Arthit Platform
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 2/71
Type of Fire & Gas (F&G) detectors
Installation
Voting philosophy
Automatic action by SIS (Safety Instrumented System) Automatic action by Addressable Fire Panel (For
ALQB)
F&G in Turbo Machinery Packages
Deluge System
Fire Water Pumps
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 3/71
Flame Detector Fusible Plug Loop
Gas Detector (Point Type)
Gas Detector (Line of Sight) VESDA (Very Early Smoke Detection Apparatus)
Smoke Detector
Heat Detector
Emergency Shutdown Pushbutton Manual Alarm Call point
Special
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 4/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 5/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 6/71
Multi spectrum IR Flame Detector
Installation All decks on APP
Field of View Distance 30 m.
90 degree horizontal
75 degree vertical
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 7/71
One flame detector – alarm only
At least two flame detector in same fire zone Activate ESD1 on APP
Activate deluge valve in that fire zone Start fire water pumps
PAGA tone 2
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 8/71
2oo27 Voting of flame detectors
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 9/71
2oo2 Voting of flame detectors
Special Action Inhibit FWPs on APP to start Deluge valve NOT activated (no deluge in this fire zone)
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 10/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 11/71
Fusible plugs are fixed temperature heat detectors thatmelt at the required temperature.
Fire detection is due to loss of air/gas pressure in thefusible plug loop.
Melt point is 203 DegF (95 DegC) on AWPs
Melt point is 160 DegF (71 DegC) on APP
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 12/71
Fusible plug melt on APP Activate deluge valve in that fire zone Start fire water pumps (due to fire water ring main pressure
low)
Fusible plug melt on AWP1 Activate ESD1 on AWP1 Activate deluge valve to AWP1 Start fire water pumps (due to fire water ring main pressure
low)
Fusible plug melt on AWPs Activate ESD1 on AWPs
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 13/71
Special Fusible plugs were provided at each riser valve to directly
close the valves when exposed to a fire.
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 14/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 15/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 16/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 17/71
The Deluge system is designed to protect high hazardareas containing a severe fuel hazard with a high heatrelease rate by bringing a large number of opensprayers into action simultaneously in the event of a
fire.
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 18/71
P&ID
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 19/71
5 Deluge valve for APP 2 for lower deck – always open together
XV-5650 and XV-5660
2 for main deck – always open together XV-5670 and XV-5680
1 for upper deck XV-5690
1 Deluge valve for AWP1 XV-5640
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 20/71
How many ways to activate deluge? Fusible plug melt
SIS energize solenoid when confirm fire
Manually press hand switch at local
Manually press push button in CCR
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 21/71
Special Manually press deluge push button in CCR will;
Activate ESD1 on APP
Start fire water pumps
PAGA tone 2
Note: for AWP1 will be activate ESD1 on AWP1 only
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 22/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 23/71
The Fire Water Manifold is pressurized at 10 barg by utility waterpumps. When the pressure drops to 6.5 barg or ConfirmedFire/Gas the first Fire Water Pump in the preset start sequencestarts. If the manifold pressure do not build to 10 barg in 30seconds, the second pump starts. If the manifold pressure still
does not reach 10 barg in another 30 seconds, the third pumpstarts. If 1st FW pump start and build pressure to 10 barg within 30s. 2nd
FW pump will not start But if the pressure drop below 10 barg after 30s. 2nd pump will start.
After 2nd pump start, if pressure drop below 10 barg, 3rd pump willstart. (With 30 seconds delay after 2nd pump started)
This logic is to prevent FW pumps start consecutively within 30seconds
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 24/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 25/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 26/71
Infrared Hydrocarbon Gas Detector
Installation All decks on APP
Theory of Operation Certain IR wavelengths are absorbed by the gas
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 27/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 28/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 29/71
Infrared Hydrocarbon Gas Detector Transmitter
Transmitter produces an intense, collimated infrared beam which is produced by a Xenon arc flash lamp.
Receiver Receiver collects infrared radiation from the transmitter and
performs measurements to enable hydrocarbon gases in thebeam path to be detected.
