60301Line & Cable Modelling 1.2
-
Upload
femi-obisesan -
Category
Documents
-
view
214 -
download
0
Transcript of 60301Line & Cable Modelling 1.2
-
8/2/2019 60301Line & Cable Modelling 1.2
1/45
Line, Cable and Load Modelling
1.1
-
8/2/2019 60301Line & Cable Modelling 1.2
2/45
Goals
To understand the basic electrical parameters of anoverhead line or a cable
1.2
length of the system affects the way in which it ismodelled
To understand the types of loads on the system andtheir response to variations in voltage
-
8/2/2019 60301Line & Cable Modelling 1.2
3/45
1.3
-
8/2/2019 60301Line & Cable Modelling 1.2
4/45
1.4
Common features metallic conductor & dielectric (air in the case of
the overhead line, XLPE in the case of the cable)
-
8/2/2019 60301Line & Cable Modelling 1.2
5/45
1.5
erm na ower
Transition from
OHL to cable
-
8/2/2019 60301Line & Cable Modelling 1.2
6/45
Introduction To Basic Line Model
We need a model that will represent the propertiesof an overhead line / cable
For a conductor we need to consider resistance
1.6
and inductance
For the dielectric, we need to consider capacitanceand conductance
We will see that these properties can vary as afunction of temperature and frequency
-
8/2/2019 60301Line & Cable Modelling 1.2
7/45
Introduction To Basic Line Model
Line / cable model must be able to function in a number ofdifferent applications.
The following are examples of potential uses for a line / cable
1.7
Volt drop estimation
Power flow studies
Temporary overvoltage studies (e.g. ferroresonance)
Transient overvoltage studies (e.g. lightning)
The requirements of these simulation types are very different.Generally, the faster the event being simulated, the morecomplex the model.
-
8/2/2019 60301Line & Cable Modelling 1.2
8/45
Equivalent of Line Or Cable
Typical model of line of cable uses lumped sections of resistance,
inductance, capacitance and conductance
How many of these sections are used in a cable model dependson the modelling need
1.8
on both the length of the cable and the intended use of the model
CONDUCTOR
INSULANT
-
8/2/2019 60301Line & Cable Modelling 1.2
9/45
Resistance
Resistance per metre of a conductor is:
20
-1
1.9
A20
-
8/2/2019 60301Line & Cable Modelling 1.2
10/45
Resistance
Variation in conductor resistance with temperature must beconsidered
[ ])20(1 2020 += tRRt m-1
1.10
Skin effect and proximity effect reduce the usable area ofconductor in practice
Tabulated values from manufacturers data sheets reflectimpact of these effects
Resistance is frequency dependent increases as frequencyincreases
-
8/2/2019 60301Line & Cable Modelling 1.2
11/45
Resistance
Coefficients below mean that a 50K shift in temperature means a19.5% increase in resistance for copper
How should this be included in modelling?
1.11
Material Resistivity / m@ 20C
TemperatureCoefficient per K
Copper 1.72 x 10-8 3.9 x 10-3
Aluminium 2.83 x 10-8
4.0 x 10-3
Lead 21.4 x 10-8 4.0 x 10-3
Steel 13.8 x 10-8 4.5 x 10-3
-
8/2/2019 60301Line & Cable Modelling 1.2
12/45
Inductance
Line and cable inductance made up from interaction ofmagnetic field with current
Both self and mutual inductances are present
For line mutual inductances with all other conductors
1.12
(earth assumed zero resistance and line currents arebalanced)
For screened cable, mutual inductance with sheath /armour
Frequency dependent falls slightly for increase infrequency (self-inductance dependent)
Overall geometries are more important than conductor
type
-
8/2/2019 60301Line & Cable Modelling 1.2
13/45
Inductance
Self Inductance
1
8
= HmL oself
1.13
bundletheofradiusmeangeometrictheisDand
bundlesconductorbetweendistancemeangeometrictheiswhere
ln2
s
01
eq
s
eq
D
D
DL
=
-
8/2/2019 60301Line & Cable Modelling 1.2
14/45
