockwise cur­rent flow for the 'north' pole and counterclockwise for the 'south' pole.

Because the rotor winding slots are cut radially, it is not possible to fit a preformed coil into the slots since the span of a coil is smaller the lower down the slot it is, and considerable distortion would be required to get the coils in. Each turn is therefore assembled separately, either as half-turns or in more pieces, with joints either at the centres of the end­turns or at the corners, being brazed together after each turn is assembled, to form a series-connected coil. Hard, high conductivity copper, with a small silver content to improve its creep properties, is used for the coils. Depending on the method of ventilation, rectangular sections with grooves and/ or slots, or tubular rectangular sections are used. When a trape­zoidal slot is used, the sections may be of several different sizes. One or two turns in the width -of the slot are normally used. Radially-aligned slots provide gas exit passages (see Fig 6.17).

The coils are not individually wrapped with insula­tion. Instead, slot liners of moulded glassfibre, or a composite of glassfibre and a more flexible insulating material, insulate the coils from the sides and bottoms of the slots, and a block of insulation separates the top turn from the wedge. Between each turn, thin separators of glassfibre or similar material, serve to insulate against the 10 V or so between adjacent turns

459

Page 27: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

FIG. 6.14 Cutting winding ;lots in a rotor

(Fig 6.18). Thick layers of insulation material on the inside surfaces of the end ring and end disc insulate them from the end windings. The spaces between turns in the end windings are partially filled with insulating blocks, which ensure that the coils do not distort, and which contain holes and passages for the transfer of ventilating gas·.

Because direct current circulates in the winding, there are no eddy current or other frequency related losses in the rotor winding. The resistance (I 2R) loss, amounting to 2 MW at rated load, together with the rotational (windage) loss, must be dissipated, and the average winding temperature must not be allowed to exceed ll5°C. A cooling system is used, in which hydrogen is in direct contact with the copper con­ductors, for optimum heat transfer. The high ro­tational speed produces a pressure head through the rotor slots which causes hydrogen to flow from both ends, under the end windings and axially through sub­slots in the rotor and channels in the coils, whence it emerges radially through the wedges into the airgap.

460

Fans mounted on the rotor, primarily to circulate hydrogen through the stator, assist the natural flow through the rotor (see Fig 6.19).

The ends of the winding are connected to flexible leads, made from many thin copper strips, which run radially inwards onto the shaft at the exciter end. These leads are housed in two shallow slots in the shaft and are retained by wedges. At a point axially beyond the end windings, the leads connect with radial copper studs and thence to D-shaped copper bars housed in the shaft bore. Seals against hydrogen leakage are provided on the radial studs. From the D-leads, connections are taken either to sliprings

. or to the shaft-mounted exciter connections in a brushless machine (see Fig 6.17).

3.3 Rotor end rings Thick end rings are used to restrain the rotor end windings from flying out under the action of centri-

Page 28: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Turbine-generator components: the rotor

HIGH \ _ __....=~ MECHANICAL STRESS

MAGNETIC FLUX

FIG. 6.15 Optimisation of a rotor section

fugal force. For electromagnetic reasons, these rings have traditionally been made from non-magnetic steel, typically .a 1807o Mn, 4% Cr austenitic steel. A 0.2% proof stress of 1000 MN/m2 is available to cope with the high operating stresses. A ring is machined from a single forging, and is attached to the end of the rotor body with a shrink fit designed to provide a small residual interference at 20% overspeed. The material has proved to be liable to stress-corrosion cracking at the stresses involved, and all the surfaces ex­cept the shrink fit are given a protective finish to ensure that hydrogen, water vapour, etc., does not have access to the surfaces. Even so, it is recom­mended that rings are removed occasionally for de­tailed surface crack detection using a fluorescent dye. Ultrasonic scanning is not entirely satisfactory,

because of the coarse grain structure, particularly where the shape is complex.

An austenitic steel, containing 18% Mn 18% Cr, has recently been developed which has shown virtual im­munity to stress-corrosion cracking in exhaustive tests, while maintaining other properties at least as good as the older material. This alloy is being used in new machines and for replacement rings, eliminating the need for pe;iodic inspection.

The end ring is prevented from moving axially either by means of lugs mating with similar lugs on the rotor body, or by small spring-loaded plungers locating into grooves (see Fig 6.20). In both these designs, the ring must be rotated through a small angle, when fully home axially, in order to lock. In a different design, a screwed ring is used to pull the

461

Page 29: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

462

ROTOR BLOWER

TURBINE HALF COUPLING

INERTIA SLITS

WINDING SLOTS AND WEDGES

FIG. 6.16 Stiffness compensation

END BELL

Chapter 6

SLIPRING TERMINAL STUD

Page 30: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

-l'> Q') w

POLE SLOT END WEDGE

POLE FACE DAMPING WINDING

POLE FACE

ROTOR BODY_-~~~~-

\-=::_-c-~ _:__~-'--=:_1'':' .. -~'\----= ___ .,_ _, """ ~- . _ /-, = I I ;,---.,~ -7=---:----- ~~: r:::t~~fjy r>~~~ .;; .,) .;------

_)

-' J

" ~ ~ 1 "' '

Ill Ill

) ') ,

....... ~ ....... -...,._......;......~~ 'l) •::-_:,

~I') .,~"

'l

"l

.. ·;?~~ -.:.:._. ---::;:_

WINDING VENTILATION HOLES

BALANCING PLUG HOLES

DAMPING BARANDTAG

~ COOLING GAS FLOW

WEIGHT

FIG. 6.17 Rotor winding

END WINDING SUPPORT BLOCK

-,

RADIAL AXIAL LEAD CONNECTION

INSULATING TUBE

CONNECTING RING

RADIAL CONNECTION BOLT

EXCQTER It END

L

INSULATING SEPARATOR

--; c ""' Q: :::l Cll

I

co Cll :::l Cll

Ol ..... 0

(')

0 3

"0 0 :::l Cll :::l ..... (/)

..... :r Cll

""' 0 ..... 0 ""'

Page 31: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

~--------------------------------------------·--

The generator

FIG. 6.18 Rotor slot

EPOXIDE GLASS STR\PS

EPOXIDE GLASS CAPPING

DOUBLE STRAP COPPER COIL TURNS

NYLON PAPER INSULATION STRIPS

BETWEEN TURNS

EPOXIDE GLASS SLOT LINER

ring through its final few millimetres, and this also locks it circumferentially.

The ring must be heated to about 300°C to expand it sufficiently for the shrink surface to pass over its mating area on the rotor. The heat is applied by a special cylindrical electrical heater. If a gas heater is used, the ring surface is protected from the direct flame by a thin metal cover.

The inner diameter of the ring is machined with

464

Chapter 6

a small taper to facilitate assembly and removal. It is insulated from the end winding with either a moulded-in glass-based liner or a loose cylindrical sleeve.

The outboard end of an end ring is partially closed by a shrunk-on annular steel disc which encloses the end wnding. Clearance between the end winding and the shaft allows hydrogen to pass into entry ports in the winding copper. No contact between the out­board end of the ring and the shaft is permissible, since the shaft flexure could promote fatigue and fretting damage at the interfaces. The end disc com­monly contains facilities for adjusting the mechanical balance of the rotor.

3.4. Wedges and dampers The winding slot contents are retained by a wedge, which must be designed to withstand the crushing stress on its lands and the bending stress across its width, bearing in mind that it contains holes or slots through which hydrogen passes. It must also be non­magnetic in order to minimise flux leakage around the rotor circumference, and to ensure a reasonable reac­tance value.

Extruded aluminium section is generally used, ma­chined in the regions of high stress. If short axial lengths are used, the potentiality for localised crack initiation in the rotor teeth exists. One continuous wedge per slot is therefore commonly used, although these are more difficult to fit.

During conditions of rapidly changing flux, for ex­ample, during system faults, or when an alternat­ing flux links the rotor 'during unbalanced electrical loading, when negative phase sequence currents and fluxes occur, current is induced in the surface of the rotor. Because the 'skin depth' of the magnetic rotor steel is about 1 mm whereas that of the non­magnetic wedges is an order of magnitude greater, current flows preferentially in the wedges, which form a 'damper winding' analogous to the rotor cage of an induction motor. The wedges are of suffi­cient cross-sectional area to carry the current cor­responding to the expected unbalanced load, without damage due to overheating, but the areas of current transfer into the end rings (which act as the short­circuiting rings) have to be carefully designed. Thin cop­per sheets with 'tongues' fitting under the ends of the wedges form an interleaved ring under the inboard end of the end ring, and assist in the avoid­ance of localised areas of preferential current transfer and hot spots.

In pole faces having axial compensating slots, a similar arrangement is provided. In those with cross­pole slits, a few very shallow axial slots are cut to accommodate copper damper strips, which are re­tained by wedges, to transfer the surface current across

Page 32: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

,, ,'

SEAL FACE LANDING

STOP KEY

OUTBOARD END

ROTOR SHAFT

VANE

Turbine-generator components: the rotor

BACK PLATE

INBOARD END

KEY

VENTILATION SLOT

BALANCE WEIGHT

FIG. 6.19 Rotor fan

the slits, and prevent hot spots at the ends of the slits.

3.5 Sliprings, brushgear and shaft earthing Connections are taken from the D-leads in the bore, through radial copper connectors (which may have back-up hydrogen seals) and flexible connections, onto the sliprings (Fig 6.21). For a 660 MW generator, the rated excitation current is about 5000 A, and sliprings must have a large surface area and run cool in order to transfer this current satisfactorily. One design uses two sliprings of the same polarity in parallel. The ring surface is grooved and drilled to im­prove its surface cooling.

The brushgear shown in Fig 6.22 is arranged with

several brushes and holders on one of several re­movable brackets, each of which can be withdrawn for brush replacement while running on-load, if spe­cial precautions are observed (see Fig 6.22 inset). Brush pressure is maintained by constant pressure springs. A brush life of at least six months should be obtained.

The brushgear is housed in a separate compart-ment of the excitation housing, separately ventilated by a shaft-mounted fan so that brush dust is not distri­buted into other excitation components. Small leakages of hydrogen past the connection seals which might accumulate in the brushgear compartments during pro­longed shutdown periods, are safely diluted by the fan on start-up before excitation current is applied. Win­dows in the cover permit easy inspection of the brushgear.

465

Page 33: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

FIG. 6.20 Rotor end ring

Monitoring of excitation current and voltage and rotor winding temperature by resistance measurement, is simply achieved in a generator with sliprings, using a current shunt and voltage connections in one of the excitation cubicles. Rotor earth fault detection, and the application of tests such as the recurrent surge method for shorted-turn detection, are also simply arranged.

Where no main excitation sliprings are fitted (Fig 6.23), signal may be transmitted from the shaft, via telemetry. Alternatively, a set of light current slip rings and brushgear may be provided for signal monitoring and protection purposes.

466

It is normal for a large generator to produce an on-load voltage of 10- SO V between its two shaft ends, due to magnetic dissymmetry and other causes. This voltage would drive .:urrent axially through the rotor body, returning through bearings and journals, causing damage to their surfaces, and insulation bar­riers are provided to prevent such current circulation. These need only be at one end, the exciter end, but must be present wherever the shaft would otherwise con­tact earthed metal, for example, at bearings, seals, oil scrapers, oil pipes and gear-driven pumps. In some designs, two layers of insulation are provided, with a 'floating' metallic component between them,

Page 34: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

.)>. 0) -....1

SLIPRING CONNECTION TUBE

·O'RING LOCKING PLATE

'0' RING , ,-,:-~ ~.,..-~----·~r

INSULATING

ROTOR SHAFT

SLIP RING

AXIAL LEAD TO SLIPRING 'A' & 'D' ----

AXIAL LEAD TO ----------====~ SLIPRING 'B' & 'C'

COMPRESSION RING /

LOCKPLATE

, SLIPRING CONNECTION STRIP

SLIPRING CONNECTION RING

SLIPRING AXIAL LEAD

INSULATION UNDER SLIPRING

SEALING GASKET

COMPRESSION PLATE

METHOD OF CONNECTING SLIPRINGS IN PARALLEL TO AXIAL LEADS

Fie. 6.21 Sliprings and connections

LOCKING SCREW

PLUG

-i c ..., S!. :::l CD

I

<0 CD :::l CD ..., QJ .... 0

0 0 3 "0 0 :::l CD :::l ...... (/)

...... ~ CD

0 ...... 0 ...,

Page 35: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

BRUSHGEAR SUPPORT BRACKET PLASTIC RING

j WASHER

STEEL WASHER

~ INSULATING CAP

~

INSULATING CAP

FLANGED INSULATING BONDED INSULATING \ BUSHES TUBE

---~- ---

NUT

STUD

METHOD OF SECURING BRUSHGEAR PALMS TO BRUSHGEAR SUPPORT BRACKET

~ ! ~·i

I

RUBBER GLOVE

INSULATED HANDLE

TUBE SPANNER LOCKING SCREW

SLIPRING

FtG. 6.22 Slipring brushgear and brushes

468

Chapter 6

,....._~___...~ MILLED RECESS

CARBON BRUSH

A MAIN GENERATOR I ~ ROTOR SHAFT

Page 36: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

I I

FLEXIBLE CONNECTOR

Turbine-generator components: the rotor

TOP NUT

R!NG NUT

"''

INSULATION

ROTOR SHAFT END STUD CONNECTOR

FIG. 6.23 Brushless rotor connections

so that a simple resistance measurement between the floating component and earth confirms the integrity of the insulation.

While all the insulation remains clean and intact, a voltage will exist between the shaft at the exciter end and earth, and this provides another method of confirming the integrity of the insulation. A shaft­riding brush enables this shaft voltage to be moni­tored, and an alarm is initiated when this falls below a predetermined value.

It is important that the shaft at the turbine end of the generator is maintained at earth potential, and a pair of shaft-riding brushes connected to earth through a resistor achieves this. Because carbon brushes develop a high resistance glaze when op­erated for long periods without current flow, a spe­cial circuit passes a 'wetting' current into and out of the shaft through the brushes; this circuit also detects when brush contact is lost (Fig 6.24). A different scheme, in which a current carrying contact

TURBINE GENERATOR

JUNCTION BOX

RESISTORS ---------

MAIN EXCITER

VOLTAGE MONITOR BRUSH JUNCTION BOX

FUSE HOLDER LINK 1 OHM

STATION EARTH

DIAGRAM OF EARTHING BRUSH CONNECTIONS

FIG. 6.24 Shaft earthing and monitoring

469

Page 37: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

or rub anywhere a!ong the turbine-generator shaft system can be detecte~, has also been used.

3.6 Fans Fans circulate hydrogen through the stator and coolers. Identical fans are mounted at each end of the shaft, each ventilating half the axial length of the generator. Fans are either of the centrifugal type, with many vanes in one annular assembly, or of the axial-flow type in which the propeller vanes may be separate bolted-on components (Fig 6.25). The diameter over the blade tips may exceed that of the stator bore, necessitating the fitting of one fan after the rotor has been threaded through the stator. Inlet and outlet conditions are far from ideal, and though stationary guide vanes are used to reduce swirl, the fan effi­ciency is low. Noise reduction is not a major concern, since the massive stator casing is an effective acoustic barrier.

3.7 Rotor threading and alignment The rotor must be inserted into the stator bore, which is about 250 mm larger than the rotor diameter. This is accomplished by supporting the inserted end of the rotor body on a thick steel skidplate which slides in the stator bore, while supporting the outboard end from a crane (Fig 6.26). The skidplate spreads the load over its area and prevents high local pressures being applied to the stator core laminations. The rotor and skidplate are pulled in using jacking ar­rangements until the inboard end emerges and can also be supported in a sling.

Other methods are also in use; short lengths of extension shaft which are successively bolted onto the inboard end enable the rotor to be supported by

Chapter 6

slings throughout the operation. The use of a support trolley running on wheels of insulation material in the bore is deprecated because of the core damage it can cause. Adequate space for rotor insertion and removal must be provided.

The whole turbine-generator line of rotors is non­flexibly coupled together and must be allowed to attain its natural catenary shape if the bearing load­ings are to be satisfactory. The supports for the generator (and exciter) rotors must be set up so that these rotors form part of the catenary. Coupling alignments are accurately set by the use of bridge gauges and concentricity checks, and the stator is set up so that the radial airgap is approximately constant.

The axial position of the rotor train is fixed by the thrust bearing, which is located in the turbine. Axial expansion of the turbine rotors downstream of the thrust face, and of the generator rotor, due to temperature changes, may amount to 25 mm or more, and this must be accommodated in bearings, seals, fan baffles, oil scrapers, etc.

3.8 Vibration Rotors for generators of 500 and 660 MW operating at 3000 r /min are relatively flexible, and pass through two main critical speeds (natural resonances in bending) during run-up to rated speed. Simple two-plane bal­ancing techniques are not usually adequate to attain the high degree of balance demanded at speed and to maintain reasonable vibration levels during run-up and run-down. Facilities for balancing are therefore provided along the length of the rotor in the form of tapped holes in the cylindrical surface, as well as in the closing discs of the end rings, and in other locations at the ends.

The rotor is balanced at speeds up to 3000 r/min in the manufacturer's works. The winding is then

FIG. 6.25 Axial flow fans on rotor

470

Page 38: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Turbine-generator components: the rotor

:1 ~~ ~

~\%~-~-~ ~ STAGE 5

11 !1 ~

~:~~ ---.. -...... -..... -.·-.·.-.-.· .. --C ,-;~ (f ,>~1 \.-~-=;

----~II I

~--J STAGE 6

FIG. 6.26 Rotor insertion and withdrawal

heated and the rotor is run at 200Jo overspeed. This subjects the rotor to stresses greater than it would experience in service, and also causes the winding and end rings to settle into their final positions. Trim balancing is then carried out, if found to be necessary.

Some rotors exhibit a relationship between vibra­tion amplitude and temperature. A few degrees dif­ference in temperature between one pole and the other, due to inequalities in ventilation, for example, can cause this. If the effect is consistent, it can usu-

ally be partially offset by balancing, so that conditions at operating temperature are optimised (see Fig 6.27).

Imperfect equalisation of the stiffnesses (see Section 3 .I of this chapter) will cause 100 Hz vibration to occur, superimposed on the normal 50 Hz. It is im­portant to distinguish between these components when presenting or analysing vibration amplitude readings. A significant crack in the rotor will have a com­paratively greater effect on the double frequency vibra­tion component; 'run-down' traces are recorded and analysed, to provide assurance that no significant

471

Page 39: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

YIBRATION AMPLITUDE

0

FIRST CRITICAL

1000

SPEED, rimm

SECOND CRITICAL

2000

(a) Typ1cal speed-v1bra11on curve

3000

Chapter .6

ORIGINAL HOT OPERATING POINT

ORIGINAL COLD BALANCE

AFTER OFFSET BALANCE, COLD

(b) Veclor plol ol oltsel balanc1ng

VECTORS REPRESENT AMPLITUDE AND PHASE ANGLE OF SHAFT DISPLACEMENT OR SINUSOIDAL VELOCITY

FIG. 6.27 Rotor vibration

change has occurred since the previous run down. Oil whirl in bearings can cause vibration at 25 Hz.

Vibration amplitude and phase are recorded at generator and exciter bearings by accelerometers mounted on the bearing supports and by proximity probes which respond to the shaft movements. Var­ious degrees of sophistication, up to complete Fourier analysis, are available.

The torsional resonance of the generator rotor coupled to the turbine rotors is of the order of 13 Hz. It is important that this is significantly dif­ferent from the frequency of torsional exciting in­fluences, of which the excitation and steam governor control (1-2 Hz), and transmission system resonances are the most important.

Transient oscillations in torque occur during elec­trical disturbances, e.g., during switching operations, lightning strikes, imperfect synchronising events, etc. Some of the torque cycles may be large enough to cause plastic deformation in the turbine-end shaft and at the generator/exciter coupling.

3.9 Bearings and seals The turbine-end bearing is located in a common ped­estal with the LP turbine outboard bearing. The ex­citer-end bearing is either located in the endshield or in a separate pedestal. The white-metalled bearings are spherically seated for ease of alignment, are pres­sure lubricated and are provided with jacking oil tap­pings. They are similar to the turbine bearings (see Chapter 1), except that the outboard and exciter bear­ings are insulated (see Section 3.5 of this chapter),

472

and are connected to the same lubricating oil system. Seals are provided in both endshields to prevent

the escape of hydrogen along the shafts. Most of these seals are like small thrust bearings, in which a non-rotating white-metalled ring bears against a collar on the shaft (Fig 6.28). Oil fed to an annular groove in the ring flows radially inwards across the face into a collection space at frame gas pressure, while the radially outward flow is collected in an atmospheric air compartment. The seal ring must be held against the rotating collar, and must therefore be able to move axially to accommodate the thermal expansion of the shaft.

Some machines have seals which resemble small journal bearings (Fig 6.29), in which oil is applied centrally and flows axially inboard to encounter the hydrogen pressure and axially outboard into an at­mospheric compartment. Such a seal does not have to move axially, since the shaft can move freely inside it. Details of the seal oil system are given in Section 5.3 of this chapter.

3.10 Size and weight A rotor for a 660 MW generator is up to 16.5 m long and weighs up to 75 tonnes. It is provided with a cradle for transport. The rotor must never be al­lowed to be supported on its end rings; the weight must be taken by the body surface leaving the end rings free. Lifting slings must only be used over the body length. It must be protected from water con­tamination, while in transit or storage, by the use of a weatherproof container with an effective moisture

Page 40: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

DIAPHRAGM OUTER RETAINING RING

Turbine-generator components: the stator

INSULATING RINGS

\ . \ DIAPHRAGM INNER

DIAPHRAGM \ RETAINING RING \ I

\ I OUTER END COVER y

SUPPORT KEY

LOWER BEARING PAD

-JOINT SCREW

WHITE METAL SEAL FACE ~--

FIG. 6.28 Thrust-type shaft seal

absorbent. If left inside an open stator, dry air must be circulated.

Protection applied to journals, sliprings, etc., must be removed before operation. Blanking tape and collars, designed to prevent ingress of foreign ma­terial into the winding, must also be removed before operation.

4 Turbine-generator components: the stator The stator must carry the output winding, provide a low reluctance path for the magnetic flux, and with­stand the torque produced, both at rated load and during faults.

When generators rated 300 MW and above were first specified, it was found that the smallest prac­ticable stator core, assembled into the lightest pos­sible casing was too heavy for transport by road in the UK, within the statutory limitation of that time. Since it is not practical to design a core in sections for on-site assembly, and complete core building and winding on site has disadvantages, a design evolved in which the core and windings were assembled into a skeletal core frame, which could

be transported. The completed core and core frame assembly was inserted into a substantial outer casing for in-works testing c'md finally at site. Although one-piece stators for 660 MW generators can now be transported, the two-piece concept has been con­tinued (see Fig 6.1).

4. 1 Stator core The core provides paths for the magnetic flux from one rotor pole around the outside of the stator wind­ing and back into the other pole.

As the rotor rotates, carrying its flux distribution with it, all points in the stator core experience a sinusoidally-varying 50 Hz flux density. This would induce a 50 Hz voltage of about 700 V axially in a solid core, and to prevent large circulating currents with their associated losses, the core is made of thin steel plates coated with an insulating material; the voltage induced axially in each plate is about 50 m V.

The sheet steel from which core plates are cut conforms to BS601, which specifies dimensional lim­its, magnetic properties, silicon content (normally 3 OJo) and state of annealing, and test methods. Sheet thick­nesses used are 0.35 and 0.5 mm, with a specific

473

Page 41: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

GAS SIDE OIL -­WIPERS

SEAL HOUSING

SEAL RETAINING RING

SEAL CARRIER RING

SEAL OIL DRAIN !GAS SIDE!

• •- AIR SIDE OIL FLOW

- GAS SIDE OIL FLOW

Chapter 6

SEAL SHAFT

FIG. 6.29 Double-flow ring seal

total loss value at 1.5 tesla and 50 Hz of 3.55 W /kg, or better.

Core plates are cut to form segments of an annular ring, twelve segments per ring being common. Wind­ing slots, location notches and holes for ventilation (if required) are cut in one pressing operation. The use of dedicated dies is justified, since nearly a quar.­ter of a million core plates are used in each 660 MW generator. The punched plates are ground to remove edge burrs, and are then coated all over with one or more thin layers of a baked-on insulating varnish.

With the core frame axis vertical, and one core end plate in position at the lower end of the frame, a ring of core plates is assembled, located on dove­tail-shaped keys on the inside periphery of the frame. The radial butt joint between plates has as small a gap as possible to minimise magnetic flux distor­tion. The next ring of core plates is assembled so that its butt joints do not coincide with those of adjacent rings (see Fig 6.30).

Gaps in the build-up of core plates are created,

474

where required, for the passage of cooling gas, by building in a ring of thicker plates to which small steel bars have been welded. These bars are aligned in a mainly radial orientation, and serve to distribute the gas through the ducts. Holes in the plates are arranged to be in axial alignment and thus form axial ventilation ducts in some designs. At intervals during core building, heavy pressure is applied to consolidate the assembly of plates.

When the build is almost complete, and with pres­sure applied at the top end, the core is subjected to a peripheral 50 Hz magnetic flux, which causes the plates to shake down further, following which the space created is filled with more core plates and the top end plate is assembled and pulled down. Core flux tests are also carried out on the completed core, with a flux density in the back of the core 90-lOOOJo of the rated value, in order to demonstrate freedom from significant faults (Fig 6. 31). If sufficient acci­dental contacts between adjacent plates occur, it is possible for current to flow, causing local hot spots.

-~

Page 42: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Turbine-generator components: the stator

FIG. 6.30 Stator core assembly

An infra-red camera is used to scan the stator bore for areas of higher than normal temperature during such a test.

Some designs include a bonding agent between layers of core plates to ensure that individual plates, and particularly the teeth, do not vibrate independ­ently. Any wavyness in core build-up is corrected by the use of suitable packing material.

Grain-oriented sheet steel, whose magnetic pro­perties are deliberately made different in the two perpendicular axes, is used in some designs (Fig 6.32). Flux in a circumferential direction behind the winding slots is arranged to coincide with the low loss orienta­tion, which enables the back of the core to be op­erated at a higher flux density than with non-oriented core steel, for the same specific loss. The opposite is true for the teeth, where the flux is radial and the specific loss is higher than normal. A reduction in outside diameter should be possible from magnetic considerations, but the mechanical properties are ad­versely affected. Core plates of grain-oriented steel must be specially annealed after punching.

The net axial length of magnetic steel presented to the flux is less than the measured stacked length by a factor between 0.9 and 0.95, known as the stacking factor. This is because of the varnish layers (and adhesive if present), and the air spaces between core plate layers due to uneven plate thickness and im­perfect consolidation.

Slots for the stator winding conductors (bars) extend radially from the bore. These slots have parallel sides, so that the deep bars can be inserted radially, the teeth between them therefore increase in section with increasing radial distance. The flux density i~ the teeth is therefore greatest at the bore, at the tooth tips, and is usually about 2 tesla for an acceptable speci fie loss in the teeth. Since the slots and teeth are roughly equally wide at the gap, the mean peak flux density in the air gap is typically 1 tesla. The peak flux density in the core back is typically 1.5 tesla. Some leakage flux in the end winding regions penetrates into the ends of the core. The axial com­ponent of this flux induces alternating voltages in the teeth, and current flows around the teeth, as shown

475

Page 43: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

---------------The generator Chapter 6

FIG. 6.31 Flux test on completed core (see also colour photograph between pp 482 and 483)

in Fig 6.33, causing unacceptable additional losses. To reduce this effect, one or more radial slots are punched in the teeth for a few centimetres at the ends of the core, referred to as Pistoye slots.

The rotating magnetic field results in a rotating radially-inward force being applied to the core across a diameter, causing an ovalising distortion moving synchronously. The strength of the core and core frame assembly must be able to resist this force with minimum strain, which is transmitted to the windings and the outer casing as a 100 Hz vibration. It is also important that the assembly has no resonances near to the exciting frequency.

Hysteresis and eddy current losses in the core form a significant proportion of the total loss. In UK designs, the heat produced by these losses is removed by hydrogen circulating radially in the ducts and axially through holes, where these are provided (Fig 6.34). Thermocouples are built into the core, parti­cularly in regio~s expected to be hotter than average, to ensure that the maximum detected core temperature does not exceed the specified value. If a hot spot exists, or develops in service, it is unlikely that there will be a thermocouple sufficiently close to it to provide an unambiguous alarm. An occasional flux test, when opportunity occurs, offers a better chance of hot spot detection. A deep-seated hot spot may be detectable by observing the rate of rise of tern-

476

perature at the bore, as well as the final steady temperature.

As noted earlier, if accidental contacts occur (at the tooth tips or due to burrs at, or damage to, the slot surfaces), a circuit may possibly exist for a cir­culating current. The current level depends, inter alia, on the contact resistances between the back of the core plates and the core frame bars on which the plates are assembled. In some designs, all these bars (except one which earths the core) are covered with insulating material, minimising the chance of current circulation (Fig 6.35). In others, there is no insu­lation, and the contact resistance is not only random, but may vary with load as the torque reaction is transferred, causing a hot spot in the core to 'switch' on and off.

4.2 Core frame The fabricated steel core frame is designed to be as light as possible consistent with its required functions, as previously explained. As well as the functions already noted, it must be able to resist elastically the axial pressure applied to the core.

A core end plate assembly consists of a thick disc of non-magnetic steel, with (usually) separate non­magnetic 'fingers' to support the teeth. Because bolts

Page 44: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

DIAGRAMMATIC REPRESENTATION OF MAGNETIC FLUX IN STATOR CORE, OPEN-CIRCUIT CONDITIONS

AREA OF MODERATE

FLUX DENSITY

AREA OF HIGH FLUX DENSITY

ROLLING DIRECTION

GRAIN-ORIENTED CORF SEGMENT

FIG. 6.32 Flux in stator core

j t HIGH

MAGNETIC LOSS

DIRECTION

passing through the core would have high voltages induced in them, the only permissible axial members are located outside the core back; these include the core plate assembly bars. In order to apply pressure uniformly over the core ends with such an arrange­ment, the end plates are machined with tapered inner faces, so that when they are pulled towards each other they distort until they present a truly plane surface to the core, at which point the design pressure is being applied to the core (Fig 6.36).

