Dear Century 21 Tri-Cities,
RE: Report No. 3200, v.0520 S Larch StKennewick, WA99336
Thanks very much for choosing us to perform your home inspection. The inspection itself and the attached report complywith the requirements of the Standards of Practice for Washington State and ASHI. This document defines the scope of ahome inspection.
Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourageyou to read the Standards of Practice so that you clearly understand what things are included in the home inspection andreport.
The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not beresponsible to any parties for the contents of the report, other than the party named herein .
The report is effectively a snapshot of the house, recording the conditions on a given date and time. Home inspectorscannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. Ifconditions change, we are available to revisit the property and update our report.
Again, thanks very much for choosing us to perform your home inspection.
Sincerely,
Platinum Inspection Teamon behalf ofPlatinum Inspection Services
Platinum Inspection Services1110 W 21st Ave
Kennewick, WA 99337509 947 2293
www.thetricitieshomeinspector.comkenny@TheTriCitiesHomeInspector.com
SUMMARY
This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as acourtesy and cannot be considered a substitute for reading the entire report. Please read the complete document.
Priority Maintenance Items
Roofing
SLOPED ROOFING \ Composition shinglesCondition: Multiple layersThere are multiple layers of roofing on the home. When the time comes to replace it it will need to be stripped beforeshingling.
SLOPED ROOF FLASHINGS \ Chimney flashingsCondition: Missing top, bottom, side flashingsThe chimney flashing is missing. I recommend that this be evaluated and repaired as needed by a licensed qualifiedroofing contractor. The plumbing jacks also need to be sealed around.Task: CorrectTime: Immediate
Exterior
GeneralVegetation against building: Vegetation was growing against the building in several areas. This creates conducive
conditions for pests and wood destroying organisms. I recommend the vegetation be trimmed back or removed.Location: Front exteriorTask: RepairTime: Immediate
WALLS \ TrimCondition: Peeling paint:I recommend that any areas of peeling paint be scraped and painted.Task: RepairTime: Immediate
WALLS \ Vinyl sidingCondition: Loose or missing piecesI recommend that the missing trim, soffit and siding pieces be installed.Location: South exterior, west exteriorTask: ProvideTime: Immediate
WALLS \ Vent (fan, clothes dryer, etc.)Condition: Cover missingI recommend that the missing cover for the dryer duct on the rear exterior be installed.Location: Rear exteriorTask: Repair
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 1 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
SUMMARY
Time: Immediate
PORCHES, DECKS, STAIRS, PATIOS AND BALCONIES \ Handrails and guardsCondition: MissingModern standards recommend that guardrails be installed when there is a 30" or more fall.Location: DeckTask: ProvideTime: Immediate
Structure
FLOORS \ JoistsCondition: Cut Joist: I recommend that the cut joist be evaluated and repaired as needed by a licensed qualifiedcontractor.Location: Laundry areaTask: RepairTime: Immediate
Electrical
SERVICE BOX, GROUNDING AND PANEL \ Distribution fuses/breakersCondition: Double taps: I recommend that the double taps in the electrical panel be repaired by a licensed qualifiedelectrical contractor.One of the wires is too small for the breaker that it's going too and the wire has overheated. The abandoned wires shouldalso be properly capped and the connection made in the box to the left of the main panel should be properly made withwire nuts. All repairs should be made by a licensed qualified electrical contractor.Location: Upper left, lower rightTask: RepairTime: Immediate
SERVICE BOX, GROUNDING AND PANEL \ Panel wiresCondition: The neutral and ground wires were bonded in the sub panel. In a sub panel these should be isolated fromeach other. I recommend that this be corrected by a licensed qualified electrician.Also there is a wire going to the double throw 20 amp breaker that appears to have overheated at some point.Location: Garage subpanelTask: RepairTime: Immediate
DISTRIBUTION SYSTEM \ Junction boxesCondition: MissingI recommend that the abandoned wires be terminated in a junction box.Location: Rear exterior, behind shop, below stairs, basement laundry area. shopTask: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 2 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
SUMMARY
DISTRIBUTION SYSTEM \ Outlets (receptacles)Condition: Ungrounded 3 Slot Outlets: Many of the 3-prong outlets were ungrounded. These should either begrounded, be replaced with 2-prong outlets, or have GFI receptacles installed. Consider updating the existing condition tomeet generally-accepted current safety standards.Location: Basement room at bottom of stairsTask: RepairTime: Immediate