Inductance
Example below shows the positive sequence impedance calculatedfor three types of overhead line
Size of conductor has little impact on reactive part
In contrast, the use of a twin conductor as opposed to a single
1.14
As expected, resistance is proportional to cross-sectional area
Line voltage / Conductor details Positive sequence impedance (ohms/km)
132kV, 1 x 175mm2 0.0177+j0.402
132kV, 2 x 175mm2 0.0089+j0.293
132kV, 1 x 400mm2 0.0076+j0.379
-
8/2/2019 60301Line & Cable Modelling 1.2
15/45
Inductance And Capacitance
For full derivation of inductance and capacitancesee:
1.15
-
-
8/2/2019 60301Line & Cable Modelling 1.2
16/45
Capacitance Of An Overhead Line Equivalent capacitance to earth of a line made up of a number of
capacitances in parallel / series
Not frequency dependent (at frequencies of interest for powersystems)
Capacitance to earth of a two conductor line is:
1.16
For a multiple conductor line (fully transposed) this becomes:
ln
== Fm
rDv
Cii
bundleainconductorsbetweendistancedandradiusconductorr
bundles,conductorbetweendistancemeangeometricDwhere
ln2
eq
10
==
=
= Fm
rd
DC eq
-
8/2/2019 60301Line & Cable Modelling 1.2
17/45
Capacitance For a screened cable, capacitance to earth is:
insulationofradiusouterRwhere
ln
2 10
=
==
Fm
r
Rv
qC
r
1.17
Cable capacitance to earth is higher per metre than OHconductor
This results from higher relative permittivity and smaller
spacing between conductor and earth Frequency dependent but only significant in transient studies
capacitance generally falls as a function of frequency
conductorofradiusouterr =
-
8/2/2019 60301Line & Cable Modelling 1.2
18/45
Comparison Of Line/Cable Parameters
Examples below refer to lines/cables of similar ratings
Lines and cables have similar series inductance values
Cables have a much higher shunt capacitance
Resistance is dependent on conductor size
1.18
un con uc ance no s gn can n mos sys ems u may nee
to be considered for some DC applications
Cable Line
275kV 315nF/km 30nF/km
400kV 330nF/km 34nF/km
Cable Line
275kV 0.7mH/km 1.1mH/km
400kV 0.7mH/km 0.9mH/km
InductanceCapacitance
-
8/2/2019 60301Line & Cable Modelling 1.2
19/45
Short Line Model
Simple model of resistance and inductance. Capacitance neglected
For short overhead lines (approx. 50 miles) where shuntcapacitance is not important / significant
Not suitable for transient studies
1.19
Vrs
I
XLR
)( LRS jXRIVV ++=
-
8/2/2019 60301Line & Cable Modelling 1.2
20/45
Medium Line Model
For medium length line, shunt capacitance must be included
Middle ground model, not fully realistic but better than short line
For medium length overhead lines (approx. 150 miles)
Not suitable for transient studies
1.20
Computationally straightforward
VrVs
IrXLR
-jXC/2-jXC/2
Is
-
8/2/2019 60301Line & Cable Modelling 1.2
21/45
Medium Line Model
Lr
rrs
c
rs
rs
jXRZZYV
IVV
jXY
YVYV
II
+=
++=
=++=
)where(
)/1where(22
1.21
VrVs
IrXLR
-jXC/2- XC/2
Is I
rrs
rrs
IZYZY
YVI
VZY
ZIV
++
+=
++=
1
24
1
12
or
-
8/2/2019 60301Line & Cable Modelling 1.2
22/45
Medium Line Model
VrVs
IrXLR
- XC/2- XC/2
Is I
1.22
+==
+==
+=
+=
411
2
ZYYCZB
ZYDA
DICVI
BIAVV
rrs
rrs
-
8/2/2019 60301Line & Cable Modelling 1.2
23/45
Long Line Model
For long length line, distributed parameter model mustbe used
Can represent potential drop along the line and
1.23
production/ consumption along line
Accurate model - also used for transient analysis
xx+x
lx rx
gx cx v
i
v+v
i+i
vr
ir
vs
is
-
8/2/2019 60301Line & Cable Modelling 1.2
24/45
Long Line Model
Long line model introduces surge impedance and propagationconstant familiar from travelling wave analysis
Propagation constant leads to existence of time delay
In travelling wave studies, complications exist from frequencydependence of z and y.