The core plate assembly bars are loose as the core is assembled, and are progressively welded to the frame as core building proceeds, using location plates. Thus, although the core frame may be stress-

Turbine-generator components: the stator

relieved, these additional welds are not. Even though the axial frame members are outside

the core diameter, they link with the low level of leakage flux existing in this area, and voltages are in­duced axially along them. Near to the ends, elec­tromagnetic end-effects tend to force the resulting currents into the core and, if the assembly bars are not insulated, core back burning and welding can oc­cur. To prevent this, copper short-circuiting connec­tions are fitted between assembly bars at the core ends. Where the bars are insulated, the currents flow into and around the core end plate.

The outer surfaces of the core end plates are covered by conducting screens of copper or alumi­nium, about 10 mm thick (see Fig 6.37, end plate flux shield). Leakage flux impinging onto these screens sets up circulating currents within them which prevent the penetration of an unacceptable amount of flux into the core end plate or the ends of the core. The high conductivity and good surface exposure to cooling hydrogen ensures that screen temperatures are not excessive. The leakage flux is produced by a combination of stator and rotor MMFs, and there­fore varies with load angle, or, roughly, with power factor, the effect on the screens being most intense at leading power factors.

The core end plate assembly carries the end winding support structure, and the design must ensure that axial forces due to differential thermal expansion be­tween core and winding do not force the end plates into a position where core pressure is significantly reduced.

The completed core and core frame assembly must be jacked into position inside the casing, where it is supported on feet with resilient mountings, or by flat vertical support plates, either of which provide some attenuation of vibration. The holding down bolts must be designed to withstand the overturning torque pro­duced during a sudden three-phase fault at the ter­minals, which may be four to six times the full-load torque.

4.3 Stator winding The stator winding must be able to carry the rated current without exceeding specified temperatures and be able to withstand the voltage to earth induced in it. The currents and voltages in the three phases must be exactly the same, but with a 27r/3 time dis­placement for balanced conditions, and so the wind­ings associated with each phase must be identical but separated by 27r/3 around the stator circumfer­ence. It is convenient in large two-pole generators to arrange each phase winding in two identical paral­lel circuits, located diametrically opposite each other, and, because they are influenced by rotor poles of opposite senses, connected back-to-back with each other (see Fig 6.10).

477

Page 45: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

COOLANT MANIFOLD WINDING FLANGED JOINT COOLANT INLET

/'._~ANIFOLO CORE CORE FRAME CORE END LEAD WINDING LEAD1

PLATE ~ CLAMP · _,

I ;_+H~,' - _L='~l11--~~;l BLANKING I -,

PLATE 1 lie-,-:·, ~"-'

1 r~ "c~--- ==j-

~~ I

I I-·

1 ~~ ~~r---

JC>-----Cr ~~~,

li

li AXIAL

EXTENT OF PISTOYE

SLOTTING

,•

I

MAIN FLUX

SUPPORT SADDLE

I .~------------

CURRENT INDUCED BY AXIAL FLUX

J AXIAL VIEW OF STATOR TEETH

FLEXIBLE HOSE

INSULATING SLEEVE

PISTOYE SLOT

FIG. 6.33 Pistoye slots in stator teeth

Slots must therefore accommodate six similar winding circuits, differing only in phase displacement; and 42, 48 or 54-slot arangements are commonly used. A two-layer arrangement is adopted, in which a winding progresses from a top conductor (bar nearest the bore) in a slot, bending in two planes after it emerges from the core to span nearly a quarter of the circumference. At this point it is connected to a similar bar which continues the span but on a larger conical diameter, and re-enters the core as a bottom conductor almost opposite the first (not exactly op­posite because of short-pitching). This bottom bar is then connected, at its other end, to the top bar in

478

the slot next to the previous one, and the winding continues in this manner until one-sixth of the slots are filled. Because of short-pitching, some slots. con­tain a top bar of one phase and a bottom bar of a different phase.

A 776 MVA, 23.5 kV generator has a rated RMS current of 19 080 A, i.e., a current of 9540 A per bar. By cooling with water in contact with the conductor, a current density of 8 A/mm2 of cross-sectional area can be achieved. With a slot width of about 45 mm, and allowing for insulation, the effective conductor width is restricted to about 30 mm. Sufficient area must be allocated for satisfactory water flow, and

Page 46: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Turbine-generator components: the stator

a: CJ >-<( a: w z w (C)

w I >-I 0 :::0 0 a: I >-z CJ ;::: (.) w (f)

>-a: it

(f) <((f) 0<(

oc.D --'>-00 UI CfJ(f) WUJ >->-00 zz WUJ 00

n

c 2 .2 ;: '-' > ~

2 , v;

"" M

-o

0 .:

479

Page 47: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

480

EARTHING STRAP

INSULATION

CLAMPING POSITION

DETAIL SHOWING CLAMPING AND EARTHING POSITIONS VIEWED FROM TURBINE END OF CORE

FtG. 6.35 Insulated core frame bars

EARTHING POSITION

CORE

Chapter 6

Page 48: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

CORE SUPPORT BARS'~

CORE

SIDE BEAMS

TRUNNION MOUNTINGS

FRAME FEET

HOLDING-DOWN BOLT HOLES

Turbine-generator components: the stator

LONGITUDINAL BEAMS

JACKING POINT

EXTENSIONS

FIG. 6.36 Core frame

the radial conductor dimension becomes about 40 mm, with the overall radial bar dimension about 80 mm.

A current carrying conductor embedded in a nar­row slot in a magnetic material drives magnetic flux around itself, mainly confined to the magnetic teeth, but completing its circuit by crossing the 'airgap' represented by the slot width, further up the slot than the conductor (Fig 6.38). If the conductor is viewed as an assembly of separate strips, it can be seen that the leakage flux density experienced by each strip increases linearly with distance from the bottom strip. This alternating leakage flux induces alternating volt­ages along the lengths of the strips, in quadrature with the main voltage, and varying as the square of the distance of the strip from the slot bottom. If a solid conductor were used, or if the strips were connected together at the core ends, these unequal voltages would circulate current around the bar, causing un­acceptable eddy current losses and heating.

In order to minimise this effect, the conductor is divided into strips, which are lightly insulated, arranged in two or four stacks in the bar width. The strips are transposed along the length of the bar by the Roebel method (Fig 6.39), in which each strip oc­cupies every position in .the stack for an equal axial length, so that the eddy current voltages are equalised and no eddy currents circulate between strips. The

effect is not quite nullified since leakage fluxes occur in the end winding areas also, and some designs use a transposition of greater than 360° in order that these end effects shall not be additive.

A differential eddy current voltage still exists bet­ween the top and bottom of each strip, and current will flow around it. The loss due to this current varies as the fourth power of the radial dimension of the strip, so the incentive is to make the strip very thin. However, the space required for insulation then becomes excessive and compromise is needed. Water is circulated in rectangular section tube, which must have a considerable depth, and in some designs an op­timised mixture of tubes and thinner solid strips is used (see Fig 6.40).

Conductors are made of high conductivity hard­drawn copper. Each strip or tube has a thin coating of glassfibre insulation, and is cranked to enable all the strips in a bar to be assembled with the Roebel transpositions correctly made. The bar ends are bent using formers to give the required shape of end winding. The strips are bound together and the main insulation is applied; a tape of mica powder loaded with a synthetic resin, with a glassfibre back­ing, is wound without breaks along the length of the bar. The straight part of the bar is pressed in a heated mould to cure the resin and obtain the

481

Page 49: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

.--------------------------------------------

The generator

ENDPLATE -FlUX SHIELD

CORE ENDPLATE

STATOR INNER FRAME RIB

Fll>. 6.37 Core end-plate and screen

design dimensions, while the curved ends are con­solidated using heat-shrinkable tape. Tests are carried out to ensure that the insulation is properly canso-

D D D

SLOT CONTAINING IDENTICAL

CONDUCTORS

DISTANCE FROM SLOT BOTTOM. X

(a) CURRENT BELOW X (b) MMFAT X

Chapter 6

lidated and free from significant voids, and electrical tests confirm the integrity of the insulation. The insulation is very hard and the insulated bar has little flexibility.

The slot length of each bar is treated with semi­conducting material to ensure that bar-to-slot elec­trical discharges do not occur, and a high resistance stress grading finish is applied to the ends to control surface discharge, particularly during high voltage tests.

Bars carrying such large currents experience large forces; in the slots these are directed radially out­wards towards the bottom (closed end) of the slot, and alternate at 100 Hz. The closing wedges therefore are not required to restrain the bars against these forces, but it is important that the bars do not vibrate, and the wedges are arranged to exert a radial force, either by tapered packers or by a corrugated glass spring member. Some designs use a corrugated glass spring packer in the slot side to provide side­ways restraint. Packers of insulation material, se­parators and drive strips, and layers of conformable thermo-setting dough are also used in the slot fill (see Fig 6.40). Support of the end windings and the arrangement of connections are dealt with in later sections.

The electrical loss due to the stator winding is traditionally separated into the 12 R loss, using the measured DC resistance of the winding phases at the operating temperature, and the 'stray' loss, in which are included components due to:

• AC resistance being greater than DC resistance (skin effect).

• Eddy currents, as already noted.

(a) FLUX LINKAGE AT X I b) EDDY VOLTAGE AT X

DISTRIBUTION OF EDDY CURRENT

FIG. 6.38 Illustrating the variatioll" of eddy currents in stator conductors

482

Page 50: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

FIG. 4.24 Heysham 2 condenser - modular construction

FtG. 6.31 Flux test on completed core

Page 51: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

-

Ftu. 6.41 View of a 660 MW generator ;;tatur end-windings

Page 52: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

I

I

I

u.. ...

'""'"

FrG. 6.90 C't!h'dltion ninnitor (NEI Parsons Ltd)

Page 53: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

FIG. 6.97 Dinorwig motor-generator during site winding

Page 54: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Turbine-generator components: the stator

FIG. 6.39 Roebel transpositions

• Currents induced in core end plates, screens, and end teeth.

• Harmonic currents induced in the rotor and end ring surfaces.

• Currents induced m frame, casing, endshields, fan baffles, etc.

These individual losses have to be assessed so that the appropriate cooling medium is directed to their sources, in order to a~oid~ unacceptable localised hot spots.

4.4 End winding support In the end windings, bands of conductors are arranged side-by-side, all carrying the same current although not all in phase, and considerable electromagnetic

forces are produced, both at rated load and parti­cularly when large current peaks occur during fault conditions. The end turns must be strongly braced to resist the peak forces and also to minimise the 100 Hz vibration.

The MMF produced in the end winding region by the combined effect of the stator and rotor end wind­ings produces a considerable magnetic flux in the end regions. Paramagnetic material would tend to concentrate the flux into itself, and electrically-con­ducting material would have eddy currents induced in it, causing both additional loss and potential hot spots, Metallic inserts and fastening devices can be caused to vibrate and loosen, or wear away their surrounding medium. Consequently non-metallic com­ponents are used, mainly moulded g!assfibre.

Substantial support brackets are bolted to the core end plate and provide a support for a massive glass­fibre conical support ring. The outer layer of end turns is pulled onto a bedding of thermosetting con-

483

li 'i

Page 55: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

484

EACH BAR COMPRISES 2 GROUPS OF 2 STACKS OF STRAPS

CROSSOVER INSULATION

ALTERNATE SOLID AND HOLLOW COPPER CONDUCTORS

RIPPLE SPRING

GROUP VERTICAL SEPARATOR

ALL HOLLOW COPPER CONDUCTORS

TOP COIL

CLOSING WEDGE

FIG. 6.40 Stator slot

BOTTOM INSULATION PACKING STRIP AND CONFORMABLE DOUGH

GROUP BINDING TAPE

ASBESTOS FINISHING TAPE

INSULATION PACKING STRIPS AND CONFORMABLE DOUGH BETWEEN COILS

MAIN INSULATION WRAP

STRAP INSULATION

PROTECTIVE DRIVING STRIP

Chapter 6

OPPOSED TAPER WEDGES APPLYING RADIAL RESTRAINT

-

Page 56: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

r------------------------------------------------------------------------------------------------------------~

formable material between i! and the support cone, and packers between the bars arch-bind the structure circumferentially. The inner layer is treated similarly, with a ring of blocks pulled down onto the cone by through-bolts, completing the very rigid structure. Some designs use sheets of insulation material to enclose any spaces and prevent the accidental ingress of any foreign material. Magnetic material is parti­cularly unwelcome, since it can be caused to vibrate and abrade, or be heated by eddy currents and de­grade the adjacent insulation (see Fig 6.33). Vibration of the end windings must be minimised, since it can promote fatigue cracking in the winding copper. This is particularly serious if it occurs in a water-carrying tube, since hydrogen will leak into the water circuit. Resonances close to 100 Hz must be avoided, since both the core ovalising and the winding exciting force occur at this frequency. Accelerometers in the end winding structure allow any increase in vibration due to support slackening to be monitored. Vibration am­plitude is highly current dependent. Any looseness developing after a period in operation can be cor­rected by tightening the bolts, by inserting or tighten­ing wedges, and/or by pumping a thermosetting resin into rubber bags located between conductor bars.

Figure 6.41 shows the stator core and end windings for a 660 MW generator.

4.5 Electrical connections and terminals Electrical connections between one conductor bar and the next in series are made differently in different designs. In one, a common electrical and water con­nector is formed by a copper tube bent into a U-shape, and brazed onto small copper waterboxes into which all the bar subconductors are brazed. In another, the electrical joint is made by a solid copper bolted joint, with the water connections separate. It is common practice to insulate the joint or to enclose it in a rubber housing.

The conductor bars at the high voltage end (line end) and the low voltage end (neutral end) of a phase band are electrically connected to tubular connectors which run circumferentially behind the end windings at the exciter end, to the outgoing terminals, usually with line terminals at the bottom and neutral ter­minals at the top, although other arrangements do exist. These connectors are internally water cooled, and must be insulated for line voltage.

Terminal bushings (Fig 6.42) are proprietary paper­insulated items, with internal water cooling from the stator winding water system. Their insulation must be capable of withstanding the hydrogen pressure in the casing, with no perceptible leakage. It is common practice to flange-mount the terminals on a plate of non-magnetic material, and to arrange for a terminal to be withdrawable from outside the casing. Current transformers for instrumentation and protection sig-

Turbine-generator components: the stator

nals are housed on the external stems of the bushings. The connections from the generator terminals to the

generator transformer are described in Volume D. Phase isolated connections are always adopted, so that an electrical fault at the connections must start as a line-to-earth fault, which is much less damaging to the generator than a line-to-line fault.

4.6 Stator winding cooling components Water is the best of the commonly available media for cooling the stator winding, and imposes only one condition that would not also apply to other fluids: it must be pure enough to be effectively non-conducting (electrically). It is continuously degassed and treated in an ion exchanger, with the following target values being aimed for:

Conductivity:

Dissolved oxygen:

Total copper:

pH value:

100 JLS/m

200 j.tg/litre max (in some systems > 2000 is acceptable)

150 JLg/litre max.

9 max.

At these levels, no aggressive attack on the winding copper has been noticed after very many years' ex­perience. Any erosion of copper is detected by the monitoring equipment.

Water is passed into one or more inlet manifolds, which are copper or stainless steel pipes running cir­cumferentially around the core end plate. From the manifolds, flexible PTFE hos~s are connected to all the water inlet ports on the stator conductor joints. In a two-pass design, water passes through both bars ~n parallel and is transferred to the two connected bars at the other end, returning through similar hoses to the outlet manifold which adjoins the inlet mani­fold. This design minimises the number of hoses, but requires a larger pressure head of water across the winding (see Fig 6.43). In a single-pass arrange­ment, hoses connect both ends of a bar to the manifolds, which are located at opposite ends.

Thin metallic-sleeved components are crimped in­side and outside the ends of the PTFE hoses, and these are then attached to bosses on the manifolds and winding connectors, using screwed-up olives, 0-rings or brazed joints. The casing hydrogen pressure is everywhere greater than the water pressure in the winding circuit, so that any leakage is of hydrogen into· water, rather than the reverse, which would be damaging to the winding insulation.

The loss input into the water circuit at rated load is designed to raise the water temperature by less than 30°C. With an inlet temperature of 40°C, there is plenty of margin before the\temperature at which boiling would occur, 115-120°C at the working pres-

485

Page 57: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

486

Ftu. 6.4! View of a 660 MW generator ;tator end-windings (see also wlour photograph between pp 4~2 and 483)

Chapter 6

Page 58: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

CLAMP FLANGE

CONNECTION PALM

GAS SIDE

AIR SIDE

FIG. 6.42 Generator terminals

Turbine-generator components: the stator

2 GAS/WATER ·o· RING SEALS.

SEAL

SEAL

TUBULAR COPPER CONDUCTOR

MAIN INSULATION

EXCITER END

SEAL

CONNECTION PALM

OUTER STATOR FRAME

ALUMINIUM TERMINAL

PLATE

487

Page 59: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

INLET TO NEUTRAL TERMINAL

PTFE HOSES

\ I

OUTLET FROM MAIN TERMINAL

- INLET MANIFOLD

'- OUTLET MANIFOLD

TO NEUTRAL TERMINAL ____\ FROM INLET MANIFOLD

, MAIN TERMINAL TO OUTLET MANIFOLD

PHASE RINGS

Chapter 6

EXCITER END

~ DIAGRAMMATIC SECTION OF STATOR

COIL-TO-PHASE RING CONNECTIONS

COIL-TO-COIL CONNECTIONS

FIG. 6.43 Stator winding water cooling system components

sure. Monitoring the temperature of each bar by thermocouples, either in the slots or in the water outlets, enables a reduction or stoppage of water flow in a bar to be detected.

4. 7 Hydrogen cooling components The advantages of hydrogen cooling, and its para­meters, are described in Section 5 of this chapter.

Hydrogen enters the generator casing through an axially-oriented distribution pipe at the top, carbon dioxide for scavenging being admitted through a simi­lar pipe at the bottom.

The rotor fans circulate hydrogen over the end windings and through the stator core, while a parallel flow passes through the rotor. At rated load, the hydrogen temperature increases by about 25°C during the few seconds taken to complete this circuit. Two or four hydrogen coolers are located vertically or

488

horizontally inside the casing; they consist of banks of finned or wire-wound tubes through which water flows in one or two passes while hydrogen flows over them. The coolers are arranged so that their headers are accessible (for tube cleaning) without degassing the casing. The tubes and the cooler frame must be supported so as to avoid resonances close to the principal exciting frequencies of 50 Hz and 100 Hz.

It is most important that moisture does not con­dense on the stator end windings, since electrical breakdown may then occur. The dewpoint of the hy­drogen (at casing pressure) must be at least 20°C lower than the temperature of the cooled hydrogen emerging from the coolers, and this is continuously monitored by a hygrometer. In normal on-load op­eration, the stator winding water maintains the wind­ing temperature above 40°C; if condensation occurred it would be on the hydrogen coolers first. During run-up, however, the stator winding water is likely to be cold, and it is either pre-heated electrically, or

Page 60: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

irculated for a lengthy period, to .warm the winding fore the generator is excited.

8 Stator casing .. e casing contains the stator core and core frame,

.nd must resist the load and fault torques. It must :o provide a pressure-tight enclosure for the hy­ogen. Historically, casings have been made strong

nough to withstand the pressure developed by an '"1ition of the most explosive mixture of hydrogen

d air, without catastrophic failure. Because any mixture of hydrogen and air within

he explosive range is not allowed to occur, attain­~nt of explosion pressure is not a credible condition,

___ d to specify the casing on the basis of withstanding uch a pressure without leaks, as would be required

BS5500, is unrealistic. Consequently, the full re-tirements of the pressure vessel code are not invoked,

hough some of them are applied. This pragmatic mproach has been justified by worldwide experience over

'ty years. Casings are fabricated steel cylinders of up to

~5 mm thickness, reinforced internally with annular rings td axial members which strengthen the structure and •rm passages for the flow of hydrogen (see

Figs 6.44 and 6.45). Internal spaces are provided with

Turbine-generator components: the stator

runners to accommodate the hydrogen coolers. At the ends, thick rings provide facings for the separate end shields. Internal supports for the core frame, in the form of horizontal footplates or spring plate fix­ings, are provided, and external feet support the complete assembly. Lifting trunnions are usually made detachable.

The design of the welded joints is carefully con­trolled to avoid the presence of unfused lands wherever possible. The main welds have to be leak-tight against hydrogen at 4 bar, which is a very exacting require­ment. The complete casing may be too large to be stress-relieved in an annealing oven, in which case it must be assumed that stresses up to yield. stress exist il). the welds. In one design, the casing is con­structed in two halves, which are stress-relieved before being welded together.

The end shields are thick circular fabricated steel plates, ribbed to withstand the casing pressure with minimal axial deflection. They house the shaft seal stationary components and, in some designs, the out­board bearing. Leak-free sealing of the end shield/ casing joints against the hydrogen pressure, as with all other casing joints, is effected by gaskets, 0-rings and sealing compounds injected into grooves.

The completed casing assembly is hydraulically pres­sure tested, and finally must be demonstrated to be leak-tight to a level corresponding to a fall from

~ COOLER ENCLOSURE

POCKET

TURBINE END

JACK SUPPORT BRACKET

COOLER SEAL ~~ ~ ~ BARS, ;:~~'-~\ ~'

FRAME RIB PLATES

MAIN TERMINAL ENCLOSURE

FIG. 6.44 Outer stator casing

\,

ROTOR COOLING GAS

DUCTS

END PLATE

JACK SUPPORT BRACKET

489

' . '

Page 61: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

FIG. 6.45 Core frame being inserted into casing

490

Page 62: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

rated hydrogen pressure of not more than 0.035 bar in 24 h. '

Some of the core vibration is' transmitted to the casing, and rotor vibration is transmitted through the end shield and the foundations. The casing assembly must be designed to avoid resonances in the range of these exciting frequencies.

Drains are arranged so that any oil or water col­lecting in the bottom of the casing is piped to liquid leakage detectors, which initiate an alarm. Distri­bution pipes for hydrogen and C02 are built-in; a temperature sensor at the C0 2 inlet initiates an alarm if the incoming gas has not been adequately heated and could chill the fal;>ricated casing locally. Electrical heaters are fitted in the lower half of the casing to maintain dry conditions during outages.

The casing is bolted down to the supporting steel­work on packing plates which are machined after trial erection to provide the correct alignment. Axial and transverse keys prevent subsequent movement. The weight of the casing, complete with core frame, coolers and water, is up to 450 tonnes.

5 Cooling systems A generator of this type has an efficiency of about 98.51Jio. Even though the. losses are low in terms of the output, they amount to some 10 MW, all of which must be removed by the cooling systems; the heat lost by convection and radiation from the casing is not significant.

In some stations, most of the generator (and exciter) losses are transferred into the boiler feedwater system by using condensate in the heat exchangers. While such an arrangement can be economic, there is a penalty in the form of added complication, and the most modern stations do !not have this feature.

5.1 Hydrogen cooling Hydrogen has several advantages over air as a means of removing heat from turbine-generators:

• The density of hydrogen is the lowest of all gases and is one-fourteenth that of air. Even at the rated pressure (4 or 5 bar) and with the allowable level of gaseous impurities, it is still only half as dense as air at normal temperature and pressure (NTP). The large loss due to the gas being churned by the rotor, and to its circulation through the fans and cooling passages, is minimised by the use of hydrogen as a coolant.

• The heat transfer cap~bility of hydrogen is up to twice that of air in similar conditions, though, as with all gases, it increases with increasing pressure. Together with the several times higher thermal con-

Cooling systems

ductivity and specific heat of hydrogen, the effect is that heat removal from heated surfaces is up to ten times more effective, resulting in lower tem­peratures. Coolers can also be considerably smaller.

• The use of hydrogen imposes the need for herme­tic sealing and condition control, which helps to ensure that the original electrical clearances are maintained.

• More importantly: the degradation of insulation by oxidation processes cannot occur in a hydrogen atmosphere.

The disadvantages are:

• Since concentrations of from 4~o to 76~o of hy­drogen in air are explosive, hydrogen must not be allowed to escape from the stator casing and its associated pipework in significant quantities and become trapped in potentially explosive pockets. The casing and end shields have to be of rugged construction and leak proof, demanding meticulous welding techniques. Penetrations such as the rotor shafts, and all outgoing connections, must be posi­tively sealed, the former requiring a sophisticated sealing system.

• A comprehensive gas control system is required. For generators rated much above I 00 MW, air cool­ing is not practical; more than half the total loss would be due to fan and rotor windage. At 500 and 660 MW, hydrogen pressures of 4 or 5 bar are economic; higher pressures than this have little or no advantage. The only practical alternative at these ratings is complete wat~r cooling including the rotor, which has not been adopted in the UK, and only rarely elsewhere, because of leakage pro­blems at the very high water pressures produced by the rotation.

5.2 Hydrogen cooling system It is necessary to ensure that potentially explosive mixtures of air and hydrogen do not occur when filling the casing with hydrogen, or when emptying it.

The usual method is to use carbon dioxide as a buffer between the two other gases, in a process known as scavenging, or simply gassing-up and degassing.

Carbon dioxide, stored as a liquid under pressure, is expanded to a suitably low pressure above atmos­pheric. It is also heated, because the expansion causes it to cool and it would otherwise freeze. With the rotor stationary, C0 2 is fed into the bottom of the stator casing through a long perforated pipe, and because it is more dense than air it displaces air from the top via the hydrogen inlet distribution pipe to atmosphere outside the station. Some mixing of gases occurs at the interface. A gas analyser is used to

491

Page 63: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

monitor the proportion of C02 in the gas passing to atmosphere; when tllis is sufficiently high, the C02 inlet is closed (see Fig' 6.46).

High purity hydrogen from a central storage tank or electrolytic! process is then fed through a bus main at about 10 bar to the gas control panel, where its pressure is reduced before being fed to the casing through the top admission pipe (Fig 6.47). Being very much lighter, it displaces the C0 2 from the bottom of the casings via the C0 2 pipe to atmosphere, again with some degree of mixing. When the proportion of C0 2 in the vent is low enough, the proportion of air left in the casing will be very low, and if the casing is then pressurised with hydrogen to its pp­erating pressure (say 4 bar), the proportion of air will be reduced to a quarter of this low value. The complete process normally occupies a few hours.

Separate procedures are followed to ensure that other components, such as tanks, are properly scav­enged, so that dangerous mixtures do not occur. The reverse of the foregoing procedure, using C02 and then dry compressed air, is followed to remove hydrogen from the machine for inspection or for a prolonged outage.

In one design of 500 MW generator, air is removed from the casing by drawing a vacuum, using the pump normally used to degas the seal oil. The shaft seals are arranged to seal effectively under this unusual operating condition. When the vacuum is as low as can be achieved, hydrogen is admitted, the resulting purity when pressurised being sufficiently high.

Normally, hydrogen purity remains high, since air cannot leak into the pressurised system. Some air may, however, be released from the shaft seal oil flowing into the casing hydrogen space. Replacement hydrogen to make up for leakage is usually sufficient to maintain the required purity.

The differential pressure developed across the rotor fans is used to circulate a sample of casing hydrogen continuously through a katharometer-type purity monitor, which initiates an alarm if the purity falls below a p'reset value, typically 97o/o. The purity monitor (and the gas analyser) can be calibrated with pure gases from the piped supplies. A check on the purity is also possible by monitoring the differential pressure developed by the fans, which responds markedly to the change in density produced by air impurity.

A pressure sensitive valve admits hydrogen from the bus main if the casing pressure falls below a pre­determined level, while a spring-loaded relief valve is set to release hydrogen to the outside atmosphere if the pressure becomes excessive. It is important that these two 1 pressures are not set so close that wastage occurs, particularly as the gas temperature and pressure changes when on-load cycling. Monitoring of the hydrogen consumption is a recently introduced feature on some units (see Fig 6.48).

The temperature of the hydrogen is normally moni-

492

Chapter 6

tored by several thermocouples, whose readings should be averaged, at the inlets to and outlets from the hydrogen coolers. Typically, hydrogen is circulated at 30 m3 Is which, with a full-load loss input of about 5000 kW, results in a temperature rise of the order of 30°C. The cooled gas should not be hotter than 40°C, so the temperature of the gas entering the coolers should not exceed 70°C.

Water cannot normally leak into the casing from the stator winding water circuit or the hydrogen coolers, since the water pressure is lower than the gas pressure in both circuits. It can be released from the shaft seal oil, particularly if the oil is untreated turbine lubricating oil which has picked. up water from the turbine steam glands. It is important that the mois­ture content of the casing hydrogen be kept low enough to prevent condensation occurring on the coldest component, which may be the water cooled winding. The differential pressure is used to circulate a flow of hydrogen continuously through a dryer, typically of the twin-tower type, using activated alu­mina, with automatic changeover and regeneration. A motor-driven blower maintains the flow through the rotor when the rotor is not running at speed (see Fig 6.49).

Continuous monitoring of the humidity of the cas­ing gas is provided by means of a hygrometer. The maximum permissible dewpoint is not less than 20°C below the cold gas temperature, measured at casing pressure. It is important that this caveat is observed, particularly if the dewpoint is being compared with that of a sample drawn from the casing and measured at atmospheric pressure.

Hydrogen is circulated by the fans through the stator core and end wiQdings, the precise paths being different in different designs. The rotor acts virtually as its own fan, hydrogen being drawn through the windings and exhausted into the airgap, again dif­ferently in different designs. The hydrogen removes the electrical loss in the rotor winding, the 'iron loss' in the stator core, the windage loss produced by the rotor and fans, and most of the electrical losses gen­erated in the frame and end winding structures.

Because it is impractical to ensure that potentially explosive mixtures of hydrogen and air never occur in the small bore instrumentation pipework, those instruments and devices containing electrical circuits in contact with the gas, such as katharometers, must be intrinsically safe in such mixtures. This means that a sudden break in an electrical circuit must not be capable of providing enough spark energy to ignite the gas.

It is impossible to ensure complete freedom from leakage of hydrogen over the lifetime of the plant, and the areas near to potential leakage sources are classified into zones of differing degrees of hazard, described in detail in CEGB Code of Practice 098/34: 'Code of Practice for the Design Principles relating to the use of Hydrogen in Large Generators'. Zones 0

I l [ I i I !

I

Page 64: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Cooling systems

I ~-----------------------------------------1 TURBINE • ... PERFORATED ADMISSION PIPE ... ... EXCITER I END GENERATOR STATOR CASING END

---------,

'1 I

t ,.

