PRESSURE CONTROL
TRAINER
Instruction manual
Contents
1 Description2 Specifications3 Installation requirements
4 Installation Commissioning
5 Troubleshooting6 Components used7 Packing slip
8 Warranty
9 Theory10 Software11 Experiments
12 Components manuals
Product Code314, 314A
-
7/31/2019 5. Pressure Control Triner
2/35
Apex Innovations
26-03-2005 Im314 Page 2
Pressure control trainer is designed forteaching the basic pressure control
principles. Pressure transmitter senses
the pressure inside pressure tank andtransmits the signals to interfacing
unit/control module. The output ofinterfacing unit/control module is
connected to I/P converter. A pneumaticcontrol valve adjusts compressed air
flow from the tank outlet. The processparameter (pressure) is controlled
through computer or p controller bymanipulating the control valve. These
units along with necessary piping arefitted on support housing designed for
tabletop mounting.Product No. 314 is DDC (Direct Digital
Control) model, in which PID control
action is through software by computer.Product No. 314A is SCADA (Supervisory
Control And Data Acquisition) model, inwhich PID controlling is by digital
indicating controller. The computer isconnected to controller through
communication port in supervisorymode.
SupplyPressure
SignalPressure
Air Regulator
I/P Converter
Control Valve
Set Point
PressureTransmitter
Process Tank
Vent Valve
Pressure Controller
Air Supply
TankPressure
AirSupply
N
N
Product Pressure control trainer
Product code 314 314A
Type of control DDC SCADA
Control unit Interfacing unit with
ADC/DAC conversion
Control module with digital
indicating controller
Communication RS232
Pressure Transmitter Type Two wire, Range 05 bar, Output 420 mA
I/P converter Input 4-20mA, Output 3-15 psig
Control valve Type: Pneumatic; Size: 1/4", Input: 315 psig, Air toclose, Characteristics: linear
Process tank Pressure vessel, MS
Air filter regulator Range 0-2.5 kg/cm2
Pressure gauge Range 0-2.5 kg/cm2(1No), Range 0-7 kg/cm2(2Nos)
Overall dimensions 475Wx430Dx440H mm
Optional Compressor
Specifications
Description
-
7/31/2019 5. Pressure Control Triner
3/35
Apex Innovations
26-03-2005 Im314 Page 3
Product 314
Shipping details
Gross volume 0.10m3, Gross weight 43kg, Net weight 18kgProduct 314A
Shipping detailsGross volume 0.10m3, Gross weight 43kg, Net weight 18kg
Electric supplyProvide 230 +/- 10 VAC, 50 Hz, single
phase electric supply with properearthing. (Neutral Earth voltage less
than 5 VAC) 5A, three pin socket with switch (1
No.)
15A, three pin socket with switch for
compressor (if ordered)Air supply
Clean, oil and moisture free air,pressure 6 Bar, Air consumption 7.0
m3/hrComputer
IBM compatible with standard
configurationSupport table
Size: 800Wx800Dx750H in mm.
Installation Unpack the box(es) received and ensure that all material is received as per
packing slip (provided in instruction manual). In case of short supply or breakage
contact Apex Innovations / your supplier for further action.
Place the set up on table. Connect air inlet pipe to process tank and regulator.
Pierce hole on the pressure gauges with pin or needle. Connect the cables from interfacing unit/control module to the set up. Connect the interfacing unit/control module with computer to "COM" port.Commissioning Connect electric supply to interfacing unit/control module. Ensure the regulator is full open by rotating anticlockwise. Switch on the
compressor.
Adjust the air filter regulator to set supply air pressure at 25 psig. Set the interfacing unit/digital indicating controller to manual mode by pressing
the A/M key.
Increase output of interfacing unit/digital-indicating controller from 0 to 100% insteps of 25%. Check the pressure on pressure gauge at the output of the I/P
converter is varying from 3-15 psig and ensure that control valve operates from
full open to fully close position. Switch on the computer and install the software. Execute the software and ensure correct signals are displayed on computer.NOTE: Maintain the pressure of the process tank below 6 kg/cm2.
Installation Commissioning
Installation requirements
-
7/31/2019 5. Pressure Control Triner
4/35
Apex Innovations
26-03-2005 Im314 Page 4
Note: For component specific problems refer components manual
Problems Possible causes / remedies
Control valve doesnot operate
Valve diaphragm breakage Faulty I/P converter
No output from Interfacing unitI/P converter doesnot work
Insufficient supply air pressure Faulty electrical input signal Clogged orifice
No communication
with computer Improper COM port connection Computer COM port not working
No full screen display Ensure screen display settings are at 800 x 600pixels.
On desktop right click mouse button & clickproperties option. In General option- Settings- setfont size- small fonts
Components DetailsControl unit (For 314) Make Cuadra, Model AX-401, Input 4-20mA (1No),
Output 4-20mA (1No), Communication RS232Control unit (For
314A)Make Cuadra, Model AX-403, Input 4-20mA, with
RS485 to RS232 converterPressure Transmitter Make Keller, Model 21S, Output 4-20mA(2 wire),
Supply 24VDC, Range 0-5 bar, Process conn.
