'6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with...
Transcript of '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with...
![Page 1: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/1.jpg)
SMART RELAYS D5096S – D5097S
D5293S - D5294S - D5295SSIL 3 Relay with Line & Load Diagnostics
DTS0536-4
![Page 2: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/2.jpg)
1. What Are Smart Relays?a. Relays + Diagnostics
b. Models: D5096S, D5097S, D5293S, D5294S and D5295S
2. Why Choosing Smart Relays?
3. Real-World Applicationsa. Normally-Energized solenoid valves
b. Strobes/beacons for Fire & Gas applications
c. Dual tone sounders for Fire & Gas applications
d. High-availability double-coil solenoid valves
e. Single-phase load interruption solenoid valves
4. Conclusions
![Page 3: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/3.jpg)
1. What Are Smart Relays?a. Relays + Diagnostics
b. Models: D5096S, D5097S, D5293S, D5294S and D5295S
2. Why Choosing Smart Relays?
3. Real-World Applicationsa. Normally-Energized solenoid valves
b. Strobes/beacons for Fire & Gas applications
c. Dual tone sounders for Fire & Gas applications
d. High-availability double-coil solenoid valves
e. Single-phase load interruption solenoid valves
4. Conclusions
![Page 4: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/4.jpg)
Relay
MatrixLine & Load
Diagnostic
Basic
concept
D5293S
2 NO Contacts in series
D5096S &
D5294S
2 x 2 NO Contacts
D5097S &
D5295S
2 x 2 NC Contacts
![Page 5: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/5.jpg)
Power
Supply
Diagnostics
Load:Solenoid Valve
Beacons/Strobes
Sounders…
24 Vdc
Digital IN
Digital
OUT
• Coil-to-contacts function
• Diagnostics functions
• Contact rating: 5 A – 250 Vac
• Zone 2 Installation
• Alarm: fault relay
• Coil-to-contacts function (SIL 3)
D5096S, D5097S
![Page 6: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/6.jpg)
Power
Supply
Modbus
Slave
Diagnostics
Load:Solenoid Valve
Beacons/Strobes
Sounders…
24 Vdc
Additional
Fault Out
Digital IN
Digital
OUT
Modbus
• Coil-to-contacts function
• Diagnostics functions
• Contact rating: 4 A – 250 Vac
• Zone 2 / Div. 2 Installation
• Alarm: fault relays, modbus
• Coil-to-contacts function (SIL 3)
Modbus
Slave
Diagnostics
• Diagnostics functions (SIL 2)
D5293S, D5294S, D5295S
![Page 7: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/7.jpg)
D5293S
D5293S – SIL 3 for Normally Energized (NE) Loads
D5293S
Off-line condition Normal condition (NE)
D5293S
Safe state condition
![Page 8: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/8.jpg)
D5293S – SIL 3 for Normally Energized (NE) Loads
Normal condition (NE)
D5293S D5293S
Safe state condition
1 relay fault
is not sufficient for
a dangerous failure!
LOAD DE-ACTIVATION
ON DEMAND
![Page 9: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/9.jpg)
D5293S – SIL 3 for Normally Energized (NE) Loads
Normal condition (NE)
D5293S D5293S
False trip condition
Low availability
AVAILABILITY
![Page 10: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/10.jpg)
D5096S &
D5294S
Normal condition (NE)
D5096S &
D5294S
Off-line conditionOff-line condition
D5096S &
D5294S
Safe state condition
D5096S & D5294S – SIL 3 for Normally Energized (NE) Loads
![Page 11: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/11.jpg)
D5096S & D5294S – SIL 3 for Normally Energized (NE) Loads
1 relay fault
is not sufficient for
a dangerous failure!
LOAD DE-ACTIVATION
ON DEMAND
D5096S &
D5294S
Normal condition (NE)
D5096S &
D5294S
Safe state condition
![Page 12: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/12.jpg)
D5096S & D5294S – SIL 3 for Normally Energized (NE) Loads
High availability
AVAILABILITY
D5096S &
D5294S
Normal condition (NE)
D5096S &
D5294S
False trip condition
![Page 13: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/13.jpg)
D5096S &
D5294S
Safe state condition
D5096S &
D5294S
Normal condition (ND)
D5096S &
D5294S
Off-line conditionOff-line condition
D5096S & D5294S – SIL 3 for Fire & Gas (F&G) / Normally De-Energized (ND) Loads
![Page 14: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/14.jpg)
D5096S &
D5294S
Normal condition (ND)
D5096S &
D5294S
Safe state condition
D5096S & D5294S – SIL 3 for Fire & Gas (F&G) / Normally De-Energized (ND) Loads
1 relay fault
is not sufficient for
a dangerous failure!
