Schneider buswayfrom 800 to 6000 A
I-LINE II
Catalogue 2008
-
7/28/2019 5. I LINE II -Schneider Busway-2008
3/111
1Schneider Electric
Contents
Introduction 3
Presentation and description 19
Catalogue numbers and dimensions 35
Design guide 81
Installation guide 95
In decentralised distribution, Schneider busway hits the high note!
With Schneider busway, you play all the right notes!Schneider busway, in total harmony with the environment!Schneider busway, fortissimo throughout the range!Schneider busway, a display of advantages!Schneider busway, every one to their music!Schneider busway, hits the right notes!With the Schneider busway tools and services, let us compose your project!
Panorama of Schneider busway rangeGeneralStraight lengthsFittingsSupports and xings
Special ttingsPlug-in units
Catalogue number coding
I-LINE II Copper Busway (CFC)Straight lengthsStraight length componentsElbowsFlanged endsCable Tap BoxSupports and xings
I-LINE II Copper Contact Busway (BFC)Straight lengthsStraight length componentsElbowsFlanged endsCable Tap BoxSupports and xings
Plug-in units
CharacteristicsDesigning with I-LINE II busbar trunking systemHarmonic currentsFire resistance
Measurements and meteringDirect current
Layout adviceHorizontal distributionRising mainsReception, handling and storageTesting and CommissioningMaintenance
3
46810121617
2026282931
3233
36
383941515455
585961666970
72
82848890
9294
9699100102104108
-
7/28/2019 5. I LINE II -Schneider Busway-2008
4/1112 Schneider Electric
-
7/28/2019 5. I LINE II -Schneider Busway-2008
5/1113Schneider Electric
Introductio
n
In decentralised distribution,Schneider busway hits the high note!
Schneider busway on its second world tour
More than 50 years of experience, with hundreds of thousands of installations inoperation throughout the world. Full KEMA type test certication (IEC60439) for each and every ampere ratingof busway.
A total coordination with theSchneider Electric systemBusway is a part of a comprehensive offering of Schneider Electric productsdesigned to operate together. This concept covers all low and mediumvoltage electrical distribution components. The result is an optimised electricalinstallation with even higher performance through full electrical, mechanical andcommunication compatibility.With the new range, you get a complete, tested distribution solution thatcomplies with standards. It is perfectly suited to traditional applications (factories,
warehouses, etc.) and to the distribution of electrical power from the incomingtransformer on through to all types of loads in ofces, commercial premises,laboratories, etc.
Schneider Busway Guangzhou was initially set up by Square D, USA in 1997, andnow is a professional busbar trunking manufacturer, product including I-LINE II andCanalis series, mainly supplying to the Asia Pacic and Middle East market.
More than 50,000 km of Schneider busbar trunking has been
sold around the world.
Square D facility in Oxford, Ohio U.S.A. is an ISO 9001 and
ISO 14001 registered busbar trunking manufacturing facility.
Schneider Buway (Guangzhou) Ltd. is certied having ISO
9001 quality management system, ISO 14001 environment
management system and OHSAS 18001 occupational health
and safety management system.
I-LINE busbar trunking system was rst introduced by Square D in 1961 in itsproduction facility in Oxford, Ohio U.S.A. As one of the major brands of theSchneider Electric, Square D has acquired worldwide recognition in a variety ofbusway applications.
Dijon Factory was set up in 1972, manufacturing Canalis Busbar trunking system,ISO 9001 and ISO 14001 certied.
Canlis Factory, Dijon, France
Schneider Busway Factories
-
7/28/2019 5. I LINE II -Schneider Busway-2008
6/1114 Schneider Electric
Introductio
n
With Schneider busway, you playall the right notes!
Distribution systems Schneider Electric offers different distribution systems to t your operating needs.
Centralised distribution
For all continuous processes: cement plants, oil and gas, petrochemicals, steel, paper, etc. Centralised distribution offers: continuity of service, combined distribution of power, control and monitoring circuits,
supervision, etc.Our solutions: Prisma Plus and Okken switchboards.
Decentralised distribution
For manufacturing industries: mechanical, textiles, lumber injection moulding, electronics, pharmaceuticals,
livestock, etc. Decentralised distribution lets you: design installations without layout details, upgrade without shutting down production, get systems up and running sooner thanks to faster installation, generate savings depending on the number of loads.
Our solutions: Prisma Plus switchboards, Schneider busbar trunking.
Combined distribution
Where the advantages of both centralised and decentralised distribution arerequired. Commercial and service buildings:
ofces, stores, hospitals, exhibition halls, etc. Infrastructures: airports, telecommunications, internet data centres, tunnels, etc. Industrial facilities: pharmaceuticals, food processing, etc.
Our solutions: Prisma Plus and Okken switchboards, Schneider busbar trunking.
-
7/28/2019 5. I LINE II -Schneider Busway-2008
7/1115Schneider Electric
Introductio
n
With Schneider busway, you playall the right notes!
The Schneider buswaydecentralised distributionconcept
Electrical power available at all points, throughout theinstallation.
Exclusive features of the Schneider Electric systemTotal coordination of the Schneider Electric system provides maximum safety of lifeand property, continuity of service, upgradeability and ease of installation.
Product characteristics are checked by calculations and tests carried out in ourlaboratories and certied in independent international recognized laboratories.
A competitive installation.Simplicity, upgradeability, safety and continuity of service and operation.
Savings start with installationWith plug-in points, Schneider busbar trunking reduces installation costs.Given the low cost of adding new circuits, savings increase as the number of loadsincreases, a natural consequence of the growth of your business.
Upgradeable during operationIn decentralised distribution, evolving operating requirements and costs areintegrated right from the start. The addition, relocation or replacement of load equipment can be carried outquickly, without de-energising the supply trunking or shutting down operation, The cost of making such changes is greatly reduced: loads are located close to supply points, plug-in points are always available,
plug-in units can be reused or new ones added quickly for load relocation orreplacement needs.
Reusable in the event of major changesWhen making major modications to your installation, the existing trunking can beeasily dismantled and reused.
Schneider busbar trunking
-
7/28/2019 5. I LINE II -Schneider Busway-2008
8/1116 Schneider Electric
Introductio
n
Schneider busway, in totalharmony with the environment!
Safety of life and property With Schneider Busway, no toxic emission in case of reThe busbar trunking has a low combustible load. Its construction uses very littleconsumable material and is halogen free.In the event of a re, the busbar trunking does not emit any gas or toxic smoke.
The busbar trunking helps prevent the propagation of a re through partition wallsand oors.
Halogen-sensitive applications Public buildings (infrastructures, hospitals, schools, etc.), Buildings with evacuation difculties (high-rises, ships, etc.) and service-activitybuildings, Sensitive processes (production of electronic components, etc.).
Schneider Busway contains no PVCs
When PVCs burn, they produce large amounts of smoke that can be a serioussafety hazard. Reduced visibility: risk of panic, complicates rescue work, Smoke toxicity: hydrogen chloride gas (highly toxic), carbon monoxide (danger of asphyxiation).
Schneider Busway reduces the risk of exposure to
electromagnetic eldsAccording to the WHO (World Health Organisation), exposure to electromagnetic
elds can be a health hazard starting at levels as low as 0.2 micro-Teslas andcould represent a long-term risk of cancer. Some countries have created standardsthat stipulate limits
All electrical conductors generate magnetic elds proportional to the distancebetween them. The design of Schneider busbar trunking with tightly spacedconductors in a metal enclosure helps to considerably reduce radiatedelectromagnetic elds.The electromagnetic eld characteristics of Schneider busbar trunking are well-dened and measurements show that they are far below potentially dangerouslevels.
Example:Consequences of a re in a 100 m2 ofce withelectrical distribution by cables.200 kg of cables (i.e. 20 kg of PVC) produces: 4400 m3 of smoke, 7.5 m3 of hydrochloric acid, 3.7 kg of corroded steel.
Health
-
7/28/2019 5. I LINE II -Schneider Busway-2008
9/1117Schneider Electric
Introductio
n
Schneider busway, in totalharmony with the environment!
Environment Schneider Busway is fully recyclable Schneider Busway busbar trunking can be reused.Schneider Busway busbar trunking is designed for a long service life and caneasily be dismantled, cleaned and reused. All packaging materials can be recycled (cardboard or recyclable polyethylenelm). All Schneider Busway products are designed for safe end-of-life recycling. PVC,on the other hand, requires neutralisation of the hydrochloric acid produced usinglime and generates dioxins that are extremely toxic.
Schneider Busway helps conserve natural resourcesThe depletion of raw materials (copper, plastics, etc.) is one of our ongoingconcerns.For this reason, we have optimised the used of all materials used to make ourbusbar trunking:
Reduction of dangerous or polluting materials. Reduction in the weight of insulating materials, Reduction in the use of plastics for improved re performance: less energyreleased during combustion, thereby limiting propagation and facilitating extinction(lower caloric value).
Example:1 kg of PVC generates 1 kg of waste.
Conservation of naturalresources
Schneider Busway reduces your line losses by 20 %
Schneider Busway divides your consumption of plastic by a
factor of fourThe cost of an electrical installation includes the initial investment for theequipment and its installation, the cost of maintenance and the cost of energylosses during operation.The concept of decentralised distribution is a way to merge all the circuits in oneand thus to reduce to the maximum the low cross-section lengths and the weight ofinsulating materials.
Example:34m of 250A Schneider busbar trunking eqipped with 7 sets of 25A load.
-
7/28/2019 5. I LINE II -Schneider Busway-2008
10/111
Application
1. Transformer/ Switchboard connection2. Horizontal distribution, from the substation to the loads in workshop
3. Vertical distribution, from the substation to the loads of each high rise oor
4. Lighting application, in Park place, supermarket, exhibition center, metro ect.
1
2
3
4
8 Schneider Electric
Introductio
n
Schneider busway, fortissimothroughout the range!
-
7/28/2019 5. I LINE II -Schneider Busway-2008
11/111
1 2
3 4
Lighting application
Horizontal distribution
Vertical distribution
Transformer/ Switchboard connection
9Schneider Electric
Introductio
n
Schneider busway, fortissimothroughout the range!
-
7/28/2019 5. I LINE II -Schneider Busway-2008
12/11110 Schneider Electric
Introductio
n
Schneider busway, a display ofadvantages!
The compact size of Schneider busway means it takes up very little space in thebuilding: used as a rising main, it takes up only a minimum of space, used for horizontal distribution, it ts easily into the buildings structure (falseoors, false ceilings, service shafts, etc).
Changes in direction have been designed to optimise the space taken up,contrary to an equivalent installation using cables which requires large bendingradii.
Tap-off units, complete with protective devices, are tted along the entire lengthof the busbar trunking thus reducing the oor area taken up by the electricaldistribution switchboards.
A compact solution
A simple and economicalsystem
The design study is easy to perform as it does not require a detailed layout ofeach load. Equipment choice is pre-determined and optimised.
Installing the busbar trunking requires 2 or 3 people only, for a time equivalentto that for installing cableways. The time normally needed for laying cables istherefore saved.
Connection to the MV/LV substation is made using a quick tting joint block. Theplug-in units can be prepared in the workshop thus reducing on-site time. Theirconnection to the busbar trunking is done in a single plugging-in operation.Forthose ratings more than 500A, it is done by bolt-on operation.
Installing busbar trunking lengths can be done as and when building workprogresses, thus optimising on-site work and allowing possible unexpected eventsto be anticipated in advance.
It is also important to note that busbar trunking is a factory tested solution,meaning the time needed for inspecting connections is reduced (visual inspectionof tightening torque).