Condition: GFCI protection needed: I recommend that the outlets in the following locations be repaired to be GFCIprotected. This should be done by a licensed qualified electrical contractor.Location: Garage, Kitchen, Main level bathroomTask: RepairTime: Immediate
Condition: Reverse Polarity: I recommend that the outlets with reverse polarity in the following locations be repaired bya licensed qualified electrical contractor.Location: Living room west wall, Dining area, Kitchen, Basement living roomTask: RepairTime: Immediate
DISTRIBUTION SYSTEM \ SwitchesCondition: FaultyThere are 3 switches that control the light at the top of the stairs. When they are at certain positions the light doesn't workcorrectly. I recommend that this be further evaluated and repaired as needed by a licensed qualified electrical contractor.Location: StairwayTask: Further evaluationTime: Immediate
Condition: Location poor (near Bathtub or Shower Stall)The switches are too close to the shower stall. I recommend that the switches be moved to at least 3' away from the stallor that they be GFCI protected.Location: BasementTask: RepairTime: Immediate
DISTRIBUTION SYSTEM \ Cover platesCondition: I recommend that any missing cover-plates be installed.Location: Living room, Northeast bedroom, Garage, BasementTask: RepairTime: Immediate
DISTRIBUTION SYSTEM \ LightsCondition: Inoperative lights: I recommend that the bulbs be replaced in the inoperative lights in the following locationsand if the lights still don't work that they be repaired by a licensed qualified electrical contractor.Location: Rear deck, Front entry, Laundry areaTask: Repair
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 3 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
SUMMARY
Time: Immediate
DISTRIBUTION SYSTEM \ Carbon monoxide (CO) alarms (detectors)Condition: None present. A CO detector will need to be provided.Smoke alarms should also be installed in the hallways and bedrooms.Task: ProvideTime: Immediate
Heating
GeneralThe masonry chimney cap is missing. I recommend that this be repaired by a licensed qualified masonry contractor.
Task: CorrectTime: Immediate
Plumbing
SUPPLY PLUMBING \ Supply piping in buildingCondition: I recommend that dielectric fittings be installed where they are missing to protect the water pipes fromelectrolysis. This should be done by a licensed qualified plumbing contractor.Location: Basement laundry areaTask: RepairTime: Immediate
WATER HEATER \ TankCondition: No earthquake straps: I recommend that earthquake straps be installed on the water heater.It also is missing a discharge tube for the TPR valve. I recommend that one be installed.Task: RepairTime: Immediate
WASTE PLUMBING \ Traps - installationCondition: Missing p-trap: The p-trap is missing in the following location(s). This will result in sewer gas entering thehome. I recommend that this be evaluated and repaired as needed by a licensed qualified plumbing contractor.There is a vent pipe coming out of the wall beside the basement shower. If this is a vent pipe it will also allow sewer gasto enter the home. Due to the plumbing deficiencies present in the basement laundry area and bathroom I recommendthat the plumbing in these areas be evaluated and repaired as needed by a licensed qualified plumbing contractor.Location: Basement Laundry Area and Bathroom.Task: CorrectTime: Immediate
FIXTURES AND FAUCETS \ Shower stallCondition: The main level bathroom shower head sprays out of the shower stall. I recommend that this be repaired.Location: Main level bathroomTask: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 4 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
SUMMARY
Condition: Missing drain cover: I recommend that the missing drain cover in the following location be provided.Location: Basement bathroomTask: RepairTime: Immediate
Interior
WINDOWS \ Glass (glazing)Condition: Broken window: I recommend that the broken window be repaired by a licensed qualified glass contractor.Location: GarageTask: ReplaceTime: Immediate
DOORS \ GeneralCondition: DamageI recommend that the damaged door in the northeast bedroom be repaired or replaced.Location: Northeast bedroomTask: RepairTime: Immediate
DOORS \ Doors and framesCondition: Does not latch properlyI recommend that the north exterior door be repaired so the deadbolt will latch and that the damaged weatherstrip bereplaced.Location: NorthTask: RepairTime: Immediate
DOORS \ HardwareCondition: MissingI recommend that the missing door knob handle be installed. The door also binds.Location: Basement bathroomTask: ProvideTime: Discretionary
EXHAUST FANS \ DuctCondition: I recommend that the missing damper be installed.Location: Rear exterior below deckTask: RepairTime: Immediate
APPLIANCES \ RangeCondition: There was no anti tip device installed on the range. I recommend these be installed to prevent injury tochildren and others.Task: Repair
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 5 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
SUMMARY
Time: Immediate
This concludes the Summary section.