LOAD ACTIVATION
ON DEMAND
![Page 15: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/15.jpg)
D5096S &
D5294S
Normal condition (ND)
D5096S &
D5294S
False trip condition
D5096S & D5294S – SIL 3 for Fire & Gas (F&G) / Normally De-Energized (ND) Loads
AVAILABILITY
High availability
![Page 16: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/16.jpg)
D5097S &
D5295S
Normal condition (NE)
D5097S &
D5295S
Off-line conditionOff-line condition
D5097S &
D5295S
Safe state condition
D5097S & D5295S – SIL 3 for Normally Energized (NE) Loads
![Page 17: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/17.jpg)
D5097S & D5295S – SIL 3 for Normally Energized (NE) Loads
1 relay fault
is not sufficient for
a dangerous failure!
LOAD DE-ACTIVATION
ON DEMAND
D5097S &
D5295S
Normal condition (NE)
D5097S &
D5295S
Safe state condition
![Page 18: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/18.jpg)
D5097S & D5295S – SIL 3 for Normally Energized (NE) Loads
High availability
AVAILABILITY
D5097S &
D5295S
Normal condition (NE)
D5097S &
D5295S
False trip condition
![Page 19: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/19.jpg)
D5097S &
D5295S
Safe state condition
D5097S &
D5295S
Normal condition (ND)
D5097S &
D5295S
Off-line conditionOff-line condition
D5097S & D5295S – SIL 3 for Fire & Gas (F&G) / Normally De-Energized (ND) Loads
![Page 20: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/20.jpg)
D5097S &
D5295S
Normal condition (ND)
D5097S &
D5295S
Safe state condition
D5097S & D5295S – SIL 3 for Fire & Gas (F&G) / Normally De-Energized (ND) Loads
1 relay fault
is not sufficient for
a dangerous failure!
LOAD ACTIVATION
ON DEMAND
![Page 21: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/21.jpg)
D5097S &
D5295S
Normal condition (ND)
D5097S &
D5295S
False trip condition
D5097S & D5295S – SIL 3 for Fire & Gas (F&G) / Normally De-Energized (ND) Loads
AVAILABILITY
High availability
![Page 22: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/22.jpg)
Diagnostics
Load ON
D5293S
A
② Load
current
③ Internal coil integrity
V① Supply voltage
Load OFF
D5293S
V① Supply
voltage
![Page 23: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/23.jpg)
Diagnostics
Load ON
D5096S
② Load
current
① Supply voltage V
A
Load OFF
D5096S
② Load
Resistance
① Supply voltage V
R
![Page 24: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/24.jpg)
Diagnostics
Load ON
D5294S
② Load current
(configurable)
③ Internal coil integrity
① Supply voltage
(configurable) V
A
Load OFF
D5294S
② Load Resistance
(configurable)
③ Earth leakage
① Supply voltage
(configurable)
V
R
![Page 25: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/25.jpg)
Diagnostics
Load ON
D5097S
① Supply
voltage V
A
D5097S
Load OFF
② Load
Resistance
① Supply voltage V
R
② Load
current
![Page 26: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/26.jpg)
Diagnostics
Load ON
D5295S
① Supply voltage
(configurable) V
A
D5295S
④ Internal coil integrity
Load OFF
② Load Resistance
(configurable)
③ Earth leakage
① Supply voltage
(configurable)
V
R
② Load current
(configurable)
![Page 27: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/27.jpg)
Smart relay to System communication
D5293S
D5294S
D5295S
Fault relay
Pulse testing
Modbus
Fault on bus
DI
DO
Modbus
master
DI
D5096S
D5097S
![Page 28: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/28.jpg)