-
7/28/2019 5. I LINE II -Schneider Busway-2008
13/11111Schneider Electric
Introductio
n
Complete safety Busbar trunking temperature rise and short-circuit withstand are known andindependent of the installation. Coordination of the Schneider Electric systemresults in complete control of the electrical network.
Installation standards IEC 60 364 chapter 5.523.6 stipulate that above 4 parallelcables, it is preferable to use busbar trunking. Paralleling many cables leads touneven distribution of currents and the risk of abnormal temperature rise.
The busbar trunking and plug-in units are designed to guarantee the safety ofpersonnel and equipment: Fully silver-plated cooper contact solution. bolted connections with tightening torque guaranteed by torque nuts. foolproof system to avoid the risk of assembly errors.
Its metal enclosure and high protection degree protect the busbar trunking from allexternal aggressions (corrosion, rodents, etc).
Operating continuity
Seismic Compliance
When working on the electrical installation, the busbar trunking provides immediatereadability of the electrical circuit thus allowing the appropriate zone to be quicklyidentied.Plug-in units(
-
7/28/2019 5. I LINE II -Schneider Busway-2008
14/111
Key projects
Pentronas Towers (Malaysia)
Hong Kong International Financial Center (HongKong)
Shanghai Jin Mao Building (China)
Emirates Palace (UAE)
Grand Indonesia Building (Indonesia)
Dubai International Finance Center (UAE)
Al Shira'a Tower (Kuwait)
Beverly Hill Tower (Qatar)
Al Safwa Tower (Saudi Arabia)
Robinson Cybergate Center Tower (Philippines)
Mita Koyamacho High-rise Apartment (Japan)
International Commerce Centre (Hongkong)
Congresss Conference Building (Egypt)
......
Key projects
Carrefour supermarket(World wide)
Guangzhou International ExhibitionCentre(China)
Convention & Exhibition Centre(Hong Kong)
Asia World Expo(Hong Kong)
Central World Mall(Thailand)
Siam paragon (Thailand)
Abu Dhabi National Exhibition Center( UAE)
Mall of Arabia (Saudi Arabia)
Melbourne Convention Centre (Australia)
Mall of the Emirates (UAE)
National Convention Centre (Vietnam)
Queensgate shopping Mall (New Zealand)
National Olympic Stadium (Guangzhou, China)
Panda Distribution Facility (Saudi Arbia)
Las Vegas Sands (Macau)
......
12 Schneider Electric
Introductio
n
Schneider busway, everyone totheir music!
Key points
Fire barrier.
Halogen free.
Small size.
Operating continuity.
Ofce and Hotel buildings
Key points
Halogen free.
Distribution and metering.
Able to be evolved.
Sprinklers.
Shopping centres andExhibition centres
-
7/28/2019 5. I LINE II -Schneider Busway-2008
15/111
Key projects
General Motors (World wide)
Hitachi Semiconductor manufacturing(China)
Chartered Semiconductor manufacturing(Singapore)
Maruti Suzuki (India)
Jabil Plant (India)
Nikon Factory (Thailand)
Intel Plant (Malaysia)
Inneon Plant (Malaysia)
Bosch (Korea)
Seagate Factory (Singapore)
ST Microelectronics (Singapore)
Ansell Lanka (PVT) Limited (Sri Lanka)......
Key projects
Bank of China Tower (Hongkong)
China Construction Bank (China)
Citibank Hongkong (Hong Kong)
Maybank (Malaysia)
Commercial Bank (Qatar)
Saudi Telecom Company (SaudiArabia)
Bharti data Centre (India)
HSBC Bank HQ (Babrain)......
13Schneider Electric
Introductio
n
Schneider busway, everyone totheir music!
Key points
Operating continuity.
Able to be evolved.
Low voltage drops.
Network readability.
Industry buildings
Key points
Operating continuity.
High tap-off density.
Able to be evolved.
Network compactnessand readability.
Data centers and Banks
-
7/28/2019 5. I LINE II -Schneider Busway-2008
16/111
Key projectsThree Gorges PowerStation(China)
Wind Farm(China)
ExxonMobil Chemicalplant(Malaysia)
Hysco Steel(India)
Shell Chemical plant (Malaysia)
Petro Rabigh(Saudi Arabia)......
Key projects
Beijing Capital New InternationalAirport(China)
Suvarnabhumi Airport (Thailand)
Tan Son Nhat Airport(Vietnam)
India Ahmedabad Airport(Inida)
Cairo Airport(Egypt)
Dubai Airport(UAE)
Jebel Ail Airport(UAE)......
Schneider Busway, everyone totheir music!
Key points
Operating continuity.
Able to be evolved.
Low voltage drops.
Network readability.
Energy
Key points
Halogen free.
Distribution and metering.
Able to be evolved.
Sprinklers.
Airport
14 Schneider Electric
Introductio
n
-
7/28/2019 5. I LINE II -Schneider Busway-2008
17/111
Key projects
The rst afliated Hospital,Guangzhou(China)
Angkor InternationalHospital(Thailand)
Al-Maidan Hospital(Kuwait)
Beijing 301 Hospital(China)
Mina Hosptital (Saudi Arabia)
Dammam Hospital (Saudi Arabia)
......
Key projects
Guangzhou Metro(China)
Singapore Metro
Madrid Metro (Spain)
London Metro (UK)
......
Schneider Busway, everyone totheir music!
Key points
Fire barrier.
Halogen free.
Small size.
Operating continuity.
Hospital
Key points
Halogen free.
Distribution and metering.
Able to be evolved.
Sprinklers.
Metro
15Schneider Electric
Introductio
n
-
7/28/2019 5. I LINE II -Schneider Busway-2008
18/11116 Schneider Electric
Introductio
n
Schneider busway, hits the rightnotes!
IEC Certication ASTA / ASEFA /KEMA / IECEE / CNAL UL Certication CCC approved ISO 9001, ISO14001 OHS18001 Six Sigma Program
Quality - Accreditations
-
7/28/2019 5. I LINE II -Schneider Busway-2008
19/11117Schneider Electric
Introductio
n
With the Schneider busway toolsand services, let us compose yourproject!
Work-out yoursolution together
Our teams are available to provide customers with technical assistance throughoutthe installation of their projects.
Design of electrical distribution architectures: design of decentralised transport and distribution systems, technical and nancial optimisation of busbar trunking design projects, transformer / switchboard link, installation coordination and discrimination.
Full installation drawings: 3D drawings with corresponding parts lists, 2D drawing with dimensions, detailed connection drawings.
Site supervision and commissioning assistance.
Training for designers and contractors.
Project
launch
Technical
support
Autocad
drawing
BRASS
drawing
Production
Project
management
On-site
instruction
and
installation
After-sales
service
-
7/28/2019 5. I LINE II -Schneider Busway-2008
20/111
Horizontal distribution
Vertical distribution
18 Schneider Electric
Introductio
n
With the Schneider busway toolsand services, let us compose yourproject!
Schneider Electric offers a comprehensive design software.The BRASS software, edited by Schneider Electric, was developed to help youdesign I-LINE II busbar trunking runs.
BRASS, a comprehensive toolThe BRASS software allows you to quickly design the best layout for your project.It allows: the material needed to be easily chosen a list of catalogue numbers and their exact quantities to be dened
BRASS gives you all thehelp you need
State-of-the-art softwareThe advanced BRASS design software enables you design from the routing to
component detail in a more accurate, convenient and quicker way.
-
7/28/2019 5. I LINE II -Schneider Busway-2008
21/11119Schneider Electric
Presentation 20Panorama of Schneider Busway range 20Lighting distribution 20Power distribution 22
I-LINE II from 800 to 6000 A 24
Description 26
General 26
Straight lengths 28
Fittings 29
Supports and xings 31
Special ttings 32
Plug-in units 33
Presentation and description
Presentation
Description
-
7/28/2019 5. I LINE II -Schneider Busway-2008
22/11120 Schneider Electric
Presentation
Presentation
Canalis
Panorama of Schneider Busway rangeLighting distribution
Range Canalis KDP
Run components
Degree of protection IP55
Number of circuits 1
Rating 20 A
Tap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm
Standard lengths 24 and 192 meters
Finish -
Maximum distance between xing points 0,70 meter
KDP-KBA-KBB tap-off units
Rating 10 and 16 A
-
7/28/2019 5. I LINE II -Schneider Busway-2008
23/11121Schneider Electric
Presentation
Canalis KBA Canalis KBB
IP55 IP55
1 1 or 2
25 and 40 A 25 and 40 A
500 - 1000 and 1500 mm 500 and 1000 mm
2 and 3 meters 2 and 3 meters
Galvanised steel Galvanised steel
3 meters 5 meters
10 and 16 A 10 and 16 A
Presentation
Canalis
Panorama of Schneider Busway rangeLighting distribution
-
7/28/2019 5. I LINE II -Schneider Busway-2008
24/11122 Schneider Electric
Presentation
Presentation Panorama of Schneider Busway rangePower distribution
Canalis
Range Canalis KS Canalis KS rising mains
Run components
Degree of protection IP52/54 IP52/54
Polarity 3L + N + PE 3L + N + PE
Rating 100, 160, 250, 400, 500, 630, 800 100, 160, 250, 400, 500, 630, 800
Tap-off intervals 1000 mm on each face 500 mm
Standard lengths 3 and 5 meters Dened by the oor pitch
Finish White RAL 9001 White RAL 9001
Maximum distance between xing points 3 meters Dened by the oor pitch
Tap-off units
Rating Plug-in 25 to 400 A 25 to 400 A
Bolt-on
-
7/28/2019 5. I LINE II -Schneider Busway-2008
25/11123Schneider Electric
Presentation
Presentation Panorama of Schneider Busway rangePower distribution
I-LINE II
I-LINE II Copper busway I-LINE II Copper contact busway
IP40 / 41 / 54 / 55 / 65 / 66 IP40 / 41 / 54 / 65 / 66
3L + N+PE / 3L+ PE ; 3L + N+PE / 3L+ PE ;
800 - 6000A 800 - 5000A
610mm/1220mm 610mm/1220mm
10 Feet 10 Feet
ANSI 49 ANSI 49
10Ft 10Ft
15 to 500 A 15 to 500 A
630A to 1600 A 630A to 1600 A
-
7/28/2019 5. I LINE II -Schneider Busway-2008
26/11124 Schneider Electric
Presentation
Run sections Plug-in units Elbow Fittings
Rating: 12 ratings are available, from800A to 6000A Standard length: 10 feet, 6 feet, 4 feet None-standard length: minimum length406mm
All I-LINE plug-in units are compatible withI-LINE II busbar trunking system Category: plug-in unit with MCCB, plug-inunit with fusible switch Plug-in unit with Merlin Gerlins MCCB,ampere rating from 15A to 1000A Plug-in unit with Square Ds MCCB,ampere rating from 15A to 1600A Plug-in unit with fusible switch, ampererating from 30A to 1600A
Standard elbow: Flatwise elbow Edgewise elbow Non-standard elbow: Double elbow Offset elbow Elbow plus anged end Elbow in special angle Elbow in special length
I-LINE II from 800 to 6000 AHigh Power transport anddistribution
Presentation
I-LINE II
-
7/28/2019 5. I LINE II -Schneider Busway-2008
27/11125Schneider Electric
Presentation
Connection ttings Fixing supports
Supply connections allow thebusbar trunking to be connected to theswitchboards busbar or to the transformer. Flanged end Qwik Flanged end cable connection, transport currentbetween cable and busbar trunking. End cable tap box Center cable tap box
Vertical support Fix hanger Spring hanger Horizontal support Flatwise hanger Edgewise hanger
I-LINE II
I-LINE II from 800 to 6000 AHigh Power transport anddistribution
Presentation
-
7/28/2019 5. I LINE II -Schneider Busway-2008
28/11126 Schneider Electric
Description
Description
The I-LINE II busbar trunking is intended for high power distribution and transportin industrial, commercial and tertiary buildings.Assembly of prefabricated sections that adapt to all run congurations.