,_ - -t I I TO f-M

t ATMOSPHERE

......... • 1--....,__ ....... I

I I I ......... -1- I

~ f-M-; I I 1-- ' I I...,.._ / ? '

I I LIQUID

f-M-ALARM 1-M-I I CHAMBERS

I

I I I

1---- ........ ----1--- --- --- _J I I I I I I I - -I

C02

KATHAROMETER I

~ -o -Q-t>4-0- - .. Ill

I : 00

GENERATOR GAS

~ DRYING SYSTEM

H2 KATHAROMETER ~ ~l

I

I o.;

r--GAS CONTROL

o- EMERGENCY PANEL

.· INTEGRATING FLOW METER '---

FROM CO

I '-~SUPPLY2

"~

I

~t

- 1-FROM

HYDROGEN LP DELIVERY MAIN I s

; l

l ----AIR

C02 ;'\

I FIG. 6.46 Generator gas system - displacing air with C02

493

I

Page 65: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

• • PERFORATED ADMISSION P!PE • • TURBINE GENERATOR STATOR CASING EXCITER END t END

1

- - -TO ~

ATMOSPHERE ..... .... -~

,. ~ ........ --... ...

r-M- rM" 1--

cl' LIQUID ALARM ~ ~ CHAMBERS

... - -- -

~ - ....

00 GENERATOR GAS

~ DRYING SYSTEM

H2

KATHAROMETER ~ J.

494

r---~~--------------~ a-INTEGRATING .___H><r----------f FLOW METER ..

.1 .,

--

GAS CONTROL EMERGENCY PANEL

I -FROM C02 SUPPLY

FROM r-~-~~-------~~~~~HYDROGENLP

DELIVERY MAINS

FIG. 6.47 Generator gas system - displacing C0 2 with H 2

.. !'!

Page 66: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

TURBINE END

PERFORATED ADMISSION PIPE

GENERATOR STATOR CASING •

FIG. 6.48 Generator gas system in normal operation

Cooling systems

EXCITER END

495

Page 67: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

DRYER H, INLET VALVE

ISOLATING VALVE

BLOWER DISCHARGE

VALVE

SECONDARY

~ ~"""" ~

Chapter 6.

PRESSURE GAUGE

co. REGULATOR

FIG. 6.49 Gas dryer and blower

and 1, in which explosive mixtures exist continuously or occur in normal operation, should not be present if the principles outlined above are followed. Zone 2, in which explosive mixtures are unlikely to occur and, if they do will only exist for a short time, covers :l,strumentation as previously noted; the hydrogen dryer and blower, the detraining tanks, and the in­terior of the control cubicle to which hydrogen is piped. Also classified as Zone 2 are the areas into which hydrogen may leak, through gaskets, seals, etc., knowing the normal pressure behind the gas and its propensity for rapid upward movement. Sources of ignition are not located in such areas. It is, however,

496

virtually impossible to eliminate some potential igni­tion sources, such as the rotating shaft rubbing an oil scraper ring, or sparking at brushgear.

Another potential source of ignition occurs where currents are induced in pipework loops, as may be the case when pipes are routed near to main con­nections. Here, flanged joints are insulated to break the possible current path.

If a serious rupture occurs, e.g., the break-up of a shaft seal, hydrogen may escape very rapidly, and if it encounters a source of ignition, say the shaft rubbing, it will burn intensely in the ambient air. In order to vent the casing to atmosphere outside the

Page 68: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

station, and to admit C0 2 to the casing, duplicated valves are provided, one set bei~g located remote from where any fire is conceivable (see Fig 6.50).

Hydrogen has been used universally for 50 years for high speed generator cooling, and incidents such as this have been very rare. The meticulous attention to safety precautions both in design and operation have been largely responsible for this good record.

5.3 Shaft seals and seal oil system Seals prevent the escape of hydrogen where the rotor shafts emerge through the casing end shields. What­ever their design, they are located in the end shields, and are inboard of the bearings. Two types of seal have been commonly used: the thrust seal and the journal seal.

5.3.1 Thrust type seal

In the thrust type seal (Fig 6.28), the seal ring acts like a thrust face, bearing onto a collar on the shaft. Turbine lubricating oil is fed to a central circum­ferential groove in the white-metalled face of the seal ring, at a pressure controlled to be greater than that of the casing hydrogen. Most of the oil flows outwards over the thrust face and drains into a well. A small proportion flows inwards, against centrifu­gal force and with only the oil/hydrogen differential pressure behind it, into a drainage compartment which is at casing hydrogen pressure. This oil can release entrained air and water at this point, thus contami­nating the casing hydrogen, as noted earlier, and it is therefore important that the inward oil flow is small.

The seal ring is attached to a housing which must be free to move axially to accommodate the 30 mm or so of axial movement imposed on the shaft by thermal expansion of all the coupled rotors down­stream from the turbine thrust bearing, as they pass from cold to hot conditions. The housing is arranged to move inside a stationary member, using rubber sealing rings to contain the oil and to create an axial pressure at the seal face.

In some designs, an additional chamber between fixed and sliding components is fed with oil at a separately controllable pressure so that the overall pressure at the seal face can be varied. In another variation, additional pressure is provided "by springs.

5.3.2 Journal type seal

Here the seal resembles a short journal bearing float­ing on the shaft. In this case the shaft can freely move axially through the seal, and it therefore does not have to accommodate the thermal expansion of the shaft. Again, oil is fed to a central annular groove

Cooling systems

in the white-metalled ring, and flows along the clear­ances between the shaft and the bore of the seal, both outwards to the drain and inwards to the hy­drogen pressurised space. The inward flow rate is much greater than that for the thrust type, because it is not inhibited by centrifugal force, and it would be capable of contaminating the hydrogen purity to an unacceptable extent. To prevent this, all the oil fed to the seals is subjected to vacuum treatment, in which much of the air and water is removed. Against this disadvantage, it is claimed that the journal type seal is inherently better able to withstand disturbances of the shaft by expanding to provide a larger clear­ance for oil flow if it is heated by excessive shaft movement.

More sophisticated versions of the journal type seal, one of which has two separate oil supplies for inward and outward flow, have been developed to avoid the need for vacuum treatment (see Fig 6.29). It is also possible to keep the oil supplies separate from the main turbine lubricating oil supply, which is the source of most of the entrained water.

5.3.3 Seal oil system

In the conventional seal oil system (sec Fig 6.51), the main seal oil supply is taken from the shaft-driven lubricating oil pump, with its pressure suitably re­duced. The pressure is further controlled by diaphragm valve which maintains a constant differential pressure above casing gas pressure at the seals. The oil is cooled in a water-cooled heat exchanger, and finely filtered to prevent metallic particles gaining access to the small clearances at the seal faces.

' Because it is necessary to maintain the shaft sealing oil at standstill, to prevent hydrogen escape, motor­driven seal oil pumps are also provided; these act as a back-up in emergencies, and are initiated by falling seal oil pressure. They are commonly vertical pump­motor units mounted on the top of the lubricating oil settling tank with the pumps submerged. A battery fed DC motor-driven pump may be provided as a back-up in case of supply failure, but this would be expected to operate only a few hours while the hydrogen is scavenged.

The oil flowing to the casing side of the seal is in a pressurised hydrogen environment and must be collected in a 'break pressure' tank, which releases it through a float controlled valve and enables it to be returned to the drain tank. The possibility of hydrogen entering the drain tank is recognised; low level alarms give a first warning (some form of pressure loop is usually provided) and a blower exhausts the gas above the oil in the 'hydrogen section' of the tank to at­mosphere. This blower aJso serves to reduce the pressure in the bearing housings (communicated via the half empty drain pipes) below atmospheric, thus reducing egress of oil vapour at the bearings.

497

Page 69: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

TURBINE END

H2 KATHAROMETER

-

,---~~--------------~ o-INTEGRATING '----f-t><l---------i FLOWMETER

' I

----- H2

----co2

Chapter 6

PERFORATED ADMISSION PIPE

GENERATOR STATOR CASING EXCITER END

TO ATMOSPHERE ......

-I-

I--

-i'-

-H-:

r'*

/ / LIQUID

l-M-ALARM CHAMBERS

--------«-

-~ ......

~ !--

~

f-M-

00 GENERATOR GAS DRYING SYSTEM

r--G-A_S_C_O_N~T-R_O_L ______ 1 ____

EMERGENCY PANEL

t-• FROM C02 SUPPLY

FROM r-~-~~---------~~--~-HYDROGENLP

DELIVERY MAINS

FIG. 6.50 Generator gas system - emergency scavenging

498

Page 70: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

3~WAY COCK !WITH L PORT!

ALARM ON GAS CONTROL CUBICLE

PRESSURE GAUGE

LIMIT SWITCH

TRANSMITTER

PRESSURE SWITCH

DIFFERENTIAL PRESSURE SWITCH

-----ELECTRICAL CONNECTIONS

-- SEAL OIL SUPPLY

--~RETURN TO MAIN OIL TANK

I SEAL OIL SUPPLY

GENERATOR

CONTINUOUS VENT RETURN --~-c><J--'­

TO MAIN OIL TANK

Q::J I

'

COMPARTMENT

TO BARRING GEAR INT,ERLOCK

FIG. 6.51 Seal oil system

DRAIN

Cooling systems

PRESSURE ACCUMULATORS

499

Page 71: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

L.

The generator

5.4 Stator winding water cooling system Water in direct contact with the winding conductors is the most effectiv·e and economic means of heat removal, and is used throughout the range of gen­erators under consideration (see Fig 6.52). Five main criteria must be observed:

• The conductivity of the water must be very low, to prevent current flow and electrical flashover.

• The means used to transfer water into the conduc­tors must be of high integrity insulation material, not easily degraded.

• The velocity of the water must be low enough to prevent erosion, and the design must not allow cor­rosion to occur, either of which could lead to a build-up of conducting material, causing an elec­trical flashover.

• The maximum water pressure must be lower than the casing hydrogen pressure, so that if any leakage occurs, it is of hydrogen into the water circuit, since leakage of water into the winding insulation could lead to an electrical breakdown.

• The maximum temperature in the water circuit must be low enough to provide an adequate margin below boiling point (commonly about ll5°C at the pressure involved). The design aims for an inlet temperature of just above 40°C, with an outlet temperature of 65 -70°C.

Demineralised water is used, which is obtained ini­tially, and made up, from the turbine condensate. A proportion is circulated through a demineraliser (Fig 6.53) to ensure that the water quality described in Section 4.6 of this chapter is maintained. All the metal with which the water is in contact is either non-ferrous or stainless steel. Even small components made of mild steel are not permissible because of the propensity for magnetite to form and be held by electromagnetic forces.

Flexible hoses made of extruded PTFE (polytetra­fluorethylene) are used to transfer water into and out of the conductors. This material has good electrical properties, is chemically inert and has a long life in the ambient conditions, has an extremely low friction factor so that particles are less likely to adhere, and is partially translucent in the thicknesses used, so that flow (containing bubbles) can be observed. The low friction has a disadvantage in that attachments are more difficult to arrange, but leak-free crimped joints have been satisfactorily developed (see Fig 6.33).

The water is circulated by duplicated pumps, through a water-cooled heat exchanger and fine filter, to the generator inlet connection. Designs differ from this point. In one, the main supply goes to a circular manifold supported from the stator core end plate.

500

Chapter 6

From the manifold, PTFE hoses connect to the elec­trical joint ('nose') between a top and bottom con­ductor bar, through which the water flows in parallel. At the exciter end, the water in each bar is trans­ferred through the electrical connector to a return bar, and thence via another PTFE hose to the outlet manifold, located alongside the inlet manifold. A small flow is· tapped-off to cool the terminal bushings and phase connections. This is a double-pass system, requiring higher pressure than a single-pass system, but half the number of hoses with their potential for leakage.

In the single-pass arrangement, the manifolds are at opposite ends, and the water flows through only one bar in series. This system allows smaller water passages in the conductors to be used because a higher pressure drop per bar can be tolerated.

Other variations may be seen in obsolescent designs. In one, all the conductors comprising a phase group were brought to a common waterbox, consisting of a large cast resin chamber with a bolted-on lid, inside which electrical connections between conductors were made. In another, the water passed through five con­ductor bars in series before returning to the manifold. This required a high pump pressure but minimised the number of hoses.

If the flow is significantly reduced, the water tem­perature rises rapidly. Reduction in flow is therefore sensed, usually by differential pressure across an ori­fice plate or across the stator winding itself, and is used to bring in the standby pump, and to trip the unit, if flow is not restored quickly.

Water pressure is determined by the height of the header tank and the pressure developed by the pump. These are not contr6!led, since it is expected that the casing hydrogen pressure will not be allowed to fall much below its rated value in operation. During start-up, the hydrogen pressure must be established before the water pump is started, to prevent a reverse pressure differential.

The water circuit is tested initially to ensure that it has a very low leak rate, but hydrogen will enter the water in small quantities. lt is detected by arranging a settling tank on the outlet side of the generator, before the header tank connection, where gas will largely detrain. It is collected in a chamber equipped with timed release valves, and an alarm is initiated if the release rate exceeds an acceptable level (see Fig 6.54).

Thermocouples in each winding slot provide a means of detecting a low flow through one (or both) of the conductor bars in that slot. More recent machines have a thermocouple in each outlet hose, which provides a more direct indication of incorrect flow. Water t1ow does differ somewhat between different paths, and outlet temperatures also differ; the best indication is a departure from normal operational experience for a similar condition of loading and primary cooling water temperature.

Page 72: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

CJ1 s

OVERFLOW PIPE

SIGHT GLASS

,_ ~

~--{ _j---- - l I t

FROM STATION'' r· ~·~I ., DEMINERALISED ~ ~

"'"' "'~" : '] :

.......,~~~~~- -i --~ i

SIGHT GLASS

i STATOR WINDING MANIFOLDS~

M

TURBINE END

GENERATOR

RESISTANCE COLUMNS

TO DRAIN

' t y

'

TO MAIN TURBINE TRIP

RELAY CUBICLE

TO ATMOSPHERE

_t_ ~j_J TtRAIN GAS TRAP

~------,::_-=:=} ___ ___ ) : I : :------ J

' I ' I ' I

I sl--------, j (

: ' y'

0\ ~{1 ! ,--,h_ . ~ (' r ------;coUNTER I ~·-------!>4--------

"fr-----J I I

1

4 ,, : : I I '"___)- ---- __ j I

"'- - ' GAS ALARM AND I ,·

L_ --1

TO GENERATOR GAS SYSTEM

,r,,,

T AUTOMATIC I

A RELEASE CHAMBER ' •

{=:=:--.J , I - --~-J' ________ __.J

--------l

r _ _L __

/ t ~

-,---J)----------, : t ~ (t ) ~/ ~--

DETRAINING 1'

1 CHAMBER

L_ J j

I 1 i I

DC EMERGENCY STATOR COOLANT PUMP

AC STATOR AC STATOR COOLANT P COOLANT

PUMP 'A

EXCITER END

!STATOR WINDING MANIFOLDS i

~ i

STATOH COOLANT

GAS RELEASE

DRAIN, PRESSURE, TEMPERATURE

CONTROL AIR

ELECTRICAL

VALVE POSITIONER

-\-\-0 ,____.. TO GENERATOR AUXILIARIES CW SYSTEM

~-\~_P_r-N----j

~dPS~

I I I I I L_____ -----~J ~- f

FIG. 6.52 Stator winding water cooling system

() 0 Q_ ;:::)

co en -< en .-+ co 3 en

_______________ ...._ ______________ .... _______ ,.

Page 73: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

~----------------------------------------------------- --

The generator

GASKET

TREATED WATER OUTLE f VALVE

U-BOLT CLAMP--.____

,,

OUTLET PIPE ASSEMBLY

I

!' L

II 1:

DRAIN VALVE

502

------------~-----, --~-

FIG. 6.53 Demineraliser

lOP COVER

UNTREATED WATER INLET VALVE

RATE OF FLOW INDICATOR

DCMINERALISER COLUMN

AIR INLET VALVE

RFSIN

RESIN REMOVAL VALVE

BOTTOM COVER

Chapter 6

:•·;

r: ~:

~j ,.:

~~

~: ~~ ~-i; f ,, j;·

" lJ ~ "' , •. ~ f' !I

t f. t I; }

* f ~

t f

{1.

a. ~ l t'.

l; 1 i r

Page 74: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Cooling systems

GAS OUTLET

FLOAT OPERATED SWITCH

t

__.IL---~ BODY

SUPPORT BRACKET

GAS INLET

FIG. 6.54 Gas-in-water detection chamber

As noted earlier, it is important that condensation does not occur on the windings. Some machines have an electrical heating element, or an automatic cooler bypassing system, to prevent water that is too cold from circulating in the windings during start-up and early loading.

It is not easy to measure the insulation resistance (IR) of a winding which has multiple high resistance paths to earth through the water-filled hoses, and even draining out the water does not ensure that the inside surfaces of the hoses are dry. Attempts have been made to use a specially designed resistance measuring device which uses the water manifolds as 'guard rings', but this is not always satisfactory. Fortunately, modern

epoxy resin insulation systems do not absorb mois­ture, and a low IR is usually indicative of surface contamination, which can be removed by warmed air circulation.

5.5 Other cooling systems Casing hydrogen is cooled by passing it through water­cooled heat exchangers arranged horizontally or ver­tically in the casing. The heat exchangers consist of many tubes of non-ferrous metal with either metallic strip fins or wire loops brazed to their outside sur­faces (Fig 6.55). These coolers have a double-pass

503

Page 75: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

water circulation, so that inlet and outlet water con­nections are at the same 'end. They are equipped with sealing devices so that access to the header box can be gained for inspection, even though the casing is pressurised. Some form of air venting system is also provided. The coolers can be withdrawn from the casing when it has been scavenged.

Water for these coolers (and other auxiliary coolers) may be condensate or distilled water in a self-contained system, or both; it is undesirable to use raw cool­ing water because of the danger of corrosion. The water pressure is arranged to be less than the rated pressure of hydrogen in the casing, so that in the event of leakage, hydrogen will leak into the water circuit. In the latest machines, hydrogen detectors are provided in the water circuit (Fig 6.56). Operation is usually possible with one hydrogen cooler valved­off; this provides some redundancy. Loss of primary water is detected by rise of hydrogen temperature, which may be so rapid that the protection is arranged to trip the unit.

Air cooling systems are provided for the rotating exciters, and for the slipring/brushgear or rotating rectifier chambers. The rotating ex~,:iter components have a closed air circuit with a water-cooled heat exchanger; the sliprings usually have open air venti­lation.

EXCITER END

SEALING GASKET

INLET AND OUTLET WATERBOX DOOR

Chapter 6

6 Excitation

6.1 Exciters

6.1.1 Historical review When the first AC generators were introduced a natural choice for the supply of the field systems was the DC exciter. These direct current commutator ma­chines were not only used as main and pilot exciters but later also as a control amplifier, known as a rotating amplifier or amplidyne.

The DC exciter suffered from commutation and brushgear problems but also offered certain advan­tages; in particular, a capability for equal voltage output of either polarity, which was used to improve generator transient performance. The main exciter ar­mature also provided a path for the commutation of induced currents, regardless of polarity, which ap­pear in the generator field winding during pole-slipping and other severe system disturbances, thereby limiting the induced voltage.

Gear-driven exciters were introduced to extend the application of these machines, however, increased demand for higher excitation currents paralleled by advances in semiconductor technology brought about

CORNER MEMBER

COVER PLATE

FLEXIBLE / ~> :r~ GASKET ~. ,II!:.;;tr ,/,.

:s.-J~ ,· ( -U , r

SMALL HOLE ~.'/ ' ··, SLIDING n

TUBEPLATE ' f /

SEALING STATOR END GASKET

WALL

SEALING RING

FIG. 6.55 Hydrogen cooler

504

f l ! ! I

I .~ ~

I t

t

I I

Page 76: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

TREATED WATER SUPPLY FROM HIGH LEVEL HEAD TANK

' I

• I I I I

11 *~ I ~ --1

I I I I

TO STATION DRAINS TRENCH

ATMOSPHERE

----- DISTILLED WATER ----- BY-PASS -..-..-.-- MAKE UP WATER

I

B

2 x I 00% EXCITER AIR/ RECTIFIER COOLERS

A

A

4 x 25°o HYDROGEN COOLERS

c

A

2 x I 00% STATOR WATER COOLERS

: B I I I

r L-1-o--------------------J

Excitation

r -::LIARY COOLING WATER OUTLET

AUXILIARY __.. ==='-'==:::::::!:U: COOLING WATER INLET

FIG. 6.56 Distilled water cooling system

505

'[

Page 77: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

the introduction of the rectified AC exciter. These were either static s~miconductor diode rectifiers sup­plying the generator field winding via sliprings, or brushless systems which carry the diode rectifier on the shaft. Developments have continued and excita­tion powers now range from 70 kW for 20 MW gas turbine-generators to 3500 kW for the 660 MW steam turbine-generators.

Where generators are connected to the main transmission system over long transmission links, it is necessary to provide a high response excitation system capable of satisfying system transient stability requirements. In these circumstances, a static thyris­tor excitation system capable of step changes in field voltage is generally specified.

6.1.2 AC excitation systems

The excitation requirements of all CEGB 500 and 660 MW turbine-generators are provided by AC excitation systems. A typical AC excitation scheme, showing the shaft-mounted main and pilot exciters together with associated brushgear is shown in Fig 6.57.

The CEGB currently operates 660 MW turbine­generators with either static or rotating excitation equipment. Detailed descriptions of these are given in Sections 6.2 and 6.3 of this chapter respectively, while this section concentrates on exciter plant which is common to both.

To maximise plant availability under 'black start' conditions, reliance on external electrical supplies is kept to a minimum by using direct-driven perma­nent magnet pilot exciters. For many years, DC pilot exciters were used, but the low currents involved introduced commutation problems due to brushgear glazing and, as a consequence, they were superseded by AC machines.

The pilot exciter provides power for the excitation A VR control equipment which, on present 660 MW plant, is of a salient pole design with ratings approach­ing 100 kW.

Both the main and pilot exciters are air cooled machines, cooling air being drawn through the ma­chine by shaft-mounted fans. Temperature measure­ments are taken at the inlet and outlet of the cooling circuit to monitor performance.

6.1.3 Exciter transient performance

Exciters must operate over a wide voltage and current range as ceiling requirements are considerably in excess of rated full-load conditions. The exciter is required to respond quickly to changes in excitation at its own rotor terminals. This requirement for a fast response characteristic is achieved by the use of a short air gap and a laminated rotor body.

Exciter transient performance is characterised by the exciter response ratio defined in BS5000 Part 2 as follows: '

506

Chapter .6

Exciter response ratio =

The average rate of increase in excitation open-circuit voltage (V /s)

Nominal excitation voltage

Typically, exciters are required to increase output volt­age from lOOo/o to 20007o in less than 0.3 seconds, corresponding to a response ratio of 3.5.

The average rate of increase of the excitation open­circuit voltage is given by the slope of AC in Fig 6.58.

Slope of AC = BC/ AB but .. AB = 0.5 seconds. Hence AC = 2BC (average rate of increase of ex­citer voltage) and the nominal exciter response ratio is given by 2BC/OA.

6.1.4 The pilot exciter

A shaft-driven excitation system consists of a main and pilot exciter, the pilot exciter providing the input power to the AVR. A number of different types have been developed including salient pole, inductor type homopolar and heteropolar designs. System require­ments for complete independence from external sup­plies during 'black start' conditions have led to a trend in favour of the permanent magnet generator (PMG) pilot exciter design. The salient pole design has gained favour on all recent 660 MW units and forms the basis of the following discussion.

The salient pole PMG is a three-phase medium frequency machine, providing an essentially constant voltage supply to the thyristor converter and A VR control circuits. A typical salient pole PMG is shown on Fig 6.59.

The permanent magnet poles of the generator are manufactured from high energy material, such as Alcomax. The permanent magnet pieces are bolted to a steel hub and held in place by pole shoes. The bolts are generally made from non-magnetic steel to prevent the formation of a magnetic shunt. In some designs of PMG, the pole shoes are also skewed one pole pitch over the stator length to improve the waveform of the output voltage and reduce electrical nOISe.

The stator core is constructed from a stack of low loss sheet steel laminations, assembled within a fabri­cated steel frame. Radial and axial cooling ducts are provided at intervals along the core length to allow cooling of the core and windings. To facilitate re­moval, certain designs of pilot exciter can be split along the horizontal centre line.

The stator winding is a two-layer design, each stator conductor comprising a number of small dia­meter copper wires insulated with polyester enamel. The coils are connected together to give the rated three-phase voltage output, and insulated with Class F (BS5000 Part 2) epoxy glass material.

Page 78: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

{]1 0 -...!

R ROTOR GENERA~~USHGEAR SLIP RING

GENERATOR I "T I

BEARING PEDESTAL

I MAIN EXCITER

ROTOR

BARRING GEAR

\ I I

I I - -==~-II ~- -h- AI- I _ ~~ . .. : . b~ ~ -fi~=-'1' • - i ~ c.~:__.-.-~~~-, .. ,,:"·~~ r ~~~J. t'--'r';''l 1

c,,-rT!.u '--crrrce-•·- =''"' l ,, : ~~L_r:f. -ijf ~ 31-~ Ill ~Jc===:J =-= rl ' . , I

MAIN EXCITER STATOR

\ \

MAIN EXCITER SLIPRING BRUSHGEAR

BEARING PEDESTAL

FIG. 6.57 Section through main and pilot exciters

PILOT EXCITER ROTOR

BEARiliG PEDESTAL

BEAR IN' PEDESTAL I PILOT EXCITER I

I I

MAIN OIL PUMP

m >< (") ;:::-.· OJ r+ c;· ::J

Page 79: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

EXCITATION

SYSTEM

VOLTAGE

ACTUAL BUILD UP OF EXCITER VOLTS

_,/' ,/

t,,;~

// SLOPE

I

RATED FIELD VOLTAGE

0.5 TIME S

FIG. 6.58 Concept of the exciter response ratio

A steel enclosure is fitted over the PMG stator, which provides mechanical protection and serves to reduce the medium frequency noise emitted from the PMG to an acceptable level, as defined in BS4999 Part 51.

Cooling of the PMG is achieved by drawing air through mesh-covered apertures in the enclosure; the air is then circulated by the rotor or shaft-mounted fans.

6.1.5 The main exciter The main AC exciter is generally of a four or six­pole revolving field construction. The exception is the revolving armature main exciter used in a rotating rectifier scheme, which is described in detail in Sec­tion 6.2 of this chapter.

The exciter magnetic circuit is designed to operate on or near the unsaturated part of its characteristic. This preserves a linear relationship between the con­trolled excitation of the main exciter and the gen­erator slipring voltage. The armature is designed for low voltage operation, with comparatively high current levels. A typical rotating field main exciter arrange­ment is shown on Fig 6.60.

The stator core and windings are air cooled, the ventilation circuit being formed by the end cover and ducting in the stator casing. Thermometers are fitted to the casing to measure inlet and outlet air temperatures.

The core is constructed from a large number of segmented plates stamped from core plate material of high magnetic quality and low electrical loss. Each

508

Chapter 6.

layer of punchings in the core is made from a number of these segments, coated with insulating varnish and laid side-by-side to form a circle. All the joints on adjacent layers are staggered.

The stator winding is of a three-phase, four or six-pole design, formed by copper coils which are contained in conductor slots in the core, and retained in position by insulating slot wedges. Each coil is made from individually-insulated copper strips, con­tained within a moulded insulating tube. To restrict eddy currents in the coil, the copper strips in each coil are transposed.

The rotor consists of a hollow-bored alloy steel forged shaft which carries the silicon steel laminations forming the rotor core. The rotor body is generally laminated to reduce paleface losses in the exciter. The reduction of this loss is important, as in the ex­citer, the ratio of stator slot opening/ gap length is comparatively large, a short airgap length being ne­cessary to lighten the burden on the main exciter ex­citation system. The stator slots form indentations in the air gap boundary; therefore, as the rotor flux moves across the stator teeth, the changing permeance due to the slot openings introduces medium frequency pulsations. These pulsations induce harmonic voltages in the surface of the stator teeth but due to the laminated construction, the resultant losses are kept to a minimum.

The rotor windings are retained in position by cylin­drical rotor endcaps. A fan is mounted on a seating machined in the balance ring to circulate cooling air. At the exciter outboard end, two slipring units are connected to the endwinding, via radial connections and upshaft leads.

6.1.6 Exciter performance testing Exciters are required to undergo a number of tests within the manufacturer's works to ensure that all of the functional requirements are fulfilled. These include open- and short-circuit tests, overspeed bal­ancing and HV testing. PMG exciters are stabilised by applying short-circuits across the stator terminals to ensure that there is no appreciable loss of output voltage over the plant life.

The full exciter test requirements are contained with­in BS5000 which covers routine and type testing.

6.1. 7 Pilot exciter protection The pilot exciter is now invariably a permanent mag­net generator with windings only on the stator. These windings are insulated to 1.1 k V and tested at 3.2 k V, 50 Hz for 1 minute, which is well in excess of the normal operating voltage of 220 V.

The pilot exciter is only ever called upon to deliver its full current output during field forcing. Modern A VR equipment is fitted with a time/current limiter which allows the pilot exciter to deliver maximum

Page 80: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

CLAMPING RING-

BAFFLE

MAIN EXCITER END

OIL THROWER RING

CENTRE SECTION

BAFFLE

AIR SCOOP

Excitation

OUTBOARD END COVER

STATOR CASING

FIG. 6.59 Salient-pole permanent magnet generator

current for a pre-set time, after which the current is ramped back to a safe value.

The result of these measures is a pilot exciter having a considerable design margin for normal duties. It is not, therefore, CEGB practice to provide additional pilot exciter protection.

6.1.8 Main exciter protection

The main exciter, like the pilot exciter, has con­siderable inbuilt margin compared with its normal duties, the AC windings being insulated for 3.3 kV, even though normal working voltages are around 500 V. During ceiling conditions, this rises to approxi­mately 1000 V.

The rated current is well below maximum current; therefore, for reasons similar to those given for the pilot exciter, no additional protection is provided.