1. What Are Smart Relays?a. Relays + Diagnostics
b. Models: D5096S, D5097S, D5293S, D5294S and D5295S
2. Why Choosing Smart Relays?
3. Real-World Applicationsa. Normally-Energized solenoid valves
b. Strobes/beacons for Fire & Gas applications
c. Dual tone sounders for Fire & Gas applications
d. High-availability double-coil solenoid valves
e. Single-phase load interruption solenoid valves
4. Conclusions
![Page 29: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/29.jpg)
SystemSolenoid Valve
Command /Power
Diagnostics
1. Old systems DO do not support load diagnostics
X
![Page 30: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/30.jpg)
1. Smart Relays make diagnostics available to the system
D5096S, D5097S,
D5293S, D5294S, D5295S
SystemSolenoid Valve
Supply
Command /Power
Diagnostics
![Page 31: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/31.jpg)
SystemSolenoid Valve
Command /Power
2. All systems DO are voltage/current limited
X
![Page 32: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/32.jpg)
D5096S, D5097S,
D5293S, D5294S, D5295S
SystemSolenoid Valve
Supply
Command /Power
Diagnostics
2. Smart Relays extend voltage/current with Diagnostics
![Page 33: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/33.jpg)
SystemBeacon
Command /Power
Diagnostics
3. DO Diagnostics limits (extreme loads, earth leakage…)
??
![Page 34: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/34.jpg)
D5096S, D5097S,
D5293S, D5294S, D5295S
SystemBeacon
Supply
Command /Power
Diagnostics
3. Smart Relays extend DO Diagnostics capabilities
![Page 35: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/35.jpg)
No Diagnostics
Line open & short circuit
Load open & short circuit
Load supply monitoring
• Modbus
• Configurable thresholds
Internal coil integrity
Load earth leakage
Line open & short circuit
Load open & short circuit
Load supply monitoring
D5094S D5095S
D5096S D5097S
D5293S
D5294S D5295SDiagnostics
![Page 36: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/36.jpg)
1. What Are Smart Relays?a. Relays + Diagnostics
b. Models: D5096S, D5097S, D5293S, D5294S and D5295S
2. Why Choosing Smart Relays?
3. Real-World Applicationsa. Normally-Energized solenoid valves
b. Strobes/beacons for Fire & Gas applications
c. Dual tone sounders for Fire & Gas applications
d. High-availability double-coil solenoid valves
e. Single-phase load interruption solenoid valves
4. Conclusions
![Page 37: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/37.jpg)
� Normally-energized solenoid valves
� Strobes/beacons for Fire & Gas applications
� Dual - tone sounders for Fire & Gas applications
� High-availability double-coil solenoid valves
� Single-phase load interruption solenoid valves
![Page 38: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/38.jpg)
D5294S
(or D5096S)
Name: Bordolano
System: Emerson DeltaV SIS
Load: Biffi 110Vdc Solenoids
Model: D5294S (or D5096S)
SystemSolenoid Valve
Command /Power
Diagnostics
Project record
#1
110 Vdc
Supply
![Page 39: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/39.jpg)
System
DO
Normal Condition (NE)
D5294S
(D5096S)
Off-line
Modbus
System
DI
110 Vdc
![Page 40: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/40.jpg)
System
DO
Safe state
Normal condition (NE)
110 Vdc
Modbus
System
DI
D5294S
(D5096S)
![Page 41: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/41.jpg)
110 Vdc
System
DO
Fault: load open circuit
Normal Condition (NE)Normal Condition (NE)
D5096S
Fault!
Modbus
System
DI
![Page 42: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/42.jpg)
110 Vdc
System
DO
Fault: load open circuit
Normal Condition (NE)Normal Condition (NE)
D5294S
Fault!
What happened?Load is open!
Modbus
System
DI
![Page 43: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/43.jpg)
110 Vdc
System
DO
Fault: load short circuit
Normal Condition (NE)Normal Condition (NE)
D5096S
Fault!
System
DI
Modbus
![Page 44: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/44.jpg)
110 Vdc
System
DO
Fault: load short circuit
Normal Condition (NE)Normal Condition (NE)
D5294S
Fault!
What happened?Load is short circuited!
Modbus
System
DI
![Page 45: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/45.jpg)
110 Vdc
System
DO
Fault: Supply
Normal Condition (NE)Normal Condition (NE)
D5096SFault!