General
Straight Length
Joint Pak
I-LINE II
12 ratings are available, from 800A to 6000A Silver plated copper contact Conductors full-length insulated using Mylar film, class B, 130CAvailable polarities: 3L +PE, 3L +N+PE Maximum rated voltage: 1000 Volts Insulation voltage: 1000 Volts
Compact Size, Sandwich Structure, totally enclosed housing
Universal Installation, no need to consider de-rating factor, regardless of themounting position. The accumulation of dirt on exposed bus bars and possibility of accidentalcontact with bus bar are greatly reduced.
No Chimney effect
Continuous air spaces inside I-line busway housing are closed off with specialbarriers to help prevent the spread of smoke and gases in the event of a fire inthe area of the busway installation. This standard internal barrier allows busway toextend through wall or floors without creating open space for a chimney effect firepath. Improve systems ventilation, satisfy higher ampere rating Less space required for installation, investment saving
The I-LINE II busbar trunking is suitable for applications containing harmonics bytaking into account the appropriate derating factor. See Harmonic currents in theDesign guide.
Joint-Pak is standard on I-LINE II system. It allows for quick removal of lengthsfrom the busbar trunking runs for load shifting or maintenance. It also can beremoved and relocated on the opposite end of the length for the last minutes jobchanges
Single bolt connection makes installation faster Belleville washer provides equal pressure across the complete joint contact areato assure proper electrical contact
Double, Silver plated surface contact ensure a good current continuity. Adjustable range: +/- 3mm
VIST-TITE BoltThe double head design, introduced by Square D in 1967, allows the customer totighten the joint to the proper torque using a standard spanner. The outer head willbreak off when the correct torque is achieved. A second bolt head remains to allowfor joint maintenance or busbar relocation. No need to purchase a replacementbolt. For maintenance of the joint or when busway is relocated, the VISIT-TITE boltshould be tightened to 70 lb-ft (95Nm) with a torque wrench
Electro-galvanized steel, better anti-corrosion. Paint: Epoxy electrostatic powder finishColor: ANSI 49 gray, special color are optional upon customers request.
Housing
-
7/28/2019 5. I LINE II -Schneider Busway-2008
29/11127Schneider Electric
Description
GeneralDescription
I-LINE II
Earthing Bus
I-line II is furnished with the integral earthing bus as standard. The earthing busis the bus housing itself and completely encloses the bus sandwich. It is rated at50% capacity. The earthing bus is Continuous bonding between top and bottombus.
Internal Aluminum/copper earthing bus is optional.
Schneider believes an earthing conductor is extremely important, to provide the
maximum amount of protection for a distribution system in todays ever expandingelectrical systems. With our design, we have given the maximum amount ofprotection in an economical package.
Conductor
Copper (Copper busway) 99.97% purity of copper Silver plated copper in full length minimize surface oxygenation, assure low surface contact resistance and lowvoltage drop
Insulation
Two layers surrounding each bus bar Class B, 130C, Vendor certified polyester film (DuPont Mylar) Excellent dielectric performance
Over 40 years of application record without failure
Class F is optional upon request Halogen free, safe in fire
Degree of Protection
Schneider offers the I-LINE II bus bar trunking system in a variety of housingconstructions to meet your application and needs.
Feeder type IP40-IP66Riser type IP40-IP54Plug-in type IP40-IP54
Aluminum with copper contact (Copper Contact busway) Use silver-plated Bi-metal cladding on Aluminum conductor through highcurrent and high pressure.
Special process enabling molecular fusion of Copper and Aluminum throughthe use of very high pressure and temperature.
All of connection zone are silver to silver.
Integral Earth Bus Internal Earth Bus
-
7/28/2019 5. I LINE II -Schneider Busway-2008
30/11128 Schneider Electric
Description
Feeder
Transport the current without plug-in opening.All straight lengths and fittings of feeder trunking are fully compatible, rating forrating, with straight lengths of plug-in trunking. 12 ratings are available, from 800A to 6000A Minimum length 406 mm Polarity: 3L+N+PE, 3L+PE system 100% neutral capacity, 50% earth bus capacity
Straight lengthsDescription
Straight section
Riser
Plug-in opening (PIO) on one side, only 4, 6, 10ft available
Maximum 2 PIO for 6 feet riser element
Maximum 4 PIO for 6 feet plug-in element
Maximum 1 PIO for 4 feet riser element
Maximum 2 PIO for 4 feet plug-in element
Maximum 3 PIO for 10 feet riser element
Maximum 6 PIO for 10 feet plug-in element
Plug-in
Plug-in opening on both sides, only 4, 6, 10ft available
I-LINE II
N N N
N N N
N NNN
N NNN
N
N
-
7/28/2019 5. I LINE II -Schneider Busway-2008
31/11129Schneider Electric
Description
FittingsDescription
I-LINE II
Simple changes of direction
Changes of direction
Elbows - Types LF, LE and T
Double elbows - Types OF, OE DR and DL
type OE, edgewise offset
type DR, double right elbow
type DL, double left elbow
type OF, flatwise offset
to go up or down, to turn right or left Standard angle: 90 Special angles : 91- 179
flat or edgewise, to move the run ais upwards, downwards, to the right or to theleft without having to bend the busbar trunking:
type LE, edgewise elobw
type T, flatwise tee
type LF, flatwise elobw
-
7/28/2019 5. I LINE II -Schneider Busway-2008
32/11130 Schneider Electric
Description
FittingsDescription
I-LINE II
Connetions to swithboards and transformers
Connetions to cable
Type FE, standard flanged end
Type QF, qwik flanged end
type LEFE, edgewise elbow plus flanged end
type LFFE, flatwise elbow plus flanged end
type ETB, end cable tap box
type CTB, center cable tap box
Cable Tap Boxcable connection , transport current between cable and busbar trunking
Flanged ends - Type FEThey allow the busbar trunking to be connected to a switchboards busbar, or to theterminals of an transformer, generator set, etc.
They come complete with a mounting plate tted: either directly to the roof of the switchboard, or via the intermediary of a protective cover.
Vertical or horizontal incoming busbar trunking.
-
7/28/2019 5. I LINE II -Schneider Busway-2008
33/11131Schneider Electric
Description
I-LINE II
Supports and fixingsDescription
Horizontal Supports
Vertical Supports
The horizontal type hanger allow the busbar trunking to be fixed and ajusted along
its length, as well as absorbing its movements.
The spring hanger has the following advantages:.
Fix hanger
Spring hanger
spring adjustment to ensure distribution of the load at each floor avoids the transmission of buiding forces to the busbar trunking (expansion andvibration)
type HFF, flatwise hanger
type HFE, edgewise hanger
type HFVS1, spring hanger
type HFV, fix hanger, for all ratings.
type HFVS2, spring hanger
type HFVS8, spring hanger
-
7/28/2019 5. I LINE II -Schneider Busway-2008
34/11132 Schneider Electric
Description
I-LINE II
Special fittingsDescription
Reducer
Expansion Joint
An Expansion Fitting should be used under the following conditions:whenever a busway run crosses a building expansion; when a long straight runof busway does not contain any elbows or both ends of the run are fixed and thebusway length is more than 30 meters. No need for riser 38mm expansion allowable more detail in page 99
Connect the high power and low power run Best way to save investment Standard reducer is non-fusible, reducer with fuse/MCCB is optional
The end closure protects and insulates the conductor ends and is fitted to the lastsection.
End closure
Connection accessory
type EJ, absorb horizontal expansion
type R
Flexible linkfor the connection between the conducting plates, to reduce the vibration from the
transformer.
Connection platesthe conductors of flanged ends are connected via connection plates to the
switchboard busbars.
-
7/28/2019 5. I LINE II -Schneider Busway-2008
35/11133Schneider Electric
Description
Plug-in UnitsDescription
I-LINE II
CompatibilityAll plug-in units are compatible with I-LINE II busbar trunking system, regardlesswhether they bear MCCB or fusible switch.
Plug-in device mountingPlug-in units are positioned along the busbar trunking length by notches in thebusbar trunking housing top which accept the mounting hooks of the plug-in unit.This aligns the plug-in unit jaws with the plug-in opening. After the unit is positionedon the busway, it is allowed to swing down into the plug-in opening where the plug-in jaws make contact with the bus bars. This is accomplished in hook-swing.
Plug-in JawsThe plug-in jaws contact to the bus bars directly with the silver plated coopercontact. The contact surface is fully silver plated to ensure a proper contact forceand low contact resistance.
EarthingEarthing established at rst and switched off at last as to protect worker againstelectrical contact shock.
All plug-in devices incorporate an earthing spring which cuts through the paint andforms an equipment earth between the housing and the body of the device beforethe phase jaws make contact with the busbars.
Interlock30 A to 250 A plug-in devices are interlocked with the busway housing to preventinstallation or removal of the unit when the disconnect is turned ON.All devices incorporates an interlock to prevent the door over the disconnectfrom being opened when the unit is ON. This door interlock can be defeated fromoutside the unit.
Operating handleThe side operating handle in the PIU makes the heavy duty switch more
convenient and safer. When the PIU is installed in the high position, you can easilyoperate the PIU on the group by the side handle.
Protection functionSchneider Plug-in unit equipped with Schneider original protection unit, whichcan provide complete overload protection, short circuit protection and earthingmalfunction protection. The maximum interrupting is 150KA.