The remainder of the report describes each of the home's systems and also details any recommendations we have forimprovements. Limitations that restricted our inspection are included as well.
The suggested time frames for completing recommendations are based on the limited information available during apre-purchase home inspection. These may have to be adjusted based on the findings of specialists.
Home Improvement - ballpark costs
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 6 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ROOFING
Description
General: WalkedThe Inspector inspected the roof and its components by walking the roof.
General: Some roof leaks will only appear during certain weather conditions and may not be possible to detect duringthe time of a home inspection.
The home is considered to face : East
Sloped roofing material: Composition shingles
Approximate age: 13 -17 years
Typical life expectancy: 20-30 years.
Roof Shape: Gable
Recommendations
SLOPED ROOFING \ Composition shingles1. Condition: Multiple layersThere are multiple layers of roofing on the home. When the time comes to replace it it will need to be stripped beforeshingling.
SLOPED ROOF FLASHINGS \ Chimney flashings2. Condition: Missing top, bottom, side flashingsThe chimney flashing is missing. I recommend that this be evaluated and repaired as needed by a licensed qualifiedroofing contractor. The plumbing jacks also need to be sealed around.Task: CorrectTime: Immediate
1. Plumbing jacks need sealant 2. Missing top, bottom, side flashings
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 7 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
EXTERIOR
Description
Gutter & downspout material: No gutters or downspouts
Lot slope: Flat
Soffit (underside of eaves) and fascia (front edge of eaves): Wood
Wall surfaces and trim: Vinyl siding
Deck: Raised Wood
Recommendations
General3. Vegetation against building: Vegetation was growing against the building in several areas. This creates conduciveconditions for pests and wood destroying organisms. I recommend the vegetation be trimmed back or removed.Location: Front exteriorTask: RepairTime: Immediate
3. Vegetation against building: Vegetation was...
WALLS \ Trim4. Condition: Peeling paint:I recommend that any areas of peeling paint be scraped and painted.Task: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 8 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
EXTERIOR
4. Peeling paint:
WALLS \ Vinyl siding5. Condition: Loose or missing piecesI recommend that the missing trim, soffit and siding pieces be installed.Location: South exterior, west exteriorTask: ProvideTime: Immediate
5. Loose or missing pieces 6. Loose or missing pieces
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 9 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
EXTERIOR
7. Loose or missing pieces 8. Loose or missing pieces
WALLS \ Vent (fan, clothes dryer, etc.)6. Condition: Cover missingI recommend that the missing cover for the dryer duct on the rear exterior be installed.Location: Rear exteriorTask: RepairTime: Immediate
9. Cover missing
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 10 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
EXTERIOR
PORCHES, DECKS, STAIRS, PATIOS AND BALCONIES \ Handrails and guards7. Condition: MissingModern standards recommend that guardrails be installed when there is a 30" or more fall.Location: DeckTask: ProvideTime: Immediate
10. Missing
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 11 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
STRUCTURE
Description
General: The attic was inspected from the attic hatch due to limited access.
11. The attic was inspected from the attic hatc... 12. The attic was inspected from the attic hatc...
13. The attic was inspected from the attic hatc... 14. The attic was inspected from the attic hatc...
Configuration: Basement Crawlspace
Foundation material: Masonry block
Floor construction: Joists Subfloor - plank
Exterior wall construction: Wood frame
Roof and ceiling framing: Rafters/ceiling joists Plank sheathing
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 12 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
STRUCTURE
Recommendations
FLOORS \ Joists8. Condition: Cut Joist: I recommend that the cut joist be evaluated and repaired as needed by a licensed qualifiedcontractor.Location: Laundry areaTask: RepairTime: Immediate