1/4"BSP(male), Accuracy +/-1%Digital indicating
controller(For 314A)
Make Yokogawa, Model UT320-01 (with RS 485
communication)I/P converter Make Control air inc, Type T500-AC, Input 4-20 mADC, output 3-15 psig, end connection 1/4 NPT
Control valve Make Apex, Model MX-101, Size x1/4, BodySS316, Trim SS316, Travel 10mm, Spring range 3-15psig, Characteristics linear, Action air to close, Valve
coefficient 0.04Air filter regulator Make Airmatic, Model MB10-021-VD-PAP, Range 0-2
Kg/cm^2, Type RelievingPressure gauge Make Waaree, Code: PW2.5GNNNS9 0-2.5 1/4"B,
Dia.2.5", Gly. filled, Brass internals, S.S. casing,
Range 0-2.5 Kg/cm2, 1/4"BSP (M) back connectionPressure gauge Make Waaree, Code: PW2.5GNNNS9 0-7 1/4"B,
Dia.2.5", Gly. filled, Brass internals, S.S. casing,Range 0-7 Kg/cm2, 1/4"BSP (M) back connection
Components used
Troubleshooting
-
7/31/2019 5. Pressure Control Triner
5/35
Apex Innovations
26-03-2005 Im314 Page 5
Product No.314
BoxNo.1/1
Size W500xD450xH425 mm; Volume:0.10m3 Gross weight: 43 kgNet weight: 18 kg
1 Set up assembly(Piping set & Male stud 2nos) 1 No
2 Communication cable 1 No
3 Tool kit 1 No
4 Set of instruction manuals consisting of:Instruction manual CD (Apex)
I/P converter manual (ControlAir)
1 No
Product No.314A
Box
No.1/1
Size W500xD450xH425 mm; Volume:0.10m3 Gross weight: 43 kg
Net weight: 18 kg
1 Set up assembly(Piping set & Male stud 2nos) 1 No
2 Communication cable 1 No
3 Tool kit 1 No
4 Set of instruction manuals consisting of:Instruction manual CD (Apex)
I/P converter manual (ControlAir)Users manual UT320 (Yokogawa)
Users manual reference CD (Yokogawa)
1 No
Packing slip
-
7/31/2019 5. Pressure Control Triner
6/35
26-03-2005 Im314 Page 6
This product is warranted for a period of 12 months from the date of supply againstmanufacturing defects. You shall inform us in writing any defect in the system
noticed during the warranty period. On receipt of your written notice, Apex at its
option either repairs or replaces the product if proved to be defective as statedabove. You shall not return any part of the system to us before receiving ourconfirmation to this effect.
The foregoing warranty shall not apply to defects resulting from:
Buyer/ User shall not have subjected the system to unauthorized alterations/additions/ modifications.
Unauthorized use of external software/ interfacing.Unauthorized maintenance by third party not authorized by Apex.
Improper site utilities and/or maintenance.We do not take any responsibility for accidental injuries caused while working with
the set up.
Apex Innovations Pvt. Ltd.E9/1, MIDC, Kupwad, Sangli-416436 (Maharashtra) IndiaTelefax:0233-2644098, 2644398
Email: [email protected] Web: www.apexinnovations-ind.com
Warranty
-
7/31/2019 5. Pressure Control Triner
7/35
26-03-2005 Im314 Page 7
COMPUTER CONTROL TECHNIQUES
Direct Digital Control (DDC)The method of process control described by the term DDC (Direct Digital Control)
applies to those cases in which digital logic circuits or a computer are an integral partof the loop.
The software program defines all the control function, setpoint and deviation aboutthe nominal. Direct digital control has the capacity to control multivariable processes
with interaction between elements.
This is most economically developed process control system basically used forlaboratory scale application. In this system the process signals are transmitted to
computer through interfacing unit. Along with data acquisition the software has
capability of controlling the process.
Comparator
PID Control
Measured VariableMeasurement
Control Element Process
ControlledVariable
Load
Set Point
Computer
Supervisory Control And Data Acquisition (SCADA)In SCADA systems process signals are transmitted the local controller. The controller is in
communication with central computer. The software performs the function of data acquisition,display and analysis. The controller settings can be changed from computer. The computer has asupervisory role as controlling is done by local controller.
Comparator
PID Control
Computer
Measured Variable
Control Element Process
ControlledVariable
Load
Set Point
Digital Indicating Controller
Theory
-
7/31/2019 5. Pressure Control Triner
8/35
26-03-2005 Im314 Page 8
PROCESS CONTROLLERIn automatic controlled process the parameter to be controlled is measured and
compared with the set point by process controller. The difference between themeasured signal and the set point is error. The controller performs on-line
calculations based on error and other setting parameters and generates an output
signal. The output signal drives the final control elements like control valve or a
damper to control the process to the set point.