Transparent shield over Line side parts - that means safety & visible
Product features of I-LINE II Plug-in Unit
-
7/28/2019 5. I LINE II -Schneider Busway-2008
36/11134 Schneider Electric
Description
Plug-in Units
I-LINE II
Description
Category of I-LINE Plug-in unit Plug-in Unit with Merlin Gerlins MCCB, ampere rating from 15A to 1000A Plug-in Unit with Square Ds MCCB, ampere rating from 15A to 1600A Plug-in with Fusible Switch, ampere rating from 30A to 1600A
Plug-in Unit with Merlin Gerins MCCB Plug-in typePNS (15-250A), PBNS (350-500A) Bolt-on typePTNS (630-1000A) (different for horizontal/vertical mounting) Fitted with Compact NSEN/ NSES/ NSEH/ NSD / NSN / NSH / NSL(on request) available for 3-pole and 4 pole congurations available for earth leakage current protection (Vigi)
Plug-in unit with Square D MCCB Plug-in typePF(15-100A), PK(125-250A), PB(250-400A) Bolt-on typePT(500-1600A) (different for horizontal/vertical mounting) 3 Poles only
PIU enclosure not interchangeable with PIU enclosure for MG breaker
Plug-in unit Square D Fusible
Plug-in typePQ(30-200A), PS(125-250A), PBQ(250-400A) Bolt-on typePTQ(500-1600A) (different for horizontal/vertical mounting) equipped with UL/IEC fuse base
Category of I-LINE Plug-in Unit
Plug-in Unit with Merlin Gerins MCCB
Plug-in Unit with Square Ds MCCB
Plug-in Unit with Square D fusible breaker
-
7/28/2019 5. I LINE II -Schneider Busway-2008
37/111Schneider Electric 35
C
ataloguenumbers
D
imensions
Catalogue numbers anddimensions
Catalogue number coding 36
I-LINE II Copper Busway (CFC)
Straight lengths 38
Straight length components 39
Elbows 41
Double elbows 43
Offset elbows 44
Elbow plus anged end 45
Internal Grounding Elbows 46
Flanged ends 51
Cable Tap Box 54
Supports and xings 55
I-LINE II Copper Contact Busway (BFC)
Straight lengths 58
Straight length components 59
Elbows 61
Double elbows 63
offset 64
Elbow plus anged end 65
Flanged ends 66
Cable Tap Box 69
Supports and xings 70
Plug-in units 72
-
7/28/2019 5. I LINE II -Schneider Busway-2008
38/111Schneider Electric36
D
imensions
Catalogue-number coding
Catalogue Numbering System Generic v Discrete
Catalogue-number composition (I-LINE II Copper Busway)
One letter designating the application.Busbar material Code
Copper C
Type Code
Feeder F
Riser plug-in R
Plug-in P
Standard Code
IEC C
I-LINE II 2
Polarity Code
3L + PE 3
3L + N + IGB (integral earth) 5
3L + N + ING (internal earth) 6
Rating Code800 08
1000 10
1250 12
1350 13
1600 16
2000 20
2500 25
3000 30
3200 32
4000 40
5000 50
6000 60
Type of PE Code
AL GCU GG
Dimension of component
Two letters identifying the type of component.Type Code
Generic Code
Elbow EL
Flange End FE
Qwik Flange End QFExpension Joint EJ
End Tap Box ETB
Center Tap Box CTB
Flat Tee T
Unfused Reducer R
Discrete CodeEdgewise Elbow LE
Flatwise Elbow LF
Edgewise Offset Elbow OE
Flatwise Offset Elbow OF
Double Left Elbow DL
Double Right Elbow DR
Flange End Edgewise Elbow LEFE
Flange End Flatwise Elbow LFFE
Flange End - Double left FEDL
Flange End - Double right FEDR
Straight Length - Feeder/Plug-in/Riser ST
Phase Transition PT
Degree of Pretection Code
IP40 --
IP54 M54
IP55*** M55
IP65*** M65
IP66*** M66*** Available for feeder system only
Catalogue numbers anddimensions
CC2GM
Generic catalogue # describes all the features of busway (e.g. copper, ampere rating,
IP rating, 3/4 poles etc except length. Hence it is not for describing individual pieces
of busway but rather for quotation/contract/invoicing purposes. The unit is 1 piece (for
ttings) or 1 feet (straights)
Discrete catalogue # describes all the features of busway including length of the
individual pieces. With the discrete catalogue number itself, it tells the detailed length
of busway and is sufcient enough for production purposes. We also call this as BOM(Bill of Materials)
I-LINE II Copper Busway
-
7/28/2019 5. I LINE II -Schneider Busway-2008
39/111Schneider Electric 37
C
ataloguenumbers
D
imensions
Catalogue-number coding
Catalogue Numbering System Generic v Discrete
Catalogue-number composition (I-LINE II Copper Contact Busway)
Catalogue numbers anddimensions
BC2GM
I-LINE II Copper Contact Busway
One letter designating the application.Busbar material Code
Bimetal B
Type Code
Feeder F
Riser plug-in R
Plug-in P
Standard Code
IEC C
I-LINE II 2
One digit indicating the trunking polarityPolarity Code
3L + PE 3
3L + N + IGB (integral earth) 5
Rating Code800 08
1000 10
1250 12
1350 13
1600 16
2000 20
2500 25
3200 32
4000 40
5000 50
Type of PE Code
AL G
Dimension of component
Two letters identifying the type of component.Type Code
Generic Code
Elbow EL
Flange End FE
Qwik Flange End QFExpension Joint EJ
End Tap Box ETB
Center Tap Box CTB
Flat Tee T
Unfused Reducer R
Discrete Code
Edgewise Elbow LE
Flatwise Elbow LF
Edgewise Offset Elbow OE
Flatwise Offset Elbow OF
Double Left Elbow DL
Double Right Elbow DR
Flange End Edgewise Elbow LEFE
Flange End Flatwise Elbow LFFE
Flange End - Double left FEDL
Flange End - Double right FEDR
Straight Length - Feeder/Plug-in/Riser ST
Phase Transition PT
Degree of Pretection Code
IP40 --
IP54 M54
IP55*** M55
IP65*** M65
IP66*** M66*** Available for feeder system only
-
7/28/2019 5. I LINE II -Schneider Busway-2008
40/11138 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Straight feeder lengths
Straight lengths
Type Length Cat. no.
3L + PE 3L + N + IGB 3L + N + INGFixed 10 Feet CFC23G10STM CFC25G10STM CFC26GG10STM
Made to measure16 inches ~119 inches CFC23G**STM CFC25G**STM CFC26**GG**STM
Straight lengths with plug-in openings
Type Length Number of
opening(Nos sides)
Cta.no
3L+PE 3L+N+IGB 3L+N+ING
Plug-in 4 feet 12 CPC23G4S2M CPC25G4S2M CPC26GG4S2M
6 feet 12 CPC23G6S2M CPC25G6S2M CPC26GG6S2M
22 CPC23G6S4M CPC25G6S4M CPC26GG6S4M
10 feet 12 CPC23G10S2M CPC25G10S2M CPC26GG10S2M
22 CPC23G10S4M CPC25G10S4M CPC26GG10S4M
32 CPC23G10S6M CPC25G10S6M CPC26GG10S6M
Riser 4 feet 11 CRC23G4S1M CRC25G4S1M CRC26GG4S1M
6 feet 11 CRC23G6S1M CRC25G6S1M CRC26GG6S1M
21 CRC23G6S2M CRC25G6S2M CRC26GG6S2M
10 feet 11 CRC23G10S1M CRC25G10S1M CRC26GG10S1M
21 CRC23G10S2M CRC25G10S2M CRC26GG10S2M
31 CRC23G10S3M CRC25G10S3M CRC26GG10S3M
Trunking cross-section
Rating (A) Type 800 1000 1250 1350 1600 2000 2500 3000 3200 4000 5000 6000
Weight
(kg/m)
3L + PE Feeder 14.8 18.0 20.5 25.0 27.2 31.4 43.3 57.6 63.5 70.3 87.9 108.9
Plug-in 17.3 21.1 23.7 28.1 30.4 34.5 46.5 60.7 65.2 76.1 91.1 111.2
3L + N + IGB Feeder 17.8 21.7 24.9 31.0 33.9 40.9 58.1 71.0 76.9 87.6 108.0 134.8
Plug-in 20.3 24.8 28.0 34.1 37.1 44.0 61.2 74.1 80.1 93.9 111.2 137.9
3L + N + ING Feeder 20.4 24.3 27.9 34.9 38.2 45.9 65.3 79.0 85.8 98.1 119.8 150.4
Plug-in 22.9 27.4 31.0 38.0 41.4 49.0 68.4 82.1 89.0 104.4 123.0 153.5
W(mm) 98 98 110 136 148 171 237 323 387 412 599 638
Figure A A A A A A A B B B C C
OrderingComplete the catalogue number by replacing by the rating and protectiondegree.
Example:Generic catalogue number of 1000A straight feeder, 3L+N+PE :
CFC2510GM54
Discrete catalogue number of a 10feet 1000A straight feeder, 3L+N+PE.
CFC2510G10STM54
Rating
Rating**
Protection degree
Protection degree
I-LINE II Copper Busway
(1) See the Trunking cross-section table below.
**= the length of the straight feeder. If the number is larger than 10, the unit is inch. otherwise,the unit is feet.
-
7/28/2019 5. I LINE II -Schneider Busway-2008
41/111
A
B
C
N
N
C
B
A
39Schneider Electric
Cataloguenumbers
Dimensions
OrderingComplete the catalogue number by replacing by the rating and protectiondegree.
Example:Generic catalogue number of 1000A expansion joint, 3L+N+PE :
CFC2510GEJM54
Discrete catalogue number of a standard 1000A expansion joint,3L+N+PE:
CFC2510GEJM54
Rating
Rating
Protection degree
Protection degree
Catalogue numbers anddimensions
Straight length components
Type Length(mm)
Height(mm)
Width (mm)
800 1000 1250 1350 1600 2000 2500 3000 3200 4000 5000 6000
Fixed 1016 508 343 343 343 343 442 442 492 492 594 594 819 819
I-LINE II Copper Busway
Type Length(mm)
Cat. no.
3L+PE 3L+N+IGB 3L+N+ING
Fixed 966 CFC23G38PTM CFC25G38PTM CFC26GG38PTM
Type Cat. no.
3L+PE 3L+N+IGB 3L+N+ING
Fixed CFC23GEJM CFC25GEJM CFC26GGEJM
Unfused Reducer
Phase transition
Type Length(mm)
Cat. no.
3L+PE 3L+N+IGB 3L+N+INGFixed 610 CFC23GRM CFC25GRM CFC26GGRM
Note: Replace R with below code. For example, CFC2520GR10 M54.
Bolt side
AmpereRating
400 600 800 1000 1250 1350 1600 2000 2500 3000 3200 4000
800 - R4 - R6 - - - - - - - - - -
1000 - R4 - R6 - R8 - - - - - - - - -
1250 - R4 - R6 - R8 -R10 - - - - - - - -
1350 - - R6 - R8 -R10 -R12 - - - - - - -
1600 - - R6 - R8 -R10 -R12 - R13 - - - - - -
2000 - - - R8 -R10 -R12 - R13 - R16 - - - - -
2500 - - - -R10 -R12 - R13 - R16 - R20 - - - -
3000 - - - -R10 -R12 - R13 - R16 - R20 - R25 - - -
3200 - - - - -R12 - R13 - R16 - R20 - R25 - R30 - -
4000 - - - - - - R13 - R16 - R20 - R25 - R30 - -
5000 - - - - - - - R16 - R20 - R25 - R30 - R32 -
6000 - - - - - - - - - R25 - R30 - R32 - R40
Note: MCCB reducers are available. Contact us for details.
Expansion Joint
-
7/28/2019 5. I LINE II -Schneider Busway-2008
42/11140 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Straight length components
I-LINE II Copper Busway
Wall and oor ange (WF)
End closure
Type Rating
(A)
Dimension (mm) Cat. no.
