5 - Geh-6126c_vol_i Hmi Manual

download 5 - Geh-6126c_vol_i Hmi Manual

of 134

Transcript of 5 - Geh-6126c_vol_i Hmi Manual

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    1/134

    GE Energy

    GEH-6126Vol I

    HMI for Turbine ControlOperators Guide

    g

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    2/134

    These instructions do not purport to cover all details or variations in equipment, nor to

    provide for every possible contingency to be met during installation, operation, and

    maintenance. The information is supplied for informational purposes only, and GE makes

    no warranty as to the accuracy of the information included herein. Changes,

    modifications and/or improvements to equipment and specifications are madeperiodically and these changes may or may not be reflected herein. It is understood that

    GE may make changes, modifications, or improvements to the equipment referenced

    herein or to the document itself at any time. This document is intended for trained

    personnel familiar with the GE products referenced herein.

    GE may have patents or pending patent applications covering subject matter in this

    document. The furnishing of this document does not provide any license whatsoever to

    any of these patents.

    This document contains proprietary information of General Electric Company, USA and

    is furnished to its customer solely to assist that customer in the installation, testing,

    operation, and/or maintenance of the equipment described. This document shall not be

    reproduced in whole or in part nor shall its contents be disclosed to any third partywithout the written approval of GE Energy.

    GE provides the following document and the information included therein as is and

    without warranty of any kind, expressed or implied, including but not limited to any

    implied statutory warranty of merchantability or fitness for particular purpose.

    If further assistance or technical information is desired, contact the nearest GE Sales or

    Service Office, or an authorized GE Sales Representative.

    2008 - 2011 General Electric Company, USA. All rights reserved.

    Issued: 2008-06-11

    Revised: 2011-09-19

    * Trademark of General Electric CompanyCIMPLICITY is a registered trademark of GE Fanuc Automation North America, Inc.

    Modbus is a registered trademark of Schneider Automation.SPEEDTRONIC is a trademark of General Electric Company, USA.

    Windows and Windows NT are registered trademarks of Microsoft Corporation.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    3/134

    We welcome comments and suggestions to make this publication more useful.

    Your Name Todays Date

    Your Companys Name and Address Job Site

    GE Requisition No.

    Publication No.Your Job Function / How You Use This Publication

    Publication Issue/Revision Date

    If needed, how can we contact you?

    Fax No.

    Phone No.

    E-mail

    Address

    General Rating

    Excellent Good Fair Poor Additional CommentsContents ____________________________________________________________

    Organization ____________________________________________________________

    Technical Accuracy ____________________________________________________________

    Clarity ____________________________________________________________

    Completeness ____________________________________________________________

    Drawings / Figures ____________________________________________________________

    Tables ____________________________________________________________

    Referencing ____________________________________________________________

    Readability ____________________________________________________________

    Specific Suggestions(Corrections, information that could be expanded on, and such.)

    Page No. Comments

    _____ _________________________________________________________________________________

    _____ _________________________________________________________________________________

    _____ _________________________________________________________________________________

    _____ _________________________________________________________________________________

    _____ _________________________________________________________________________________

    _____ _________________________________________________________________________________

    Other Comments (What you like, what could be added, how to improve, and such.)________________________________________________

    __________________________________________________________________________________________

    __________________________________________________________________________________________

    __________________________________________________________________________________________

    __________________________________________________________________________________________

    __________________________________________________________________________________________

    __________________________________________________________________________________________

    Overall grade(Compared to publications from other manufacturers of similar products, how do you rate this publication?)

    Superior Comparable Inferior Do not know Comment ____________________________________________

    Detach and fax or mail to the address noted above.

    g Reader CommentsTo:

    GE EnergyDocumentation Design, Rm. 2931501 Roanoke Blvd.Salem, VA 24153-6492 USA

    Fax: 1-540-387-8651(GE Internal DC 8-278-8651)

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    4/134

    ........................................................................ Fold here and close with staple or tape.........................................................................................

    ____________________________

    ____________________________

    ____________________________

    GE Energy

    Documentation Design, Rm. 2931501 Roanoke Blvd.Salem, VA 24153-6492 USA

    ..........................................................................................Fold here first .......................................................................................................

    Place

    stamphere.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    5/134

    Safety Symbol Legend

    Indicates a procedure, condition, or statement that, if not

    strictly observed, could result in personal injury or death.

    Indicates a procedure, condition, or statement that, if not

    strictly observed, could result in damage to or destruction of

    equipment.

    Indicates a procedure, condition, or statement that should bestrictly followed in order to optimize these applications.

    Note Indicates an essential or important procedure, condition, or statement.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    6/134

    This equipment contains a potential hazard of electric shock

    or burn. Only personnel who are adequately trained and

    thoroughly familiar with the equipment and the instructions

    should install, operate, or maintain this equipment.

    Isolation of test equipment from the equipment under test

    presents potential electrical hazards. If the test equipment

    cannot be grounded to the equipment under test, the test

    equipments case must be shielded to prevent contact by

    personnel.

    To minimize hazard of electrical shock or burn, approved

    grounding practices and procedures must be strictly followed.