Error Controller OutputController
Feedback Signal
Block Digaram of Typical Controller
Process Parametert
ReferenceSignal
On/Off controllers
Time
SetValue
On-Off Controller
Dead Band
A special case of proportional control is On-Off control. If the proportional band ofthe controller is made very low (=0) the controller out put will move from one
extreme position to other for slight deviation of process value from the set point.This very sensitive action is called On-Off control because final control element is
either open (On) or close (Off) i.e. operates like a switch. These are the simplest
controllers.These controllers incorporate a dead band to keep the output from cycling rapidly
between on and off. The controller will not turn on or off until the error signal movesout of the dead band. The process variable controlled by an on/off controller always
cycles back and forth about the set point as shown in the fig. Dark line and dottedline shows process parameter and reference values respectively.
Hysteresis is a value set in the vicinity of on-off operating point. Upper hysteresis isvalue or band in which process value is allowed to operate above the set point and
lower hysteresis is value or band in which process value is allowed to operate below
the set point.
Proportional (P) controllers
-
7/31/2019 5. Pressure Control Triner
9/35
26-03-2005 Im314 Page 9
Time
Param
eterValue
Propertional Controller
Offset
In proportional controller the control algorithm generates a linear control output
proportional to deviation. In proportional action the amount of change in themeasured value (or deviation) is expressed in percent of span that is required to
cause the control output to change from 0 to 100 % is called the proportional band.The controller output is given by:
ePB
bOP +=100
Where, OP is the output, PB is proportional band in %, b is the bias value, and e is
the error signal. If there is no biasing, output OP will become zero when error iszero. Hence bias value decides the value of output when error is zero.
The proportional controllers usually show some difference between the set point andprocess variable called offset. The offset can be reduced by decreasing proportional
band or by readjusting the bias. With decrease in proportional band the processbecomes oscillatory.
There are two types of controller actions:
1) Increase-increase in which output increases as measurement increases.(error e = measurement set point)
2) Increase-decrease in which output decreases as measurement increases.
(error e = set point measurement)
Proportional- Integral (PI) controllers
Time
ParameterVale
Propertional - Integral Controller
The offset in proportional controller can be overcome by adding integral action. Thecontrol algorithm that applies changes in output as long as deviation exits, so as to
bring the deviation to zero, is called integral action. Output of proportional-Integralcontrollers is given by:
++= dteTiePBbOP1100
-
7/31/2019 5. Pressure Control Triner
10/35
26-03-2005 Im314 Page 10
Where OP is the output, b is the bias, PB is the proportional band in %, e is the error
signal, Tiis integral time; this is the time required to repeat proportional action.
Proportional-Derivative (PD) controllerThis mode of control is described by the relationship
++= dtde
TdePBbOP
100
Where OP is the output, b is the bias, PB is the proportional band in %, e is the errorsignal, Tdis derivative time.Larger the derivative time larger is the action. Smaller is the proportional band thelarger is the derivative action.
In order to achieve faster response and more stable operation in slow processesderivative action is added to apply an output component proportional to the rate of
change of input (error). Derivative action is used with P action or PI action.
ProportionalIntegralDerivative (PID) controllersPID controllers are used for controlling almost all process variables like temperature,flow, level, pressure etc. in a continuous or batch process.
The output of a PID controller is given by:
+++= dtde
TddteTi
ePB
bOP1100
Where OP is the output, b is the bias, PB is the proportional band in %, e is the errorsignal, Ti is the integral time and Tdis derivative time.Selection of proportional band, integral time and derivative time to achieve desiredprocess response to load changes is called tuning of controller.
-
7/31/2019 5. Pressure Control Triner
11/35
26-03-2005 Im314 Page 11
CONTROLLER TUNINGThe three-mode controller (PID) is the most common feedback controller used in
industrial control. The method of determination of the optimum mode gains,depending on the nature and complexity of the process is known as loop tuning.
The three parameters should be selected to meet a set of defined goals. These goals
typically require a plant response with minimum steady state error, insensitivity to
load disturbances and an acceptable transient response to set point changes anddisturbances.In practice the choice of proportional band, integral time and derivative time is a
compromise between the set point tracking and disturbances. If a mathematicalmodel of the process is known, selecting the controller parameters is relatively
simple. But in many industrial applications, a reliable mathematical model is notavailable or it is difficult to determine. So empirical rules are developed for PID
tuning which do not require mathematical model. A widely used set of rules is
proposed by Ziegler- Nichols by open loop method and close loop method in 1942.
Open loop method (Process reaction curve metood)In open loop method the process is assumed to be model of first order. The step
response i.e. process reaction curve, allows to obtain the approximate values of P, I
and D parameters. With the feedback loop open, a step response is applied tomanipulated variable and the values of P, I and D are estimated.