1.24
impedancesticcharactericonstant,npropagatiodistance,
sinhsinhcosh
===
==
====
+=
+=
c
c
c
c
rrs
rrs
Zl
zyy
zZ
Z
lClZBlDA
DICVI
BIAVV
-
8/2/2019 60301Line & Cable Modelling 1.2
25/45
Cable Modelling Example A 275kV cable has the following parameters (per phase):
R: 0.06/km Xl: j0.2/km
C: 0.17F/km
1.25
The thermal rating of the cable is 1000A. Using the short andmedium length line models, calculate the sending end current,voltage and injected power based on the following loads beingapplied to the end of a 75km length of cable:
125MVA @ 0.98pf lagging (per phase), 1pu receiving end voltage 125MVA @ 0.98pf leading (per phase), 1pu receiving end voltage
-
8/2/2019 60301Line & Cable Modelling 1.2
26/45
Cable Modelling Example Answers Use of short cable model shows no difference between receiving and start
end current
In both cases, medium length model sees capacitive flows at start of cable.Not the case for the short model
Significant differences in calculated current values smaller difference involtage drops
1.26
Vsend Isend Ssend
Leading Medium (155+j13.7)kV 0.98pu
(744+j785)A 1.08pu
(126-j111)MVA
Leading Short (160+j12.3)kV
1.01pu
(771+j157)A
0.79pu
(125-j16)MVA
Lagging Medium (160+j12.3)kV 1.01pu
(747+j481)A 0.89pu
(125-j68)MVA
Lagging Short (164+j10.9)kV
1.04pu
(771-j156)A
0.79pu
(125+j34)MVA
-
8/2/2019 60301Line & Cable Modelling 1.2
27/45
Cable Modelling Example Answers Long length model and medium length models give similar results for sending
end current
Medium length model not accurate for use in sending end voltage estimation
Computer software can always implement long line models by hand this isnot so straightforward (exponentials of complex numbers required)
Errors will reduce as system length reduces
1.27
Vsend Isend Ssend
Leading Long (159+j25.1)kV 1.01pu
(758+j791)A 1.1pu
(140-j107)MVA
Leading Medium (155+j13.7)kV
0.98pu
(744+j785)A
1.08pu
(126-j111)MVA
Lagging Long (168+j22.4)kV 1.07pu
(759+j482)A 0.9pu
(138-j64)MVA
Lagging Medium (160+j12.3)kV
1.01pu
(747+j481)A
0.89pu
(125-j68)MVA
-
8/2/2019 60301Line & Cable Modelling 1.2
28/45
Impact Of System Capacitance Example below shows results of calculations performed with long and
medium length models on a cable and line (lagging pf). 1000A base retained
for conversion of current to per-unit. Line capacitance around one order of magnitude less than the cable
Voltage estimation from medium length line model now more accurate
Vsend Isend Ssend
1.28
Cable - Long (168+j22.4)kV 1.07pu
(759+j482)A 0.9pu
(138-j64)MVA
Cable - Medium (160+j12.3)kV 1.01pu
(747+j481)A 0.89pu
(125-j68)MVA
Line - Long (170+j21.8)kV 1.08pu
(770-j92)A 0.78pu
(129+j32)MVA
Line - Medium (164+j11.0)kV 1.04pu
(769-j92)A 0.77pu
(125+j23)MVA
-
8/2/2019 60301Line & Cable Modelling 1.2
29/45
Reactive Losses Short line model only allows consumption of reactive power
even when system is lightly loaded
800.00
1000.00
1.29
-400.00
-200.00
0.00
200.00
400.00
600.00
0.00 200.00 400.00 600.00 800.00 1000.00 1200.00 1400.00 1600.00
Power / MW
ReactiveLosses/MVAR
50km 100km 200km Short Line - 200km
-
8/2/2019 60301Line & Cable Modelling 1.2
30/45
Impact Of Capacitance On Performance
PI Model of a 275kV Cable, 630mm2
Let us plot possible combinations of real andimaginary current at receiving end
1.30
j0.2
0.062
-j38350 -j38350Vs
Vr
IrIs
-
8/2/2019 60301Line & Cable Modelling 1.2
31/45
600
800
1000
1200
tA
tR
ecev
ingE
nd/
A
Reactive Power Flow To Sending EndReactive Power Flow From Sending End
Optimal power transferachieved for long cable when
50% of charging current
supplied from either end
allowin maximum real current
1.31
0
200
400
-1200 -800 -400 0 400 800 1200
Imaginary Current At Receiving End / A
R
ealC
urren
1km 50km 100km
Reactive power transfer to sending
end imposes thermal limit at sending
end where 860A of charging current
flows. Maximum of 200A reactivecurrent can flow at the receiving end
Inductive current at receiving end at
a maximum owing to thermal
constraint. Current at start of cable is
reduced owing to the contribution of
the capacitive current.
