5 Ways to Tell if Your Company is NFPA 70E Compliant David Paoletta, CSP Bay Area Safety Symposium 2020 [email protected] m

Transcript of 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical...

Page 1: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

5 Ways to Tell if

Your Company is

NFPA 70E Compliant

David Paoletta, CSP

Bay Area Safety Symposium 2020

[email protected]

m

Page 2: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Agenda

The Five Aspects of 70E Compliance

Quick review of Arc Flash Concepts & Hazards

(1) Do You Have a Plan?

(2) Are your Workers “Qualified” and “Authorized”?

(3) Do You Have the Right Tools for the Job?

(4) Do Your Electrical Work Areas Look Like This?

(5) Walk the Talk: Program Audits and Permits

Conclusion & Questions & Answers

www.NewDimensionsInSafetyLLC.com 2

Page 3: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Introduction

NFPA 70E (the Standard for Electrical Safety in the

Workplace) and OSHA regulations require using

electrical safety practices that reduce the risk of injury

to personnel to an acceptable level for equipment

installed IAW the NEC and maintained IAW NFPA 70B.

Electrical workers, according to NFPA 70E, are

workers who:

work inside the limited approach boundary, or

who perform zero energy verification as part of a

lockout/tagout procedure.

www.NewDimensionsInSafetyLLC.com 3

Page 4: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Limited Approach Boundary (arc + shock)

151 – 750 V = 3 ft. 6 in.

Flash Protection Boundary Calculated-can range from <1” to >10’600V Class nominal voltage ~ 5 ft.(Table 130.7(C)(15)(A)(b)

Restricted Approach Boundary (shock)

151 – 750V = 1 ft.

Critical Definitions/Concepts

www.NewDimensionsInSafetyLLC.com 4

Page 5: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Two Primary Electrical Hazards

Shock – injury from contact with energized electrical conductors and circuit parts Electrocution is death by electricity

Arc Flash – the passage of substantial electrical current through air Flash

Blast

Burns

Electrical Hazards to

Personnel

www.NewDimensionsInSafetyLLC.com 5

Page 6: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Electrical Hazards: Shock

www.NewDimensionsInSafetyLLC.com 6

Page 7: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Effects of Short Contact

For contact <0.1 second and with currents of several

amperes, ventricular fibrillation can occur

For contact >0.8 second and with currents just

greater than 0.5 A, cardiac arrest can occur

For contact >0.8 second with currents of several

amperes, burns and death are probable

www.NewDimensionsInSafetyLLC.com 7

Page 8: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Electrical Hazard: Arc Flash

www.NewDimensionsInSafetyLLC.com 8

Page 9: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Electrical Hazard: Arc Flash

www.NewDimensionsInSafetyLLC.com 9

Page 10: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Three Factors Affecting Arc Energy

Available short circuit current: (Amperes)

High may be worse – large amounts of energy

released

Low may be worse – longer to protective actions

Duration of the arc: (Cycles)

Long time to protective action (fuse blow or breaker

trip) is worse

Distance from the arc: (Ft. and In.)

Nearer to the arc is worse – the blast zone can

extend to beyond 10 feet from the initiating event

www.NewDimensionsInSafetyLLC.com 10

Page 11: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Introduction

Typical 1st & 2nd

Degree burns

from arc-flash

event.www.NewDimensionsInSafetyLLC.com 11

Page 12: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

www.NewDimensionsInSafetyLLC.com 12

Page 13: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Hazard Analysis

Shock or Arc Flash?www.NewDimensionsInSafetyLLC.com 13

Page 14: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Shock or. Arc Flash?

Hazard Analysis

www.NewDimensionsInSafetyLLC.com 14

Page 15: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Shock or. Arc Flash?

Hazard Analysis

www.NewDimensionsInSafetyLLC.com 15

Page 16: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Shock or. Arc Flash?

Hazard Analysis

www.NewDimensionsInSafetyLLC.com 16

Page 17: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

#1: Do You Have a Plan?

Assessment Points:

Does the facility have a written Electrical Safety

program?