A
End closure 800 110 ACF38EC
1000 110 ACF38EC
1250 123 ACF43EC
1350 148 ACF53EC
1600 161 ACF58EC
2000 184 ACF67EC
2500 250 ACF93EC
3000 336 ACF13EC
3200 399 ACF15EC
4000 425 ACF17EC
5000 612 ACF24EC
6000 650 ACF25EC
Note: please add the sufx M for higher protection degree. For example, ACF38ECM54
Rating(A)
Straight Length Flanged End Cat. no
A(mm) Y W Y W
800 211 152 203 254 381 ACF38WF
1000 211 152 203 254 381 ACF38WF
1250 224 152 203 254 381 ACF43WF
1350 249 178 203 279 381 ACF53WF
1600 262 203 203 305 381 ACF58WF
2000 285 229 203 356 381 ACF67WF
2500 351 279 203 483 533 ACF93WF
3000 437 381 203 483 533 ACF13WF
3200 500 432 203 584 533 ACF15WF
4000 526 457 203 584 533 ACF17WF
5000 713 660 203 813 533 ACF24WF6000 751 686 203 813 533 ACF25WF
Flatwise Elbow Wall thickness (mm)
Rating(A)
100 200 300 400 500 600
W(mm) Y(mm)
800 203 229 279 330 381 432 483
1000 203 229 279 330 381 432 483
1250 203 254 305 356 407 457 508
1350 203 305 356 406 457 508 559
1600 203 305 356 406 457 508 559
2000 203 356 406 457 508 559 610
2500 203 432 483 533 584 635 686
3000 203 559 610 660 711 762 813
3200 203 660 711 762 813 864 9144000 203 686 737 787 838 889 940
5000 203 940 991 1041 1092 1143 1194
6000 203 1016 1067 1118 1168 1219 1270
Edgewise Elbow Wall thickness (mm)
Rating(A)
100 200 300 400 500 600
Y(mm) W(mm)
800 150 305 356 406 457 509 559
1000 150 305 356 406 457 509 559
1250 150 305 356 406 457 509 559
1350 176 305 356 406 457 509 559
1600 203 305 356 406 457 509 559
2000 229 305 356 406 457 509 559
2500 279 305 356 406 457 509 559
3000 381 305 356 406 457 509 559
3200 432 305 356 406 457 509 559
4000 457 305 356 406 457 509 559
5000 660 305 356 406 457 509 559
6000 686 305 356 406 457 509 559
-
7/28/2019 5. I LINE II -Schneider Busway-2008
43/11141Schneider Electric
Cataloguenumbers
Dimensions
Catalogue numbers anddimensions
Elbows
Type Rating(A)
Cat. no3L+PE 3L+N+IGB
Standard 800 CFC2308GLFM11M CFC2508GLFM11M1000 CFC2310GLFM11M CFC2510GLFM11M1250 CFC2312GLFM11M CFC2512GLFM11M1350 CFC2313GLFM12M CFC2513GLFM12M 1600 CFC2316GLFM12M CFC2516GLFM12M 2000 CFC2320GLFM12M CFC2520GLFM12M 2500 CFC2325GLFM14M CFC2525GLFM14M 3000 CFC2330GLFM15M CFC2530GLFM15M 3200 CFC2332GLFM16M CFC2532GLFM16M 4000 CFC2340GLFM17M CFC2540GLFM17M 5000 CFC2350GLFM21M CFC2550GLFM21M 6000 CFC2360GLFM21M CFC2560GLFM21M
Made tomeasure
All CFC 23GLFSBM CFC25GLFS BM
=+Dimension
Type Rating (A) Dimension (mm)
A B
Standard (min)800 279 2791000 279 2791250 279 2791350 305 3051600 305 3052000 305 3052500 356 3563000 381 3813200 406 4064000 432 4325000 533 5336000 533 533
Made to measure All min ~ 1219 min ~ 1219
I-LINE II Copper Busway
Flatwise elbows with made to measure angles
Flatwise elbow
Type Rating Angle(W)
Cat. no
3L+PE 3L+N+IGB
Made tomeasure
All 91 ~ 1 79 CFC23GLFOASBAM CFC25GLFOASBAM
=+, A=A+angle
OA - special angle
OrderingComplete the catalogue number by replacing by the rating and protectiondegree.
Example:Generic catalogue number of 1000A atwise elbow, 3L+N+PECFC2510GELM54
Discrete catalogue number of a 24 inch, 1000A atwise elbow, 3L+N+PE:CFC2510G24LFS13B11M54
S - the elbow side without joint pakB - the elbow side with joint pak
Rating
Rating
Protection degree
Protection degree
- the length of the elbow side with joint pak - the length of the elbow side without joint pak - the total length of elbow
-
7/28/2019 5. I LINE II -Schneider Busway-2008
44/11142 Schneider Electric
Dimensions
Type Rating
(A)
Cat. no
3L+PE 3L+N+IGBStandard 800 CFC2308GLEM11M CFC2508GLEM11M
1000 C FC 2310G LE M11M CFC2510GLEM11M1250 C FC 2312G LE M11M CFC2512GLEM11M1350 C FC 2313G LE M11M CFC2513GLEM11M1600 C FC 2316G LE M11M CFC2516GLEM11M2000 C FC 2320G LE M11M CFC2520GLEM11M2500 C FC 2325G LE M11M CFC2525GLEM11M3000 C FC 2330G LE M11M CFC2530GLEM11M3200 C FC 2332G LE M11M CFC2532GLEM11M4000 C FC 2340G LE M11M CFC2540GLEM11M5000 C FC 2350G LE M11M CFC2550GLEM11M6000 C FC 2360G LE M11M CFC2560GLEM11M
Made tomeasure
All CFC 23GLESBM CFC25GLESBM
=+
Catalogue numbers anddimensions
Elbows
Edgewise elbows
Edgewise elbows with made to measure angles
Dimension
Type Rating (A) Dimensions (mm)
A BStandard(min) All 279 279Made to measure All min ~ 1219 min ~ 1219
I-LINE II Copper Busway
Type Rating Angle(W)
Cat. no
3L+PE 3L+N+IGB
Made tomeasure
All 91~179CFC23GLESBA M CFC25GLESBA M
=+, A=A+angle
A
B
Flatwise Tee
Type Rating(A)
Cat. no
3L+PE 3L+N+IGB
Standard 800 CFC2308G33TFS11B11S11M CFC2508G33TFS11B11S11M
1000 CFC2310G33TFS11B11S11M CFC2510G33TFS11B11S11M
1250 CFC2312G33TFS11B11S11M CFC2512G33TFS11B11S11M
1350 CFC2313G36TFS12B12S12M CFC2513G36TFS12B12S12M
1600 CFC2316G36TFS12B12S12M CFC2516G36TFS12B12S12M
2000 CFC2320G36TFS12B12S12M CFC2520G36TFS12B12S12M
2500 CFC2325G42TFS14B14S14M CFC2525G42TFS14B14S14M
3000 CFC2330G45TFS15B15S15M CFC2530G45TFS15B15S15M
3200 CFC2332G48TFS16B16S16M CFC2532G48TFS16B16S16M
4000 CFC2340G51TFS17B17S17M CFC2540G51TFS17B17S17M5000 CFC2350G63TFS21B21S21M CFC2550G63TFS21B21S21M
6000 CFC2360G63TFS21B21S21M CFC2560G63TFS21B21S21M
Made tomeasure
All CFC23GTFSBSM CFC25GTFS BSM
=++
Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)
800 279 279 279
1000 279 279 279
1250 279 279 279
1350 305 305 305
1600 305 305 305
2000 305 305 305
2500 356 356 3563000 381 381 381
3200 406 406 406
4000 432 432 432
5000 533 533 533
6000 533 533 533
Made to measure All min ~ 1219 min ~ 1219 min ~ 1219
-
7/28/2019 5. I LINE II -Schneider Busway-2008
45/111
A
B
C
43Schneider Electric
Cataloguenumbers
Dimensions
Catalogue numbers anddimensions
Double elbows
Double left elbow
I-LINE II Copper Busway
Type Rating(A)
Cat. no
3L+PE 3L+N+IGB
Made tomeasure
800 CFC2308GDLB CSM CFC2508GDLB CSM1000 CFC2310GDLB CSM CFC2510GDLB CSM1250 CFC2312GDLB CSM CFC2512GDLB CSM1350 CFC2313GDLB CSM CFC2513GDLB CSM
1600 CFC2316GDLB CSM CFC2516GDLB CSM2000 CFC2320GDLB CSM CFC2520GDLB CSM2500 CFC2325GDLB CSM CFC2525GDLB CSM3000 CFC2330GDLB CSM CFC2530GDLB CSM3200 CFC2332GDLB CSM CFC2532GDLB CSM4000 CFC2340GDLB CSM CFC2540GDLB CSM5000 CFC2350GDLB CSM CFC2550GDLB CSM6000 CFC2360GDLB CSM CFC2560GDLB CSM
=++Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 203
1600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457
Made to measure All min ~ 1219 min ~ 1219 min ~ 1016
B
C
A
Double right elbow
Type Rating(A)
Cat. no
3L+PE 3L+N+IGB
Made tomeasure
800 CFC2308GDRBCSM CFC2508GDRBCSM1000 CFC2310GDRBCSM CFC2510GDRBCSM1250 CFC2312GDRBCSM CFC2512GDRBCSM1350 CFC2313GDRBCSM CFC2513GDRBCSM
1600 CFC2316GDRBCSM CFC2516GDRBCSM2000 CFC2320GDRBCSM CFC2520GDRBCSM2500 CFC2325GDRBCSM CFC2525GDRBCSM3000 CFC2330GDRBCSM CFC2530GDRBCSM3200 CFC2332GDRBCSM CFC2532GDRBCSM4000 CFC2340GDRBCSM CFC2540GDRBCSM5000 CFC2350GDRBCSM CFC2550GDRBCSM6000 CFC2360GDRBCSM CFC2560GDRBCSM
=++Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 203
1600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457
Made to measure All min ~ 1219 min ~ 1219 min ~ 1016
OrderingComplete the catalogue number by replacing by the rating and protection degree.Example:Generic catalogue number of 1000A double left elbow, 3L+N+PE:
CFC2510GELM54Rating
Rating
Protection degree
Protection degreeS - the elbow side without joint pakB - the elbow side with joint pakC or O - the straight feeder of the elbow
- the total length of elbow - the length of the elbow side with joint pak - the length of straight feeder - the length of the elbow side without joint pak
Discrete catalogue number of a 29 inch, 1000A double left elbow, 3L+N+PE:CFC2510G29DLB11C07S11M54
-
7/28/2019 5. I LINE II -Schneider Busway-2008
46/111
A
B
C
A
B
44 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Offset elbows
Flatwise offset elbow
Edgewise offset elbow
I-LINE II Copper Busway
Type Rating
(A)
Cat. no
3L+PE 3L+N+IGB
Made tomeasure
800 CFC2308GOFS OBM CFC2508GOFS OBM1000 CFC2310GOFS OBM CFC2510GOFS OBM1250 CFC2312GOFS OBM CFC2512GOFS OBM1350 CFC2313GOFS OBM CFC2513GOFS OBM1600 CFC2316GOFS OBM CFC2516GOFS OBM2000 CFC2320GOFS OBM CFC2520GOFS OBM2500 CFC2325GOFS OBM CFC2525GOFS OBM3000 CFC2330GOFS OBM CFC2530GOFS OBM3200 CFC2332GOFS OBM CFC2532GOFS OBM4000 CFC2340GOFS OBM CFC2540GOFS OBM5000 CFC2350GOFS OBM CFC2550GOFS OBM6000 CFC2360GOFS OBM CFC2560GOFS OBM
=++
Type Rating(A)
Cat. no
3L+PE 3L+N+IGB
Made tomeasure