Installation All decks on APP
Theory of Operation Certain IR wavelengths are absorbed by the gas
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 30/71
One gas detector more than 20% LEL – alarm only
In process area (within same fire zone) One gas detector more than 20% LEL
And
One gas detector more than 60% LEL Activate ESD1
Start fire water pumps
PAGA tone 2
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 31/71
Inlet enclosure of turbo machinery (within same firezone) Two gas detector more than 40% LEL (2ooN)
Activate ESD1
Start fire water pumps PAGA tone 2
Isolate essential power to turbo machinery package
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 32/71
In HVAC air inlet LER, SWR (within same fire zone) Two gas detectors more than 40% LEL (2ooN)
Activate ESD1
Start fire water pumps
PAGA tone 2 Trip HVAC, close fire dampers
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 33/71
In LER, SWR (within same fire zone) Two gas detectors more than 40% LEL (2ooN)
Activate ESD1
Start fire water pumps
PAGA tone 2 Trip HVAC, close fire dampers
Isolate battery of UPS and Battery Charger. (10 s delay) This will lead to black-out. SIS loss power. EDG can not start.
Gas detector in airlock is alarm only
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 34/71
AQP Main deck One gas detector more than 20% LEL
And
One gas detector more than 60% LEL Activate ESD1 Inhibit AQP fire water pump to start
Start fire water pumps on APP
PAGA tone 2
Stop/Inhibit to start EDG Trip AQP HVAC
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 35/71
AQP HVAC air inlet Two gas detectors more than 40% LEL (2ooN)
Activate ESD1
Inhibit AQP fire water pump to start
Start fire water pumps on APP PAGA tone 2
Stop/Inhibit to start EDG
Trip AQP HVAC
Isolate battery of AQP All HMI in CCR will power loss
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 36/71
ALQB HVAC air inlet Two gas detectors more than 40% LEL (2ooN)
Activate ESD1
Start fire water pumps
PAGA tone 2 Trip ALQB HVAC
Trip ALQB UPS and essential power
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 37/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 38/71
Turbo machinery package has “Eagle Quantum”controller as independent F&G system
No detectors voting
No ESD1
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 39/71
Feed gas compressors Confirm fire by heat detector Confirm fire by flame detector (3s delay in “eagle quantum”
for confirmation) Shutdown FGC (with blowdown) Release CO2 for package
Release “main” CO2 then wait for 90 seconds. If fire still active, willrelease “reserve” CO2
Start fire water pumps PAGA tone 2
Isolate all power to package Gas alarm at 5% LEL Confirm gas at 10% LEL
Same action as above except no CO2 release
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 40/71
Sale gas compressors Confirm fire by heat detector Confirm fire by flame detector (5s delay in “flame
detector” for confirmation)
Shutdown SGC (with blowdown) Release CO2 for package
Release “primary” and “extended”
Start fire water pumps PAGA tone 2
Isolate all power package Gas alarm at 20% LEL Confirm gas at 40% LEL
Same action as above except no CO2 release
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 41/71
Power Generators Confirm fire by heat detector Confirm fire by flame detector (5s delay in “flame
detector” for confirmation)
Shutdown power generator Release CO2 for package
Release “primary” and “extended”
Start fire water pumps PAGA tone 2
Isolate all power package Gas alarm at 20% LEL Confirm gas at 40% LEL
Same action as above except no CO2 release
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 42/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 43/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 44/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 45/71
Very Early Smoke Detection Apparatus Work by continually drawing air into the pipe network. The sample
enter to laser detection chamber for smoke detection
Installation APP LER, APP SWR, APP ESWR, AQP SWR
Action When fire alert Alarm in CCR Operator have to investigate the root cause of smoke and try to stop it
When confirm fire Start fire water pumps
Trip HVAC units and close fire dampers. Isolate normal and essential lighting PAGA tone2
Note: There is no ESD1 in this case.
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 46/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 47/71
Manual Alarm Call point Located around the facility to allow personnel to raise
an alarm.
Alarm in CCR only.
Panel operator will take necessary action.
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 48/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 49/71
Located principally near main stairways on mainprocess decks.