Time
10
10
0 20
20
30
30
40
40
ControlledVariable
L X
Y
Open loop response for input step change
(Process reaction curve)
WhereSlope R: Slope of line drawn tangent to the point of inflection.
X
Y
time
riableChangeinVaR ==
(min)
%
Dead time L: Time between the step change and the point where tangent line
crosses the initial value of the controlled variable (in min.)
P = Step change applied in %
-
7/31/2019 5. Pressure Control Triner
12/35
26-03-2005 Im314 Page 12
Using these parameters, the empirical equations are used to predict the controller
settings for a decay ratio of 1/4.
For P, PI and PID controller the parameters are calculated as follows.
Mode Proportional band(in %)
Integral time(in Min)
Derivative time(in Min)
P 100RL/P
P+I 110RL/ P L/0.3P+I+D 83RL/ P L/0.5 0.5L
Closed loop method (Ultimate gain method)This method is also called as ultimate gain method. The term ultimate was attachedto this method because its use requires the determination of the ultimate
proportional band and ultimate period. The ultimate proportional band, PBu is theminimum allowable value of proportional band (for a controller with only proportional
mode) for which the system continuously oscillates at constant amplitude. Theultimate period, Tu is the period of response with the proportional band set to its
ultimate value. To determine the ultimate proportional band and ultimate period the
proportional band of the controller (with all integral and derivative action turned off)
is gradually reduced until the process cycles continuously.
Time
Outut
Continuous Cycling
Tu
Response curve for ultimate gain and period
The process is placed in the closed loop with a proportional controller. The
Proportional band is decreased until the process goes to continuous oscillations. Thecorresponding value of proportional band is called as ultimate proportional band PBu
and the period of oscillation is called the ultimate period Tu. The PID controller
parameters are selected from the following table.
Mode Proportional Integral Derivative
P 2 PBu
P+I 2.2 PBu Tu/1.2
P+I+D 1.65 PBu 0.5 Tu Tu/8.0
-
7/31/2019 5. Pressure Control Triner
13/35
26-03-2005 Im314 Page 13
FREQUENCY RESPONSE ANALYSISLaplace transform techniques are used to express mathematical models in terms of
transfer functions in order to calculate transient response. An alternative way tointerpret the transfer function model, refereed to as the complex transfer function or
the frequency response. It shows how the output response characteristics depend
upon the frequency of the input signal. This is the origin of the term, frequency
response.
Stability analysis by using bode plotsFrequency response may be plotted in three ways:i. The rectangular plot with amplitude ratio verses frequency and phase lag verses
frequency.ii. A polar plot with magnitude and phase shown in vector form with frequency as a
parameter.
iii. A phase margin plot with magnitude shown verses a function of phase withfrequency as a parameter.
If the system is linear, the output signal for sine wave input must be a sine wavehaving the same frequency as the input.
Assume that the input to the first order system is suddenly switched from a constant
input to a sine wave input. The initial slope of the sine wave input signal may beapproximated by a ramp input or even exponential input.
If the input frequency is very low, period of the sine wave will be very long. Stated inanother way, period is very much larger than the system time constant. Under this
condition the output will have sufficient time to approach the condition, which isnearly in equilibrium with the input signal. Thus, at low frequencies both magnitude
and phase angle of the output signal will be close to magnitude and phase angle ofthe input signal. However as the frequency increases period decreases, and the
system does not have sufficient time to achieve the equilibrium status between input
and output. Under these conditions output magnitude will decrease, and outputphase angle will fall behind or lag the input phase angle. Thus it is evident that any
solution must show a decrease in ratio of output to input magnitude as frequencyincreases.
Magnitude and phase angle calculation:Let,
M Magnitude ratio
A1 Input amplitude (%)A2 Output amplitude (%)
Phase angle (degrees)x lag (seconds)
T Period (seconds)f frequency (cycles per seconds) = 1/T.
Then,M = A2/A1
= (x/T) x 360
-
7/31/2019 5. Pressure Control Triner
14/35
26-03-2005 Im314 Page 14
TimeFrequency Response
Outpu
Inpu
T
X
A2
A1
BODE diagramIn Bode diagram the magnitude ratio verses frequency is plotted on log-log co
ordinates and the phase angle verses frequency on semi-log coordinates.
Frequency
Bode Diagram
Frequency
Log Scale
0.1
0.1
-180
0.1
0.01
0.01
1
1
-90
1
10
10
0
10
PhaseA
ngleDeg
MagnitudeRatioM
Stability criteria A system is stable if the phase lag is less than 180 Deg. at the frequency for
which the gain is unity (one). A system is stable if the gain is less than one (unity) at the frequency for which
the phase lag is 180 Deg.
-
7/31/2019 5. Pressure Control Triner
15/35
26-03-2005 Im314 Page 15
Windows based control software package provided is designed to fulfill basic pressure
control study. It helps in understanding PID logic and combinations of differentcontrol actions.
Installing the software package
Switch on computer. Ensure display settings are 800x600 pixel and font size issmall fonts.