15. Cut Joist: I recommend that the cut joist...
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 13 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
Description
General: Main Panel Description:A main electrical service panel is a metal enclosure containing various electrical components. The type, condition andarrangement of the service panel and its components must comply with safety standards, usually the National ElectricCode established by the National Fire Protection Association. Requirements may also vary by jurisdiction.Components typically found in main service panels are as follows:- Main disconnect- is one switch controlling all the circuit breakers. Not all panels have a main disconnect. Shutting offthe main disconnect automatically shuts off power to all the electrical circuits in the main panel.- Circuit breakers- are each designed to automatically turn off electricity to the circuit it protects if it detects a problem.The type of problems detected by circuit breakers depends on the type of circuit breaker installed.- Grounding, neutral and power supply bus bars- are components which allow wires or groups of wires to be electricallyconnected and which support circuit breakers.- A label- on the inside listing the circuits controlled by each switch and providing information about the enclosure.- Bonding devices- designed to prevent shock or electrocution.
Service entrance cable and location: Overhead copper
Service size: 200 Amps (240 Volts)
Main disconnect/service box rating: 200 Amps
Main disconnect/service box type and location: Breakers- exterior
16. Breakers- exterior
System grounding material and type: Not visible
Auxiliary panel (subpanel) type and location:Breakers
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 14 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
17. Breakers
Auxiliary panel (subpanel) rating: 120 amps
Distribution wire material and type: Copper - non-metallic sheathed
Type and number of outlets (receptacles): Grounded and ungrounded - typical
Limitations
Inspection limited/prevented by:Restricted access
I was unable to get the subpanel cover off in the garage and in the laundry room because of the restricted access.
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 15 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
18. Restricted access 19. Restricted access
Recommendations
SERVICE BOX, GROUNDING AND PANEL \ Distribution fuses/breakers9. Condition: Double taps: I recommend that the double taps in the electrical panel be repaired by a licensed qualifiedelectrical contractor.One of the wires is too small for the breaker that it's going too and the wire has overheated. The abandoned wires shouldalso be properly capped and the connection made in the box to the left of the main panel should be properly made withwire nuts. All repairs should be made by a licensed qualified electrical contractor.Location: Upper left, lower rightTask: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 16 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
20. Repair connection 21. Double taps: I recommend that the double...
22. Double taps: I recommend that the double...
SERVICE BOX, GROUNDING AND PANEL \ Panel wires10. Condition: The neutral and ground wires were bonded in the sub panel. In a sub panel these should be isolatedfrom each other. I recommend that this be corrected by a licensed qualified electrician.Also there is a wire going to the double throw 20 amp breaker that appears to have overheated at some point.Location: Garage subpanelTask: RepairTime: Immediate
DISTRIBUTION SYSTEM \ Junction boxes11. Condition: MissingI recommend that the abandoned wires be terminated in a junction box.Location: Rear exterior, behind shop, below stairs, basement laundry area. shopTask: Repair
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 17 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
Time: Immediate
23. Junction box needed.
24. Missing
25. Missing
DISTRIBUTION SYSTEM \ Outlets (receptacles)12. Condition: Ungrounded 3 Slot Outlets: Many of the 3-prong outlets were ungrounded. These should either begrounded, be replaced with 2-prong outlets, or have GFI receptacles installed. Consider updating the existing condition tomeet generally-accepted current safety standards.Location: Basement room at bottom of stairsTask: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 18 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
26. Ungrounded 3 Slot Outlets: Many of the...
13. Condition: GFCI protection needed: I recommend that the outlets in the following locations be repaired to be GFCIprotected. This should be done by a licensed qualified electrical contractor.Location: Garage, Kitchen, Main level bathroomTask: RepairTime: Immediate
14. Condition: Reverse Polarity: I recommend that the outlets with reverse polarity in the following locations be repairedby a licensed qualified electrical contractor.Location: Living room west wall, Dining area, Kitchen, Basement living roomTask: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 19 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