800 CFC2308GOESOBM CFC2508GOESOBM1000 CFC2310GOESOBM CFC2510GOESOBM1250 CFC2312GOESOBM CFC2512GOESOBM1350 CFC2313GOESOBM CFC2513GOESOBM1600 CFC2316GOESOBM CFC2516GOESOBM2000 CFC2320GOESOBM CFC2520GOESOBM2500 CFC2325GOESOBM CFC2525GOESOBM3000 CFC2330GOESOBM CFC2530GOESOBM3200 CFC2332GOESOBM CFC2532GOESOBM4000 CFC2340GOESOBM CFC2540GOESOBM5000 CFC2350GOESOBM CFC2550GOESOBM6000 CFC2360GOESOBM CFC2560GOESOBM
=++
Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)800 279 279 1021000 279 279 1021250 279 279 1021350 305 305 1021600 305 305 1022000 305 305 1522500 356 356 2793000 381 381 3563200 406 406 4064000 432 432 4065000 533 533 5846000 533 533 635
Made to measure All min ~ 1219 min ~ 1219 min ~ 1016
Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)All 279 279 152
Made to measure All min ~ 1219 min ~ 1219 min ~ 1016
-
7/28/2019 5. I LINE II -Schneider Busway-2008
47/11145Schneider Electric
Cataloguenumbers
Dimensions
B
A
Catalogue numbers anddimensions
Elbow plus Flanged end
Flatwise elbow anged end
Edgewise elbow anged end
I-LINE II Copper Busway
Type
Rating(A)
Cat. no
3L+PE 3L+N+IGB
Made tomeasure
800 CFC2308GLFFE*FM CFC2508GLFFE*FM1000 CFC2310GLFFE*FM CFC2510GLFFE*FM1250 CFC2312GLFFE*FM CFC2512GLFFE*FM1350 CFC2313GLFFE*FM CFC2513GLFFE*FM1600 CFC2316GLFFE*FM CFC2516GLFFE*FM2000 CFC2320GLFFE*FM CFC2520GLFFE*FM2500 CFC2325GLFFE*FM CFC2525GLFFE*FM3000 CFC2330GLFFE*FM CFC2530GLFFE*FM3200 CFC2332GLFFE*FM CFC2532GLFFE*FM4000 CFC2340GLFFE*FM CFC2540GLFFE*FM5000 CFC2350GLFFE*FM CFC2550GLFFE*FM
6000 CFC2360GLFFE*FM CFC2560GLFFE*FM=+
* = B or S. B - elbow side with joint pak, S - elbow side without joint pak
Dimension
Type Rating (A) Dimension (mm)
A B
Standard (min)800 204 2791000 204 2791250 204 2791350 204 3051600 229 3052000 229 3052500 254 3563000 305 3813200 330 4064000 356 432
5000 457 5336000 457 533Made to measure All min ~ 1219 min ~ 1219
Type Rating(A)
Cat. no
3L+PE 3L+N+IGB
Made tomeasure
800 CFC2308GLEFE*FM CFC2508GLEFE*FM1000 CFC2310GLEFE*FM CFC2510GLEFE*FM1250 CFC2312GLEFE*FM CFC2512GLEFE*FM1350 CFC2313GLEFE*FM CFC2513GLEFE*FM1600 CFC2316GLEFE*FM CFC2516GLEFE*FM2000 CFC2320GLEFE*FM CFC2520GLEFE*FM2500 CFC2325GLEFE*FM CFC2525GLEFE*FM3000
CFC2330GLEFE*
F
M CFC2530GLEFE*
F
M3200 CFC2332GLEFE*FM CFC2532GLEFE*FM4000 CFC2340GLEFE*FM CFC2540GLEFE*FM5000 CFC2350GLEFE*FM CFC2550GLEFE*FM6000 CFC2360GLEFE*FM CFC2560GLEFE*FM
=+
* = B or S. B - elbow side with joint pak, S - elbow side without joint pak
Dimension
Type Rating (A) Dimension (mm)
A B
Standard (min)800 152 2791000 152 2791250 152 2791350 152 2791600 152 2792000 152 2792500 152 2793000 152 2793200 152 2794000 152 2795000 152 2796000 152 279
Made to measure All min ~ 1219 min ~ 1219
-
7/28/2019 5. I LINE II -Schneider Busway-2008
48/11146 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Internal Grounding Elbows
Flatwise Elbow
Edgewise Elbow
I-LINE II Copper Busway
Type Rating
(A)
Cat. no
1a 1b
Standard 800 CFC2608GG22LFIS11B11M CFC2508GG22LFOS11B11M1000 CFC2610GG22LFIS11B11M CFC2510GG22LFOS11B11M1250 CFC2612GG22LFIS11B11M CFC2512GG22LFOS11B11M1350 CFC2613GG24LFIS12B12M CFC2513GG24LFOS12B12M1600 CFC2616GG24LFIS12B12M CFC2516GG24LFOS12B12M2000 CFC2620GG24LFIS12B12M CFC2520GG24LFOS12B12M2500 CFC2625GG28LFIS14B14M CFC2525GG28LFOS14B14M3000 CFC2630GG30LFIS15B15M CFC2530GG30LFOS15B15M3200 CFC2632GG32LFIS16B16M CFC2532GG32LFOS16B16M4000 CFC2640GG34LFIS17B17M CFC2540GG34LFOS17B17M5000 CFC2650GG42LFIS21B21M CFC2550GG42LFOS21B21M6000 CFC2660GG42LFIS21B21M CFC2560GG42LFOS21B21M
Made tomeasure
All CFC26GGLFISBM CFC25GGLFOSBM
=+
Type Rating(A)
Cat. no
2a 2b
Standard 800 CFC2608GG22LEIS11B11M CFC2508GG22LEOS11B11M1000 CFC2610GG22LEIS11B11M CFC2510GG22LEOS11B11M1250 CFC2612GG22LEIS11B11M CFC2512GG22LEOS11B11M1350 CFC2613GG22LEIS11B11M CFC2513GG22LEOS11B11M1600 CFC2616GG22LEIS11B11M CFC2516GG22LEOS11B11M2000 CFC2620GG22LEIS11B11M CFC2520GG22LEOS11B11M2500 CFC2625GG22LEIS11B11M CFC2525GG22LEOS11B11M3000 CFC2630GG22LEIS11B11M CFC2530GG22LEOS11B11M3200 CFC2632GG22LEIS11B11M CFC2532GG22LEOS11B11M4000 CFC2640GG22LEIS11B11M CFC2540GG22LEOS11B11M5000 CFC2650GG22LEIS11B11M CFC2550GG22LEOS11B11M6000 CFC2660GG22LEIS11B11M CFC2560GG22LEOS11B11M
Made tomeasure
All CFC26GGLEISBM CFC25**GGLEOSBM
=+
Dimension
Type Rating (A) Dimension (mm)
A B
Standard (min)800 279 2791000 279 2791250 279 2791350 305 3051600 305 3052000 305 3052500 356 3563000 381 3813200 406 4064000 432 4325000 533 5336000 533 533
Made to measure All min ~ 1219 min ~ 1219
Flatwise elbows with made to measure angles
Type Rating(A)
Angle(W)
3L+N+ING
Ground bar inside Ground bar outside
Standard(min)
All 91 ~ 179 CFC26GGLFIOASBAM CFC26**GGLFOOASBAM
=+,A=A+angle
Dimension
Type Rating (A) Dimension (mm)A B
Standard (min)All 279 279
Made to measure All min ~ 1219 min ~ 1219
EL1
NL2L3
EL1L2L3
N
#'',&)3"
B
S
B
A
1a
EL1N
L2L3
EL1
L2L3N
B
S
#'',&/3"
A
B
1b
EL1
NL2
L3
EL1
L2
L3
N
CFC2608GG22LEIS11B11
B
S
A
B
2a
EL1
N
L2L3
EL1
L2
L3
N
CFC2608GG22LEOS11B11
B
S
A
B
2b
-
7/28/2019 5. I LINE II -Schneider Busway-2008
49/11147Schneider Electric
Cataloguenumbers
Dimensions
Catalogue numbers anddimensions
Internal Grounding Elbows
Tee - Feeder
Double left elbow
I-LINE II Copper Busway
Type Rating(A)
Cat. no3a 3b
Made tomeasure
800 CFC2608GGDLIBCSM CFC2608GGDLOBCSM1000 CFC2610GGDLIBCSM CFC2610GGDLOBCSM1250 CFC2612GGDLIBCSM CFC2612GGDLOBCSM1350 CFC2613GGDLIBCSM CFC2613GGDLOBCSM1600 CFC2616GGDLIBCSM CFC2616GGDLOBCSM2000 CFC2620GGDLIBCSM CFC2620GGDLOBCSM2500 CFC2625GGDLIBCSM CFC2625GGDLOBCSM3000 CFC2630GGDLIBCSM CFC2630GGDLOBCSM3200 CFC2632GGDLIBCSM CFC2632GGDLOBCSM4000 CFC2640GGDLIBCSM CFC2640GGDLOBCSM5000 CFC2650GGDLIBCSM CFC2650GGDLOBCSM6000 CFC2660GGDLIBCSM CFC2660GGDLOBCSM
=++
Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)800 279 279 2791000 279 279 2791250 279 279 2791350 305 305 3051600 305 305 3052000 305 305 3052500 356 356 3563000 381 381 3813200 406 406 4064000 432 432 4325000 533 533 5336000 533 533 533
Made to measure All min ~ 1219 min ~ 1219 min ~ 1219
Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457
Made to measure All min ~ 1219 min ~ 1219 min ~ 1016
Type Rating Cata. no
3L+PE+ING
Standard800 CFC2608GG33TFS11B11S11M1000 CFC2610GG33TFS11B11S11M1250 CFC2612GG33TFS11B11S11M1350 CFC2613GG36TFS12B12S12M1600 CFC2616GG36TFS12B12S12M2000 CFC2620GG36TFS12B12S12M2500 CFC2625GG42TFS14B14S14M3000 CFC2630GG45TFS15B15S15M3200 CFC2632GG48TFS16B16S16M4000 CFC2640GG51TFS17B17S17M5000 CFC2650GG63TFS21B21S21M6000 CFC2660GG63TFS21B21S21M
Made to measure All CFC26**GGTFSBSM=++
EL1
N
L2L3
EL1
L2
L3
N
CFC2608GG29DLIS11C07B11
S
B
A
C
B
3a
CFC2608GG29DLIB11C07S11
EL1
NL2L3
EL1
L2
L3
N
B
S
A
C
B
3a
CFC2608GG29DLOS11C07B11
EL1
N
L2L3
EL1
L2
L3
N
S
B
A
C
B
3b
CFC2608GG29DLOB11C07S11
EL1N
L2L3
E
L1
L2
L3
N
B
S
A
C
B
3b
-
7/28/2019 5. I LINE II -Schneider Busway-2008
50/11148 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Internal Grounding Elbows
Double Right elbow
Flatwise offset elbow
I-LINE II Copper Busway
Type
Rating(A)
Cat. no
4a 4b
Made tomeasure
800 CFC2608GGDRIBCSM CFC2608GGDROBCSM1000 CFC2610GGDRIBCSM CFC2610GGDROBCSM1250 CFC2612GGDRIBCSM CFC2612GGDROBCSM1350 CFC2613GGDRIBCSM CFC2613GGDROBCSM1600 CFC2616GGDRIBCSM CFC2616GGDROBCSM2000 CFC2620GGDRIBCSM CFC2620GGDROBCSM2500 CFC2625GGDRIBCSM CFC2625GGDROBCSM3000 CFC2630GGDRIBCSM CFC2630GGDROBCSM3200 CFC2632GGDRIBCSM CFC2632GGDROBCSM4000 CFC2640GGDRIBCSM CFC2640GGDROBCSM5000 CFC2650GGDRIBCSM CFC2650GGDROBCSM6000 CFC2660GGDRIBCSM CFC2660GGDROBCSM
=++
Type Rating(A)
Cat. no
6a 6b
Made tomeasure
800 CFC2608GGOFISOBM CFC2608GGOFOSOBM1000 CFC2610GGOFISOBM CFC2610GGOFOSOBM1250 CFC2612GGOFISOBM CFC2612GGOFOSOBM1350 CFC2613GGOFISOBM CFC2613GGOFOSOBM1600 CFC2616GGOFISOBM CFC2616GGOFOSOBM2000 CFC2620GGOFISOBM CFC2620GGOFOSOBM2500 CFC2625GGOFISOBM CFC2625GGOFOSOBM3000 CFC2630GGOFISOBM CFC2630GGOFOSOBM3200 CFC2632GGOFISOBM CFC2632GGOFOSOBM4000 CFC2640GGOFISOBM CFC2640GGOFOSOBM5000 CFC2650GGOFISOBM CFC2650GGOFOSOBM6000 CFC2660GGOFISOBM CFC2660GGOFOSOBM
=++
Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457
Made to measure All min ~ 1219 min ~ 1219 min ~ 1016
Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)800 279 279 1021000 279 279 1021250 279 279 1021350 305 305 1021600 305 305 1022000 305 305 1522500 356 356 2793000 381 381 3563200 406 406 4064000 432 432 406