Create separate directory and copy software files & instruction manual from theCD supplied with the product.
Create a short cut on the desktop for the executable file. Click on the icon created on the desktop to execute the software.Getting startedReal time data accessFor DDC model: Select Data Access |Interface. Select Start.
For SCADA model: Select Data access| Microprocessor| COM1 or COM2 as thecase may be. Select Start.
Studying data logging from file
Select Data Access, controland then Data File. By default data file for PID controlis opened using a dialog box to select file name.
Software
-
7/31/2019 5. Pressure Control Triner
16/35
26-03-2005 Im314 Page 16
Menus
Data Access
This menu gives three options to start the experiments.
Interface/ microprocessor
Selecting this option, accesses real-time data from field using interfacing unit/control
module.Data FileThis option accesses data from stored file. Results and data of experiment conducted
are observed. A file open window lets you open the desired file. There is a predefined
file extension. While opening the file user need not know the file extensions,software lists the files related to the experiment. User can see the data, stored in
file, in the form of tables as well as graphs.Simulator
This option accesses data from PID simulation logic. The user has to enter processvalue and set point. With different values of the PID parameters, user can observe
the change in the controller output to the error produced. Changing set point
produces error to the controller.Control
This menu gives two options to select control mode.
Closed loop: This option enables, close loop control action. In this action, controllercalculates output to the process based on process parameters automatically.
Open loop: This option enables the open loop control action. Selecting this optioncontrol loop is opened i.e. output to the controller can be changed manually.
Controller does not work in open loop.
Controller
-
7/31/2019 5. Pressure Control Triner
17/35
26-03-2005 Im314 Page 17
It provides four different modes of controller for controlling the process variable.
Each controller is provided with separate controller setting facility. Select respective
controller and set the desired control parameters. Various types of controller arementioned below.
On Off: This option allows selecting on-off controller.P: This option allows selecting Proportional controller.
PD: This option allows selecting Proportional + Derivative controller.PID: This option allows selecting Proportional + Integral + Derivative controller.
Note: PI controller can be set in PID controller option by keeping the derivative time
equal to zero.Function Generator
This option is used to apply the dynamic input to the process. The dynamic
(sinusoidal) wave form is applied to the process. During the close loop operation the
function is applied to the set point, in open loop operation the function is applied to
output.
On: Enables the function generator selection. Amplitude and period is entered to the
wave.Off: Stops the function generator.
LogOn: Enables the data logging.
Off: Stops the data logging.
Print
Use Print for printing graphs and data table from Data File.Graph: To print graph click pause when you reach at the desired data plotting.
Select print then graph to get a window for printer selection. Select a printer and
click OK to print selected graph. Again clicking the run switch will start the plottingof the remaining data.
Tables: Data table for PID values is available. Select any option for printing.PID Tune contains tuning values set during experiment. Select Print then Table
with option to get a window for printer selection. Select a printer and click OK toprint selected graph.
StartClick Start to activate selected Data Access option.
Stop
Click Stop to deactivate selected Data Access option.ShutdownSelect Shutdown for closing software application.
Basic functionsON- OFF ControlOn - off control compares set point and process value and gives output an ON or OFF
signal according to the positive or negative deviation.Hysteresis: A value set in the vicinity of the on/off operating point is referred to as
the hysteresis.Upper hysteresis and lower hysteresis can be set. To set hysteresis
values Tune button is provided on the screen.PID controlPID controller compares set point and process value. It gives output by calculations
based on PID logic. To setPID values Tune button is provided. Set values for P, I,
D; Outputhigh, Output low and Action. Use Download for applying new valuesfor controller.
PProportional band value for this controller is denoted by P. Set proportional band
values.
-
7/31/2019 5. Pressure Control Triner
18/35
26-03-2005 Im314 Page 18
I
Integral time for controller denoted by I and it is applied in seconds.
DDerivative time for controller denoted by D and it is applied in seconds.
BiasBias is the value of normal output of controller at zero error. This option appears if
Proportional controller or Proportional + Derivative controller is selected..Output High
Higher bound of the controller output
Output LowLower bound of the controller output
ActionIn INC-INC mode, increase in process variable increases controller output & vise-
versa. For INC-DEC mode, increase in process variable decreases controller output& vise-versa.
Download
Use Download for applying new values for controller.PID Tune screen
-
7/31/2019 5. Pressure Control Triner
19/35
26-03-2005 Im314 Page 19
Switching between auto and manual
You can use a button, marked Auto (by default) for switching between the two
modes. Click to change the mode from Auto to Manual. Click again to change themode from Manual to Auto. In Auto mode output of process is controlled by
software and in Manual user controls mode output of process.Pause or Run trend graph in offline
In Data File, Data access mode a button marked Pause (by default) is used to stopthe trend graphs.
To run the trend graph click RUN display.