Does the facility perform a documented self-

assessment periodically (not greater than 3 years)?

Does the facility conduct pre-job briefing/planning for

electrical work?

Does the facility utilize a permit system (EEWP) for

live work?

Have qualified electricians received documented

training for the tasks they perform?

www.NewDimensionsInSafetyLLC.com 17

Page 18: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Electrical Safety Program Requirements

The employer’s electrical safety program needs to address all

situations that can lead to the potential exposure of an employee

to an electrical hazard.

www.NewDimensionsInSafetyLLC.com 18

Page 19: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Electrical Safety Program Requirements

• Electrical Safety Risk Assessment

• Shock and Arc Flash Hazard Analysis

• Qualified Worker Training

• Electrical Safe Work Procedures

• PPE, Insulated Tool and Rubber Goods Program

• Requirements for Authorizing Energized Work

• Program Auditing

• Recordkeeping

www.NewDimensionsInSafetyLLC.com 19

Page 20: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Equipment Labeling – the Electrician’s

Friend

Switchboards, panel boards, industrial control panels,

motor control centers that are likely to require

examination, adjustment, servicing or maintenance shall

be marked with a label containing all the following:

Nominal system voltage

Arc flash boundary

Available incident energy and working distance OR the

arc flash PPE category –

Site specific level of PPE

Minimum arc rating of clothing

www.NewDimensionsInSafetyLLC.com 20

Page 21: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

#2: Do You “Qualify” Your

Electrical Workers?Assessment Points:

Have qualified electricians received documented

training for the tasks they perform?

www.NewDimensionsInSafetyLLC.com 21

Page 22: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

What is a Qualified Electrical Worker?

QUALIFIED PERSON:

One who has demonstrated skills and knowledge

related to the construction and operation of electrical

equipment and installations and has received safety

training to identify the hazards and reduce the

associated risk.

(NFPA 70E Article 100)

www.NewDimensionsInSafetyLLC.com 22

Page 23: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Qualified Electrical worker

• Can demonstrate

safe work practices

• Understands

electrical hazards

• Able & Capable of

performing electrical

work

• Knows methods of

release

• Able & Capable of

performing CPR,

AED & First Aidwww.NewDimensionsInSafetyLLC.com 23

Page 24: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Qualified Electrical Worker

• Able to anticipate

hazards

• Knowledgeable @

equipment

construction &

operation

• Ability to recognize

and avoid hazards

• Proper use of

electrically safe

procedures; PPE;

test equipment

www.NewDimensionsInSafetyLLC.com 24

Page 25: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Lets Get To Work!Task:

Access the white LCD

controller and run a

diagnostic test-

Is this electrical work?

www.NewDimensionsInSafetyLLC.com 25

Page 26: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Lets Get To Work!Task:

Perform LOTO verification

on this panel after opening

the upstream supply

breaker-

Is this electrical work?

www.NewDimensionsInSafetyLLC.com 26

Page 27: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

#3: Are You Using The Right

Tool For The Job?

Assessment Points:

Does the facility provide the tools and test equipment that are required to be used by the Qualified Person?

Are voltage rated gloves provided that adequately protect against equipment voltages that are present?

Are rated insulated gloves field-tested for damage and pinhole leaks before each use?

Are rated insulated gloves, mats and rubber goods electrically tested before issue and not greater than 12 months thereafter?

Are rated insulated gloves, mats and rubber goods date stamped to indicate when the equipment needs to be tested?

www.NewDimensionsInSafetyLLC.com 27

Page 28: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Arc Flash PPEArc Rated Face Shield / Arc Thermal Protection Value (APTV): 8 cal/cm2

Standards & Approvals: ANSI Z87.1 tested to ASTM F2178 specifications.