6.2 Brushless excitation systems

6.2.1 System description

The development of the solid state silicon diode, with its inherent robustness and reliability, made possible the design of a compact rectifier system that can be rotated at rated generator speed. This alternative to the conventional slipring excitation system eliminates

509

Page 81: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

GENERATOR END

END WINDING SUPPORT RING

SUPPORT RING

HAND HOLE COYER

THERMOCOUPLE ACCESS DOOR

CORE KEY

EXCITER TERMINAL LEAD

TRANSFER HOLE LIFTING LUG

FERRULE

CONNECTING STRIP

EXCITER LEAD SUPPORT CLEAT

OUTER END COVER / ~ DIVIDING PLATE / /STIFFENING STRAP ~ BAFFLE

Chapter 6

BAFFLE RING ASSEMBLY

/ STIFFENING RING

DIRECTION OF ROTATION

FIG. 6.60 Main exciter

the need for brushgear maintenance and reduces the overall unit size.

Basically, the brushless scheme consists of a re­volving armature AC exciter supplying a rotating recti­fier mounted on the same shaft, which itself is directly coupled to the main generator shaft.

The rotating excitation system does not use field suppression switches and discharge resistors. The inain generator field is de-energised by suppressing the ex­citer field which can be done rapidly by inverting the thyristor bridge which supplies it. The exciter time constants are short; therefore the time taken to sup­press the generator field is only slightly longer than in a conventional system.

All modern gas turbine units are fitted with brushless excitation systems, where the pilot exciter, main exciter and diode wheel are overhung; this arrangement means the equipment is readily accessible for inspection. The complete rotating system is balanced as a unit. The rotating diode~ are connected in a three-phase bridge arrangement, the bridge arm consisting of two diodes in series, so that if one fails by going short-circuit, the other diode will continue to operate and hence

510

the bridge operates normally. In the unlikely event of two diodes failing in the same bridge arm, a moni­toring circuit in the field of the main exciter detects the fault and trips the machine.

Because of the high excitation power requirements of a 660 MW generator, a number of diodes are con­nected in parallel in each rectifier bridge arm. A fuse is connected in series with each diode to isolate it if it fails. Present CEGB requirements include built­in redundancy of rectifier components so that, should two of the parallel paths in each arm fail, full MCR excitation requirements can still be supplied._ This increase in components has meant the use of larger diameter diode wheels. Diodes and their associated components have therefore to be designed to with­stand centrifugal forces in the region of 6000 g.

Measurements of essential quantities, such as ro­tor earth fault indication, field voltage and current are obtained via a telemetry link or instrument slip­rings.

Recent designs of rotating diode wheel have taken advantage of continued developments in semiconduc­tor diode technology to reduce the number of com-

Page 82: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

ponents. This has 'led to a simplified mechanical arrangement.

6.2.2 The rotating armature main exciter

The main exciter is a brushless machine which, in conjunction with the other units of the brushless ex­citation system, supplies power to the main generator rotor. By dispensing with commutators, sliprings and brushgear, the brushless machine requires less main­tenance than the conventional machine and there are no sliding or rubbing electrical contacts to cause sparking or carbon dust.

The machine is a three-phase rotating armature AC generator driven directly from the main generator through a solid coupling. The DC field system is mounted in the stator and the AC winding is on the rotor. A laminated pole construction is used, giving a field circuit with a short time constant to produce a fast response.

The AC output from the main exciter is rectified by diodes on the shaft and, in order to reduce diode commutation reactance, a fully interconnected damper winding is fitted to the exciter palefaces. Figure 6.61 shows a typical rotating armature main exciter.

The stator consists essentially of a fabricated support structure which carries the laminated magnet frame and the associated field windings. The support frame is formed from two steel end plates connected by rectangular steel axial tie bars. The tie bars are equally spaced around the bore to form a cage into which the magnet frame laminations are assembled.

The stator core consists of a laminated magnet frame with the laminated field poles bolted into the bore of the frame. The magnet frame is built up from segmental laminations of sheet steel. Each ring of laminations is made up of six segments; the segments in adjacent rings are half overlapped so that the radial joints do not coincide. Ventilation spacers are inserted during manufacture to form radial ventilation ducts.

The field poles are laminated and assembled onto key bars which allow the bolting of the poles onto the bore of the magnet frame. The poles are built up from T -shaped laminations clamped between end­plates by axial rivets.

The exciter armature is formed from laminations of low loss electrical sheet steel, shrunk onto a shaft forged from annealed carbon steel. Each segment is thinly insulated on both sides with a varnish, baked on to give a durable insulation. The shrink-fit is such that the stampings are always in contact with the shaft. The laminations are clamped between heavy endplates of non-magnetic steel with strong finger supports for the armature teeth.

Radial ventilation ducts are formed by spacer plates at intervals along the rotor body. Cooling air from both ends flows axially along slots machined in the shaft to feed air into the interpolar gap through the

Excitation

radial ventilation ducts. The armature windings are held in place by wedges

driven into dovetail slots formed when the winding slots are punched. The armature winding overhang is cooled by axial vents in the teeth in each end packet. The three-phase two-layer winding is secured in place by wedges made from epoxy glass mat. In order to minimise losses caused by eddy currents, the conduc­tor is made from braided strips in parallel. A Roebel transposition is used in the slot portion to reduce eddy current losses.

Each of the phase ends of the three-phase winding is connected to the appropriate_ phase conductor in the AC shaft connection assembly by six laminated copper connecting straps. A copper ring under the outboard endwinding forms the neutral point.

The AC shaft connections between the exciter and rectifier consist essentially of three cylindrical con­centric conductor assemblies which pass through the wall of the shaft. The conductor bars are insulated from each other and from the shaft.

Figure 6.62 shows the rotating rectifier unit of a 660 MW generator which is mounted outboard of the main AC exciter. Three-phase AC power is supplied to the silicon diode rectifier from the main exciter by conductors taken axially along the surface of the shaft. The components within the rectifier are con­tained against the high centrifugal forces by a steel retaining ring.

The diode modules are accommodated within the retaining ring in two circular rows, the complete rectifier being a '3-2-1 - 9' connection of 54 diodes. The notation signifies three AC connections, two DC connections, one d,iode in series per arm, and the last number indicates that there are nine paths per phase.

The rotating rectifier includes a 2007o standby ca­pacity, this ensures continued unrestricted operation in the unlikely event of diode failure. Anode-based diodes are used in the positive arm and cathode-based diodes in the negative arm of the bridge. The diodes are of a compression bonded construction.

Individual diodes are protected by two HRC (high rupturing capacity) fuses, connected in parallel, which isolate the diode should it become faulty, leaving the remaining healthy diodes to carry the full excitation current. Each diode module has a resistance-capaci­tance spike voltage suppression circuit and an indi­cator fuse. The indicator fuse, in conjunction with the blown fuse detector equipment, is designed to detect the operation of the main diode protection fuses.

The rectifier retaining ring is shrunk onto the out­side of the hub. A thick cylinder of insulation is moulded onto the inside bore of the retaining ring, and the circular rows of diodes are attached to it via the diode module heat sinks.

The anode-based diode modules, situated at the hub end of the retaining ring each consist of a heat sink, diode, capacitor, capacitor fuse and main fuse.

511

Page 83: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

AIR FILTERS

AIR TEMPERATURE GAUGE

TURBINE END ~

ARMATURE RETAINING RING

DRAIN FROM COLLECTING TROUGHS

Chapter 6

MAIN ENCLOSURE

-~~

SHAFT

ANTI-CONDENSATION HEATER

FIG. 6.61 Rotating armature main exciter

The cathode-based diode modules are situated at the open end of the retaining ring, and in addition to the anode based components have two indicator fuses mounted on the heat sink. Figure 6.63 shows a typical cathode-based module.

The DC output from the rectifier is connected to copper alloy rings shrunk onto bushes on the shaft, with insulation between the connection rings and the

512

bushes. Laminated copper straps connect the positive and negative rings to insulated radial studs in the shaft. These studs are screwed into the shaft bore insulated D-leads.

With a rotating rectifier system, diode condition monitoring is not as simple as it is on the equivalent static rectifier scheme. A method of indirect measure­ment is required to indicate a diode failure. The blown

Page 84: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Excitation

ANODE-BASED DIODE MODULE

CATHODE-BASED DIODE MODULE

INSULATION CYLINDER

SCREWED DOWELS

INSULATED CLAMPING BOLT

COUPLING BUSH AND BOLT

VENTILATION HOLES

INSULATION CYLINDER

NEGATIVE RADIAL TERMINAL STUD

-(UNDER)

RADIAL TERMINAL STUD (POSITIVE)

COOLING-AIR FLOW

FIG. 6.62 Rotating rectifier

fuse detector performs this function; it consists of two main units, an optical detector head and a ter­minal unit containing the detection equipment, shown diagrammatically in Fig 6.64.

The optical detector head consists of a unit con-

taining the three photoelectric cells associated with three separate light sources, two on the bottom face and one (the datum) on the top face. The light beams on the bottom face pass over the path traversed by the tips of the diode failure indicator fuses as the

513

Page 85: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

DIODE~

INSULATION SUPPORT PILLARS

CAPACITOR

CAPACITOR FUSE

CONNECTION STRAPS

Chapter 6

EPOXY RESIN GLASS STEADY

STRAP

INDICATING FUSES

METAL SUPPORT PILLARS

INSULATION PLATES

FIG. 6.63 Negative DC diode module

rectifier rotates. Under normal operating conditions, these light beams remain unbroken and the light shines continuously on the photoelectric cell immediately op­posite, thus maintaining a constant signal. However, should a diode fail, the associated indicator fuse op­erates and ejects a striker pin which interrupts the appropriate beam of light on each revolution. This interruption produces a pulsed DC signal at the output of the photoelectric cell which is fed to the blown fuse

514

detector circuit, where an alarm signal is generated. To distinguish between the two rows (positive and

negative) of indicator fuses, the light beams from the two probes are offset by an amount equal to half the circumferential distance between fuses. Without this arrangement, signals from the two rows of fuses would be coincident and therefore unidentifiable.

To establish the angular position of a failed diode on the rotating rectifier, a fixed datum point is con-

Page 86: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

I

I

I

I

J

I

I

l

I

I

I I

j

TUNGSTEN- HALOGEN LIGHT SOURCE

LIGHT GUIDE LIGHT BEAM

OPTICAL PROBE

INDICATOR FUSE PIN

(BACK ROW)

DATUM SIGNAL

DATUM DETECTOR

CIRCUIT

BLOWN FUSE

DATUM REf •

BLOWN FUSt

SIGNAL

DETECTOR 1---------< CIRCUIT

Excitation

OSCILLOSCOPE

REMOTE ALARM

CIRCUITS

(FRONT ROW) BLOWN FUSE SIGNAL

INDICATOR FUSE PIN

LOCAL ALARM INDICATOR

LAMP

FJG. 6.64 Blown fuse detector system

tinuously scanned by the third photoelectric cell. The datum detector output is compared with the blown fuse detector signal and the relationship be­tween the two establishes the position of the failed diode.

Generators fitted with brushless exciters employ tele­metry systems to provide measurement of generator rotor winding quantities, including rotor current, volt­age, temperature and most importantly earth fault indication.

The equipment uses solid state electronics, some of which are shaft-mounted and the remainder rack­mounted within the A VR. The rotating units are com­pletely encapsulated and accommodated in transverse holes in the exciter shaft. Plugs and sockets are used for connections. The power supply for the rotating electronics is supplied from the stationary unit at me­dium frequency via windings on the aerial assembly. The overall schematic of the telemetry system is shown on Fig 6.65:

• Voltage measurement The field voltage is obtained from a voltage divider circuit connected across the field winding. This comprises resistors Rl and R2 which have a voltage output of 0.6 V corresponding to the generator field voltage.

• Current measurement A current shunt is built into the rotor winding, giving a rriV output correspond­ing to the 0-5000 A flowing in the field winding.

• Earth leakage A DC supply is produced in the rotating electronic equipment, the positive supply of which is connected to the negative end of the field winding via a resistor R3. The negative is con­nected to the rotor shaft through a high value resistor R4. Leakage to earth will result in current flowing through these resistors which is measured by the voltage drop across R3.

The output from the current channel is fed to a volt­age controlled oscillator that produces a frequency modulated (FM) signal, which is then conveyed to the stationary unit by the aerial assembly. Voltage and earth leakage signals are treated similarly. Values of winding resistance and average winding temperature are derived from the voltage and current signals.

The signal from the field voltage demodulator is also fed to an active filter tuned to the exciter funda­mental frequency. Should a complete rectifier bridge arm fail, signals at this frequency appear in the field winding causing the filter output to increase, initiating an alarm.

515

Page 87: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

ROTOR EARTH

VOLTAGE DIVIDER

FIELD WINDING

SHUNT

EARTH LEAKAGE LIMITING RESISTOR

ROTATING PARTS

VOLTAGE TO

R1 FREQUENCY CONVERTERS

A2 VOLTAGE

CURRENT

FM OUTPUT

FM OUTPUT

~

AERIAL ASSEMBLY

FIG. 6.65 Rotational telemetry

An alternative brushless exciter design cons1stmg of a rectifier with a 3-2-2-8 arrangement of connec­tions totalling 96 diodes is also in common use. The notation signifies three AC connections, two DC con­nections with two diodes in series and eight parallel paths per bridge arm. The rectifier is designed to maintain rated output following the failure of up to two paths in any bridge arm.

A circular row of fuse modules and two circular rows of diode modules are contained against the cen­trifugal forces by a steel retaining ring. The diode modules consist of anode and cathode units, which are used in the positive and negative arm of the bridge. In contrast to the mark 1 systems, the mark 2 is fused on the AC side of the rectifier and advantage has been taken of the improved peak inverse voltage capability of modern diodes to eliminate the capacitor fuse cir­cuits. A typical mark 2 diode module is shown on Fig 6.66.

Fusing on the AC side means a reduction in fuse size, as the elements are no longer subjected to the high induced generator field voltages which occur during system faults and pole slipping incidents.

516

--

--

FREQUENCY TO VOLTAGE

CONVERTERS

VOLTAGE

CURRENT

9kHz OSCILLATOR

STATIONARY PARTS

H AMPI_I~IER

AMPLIFIER

overall schematic diagram

p~~

0-10V DC

Chapter 6

VOLTAGE

CURRENT

BRIDGE ARM FAILURE

EARTH LEAKAGE

SIGNAL OUTPUTS

ALARM OUTPUTS

The need for the two diodes in series was deter­mined from consideration of two diodes failing simul­taneously in the same phase of the rectifier. If the series diodes were not present, the result would be a short-circuiting of the generator rotor.

Indicator fuses are connected in parallel with the main fuses as a secondary method of determining diode failures. When the generator is shut down, in­spection of the indicator fuses readily identifies failed diodes.

For cooling purposes, air is circulated in a closed ventilation system which contains a water cooled heat exchanger. Air from the outlet side of the cooler cir­culates within the main enclosure. The self-fanning action of the fuse and diode modules draws air from the main enclosure through the rectifier.

6.2.3 Telemetry system The telemetry system employed on this design of rectifier makes use of the principle of frequency di­vision multiplexing and includes a number of addi­tional features. The most significant of these is the

Page 88: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

LOCATION KEYWAY

BALANCE WEIGHTS

DIODE

BASEPLATE •AND HEATSINK

LAMINATED COPPER STR!1P

INSULATION BASE

Excitation

HEAT SINK

FIG. 6.66 Rectifier module (anode)

indication and phase location of up to three blown fuses per phase, making a total indicating capacity of nine blown fuses. The other changes are the use of a single transmitter, directly modulated by the field voltage, to which are added sub-carriers contain­ing the rotor current, blown fuse and earth leakage information.

Voltage

The field voltage measurement is taken differentially at each end of the shaft, as shown on Fig 6.67. Voltage measurement is made via a voltage divider and differential amplifier 1. The output of this ampli-

fier is fed via the mixer unit 4 to the transmitter 10 to give direct frequency modulation of the trans­mitted carrier frequency.

The transmitter output is transferred via the aerial -to a carrier amplifier 16 and demodulator 17 to give a mean output voltage proportional to the carrier fre­quency. The output is then smoothed and scaled to produce an output corresponding to the DC field voltage.

Earth leakage detection

Rotor earth leakage is detected as a voltage devel­oped across a resistor R6 which produces a frequency

517

Page 89: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

(Jl

0)

PHASE A

21-32kHz

lt n! :- e":" --: -e";~ : Rl

I I I I I I I I I I I ; ; I

' ' I I i I I I I I 1

I II I : I I EIGHT SERIES I EIGHT SERIES

CONNECTED

I CONNECTED

TRANSISTOR TRANSISTOR

SWITCHES SWITCHES

AND CURRENT 1 AND CURRENT

TRANSFORMERS I TRANSFORMERS

R3

R4

FIG. 6.67 Telemetry system

I I

t--J

C2

10 AERIAL

block diagram

y,,

l l' I I

I " H DIVIDER

Y/1

,, 16

CAR FilER AMF--LIFIER

[:·0-W r~-f~c: -~ DISPLAY

-~-,-,

\ ' L_. ___ --

Jl I 33

17

CARRIER [ 1EM00ULATOR

-I ::r CD

co CD :l CD ..... OJ .-+ 0 .....

() ::r OJ "0 ..... CD -. en

Page 90: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

I

I

I

I

I

I '

r

change at the output of a voltage-to-frequency con­verter 3. This output is adcted to the voltage signal in the transmitter input mixer 4. The earth leakage signal is isolated from the carrier demodulator 17 out­put by a band-pass filter 22 and processed to provide an earth leakage alarm signal.

Field currem measurement

Field current is measured by means of eight series­connected current transformers (Tl- TS) in phase A of the main exciter output. Since each current trans­former (CT) surrounds a conductor between the fuses and the associated rectifier in one phase, the total output from the current transformers corresponds to the total phase current. The CT output modulates the voltage-to-frequency converter 5 over a range of field currents from 0-6000 A DC. The signal carrying the current information is selected by a band-pass filter 20, demodulated and rectified to give field current indication.

Blown fuse indication

Eight CTs (T9- T16) in each phase, identical to those used for current measurement, are each loaded by a transistor switch (TRS 1-TRSS), shunted by a resistor ( R 17- R24). The resistors are connected in series but under normal operating conditions each one is shorted out by its associated transistor switch. The resistance of the circuit is therefore low. If a fuse operates, the associated transistor switches off and the circuit resistance increases; further fuse failures result in fur­ther increases in resistance. This arrangement is re­peated on each of the three phases and connected to the summing unit 40 which, by supplying a current to each of the circuits, provides an output voltage proportional to the number of blown fuses in each phase. The output of the summing unit controls the output of the voltage-to-frequency converter.

The blown fuse information is selected from the receiver carrier demodulator 17 by a band-pass filter 21. The signal is then recovered by the demodulator 24. The output waveform for the circuit corresponds to the number of blown fuses so the waveform is analysed to give the number of fuse failures. Phase identification is carried out by a strobe generator 30 which produces three separate pulses that coincide with the centres of each positive phase current period.

6.2.4 Instrument sliprings

An alternative scheme is shown diagrammatically on Fig 6.68 and uses shaft-mounted sliprings. Connec­tions are taken from the exciter upshaft leads through the shaft bore to instrument sliprings mounted on the permanent magnet generator shaft. These slip­rings permit direct measurement of field voltage. The rotor earth fault indicator relay is connected to one

Excitation

of these sliprings. The brushes are designed to operate continuously in

order to achieve uninterrupted rotor earth fault pro­tection. This arrangement is lightly loaded and would, after a short period of operation at low current, develop a high resistance contact film, resulting in incorrect readings. To overcome this difficulty, a constant current is circulated through the two brushes ('brush-wetting'). This continuous flow of current Il.laintains the interface resistance constant at normal levels.

A signal proportional to generator rotor current is obtained from a search coil mounted in the quadrature axis of the exciter field coils._ The output signal is filtered and converted from a voltage to a standard 4-20 mA current signal suitable for use with the station central logging computer. The field voltage signal is similarly conditioned and buffered to protect the instrumentation from the high voltages induced in the rotor field following incidents, such as pole slipping. The current and voltage signals are subsequently processed to provide an average rotor winding temperature measurement.

Continuous monitoring of the rotating diode equip­ment is considered unnecessary, given the proven operational reliability of the equipment. This is the simplest and most robust of the described schemes to monitor essential rotor quantities. It has the added advantage that generator rotor RSO (recurrent surge oscilloscope) testing can be carried out, a facility not available with equivalent telemetry schemes.

6.2.5 Rotating rectifier protection

The main exciter is protected, against the effect of diode failure by the provision of fusing, either on the AC or DC side of the rectifier. When a diode fails, it usually fails to short circuit, blowing the high rupture capacity (HRC) fuse, which in turn blows an ejector pin indicator fuse to initiate an alarm. On the mark 1 system, the pin is detected by a photoelectric cell, and an alarm is raised in the control room. In contrast, the mark 2 system can identify up to nine individual diode failures.

On the basis of the proven high operational relia­bility of the rotating diodes, it is not now considered necessary to continuously monitor the rotating system for failure. Present practice is to examine the indica­tor fuses on an opportunity basis and during planned maintenance overhauls.

Should a major fault occur, such that a complete bridge arm is either short- or open-circuited, major damage can be caused to the excitation system. To protect the unit in the event of such a failure, it is CEGB practice to provide bridge arm failure protec­tion. This device initiates a turbine trip on detection of a failure.

The detector monitors the amount of ripple induced in the main exciter field, which in a healthy rectifier

519

Page 91: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

D

D

SIGNAL CONDITIONING

UNIT

VOLTAGE TRANSDUCER

ROTOR E::ARTH FAULT INDICATION RELAY

Chapter 6

AUXILIARY SUPPLY 110V 50Hz

4-20mA OUTPUT TO DATA LOGGER

CURREN'!" TRANSDUCER

4-20mA OUTPUT TO DATA LOGGER

FIG. 6.68 Arrangement of instrument sliprings

is the sixth harmonic of the exciter fundamental fre­quency. This ripple is associated with the normal three-phase full wave rectification of the exciter ar­mature voltage. Should a bridge arm fail (to either open- or short-circuit), a component of ripple at the exciter fundamental frequency appears in the exciter field. This is detected by a band-pass filter tuned to the exciter fundamental frequency. Once the input is of sufficient magnitude to overcome an internal bias signal, which is set to prevent spurious operation, a relay is energised which initiates a Category B unit trip.

6.3 Static rectifier excitation equipment

6.3.1 Introduction

Excitation systems based on the static semiconductor diode bridge were the first alternatives to the DC

520

excitation system. Early equipment contained diodes of relatively low rating, where up to three diodes were required in series to meet reverse voltage requirements during pole slipping. This, together with a cautious design approach, resulted in high spare capacity.

The rapid development of semiconductor techno­logy has resulted in a reduced number of simpler, more compact devices, capable of operating at high voltage and current levels. Equipment of this type has a record of high reliability on the CEGB system, and is currently in use on a number of 660 MW units.

With the introduction of the thyristor, the role of the static rectifier has radically changed. The thyristor rectifier plays an active role in the control of excita­tion power to the generator field. Like the diode, the thyristor conducts current in one direction only; however, unlike the diode, the point at which con­duction takes place can be controlled.

Excitation power modulation is achieved by con­trolling the thyristor firing angle, eliminating the need for a main AC exciter. As the time constant asso-

Page 92: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

ciated with the exciter is the principal cause of delay, its removal greatly improv~s the speed of excitation system response, enhancing generator transient stability margins.

A feature of all static excitation equipment is the need for slipringS" and brushgear which require regular maintenance. As this is carried out on-load, an inter­lock system is normally provided so that access to the slipring enclosure is prevented, unless a safety procedure has been followed. No further mention of sliprings or brushgear will be made here, as a detailed account of the equipment is given in Section 3 of this chapter.

6.3.2 General description of static diode rectifier equipment

A static rectifier system is an assembly of diodes and diode protective equipment. Typical 660 MW rectifier units consist of up to four self-contained, three-phase, full wave bridges. The number of diodes per section are selected so that MCR requirements can be met with one section out of commission. Each section is provided with AC and DC isolators, and an interlock system ensures that, during on-load operation, access can be gained to one section only.

Diode rating is based on the continuous and peak inverse voltages, together with the current/time rating on overload. A typical rectifier bridge has a number of parallel paths per arm (the diodes being specially selected to ensure satisfactory current sharing) with one diode in each parallel path.

To dissipate the heat generated during rectifica­tion, the diodes are mounted on heat sinks. Cooling is provided by either forced or natural air circula­tion and alarms are generally provided to warn op­erators of high temperature conditions which require investigation.

Busbars are used for the AC connections from the main exciter, and for the DC rectifier output to the generator field winding. The busbar system, like the exciters, is rated for llOOJo MCR and is capable of withstanding the mechanical forces arising from the worst overcurrent fault conditions.

All rectifier equipments supplied to the CEGB must meet the requirements of BS4417 which covers both routine and type testing.

6.3.3 Rectifier protection

Diodes are susceptible to overcurrent, which causes excessive heating of the element, and to overvoltages which can pierce the rectifying element and cause com­plete breakdown. It is therefore essential for system integrity that both the operating and ceiling voltages are within the capacity of the diodes.

During generator pole slipping or asynchronous op­eration, the peak voltages appearing at the slipring are about 2000 V on a 660 MW machine. Since these

Excitation

voltages appear across the rectifier in the reverse direction, it is CEGB practice to use diodes with a peak inverse capability of 3.4-4.2 kV, thus providing ample margin.

To protect the diodes against voltage spikes (caused by diode commutation effects and external switching), each diode is provided with a dV /dt suppression cir­cuit, consisting of a capacitor and series resistor. In addition, each rectifier section has a resistor-capacitor suppression network connected across the DC output to limit voltage transients coming from the DC side of the rectifier to within the peak transient voltage rating of the diodes.

The rectifier diodes are easily dama-ged by over­currents and are therefore individually protected by high speed, high rupturing capacity fuses, with micro­switches for fuse failure indication. These fuses op­erate for an internal fault to isolate the faulty diode and allow continued operation of the remaining diodes in the arm. The most severe fault experienced by the diode is a short-circuit on the DC side of the rectifier; this is cleared by HRC fuse operation.

Overcurrents due to system faults or slipring flash­overs are cleared by DC circuit-breaker operation.

6.3.4 Static thyristor rectifier schemes

The thyristor has radically changed the role of static rectifier equipment, as it no longer plays a passive but an active role in the control of generator excita­tion. One of the principal features of this form of excitation control is its very fast rate of response due to the elimination of a main exciter. A typical thyristor excitation scheme is shown on Fig 6.69.

Excitation power is generally taken from an excita­tion transformer which is connected to the generator output terminals. With this arrangement, the trans­former primary voltage follows the generator terminal voltage during normal and fault conditions. Under fault conditions the excitation power transformer must be capable of meeting the field forcing requirements at reduced terminal voltage, and of withstanding the overvoltage experienced following a load rejection.

An alternative scheme, which is not subject to system voltage variations, is the compound source rectifier system. These static systems use both current and voltage sources (generator terminal quantities) to make up the excitation power source.

To ensure integrity under 'black start' conditions, however, a scheme based on shaft-mounted exciters is an attractive alternative. The exciter runs continuously at ceiling output with low power factor, providing the thyristor converter with a constant voltage source of excitation power.

The thyristor rectifier unit is arranged in several isolatable sections so that any one section can be ser­viced while the remaining sections provide full MCR excitation requirements. Thyristor free-wheel and pole­slip crowbar circuits are generally included to protect

521

Page 93: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

REVERSIBLE CURRENT INPUT FROM STATOR

I

I I I I I I I

Chapter 6

EXCITATION TRANSFORMER

VOLTAGE FEEDBACK I ~---------~-------------------~------~~---~~

I CURRENT FEEDBACK VT

I II_ I I I

VOLTAGE REFERENCE

AUTO SIGNAL

I

I

AUTO/MANUAL CHANGEOVER

I

I

THYRISTOR CONTROL

SIGNAL

AVR

GENERATOR/MOTOR

EXTERNAL PLANT

FIG. 6.69 Typical thyristor excitation system

the thyristors from excessive overvoltages. Direct cur­rent voltage transformers (DCVTs) trigger the crow­bar into operation on detection of an overvoltage condition. Free-wheel thyristors provide a path for stored energy in the rotor during thyristor commu­tation and system fault conditions. The pole-slip crowbar provides a path for the induced reverse direction pole­slip current, so avoiding excessive pole-slip voltage developing across the rotor terminals.

The DC output of the thyristor rectifier is provided with voltage and current surge suppression circuits which are designed to protect the thyristor from volt­age spikes generated during thyristor commutation or field circuit-breaker operation. In addition, individual thyristors are protected against dV I dt breakdown by a capacitor-resistor suppression circuit connected in parallel (identical to the circuit used to protect diodes). Overcurrent protection is provided by a series-connected HRC fuse. In the event of an individual thyristor drawing excessive current the series fuse will rupture, ejecting a striker pin which initiates an alarm. Over­current excursions are normally controlled by the A VR to within the rotor heating limit; however, in the event of a prolonged overcurrent condition, the ex­citation is tripped through the field circuit-breaker.

To meet the high current requirements of large turbine-generator excitation systems, it is necessary

522

to connect a number of thyristors in parallel. This presents difficulties, since individual thyristors have different forward path c,haracteristics, causing one to conduct the majority of current; if allowed to con­tinue, this would cause breakdown. Forced current sharing, by the addition of a low value resistance or inductance in series with each anode, is normally used to obviate this.

Thyristor cooling is provided by a natural or forced air scheme. Temperature detectors mounted within the air circuit provide early warning of high temperature conditions, allowing appropriate operator action to be taken. On future large plant, the higher current ratings and associated losses may make it necessary to use water cooled thyristor equipment.

Thyristor excitation systems can improve the steady state and transient stability limits considerably because of their ability to change the generator field voltage almost instantaneously. They are therefore finding gen­eral application on generating plant which is connected to the periphery of the main transmission system, where the inversion mode of operation, in which the field current is rapidly reduced by the reversal of energy flow, is exploited to the full. The rapid field suppression achieved following isolation from the sys­tem under load rejection or fault conditions is illus­trated on Fig 6. 70.

Page 94: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Excitation

-----------------------------------

GENERATOR FIELD VOLTAGE VFD

t,

AC RECTIFIER FIELD CURRENT

time _....