Stored data screen
-
7/31/2019 5. Pressure Control Triner
20/35
26-03-2005 Im314 Page 20
Setting parameters for digital indicating controller(For product no. 314A )[Refer instruction manual of the controller (separately provided) for controller
operation].
Operating parameter
table
Setup parameter table Input output related
LED Display Value LED Display Value LED Display Value
Press ENT for 3 sec. OP.PA (pressup/down):
STUP (press ENT)
FUnC (press up/down):I/o (press ENT)
oP.PA Pyd 0 I/O
LL (**) oFF FUnC In 41
A1 100.0 SPH (**) 100.0 RH 5.000
A2 0.0 SPL (**) 0.1 RL 1.000
A3 100.0 AL1 1 SdP 1
At oFF AL2 2 SH 100.0
SC oFF AL3 1 SL 0.0
SP.no 1 Hy1 0.5 bSL 1PId MenU or Hy2 0.5 Ot 2
FL oFF Hy3 0.5 rEt 3
bS 0.0 dY1 (**) 0.00 rtH (**) 100
UPr oFF dY2 (**) 0.00 rtL (**) 0
dnr oFF dY3 (**) 0.00 diS 1
oH 100.0 Ct 30 C.S1 oFF
oL 0.0 Po 0.0 C.S2 oFF
dr 0 C.md 0 C.S3 oFF
Hb1 oFF Zon oFF C.S4 oFF
Hb2 oFF Ar Auto LoCK oFF
HC1 0.0 tmU 1HC2 0.0 P.SL 0
orb 1.0 bPS 4
orH 100.0 PrI 0
orL 0.0 StP 1
or 0 dLn 8
1.SP 50.0 Adr 1
2.SP 0.1 rP.t 0
3.SP 0.1 test 0
4.SP 0.1
(**) Marked steps are not visible in some controller models.
-
7/31/2019 5. Pressure Control Triner
21/35
26-03-2005 Im314 Page 21
Note:The experiment nos 1 thr 6 are to get feel of the process and PID settings.
1 Study of open loop response (Manual control)
Procedure Start up the set, adjust the vent valve. Select open loop option from software. Close the control valve by increasing the controller output to 100%. Apply the step change by 10% to controller output in manual mode, wait for
process value to reach the steady state value.
Repeat the above step until the controller output reaches to minimum 0%.Observations
Tabulate the observations as follows
Controller output in % Process Value in %
100
90
80
0
From the above data, note the output required for maintaining the process atdesired set points. (for particular vent valve opening).
Set the output of the controller to the noted value and at steady state apply theload change to the process. Load change can be given by slightly varying thevent valve. Observe new steady state process value.
Experiments
-
7/31/2019 5. Pressure Control Triner
22/35
26-03-2005 Im314 Page 22
2 Study of on/off controllerProcedure
Start up the set up and select close loop option for control from software. Set the controller to On/Offmode. Press Tune & set the upper and lower hysteresis of the controller. Change the values of the set point and observe the On-Off control operation.Observations
Observe that if process value exceeds the set point, controller closes the valve and if
process value decreases below the set point control valve opens, i.e. the controlleroperates like On/Off switch.
-
7/31/2019 5. Pressure Control Triner
23/35
26-03-2005 Im314 Page 23
3 Study of proportional controllerProcedure
Start up the set up and select close loop option for control from software. Set the controller to proportional control (P) mode. Adjust the process value by switching the controller to manual mode to a
particular pressure (say 50 %) on the screen and apply output of the controlleras bias value. Change the proportional band to 100%.
Switch the controller to auto mode. Apply step change of 10% to set point. Switch the controller to manual mode. Decrease proportional band to half of the
previous value. With each decrease, obtain a new response of the step change.Ensure that the set point changes are around the same operating point (Say
50%).
Observations
Observe the effect of very low proportional band values (system works as on-offcontrol).
Observe the response of the system at load change. Load change can be given byslightly manipulating the vent valve of the tank.
-
7/31/2019 5. Pressure Control Triner
24/35
26-03-2005 Im314 Page 24
4 Study of proportional integral controllerProcedure
Start up the set up and select close loop option for control from software. Select PID controller. Set the proportional band estimated in Proportional control.
Set derivative time to 0 sec and integral time 6000 sec, which will cut off the
derivative action and widen the effect of integral action.
Set the set point to desired flow value. Allow the process to reach at steadystate. Record the steady state error.
Switch the controller to manual mode. Reduce the integral time to half of theprevious value. Switch to Auto mode and apply step change(+/- 10%) to the set
point. Note the response of the system. Repeat above step to observe the effect of changes in Integral setting.Observations
Observe the effect of reducing integral time on the response of the process.
-
7/31/2019 5. Pressure Control Triner
25/35
26-03-2005 Im314 Page 25
5 Study of proportional derivative controllerProcedure
Start up the set up and select close loop option for control. Select PD controller. Set the proportional band estimated from Proportional
control (P only) Set derivative time to 0 and integral time=6000 sec.