-
8/2/2019 60301Line & Cable Modelling 1.2
32/45
Travelling Wave Theory
Travelling wave theory describes the propagation ofsurges along overhead lines and cables. It is importantto understand the behaviour of lightning/switchingsurges
1.32
Travelling waves: have a velocity that depends on the item of plant through
which they are propagating
are altered in magnitude and shape when they propagatethrough a piece of plant
are reflected at discontinuities in surge impedance
-
8/2/2019 60301Line & Cable Modelling 1.2
33/45
Major Travelling Wave Equations
At any point on a lossless line, the voltage can beexpressed as:
reflectedincidentalter VVV +=min
1.33
Voltage and current are related by surge impedancereflecteincidentalter III +=min
c
reflected
c
incidentalter
Z
V
Z
VI =min
-
8/2/2019 60301Line & Cable Modelling 1.2
34/45
Major Travelling Wave Equations
The surge impedance can be written as:
c
lZc =
1.34
where l and c are impedance and capacitance per unit length,
Surge impedances range from 400 for lines to 25 for cables
Waveforms propagate along the line with a velocity of:
Velocities range from near light speed (300m/s) in lines tohalf of this (150m/s) in cables
lcv
1=
-
8/2/2019 60301Line & Cable Modelling 1.2
35/45
Behaviour At An Open Circuit
At an open circuit, transmitted current must be zero
reflectedincidentalter VVV +=minreflecteincidentalterIII +=min
1.35
incidenreflectedincidentcincidentalter
Cincidentcincidentalter
Creflectedcincidentalter
creflectedreflectedcincidentincident
VVVZIV
ZIZIV
ZIZIV
ZIVZIV
===
+=
=
==
22
and
min
min
min
reflectedincident
reflectedincident
II
II
=
+=0
-
8/2/2019 60301Line & Cable Modelling 1.2
36/45
Behaviour At A Short Circuit
At a short circuit, transmitted voltage must be zero
reflectedincidentalter
ZVIZVI
III
==
+=
/and/
minreflectedincidentalter
VV
VVV
+=
+=
0
min
1.36
incidentreflectedincidentcincidentalter
Cincidentcincidentalter
Creflectedcincidentalter
IIIZVI
ZVZVI
ZVZVI
===
+=
=
22
//
//
min
min
min
reflectedincident VV =
-
8/2/2019 60301Line & Cable Modelling 1.2
37/45
Behaviour At A Specific Impedance
creflectedcincidenttermterm
termtermtermcreflectedreflectedcincidentincident
reflectedincidentterm
ZVZVZV
ZVIZVIZVI
III
=
===
+=
///
/,/,/
1.37termc
term
term
incident
incident
term
cterm
termincidenttermcterm
termincidentincidenttermcterm
reflectedincidentterm
ZZ
Z
V
V
VZ
ZV
VVZZV
VVVZZVVVV
+=
=
+
=
+=+=
2
21
]2[)/(
)]([)/(g...rearranginsoand:Also
-
8/2/2019 60301Line & Cable Modelling 1.2
38/45
Transmission / Reflection Coefficients Transmission and reflection coefficients (relating magnitude of
transmitted and reflected wave to incident) can be derived asfollows:
Voltagetransmission
VoltageReflection
CurrentTransmission
Current Reflection
BasicalterZ min2 alter ZZ min Z2
alter ZZ min
1.38
Note in all cases the values of transmitted and reflectedpulses when the terminal surge impedance is equal to the line
surge impedance Transmitted pulses have a magnitude of 1pu Surge impedance termination appears as an infinite line
Reflected pulses are all zero
t
alterZZ+ min
r
alter ZZ +min
t
alterZZ+ min
r
alter ZZ +min
-
8/2/2019 60301Line & Cable Modelling 1.2
39/45
Transmission / Reflection Coefficients
Table below shows transmission and reflectioncoefficients for three main cases
Complex impedances behave differently as a
1.39
.