27. Reverse Polarity: I recommend that the...
DISTRIBUTION SYSTEM \ Switches15. Condition: FaultyThere are 3 switches that control the light at the top of the stairs. When they are at certain positions the light doesn't workcorrectly. I recommend that this be further evaluated and repaired as needed by a licensed qualified electrical contractor.Location: StairwayTask: Further evaluationTime: Immediate
28. Faulty
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 20 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
16. Condition: Location poor (near Bathtub or Shower Stall)The switches are too close to the shower stall. I recommend that the switches be moved to at least 3' away from the stallor that they be GFCI protected.Location: BasementTask: RepairTime: Immediate
29. Location poor (near Bathtub or Shower Stall)
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 21 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
DISTRIBUTION SYSTEM \ Cover plates17. Condition: I recommend that any missing cover-plates be installed.Location: Living room, Northeast bedroom, Garage, BasementTask: RepairTime: Immediate
30. I recommend that any missing cover-plates b...
DISTRIBUTION SYSTEM \ Lights18. Condition: Inoperative lights: I recommend that the bulbs be replaced in the inoperative lights in the followinglocations and if the lights still don't work that they be repaired by a licensed qualified electrical contractor.Location: Rear deck, Front entry, Laundry areaTask: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 22 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
ELECTRICAL
31. Inoperative lights: I recommend that the...
DISTRIBUTION SYSTEM \ Carbon monoxide (CO) alarms (detectors)19. Condition: None present. A CO detector will need to be provided.Smoke alarms should also be installed in the hallways and bedrooms.Task: ProvideTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 23 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
HEATING
Description
System type: Electric Wall HeatNote: Rebates may be available through the PUD to upgrade your heating system.
Recommendations
General20. The masonry chimney cap is missing. I recommend that this be repaired by a licensed qualified masonry contractor.Task: CorrectTime: Immediate
32. Missing masonry cap
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 24 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
INSULATION AND VENTILATION
Description
Attic/roof insulation material: Glass fiber
Attic/roof insulation amount/value: R-32
Attic/roof ventilation: Roof and soffit vents
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 25 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
PLUMBING
Description
Water supply source: Public
Water flow and pressure: Functional
Water heater type: Conventional
Water heater location: Basement
Water heater fuel/energy source: Electric
Water heater manufacturer: RUUD
33. RUUD 34. RUUD
Water heater tank capacity: 50 gallons
Water heater approximate age: 5 years
Water heater typical life expectancy: 8 to 12 years
Hot water temperature (Generally accepted safe temp. is 120° F): 120° F
Waste disposal system: Public
Exterior hose bibb (outdoor faucet): The exterior hose bibbs are not frost free and will need to be protected fromfreezing in the winter.
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 26 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
PLUMBING
Recommendations
SUPPLY PLUMBING \ Supply piping in building21. Condition: I recommend that dielectric fittings be installed where they are missing to protect the water pipes fromelectrolysis. This should be done by a licensed qualified plumbing contractor.Location: Basement laundry areaTask: RepairTime: Immediate
35. I recommend that dielectric fittings be...
WATER HEATER \ Tank22. Condition: No earthquake straps: I recommend that earthquake straps be installed on the water heater.It also is missing a discharge tube for the TPR valve. I recommend that one be installed.Task: RepairTime: Immediate
WASTE PLUMBING \ Traps - installation23. Condition: Missing p-trap: The p-trap is missing in the following location(s). This will result in sewer gas enteringthe home. I recommend that this be evaluated and repaired as needed by a licensed qualified plumbing contractor.There is a vent pipe coming out of the wall beside the basement shower. If this is a vent pipe it will also allow sewer gasto enter the home. Due to the plumbing deficiencies present in the basement laundry area and bathroom I recommendthat the plumbing in these areas be evaluated and repaired as needed by a licensed qualified plumbing contractor.Location: Basement Laundry Area and Bathroom.Task: CorrectTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 27 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
PLUMBING
36. Missing p-trap: The p-trap is missing in th... 37. Missing p-trap: The p-trap is missing in th...
38. Missing p-trap: The p-trap is missing in th...
FIXTURES AND FAUCETS \ Shower stall24. Condition: The main level bathroom shower head sprays out of the shower stall. I recommend that this be repaired.Location: Main level bathroomTask: RepairTime: Immediate
25. Condition: Missing drain cover: I recommend that the missing drain cover in the following location be provided.Location: Basement bathroomTask: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 28 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
PLUMBING
39. Missing drain cover: I recommend that the...
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 29 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
INTERIOR
Description
General: The range, dishwasher, microwave, garbage disposal, and refrigerator were checked and were functioning atthe time of the inspection.