Set the set point to desired value. Allow the process to reach at steady state.Note the response of the system.
Switch the controller to manual mode Increase the derivative time by 1 sec.Switch to Auto mode and apply step change to the set point by 5 to 10%. Notethe response of the system.
Increase the derivative time gradually and observe the process response for stepchange.
Observations
Compare the steady state response of the PD controller with PI controllerobtained in the previous experiment.
-
7/31/2019 5. Pressure Control Triner
26/35
26-03-2005 Im314 Page 26
6 Study of proportional integral derivative controllerProcedure
Start up the set up. Select close loop option for control from software. Select PID controller. Switch the controller to manual mode. Change the proportional band to the value that estimated in proportional
controller. Set integral time and derivative time based on the responses in
previous experiments.
Adjust the set point to @ 50 %. Switch the controller to auto mode. Apply stepchange of 10%. Observe the process response.
Change the proportional band, integral time, derivative time and observe theresponse of the process for step change for each change in setting.
Observations
Compare the steady state response of the PID controller with P. PI and PD controller
obtained in the previous experiments.
-
7/31/2019 5. Pressure Control Triner
27/35
26-03-2005 Im314 Page 27
7 Tuning of controller (Open loop method)Procedure
Start up the set up and select Open loop option for control. Adjust controller output, so that the process value is maintained at 50%. Start data logging. Apply a 20 - 30 % change to controller output. (Open the control valve) Record
the step response. Wait for the steady state.
Stop data logging. Plot the step response (Process reaction curve) from stored data. Find out the
value of slope at the point of inflection and time lag.
Calculate P I D settings for different modes. Select close loop, switch auto manual key to auto mode and then select
controller to study. Set the PID values obtained from the calculations. Apply thestep change & observe the response of the system. Allow the system to reach
steady state.
Observations
(Refer theory for formulae.)
Step change to the system P = Initial output - Final output of the controller.
Plot the graph of process value Vs Time on a graph paper.From process reaction curve: Slope of the process reaction curve R = Time lag L=
Calculate P, PI, PID setting from above values.
Observe response of the system for different PID settings.
-
7/31/2019 5. Pressure Control Triner
28/35
26-03-2005 Im314 Page 28
8 Tuning of controller (Closed loop method)Procedure
Start up the set up and select close loop control. Select P controller only. Set the proportional band value to maximum (Say 200).
Set the controller to manual mode and adjust the output so that the process
value reaches to 50%.
Switch the controller to auto mode and decrease the proportional band and applythe step change to the set point and observe the process response.
Repeat the above procedure and find out correct value of proportional band forwhich the system just goes unstable i.e. continuous oscillations are observed in
the output of controller. Record the ultimate proportional band and ultimate period from the response. Calculate the PID values from the table. Select the PID controller and apply the
parameter values obtained from the above steps. Observe the response of the
process to a step change with these settings.
Observations
Record the ultimate proportional band (Pbu) and ultimate period (Tu) from aboveexperiment.
Calculate PID values by referring theory part for different control actions. Observe the process response for these settings. Compare the values obtained with open loop response method.
-
7/31/2019 5. Pressure Control Triner
29/35
26-03-2005 Im314 Page 29
9 To study stability of the system (Bode plot)Procedure
Start up the set up and select open loop option from software Start data logging. Select function generator to apply the sinusoidal input to the output of the
controller.
Enter Reference point, Amplitude and Period. Observe the sinusoidal output of the controller and sinusoidal response of the
process. Log the data for records. Change the period and repeat the observation for 3-4 different values of the
period.
Repeat above procedure for different amplitude and period values.
Observations
From the data file stored observe the output response of the process and notedown the output amplitude.
Measure output wave period and note down as T sec. Measure the phase lag x
and note down in sec.Obs.
No.
Input
amplitudeA1 %
Output
amplitudeA2 %
Output
PeriodTin sec
Lag X
In sec
Frequency
Calculations
Calculate for each observationMagnitude ratio as M = A2/A1
Phase angle = (X/T) x 360Frequency = 1/T cycles / sec.
Draw the graphs of:
Magnitude Vs frequency on log - log scalePhase angle Vs frequency on semi-log coordinates.
Study the graph for stable conditions mentioned in theory.
-
7/31/2019 5. Pressure Control Triner
30/35
26-03-2005 Im314 Page 30
Electro pneumatic transducer (I/P)The ControlAir Type 500X converts a current input signal to a linearly proportional
pneumatic output pressure.
Technical specificationsModel 500X-ACMake ControlAir
Input 4-20 mAOutput 3-15 psi
Min./Max supply pressure Min. 18 psig, Max 100 psigLinearity +/-0.75 % of span
Repeatability
-
7/31/2019 5. Pressure Control Triner
31/35
26-03-2005 Im314 Page 31
TroubleshootingProblem Check
No output or low output Zero adjustment
Supply pressure too low
Clogged orifice
Leakage ConnectionsLow or improper span Zero and span adjustments
Supply pressure too low
Output leakage
Erratic operation Electrical input signalLoose wires or connections
Liquid in air supply
Calibration1 Open protective covers to expose zero and span adjustment screws.
