ADCA The BFT boiler feed tank is one of the most important devices in a boiler room. Its main function is to store the make-up water and condensate, assuring a reserve of treated water to supply to the steam boilers. The make-up water has to be softened to prevent scale formation on the boiler and the oxygen also has to be removed, so that corrosion in the boiler and steam system is avoided (this situation is normally handled by specialists). The consumption of chemicals used to eliminate the oxygen can be drastically reduced if you use one of the several ADCATherm thermal degasification processes (ADG, TDG, FCD) for the removal of oxygen and other non-condensable gases (mainly carbon dioxide). Even if you choose not to use one of the mentioned systems, the ADCATherm boiler feed tanks will always be optimized according to the existing needs, therefore being able to include water pre- heating, as well as other features obvious to a true steam expert, but not to a simple tank manufacturer. Sandblasted and metalized internally and externally (externally painted). Prevents energy wasting. Can be installed on new or existing systems. ADCATHERM BOILER FEED TANKS BFT OPTIONS: USE: AVAILABLE MODELS: CONNECTIONS: CONSTRUCTION: INSTALLATION: Vertical and special designs for different applications. Complete stainless steel construction. Complete system including all the necessary equipment. Vent condenser for energy recovery. Steam boiler feed water. BFT – standard horizontal design. BFT/ADG or TDG – vessel and correspondent deaerator dome. BFTV – special vertical design. Flanged EN 1092-1 or ASME. ISO or NPT threaded sockets. Different connections on request. Carbon steel with internal stainless steel components. See ADG/TDG catalogues for typical installations. Standard horizontal install. Vertical on request. Final dimensions and connections according to the drawing supplied after order confirmation. Insulation (not included) recommended after installation. DESCRIPTION MAIN FEATURES VALSTEAM ADCA We reserve the right to change the design and material of this product without notice. IS BFT.20 E 09.12 LIMITING CONDITIONS PS – Maximum allowable pressure 0,5 bar TS – Maximum allowable temperature 120 ºC Minimum operating temperature: -10 ºC; Design code: AD-Merkblatt. Remark: other conditions and CE marking on request.

Transcript of 5.133.E.BFT Boiler feed tanks€¦ · Steam boiler feed water. BFT – standard horizontal design....

Page 1: 5.133.E.BFT Boiler feed tanks€¦ · Steam boiler feed water. BFT – standard horizontal design. BFT/ADG or TDG – vessel and correspondent deaerator dome. BFTV – special vertical

ADCA

The BFT boiler feed tank is one of the most important devices in a boiler room. Its main function is to store the make-up water and condensate, assuring a reserve of treated water to supply to the steam boilers.The make-up water has to be softened to prevent scale formation on the boiler and the oxygen also has to be removed, so that corrosion in the boiler and steam system is avoided (this situation is normally handled by specialists).The consumption of chemicals used to eliminate the oxygen can be drastically reduced if you use one of the several ADCATherm thermal degasification processes (ADG, TDG, FCD) for the removal of oxygen and other non-condensable gases (mainly carbon dioxide).Even if you choose not to use one of the mentioned systems, the ADCATherm boiler feed tanks will always be optimized according to the existing needs, therefore being able to include water pre-heating, as well as other features obvious to a true steam expert, but not to a simple tank manufacturer.

Sandblasted and metalized internally and externally (externally painted).Prevents energy wasting.Can be installed on new or existing systems.

ADCATHERM BOILER FEED TANKSBFT

OPTIONS:

USE:

AVAILABLE MODELS:

CONNECTIONS:

CONSTRUCTION:

INSTALLATION:

Vertical and special designs for different applications.Complete stainless steel construction.Complete system including all the necessary equipment.Vent condenser for energy recovery. Steam boiler feed water.

BFT – standard horizontal design.BFT/ADG or TDG – vessel and correspondent deaerator dome.BFTV – special vertical design.

Flanged EN 1092-1 or ASME.ISO or NPT threaded sockets.Different connections on request.

Carbon steel with internal stainless steel components.

See ADG/TDG catalogues for typical installations. Standard horizontal install. Vertical on request.Final dimensions and connections according to the drawing supplied after order confirmation.Insulation (not included) recommended after installation.

DESCRIPTION

MAIN FEATURES

VALSTEAM ADCA We reserve the right to change the design and material of this product without notice.