Capacitors act as a short circuit Inductors act as an open circuit
Line Terminated With: at=voltagetransmission
coefficient
ar=voltagereflection
coefficient
bt=currenttransmission
coefficient
br=currentreflection
coefficient
Line Surge Impedance 1 0 1 0Short Circuit 0 -1 2 1Open Circuit 2 1 0 -1
-
8/2/2019 60301Line & Cable Modelling 1.2
40/45
A voltage surge of 95kV is propagating down a 400overhead line and is transmitted into a 20 cable
The current in the overhead line will be95kV/400=237.5A
Practical Example - Overhead Line To Cable
1.40
ccor ng o e vo age ransm ss on equa on on e
previous slide:
Reflected voltage wave given using VT=VF+VRequation on former slide. Must be 9kV-95kV, i.e. -86kV
kVkVZZ
ZVV
lineOHcable
cablelineOHcable 0.9
40020
4095
2=
+
=
+=
-
8/2/2019 60301Line & Cable Modelling 1.2
41/45
Thevenin Equivalent To produce a Thevenin equivalent of a circuit:
Find voltage source with magnitude equal to open circuitresponse
Find impedance to give short circuit response
1pu voltage propagating into an open circuit willproduce a voltage of 2pu - this is the open circuit
1.41
response - voltage source of 2pu required
1pu current propagating into a short circuit will givea current of 2pu - this is the short circuit response -impedance equal to Zc required
LINE IMPEDANCE Z
2VincidentTERMINATIONIMPEDANCE
Vterminal
-
8/2/2019 60301Line & Cable Modelling 1.2
42/45
Multi-Line Substation Multi-line substation an important case, many
substations have multiple overhead lines connected.
Thevenin equivalent for system with n-lines connectedhas impedance of Z/n
1.42
2VincidentZ/ n-1 Vterminal
n
V
nZZ
nZVV incidentincidentterm
2
)1/(
)1/(2 =
+
=
-
8/2/2019 60301Line & Cable Modelling 1.2
43/45
Bewley Lattice Diagram Used to find voltages and current on points of finitelength systems
Transit times can be low in relation to waveform time
Firstly, all coefficients required must be calculated Cable Connection Z2Overhead Line Z1
1.43
Incoming Surge RVoltage
transmissionVoltage
ReflectionCurrent
TransmissionCurrent Reflection
BasicFormulae t
alter
alter aZZ
Z=
+ min
min2
r
alter
alter aZZ
ZZ=
+
min
min
t
alter
bZZ
Z=
+ min
2 r
alter
alter bZZ
ZZ=
+
min
min
OH Line to
Cable
21
22
ZZ
Z
+()
12
12
ZZ
ZZ
+
()
21
12
ZZ
Z
+
12
12
ZZ
ZZ
+
Cable -
ResistanceRZ
R
+2
2()
2
22
ZR
ZR
+
()
RZ
Z
+2
22
2
2
ZR
ZR
+
Cable to
OH Line21
12
ZZ
Z
+()
21
21
ZZ
ZZ
+
()
21
22
ZZ
Z
+
21
21
ZZ
ZZ
+
-
8/2/2019 60301Line & Cable Modelling 1.2
44/45
BewleyLattice
Diagram 0
RZ2Z1
e
e
e
e
e
e
e
1.44
4L/v
6L/v
Time
22e
e
23e
22e
2e
e
2e
23e
-
8/2/2019 60301Line & Cable Modelling 1.2
45/45
Further reading
There are many text books which have a classicaltreatment: See library shelves around 621.319
For example
1.45
,
Wiley
H Waddicor The Principles of Electric PowerTransmission