System
DI
Modbus
![Page 46: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/46.jpg)
110 Vdc
System
DO
Fault: Supply
Normal Condition (NE)Normal Condition (NE)
D5294SFault!
What happened?Fault supply
Modbus
System
DI
![Page 47: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/47.jpg)
110 Vdc
System
DO
Fault: Internal coil fault
Normal Condition (NE)Normal Condition (NE)
D5294S
Fault!
What happened?Internal coil fault
Modbus
System
DI
![Page 48: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/48.jpg)
D5295S
(or D5097S)
System: ABB S800
Load: MEDC Beacon/Strobe
Model: D5295S (or D5097S)
SystemBeacon / Strobe
Command /Power
Diagnostics
Project record
#2
220 Vac Supply
![Page 49: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/49.jpg)
220 Vac
System
DO
Normal Condition (ND)
Off-line
Modbus
D5295S
(D5097S)
![Page 50: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/50.jpg)
System
DO
Safe state
Normal condition (ND)
220 Vac
Modbus
D5295S
(D5097S)
![Page 51: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/51.jpg)
220 Vac
System
DO
D5097S
Fault: load open circuit
Normal Condition (ND)Normal Condition (ND)
Fault!
Modbus
![Page 52: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/52.jpg)
220 Vac
System
DO
D5295S
Fault: load open circuit
Normal Condition (ND)Normal Condition (ND)
Fault!
Modbus
What happened?Load is open!
![Page 53: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/53.jpg)
220 Vac
D5097S
Fault: load short circuit
Normal Condition (ND)Normal Condition (ND)
Fault!
System
DO
Modbus
![Page 54: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/54.jpg)
220 Vac
D5295S
Fault: load short circuit
Normal Condition (ND)Normal Condition (ND)
Fault!
Modbus
What happened?Load is short circuited!
System
DO
![Page 55: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/55.jpg)
220 Vac
D5097S
Fault: Supply
Normal Condition (ND)Normal Condition (ND)
System
DO
Fault!
Modbus
![Page 56: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/56.jpg)
220 Vac
D5295S
Fault: Supply
Normal Condition (ND)Normal Condition (ND)
Modbus
What happened?Fault supply
System
DO
Fault!
![Page 57: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/57.jpg)
220 Vac
D5295S
Fault: Earth Leakage
Normal Condition (ND)Normal Condition (ND)
Fault!
Modbus
What happened?Earth leakage
System
DO
![Page 58: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/58.jpg)
D5294S
( or D5096S)
Name: Kioc (Kuwait)
System: Invensys FBM200
Load: MEDC Sounder
Model: D5294S (or D5096S)
SystemSounder
Command /Power
Diagnostics
Project record
#3
220 Vac Supply
![Page 59: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/59.jpg)
Normal Condition (ND)
Off-line
D5294S
D5096S
System
DO
System
DO
+ Vac/Vdc
- Vac/Vdc
D5294S
D5096S
System
DI
System
DI
![Page 60: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/60.jpg)
System
DO
System
DO
+ Vac/Vdc
- Vac/Vdc
Safe state 1
Normal condition (ND)
D5294S
D5096S
D5294S
D5096S
System
DI
System
DI
![Page 61: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/61.jpg)
System
DO
+ Vac/Vdc
- Vac/Vdc
Safe state 2
Normal condition (ND)
System
DO
D5294S
D5096S
D5294S
D5096S
System
DI
System
DI
![Page 62: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/62.jpg)
System
DO
System
DO
+ Vac/Vdc
- Vac/Vdc
DETECTABLE FAULTS
D5294S
D5096S
D5294S
D5096S
Fault supply
System
DI
System
DI
![Page 63: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/63.jpg)
System
DO
System
DO
+ Vac/Vdc
- Vac/Vdc
DETECTABLE FAULTS
D5294S
D5096S
D5294S
D5096S
Load short circuit
System
DI
System
DI
![Page 64: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/64.jpg)
System
DO
System
DO
+ Vac/Vdc
- Vac/Vdc
DETECTABLE FAULTS
D5294S
D5096S
D5294S
D5096S
Load open circuit
System
DI
System
DI
![Page 65: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/65.jpg)
System
DO
System
DO
+ Vac/Vdc
- Vac/Vdc
DETECTABLE FAULTS
D5294S
D5096S
D5294S
D5096S
Internal coil fault (only D5294S)
System
DI
System
DI
![Page 66: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/66.jpg)
System
DO
System
DO
+ Vac/Vdc
- Vac/Vdc
DETECTABLE FAULTS
D5294S
D5096S
D5294S
D5096S
Fault supply
Internal coil fault (only D5294S)
Load open circuit
Load short circuit
System
DI
System
DI
![Page 67: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/67.jpg)
D5294S
System
Double Solenoid Valve
Command /Power
Diagnostics110 Vdc
Supply
System: Yokogawa RS Prosafe
Load: Double coil valve
Model: D5294S
Project record
#4
![Page 68: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/68.jpg)
110 Vdc
System
DO
Normal Condition (NE)
D5294S
Off-line
Modbus
System
DI
![Page 69: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/69.jpg)
System
DO
Safe state
D5294S
Normal condition (NE)
110 Vdc
Modbus
System
DI
![Page 70: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/70.jpg)
110 Vdc
System
DO
Fault: single coil open
Normal Condition (NE)Normal Condition (NE)
D5294S
Fault!