IS BFT.20 E 09.12

LIMITING CONDITIONS

PS – Maximum allowable pressure 0,5 bar

TS – Maximum allowable temperature 120 ºCMinimum operating temperature: -10 ºC; Design code: AD-Merkblatt.Remark: other conditions and CE marking on request.

Page 2: 5.133.E.BFT Boiler feed tanks€¦ · Steam boiler feed water. BFT – standard horizontal design. BFT/ADG or TDG – vessel and correspondent deaerator dome. BFTV – special vertical

ADCA

DIMENSIONS (mm)

MODEL CAPACITY(L) A B C D E F WEIGHT

(kg)BFT-500 537 1800 640 1500 900 150 4 180

BFT-750 856 1860 800 1500 900 180 5 290

BFT-1000 1107 2360 800 2000 1200 180 5 350

BFT-1250 1336 1920 960 1500 900 210 5 360

BFT-1500 1698 2420 960 2000 1200 210 5 410

BFT-2000 2248 2480 1080 2000 1200 240 6 570

BFT-2500 2706 2980 1080 2500 1500 240 6 665

BFT-3000 3068 2560 1280 2000 1200 280 7 795

BFT-3500 3711 3060 1280 2500 1500 280 7 920

BFT-4000 4176 2660 1500 2000 1200 330 8 1160

BFT-5000 5060 3160 1500 2500 1500 330 8 1335

BFT-6000 5943 3660 1500 3000 1800 330 8 1510Remarks: approximate dimensions. Consult manufacturer for certified dimensions. Pipe connections and location approved after order confirmation.

VALSTEAM ADCA We reserve the right to change the design and material of this product without notice.

IS BFT.20 E 09.12

VALSTEAM ADCA We reserve the right to change the design and material of this product without notice.

IS BFT.20 E 09.12

MATERIALS

DESIGNATION MATERIALCylindrical shell EN 10025 / S235JR / 1.0038

Domed ends EN 10025 / S235JR / 1.0038

Inlet/outlet pipes EN 10216-2 / P235GH / 1.0345

EN flanges EN 10222-2 / P250GH / 1.0460

ASME flanges ASTM A105 / 1.0432

Sockets ASTM A105 / 1.0432

Internals EN 10028-7 / AISI 316 / 1.4401

Supports EN10025 / S235JR / 1.0038

Bolts Steel 8.8EN 10204 3.1 certificate available on request.

THERMAL DEAERATOR DATA INQUIRY

Make-up water pressure bar

Make-up water temperature ºC

Make-up water flow rate kg/h

Condensate return pressure bar

Condensate temperature ºC

Condensate flow rate kg/h

Saturated heating steam pressure bar

Feed water tank required capacity m3

Max. dearated water flow required kg/h

Page 3: 5.133.E.BFT Boiler feed tanks€¦ · Steam boiler feed water. BFT – standard horizontal design. BFT/ADG or TDG – vessel and correspondent deaerator dome. BFTV – special vertical

ADCA

VALSTEAM ADCA We reserve the right to change the design and material of this product without notice.

IS BFT.20 E 09.12

VALSTEAM ADCA We reserve the right to change the design and material of this product without notice.

IS BFT.20 E 09.12

CONNECTIONS *

POS. Nº DESIGNATION REMARKS1 Boiler feed pump supply Larger diameter to optimize pressure loss (preventing cavitation)

2 Anti vortex ̶

3 Drain To be connected to a BEX (always at a lower level than the feed tank)

4 Overflow Float trap or “U” bend (only for atmospheric)

5 Heating steam Can be located at the domed ends

6 Chemical dosing Can be located at the domed ends

7 Condensate return Only if not connected to a dearetor dome

8 Soft water inlet Only if not connected to a dearetor dome

9 Vent outlet Only if not connected to a dearetor dome

10 Recirculating pump Recommended for atmospheric design only

11 Temperature indicator Can be located at the domed ends

12 Level indicator Can be located at the domed ends

13 Level controller Can be located at the domed ends

14 Headhole DN 300 PN 6 up to 1000 L

14 Manhole DN 500 PN 6 for 1250 L and above

15 Dome flange For ADG or TDG

16 Vacuum valve For pressurized systems only

17 Safety valve For presurized systems only

18 Temperature control Suitable for electrical or self operated valve control

19 Lifting eyes ̶

20 Name plate ̶* Sizes to be defined according to the real flow conditions.