-VFD MAX --------------------------\iF 0 - FIELD VOLTAGE

T1- FIELD TIME CONSTANT

11- SUPPRESSION TIME FOR A THYRISTOR EXCITER

T2- SUPPRESSION TIME FOR AN AC RECTIFIER EXCITER

FIG. 6.70 Field suppression time

6.4 The voltage regulator

6.4.1 Historical review

Early designs of voltage regulator equipment had a large deadband, were slow to respond to system changes and required regular maintenance. This was due main­ly to the use of moving mechanical components within the automatic voltage regulator (A VR). To eliminate these difficulties, A VR systems were developed which made use of the cross-field generator or amplidyne. The amplidyne was used as the regulator output stage and controlled the field of the DC exciter.

The amplidyne and DC exciter were, in turn, super­seded by the magnetic amplifier and AC exciter. In this scheme, the magnetic amplifier was used as the regulator output stage controlling the main exciter field. The output from the exciter was rectified by a diode bridge and taken, via slipring connections, to the generator field winding. Schemes of this type were successfully employed on all the CEGB 500 MW gen-

erators and continue to provide reliable operation. The rapid developments in the field of semiconduc­

tor technology brought about the introduction of the transistor amplifier and the thyristor output ampli­fier, which have increased the speed of response and improved the overall system performance. Subsequent­ly, the discrete component operational amplifier has been replaced by integrated circuit equivalents. A typical modern dual channel arrangement is shown on Fig 6.71.

Future developments in the field of A VR design will centre around the use of digital microprocessor tech­niques. These discrete time controllers offer a number of potential advantages, most notably the introduction of adaptive control strategies.

6.4.2 System description

The A VR is an essential part of the operation of a modern electrical power system. It is at the heart of the excitation control systems around which the re-

523

Page 95: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

VT 8

VT A

MONITORING \/T

WJj LlW WJJ rrm rrm rr:n

STATIC RECTIFIER

Chapter 6

400Hz

ROTOR ANGLE MEASUREMENT

UP-TO-FREQ DETECTOR

CHANNEL A

AVR

CHANNEL B

AVR

OVERFLUX EXCITATION

TRIP & ALARM

CHANNEL A

CONVERTER

PILOT EXCITER SUPPLY

CHECKING ALARM/TRIP

CHANNEL B

CONVERTER

TOTAL CURRENT

MAIN RECTIFIER

ARM O!C

FIELD DISCHARGE

FIG. 6.71 Dual channel AVR

mammg equipment operates. The central function of the A VR is to maintain constant generator terminal voltage under conditions of changing load. There are, however, a number of other functions which are required from the A VR, if a large generator is to operate satisfactorily under all operational conditions.

The CEGB currently specifies dual channel A VR equipment complying fully with EES 1980 together with manual back-up control on all 660 MW plant. This provides maximum reliability as the loss of one chan­nel does not inhibit operational performance. Facilities are provided to repair the faulty channel while the generator remains in service. On small gas turbine plant, single channel A VR equipment is specified.

6.4.3 The regulator

The A VR is a closed loop controller which uses a signal proportional to the generator terminal voltage and compares it with a steady voltage reference. The difference or error voltage obtained is then used to control the exciter output.

If the load on the generator changes, the generator

524

terminal voltage also changes, increasing the error sig­nal. The error is amplified by the regulator and used to increase or reduce excitation, as necessary, to bring the voltage back to its original value. The need for a rapid, stable response following such changes is of paramount importance and, since control systems us­ing such high steady state gains would rapidly become unstable, special signal conditioning networks are in­cluded. These consist of phase advance and phase lag circuits which have adjustable time constants al­lowing accurate tuning of the voltage response. To­gether, these circuits act as a notched filter, reducing gain at generator electromechanical oscillation frequen­cies, whilst permitting the high gains necessary for accurate voltage control. The setting of the time con­stants is of great importance, as transmission system

· dynamic stability is sensitive to A VR settings. For this reason, sophisticated analytical techniques (see Section 6.7 of this chapter) have been developed and applied in order to obtain optimal performance.

The A VR accepts the generator terminal voltage signal via its own interposing voltage transformer. The voltage signal is then rectified and filtered before

Page 96: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

being compared with the refer~nce voltage. Provision is made for the operator to .change the reference voltage in response to system requirements.

In addition to the basic voltage control require­ment, the A VR includes control loops which perform other vital tasks. These controllers, which include the MVAr limiter and overfluxing limiter, are discussed in detail in Section 6.5 of this chapter.

6.4.4 Auto follow-up circuit With a dual channel design, both regulator channels can be active at the same time, each providing half the total generator excitation requirements. An alter­native arrangement allows for one channel to be active, whilst the other follows passively. Should a channel trip in either scheme, then the other picks up the full excitation requirement of the generator in a 'bumpless' manner. This is achieved using follow-up circuits which track the primary (or active) channel and drive the standby channel output while a dif­ference exists between the two.

6.4.5 Manual follow-up This is similar to the auto follow-up but is used to adjust the manual control system in response to automatic channel changes. In the event of an A VR failure, the manual control takes over in a smooth bumpless manner.

6.4.6 Balance meter

A balance meter is provided in the power station control room and in the A VR cubicle. This monitors the difference between the automatic and manual control output settings. During automatic control, the follow-up circuits ensure this error is minimal, whereas during manual control no such facility exists to adjust the A VR, and a large discrepancy can therefore exist. During manual operation and prior to selection of A V R control, the balance meter is consulted and an adjustment is made so as to avoid large MY Ar dis­turbances following control changeover.

6.4. 7 A VR protection

The A VR plays a vital role in the unit overall pro­tection scheme, as it controls suppression of the gen­erator field after faults. In addition, it is necessary to protect against A VR component failure which would otherwise jeopardise generator operation.

The field suppression circuit accepts signals from the main unit overall protection scheme, in addition to signals from the overvoltage and transformer over­fluxing relays. The circuit switches the A VR thyristor '.:onverters to their inversion mode of operation and "hen trips the excitation.

The overvoltage relay monitors the generator ter-

Excitation

minal voltage and, if it exceeds a safe level (normally 1.3 pu), the thyristor converter is immediately switched into the inverting mode, which reduces the field cur­rent in minimum time. This relay is only active during unsynchronised operation.

The overfluxing relay is also only active during un­synchronised operation, when there is a chance that the generator transformer could be overfluxed if the safe voltage/frequency ratio is exceeded. A special relay detects this condition and initiates an alarm. Control loops within the A VR will act to reduce this to a safe level but, if the condition persists, the thy­ristor converter is switched to the inverting mode and the excitation is tripped.

Most faults within the regulator loop give rise to either an over or under excitation condition. There­fore comparator circuits are used to monitor regulator and converter bridge input and output levels. Alter­natively, a single comparator monitors the thyristor output current and compares it with maximum and minimum field current limits allowed. Transiently, these limits are exceeded during system faults, but the chan­nel is tripped if the condition persists beyond a few seconds.

6.4.,8 Thyristor converter protection In addition to the above, A VR channels are tripped if any of the indicator fuses protecting the converter thyristors rupture. The thyristor converter is further protected by a temperature sensing device which op­erates in the event of excessive heating.

6.4.9 Fuse failure detection unit The regulator relies upon a signal from the generator voltage transformers for its controlling action. Loss of the signal is due in general to failure of the fuses in the voltage transformers. A fuse failure detector unit monitors the input to each channel and compares it with that of a check or reference transformer. If a fuse fails in the voltage transformer supplying the reset voltage, the channel is tripped; a fuse failure in the reference transformer initiates an alarm.

6.4.10 The digital AVR

The rapid development of the microprocessor has brought about the increased use of digital electronic techniques in a number of industrial control appli­cations. While the present generation of solid state A VRs meet all existing CEGB functional requirements, there are advantages to be gained if microprocessor schemes are considered.

High reliability, which has been a feature of pre­sent A VR equipment, can be expected to improve still further due to the reduction in the number of components, since much of the control logic, at pre­sent carried out by electromechanical relays, will be

525

Page 97: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

software specified. Cost advantages are also envisaged as standard memory circuits replace the present cus­tomised printed circuit boards. However, the principal motivation lies in the range of sophisticated control" ler designs that the microprocessor makes physically realisable. One class of controller is the adaptive regulator, which (as the name suggests) is capable of adjusting its structure to take account of changing plant conditions. This type of regulator, shown sche­matically on Fig 6. 72, consists of a recursive real­time parameter estimator (based on a form of least squares structure) which is used to identify the con­trolled plant. The estimated plant model is then used by the regulator to form the control law. A wide choice of regulator I control law designs exists; typical strategies include pole placement and minimum var­iance. Both have a very flexible structure, making it a simple matter to include additional input signals, such as machine accelerating power (which has been demonstrated to enhance transmission system dyna­mic performance), and post-fault recovery.

Chapter 6

6.5 Excitation control In addition to the basic voltage control loop, modern excitation equipment includes a number of additional limiter circuits. These limiters operate as parallel con­trollers, in that their signals replace the generator voltage as the controlled variable whenever those in­put signals exceed predefined limits.

6.5.1 Rotor current limiter All exciters are capable of supplying generator field current well in excess of that required for normal MCR operation. This field forcing capability or mar­gin is necessary during system fault conditions, where the additional reactive power provides the much needed boost of synchronous torque. However, this current must be restricted in duration because of the danger of overheating the generator rotor which would cause insulation system degradation. To prevent overheat­ing, the exciter field current signal is applied to the rotor current limit circuit which detects values of field current in excess of ll007o MCR.

CONVENTIONAL SPEED GOVERNOR

526

GOVERNOR VALVE REF

DIGITAL TO ANALOGUE

CONVERTER

OPTIMAL CONTROL

SIGNAL

TURBINE GENERATOR

GENERATOR OUTPUT

- POWER

1--1-------------VOLTAGE

ANALOGUE TO DIGITAL

CONVERTER

RECURSIVE PARAMETER ESTIMATOR 1----11__,~ COMPARATOH ~1---- REF

~--~----~ ll~------~r ESTIMATED

SYSTEM PARAMETER

CONTROLLER WITH ADAPTIVE

GAINS

FIG. 6.72 Block diagram of adaptive excitation controller

Page 98: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

During system fault conditions, the A VR reacts to boost excitation; normally this situation lasts only milliseconds before circuit-br'eaker operation clears the fault. However, it is necessary to allow for the longest back-up protection clearance times and hence a delay of up to 5 s is specified. After this delay, the rotor current limit circuit generates a signal which opposes that from the A VR and ramps excitation current back to a safe value.

6.5.2 MVAr limiter ~1odern A VR equipment is capable of controlling generator operation at rotor angles of 130° to 140°. This mode of operation is not, however, tenable when transient stability criteria are taken into account; it is therefore customary to limit the generator operation to a rotor angle of 75°.

The permissible leading MY Ar varies with the square of the generator terminal voltage, the limit line being defined by the following equation:

MVAr + MW y 2

VI sin¢ + VI cos¢ v2

The in-phase and quadrature components of stator current are obtained from a form of phase sensitive rectifier. The signals are then compared with the generator terminal voltage bias and, if the limit set­ting is exceeded, an output is generated which acts to boost excitation and reduce rotor angle.

6.5.3 Overfluxing limit

In addition to the overfluxing protection circuit, mod­ern A VR equipment includes overfluxing limiter cir­cuits. This is a closed loop controller which monitors the voltage/frequency ratio during unsynchronised op­eration. Should a predefined ratio be exceeded, the limiter generates a signal which acts to reduce ex­citation and thereby prevent generator transformer overfluxing.

6.5.4 Speed reference controller In accordance with current CEGB functional require­ments, this feature controls the application of excita­tion during the turbine run-up sequence. This limiter unit ensures that voltage is brought up to nominal and the unit synchronised with the minimum delay.

6.6 The power system stabiliser

6.6.1 Basic concepts

Situations have occurred where groups of generators

Excitation

at one end of a transmission line oscillate with respect to those at the other end. These oscillations, known as power system oscillations, are load dependent and, if not prevented, severely limit the MW transfer across the transmission system. To obtain a solution to this problem, an understanding of the basic machine tor­que relationships is necessary.

For a generator to remain in synchronism following system faults, it must produce a braking torque to balance the accelerating torques introduced by changes to the electrical transmission system. The braking tor­que can be separated into two components:

• The synchronous torque, which is in-phase with rotor angle changes and is necessary to ensure res­toration of rotor angle following displacements.

• The damping torque component, which is in-phase with rotor speed changes and provides damping of rotor oscillations.

Where generating units are connected to the grid over high reactance tie lines, fast response excitation sys­tems are vital to maintain system transient stability. This has the effect, however, of reducing the inherent generator damping torque; consequently, under cer­tain load conditions, generator rotor swings following system changes will have little damping.

As the component of torque in question is strongly associated with rotor speed, a logical starting point for investigation is the generator torque speed loop shown in Fig 6. 73 (a).

The introduction of an A VR, while enhancing syn­chronising torque, has a deleterious effect on the small inherent generator damping torque (the latter is ob­tained by means of paleface windings or induced eddy current effects). This presents some difficulty, as from considerations of transient stability a fast response high gain excitation system is necessary, however, its implementation could result in reduced power system damping and a consequential reduction in load trans­fer capability.

To counteract this, a device known as a power system stabiliser (PSS) has been developed. Figure 6. 73 (b) shows the addition of such a device to the torque speed loop. A signal derived (in this case) from shaft speed is used as the input to the stabiliser; this is then processed and conditioned to provide sufficient phase lead to compensate for the phase lags inherent in the generator plant and transmission system. The output of the stabiliser is superimposed onto the A VR demand signal in order that an increased damping torque component is produced.

A comprehensive linearised generator and power sys­tem stabliser representation is shown on Fig 6.73 (c), where it can be seen that the PSS signal is fed to the block denoted as GEP. This represents the generator, exciter and power system, detailed knowledge of which is vital if the PSS is to compensate for the phase

527

Page 99: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

528

t>T s

IWR AND

EXCITER

SYNCHRONISING TORQUE CONTRIBUTION

'-------------- !> E ref

(a)

-CHANGE IN MECHANICAL TORQUE -CHANGE IN DAMPING TORQUE -CHANGE IN SYNCHRONISING TORQUe -GENERA TO"' DAMPING FACTOR -CHANGE IN SPEED

.0,0

COMP PSStn w

0. E ref

SYNCHRONISING TORQUE CONTRIBUTION

' \ T

AVR AND

EXCITER

-CHANGE IN ROTOR ANGLE -COMPARATOR -POWER SYSTEM STABILISER -ABSOLUTE MACHINE SPEED - AVR DEMAND SIGNAL

,~ E ref

(b)

t----'-------------- 1 PSSw(S) h r--- ---, I I I I I I I I I ~ I L __________ -----------------, I I I I I I I I I I I "E, I I I I

L-------~~E~~~~~~~~~~~~~~-------~ (c) COMPREHENSIVE LINEAR I SED

GENERATOR AND POWER SYSTEM STABILISER

'-\ E ref

K1 - f~~~~~T:~R RAE~~~~~gEc1~A~gf6~ ;~~~~RICAL K2- PARAMETER RELATING CHANGE IN ELECTRICAL

TORQUE FOR A CHANGE IN MACHINE FLUX LINKAGE LlEq

K3- IMPEDANCE FACTOR K4- DEMAGNETIZING EFFECT OF A CHANGE IN

ROTOR ANGLE

K5 - ;;~~~J:GEJ~~T~E~~:~zgEci~AR~T~I~ ;~~~~NAL K6 - CHANGE IN TERMINAL VOLTAGE WITH CHANGE

IN MACHINE FLUX LINKAGE t>Eq Tdo- MACHINE FIELD OPEN CIRCUIT TIME CONSTANT EXC(S)- VOLTAGE REGULATOR SYSTEM

FiG. 6.73 Simplified torque-speed loop diagrams

Page 100: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

lag within GEP and produce a component of gen­erator torque in phase with speed changes. This in­formation can be obtained in a variety of ways, nota­bly by on-load frequency response analysis, using pulse injection techniques and by computer simulation tech­niques based on representative system models.

6.6.2 Characteristics of GEP

Extensive system investigations are used to establish the characteristics of GEP. All operating modes of the plant are examined to identify the conditions under which stability is marginal. In general, operation at leading power factor during times of low system demand are the most critical. However, in the case of pumped-storage plant, which will generally be operat­ing in the pumping mode during these periods, the situation can be more critical because of the large machine rotor angle with respect to the rest of the system.

A series of simulation studies is then conducted, using detailed plant representation (including the A VR and PSS), the results being assessed by the analytical techniques described in Section 6. 7 of this chapter. The model PSS settings are adjusted until optimum excitation performance is achieved at all critical op­erating conditions. These settings are then used as a basis for plant commissioning tests, thereby reducing expensive on-site testing.

6.6.3 System modes of oscillation

Examination of the basic torque-speed-angle loop in Fig 6.73 yields W0 (natural frequency of electro­mechanical oscillations) = )(wKie/M) rad/s. For typical values of machine inertia (M) and synchron-

- ising torque coefficients (Kie), the frequency range of interest is 0.2-4.0 Hz. Within this frequency range, the oscillatory modes can be broadly divided into three main components.

Inter-area or inter-tie oscillations

Inter-area oscillations range typically from 0.2-0.6 Hz and occur where two generation groups are connected by a weak tie line; they tend to be power transfer dependent. Inadequate damping of these modes will result in operational difficulties, since power transfer capability is reduced. These low frequency inter-tie oscillations have been initiated by random events oc­curring during periods of high MW transfer over weak transmission links and/or unusual load distribution.

Local mode oscillations

These occur where a single generator is exporting power over a high reactance transmission link. In these situations the need for static thyristor excitation systems (because of transient stability requirements) aggravates the problem of steady state stability which,

Excitation

if uncorrected, will result in prolonged rotor swings in the region of 0.9-1.6 Hz.

Intra-plant modes

Intra-plant modes of oscillation occur between units within the same power station. Unlike the above, these are not power transfer dependent but result from interaction between generator excitation systems. If action is not taken, intra-plant interactions will limit the available PSS gain and hence its effectiveness.

6.6.4 Principles of PSS operation

PSS action is inhibited during steady state trans­mi~sion system conditions, as it has a detrimental effect on voltage control. A steady state voltage offset is prevented by the use of a washout circuit at the PSS input. The washout circuit, shown on the PSS block diagram on Fig 6. 74, is essentially a differen­tiating circuit which attenuates low frequency changes. The time constant of the circuit, Tw, is chosen to washout low frequencies but not to interfere with the signal conditioning networks at system electro­mechanical frequencies.

The signal conditioning network provides the phase compensation, so that a torque is produced in phase with speed changes. This network essentially shapes the PSS characteristic to provide the best damping performance at all electromechanical modes. Generally this is achieved by maximising stabiliser gain (within the constraints imposed by the power system control loop) and shaping the phase characteristic so that it has a slightly lagging value at the particular inter­area oscillation frequencies of concern. To prevent the intra-plant interaction, tuning should ensure that the overall phase characteristic is not greater than 90° lagging at frequencies up to 4.0 Hz.

It is important to emphasise that PSS action is intended to improve the system damping following small disturbances. PSS action following system faults will degrade A VR performance, and hence system recovery; therefore, the stabiliser output is limited, so that A VR action is dominant during the first post­fault cycles.

6.6.5 The choice of stabiliser signal

An obvious choice for the stabiliser input signal is rotor shaft speed, measurements being generally made at the HP turbine pedestal. The drawback with this form of signal is its inherent susceptibility to shaft torsional frequencies. This term refers to the reso­nance conditions on the shaft line which cause one section of shaft to oscillate with respect to another with little natural damping. These frequences act through the PSS and excitation system to set up elec­tromechanical torques which tend to aggravate the situation and, in the extreme, to cause shaft damage. To eliminate this potential problem, detailed infor-

529

Page 101: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

STABILISER LIMITS

L1

STABILISER GAIN

.....____ K

STABILISER OUTPUT ....----

-L2

COMP

ERROR

COMP

SIGNAL CONDUCTIVITY

(1 + T,S) (1 + T,S)

(1 + T,S) (1 + TdS)

AVR;EXCITER/GENERATOR

REFERENCE VOLTAGE

GENERATOR TERMINAL VOLTAGE

Chapter 6

WASHOUT POWER TRANSDUCER

T.s p

--1 + T.s 1 + T

VT CT VT I..A..Lv '-A..Lv GRID

rY""'"V"\

FIG. 6.74 Power system stabiliser - block diagram

mation is required of the shaft torsional conditions so that, if possible, speed probes can be mounted at a torsional node and suitable torsional filtering can be applied.

Because of these considerations, use is made of a signal derived from generator electrical power which is related to shaft speed by the following relationship:

where w is shaft speed change, P m is mechanical input power, P e is machine electrical power and M is the angular momentum. If the mechanical power is assumed to remain constant, Equation (6.1) is sim­plified to:

(6.2)

The major advantage of this form of stabilising signal is its insensitivity to torsional oscillations and the simplicity of measurement. Its adoption, therefore, has both technical and cost advantages.

530

6.7 Excitation svs,tem analysis Trends in modern generator design, with the empha­sis on large thermally-efficient but electrically-remote centres of generation, have combined to reduce trans­mission system stability margins. As a consequence, the primary responsiblity for power system dynamic and transient stability rests with the generator excita­tion system.

Dynamic stability refers to the system performance following small load changes which, under conditions of high MW transfer over long distances, can result in sustained oscillations in the region of 0.5 Hz. If these oscillations are not rapidly attenuated, severe limits will be imposed on transmission system operation.

Transient stability is concerned with the ability of a generator or group of generators to maintain syn­chronous operation following system faults. Under such operating conditions, the generator requires a boost of synchronous torque. This is provided by the transmission system in the form of a synchronous component of the post-fault infeed. However, as the reactance of the transmission line connecting the gen-

Page 102: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

erator to the system increases,, the synchronous tor­que component is reduced. Under these circumstances, the A VR bucks and/ or boosts the generator field current in such a way that the generator itself develops the additional synchronising torque.

A properly tuned A VR therefore performs a vital role in the maintenance of stable system operation under all operating conditions, and this section is concerned with the methods developed and employed to analyse A VR performance, and hence to arrive at tuned settings.

6.7.1 Frequency response analysis

Frequency response analysis is based on the injection of a sinusoidal signal at the input to the A VR and the corresponding measurement of generator terminal voltage magnitude and phase shift. This procedure is repeated over the range of frequencies necessary to identify the plant, which in the case of the generator excitation system is 0.2-4.0 Hz. Results are plotted in the form of inverse Nyquist or Bode diagrams, from which information on system stability and damping can be obtained. These tests can be repeated for a range of A VR settings until an acceptable system response is established. Performance indices used in this form of analysis are system gain and phase mar­gins, both of which are measures of relative stability. In general, a phase margin of 40° or more, and a gain margin of 6 decibels is considered good design practice for most feedback control systems.

An alternative approach is the injection into the A VR summing junction of a short duration rectan­gular pulse. The corresponding machine terminal volt­age response is measured and harmonically analysed by a computer, using a fast Fourier transform pack­age. The results are then plotted in the form of an inverse Nyquist diagram from which measurements can be made of relative stability and damping. This approach has a number of distinct advantages, par­ticularly during on-load testing as, unlike variable frequency techniques, pulse injection testing can be undertaken without the risk of exciting power system oscillations.

6.7.2 State variable analysis

l." A common method used to assess the performance I and stability of feedback control systems is to track

the path taken by the roots or poles of the closed

I loop transfer function. Changes in system parameters, such as gain and time constants, cause these poles to move. The path taken by the poles in response to control system changes can be plotted and are

I known as a root locus. Referring to Fig 6.75 any , roots appearing on the right hand side of the S-plane

imply an unstable system. Roots on the real axis in-

1 dicate an exponential or overdamped response, and

~ mo" containing an imaginacy component imply an

Excitation

oscillatory response. It is possible to simplify the interpretation of the root locus diagram by consider­ing those poles which lie furthest to the right as dominating the system response.

This approach is extended to the multivariable situ­ation by making use of modern state variable theory. The system considered is first linearised about the operating point of interest and the equations of state formed.

X

y

AX+ CV

DX + FV

Input equation

Output equation

where X is the vector of state variables, Y is the vector of output variables, A is the state matrix and C,D,F are the feedback, input and output matrices, respectively.

A series of simulations is conducted over the com­plete generator operating regime, using a detailed model of the turbine-generator and excitation sys­tem. The dominant poles (or equation solutions) are plotted for a range of control settings, and those iden­tified as providing optimal damping at the most critical operating condition are selected for commissioning purposes. This method of analysis therefore provides advanced information regarding equipment settings and plant performance, thus reducing expensive com­missioning time.

6.7.3 Large signal performance investigations

The foregoing methods are based on the response of the excitation system to small signals; hence non­linearities can be ignored and the system assumed to be linear.

It is equally important, however, to investigate the performance of the turbine-generator plant following substantial changes in operating conditions. In these situations the non-linear characteristics of the plant must be taken into account to obtain realistic results. These large signal performance investigations pro­vide a means of evaluating excitation system response foll9wing a major transmission system disruption (gen­erally a three-phase fault at the generator transformer high voltage terminals is used for standard studies and investigations), which could jeopardise system transient stability.

Transient stability analysis is primarily concerned with the effect of transmission line faults on genera­tor synchronism. While certain simplistic approaches exist dealing with the case of a single machine operating onto an infinite bus (such as the equal area stability criteria), a full multi-machine solution is generally necessary requiring the use of digital computer simula­tion techniques. These simulation packages represent in detail the generator, transmission and excitation systems, and solve the governing non-linear differen­tial equations by numerical integration.

531

Page 103: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

FORM OF TIME-DOMAIN RESPONSE

MAGNrTUDE

~ X

LOCATION OF EIGENVALUE OR ROOT IN S-PLANE

MAGNrTUDE

I~ TIME

-6 -4

STABLE

Chapter 6

jW UNSTABLE

MAGNITUDE

~ I 15

~ ~-V--VTJMJ

X X

MAGNITUDE J__..-/ TIME

-2

FIG. 6.75 S-plane showing possible root locations with corresponding time response

The ability to simulate these situations is essential to the CEGB, because generator excitation system performance under system fault conditions cannot be demonstrated by test methods, due to the potential risk to system stability.

7 Generator operation In this section, the operation of the generator under all common conditions is considered. Electrical and other parameters are introduced as necessary in order to describe the condition.

7.1 Running-up to speed Before running-up to speed, the casing and other components will have been scavenged of air and filled with hydrogen to a pressure approaching the rated. Hydrogen pressure increases with increasing tempera­ture and the objective is to achieve rated pressure when on steady load. The seal oil system must be operating in order to contain the hydrogen. The stator winding water system is established, taking care that

532

the windings are not ~older than their ambient hy­drogen. Cooling water to the hydrogen, distilled water, winding water, seal oil and excitation heat exchangers is established. The lubricating oil system (common with the turbine) must also be operating, and also the jacking oil system if the shaft is at standstill.

The run-up cycle is primarily determined by the requirements of the steam turbine, and may be under the control of an automatic run-up system. It is ad­visable to pass through the first and second critical speeds of the generator rotor (roughly, 800 and 2200 r/min) quickly to avoid subjecting the bearings to the increased vibration amplitudes which may occur at these speeds (see Fig 6.27).

As the rated speed is approached, excitation may be automatically applied by the voltage regulator (or this may be manually applied) by closing the exciter and main field switches. The resulting voltage will be pre­vented, by a voltage/frequency control device, from being greater than would maintain rated voltage/fre­quency, so as to prevent overfluxing of the generator transformer. At rated speed, rated voltage should be generated, with the machine on open-circuit, unless some other voltage condition is required. Speed is under the control of the turbine governor. Vibration

Page 104: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

levels are monitored at all the qearing housings and at the shafts adjacent to the genen;ttor bearings during run-up.

7.2 Open-circuit conditions and synchronising Generators are usually operated at or near their rated voltage, any departure demanded by the transmission system being accommodated by the transformer tap­changer. A generator voltage range of ± 5% is speci­fied. For the same MV A output, a higher voltage results in greater losses and temperatures in the core but lower current in the stator winding, so the overall thermal conditions are not much changed.

Since these large generators are invariably connected to the grid through generator transformers, the rated voltage of the generator can be determined by the manufacturer to give the most economic design. Once

, the first of a new rating has been decided, a degree of standardisation is imposed to allow generator trans­former units to be made interchangeable, 22 kV being standard for 500 MW units and 23.5 kV for 660 MW units, on the CEGB's system.

The electrical phasor diagram for this excited, open­circuit condition is shown in Fig 6.7, though, at this stage, the machine is not running synchronously with :he transmission system.

The open-circuit characteristic will have been es­tablished during running tests in the manufacturer's ·vorks. The rotor currents for several values of stator mltage are measured and plotted (Fig 6. 76). The relationship is virtually linear (the airgap line) up to about 75o/o rated voltage, demonstrating that the air­~ap reluctance is constant, whereas the iron circuits Jepart markedly from constant reluctance as the flux density increases above the point at which saturation tarts to occur. After ·a long shutdown, it is reas­uring to check a few points on the open-circuit

characteristic with the unit on manual excitation. Note 'hat direct measurement of rotor current is not possi­Jle on brushless machines.

Synchronising is effected either manually or by means of an automatic synchroniser. The speed of he unit is adjusted by controlling the speed governor

.mtil the generated frequency closely matches the system frequency. The generator voltage is adjusted · y the setpoint of the voltage regulator until it closely quais the voltage of the system, as monitored by a

voltage transformer with the same ratio as the "enerator transformer, or directly where a low volt­ge switch is used. The main circuit-breaker is closed

when the two voltage phasors are almost coincident, and the generator will then pull into and remain in ynchronism with the system. If the voltage phasors ·ere significantly different in magnitude or angular

position when. the circuit-breaker is closed, the dif-

Generator operation

STATOR VOLTAGE %

FULL LOAD

CURRENT 0 L-------------~------------------~-

ROTOR CURRENT

FIG. 6.76 Open-circuit characteri.ltics

ference voltage would cause a large current to circulate from the system through the stator windings, causing high forces in the windings. If the frequencies were significantly different, the sudden pulling into syn­chronism would impose a large torque on the rotors. A back-up check synchronising device inhibits the circuit-breaker from closing if the voltages, angular positions and speeds do not match within predeter­mined tolerances.