General: Appliances are tested for basic function only. In the time of a home inspection it is not possible to check eachcycle of each appliance.
Major floor finishes: Carpet Laminate
Major wall and ceiling finishes: Plaster/drywall
Windows: Single/double hung Vinyl
Glazing: Double
Exterior doors - type/material: Hinged Sliding glass Plastic/fiberglass
Oven type: Conventional
Oven fuel: Electricity
Range fuel: Electricity
Laundry facilities: Hot/cold water supply 120-Volt outlet 240-Volt outlet Waste standpipe
Kitchen ventilation: Microwave/Rangehood
Kitchen ventilation: Recirculating type
Bathroom ventilation: Exhaust fan
Recommendations
WINDOWS \ Glass (glazing)26. Condition: Broken window: I recommend that the broken window be repaired by a licensed qualified glasscontractor.Location: GarageTask: ReplaceTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 30 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
INTERIOR
40. Broken window: I recommend that the broken...
DOORS \ General27. Condition: DamageI recommend that the damaged door in the northeast bedroom be repaired or replaced.Location: Northeast bedroomTask: RepairTime: Immediate
DOORS \ Doors and frames28. Condition: Does not latch properlyI recommend that the north exterior door be repaired so the deadbolt will latch and that the damaged weatherstrip bereplaced.Location: NorthTask: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 31 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
INTERIOR
41. Does not latch properly 42. Damaged weatherstrip
DOORS \ Hardware29. Condition: MissingI recommend that the missing door knob handle be installed. The door also binds.Location: Basement bathroomTask: ProvideTime: Discretionary
43. Missing
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 32 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
INTERIOR
EXHAUST FANS \ Duct30. Condition: I recommend that the missing damper be installed.Location: Rear exterior below deckTask: RepairTime: Immediate
44. I recommend that the missing damper be instal
APPLIANCES \ Range31. Condition: There was no anti tip device installed on the range. I recommend these be installed to prevent injury tochildren and others.Task: RepairTime: Immediate
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 33 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
INTERIOR
45. There was no anti tip device installed on...
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 34 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
SITE INFO
Description
General: Inspectors present: Kenny Larsen and Mason Fox
General: Hidden defects may exist: A home inspection is limited only too what is visible, hidden defects may be presentwhere they cannot be seen.
General: We recommend that all repairs be made by licensed qualified professionals. When a professional is hired tomake a repair they are liable for the quality of the repair. When repairs are made by the homeowner we cannotdetermine the quality of the repair. When you opt to have Platinum Inspection Services do a re-inspection we are onlyable in most cases to determine if a repair was made not necessisarily if it was done to the highest standard.
Weather: Sunny
Approximate temperature: 66°
Occupancy: The home was vacant during the inspection.
Utilities: All utilities were on during the inspection.
Approximate inspection Start time: The inspection started at 8:00 a.m.
Approximate age of home: 79 years
Approximate date of construction: 1940
Approximate size of home: 1100 ft.²
END OF REPORT
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 35 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE
REFERENCE LIBRARY
The links below connect you to a series of documents that will help you understand your home and how it works. Theseare in addition to links attached to specific items in the report.
Click on any link to read about that system.
01. ROOFING, FLASHINGS AND CHIMNEYS
02. EXTERIOR
03. STRUCTURE
04. ELECTRICAL
05. HEATING
06. COOLING/HEAT PUMPS
07. INSULATION
08. PLUMBING
09. INTERIOR
10. APPLIANCES
11. LIFE CYCLES AND COSTS
12. SUPPLEMENTARY
Asbestos
Radon
Urea Formaldehyde Foam Insulation (UFFI)
Lead
Carbon Monoxide
Mold
Household Pests
Termites and Carpenter Ants
13. HOME SET-UP AND MAINTENANCE
14. MORE ABOUT HOME INSPECTIONS
520 S Larch St, Kennewick, WA July 3, 2019 www.thetricitieshomeinspector.com
Providing Peace of Mind
Report No. 3200, v.0
Page 36 of 36
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR SITE INFO
REFERENCE