AR Coverall:

Arc Rating / Arc Thermal

Protection Value (APTV): 8

Fabric: UltraSoft

www.NewDimensionsInSafetyLLC.com 28

Page 29: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Shock PPE

www.NewDimensionsInSafetyLLC.com 29

Page 30: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Glove Testing

www.NewDimensionsInSafetyLLC.com 30

Page 31: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Shock PPE Testing

Testing requirements are from ASTM D120-09, Standard Specification for Rubber Insulating Gloves; and 29 CFR 1910.137 Table I-5.

www.NewDimensionsInSafetyLLC.com 31

Page 32: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Contact vs. Proximity ➔ Purpose

Zero energy verification – must include a contact meter

Other uses – proximity tester is ok

Ensure meters are rated for circuit

TEST the meter before and after zero energy

verification on known source to ensure safety

Selection and Use of meters

www.NewDimensionsInSafetyLLC.com 32

Page 33: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Selection and Use of meters

www.NewDimensionsInSafetyLLC.com 33

Page 34: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

#4: Do Your Electrical Work

Areas Look Like This?

www.NewDimensionsInSafetyLLC.com 34

Page 35: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Electrical Work Area

• Electrical sources and

approach boundaries

known

• Area posted & secured

• Electrically safe work

condition

• Worker in arc & shock PPE

• Observer trained in: /First

Aid/CPR/AED/Contact

Release

• Test equipment inspected

• Work procedure

• Pre-job briefingwww.NewDimensionsInSafetyLLC.com 35

Page 36: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Electrical Work Area

www.NewDimensionsInSafetyLLC.com 36

Page 37: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Electrical Safety Program: Verify that the principles and

procedures are in compliance with the standard. Not to

exceed 3 years

Field Audits: To verify that the ESP requirements and

work procedures are being followed.

All audits shall be documented

Completed risk assessments & Energized Electrical

Work Permits (EEWP) saved for 5 Years.

Corrective action tracking documented w/completion

dates

#5: Walk The Talk

www.NewDimensionsInSafetyLLC.com 37

Page 38: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Work Planning: Risk Assessment

The shock hazard analysis shall determine:

The voltage the worker will be exposed to

The boundary requirements

PPE

Must assess all exposed voltages within the limited approach boundary for type (AC, DC, RF etc.) and quantity (frequency and voltage)

The highest voltage determines the boundary limits

www.NewDimensionsInSafetyLLC.com 38

Page 39: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Work Planning: Risk

Assessment Arc Flash Analysis must determine:

The arc flash boundary

The incident energy at the working distance

The appropriate PPE required inside the arc flash boundary

Determination of this information may require assistance from an Electrical Engineer (requires panel and equipment-specific information to be properly calculated)

www.NewDimensionsInSafetyLLC.com 39

Page 40: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Work Planning: Risk

Assessment Energized electrical conductors and circuit parts must be put

into an electrically safe work condition before an employee

performs work within the Limited Approach Boundary.

Energized work is permitted if you can demonstrate that de-

energizing creates additional hazards. There are 3

justifications:

1. Equipment operating < 50 Volts

2. De-energizing introduces additional hazards or increased

risks

De-energizing is unfeasible due to equipment design or

operational limitations

www.NewDimensionsInSafetyLLC.com 40

Page 41: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

#5: Show Me Your Plan Reviews & Permits!

www.NewDimensionsInSafetyLLC.com 41

Page 42: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Review

Five Key Aspects of NFPA-70E Compliance:

1. Written Electrical Safety Program

2. Process to Train and authorize Qualified Electrical Workers

3. Appropriate Shock and Arc Flash PPE (including test meters and instruments)

4. QEWs use correct ESW procedures

5. Program audits and work process reviews

www.NewDimensionsInSafetyLLC.com 42

Page 43: 5 Ways to Know if Your Company is NFPA 70E Compliant · For complete NFPA 70 E and Electrical Safety Program support: - Program Writing -Program Implementation - NFPA 70E Training

Q & A

For complete NFPA 70 E and Electrical Safety

Program support:

- Program Writing -Program Implementation

- NFPA 70E Training - Program Assessments

- Hazard Analysis - Energized Electrical Work

Permits - Compliance Assistance

www.NewDimensionsInsafetyLLC.comwww.NewDimensionsInSafetyLLC.com 43