What happened?One coil is open!
Modbus
System
DI
![Page 71: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/71.jpg)
D5294S
D5096S
SystemSounder
Command /Power
Diagnostics
220 Vac Supply
System: Honeywell C300
Load: Solenoid valve
Model: D5294S
Project record
#5
![Page 72: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/72.jpg)
System
DO
Normal Condition (NE)
D5294S
Off-line
System
DI
110 Vdc
![Page 73: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/73.jpg)
System
DO
System
DI
110 Vdc
Safe state
Normal condition (NE)
D5294S
![Page 74: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/74.jpg)
System
DO
System
DI
110 VdcD5294S
DETECTABLE FAULTS
Fault supply
![Page 75: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/75.jpg)
System
DO
System
DI
110 VdcD5294S
Internal coil fault
DETECTABLE FAULTS
![Page 76: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/76.jpg)
System
DO
System
DI
110 VdcD5294S
Load open circuit
DETECTABLE FAULTS
![Page 77: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/77.jpg)
System
DO
System
DI
110 VdcD5294S
Load short circuit
DETECTABLE FAULTS
![Page 78: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/78.jpg)
System
DO
System
DI
110 VdcD5294S
Fault supply
Internal coil fault
Load open circuit
Load short circuit
DETECTABLE FAULTS
![Page 79: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/79.jpg)
1. What Are Smart Relays?a. Relays + Diagnostics
b. Models: D5096S, D5097S, D5293S, D5294S and D5295S
2. Why Choosing Smart Relays?
3. Real-World Applicationsa. Normally-Energized solenoid valves
b. Strobes/beacons for Fire & Gas applications
c. Dual tone sounders for Fire & Gas applications
d. High-availability double-coil solenoid valves
e. Single-phase load interruption solenoid valves
4. Conclusions
![Page 80: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/80.jpg)
1. Coil-to-contact SIL 3 -TUV Certified
2a. D5293S, D5294S, D5295S Complete Load & Line Diagnostics (SIL 2):a. Configurable voltage on load
b. Configurable Current on load
c. Configurable Load resistance (patented)
d. Configurable Leakage from load to earth
e. Coil integrity, internal faults
3. Modbus RTU RS485 supported (only D5293S, D5294S, D5295S)
4. Compatible with DO Card Line Monitoring Pulse Test
5. Fault mirroring to the DO Card
2b. D5096S, D5097S Load & Line Diagnostics :a. Line open & short circuit
b. Load open & short circuit
c. Load supply presence
![Page 81: '6 SMART RELAYS DTS0536 r4 · SMART RELAYS D5096S –D5097S D5293S -D5294S -D5295S SIL 3 Relay with Line & Load Diagnostics DTS0536-4](https://reader033.fdocuments.us/reader033/viewer/2022051811/601f29723ac2776aa50e510f/html5/thumbnails/81.jpg)
6. Suitable for many applications
D5293S
• 2 NO Contacts in series
• For NE or ESD Applications
D5096S &
D5294S
• 2 x 2 NO Contacts
• For F&G or ND Applications
/ NE high availability
D5097S &
D5295S
• 2 x 2 NC Contacts
• For F&G or ND Applications
/ NE high availability