5000 533 533 5846000 533 533 635
Made to measure All min ~ 1219 min ~ 1219 min ~ 1016
EL1
L2
L3
N
EL1
N
L2L3
B
S
CFC2608GG29DRIB11C07S11
C
B
A
4a
EL1
N
L2L3
S
EL1
L2
L3
N
B
CFC2608GG29DRIS11C07B11
AC
B
4a
EL1N
L2L3
S
CFC2608GG29DROS11C07B11
C A
4b
EL1
L2
L3
N
B
B
B
EL1N
L2L3
E
L1
L2
L3
N
S
CFC2608GG29DROB11C07S11
AC
B
4b
EL1
N
L2
L3
EL1
N
L2
L3
B
S
CFC2608GG26OFIS11O04B11
A
B
C
6a
EL1
N
L2L3
B
S
EL1
N
L2
L3
CFC2608GG26OFOS11O04B11
A
B
C
6b
-
7/28/2019 5. I LINE II -Schneider Busway-2008
51/11149Schneider Electric
Cataloguenumbers
Dimensions
Catalogue numbers anddimensions
Internal Grounding Elbows
Edgewise offset elbow
Flange end atwise elbow
I-LINE II Copper Busway
Type
Rating(A)
Cat. no
5a 5b
Made tomeasure
800 CFC2608GGOEISOBM CFC2608GGOEOSOBM1000 CFC2610GGOEISOBM CFC2610GGOEOSOBM1250 CFC2612GGOEISOBM CFC2612GGOEOSOBM1350 CFC2613GGOEISOBM CFC2613GGOEOSOBM1600 CFC2616GGOEISOBM CFC2616GGOEOSOBM2000 CFC2620GGOEISOBM CFC2620GGOEOSOBM2500 CFC2625GGOEISOBM CFC2625GGOEOSOBM3000 CFC2630GGOEISOBM CFC2630GGOEOSOBM3200 CFC2632GGOEISOBM CFC2632GGOEOSOBM4000 CFC2640GGOEISOBM CFC2640GGOEOSOBM5000 CFC2650GGOEISOBM CFC2650GGOEOSOBM6000 CFC2660GGOEISOBM CFC2660GGOEOSOBM
=++
Type Rating(A)
Cat. no
7a 7b
Made to
measure
800 CFC2608GGLFIFE*FM CFC2608GGLFOFE*FM
1000 CFC2610GGLFIFE*
FM CFC2610GGLFOFE*
FM1250 CFC2612GGLFIFE*FM CFC2612GGLFOFE*FM1350 CFC2613GGLFIFE*FM CFC2613GGLFOFE*FM1600 CFC2616GGLFIFE*FM CFC2616GGLFOFE*FM2000 CFC2620GGLFIFE*FM CFC2620GGLFOFE*FM2500 CFC2625GGLFIFE*FM CFC2625GGLFOFE*FM3000 CFC2630GGLFIFE*FM CFC2630GGLFOFE*FM3200 CFC2632GGLFIFE*FM CFC2632GGLFOFE*FM4000 CFC2640GGLFIFE*FM CFC2640GGLFOFE*FM5000 CFC2650GGLFIFE*FM CFC2650GGLFOFE*FM6000 CFC2660GGLFIFE*FM CFC2660GGLFOFE*FM
=+
* = B or S. B - elbow side with joint pak, S - elbow side without joint pak
Dimension
Type Rating (A) Dimension (mm)
A B C
Standard (min)All 279 279 152
Made to measure All min ~ 1219 min ~ 1219 min ~ 1016
DimensionType Rating (A) Dimension (mm)
A B
Standard (min)800 204 2791000 204 2791250 204 2791350 204 3051600 229 3052000 229 3052500 254 3563000 305 3813200 330 4064000 356 4325000 457 5336000 457 533
Made to measure All min ~ 1219 min ~ 1219
EL1
N
L2L3
EL1
N
L2L3
S
B
CFC2608GG28OEIS11O06B11
A
B
C
5a
EL1
N
L2L3
S
B EL1
N
L2L3
CFC2608GG28OEOS11O06B11
A
B
C
5b
L1L2
L3N
E
SEL1
NL2
L3
CFC2608GG19LFIFES11F08
B
A
7a
L1L2
L3N
E
B
EL1N
L2L3
CFC2608GG19LFIFEB11F08
B
A
7a
S
EL1N
L2L3
NL3
L2L1
E
CFC2608GG19LFOFES11F08
B
A
7bB
EL1N
L2L3
NL3
L2L1
E
CFC2608GG19LFOFEB11F08
B
A
7b
-
7/28/2019 5. I LINE II -Schneider Busway-2008
52/11150 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Internal Grounding Elbows
Flange end edgewise elbow
I-LINE II Copper Busway
Type
Rating(A)
Cat. no
8a 8b
Made tomeasure
800 CFC2608GGLEIFE*FM CFC2608GGLEOFE*FM1000 CFC2610GGLEIFE*FM CFC2610GGLEOFE*FM1250 CFC2612GGLEIFE*FM CFC2612GGLEOFE*FM1350 CFC2613GGLEIFE*FM CFC2613GGLEOFE*FM1600 CFC2616GGLEIFE*FM CFC2616GGLEOFE*FM2000 CFC2620GGLEIFE*FM CFC2620GGLEOFE*FM2500 CFC2625GGLEIFE*FM CFC2625GGLEOFE*FM3000 CFC2630GGLEIFE*FM CFC2630GGLEOFE*FM3200 CFC2632GGLEIFE*FM CFC2632GGLEOFE*FM4000 CFC2604GGLEIFE*FM CFC2640GGLEOFE*FM5000 CFC2650GGLEIFE*FM CFC2650GGLEOFE*FM6000 CFC2660GGLEIFE*FM CFC2660GGLEOFE*FM
=+
* = B or S. B - elbow side with joint pak, S - elbow side without joint pak
Dimension
Type Rating (A) Dimension (mm)
A B
Standard (min)All 152 279
Made to measure All min ~ 1219 min ~ 1219
EL1
NL2
L3
S
E
L1
L2
L3
N
CFC2608GG17LEIFES11F06
B
A
8a
S
L1
L2
L3
N
E
EL1
N
L2L3
CFC2608GG17LEOFES11F06
B
A
8b
-
7/28/2019 5. I LINE II -Schneider Busway-2008
53/11151Schneider Electric
Cataloguenumbers
Dimensions
Rating (A) Dimension (mm)
A B C D
800 162 81 - -
1000 162 81 - -
1250 162 81 - -
1350 178 89 - -
1600 203 102 - -
2000 254 127 - -
2500 378 127 - -
3000 378 127 - -
3200 480 121 119 -
4000 480 121 119 -
5000 705 117 118 118
6000 705 117 118 118
Catalogue numbers anddimensions
Flanged ends
I-LINE II Copper Busway
TypeRating
(A)
Cat. no
3L+PE 3L+N+IGB 3L+N+ING
Satandard al l CFC23 G10FE*M CFC25G10FE*M CFC26GG10FE*M
Made tomeasure
800 CFC2308GFE*M CFC2508GFE*M CFC2608GFE*M
1000 CFC2310GFE*M CFC2510GFE*M CFC2610GFE*M1250 CFC2312GFE*M CFC2512GFE*M CFC2612GFE*M
1350 CFC2313GFE*M CFC2513GFE*M CFC2613GFE*M
1600 CFC2316GFE*M CFC2516GFE*M CFC2616GFE*M
2000 CFC2320GFE*M CFC2520GFE*M CFC2620GFE*M
2500 CFC2325GFE*M CFC2525GFE*M CFC2625GFE*M
3000 CFC2330GFE*M CFC2530GFE*M CFC2630GFE*M
3200 CFC2332GFE*M CFC2532GFE*M CFC2632GFE*M
4000 CFC2340GFE*M CFC2540GFE*M CFC2640GFE*M
5000 CFC2350GFE*M CFC2550GFE*M CFC2650GFE*M
6000 CFC2360GFE*M CFC2560GFE*M CFC2660GFE*M
* =B with joint pak, S without joint pak
Dimension
Type Rating (A) Dimension (mm)A
StandardAll 254
Made to measure All min ~ 1219
Flanged Collar and Cutout and DrillingTemplate 800A-6000A Feeder
Rating(A)
N Holes Dimension (mm)
E F G H J K W
800 10 98 - 130 187 254 296 335
1000 10 98 - 130 187 254 296 335
1250 10 98 - 130 187 254 296 335
1350 10 98 - 145 203 254 296 335
1600 10 98 - 171 229 254 296 335
2000 10 98 - 222 279 254 296 335
2500 16 88 87 346 403 406 451 487
3000 16 88 87 346 403 406 451 487
3200 18 88 87 448 505 406 451 487
4000 18 88 87 448 505 406 451 487
5000 22 88 87 673 730 406 451 487
6000 22 88 87 673 730 406 451 487
Cutout
FlangedCollar
FlangedCollar
8 Dia.(Holes)
Flanged end
OrderingComplete the catalogue number by replacing by the rating and protection degree.Example:
Generic catalogue number of 1000 A anged end, 3L+N+PEBFC2510GFEM54
Discrete catalogue number example of a 12 inch, 1000A anged end, 3L+N+PE:BFC2510G12FEBM54
Rating
Rating *
Protection degree
Protection degree
- the length of the straight feeder of anged end
* = B or S. B - with joint pak, S - without joint pak
-
7/28/2019 5. I LINE II -Schneider Busway-2008
54/11152 Schneider Electric
Dimensions
Rating (A) Dimension (mm)
S T U
800 76 92 97
1000 76 92 97
1250 76 92 97
1350 76 92 97
1600 76 92 97
2000 76 92 97
2500 127 169 173
3000 127 169 173
3200 127 169 173
4000 127 169 173
5000 127 169 173
6000 127 169 173
Rating (A) Figure Dimension (mm)
A B C D
800 1 64 - - -
100 1 64 - - -
1250 1 76 - - -
1350 1 102 - - -
1600 1 114 - - -
2000 1 137 - - -
2500 4 203 - - 127
3000 2 114 289 60 -
3200 2 127 353 99 -
4000 2 152 378 73 -
5000 3 114 565 111 -
6000 3 152 604 73 -
Rating (A) Catalogue No. No. of Pieces required per phase&neutral
800 FLEX508 2
1000 FLEX510 3
1250 FLEX512 3
1350 FLEX513 4
1600 FLEX516 4
2000 FLEX520 5
2500 FLEX525 7
3000 FLEX530 8
3200 FLEX532 8
4000 FLEX540 10
5000 FLEX550 13
6000 FLEX560 15
Catalogue numbers anddimensions
Flanged ends
Figure 1
Flanged Collar
4-pole with Earth Bus
(Bottom View)
4-pole with Earth Bus 3-pole with Earth Bus
Flanged end termination details
Physical Data
Figure 2
Figure 3
Figure 4
I-LINE II Copper Busway
Flexible link
-
7/28/2019 5. I LINE II -Schneider Busway-2008
55/11153Schneider Electric
Cataloguenumbers
Dimensions
Rating (A) Figure Dimension (mm)
A B C D
800 1 64 - - -
1000 1 64 - - -
1250 1 76 - - -
1350 1 102 - - -
1600 1 114 - - -
2000 1 137 - - -
2500 4 165 - - 127
3000 2 114 289 60 -
3200 2 127 353 86 -
5000 3 114 565 111 -
6000 3 152 604 73 -
Rating (A) Dimension (mm)
A B X Y Z
800 650 432 267 458 190
1000 650 432 267 458 190
1250 650 432 267 458 190
1350 650 432 267 458 190
1600 650 432 267 458 190
2000 650 432 267 458 190
2500 650 445 279 458 190
3000 650 533 364 458 190
3200 650 584 428 458 190
4000 650 610 453 458 190
5000 650 813 641 458 190
6000 650 838 679 458 190
Catalogue numbers anddimensions
Flanged ends
Figure 1
Figure 3
Figure 2
Figure 4
I-LINE II Copper Busway
Qwik Fange (Indoor Only)
CL
A
D32
71
Type Rating(A)
Cat. no3L+PE 3L+N+IGB
Satandard
800 CFC2308GQF CFC2508GQF
1000 CFC2310GQF CFC2510GQF
1250 CFC2312GQF CFC2512GQF
1350 CFC2313GQF CFC2513GQF
1600 CFC2316GQF CFC2516GQF
2000 CFC2320GQF CFC2520GQF
2500 CFC2325GQF CFC2525GQF
3000 CFC2330GQF CFC2530GQF
3200 CFC2332GQF CFC2532GQF
4000 CFC2340GQF CFC2540GQF
5000 CFC2350GQF CFC2550GQF
6000 CFC2360GQF CFC2560GQF
Note: please add the sufx M for higher protection degree. For example, CFC2508GQFM54
CL
A
32
71
B
CA A
B
A A AC C
-
7/28/2019 5. I LINE II -Schneider Busway-2008
56/111
D
54 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Cable Tap Box
Type Rating(A)
Cat. no.