Once synchronised, the speed is effectively con­trolled by the transmission system and the steam ad­mitted to the turbine produces just sufficient power to overcome the mechanical and magnetisation losses.

7.3 The application of load If the voltages and angular positions match exactly, no current flows in the windings and no electrical torque is produced. In order to generate load, an imbalance in the phasors must be created.

The turbine steam inlet valves are therefore gradu­ally opened further; the extra torque thus produced starts to accelerate the rotors so that they move for­ward relative to their no-load (direct axis) position, though still in synchronism with the system. The volt­age phasor difference created by this angular change results in current circulating from the system through the stator windings, producing an electrical torque which balances the increased mechanical torque, re-

533

Page 105: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

suiting in a new state of synchronous equilibrium at a 'load angle' (see also' Section 2.6 of this chapter).

Because the generatea voltage effectively depends on the system voltage and the load being generated, action by the voltage regulator cannot change the generated voltage directly. However, if the rotor cur­rent is changed, the phase relation between the gen­erated voltage and current is changed, and the required power factor can be maintained by voltage regulator action. These processes of control of generated load and power factor continue to meet the requirements of the transmission system, as long as the unit remains synchronised. Phasor diagrams for various on-load conditions are shown in Figs 6.8 and 6.9.

7.4 Steady state stability The power produced by a synchronised generator can be expressed as (VE sin b)/(Xd). For a given machine, operating at a terminal voltage V, the synchronous reactance Xd is a constant parameter, and if the 'internal voltage' E, or rotor current, is kept constant, power varies as sin b. At rated conditions, b is about 45-55°.

From this position, a sudden increase in steam throughput, or (more likely) a sudden demand for more power into the system, perhaps because of a fault on the lines, results in an increase in b and in generated power until a new equilibrium position is reached (Fig. 6.77 (a)).

This is valid if o is less than 90° before the sudden change. Once b is greater than 90°, a demand for more power cannot be met by an increase in load angle, and the generator rotors cannot attain a posi­tion of equilibrium (Fig 6.77 (b)). The rotor then accelerates to just above synchronous speed and op­erates in a non-synchronous mode ('pole slipping'), with large power and voltage oscillations which are unacceptable to either the transmission system or the boiler controls. The situation may be retrievable if the voltage regulator can initiate a rapid increase in the field current, increasing E in the equation, to prevent instability (Fig 6. 77 (c)).

Load angles approaching 90° are associated with operation at leading power factor, which is not a normal requirement in the UK. However, studies of the transmission system under all credible conditions of loading, line outages and faults are carried out to ensure that the system will not fall into instability, and the required values of synchronous reactance and excitation response are based on these studie~, which may recommend different values in different locations. In practice, because of magnetic saturation, Xd is reduced as the load angle moves towards 90°, the 'quadrature axis' position, so that the limiting condition is ameliorated slightly. Values for CEGB machines are about 1.8 per unit, falling to 1. 7 per

534

ROTOR ANGLE &

(a) Illustrating stable equrilbnum

51 90'

ROTOR ANGLE &

(b) lllustratrng mstabilrtv

ROTOR ANGLE S

(c) Marntaming stabrrily b; ,, , •eas:ng excrtation

FIG. 6.77 Steady state stability

unit in the quadrature axis.

Chapter 6

180'

Operation at leading power factors requires re­duced rotor current. Operation with zero rotor current, at zero MW, and a leading reactive output = Rated

•\

Page 106: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

MYA/Xd (or strictly Rated MV.A/Xq where Xq is ~he quadrature axis synchronous rea,ctance), determines the theoretical limit of stability. The practical values of leading reactive outputs, allowing a margin for overshoot, with different types of excitation control (see Section 5 of this chapter), can be plotted on a MW -MV Ar diagram. The example shown in Fig 6. 78 allows for instantaneous increases in MW of 40Jo at rated load and I OOJo at zero load.

7.5 Capability chart The capability chart is a MW-MYAr diagram, for which the limits of leading MV Ar were discussed above.

A constant MW limit can be drawn at the rated power output of the turbine, though the maximum power capability of the steam system may be signi­ficantly greater than this. The circular locus of rated stator current cuts the rated MW line at the rated MY A and power factor point, but does not in prac­tice impose a limit. The rated rotor current, also a circular locus but with its origin at the 0 MW, Rated MY A/Xq MY Ar point, imposes a limit at con­ditions of MW and lagging power factor both lower than rated. Such a capability chart is used as the

104%MW

THEORETICAL STABILITY

LIMIT

PRACTICAL STABILITY

LIMIT

0

Generator operation

scale of a vector meter, across which cursors travel parallel to the axes, representing generated MW and MVAr, the operating point being where the cursors intersect. Permissible operating areas are indicated on the instrument.

It can be seen that the capability chart is another manifestation of the generator phasor diagram. Op­eration at rated load and about 0.95 power factor leading is possible, though rarely required.

7.6 Steady short-circuit conditions, short­circuit ratio Another relationship that is established during works testing, is between the field current and the stator current with the three stator line terminals short­circuited (Fig 6. 79). In this condition, the voltage re­quired to circulate, say, rated current through the wind­ings is very low ( = xe, say 0.15 per unit) and there­fore the flux is also very low and conditions are lin­ear, since there is no magnetic saturation. Most of the considerable magneto motive force (MMF) produced by the rotor is required to counteract the armature reaction MMF produced by the stator winding.

Running under these conditions in order to cir­culate current through the windings to dry out the

RATED STATOR C\,IRRENT

LAGGING

RATED CONDITIONS

RATED ROTOR _.- CURRENT

-------RANGE OF MVAR FOR SYNCHRONOUS COMPENSATION ----~1

MVAR

FIG. 6.78 Capability chart

535

Page 107: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

STATOR VOLTAGE

%

OPEN CIRCUIT

ROTOR CURRENT

FIG. 6. 79 Open- and short-circuit characteristics

STATOR CURRENT

%

insulation is not a normal requirement for these large generators. It may, however, be necessary to demon­strate the capability of the connections between gen­erator and transformer, in which case the short­circuit would be applied at the transformer terminals. Manual control of excitation is essential.

The open- and short-circuit characteristics enable certain parameters to be established. Short-circuit ra­tio (SCR)

Rotor current for rated voltage on open-circuit

Rotor current for rated current on short-circuit

Ifo

Ifs

This rough measure of steady state stability is nearly the reciprocal of Xd; minimum values of 0.4 and 0.5 are specified for the 500 and 660 MW units, re­spectively.

Synchronous reactance Xd may be quoted as the reciprocal of short-circuit ratio, in which case it is the value corresponding to the degree of saturation at rated voltage on open-circuit (which is not the same as that at rated load). It is of interest when discussing operation close to the stability limit, in which case its unsaturated value is appropriate and given by:

536

Rotor current for rated current on short-circuit

Rotor current for rated voltage on airgap line

Ifs

Ifg

Chapter 6}i

(Note that different considerations apply to a salient·!. ·f

pole machine, where the geometry of the magnetic.:) paths is very different when operating near the quad"'j rature axis from that in the direct axis, and Xd and i Xq have dissimilar values.) .t,

):r ,;;

7. 7 Synchronous compensation While operation in this mode is not foreseen fod generators of this rating in the UK, a note here isl included for completeness. A generator, synchronised~ to the system, may be used to generate or absorb! reactive MV A, while drawing its loss power from the; system. By varying its cxcit<ttion, it can be operated:~ over the range shown on Fig 6.78, to meet the re-·{ quirements of the system. It is not normally possible~ to drive the turbine at rated speed with no steam flow, ; and smaller generators operated in this way are de­coupled from their turbines. At large values of leadingj~ reactive generation, stator core end temperatures may;i be high, because the axial components of MMF from~ both stator and rotor windings become more in phase,:~ resulting in higher values of axial leakage flux. '~

·~ :jl

~~ 7.8 Losses, efficiency and temperature ~ Many separate components of loss can be identified,~ some of which are substantially constant irrespective of load; others can, for simplicity, be assumed ro: vary approximately as (stator current)2 • These com­ponents are listed below, with kW values given for a typical 660 MW generator at rated conditions:

Constant losses Coolant loss, fl kW~

Fan loss Hydrogen 600 ~ Rotor windage loss Hydrogen 350 ~ ;1

Other windage loss Hydrogen 150 ~ ~

Open-circuit core (iron) loss Hydrogen 950 j Bearing loss Lub oil 600 .~

Shaft seal loss Seal oil 100 ~ !J

Rotating exciter constant loss Exciter air 100 ~ Auxiliary system losses, e.g., motors 100

!'l

Variable losses Coolant loss, kW

Stator copper loss Stator winding water 1600 Eddy current loss in

windings Stator winding water 600 1 Additional core loss,

due to higher flux and end loss

Loss in core end plates and frame

Loss in rotor surface

Rotor copper loss

Variable excitation loss

Hydrogen

Hydrogen

Exciter air

1600

2400 ~ i

!50 'i

~ ~ ~ ' 1:

Page 108: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The total loss is typically 9300 kW, and the effi­ciency is 98.60Jo. The efficiency is slightly higher at about 80% than at 1000Jo MW load, and also im­proves as the power factor increases towards unity.

' The losses shown in the list are removed by the var­ious cooling systems described in Section 5 of this chapter. The total loss removed by each system is r therefore known, and the tlow rates are designed to

!; maintain an appropriate temperature. In the hydro­gen system, 30 m3 Is of hydrogen is circulated, being cooled to about 40°C by the heat exchangers, and reaching about 65°C on entry to the coolers. The stator core will attain about 75°C, except at the ends, which are likely to be hot, but within the BS limit of 120°C. The rotor winding will reach an average temperature of 105°C with local hot spots perhaps 20°C higher than this, which poses insignificant ther­mal stresses on the insulation and creep conditions on the copper and aluminium components.

In the stator winding water system, conditions differ j' · between single and double pass arrangements, but t'" with inlet water cooled to 40°C, the outlet water will

';•,1 not exceed 70°C. Hence the winding copper will bare­

ly exceed 70°C, and then only at the water outlet ~; end, and the winding insulation will nowhere exceed ~H " 100°C. CEGB specifies Class F insulation with Class

B rises, which are very comfortably met in these , ,., designs.

A considerable advantage of water cooled windings is that the temperatures are inherently constrained to be very low, thus maximising the intrinsic life of the insulation. Also, since the temperature rises of the

"' core and windings are similar, problems associated with differential thermal expansion are minimised,

;·,;; and it has not been found necessary to incorporate ~{; features in the end windings to accommodate axial

ii~~ "·[:

~:~ J;~·t

"t'

~;'~ e

1.:~~ ~~~

f1 ~ Jf ~~;

movement.

7.9 Electrically ·unbalanced conditions The amplitudes and phase displacements of the three­phase voltages and currents in the transmission system are usually symmetrical to within about 1 OJo, which does not impose any significant difficulties in the generator. However, it is possible for much larger unbalances to exist, for example, if one phase of a circuit-breaker remains closed while the others are open for considerable lengths of time, then the ability of the generator to withstand such conditions must be established.

The well known method of resolution of unbal-• • anced phasors into systems of symmetrical components '"· is used in the analysis shown in Fig 6.80. Because

generators are invariably connected to transformers whose LV windings are arranged in delta, which there-

i,. fore do not have a neutral connection, zero sequence voltages and currents cannot exist. The only campo-

Generator operation

nents of concern are the negative sequence components. In order to circulate negative sequence currents

thr,ough the generator stator and transformer wind­ings, a system of negative sequence voltages must be produced by negative sequence flux, i.e., flux rotating at synchronous speed but in the opposite direction of rotation to the main flux. This cuts the rotor at twice the rotational speed, and induces a 100 Hz voltage in the rotor surface. 100 Hz current flows in the outside 'skin' of the rotor body, in the wedges and in the top winding conductors, as if these components were part of the squirrel cage of an induction motor. Additional heating therefore occurs in these regions; in particular, in positions where current transfers from one component to another, such as at the wedge ends, and at the endring shrink face-..

Because of the potentially damaging effect of this extra heating, limits on the extent of unbalance have to be established. These are conservatively set to ini­tiate alarms when the negative sequence component exceeds 50Jo of the rated current and to trip at above IOOJo. The component is detected by a three-phase cir­cuit designed to respond to negative sequence current.

In some designs, copper shims are placed in the ends of the rotor slots, below the wedges, and extend­ing outboard of the rotor body to form a continuous ring, in order to assist circumferential current flow and to minimise the small intense hot spots where current transfer is concentrated. Where circumfer­ential slots are cut into the pole faces (Section 3 of this chapter), means for transferring surface current across the slots are provided, usually in the form of copper strips retained by wedges in shallow 'pole face slots', to avoid overheating at positions of current concentration. ,

The shallow surface current paths must also handle the very much larger, short duration currents imposed by unbalanced conditions during transient faults. A rough criterion of acceptability is provided by assuming that the heating is proportional to L:(I 2)2t, where 12 is the negative sequence stator current (per unit) and t the time (in seconds) for which the condition persists. This is only approximately valid for times short enough for heat dissipation to be ignored. Per­missible values of (I 2)2t of about 3 are usual for 500/660 MW generators, and 'instantaneous' trip­ping is initiated if this value is exceeded (see Fig 6.81).

The surface current paths are also involved in any condition in which the generator is connected to the system but is not operating synchronously. This may happen on total or partial loss of excitation, and can usually be tolerated by the generator for a short time, although slip frequency surges will occur on the system. Because the induced currents are at slip frequency, they are able to penetrate further into the rotor, wedges and winding, and the thermal conditions are not as critical as with the 100 Hz currents pro­duced by unbalanced operation.

537

('

Page 109: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

1/ao

Va

Vb

Vc+

V Vc

Vco

Vc-

UNBALANCED VOLTAGE SET

AN UNBALANCED VOLTAGE SET CAN BE RESOLVED INTO THE FOLLOWING:

Va+

Vb-

Va-

VC+ Vb+

(a) Balanced pos1t1ve-sequence components

(b) Balanced negattve-sequence components

(C) Zero~sequence cornponents (nurrnally negligible)

FIG. 6.80 Unbalanced phase conditions

7.10 Transient conditions Changes in the load demand, system operation con­ditions and the response of other generating units, mean that conditions at the unit transformer terminals are constantly changing. Increase in overall demand causes a fall in frequency to which the speed gover­nors of all the connected turbines respond. Their rate of response depends on the settings of the individual governors, some units being deliberately arranged to act more responsively than others.

A highly responsive unit varies its steam inlet valve position frequently, causing the steam throughput to change and altering the torque equilibrium. The ro­tors move forward or backward relative to their pre-

538

vious positiOn, i.e., o changes, so that the electrical power generated changes to restore equilibrium. The combined effect of similar load changes occurring in many units acts to restore the system frequency to its original value.

Coincident with the change of load will be a change in system voltage, which causes the voltage regulator to adjust the excitation to restore the original voltage value. (A large voltage change may require a trans­former tapchanging operation to maintain the gen­erator terminal voltage near its rated value.)

Flux cannot change in the machine instantaneously, and the rate-of-change is influenced by the transient reactance Xd, . This depends largely on the flux paths

Page 110: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Generator operation

t-------------------------------------------

I PeRMISSIBLE FAULT CURRENT

LMES MCR CURRENT

3 2 I I

I I

-- -t----

\ I

I. I'

\

I 1\ \

I I,

\ \

li _\

-~ ~ 1\

I I ~ i i I I

I I

I - f---I i

I

I I

I

I

""' --

~HASE-TO-PHASE FAULT CURRENT

.......... r-_ r--"'-... PHASE TO-EARTH FAULT --r--- ~ECREASING 30% CONTiNUOUSLY r--....._ , CURRENT r--

---r-- DECtAS!N~ 17 J•;J CONTtUOUS~ y --r-- -

10 20

I 30 40 so

TIME-S

60 70 80 90 100

FIG. 6.81 Duration oLfault currents

I ~bracing the stator winding slots, the airgap and

I~ rotor slots, with a small component associated .th the end windings, and is affected by the degree f magnetic saturation. The normal value for un-

11, urated transient reactance is of the order of 0.3 ~~ · unit.

It is this reactance which controls the initial rise­l1' voltage when load is suddenly tripped off; typi­.•- ly the voltage rises instantaneously to 1.3 per unit

td finally reaches a value determined by the pre­iling value of rotor current. Also, transient reactance Jsed in calculations involving the stability of the t with the system during a transient fault situation.

ch studies require accurate representation of gen­~or parameters, and in this context it is important t its specified value has been met (see Fig 6.82).

During conditions of massive change, such as those Jt occur during a close-up fault, when the terminal

age may be suddenly reduced to half its rated Je (or e\en to zero for a fault at the generator or nsf'-1rmer low voltage connections), the \·ery rapid

change of flux induces currents in the rotor surface paths, and for the first few cycles, say up to 200 ms, conditions depend more on a reactance linking these surface flux paths with the stator winding. This is referred to as the sub-transient reactance, Xct", with a value of about 0.2 per unit. It is this reactance which limits the current in the first few peaks after a fault. For a three-phase fault at the generator terminals from rated voltage open-circuit, the RMS value of the initial current peak will be V !Xct", i.e., 1/(0.2) = 5 per unit.

The peak value is .J2 times this, and, if the par­ticular phase experiences full asymmetry (depending on the instant at which the fault occurred), it is pos­sible for the first peak to reach 2.J2 x 5 = 14.14 times rated current. In practice, flux decay results in the maximum current being about 9007o of this value, but if the short-circuit is applied from a condition of load, i.e., with increased flux and a highe~ 'internal' voltage, the peak current could be greater.

Such peaks of current result in enormo:.~s forces on the stator windings in the slots and end \\in dings

539

!'

Page 111: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

INSTANTANEOUS RISE

100 +-------,,_----------l---------- _______ ...

VOLTAGE %

ROTOR CURRENT FOR RATED LOAD

L----~~-------~~----------------~------------ROTOR CURRENT TIME

OPEN"CIRCUIT CHARACTERISTIC ASSUMES NO VOLTAGE REGULATOR ACTION

FIG. 6.82 Voltage rise on rated load throw-off

(since force varies as current squared), and in the connections, which would result in considerable move­ment if the components were not adequately sup­ported to resist them. It is therefore vital to establish the value of sub-transient reactance. (It should be noted that the thermal effects are not troublesome because of the rapid rate-of-decay of current.)

Another reason is to ensure that the main circuit­breaker (and low voltage switch, if fitted) is able to withstand these very large through-currents and that it can, if necessary, break them although, in practice, it rarely breaks on the first peak of current.

To measure the transient and sub-transient re­actances and their associated time constants, a three­phase short-circuit is suddenly applied to the prototype generator running at speed during the in-works tests, while excited to one or more agreed voltage values, and the resulting three-phase currents recorded. Figure 6.83 shows a typical trace and how the Xct' and Xct" values are deduced, while Fig 6.84 shows how the reactances vary with initial voltage due to saturation.

A generator terminal fault, though physically vir­tually impossible, imposes the most severe of the three-phase conditions, with the effective voltage 1.0 per unit, or higher. More likely is a fault on the system which, because of the interposed reactance of the generator transformer, imposes short-circuit currents similar to those from a terminal fault at a voltage equal to Xct II /(Xct II + Xe), where Xe is the reactance of the transformer and that part of the system between it and the fault.

A type of fault more likely to occur, particularly inside the generator, is one involving a short-circuit

540

between two phases. Here, the phasors become highly unbalanced, and the 'negative sequence reactance', X 2 , helps to determine the peak current, which may attain a maximum of 2v'2 x v'3(V /Xct" + X 2) which is of a similar magnitude to that in the three-phase case.

In a line to earth fault, the 'zero sequence reactance', X 0 , is involved, and the peak current may be 2v'2 X

v'3 (V /Xct" + X 2 + Xp) usually considerably lower than the three-phase value, depending very much on the neutral earthing arrangement.

Works tests for X2 and X 0 are not normally carried out, even on prototype designs, since X 2 is easily derived from the positive sequence reactances, and the value of X 0 is not as critical as the others.

Another factor involved in transient stability repre­sentations is the inertia of the rotating masses, usually quoted as the 'inertia constant' H, with units of MW seconds/MY A (or simply seconds). For these ratings, H will be of the order of 3.0, of which the generator contributes only about 0.8. The higher the inertia, the longer the time taken to accelerate the rotors into instability, allowing more time for corrective action and hence a bigger margin.

7.11 Neutral earthing The neutral ends of the three phases of the stator wind­ing are connected together, outside the casing, by the 'star-bar', which may be located underneath the cas­ing alongside the line connections, or above it in a special enclosure. The star point is connected to earth

Page 112: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

I I

10

'/A LUES OF STATOR f-'UL.l. LOAD

CURRENT AND ROTOR 7 I NO-LOAD CURRENT

I

3-P~ASE SHORT-CIRCUIT CURRENT WAVES

2 4 6 8 10 INSTANT OF

40 50 1 00 200 300

I I I

Sf-IORT CIRCUIT

STAfOR AND ROTOR SHORT-CIRCUIT CHARACTERISTICS WITH 1 00'1c ASYMMETRY

I·1c •. (J.83 Three-phase short-circuit current characteristics

EACTANCE

I I I I I I I·

30

20

10

SUB-TRANSIENT REACTANCE

50

INITIAL VOLTAGE ••,

F:G. 6.84 Transient and sub-transient reactances

100

Mechanical considerations

through a neutral earthing device, designed to limit the fault current in the event of a stator winding fault to earth.

The neutral earthing device of earlier generators consisted of a water resistor, designed to limit the cur­rent 1n a llne to earth fault to a maximum of 300 A. More recent machines use a small si:-.,:ie-p~ase d:s­tribution type transformer with its pr::~~::~:- -:-onne;:ted between the generator star point anc ~3.~::1. and its secondary loaded onto a resistor. Th;, arrangement limits the fault current to about 15 :\. and \\as ori­ginally intended to allow an internal fault to be sus­tained while load was reduced, rather than requiring an instantaneous trip. Modern practice is to trip in­stantaneously on fault detection, even \\ ith this form of earthing. In both cases the sensitivity of protection is such that a fault at less than 1 007o from the neutral point is not detectable, and could persist, though the low voltage to earth in this part of the winding makes fault initiation less likely and fault current compara­tively low.

7.12 Shutting down The process of load reduction is the reverse of that for load increase except that, when the load has reached a low value, the main circuit-breaker (or the LV switch, if fitted) is opened, and with it the turbine steam valve and the excitation crcuit-breakers. The unit runs down in a time determined by the inertia of the rotors and the windage and friction losses. At some stage, the motor-driven lub,rication pump is switched in to take over from the shaft-driven pump. The turbine must usually be barred for some hours on shutdown, and lubricating oil must be maintained to all the bearings during this process.

It is usual to leave the hydrogen in the generator casing, unless a prolonged shutdown is envisaged or access to the casing is required in order to avoid wastage of gas. The pressure will fall as the tem­perature drops, but it is not usual for the pressure to be maintained exactly at rated value, nor for water to be circulated in the coolers and windings. It is essential that the shaft seals are supplied with oil both during barring and when ~tationary, to prevent hydrogen leak­age, and, because of the possibility of moisture ingress from the seal oil, the blower may be run in order to circulate hydrogen through the dryer.

8 Mechanical considerations Some aspects of torque, stresses, vibration. etc., were mentioned in Sections 3 and 4 of this chapter, and these and other mechanical aspects are considered in more detail in this section.

541

Page 113: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

8.1 Rotor torque At a constant load (eiectrical output and generator losses) of P kW, the tor'que (Nm) experienced at the turbine-generator coupling is 9545P divided by (r/min). The coupling must be capable of transmitting the torque associated with rated output continuously with­out deformation. These couplings commonly have four of their bolts closely fitted into both coupling flanges, while the other bolts have smaller diameter and a clearance in the coupling holes. The torque is transmitted partly through the fitted bolts and partly through friction between the flange faces. The full torque must also be transmitted through the shaft end at the turbine end, which must therefore be de­signed to withstand it.

In the very much larger section of the rotor body, shear stress due to torque is very much less than in the shaft ends and is not of significant magnitude. Also, the transmitted torque reduces in a linear man­ner along the length of the rotor body, so that at the exciter end, only the small torque required to drive the rotating exciters (and any other coupled equip­ment) has to be transmitted.

As noted previously, during electrical faults, stator currents of many times rated value occur, and these cause electromagnetic torques of a similar magnitude. The torque reaction at the turbine to generator cou­pling and in the associated shafts depends, among other things, on the ratio of inertias of the turbine and generator rotors, but can also be several times rated torque. The specification requires that the shaft and coupling shall be designed to withstand stipulated fault conditions, without failure, though not neces­sarily without permanent distortion of components such as coupling bolts. It is not unknown for the fitted coupling bolts to exhibit distortion after a severe electrical fault.

Materials subjected to repeated high stresses ex­hibit a lifetime, during which damage is accumulated, and at the end of which failure occurs fairly rapidly. Much effort has been devoted to establishing models of turbine-generator shaft systems in order to be able to predict their remaining 'life' (i.e., ability to with­stand further faults), knowing the history of the faults to which they have already been subjected. This has been done analytically, knowing the torsional char­acteristics of the rotor system, and computing the shaft torques due to postulated electrical transients. It was found that in the case of rapid reclosure of a circuit-breaker following clearance of a faulty line, the magnitude of the peak of torque depends very critically on the timing of the instant of reclosure.

This has also been demonstrated, during transient conditions, using values of stress obtained from strain gauges fixed to the shafts. Devices which calculate shaft torques from electrical inputs have also been used.

It is difficult to relate measured or calculated torque peaks accurately to damage caused, or to remaining

542

Chapter 6

life. Results from models do not scale accurately and at the most extreme (and therefore most damaging) stress, the highly non-linear effects of material damp­ing must be considered.

In the UK, where high speed reclosure is not prac­tised, sub-synchronous resonance due to the use of series capacitors is not a problem and the operation of the transmission system is under close control, it is thought that the combination of very high stresses and very low probability of occurrence results in an acceptable risk for rotors designed to conventional specifications, and that lifetime monitoring is not justified.

The exercise has highlighted the need to avoid stress raisers such as unnecessarily small radii, and to ensure a high quality surface finish. It has also drawn attention to the need to design the generator to ex­citer coupling to withstand torques of the order of the rated generator torque, since it has been shown that these can exist during transient conditions.

The requirement for torque transmission places a limit on the minimum diameter of the shaft and therefore of the journal. An acceptable compromise between the higher loss associated with a large diameter and adequate hydrodynamic stability results in a bearing somewhat shorter than its diameter for these ratings. Bearing performance is described in Chapter 1.

8.2 Stress due to centrifugal force All rotating components are subjected to stresses due to centrifugal forces, and are designed so that the yield stress of the material exceeds the stress at over­speed by an adequate saf,ety factor. Usually the com­ponents closest to the limit are the rotor teeth, rotor wedges, end rings and outermost winding conductors.

The tensile stress in the rotor teeth was considered as part of the rotor optimisation in Section 3 of this chapter. It is greatest at the tooth root, but will have local concentrations at the wedge dovetail. There will also be a high local stress where the wedge transfers the centrifugal force (CF) load of the slot into the tooth. Detailed finite element analysis is carried out to ensure that unacceptable stress concentrations are avoided. These stresses are constant at constant speed, so that the only cyclic factor is the number of stop­start cycles, which is relatively few ( < 104 ) over the lifetime of the machine. Thus crack propagation by high cycle fatigue from this mechanism alone is not of concern.

Similar considerations apply to the slot wedges, in which the loading pattern is similar to that in a short beam in bending, uniformly loaded on its underside, and with built-in ends. Aluminium alloy wedges are commonly made from extruded sections, but have the outermost layer (1 mm, or so) machined away where stresses are high, so that the properties of the parent metal are fully realised. It would be necessary

I , I

Page 114: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

to take the creep behaviour of, aluminium into con­sideration at temperatures in e~cess of 100°C, but it is not usual for wedge temperatures to exceed this value (see Fig 6. 85).

Pole face wedges are much less stressed, and are commonly made of steel.

The most inboard of the field lead wedges may be unusually highly stressed because of the extra CF loading imposed on it by the section of connector leading into the winding.

The shrink-fits of the end ring onto its seatings on the rotor body and end disc reduce as speed increases, and are greatest at standstill. There are therefore large circumferential strains at the ends of the rings, and correspondingly high stresses, at stand­still. As speed increases, the centrifugal force of the rotor end windings imposes a load and stress in the central part of the ring, which combine with the

Mechanical considerations

rotational hoop stress due to the rotation of the ring. At rated speed and overspeed, the stress at the shrink-fits may be less than that in the centre. There is also an axial stress due to the higher thermal expansion of the copper in the end winding relative to that of the steel ring. As noted in Section 3.3 of this chapter, direct contact of the end disc onto the shaft is not normal, since the flexure of the shaft would transmit a small alternating stress onto the highly stressed ring which could promote crack pro­pagation by high cycle fatigue. Again, it is important that the stresses under all conditions are analysed in detail, and this may necessitate a three-dimensional finite element computation in order to ensure free­dom from high stress concentrations, particularly at the sudden changes of section involved (see Fig 6.86). In the rotor conductor nearest the wedge, it is the compressive stress produced by the centrifugal force

J ~~\ ~ ~~/[\ ~

\ --~~ /~ ""~~/""',{ / l/

I

I I

I I ·~

I '

~-irr, ~ II\ II\,( -~ ~Vv/~,., '-+5'"'/

~ v~~ :LJ I r- \I/ "-,V ------ v L! I "'+-- D . / VV I I "> "'V \

/ VVI J \/ ~ //VI I /I I

/I I I

FIG. 6.85 Finite element mesh for tooth-wedge stress calculations

543

Page 115: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

FIG. 6.86 End ring lug area - finite element mesh and stress contours

of all the other conductors in the slot which is of concern, particularly where the copper area is reduced by ventilation grooves and slots. Some creep of the copper may be observed at such slots after many yeqrs in operation.

544

Chapter 6

8.3 Alternating stresses, fretting and fatigue A stationary rotor sags under its own weight, causing a compressive stress in the outermost fibres at the top and at the axial centre of about 15 MPa, with a corresponding tensile stress at the bottom of the same magnitude. As the rotor rotates, each fibre ex­periences a compressive/zero/tensile/zero/ compres­sive stress cycle once per revolution. Since a rotor operating at 3000 r/min accumulates 1.5 x 109 cycles in a year, alternating stress due to bending has to be considered in the design. Though its magnitude is small, it is superimposed on the high steady stresses in the rotor and wedges identified above, and can pro­mote the growth of cracks by high cycle fatigue.