2 Connect the recommended air supply to the inlet of the transducer and an accuratepressure gauge at the outlet.
3 connect the electrical input and set it to 4 mA.4 Observe the output pressure. If necessary adjust zero screw until reaching
minimum output pressure setting (3 psi). Turn zero screw counter clockwise toincrease pressure, clockwise to decrease pressure. If unable to achieve output
during calibration process, turn zero adjustment screw counter clockwisefor up to 30 revolutions, until output pressure rises.
5 Increase electrical input to 20 mA
-
7/31/2019 5. Pressure Control Triner
32/35
26-03-2005 Im314 Page 32
6 Observe the output pressure. If necessary adjust the span screw until output
pressure reaching 15 psi. Turn span screw counter clockwise to increase pressure,
clockwise to decrease pressure.7 The zero span adjustments are interactive. After adjusting the span it will be
necessary to recheck the zero. Repeat steps 3-6 until both end points are at therequired values.
Manufacturers addressIf you need any additional details, spares or service support for this unit you may
directly communicate to the manufacturer / Dealer / Indian Supplier.
Control Air Inc.8 Columbia Drive, Amherst, NH 03031
USAEmail: [email protected]
Indian supplier:Control teknics
5,Aboorva Flats, old No.6, New No. 117th main road, Raja Annamalaipuram
Chennai - 600 028Email: [email protected]
-
7/31/2019 5. Pressure Control Triner
33/35
26-03-2005 Im314 Page 33
Mini combination air filter regulatorThese modular series filter regulator are high flow, low pressure, and high accuracy.
Technical specifications
Make AirmaticModel MB10-021-VD-PAP
Range 0 2 Kg/cm2Type Diaphragm, Relieving
Connection BSPBody Aluminium
Bowl PolycarbonateElement Porous material
Drain BrassSeals Buna N
Diaphragm Buna N
Spring pressure Spring steel Zn platedSpring valve Stainless steel
Spring cage and nob Acetyl resinGauge ports Two
Element rating 25 micronDrain Manual
Bowl capacity 30 ml
Max. pressure 12kg/cm2Max. temperature 500C
Overall dimensions 40diameter x 155 H mmWeight 220 gm
Manufacturers addressIf you need any additional details, spares or service support for this unit you maydirectly communicate to the manufacturer / Dealer / Indian Supplier.
Shah pneumatics
28/30, Navketan Industrial Estate,Mahakali Caves Road, Andheri (E)
Mumbai 400 093.E-mail: [email protected]
Web: www.shahpneumatics.com
-
7/31/2019 5. Pressure Control Triner
34/35
26-03-2005 Im314 Page 34
Pressure gaugeIntroduction
Pressures gauges are suitable for use with air, oil, water or compatible gases. The
phosphor bronze bourdon tube is housed within a rugged SS case. The aluminum dialand pointer are protected by an impact resistant polycarbonate window. Accuracy is
+/- 3-2-3% per ASME grade B. Brass back connection is male NPT.
Technical specificationsMake Waaree Instruments
Code PW2.5GNNNS9 0-2.5 B
Pressure gauge 2.5 diameterLiquid filled Glycerin
Internals part BrassHousing SS
Range 0 2.5 and 0 7 Kg/cm2Connection center back
Accuracy +/-3-2-3% per ASME grade B.Media Clean, no corrosive liquid
Bourdon tube Phosphor bronze
Dial/pointer Aluminum dial with black enameled pointerWetted parts Phosphor bronze bourdon tube with brass
stemTemperature range -10 to 800C
Mounting Panel mountingOverall dimensions 70diameter x 55mmL
Weight 140 gm
Manufacturers addressIf you need any additional details, spares or service support for this unit you maydirectly communicate to the manufacturer / Dealer / Indian Supplier.
Waaree Instruments Ltd.10, Damji Shamji Industrial Complex,
Off Mahakali Caves Road, Andheri (E),
Mumbai 400 093.
E-mail: [email protected]: www.waaree.com
-
7/31/2019 5. Pressure Control Triner
35/35
Pressure TransmitterPressure transmitters are use for air, fluid and gas pressure in the close tank.
Technical specificationsModel 21S
Make Keller
Output 4-20mA (2wire)Supply 24 VDCPressure Range 0-5 Bar
Process connection BSP (Male)
Accuracy +/-1%
TroubleshootingProblem Check
No output at the output pin Check the wiring configuration.
Check the input + Vcc supply.
No variation in the output Check for the leakage at pressure port.
Check for the span set of indicator / controller.
Pressure not holding at constant
input pressure
Check for the leakage at pressure port.
Manufacturers addressIf you need any additional details, spares or service support for this unit you maydirectly communicate to the manufacturer / Dealer / Indian Supplier.