3L+PE 3L+N+IGB 3L+N+IGB
Standard all CFC23GETB*M CFC25GETB*M CFC26GGETB*M
Made tomeasure 800 CFC2308GETB*
M CFC2508GETB*
M CFC2608GGETB*
M1000 CFC2310GETB*M CFC2510GETB*M CFC2610GGETB*M
1250 CFC2312GETB*M CFC2512GETB*M CFC2612GGETB*M
1350 CFC2313GETB*M CFC2513GETB*M CFC2613GGETB*M
1600 CFC2316GETB*M CFC2516GETB*M CFC2616GGETB*M
2000 CFC2320GETB*M CFC2520GETB*M CFC2620GGETB*M
2500 CFC2325GETB*M CFC2525GETB*M CFC2625GGETB*M
3000 CFC2330GETB*M CFC2530GETB*M CFC2630GGETB*M
3200 CFC2332GETB*M CFC2532GETB*M CFC2632GGETB*M
4000 CFC2340GETB*M CFC2540GETB*M CFC2640GGETB*M
5000 CFC2350GETB*M CFC2550GETB*M CFC2650GGETB*M
6000 CFC2360GETB*M CFC2560GETB*M CFC2660GGETB*M
Type Ampererating
Cat. no.
3L+PE 3L+N+IGB 3L+N+ING
Standard all CFC23GETB*M CFC25GETB*M CFC26GGETB*M
Cable Tap Box - End
I-LINE II Copper Busway
Cable Tap Box - Center
Dimension
Type Rating(A)
Lugs perPH&N
Earth lugs Dimension (mm)
300 mm2 150 mm2 300 mm2 A B C D
Standard(Min)
800 3 3 - 740 279 406 254
1000 3 3 - 740 279 406 254
1250 4 4 - 740 279 406 254
1350 4 4 - 740 279 406 254
1600 5 5 - 740 378 406 254
2000 6 - 3 740 378 406 254
2500 8 - 4 1000 530 660 254
3000 9 - 5 1000 530 660 254
3200 10 - 5 1000 530 660 254
4000 12 - 6 1000 530 660 254
5000 15 - 8 1000 756 660 254
6000 17 - 9 1000 756 660 254
Made tomeasure
All min min min min ~ 1219
Dimension
Type Rating (A) Lugs per PH&N
Earth lugs Dimension (mm)
300 mm2 150 mm2 300 mm2 A B C D
Standard
(Min)
800 3 3 - 889 356 406 185
1000 3 3 - 889 356 406 185
1250 4 4 - 889 356 406 1851350 4 4 - 889 356 406 185
1600 5 5 - 889 356 406 185
2000 6 - 3 889 356 406 185
2500 8 - 4 1059 508 447 261
OrderingComplete the catalogue number by replacing by the rating and protection degree.Example:Generic catalogue number of 1000 A end cable tap box, 3L+N+PE:
CFC2510GETBM54
Discrete catalogue number example of a 10 inch, 1000A end cable tap box, 3L+N+PE:CFC2510G10ETBBM54
Rating
Rating *
Protection degree
Protection degree
- the length of the straight feeder of end cable tap box
* = B or S. B - with joint pak, S - without joint pak
Note: please contact us for the ratings not shown above
-
7/28/2019 5. I LINE II -Schneider Busway-2008
57/11155Schneider Electric
Cataloguenumbers
Dimensions
Catalogue numbers anddimensions
Supports and fixings
Flatwisehorizontal hanger
Edgewisehorizontal hanger
Type Rating
(A)
Dimension (mm) Cat. no.
A (mm) B (mm)
Flatwise horizontal hanger 800 186 148 HF38F
1000 186 148 HF38F
1250 199 161 HF43F
1350 225 186 HF53F
1600 237 199 HF58F
2000 260 222 HF67F
2500 326 288 HF93F
3000 412 374 HF13F
3200 475 437 HF15F
4000 501 463 HF16F
5000 688 650 HF24F
6000 726 688 HF25F
Type Rating(A)
Dimension (mm) Cat. no.
A (mm)
Edgewise horizontal hanger 800 212 HF43E
1000 212 HF43E
1250 212 HF43E
1350 250 HF58E
1600 250 HF58E
2000 276 HF67E
2500 339 HF93E
3000 438 HF13E
3200 501 HF15E
4000 527 HF16E
5000 714 HF24E
6000 752 HF26E
I-LINE II Copper Busway
-
7/28/2019 5. I LINE II -Schneider Busway-2008
58/11156 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Supports and fixings
Vertical xed hanger
Vertical spring hanger
Type Rating(A) Cat. no.
Vertical Spring hanger 800 HFVS1
1000 HFVS1
1250 HFVS1
1350 HFVS1
1600 HFVS2
2000 HFVS2
2500 HFVS2
3000 HFVS8
3200 HFVS8
4000 HFVS85000 HFVS8
6000 HFVS8
Type Rating(A) Cat. no.
Vertical xed hanger all HFV
I-LINE II Copper Busway
-
7/28/2019 5. I LINE II -Schneider Busway-2008
59/11157Schneider Electric
Cataloguenumbers
Dimensions
-
7/28/2019 5. I LINE II -Schneider Busway-2008
60/11158 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Straight lengths
Type Length L Cat. no.
3L + PE 3L + N + IGB 3L + N + ING
Fixed 10 Feet BFC23G10STM BFC25G10STM BFC26G10STM
Made to measure16 inches ~119 inches BFC23G**STM BFC25G**STM BFC26 G**STM
Type Length Number ofopening
(Nos sides)
Cta.no3L+PE 3L+N+IGB 3L+N+ING
Plug-in 4 feet 12 BPC23G4S2M BPC25G4S2M BPC26G4S2M
6 feet 12 BPC23G6S2M BPC25G6S2M BPC26G6S2M
22 BPC23G6S4M BPC25G6S4M BPC26G6S4M
10 feet 12 BPC23G10S2M BPC25G10S2M BPC26G10S2M
22 BPC23G10S4M BPC25G10S4M BPC26G10S4M
32 BPC23G10S6M BPC25G10S6M BPC26G10S6M
Riser 4 feet 11 BRC23G4S1M BRC25G4S1M BRC26G4S1M
6 feet 11 BRC23G6S1M BRC25G6S1M BRC26G6S1M
21 BRC23G6S2M BRC25G6S2M BRC26G6S2M
10 feet 11 BRC23G10S1M BRC25G10S1M BRC26G10S1M
21 BRC23G10S2M BRC25G10S2M BRC26G10S2M
31 BRC23G10S3M BRC25G10S3M BRC26G10S3M
I-LINE II Copper Contact Busway
Straight feeder lengths
Straight lengths with plug-in openings
OrderingComplete the catalogue number by replacing by the rating and protectiondegree.
Example:Generic catalogue number of 1000A straight feeder, 3L+N+PE :
BFC2510GM54
Discrete catalogue number of a 10feet 1000A straight feeder, 3L+N+PE.
BFC2510G10STM54
Rating
Rating**
Protection degree
Protection degree
**= the length of the straight feeder. If the number is larger than 10, the unit is inch. otherwise,the unit is feet.
Trunking cross-section
Rating (A) Type 800 1000 1250 1350 1600 2000 2500 3200 4000 5000
Weight
(kg/m)
3L + PE Feeder 13.0 14.2 15.9 16.5 18.0 20.5 28.4 33.2 44.8 50.4
Plug-in 15.8 17.3 18.8 19.6 21.2 23.6 31.5 36.3 47.0 53.6
3L + N + IGB Feeder 14.0 15.6 17.8 18.6 20.5 23.5 33.5 39.7 51.8 60.1
Plug-in 17.2 18.8 21.0 21.7 23.7 26.6 36.6 42.8 55.0 63.2
W(mm) 98 120 148 161 186 225 323 412 566 650
Figure A A A A A A B B C C
-
7/28/2019 5. I LINE II -Schneider Busway-2008
61/11159Schneider Electric
Cataloguenumbers
Dimensions
I-LINE II Copper Contact Busway
Catalogue numbers anddimensions
Straight length components
Type Length(mm)
Height(mm)
Width (mm)
800 1000 1250 1350 1600 2000 2500 3200 4000 5000
Fixed 1016 508 343 343 343 343 442 442 492 594 819 819
Phase transition
Type Length(mm)
Cat. no.
3L+PE 3L+N+IGB 3L+N+ING
Fixed 966 BFC23G38PTM BFC25G38PTM BFC26GG38PTM
Type Cat. no.
3L+PE 3L+N+IGB 3L+N+ING
Fixed BFC23GEJM BFC25GEJM BFC26GEJM
Bolt side
Ampere Rating 400 630 800 1000 1250 1350 1600 2000 2500 3200 4000
800 R04 R06 - - - - - - - -
1000 R04 R06 R08 - - - - - - - -
1250 R04 R06 R08 R10 - - - - - - -
1350 - R06 R08 R10 R12 - - - - - -
1600 - R06 R08 R10 R12 R13 - - - - -
2000 - - R08 R10 R12 R13 R16 - - - -
2500 - - - R10 R12 R13 R16 R20 - - -
3200 - - - - R12 R13 R16 R20 R25 - -
4000 - - - - - R13 R16 R20 R25 R32 -
5000 - - - - - - R16 R20 R25 R32 R40
Note: MCCB reducers are available. Contact us for details.
Type Length(mm) Cat. no.3L+PE 3L+N+IGB 3L+N+ING
Fixed 610 BFC23GRM BFC25GRM BFC26GRM
Note: Replace R with below code. For example, BFC2520GR10M54.
Unfused Reducer
OrderingComplete the catalogue number by replacing by the rating and protectiondegree.
Example:Generic catalogue number of 1000A expansion joint, 3L+N+PE :
BFC2510GEJM54
Discrete catalogue number of a standard 1000A expansion joint,3L+N+PE:
BFC2510GEJM54
Rating
Rating
Protection degree
Protection degree
Expansion Joint
A
B
C
N
N
C
B
A
-
7/28/2019 5. I LINE II -Schneider Busway-2008
62/11160 Schneider Electric
Dimensions
Catalogue numbers anddimensions
Straight length components
I-LINE II Copper Contact Busway
Wall and oor ange (WF)
End closure
Type Rating
(A)
Dimension (mm) Cat. no.