One source of crack initiation may be fretting. If a once per cycle movement can occur, say at the gap between two short slot wedges, the resultant localised damage may be sufficient to intensify the local stress field at a minute 'crack-tip', from which the alter­nating bending stress can propagate. Such features are avoided wherever possible, and particularly near the axial centre where alternating bending stresses are highest. The concepts of fracture mechanics are used to study such crack tip stress intensification.

8.4 'Slip-stick' of rotor windings One effect not mentioned in Section 3.8 of this chap­ter is the behaviour of the rotor winding during a loading cycle. The rotor is run up from cold, and though the windings and rotor body are warmed by gas friction, there is little differential in thermal effect at this stage. At speed, the winding conductors are locked together and to' the wedge by the centrifugal force, unless an axial force can overcome the friction between them.

When current is applied to the rotor winding, it reaches a higher temperature than the rotor body, and as the coefficient of thermal expansion of copper is nearly twice that of steel, the conductors experience an axial force directed outwards from the axial centre. As the differential temperature increases, the axial forces increase, until slippage occurs at a point where the build-up of axial force is able to overcome the friction. Because the 'bottom' conductor experiences the least centrifugal load, it is most easily able to overcome friction, and a shorter length of it rem_ains frictionally-locked than those of coils further up the slot. Slippage in most windings appears to occur in small steps, apparently randomly, though possibly re­peatably, so that the release of the axial forces does not result in sudden changes in vibration of sufficent magnitude to be significant. In some rotors, however, due to higher frictional restraints having to be over­come, the release of much larger axial forces appears to cause the bending moment to change significantly, resulting in a noticeable sudden change in vibration.

Page 116: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

-. One feature of this is that th~ rotor must usually be

,.... run down in speed before the changed vibration dis­appears, when the cycle can be repeated.

Once the rotor is at speed and temperature, it does not tend to suffer from high cycle effects. It is more vulnerable to effects promoted by relative movement, such as abrasion, when running at lower speeds and \\'hile barring, when the centrifugal locking-up is absent.

8.5 Noise . The generator rotor, with its fans, generates very ' high noise energy at speed. The spectrum is wide, but

contains peaks at frequencies related to the number · of fan blades and slots.

The other main source of noise is generated by . the stator core when magnetically excited. As pre­

viously noted, the magnetic forces 'ovalise' the stator , core, causing vibration and noise at 100 Hz and mul­

tiples. The main component of magnetic noise, how­ever, arises from distortions on a much smaller scale, that of the magnetised iron crystals, in the pheno­menon known as magnetostriction, at 50 Hz and multiples thereof.

The robust stator casing acts as an effective sound attenuator, and little can be achieved to reduce the

- transmitted noise further, for example, by the acoustic treatment of the inside surfaces. In practice, the major sources of high noise intensity tend to occur in the driven components such as exciters, which have fans operating in air and no heavy steel surround. Some­times the complete line of driven units is housed under an acoustic cover to attenuate these sources. Access doors and windows must be provided, and these can reduce the effectiveness of the covers.

A sound power level of 93 dBA is specified at - 1 m distant from the plant. Legislation may require

this to be reduced for new plant in the future.

9 Electrical and electromagnetic aspects __ Some electrical and magnetic aspects of generators,

not previously considered, are dealt with in this section.

9.1 Flux distribution on load When, in previous sections, magnetic flux densities

·have been mentioned, operation at rated voltage, no-load has been assumed, where the load angle is zero and the rotor operates in the 'direct axis'. In

. practical load situations, the load angle is 40-50° ,md the effective f1ux level must be large enough to overcome the leakage reactance voltage drop. The first effect distorts the flux pattern markedly; the

Electrical and electromagnetic aspects

second increases the required flux magnitude; both increase saturation, the effects of which are highly non-linear (see Fig 6.87). One result of this is that overall iron losses will be higher than those calculated for no-load conditions, and their distribution will dif­fer. Another is that the calculation of the required MMF (rotor current) required for any load condition cannot be accurately based on the simple phasor diagram. Since the rotor is necessarily designed with little margin, accurate calculation of the rotor current needed for rated conditions is essential.

FiG. 6.87 Flux distributioq on load

A method previously used took as its basis the simple no-load unsaturated phasor diagram, and de­fined an imaginary reactance, the 'Potier' reactance, empirically derived, which was used to define a 'Potier' voltage drop, IXP, for the given load conditions. An internal voltage required to overcome this voltage drop, the 'Potier voltage' was thus established. The MMF difference between the airgap and open-circuit characteristics at the 'Potier voltage' was then pha­sorially added to the unsaturated MMF phasor. In this way, the increasing and non-linear effects of sat­uration were taken into consideration (see Fig 6.88).

Present methods use finite element calculations, which can be reduced to two dimensions for the central part of the machine. Even so, the detailed geometry and non-linear magnetic characteristic make the calculation complex.

In the end regions, a three-dimensional approach is almost essential, although various schemes have been devised in which simplifications can be made. In addition to the difficulties already noted, the thick conducting plates in which non-linear eddy currents

545

Page 117: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

mi

I

II

II.

.1' II

ll

II I

The generator

STATOR VOLTAGE

ROTOR CURRENT

ADDITIONAL ROTOR CURRENT REQUIRED

FOR POTIER REACTANCE DROP

Chapter 6

v

FtG. 6.88 Potier construction for on-load excitation current

are induced, and other conducting components,. must be included in the modelling. It has reached the stage of refinement where detailed changes, say, in the thickness of magnetic screens, can be modelled in order to optimise the design, and to indicate where potential hot spots may occur due to unwanted flux concentrations.

9.2 Control and calculation of reactances The reactance of an inductive circuit determines its voltage/current relationship. In a generator, different reactances are identified in order to model or de­scribe voltage (or flux)/ current relationships under different circumstances.

The synchronous reactance, Xct, relates the arma­ture reaction MMF (proportional to stator current) to the MMF needed for rated flux in the air gap. For a given design of machine, increasing the radial length of the air gap proportionately reduces Xct and im­proves steady state stability. This results in a larger outside diameter, and a higher rotor current at full load.

The stator leakage reactance, Xf, is not a specified quantity, and its value is a matter of economic design. The transient and sub-transient reactances, Xct' and Xct", are specified. They describe the flux/current rela­tionships during transient changes, and under these cir­cumstances, ·the amount of flux encircling the sta­tor slots, rotor slots and end windings are of impor-

546

tance. If higher values are required than the 'natural' ·~ design produces, the leakage reluctance can be re- ! duced by making the slots narrower, and/or sinking them deeper into the core. Again, this is extravagant

~~ and results in a larger design. If lower values are required, it is not usually suf­

ficient to manipulate the slot geometry, and a more basic change to the design might be needed.

Using computer programs similar to those men­tioned in the previous section, more accurate repre­sentation of the reactances can be made, over the range of load conditions, than is possible by simple calculation.

9.3 The cause and effect of harmonics As explained earlier, stator winding distribution is designed to minimise the generation of harmonic volt­ages and currents.

The stator winding is invariably star connec.ted, so that triple harmonics cannot occur in the line voltage or current. Since one pole of the rotor is identical with the other, it cannot produce second-order flux harmonics, which would make the two halves of the flux wave dissimilar. The only harmonics of signi­ficant magnitude which will appear are those of order S, 7, 11, 13, etc., with diminishing amplitudes, and those near to the rotor slot pitch, e.g., 41 and 43 for a 42-pitch rotor slotting. The no-load rated volt­age wave must not contain a greater total harmonic ]

l

i

Page 118: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

content than that specified in RS5000, in which cer­tain ranges of frequency are more highly weighted than others because of their effect (in the transmission system) on communications lines. This now rather out­dated concept is still accepted as an agreed and useful criterion, since high harmonic levels can induce high local losses in parts of t~e generator, e.g., the rotor surface.

In practice, harmonics are generated by the con­nected loads, a recent trend being the even-order harmonic requirements of equipment using thyristors. This must be supplied by the generators and must therefore appear in the flux wave, causing rotor surface losses similar to those produced by unbalanced load conditions.

Rotor windings occasionally develop short-circuits between adjacent turns in a coil, and while this is not usually of great concern, the difference in flux pat­tern from the two poles is detectable, using a small flux coil mounted in the airgap. When the signal from one pole is offset against the signal from the other, differences reveal any abnormality. Another method which has been suggested uses the presence of second harmonics in the stator current, as noted above, but this has to be able to reject those imposed by the load requirements.

9.4 Magnetic pull 1 If the rotor is exactly centred in the bore of the sta­i tor, the magnetic pull between one pole of the rotor

and the stator will be exactly balanced by that of the other. If not centred, there will be an unbalanced

f pull acting as an attractive force on the pole with " the smaller air gap. However, the air gap of these

large machines is so large (80 to 130 mm), in order t to achieve the required synchronous reactance, that J centring the rotor to a readily achievable accuracy

does not impose a magnetic pull at all comparable

1 with the gravitational force on the rotor. 1 Similarly, the net axial magnetic force on the rotor

is Lcro if it is axially centred in the stator, and this is the condition normally achieved at rated load with

l the rotors at their normal temperatures. With the i usual axial offset which occurs with the rotors cold,

the axial magnetic pull is only of the order of a few t thousand Newtons and is not a significant additional f load on the thrust bearing.

9.5 Shaft voltage and residual magnetism The production of a voltage (predominantly at 50 Hz)

, from one end of the generator rotor to the other oc-

1 ~~-~: -~"~~~s~ ~;~om~-asymmetry, ei.tb.~r af tb.e ?asi.ti.arr , ·= . ~ .::> .... ,!"!e ,,ator. or some d1fference m mag-

;·ro;:-~<-:'. T!"!is me-:hanism has a low effecti\·e

Electrical and electromagnetic aspects

source impedance, and can circulate significant cur­rent through bearings, seals, etc., causing eventual break-up of white-metalled surfaces.

Voltages of the same frequency as the shaft-driven excitation machines can be measured on the generator shaft, but these are capacitively coupled, have a high sour.ce impedance and will not sustain a large current.

The steam turbine rotors may develop a voltage due to the electrostatic action of steam and water droplets on the blades, and one function of the shaft earthing brushes is to ensure that this is discharged. A phenomenon which has occurred (rarely) on tur­bines is that, where a rotor or rotors have a degree of permanent magnetism and there are contacts of low resistance between shaft and earth at suitable axially­separated locations, the small generated voltage can circulate a small current through the turbine casing, which, in certain designs, can act as a partial 'turn' of a winding encircling the shaft. This then produces an MMF and therefore a higher shaft voltage, the whole process building up until many thousands of amperes circulate, causing damage at the contacts. It is therefore important to ensure that deliberate con­tacts, such as earthing brushes, have a resistance (say, 1 ohm) deliberately included in series, and that heavily magnetised shafts are de-magnetised (see Fig 6.24).

The residual magnetism of a generator rotor will normally produce a voltage of several hundred volts at speed, even without external excitation; and access to terminals, connections, etc., must not be allowed.

9.6 Field suppression If an electrical fault occurs in ' the generator, the connections, or on the generator transformer, the protection will act to trip the main circuit-breaker. This will extinguish the stator current within one cycle of circuit-breaker operation but the flux cannot be reduced so quickly. In all except brushless ma­chines, a field circuit-breaker is connected in circuit between the excitation source and the rotor winding. If this were to be opened, the instantaneous reduc­tion in current would induce a large (several kV) voltage in the rotor winding, with the risk of insulation breakdown.

Instead, a field suppression resistor is inserted in series with the rotor winding, the excitation source circuit being opened subsequently. The resistor has an ohmic value of 1 to 3 times that of the winding, and reduces the current (and flux) rapidly, without imposing an excessive voltage. Thus the ability of the flux to prolong the current in the fault is safely minimised.

In brushless machines, direct suppression of the rotor winding current is not possible. The exciter field curre.rrt i..s ca~i..dt'j ce.duce.d b':f the. ()~<C'>'i'>t~()~ (){ th~ exciter field switch (this also applies in a non-brush­less machine), or by invenion of the thyristors, but

547

!'

Page 119: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

content than. that specified in R$5000, in which cer-• tain ranges of frequency are more highly weighted

,than others because of their effect (in the transmission system) on communications lines. This now rather out­

l dated concept is still accepted as an agreed and useful -'- criterion, since high harmonic levels can induce high

local losses in parts of t~e generator, e.g., the rotor surface.

_ In practice, harmonics are generated by the con­nected loads, a recent trend being the even-order harmonic requirements of equipment using thyristors.

\ This must be supplied by the generators and must --.therefore appear in the flux wave, causing rotor surface

losses similar to those produced by unbalanced load conditions.

- Rotor windings occasionally develop short-circuits between adjacent turns in a coil, and while this is not usually of great concern, the difference in flux pat-

.....:. tern from the two poles is detectable, using a small flux coil mounted in the airgap. When the signal from one pole is offset against the signal from the other, differences reveal any abnormality. Another method

~ which has been suggested uses the presence of second harmonics in the stator current, as noted above, but

· this has to be able to reject those imposed by the load requirements.

9.4 Magnetic pull t If the rotor is exactly centred in the bore of the sta­. l tor, the magnetic pull between one pole of the rotor

and the stator will be exactly balanced by that of the other. If not centred, there will be an unbalanced

·l pull acting as an attractive force on the pole with ~

·~the smaller air gap. However, the air gap of these large machines is so large (80 to 130 mm), in order

~ to achieve the required synchronous reactance, that · f centring the rotor to a readily achievable accuracy

does not impose a magrietic pull at all comparable , with the gravitational force on the rotor.

j Similarly, the net axial magnetic force on the rotor is zero if it is axially centred in the stator, and this is the condition normally 'achieved at rated load with

f the rotors at their rionnal temperatures. With the usual axial offset which occurs with the rotors cold, the axial magnetic pull is only of the order of a few

~thousand Newtons and is not a significant additional $ load on the thrust bearing.

9.5 Shaft voltage and residual magnetism . The production of a voltage (predominantly at 50 Hz) ~ from one end of the generator rotor to the other oc­. curs because of some asymmetry, either of the position

of the rotor in the stator, or some difference in mag­\ netic properties. This mechanism has a low effective l

Electrical and electromagnetic aspects

source impedance, and can circulate significant cur­rent through bearings, seals, etc., causing eventual break-up of white-metalled surfaces.

Voltages of the same frequency as the shaft-driven excitation machines can be measured on the generator shaft, but these are capacitively coupled, have a high sour,ce impedance and will not sustain a large current.

The steam turbine rotors may develop a voltage due to the electrostatic action of steam and water droplets on the blades, and one function of the shaft earthing brushes is to ensure that this is discharged. A phenomenon which has occurred (rarely) on tur­bines is that, where a rotor or rotors have a degree of permanent magnetism and there are contacts of low resistance between shaft and earth at suitable axially­separated locations, the small generated voltage can circulate a small current through the turbine casing, which, in certain designs, can act as a partial 'turn' of a winding encircling the shaft. This then produces an MMF and therefore a higher shaft voltage, the whole process building up until many thousands of amperes circulate, causing damage at the contacts. It is therefore important to ensure that deliberate con­tacts, such as earthing brushes, have a resistance (say, 1 ohm) deliberately included in series, and that heavily magnetised shafts are de-magnetised (see Fig 6.24).

The residual magnetism of a generator rotqr will normally produce a voltage of several hundred volts at speed, even without external excitation; and access to terminals, connections, etc., must not be allowed.

9.6 Field suppression If an electrical fault occurs in 'the generator, the connections, or on the generator transformer, the protection will act to trip the main circuit-breaker. This will extinguish the stator current within one cycle of circuit-breaker operation but the flux cannot be reduced so quickly. In all except brushless ma­chines, a field circuit-breaker is connected in circuit between the excitation source and the rotor winding. If this were to be opened, the instantaneous reduc­tion in current would induce a large (several kV) voltage in the rotor winding, with the risk of insulation breakdown.

Instead, a field suppression resistor is inserted in series with the rotor winding, the excitation source circuit being opened subsequently. The resistor has an ohmic value of 1 to 3 times that of the winding, and reduces the current (and flux) rapidly, without imposing an excessive voltage. Thus the ability of the flux to prolong the current in the fault is safely minimised .

In brushless machines, direct suppression of the rotor winding current is not possible. The exciter field current is rapidly reduced by the operation of the exciter field switch (this also applies in a non-brush­less machine), or by inversion of the thyristors, but

547

Page 120: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Tile gen?r:J tor

the rotor current has an effectively zero resistance path through the rotating diodes, and decays with the natural time constant of the winding (see Fig 6.89).

9.7 Voltage in the rotor winding At rated load, the voltage required to circulate rated rotor current is of the order of 500 V. During field forcing, this may rise to almost twice this value for a few seconds. The rapid decay of current during field suppression may possibly induce 1500 V briefly in the winding. During transient fault conditions, the requirement of maintaining the previous flux level may cause large currents to be induced into the winding, with correspondingly high voltages (1500 V or so). The highest voltages are likely to be applied during asynchronous operation, during which the induced alternating rotor current (at slip frequency) seeks to reverse. This possibility is blocked by the excitation diodes and high voltage peaks occur ( > 2000 V) at the sudden changes in current.

The winding insulation of a new rotor is finally tested .at 3500 V, having withstood higher test voltages during manufacture. However, the arduous operating conditions may cause insulation to become physically damaged, displaced, or just oily or dirty from con­tamination, and such high voltages are less easily withstood in an older rotor.

When brushes are being changed with the generator on-load, it is common practice to ensure that the excitation control is on 'manual', so that the rotor cannot be subjected to field forcing voltages, and to disconnect the earth fault indication biasing voltage. It may be thought to be advantageous to earth the slipring being worked on deliberately, but if this were done and an earth fault developed in the rotor wind-

SLIPRINGS AND BRUSHGEAR

GENERATOR ROTOR

WINDING

MAIN FIELD SUPPRESSION

SWITCH

MAIN FIELD SUPPRESSION

RESISTOR

;r :~ ...

Chapter 6::.

'I ing, a large fault current would flow, with danger to;\ the maintenance operator. It is considered prefer-;! able not to apply an earth, but to ensure that thei[ operator is properly clothed and is using special in-:j sulated equipment. '

9.8 Stator winding insulation i ln normal operation, the highest voltage to earth~ occurs in the winding bar (and connection) at the highl voltage ('line') end of each phase. This amounts to! 23.5/--./3 = 13.5 kV (RMS) for the 660 MW units.: Voltage to earth on the other conductor bars is re­duced through the winding to effectively zero at the neutral end. The electrical stress in the insulation is not high even on the line-end bars; all the bars are !i similarly insulated. ,

The system of insulation has to undergo searching . type tests before it is approved for general use, and~ even then, quality control tests on production bars · include the destructive cutting up of two sacrificial bars per machine to ensure freedom from cavities in the insulation, among other quality checks.

In operation, electromagnetic forces cause the bars to vibrate at 100 Hz in the slots and end windings, I to an extent limited by their restraining devices. If bars become loose in their slots due to relaxation. of ripple springs or wedges, the layers of insulation i tape may become locally de-laminated, in spite of the bonding resin. Electrical discharges can occur at such sites which might eventually lead to electrical breakdown of the bar to earth. Fortunately, in a hy-. drogen atmosphere, carbonisation of the surfaces does" not occur as readjly as it would in air, and break­downs from this cause are uncommon. Discharge on the bar surface, either in the slot, or across the end

BRIDGE RECTIFIER

MAIN EXCIT~R

FIELD WINDING

FIELD SUPPRESSION

SWITCH

FIG. 6.89 Field suppression circuits

548

Page 121: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Operational measurement, control, monitoring and protection

winding surfaces, may occur, particularly where the semi-conducting shrface treatment layers become bro­ken or damaged, but again this does not normally lead to breakdown. Much more likely is mechanical damage to the insulation by pieces of core punching which become detached, magnetic debris (which can cut 'wormholes' into the end winding insulation un­der electromagnetic forces), and abrasion of packing blocks into insulation. For these reasons, insulation thicknesses have not been reduced to take advantage of the superior electrical properties available with modern insulation systems.

Considerable effort has been devoted to devising means of detecting signs of insulation deterioration, for instance, by observing discharge activity in a permanently installed, capacitively coupled device, or by radio frequency aerials inside the casing; both methods are still being developed. Discharge energy is predominantly in the 1 MHz range, whereas corona discharge, which also occurs, is predominantly at a higher frequency. Occasional 'fingerprint' measure­ments can show whether either activity is increasing with time.

Similarly, an overall measure of the insulation integrity of a whole phase can be gained by mo­nitoring the capacitative component of current at various voltage levels, usually expressed as 'tan delta' values, i.e., a measure of (very low) power factor.

Breakdown, however, is most likely to occur from one local area of damage, as already noted, and the poor results from this local area are swamped by the better measurements of the rest, so that such methods are relatively insensitive.

Stator insulation withstands more than twice its rated line voltage, i.e., >2['\"'3 x maximum (phase) operating voltage], and an insulation sample will with­stand at least twice this again, so there is a huge safety margin on intact insulation. Even so, testing at high voltage is destructive, and repeat testing in service is deprecated.

If an earth fault occurred at one of the phase ends, the voltage at the neutral would be elevated, and that at the other phase ends could rise to )3 x normal. This condition would persist for only a few seconds, at most, before the protection acted to trip the unit and suppress the flux. In normal operation, the maximum voltage a winding can attain is limited to about 350Jo above rated, for example, if rated load were tripped, but again this would quickly be suppressed.

Surges arising from switching or other operations on the system are greatly attenuated in the generator transformer, and do not pose a significant hazard to the generator winding. These large machines do not haYe multi-turn coils, which are more at risk from 'c:~ges. The surge withstand voltage is quoted at about !'5 -90 kY. but surge withstand tests are never carried out.

10 Operational measurement, control, monitoring and protection Many of these subjects have been mentioned in pass­ing. In this section, each group is considered as a co-ordinated whole.

10.1 Routine instrumentation Provisions vary between manufacturers and have chang­ed over the years, but the following is representative.

10.1.1 Temperature

Thermocouples are used to detect the temperature in:

• Stator core - in teeth, back of teeth, core ends and axial centre.

• Core end plates and end plate screen these are permitted to attain higher temperatures than the core if not in contact with insulation.

• Hydrogen inlet to and outlet from coolers -several, to allow averaging.

• Stator winding, either one per slot or in water outlet hose - basically to monitor water flow in in­dividual bars.

• Hydrogen seal faces - to detect rubbing, or oil starvation.

• Stator frame, at C02 inlet to detect freezing.

Resistance elements or other thermometers are used for:

• Water inlet and outlet temperatures in all water cooling systems.

• Oil outlets from bearings and seals.

• Seal oil at outlet from cooler.

• Hydrogen to and from cooler, as back-up to ther­mocouples.

• An ohmmeter is used to display rotor winding _ temperature.

• Temperatures are monitored during works tests and during on-load commissioning, to ensure that the specified limits have not been exceeded. The alarm level would normally be set above the high­est temperature attained at rated load with the warmest ambient conditions, but recent thoughts are that this practice may miss early warnings of developing abnormalities. If a measured tempera­ture is related to other parameters, such as current

549

Page 122: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

and cooling water temperature, or even compared to other similar' signals to see that its magnitude in the established scatter pattern is correct, by using a dedicated microprocessor, a more informative indication can be provided to the operator.

10.1.2 Pressure

Pressures are monitored as follows:

• Hydrogen in supply bus.

• Hydrogen in casing.

• Carbon dioxide in supply line.

• Stator wiJ:tding water.

• Seal oil (and thrust oil, if separate).

• Vacuum in seal oil treatment plant (if used).

Differential pressures are monitored between:

• Hydrogen and stator winding water.

• Hydrogen and seal oil.

• Fan inlet and outlet.

10.1.3 Flow

Flow rates of the following are measured:

• Stator winding water, by flowmeter or by differen­tial pressure across either an orifice or the winding.

• Make-up hydrogen (in some machines).

• Hydrogen through katharometer.

10.1.4 Condition monitoring

• Purity of hydrogen (katharometer).

• Humidity of hydrogen (hygrometer).

• Humidity of exciter air (hygrometer).

• Conductivity of stator winding water.

• Composition of scavenging gases (katharometer).

• Quantity of particulate matter in hydrogen (condi­tion monitor).

Fig 6.90 srows a typical condition monitor console.

10.1.5 Electrical

• MW, MVAr, voltage, current, power factor (in control room).

Chapter 6

• Vectormeter (on control desk).

• Excitation voltage, current.

• A VR indications (locally, on A VR panel).

• Diode failure.

• Shaft voltage.

10.1.6 Vibration

• Bearing and shaft movement.

• End winding vibration, using ~ccelerometers on sup­port beams.

10.2 Logging and display Transducer outputs are received as inputs to the com­puter at intervals determined by consideration of what event could have caused a signal different from nor­mal, and in what time scale this could cause damage. Readings may be logged only when outside the normal range or, alternatively, readings within the range may be logged at intervals.

The most modern stations display only the essen­tial information continuously to the control room operator. Some systems display 'by exception', i.e., when a parameter falls outside its expected range. All information is available on demand, on VDU screens or printers.

10.3 Control The load and, excitation control systems have already been described. The following quantities are common­ly controlled automatically:

• Hydrogen pressure, by spring-loaded valve, backed up by spring-loaded overpressure valve.

• Seal oil pressure, by pump pressure control and differential control valve.

• Stator winding water pressure, by spring-loaded bypass valve.

• Cooling water temperature, by heaters and bypass valve.

• Gas-in-water detection, by timed operation of solenoid valve.

• Regeneration of dryer, by timer and automatic valves.

Other parameters, such as water temperature, are commonly controlled manually, adjustments to valves being made as necessary when indicated values exceed given limits.

Page 123: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

..

' • I·

1. I

Operational measurement, control, monitoring and protectiol}

0 I! 0

"' " ro· 0 0 o;

~· CONDITION MONITOR

FIG. 6.90 Condition monitor (NEI Parsons LtJ 1

\S'<-"- ci.so;:, "-"'~"'""-" "''"''"''='c.\,"'"'''""-"-"'»» .l,'<\1. '"''"'- .l,'i,',·,

551

Page 124: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

I

I a

I

-

The generator

10.4 On-load monitoring, detection and diagnosis Detection of abnormal conditions is divided between two sections: on-load detection techniques, described here, and techniques which are applied off-load, at standstill, or during maintenance, which are grouped with Tests under Section 11 of this chapter.

Some equipment is provided so that on-load checks can be carried out periodically on a routine basis in order to ensure that previously established conditions have not changed.

10.4.1 Air gap flux coil

A search coil monitors the rate of change of leakage flux in the air gap as the rotor rotates (Fig 6.91). The signal from one pole is subtracted from the signal from the other; significant differences are indicative

Chapter 6

of one or more turns in a coil becoming short­circuited. (In some machines, this condition may be continuously monitored.) The condition normally re­quires remedial action but it is prudent to check that the situation is stable.

10.4.2 Core or condition monitor

In this device (Fig 6.90), hydrogen is drawn from the casing through a chamber in which a radioactive source emits a normally constant rate of electrons. Ionised particles in the hydrogen stream, due to dust or liquid aerosol droplets, cause the collected current to fall, and initiates an alarm at a given level. It is, in effect, a sophisticated smoke detector. The particles may be from areas of overheating stator core (hence the name) or from insulation; they can be trapped in a filter and analysed.

FIG. 6.91 Airgap search coil and waveforms

1 552

., •·,

'!

t.[ ·"

:>I

~ ~ :~;~

" '~ '" ' -~ ~· " ~' :j '~ l i! i i •l j .j

Page 125: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

a

I

I I I I I I

Operational measurement, control, monitoring and protection

30

23

15

VOLTAGE IV)

-8

--15

-23

3.0

2.5

VOLTAGE (V) 2.0

15~ 10~ 0 5

-0 5

b

~ FAULTED COIL SEARCh COIL WAVEFORM

20ms

n ar1d b are the two s1des of the faulted co11

FIG. 6.91 (contd.) Airgap search coil and 11avelorms

10.4.3 Insulation discharge

These techniques were discussed in Section 9 of this chapter.

10.4.4 Rotor winding earth fault indication

The rotor winding and its connected excitation circuits are not earthed. In order to detect a low value of insulation resistance while on-load, a biasing voltage ol about 30 V DC is applied to the 'positive' end of the winding through a current relay, causing the entire circuit to have a negative voltage to earth (Fig 6. 92). If the overall insulation resistance to earth falls h.'IO\\ I 00 000 ohm (the actual value depends on r he po,ition of the 'fault' in the circuit), the relay c1perate' to initiate an alarm. Operation of the rotor 111a\ be continued but it is recommended that the _.n:: ,hc)uld be taken off-load as soon as comenient

and the condition investigated. If it is decided that a calculated risk can be taken to enable generation to be continued, a protection device developed in 1987 can be installed. This will initiate a Class 1 trjp on the occurrence of a second rotor earth fault, and minimise the damage from the high circulating current that this would otherwise cause (see Fig 6.93).

10.4.5 Shaft current insulation integrity

In a machine with 'islanded' insulation (see Section 3 of this chapter), the integrity of it'i insulation can be checked with a megger.

10.4.6 Stator winding water analysis

This water !l1Lht be checked for O.\ygc:· and copper con­tent at recommended inten-als.

553

Page 126: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

• -

I

I I I I

I

The generator

I

-530V

' EARTH

LEAKAGE CURREtH

DETECTION

EXCITATION SUPPLY SOOV 4000A DC It TYPICALLY <0.75mA

RELAY

-30V BIASSING VOLTAGE

STATION EARTH

+

SWITCH OPEN· K ~ V t

SWITCH CLOSED K 1 ~

I ' v1 v2

APPARENT CHANCE \I.\= K1- K

VOLTAGE V, ACROSS FAULT RESISTANCE R1

o-.\K ve"' \K (\/., + V:

CURRENT It IN FAULT RE'SISTANCE ~ V21

Am

FAULT RESISTMJCE R, ~ V1

K IS ACTUAL FAULT POSITION K' IS APPARENT FAULT POSITION

HENCE BOTH FAULT POSITION AND FAULT RESISTANCE CAN BE COMPUTED AND COMPARED WITH PREVIOUS VALUES

FIG. 6.93 Second rotor earth fault protection

10.5 Protection Protc:crion. here defined as equipment dc:signed to trip the unit \\hen necessary. is classified by the speed

554

Chapter 6

of its trip initiation:

• Class 1 protection mitiates a main circuit-breaker trip as fast as can be arranged. Taking the trip relay and circuit-breaker operating times into ac­count, this means about 120 ms (6 cycles) after initiation. With the most modern circuit-breakers, this time may be reduced tu about 80 ms.