Action - Activate ESD1 Close all shutdown valves
Open all blowdown valves
Trip all packages
ESD2 on all wellhead platforms
Start Fire Water Pumps
PAGA tone2
Trip normal power (Main Generators) EDG will start automatically
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 50/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 51/71
Located at Helideck Access Landing Lifeboat embarkation area Drain Deck
Action – Activate ESD0 ESD1 ESD1 on all wellhead platforms Stop EDG PAGA tone1 Isolate Battery charger on AQP Delay 30 minutes to isolate UPS on AQP Delay 3 hours to isolate UPS and Battery charger on APP
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 52/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 53/71
Located at In front of LER
In front of ESWR
In front of CCR
This PB is use for isolate power in the room in case of
fire.
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 54/71
LER and ESWR Activate ESD1
Stop/Inhibit to start EDG
Isolate APP battery charger
120 seconds delay to isolate APP UPS
This will lead to black-out. SIS loss power.
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 55/71
CCR Activate ESD1
Isolate AQP battery charger and UPS
All HMI in CCR will loss power
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 56/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 57/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 58/71
Photoelectric sensing detect visible fire particles Located in AQP Workshop, CCR, Raised floors,
Laboratory, Battery room
Action Confirm smoke in Laboratory (1oo1)
PAGA tone 2
Trip HVAC units and close fire dampers.
Isolate all power sources within the laboratory
Start fire water pumps
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 59/71
Action Confirm smoke in APP battery room (2oo2)
PAGA tone 2
Close fire dampers.
Start fire water pumps Confirm smoke in AQP battery room (1oo1)
PAGA tone 2
Trip AQP HVAC
Start fire water pumps
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 60/71
Action Confirm smoke in AQP workshop (2ooN in same fire
zone) PAGA tone 2
Trip AQP HVAC and close fire dampers. Isolate all power sources within fire zone
Start fire water pumps
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 61/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 62/71
The outer shell is made of a rapidly expanding alloy which closely follows changes in surrounding air temperature. The inner strutsare made of a lower expanding alloy. Designed to resist thermalenergy absorption and sealed inside the shell, the struts followtemperature changes more slowly.
Designed to activate at a fixed temperature, regardless of the rate of temperature rise.
Set point is 60 DegC.
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 63/71
They will be used as the primary means of firedetection in areas where smoke is regularly expectedand accepted (Welding workshop, mechanical
workshops, EI workshop).
Action Confirm heat in one fire zone (1ooN)
PAGA tone 2
Trip HVAC units and close fire dampers.
Isolate all power sources within fire zone Start fire water pumps
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 64/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 65/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 66/71
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 67/71
Autronica AutroSafe on ALQB Automatic addressing of detectors.
Self-Verify Function for automatic testing of detectors
The system operates on the new AUTROLON
communication bus, enabling networking of all panels,detectors and interfaces to easily form a complex,distributed and totally interactive system - giving theflexibility to adapt to the individual requirements of any
site.
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 68/71
Smoke Detector (optical type) installed in every cabins,offices, recreation area
MAC installed in around the building to allow personnelto raise an alarm
Heat Detector install in galley VESDA installed in TER
Flame detectors at Helideck
Addressable interface unit installed on every floors
Addressable control panel is in CCR
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 69/71
Action Confirm fire inside ALQB
Alarm in CCR with tag and location of fire.
Close fire dampers
Trip ALQB HVAC Start stairwell pressurize fans
Confirm gas outside ALQB (XS-8600; signal from SIS) Alarm in CCR
Close fire dampers
Trip ALQB HVAC
NOT Start stairwell pressurize fans
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 70/71
Action Confirm fire inside galley
Alarm in CCR with tag and location of fire.
Close fire dampers
Trip ALQB HVAC Start stairwell pressurize fans
Trip galley distribution board (LSB-QP-360)
All ALQB F&G detection will not alarm to PAGA
8/2/2019 54653358 Fire Gas Detection Philosophy Rev1 Full
http://slidepdf.com/reader/full/54653358-fire-gas-detection-philosophy-rev1-full 71/71
Please refer to C&E for detail actions for each F&Gdetection