• Class 2 protection initiates the closing of the tur­bine stop and interceptor valves. The load reduces to I U7o or less within a few seconds; this situation is detected by a 'low forward power' relay which, after a short delay, initiates a main circuit-breaker trip. The process takes 4- 5 s from the original initiation and is intended to prevent a possible speed runaway if the overspeed governor does not func­tion correctly on load rejection. Consequently, those conditions in which a 5 s delay can be tolerated before tripping are arranged to be protected by a Class 2 trip.

10.5.1 Class 1 trips

Electrical failure damage propagates so quickly that Class I tripping is essential. The following situations are co111monly protected by Cla~s I trips:

• Generaror transformer winding fault This causes imbalance between currents in the HV side of the transformer and the generator neutrals. (Note that, for faults beyond the transformer, no damage in­ternal to the generator and transformer is expected, and tripping is not initiated.)

• Unbalanced load (negative sequence) faults These are described in Section 7. 9 of this chapter.

• Stator winding earth fault With high impedance neutral earthing fault current could be tolerated for the 5 s of a Class 2 trip, but this condition has been found to be the forerunner of a more serious fault in the windings and Class 1 tripping is now recommended.

• High hydrogen temperature The most positive method of protection against a complete loss of raw cooling water to the generator cooling circuits is to trip on high hydrogen temperature. Gas tem­peratures and stator winding water temperatures rise to a dangerous level so quickly that activating an alarm to advise an operator to take action is unlikely to result in action which is fast enough to be effective.

• Splir phase protection This is not yet fitted except experimentally. It is intended to detect a difference in the currents in the two parailel paths of a stator phase \\'inding, which are normally equal. A bar­to-bar fault in one path \\ uuld result 1!1 a detec:­able imbalance, which could trip the unit before

Page 127: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

the fault had time to develop into a more damag­ing fault between ph~ses.

• Second rotor earth fault

10.5.2 Class 2 trips

• Loss of stator winding water flow This is time delayed to allow the standby pump to start.

• Exciter rectifier bridge-arm failure This protects against the loss of all the diodes in one arm of the excitation rectifier.

• Loss of excitation Detected by a mho relay after the rotor has moved into a pole slipping mode.

• High vibration This is described in Chapter 2.

• Emergency pushbutton This is described in Chap­ter 2.

11 Maintenance, testing and diagnosis

11.1 Maintenance and tests during operation Sliprings and brushgear require regular maintenance to ensure trouble-free operation. The selective pass­age of more current through one particular brush can lead to excessive wear on that brush, so that even though an average brush life is 6 months, one brush may wear to the point where spring pressure is lost within 2 weeks. Facilities for on-load brush changing are provided, and are necessary for base load units. Occasionally, slip rings may require re­surfacing by grinding, but this cannot be done on­load and must await a shutdown. Shaft riding earthing brushes, and the instrumentation brushes provided on some 'brushless' units, also need regular attention.

There is little other maintenance work which can be carried out with the machine on-load, apart from keeping clean components such as pedestal and exciter insulation shims, emptying drains when necessary, and noting what they contain, cleaning or replacing filter elements where possible, and ensuring that pumps, control valves, etc., are functioning correctiy.

Apart from monitoring both the regular and more specialised instrumentation, as described earlier, there are few tests which can usefully be carried out. Cal­ibrating checks can be made on the purity meter by diverting pure hydrogen through it, and manual sampling can provide samples of casing hydrogen for . back-up monitoring of impurities and moisture con­tent, and of stator winding water for pH value, oxy­gen and copper content, and conductivity. In some stations, means are provided for the on-load testing of certain protection devices, for example, flow of

Maintenance, testing and diagnosis

stator water. Any sudden departure from normal conditions

should be investigated. Changes in shaft or stator winding overhang vibration should be correlated with load and temperature, and changes in stator core or casing vibration with voltage and temperature. Con­dition monitor excursions should require samples to be analysed. Such information may be invaluable when assessing the condition of the machine at the next major outage, or when planning remedial work.

11.2 Maintenance and tests when shut down for a short outage During outages as short as 2- 5 days, the casing would not normally be scavenged, and the shaft would be barred for much of the time. Therefore the generator and its systems are not much more accessible than when in operation.

Cleaning of brushgear and the slipring area can be carried out to remove built-up deposits of carbon, possibly soaked with oil, which can form electrical tracking paths. It may be po,sible to grind the slip­rings.

lf the brushes are lifted clear of the sliprings and a pair of insulated brushes fitted, a test on the rotor windings can be made with a recurrent surge oscillo­scope (RSO). In this test, a steep-fronted pulse is applied to one end of the winding. Any abnormality in the winding, such as a short-circuit between turns, will cause a smaller surge to be reflected back to the source, just as if the winding were a transmission line. Figure 6.94 shows typical waveforms of signals reflected from each end.' By subtracting the signals, an abnormality may be detected. Such tests can be very sensitive, and must be interpreted with care.

11.3 Maintenance during a longer outage If the outage is known to be longer than a week or so, the casing can conveniently be scavenged. When this has been properly carried out, access to the inside of the casing can be gained by withdrawing a cooler, or to the end winding area by taking off a cover in the endshields.

Visual examination of the interior may reveal ex­cessive amounts of oil, indicative of a malfunctioning shaft seal, or of water, indicating a cooler or cooling circuit leak. Signs of overheated insulation may be evident, or of powdered glass or mica, indicative of abrasion of insulation. Excessive burning or welding between core bars and the core back may indicate an embedded core fault. Loose packers, bolts or hoses in the end winding may be apparent, and loose debris may be visible. The effort involved in such an inspection is worthwhile to preserve confidence in the continuing good performance.

555

Page 128: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

""

~ ~

-~

-

p-r Jr

10

v /

I

' I

'

~ -_,-6

~ J"-'"'

- _ _,

~// .r -

·'

4 JV ! VOLTS

/I..)

v'-''

~ ~ fl\ -··--

'[/\f ~ I~ )v-LA... fA J!L----, I 0

~ fwvvvv--r ~w Al.fl ~~ I l.JVV'\AAA. I DEVIATION I

i

' I

i

' 10 40 "fJ 70 9J 100

TIME ,S

FIG. 6.94 Recurrent surge te;t

All such examinations of the interior must be sub­ject to the rigorous enforcement of rules concerning tools, the wearing of overshoes, etc., to ensure that foreign materials are not left inside. The stator casing heaters should be kept on once degassing has been completed.

At these outages, seals and bearings may be dis­mantled for inspection, both for signs of wear and damage, and of electrical discharges due to the pass­age of shaft current. The inside of exciters can also be inspected, as can components in the various aux­iliary systems.

A limited amount of testing can be carried out, e.g., the insulation resistance of the rotor winding, using a 500 or 1000 V megger, and the IR of the shaft current insulation if islanded.

11 .4 Maintenance and tests with the machine dismantled If the outage is to be long enough for the rotor to be withdrawn, much better access to both rotor and

556

stator is possible. Inspection of the rotor surface, particularly where crack initiation sites are suspected, such as the gaps between short wedges, should be carried out. Inspection down the radial ventilation holes to check that insulation packing has not moved to block the gas cooling passages, is recommended, following which the holes should be sealed with a continuous strip of adhesive tape, to prevent the ingress of debris.

Limited inspection of the end winding is also pos­sible, and signs of fretting, looseness, distortion of coils, or movement of insulation, blades or coils should be looked for. If the pole-to-pole crossover is visible, it is advisable to examine it for signs of fatigue cracking.

End rings should be examined for surface cracking and, by using ultrasonic techniques, for embedded defects. The CEGB guidelines recommend that those end rings which are not of 18118 material should be removed after about 80-90 000 h in operation, and skimmed to a depth of about 0.25 mm over the cyl­indrical surfaces (but not the shrink face), following which a fluorescent dye ('Zyglo' or equivalent) ex-

Page 129: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

~----------------------------------------------------------------~,--

I ~

· amination is made. Defects greater than 2 mm should ' be ground out, blending in the .ground area so that ' there are no discontinuities. Finally, the ring must · be re-treated with its protective finish before being ·· refitted. The whole operation requires great skill and ~ experience, and though it can be carried out at site,

it is better done at the manufacturer's works, fol­, lowing which the rotor can be subjected to overspeed i and balancing runs. These comments also apply to ; exciter end rings.

Examination of the stator core can be carried out : by inspecting the bore for loose areas, which can I be tightened by insertions of hard insulation, or by ' treating with an epoxy-based liquid having low sur­' face tension which will penetrate between the la-

minations. Ventilation ducts should be inspected for ''debris, blockages and broken spacer bars. The back . ' '0\ \.'D.'\. '\.'0'i.'\. ~\\\ W'9~a\ 't'.\'\.'t'S~)'Y'e \\>~\\\)11~ L>'i 'Ct:>1'e \I)

core bars, or damaged core bar insulation, where • this is fitted. Some core back burning, and some

fretting products (e.g., 'cocoa dust') seems to be innocuous. The core frame can be inspected for ob­\ious signs of damage, and patches of overheated paint or metal should be investigated.

E\ery stator slot wedge should be checked for tight­n-:'~~ along its whole length, using a tightness tester de1 eloped in 1985, or by tapping with a coin or simi­l~n l>biect to observe the expected 'ringing', indicative ,,r .1 tight slot. Airgap flux coils can be fitted or :en ell eel at this stage.

C.,r,nor end windings can be more thoroughly checked ~han a-; described in the previous section. Signs of lc'O.,cncss of packings, fretting, slack fastenings, etc., a: c all indicative of movement. If there are unfilled bags between coils, these can be filled with epoxy resin at this stage. The surfaces should be cleaned using a proprietary cleaner suitable for electrical windings, but it is not recommended that repainting is under-

'1.11!' taken without the manufacturer's advice. If a 'worm­'~11\ lwlt:' (made by small conducting particles) is found,

the particle should be removed and the insulation patched rather than left in, possibly to break through

'lllj'·i: intL' the copper. ~~Iii The state of the hoses and their connecting joints

should be checked. A leakage test on the stator wind­in.;:. using vacuum or pressurised air with a tracer gao. 1\ ill reveal any significant leaks. It may be con.,idered prudent to renew all the rubber 0-rings, bl'th :n these locations and elsewhere, if they have b~cn in sen ice for several years. Care must be taken lL' · ,, ilo11 the assembly instructions meticulously, as 01 ercJghtening may damage the joints.

The opportunity should be taken to clean the sta­tor casing. particularly at the bottom, noting if water ha~ collected, and checking that the flow to the leak-

l a£e detector is unobstructed. lnsulat1on res1stance tests should be carried out

on the rotor winding, using a 500 or 1000 V megger,

1 and on excitation windings. An RSO test could also

Maintenance, testing and diagnosis

be performed on the rotor winding, with slipring brushes lifted.

If any hot spots in the stator core are suspected, or as a reassurance exercise, a core flux test can be carried out. This may take the form of an hour long test with about rated flux in the core, using about 10 turns of 11 kV cable wrapped around the core and fed from a suitable 11 kV source, and using an infra-red camera to scan the bore to monitor its temperature. Easier, but less positive, is a low flux test using one turn of light current cable and a magnetic imperfection detector.

It is not easy to ensure that the stator winding is dry enough to make an insulation resistance test meaningful, though a technique of applying a vacuum to the winding has been used. A 2 or 2.5 kV motor­ised megger should be used, monitoring one phase at a l1me, ana mamtam'mg fhe test tor l 0 minutes so that the polarisation index can be obtained. It is not normal to apply a high voltage test, the only ex­ception being after some damage has occurred, possi­bly with partial replacement of the winding, when an agreed HV test on the remaining bars gives some reassurance.

11.5 Reassembly With the rotor reassembled, mechani~·a! checks such as alignment, axial clearances and concentricity of cou­plings, and of the rotor in the stator, arc carried out, and that all locking plates and other cle\ ices are pro­perly assembled. All jointing materials, 'uch as gaskets, 0-rings, jointing compound, etc., should be renewed, and the appropriate leakage tests 'carried out.

It is so important that small metallic items do not fall into, or get left inside, the generator, where they could be drawn into the windings, that a strict ac­counting system for such items is recommended. Several expensive failures have occurred a short time after a major maintenance outage, due to this cause.

11.6 Diagnosis If the reading of any instrument has been outside its expected limit, or caused concern in other ways, it is sensible to investigate its possible causes during an outage. It may be tempting to extend the operating regime beyond its normal level, before such an out­age, in order to observe the effects, but this is not recommended, since a 'stable' fault hch been known to become 'unstable' during such operation. causing problems when the unit is recommissioned.

Specialised techniques, some in their de1 elopment phase, may be a\ ailable to assist in ,uspected fault location, and up to date advice should be sought.

Sometimes readings of more than one type may be high, though not so high as to be alarming in

557

Page 130: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

• - 1

!

' amination is made. Defects greater than 2 mm should - : be ground out, blending in the .ground area so that

' there are no discontinuities. Finally, the ring must · be re-treated with its protective finish before being i refitted. The whole operation requires great skill and \ experience, and though it can be carried out at site, . it is better done at the manufacturer's works, fol­' lowing which the rotor can be subjected to overspeed !: and balancing runs. These comments also apply to 1 exciter end rings.

· '· Examination of the stator core can be carried out ' . by inspecting the bore for loose areas, which can t be tightened by insertions of hard insulation, or by

treating with an epoxy-based liquid having low sur­face tension which will penetrate between the la­minations. Ventilation ducts should be inspected for

:·debris, blockages and broken spacer bars. The back :, of the core will reveal excessive welding of core to

core bars, or damaged core bar insulation, where this is fitted. Some core back burning, and some

·fretting products (e.g., 'cocoa dust') seems to be :tinnocuous. The core frame can be inspected for ob­

vious signs of damage, and patches of overheated paint or metal should be investigated.

Every stator slot wedge should be checked for tight­ness along its whole length, using a tightness tester developed in 1985, or by tapping with a coin or simi­lar object to observe the expected 'ringing', indicative of a tight slot. Airgap flux coils can be fitted or

. renewed at this stage. Stator end windings can be more thoroughly checked

than as described in the previous section. Signs of . .looseness of packings, fretting, slack fastenings, etc., .are all indicative of movement. If there are unfilled :bags between coils, these can be filled with epoxy resin at this stage. The surfaces should be cleaned using a proprietary cleaner suitable for electrical windings, but it is not recommended that repainting is under-

·. taken without the manufacturer's advice. If a 'worm­hole' (made by small conducting particles) is found, the particle should be removed and the insulation patched rather than left iu, possibly to break through

;'into the copper. ;, The state of the hoses and their connecting joints

.'·should be checked. A leakage test on the stator wind­, 1ng, using vacuum or pressurised air with a tracer . gas, will reveal any significant leaks. It may be :::considered prudent to renew all the rubber 0-rings, ~.both in these locations and elsewhere, if they have .~peen in service for several years. Care must be taken ji'tb follow the assembly instructions meticulously, as yovertightening may damage the joints. :~} The opportunity should be taken to clean the sta­tor casing, particularly at the bottom, noting if water

:'has collected, and checking that the flow to the leak­:age detector is unobstructed.

Insulation resistance tests should be carried out 'on the rotor winding, using a 500 or 1000 V megger, ,and on excitation windings. An RSO test could also

Maintenance, testing and diagnosis

be performed on the rotor winding, with slipring brushes lifted.

If any hot spots in the stator core are suspected, or as a reassurance exercise, a core flux test can be carried out. This may take the form of an hour long test with about rated flux in the core, using about 10 turns of II k V cable wrapped around the core and fed from a suitable II kV source, and using an infra-red camera to scan the bore to monitor its temperature. Easier, but less positive, is a low flux test using one turn of light current cable and a magnetic imperfection detector.

It is not easy to ensure that the stator winding is dry enough to make an insulation resistance test meaningful, though a technique of applying a vacuum to. the winding has been used. A 2 or 2.5 kV motor­ised megger should be used, monitoring one phase at a time, and maintaining the test for I 0 minutes so that the polarisation index can be obtained. It is not normal to apply a high voltage test, the only ex­ception being after some damage has occurred, possi­bly with partial replacement of the winding, when an agreed HV test on the remaining bars gives some reassurance.

11.5 Reassembly With the rotor reassembled, mechanical checks such as alignment, axial clearances and concentricity of cou­plings, and of the rotor in the stator, are carried out, and that all locking plates and other devices are pro­perly assembled. All jointing materials, such as gaskets, 0-rings, jointing compound, etc., should be renewed, and the appropriate lekkage tests 'carried out.

It is so important that small metallic items do not fall into, or get left inside, the generator, where they could be drawn into the windings, that a strict ac­counting system for such items is recommended. Several expensive failures have occurred a short time after a major maintenance outage, due to this cause.

11 .6 Diagnosis If the reading of any instrument has been outside its expected limit, or caused concern in other ways, it is sensible to investigate its possible causes during an outage. It may be tempting to extend the operating regime beyond its normal level, before such an out­age, in order to observe the effects, but this is not recommended, since a 'stable' fault has been known to become 'unstable' during such operation, causing problems when the unit is recommissioned.

Specialised techniques, some in their development phase, may be available to assist in suspected fault location, and up to date advice should be sought.

Sometimes readings of more than one type may be high, though not so high as to be alarming in

Page 131: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

----

The generator

themselves. Wheh judged jointly, clues may be ob­tained which individual' ~eadings might not have re­vealed.

12 Future developments

12.1 Extension of present designs The choice of 3000 or 1500 r/min for future turbine­generators is made almost entirely from considerations of the steam turbine and its steam cycle. ln general, if a two-pole generator can be designed and manu­factured at a particular rating, then so can a four­pole generator, its overall dimensions will be a little larger.

The present UK designs with water cooled stator windings and hydrogen cooled stator core and rotor can be extended to .at least 1300 MW by extrapola­tion. Increases of the order of lOOJo to the rotor and casing diameters, electrical loading (ampere conductors per metre of circumference), magnetic densities and voltage, and perhaps 25% on length over the pre­sent designs, would be envisaged (see Fig 6.3). The increased diameter and length of the rotor result in the critical speeds and alternating bending stesses being similar to those of the present machines. A judgement would have to be made about the number of parallel paths in the stator winding of a two-pole machine. If only two paths are used, the number of slots and bars is low, but the bar forces become very large; if four are used the circuits cannot be exactly balanced, and circulating currents and losses are generated. Parameters, such as reactances and effi­ciencies, would not be very different from those of the present machines.

12.2 Extension of water cooling Since water cooling has been used so effectively for the stator winding, it may be wondered why it is not used in the rotor winding where space is at such a premium. Water cooled rotor windings have been successfully operated; in the UK in a 500 MW unit with an experimental rotor for a few months, and internationally in a few units commercially.

The more intensive cooling provided by water means that smaller winding copper sections can be used, but this increases the resistance and therefore the l 2R loss. In a hydrogen cooled 660 MW rotor, this loss is about 2.5 MW at rated load, so a worthwhile reduction in section brings an expensive loss penalty. There are difficult problems to be solved in feeding the water into and out of the rotating rotor, but the major concern is that the centrifugal force imposes very high pressures (20 MPa) in the water circuit,

558

Chapter 6

which the plumbing and insulated connections have to withstand with no detectable leakage. Stainless steel pipes, with some welds having to be made in situ, were found to be necessary in the UK experience.

Nevertheless, water cooling the rotor winding and other parts, for example, the stator core, may be an answer if unit ratings much above 1300 MW are en­visaged. One difficulty, that of aqueous stress cor­rosion of rotor end rings, has been removed with the advent of 18/18 rings. A major advantage is that in an all-water-cooled generator, hydrogen is no longer necessary, and the casing can be of much lighter construction. The rotor can operate in a partial vacuum to reduce windage losses.

12.3 Slotless generators The very large radial dimension of the air gap in the 660 MW design appears to be a waste of space, and prompted much activity in the 1970s into the design of generators with slotless stators and even slotless rotors. In a slotless stator, winding conductors oc­cupied a radial dimension of about half the stator slot depth, and since there were no teeth, could occupy twice the circumferential distance. This is economical on outer core diameter, and because the conductor bars are not embedded in iron slots, a more eco­nomical design of insulation should be possible.

The idea has not been pursued, largely because it was overtaken by the superconducting generator concept, which promised greater economies of size, better efficiency and the prospect of much larger unit ratings than any other design.

12.4 Superconducting generators The phenomenon of superconductivity can be applied to DC circuits, but cannot sensibly be used with the rapidly changing fluxes and currents involved with 50 Hz (see Fig 6.95). It is therefore used only in the rotor windings, where it has two advantages:

• The rotor I2R loss is reduced to zero.

• The rotor current and MMF can be very large, so that higher levels of flux density can be used than are permitted by iron saturation.

The need to maintain the rotor winding at a tem­perature of 10 K means that only that amount of heat which can be removed by the refrigerant can be allowed to pass into the rotor, so that elaborate heat shields are necessary. Liquid helium is used as the refrigerant, the windings being made of a ni­obium-tin alloy embedded in a copper matrix. The rotor body is made from a stainless steel forging.

Page 132: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

--- DRIVE END

Other types of generator

LAMINATED IRON CORE

CONCRETE STATOR

STATOR WINDING

OUTER ROTOR

INNER ROTOR WITH SUPERCONDUCTING WINDING

NON-DRIVE END.

TAIL BEARING

FIG. 6.95 Prototype superconducting 500 MW generator

At the higher flux densities envisaged, an iron core offers no advantages and the disadvantage of the magnetic core loss, so a cast 'concrete' core is en­visaged. Some form of outer environmental screen around the core is necessary to prevent leakage flux from inducing currents in support steelwork, etc., this can take the form of an annular magnetic or conductin,g copper scr.een.

Many problems remain to be solved, and develop­ment is ongoing in seyeral countries. If the technique reaches the stage where reliability is as good as for conventional machines, it offers the possibility of up to 5000 MW in one generating unit, a prospect not available through any other known technology.

12.5 Auxiliary systems The most likely other areas for new developments are those of instrumentation, control and diagnosis.

New techniques are continually being investigated for instrumentation, and in the environment of a gen­erator, the means of communicating the signal non­electrically in order to avoid the pick-up of spurious electromagnetic signals and noise are very well worth pursuing. Here, fibre optics are expected to be pro­minent. Also, the use <;>f microprocessors to relate one parameter to others, as previously noted, will become more common. Perhaps automatic diagnostic tech­niques will reach a stage where they can be used with confidence, and selective recording of non-standard signals will be introduced more widely.

It should be recognised that generator design and manufacturing techniques are old-established. Ma-

'

chines from an established design achieve a settled reliability of better than 990Jo, and operate at an efficiency of better than 98.5%. Those breakdowns which do occur are generally due to lapses in quality control, or if in old machines, to practices long since overtaken. Thus the impetus for embracing new ma­terials and technologies is not great.

13 Other types of generator Generators, other than the 500 and 660 MW turbine­generators and direct coupled AC exciters for tur­bine-generators, described in the previous sections, m operation by the CEGB include:

e Turbine-generators of lower rating.

• Water turbine driven salient-pole synchronous generators.

• Diesel engine driven salient-pole generators.

• Induction generators.

A very brief survey of these groups follows.

13.1 Turbine-type generators of lower rating Virtually all the steam turbine driven turbine-generators now in operation are hydrogen cooled. At the lower end of the range, machines of 60 MW have a rated pressure of 0.1 bar, i.e., just above atmospheric. Above 200 MW, water cooled stator windings are used,

559

Page 133: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator

though there are some units in which higher pressure hydrogen is blown through the hollow conductors of the stator winding. '

In other respects, the generators are very similar to the larger, more modern units, except that they are less intensively rated. In some cases, a degree of refurbishment has been carried out to extend their operating lives beyond the 25 years or so already achieved.

There are also a number of gas turbine driven generators intended for peak load and synchronous compensation duty. These have ratings up to 70 MW, and are usually air cooled. The single-piece stators are of lighter construction than is necessary in hydrogen cooled units, and the auxiliary systems are minimal. In some cases they were designed for unmanned sta­tions, so manual monitoring equipment and sophis­ticated logging is minimal. Brushless excitation is universal, for reasons of minimum maintenance, and even the fuses protecting the excitation diodes have been omitted.

A noteworthy feature of the most recent of these units is the facility to disengage the prime mover, or, in the case of the Quad-Olympus units (Fig 6.96) in which the generator is driven at both ends, both prime movers. Then, after a period of peak load gen­eration, the synchronous clutches are disengaged, leav­ing the generators operating as synchronous compen­sators, with excitation controlled to suit the require­ments of the system. When peak load or emergency generation is next required, the gas turbines are run­up to speed and the clutches moved into engagement.

13.2 Water turbine driven salient-pole syn­chronous generators There are only a few of these on the CEGB system, but the most recent, the pumped-storage units at Oinorwig, rate a brief description to complement the water turbine section in Chapter 5.

The six generators are each rated at 330 MW, 0.95 power factor, 18 kV, 500 r/min, and have a motor rating slightly lower when operating in the reverse direction.

The very onerous requirements included:

• Full speed, no-load to full-load, in I 0 s.

• From rest to full-load in 100 s.

• From full-load pumping to full-load generating in 90 s.

• 5000 stop/start cycles per year.

• Multiple load cycling from 5007o to 100% for system frequency regulation.

• Availability of 9807o and mode change reliability of 99%.

560

Chapter 6

The comparatively low speed meant large diameters, and 011-~itt:: assembly of the stators was essential (see Fig 6.97). Air cooling was adopted, mainly for rea­sons of reliability. Partly on account of this, the stator winding bars were unusually deep, with a large number of subconductors, necessitating a 540° Roebel transposition. The core was stacked in situ, being com­pressed with hydraulic jacks at intervals, and bonded together for mechanical stability.

A fabricated steel spider surrounds the forged steel shaft and carries the keyed-on laminated rim and poles. Great care was taken to ensure the integrity of the welds, which are subject to an unusual amount of cyclic stressing.

Ventilation is provided by motor-driven fans blow­ing cooled air onto the stator end windings top and bottom, with some booster fans for the centre of the core. Water cooled heat exchangers are mounted at the outside diameter of the core.

The thrust bearing has an arduous duty, having a load of 510 tonnes and requiring larger thrust pads, at the specific loading, than had previously been used at the specific loading and speed. Each pad rests on a 'mattress' of coiled springs, and is arranged to pivot centrally to allow for rotation in both directions. Lubrication is by oil bath and natu­ral oil circulation, with an immersed water cooled heat exchanger.

13.2.1 Excitation and control Two variable-frequency starting equipments are pro­vided for the station, each rated at 14.8 MV A, consist­ing of air cooled thyristor rectifier/ AC connector/ inverter banks.

On starting as a pump, the stator winding is fed with low frequency AC from the starter, using forced commutation at speeds below I 0% and natural com­mutation thereafter. It is run to just above 500 r/min and is synchronised as it runs down through syn­chronous speed. There are also arrangements for start­ing one unit as a pump from another, being driven up to speed by its turbine.

Excitation power is taken from the generator ter­minals, through a transformer to a thyristor bridge, whose output is controlled by the A VR, and then to the sliprings which are located at the top end of the rotor shaft.

The synchronous operation of such machines fol­lows very closely that of steam-driven turbine-gen­erators. The electromagnetic loading is considerably less, leading to a smaller radial air gap. The very different magnetic path presented by a pole centre line and an inter-pole gap results in marked differ­ences in direct axis and quadrature axis synchronous reactances, compared to a turbine-generator in which they are almost identical; this is the 'saliency' effect. By applying excitation in the reverse direction to normal, an increase in the steady state stability can

Page 134: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

Ul (J) c.v

U1 m

• •

AIR INTAKE SPLITIERS

POWER TURBINE EXHAUST DUCTING

A C GENERATOR AIR INTAKE FILTER HOUSE

OLYMPUS GAS GENERATOR

AUTOMATIC DRY ROLL TYPE AIR INTAKE FILTERS

BYPASS DOORS

GAS GENERATOR INSTRUME PANEL

GAS GENERATOR LUB. OIL

FUEL VALVE CABINET

GAS GENERATOR AIR INTAKE FILTER HOUSE

GAS GENERATOR ACOUSTIC CELL

TURBINE AND GENERATOR LUB. OIL PACKAGE

POWER TURBINE ACOUSTIC SCREEN

A C GENERATOR

MAIN GENERATOR CONNECTIONS

BRUSHLESS EXC ,TEA

LUTCH AND BEARING ASSEMBLY

POWER TURBINE ASSEMBLY

CORNER BEND

FIG. 6.96 Quad-Olympus generator

0 ~

::r (1)

.... -< '0 (1) (J)

0 ._.., (Q (1) ::J (1) .... Ill ~

0 ....

Page 135: 63863090 Modern Power Station Practice VolumeC Chapter6 the Generator

The generator Chapter 6

FIG. 6.97 Dinorwig motor-generator during site winding (see also colour photograph between pp 482 and 483)

be gained, i.e., operation further into the leading reactive regime becomes possible.

13.2.2 Other features

Other features peculiar to these machines include the continuing integrity of stator bar insulation in an air environment, the continuing stability of the bonded stator core and the built-up rotors, the vacuum ex­traction of dust from the shaft brakes, and the very high overspeeds possible; e.g., a transient value of 1.5 for Dinorwig.

13.3 Diesel engine driven salient-pole generators

These machines, with ratings of a few MW, are in-

562

stalled in a few stations for emergency duty. The generators are standard industrial units with proven high reliability. The need for sudden run-up after long periods at standstill means that brushless excitation and casing heaters are essential.

13.4 Induction generators These machines, rated usually at less than I MW, are used in remotely controlled run-of-the-river hydro plants, and in wind generators on an experimental basis. Such machines do not operate synchronously, but have a characteristic similar to induction motors except that they run at above synchronous speed. A greater input from the prime mover increases the power output. Like all induction machines, they draw their magnetising current from the system and there­fore do not require an excitation supply.

,, r ·'