    To prevent personal injury or equipment damage caused by

    equipment malfunction, only adequately trained personnel

    should modify any programmable machine.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    7/134GEH-6126CVol I HMI Operators Guide Contents i

    Contents

    Chapter 1 Overview 1-1Introduction...............................................................................................................................................1-1HMI Overview ..........................................................................................................................................1-1

    Product Features.............................................................................................................................1-1HMI Components...........................................................................................................................1-2Graphic Displays............................................................................................................................1-3Communications ............................................................................................................................1-5Optional Features ...........................................................................................................................1-5Application-Specific Features........................................................................................................1-6

    Technical Specifications............................................................................................................................1-6Related Documentation.............................................................................................................................1-7How to find the 3V number.......................................................................................................................1-8

    Chapter 2 Quick-Start Procedures 2-1

    Introduction...............................................................................................................................................2-1Starting Up the HMI..................................................................................................................................2-1Other HMI Displays ..................................................................................................................................2-4

    Lockout Function Master Reset - Mark IV, Mark V, Mark V LM and Mark VI...........................2-4Trip Diagram Display - Mark IV, Mark V, Mark V LM and Mark VI ..........................................2-5Lockout Function Diagnostic Reset - Mark V, Mark V LM and Mark VI....................................2-6Start Checks Display - Mark V, Mark V LM and Mark VI ..........................................................2-7Alarm Setup - Mark IV, Mark V, Mark V LM and Mark VI........................................................2-8Turbine Startup Trend Display - Mark IV, Mark V, Mark V LM and Mark VI ............................2-9Synchronization Display - Mark IV, Mark V, Mark V LM and Mark VI...................................2-10

    Optional HMI Displays ...........................................................................................................................2-11Reactive Capability Display - Mark IV, Mark V, Mark V LM and Mark VI .............................2-11Manual Synchronizing Display....................................................................................................2-12Triggered Plot Display.................................................................................................................2-15

    Other Tools..............................................................................................................................................2-16Viewing Sequencing Information ................................................................................................2-16Viewing Trip Information............................................................................................................2-24Alarm Logger Control..................................................................................................................2-30Hold List Display (Steam Turbine Applications).........................................................................2-31Accessing the Web-Based Displays- Mark IV, Mark V, Mark V LM, Mark VI ........................2-32

    Chapter 3 Display and Control (Command) Programs 3-1

    Introduction...............................................................................................................................................3-1Viewing Sequencing Information..............................................................................................................3-1

    Viewing Sequencing Information - Mark IV .................................................................................3-1Viewing Sequencing Information - Mark V and Mark V LM ......................................................3-2Viewing Sequencing Information - Mark VI ...............................................................................3-10

    Viewing Trip Information .......................................................................................................................3-14Viewing Trip Information - Mark IV...........................................................................................3-14Viewing Trip Information Mark V and Mark V LM ................................................................3-14Viewing Trip Information - Mark VI...........................................................................................3-20

    Web-Based Displays - Mark IV, Mark V, Mark V LM, and Mark VI....................................................3-25Accessing the Web-Based Displays.............................................................................................3-25Historical Alarm and Event Report..............................................................................................3-26

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    8/134ii Contents GEH-6126CVol I HMI Operators Guide

    Hold List (Steam Applications) - Mark V and Mark VI..........................................................................3-31Hold List Rules ............................................................................................................................3-32

    Demand Display - Mark IV, Mark V, and Mark V LM ..........................................................................3-33Starting Demand Display .............................................................................................................3-33Demand Display Menu Window..................................................................................................3-35Using Demand Display ................................................................................................................3-39

    Logic Forcing Display - Mark V and Mark V LM..................................................................................3-46Starting the Logic Forcing Display ..............................................................................................3-46Opening, Creating, Modifying and Saving Logic Forcing Displays ............................................3-49Using the Logic Forcing Display Program...................................................................................3-50

    Forced Variables - Mark VI.....................................................................................................................3-53Starting toolbox............................................................................................................................3-53Using Finder to Locate a Variable to Force .................................................................................3-54Locating Forced Variables ...........................................................................................................3-56Forced Variables using Control System Toolbox.........................................................................3-57

    Toolbox Privilege Level Functions - Mark VI ........................................................................................3-58

    Appendix A HMI Function Reference A-1

    HMI Functions for GE Turbine Controllers .............................................................................................A-1

    CIMPLICITY HMI Supported Functions ................................................................................................A-4

    Appendix B Alarm Overview B-1

    Introduction ..............................................................................................................................................B-1Hold List Alarms (Steam Turbine Only) ..................................................................................................B-1Process Alarms.........................................................................................................................................B-2

    Process (and Hold) Alarm Data Flow ...........................................................................................B-2Diagnostic Alarms....................................................................................................................................B-3

    Glossary of Terms G-1

    Index I-1

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    9/134

    GEH-6126CVol I HMI Operators Guide Chapter 1 Overview 1-1

    IntroductionThe Human-Machine Interface (HMI) for SPEEDTRONIC turbine control is anoperator interface for real-time control of power-plant processes and equipment. It

    runs on a computer-based workstation using a Microsoft

    Windows Operating

    System. The HMI provides operator display and control for the Mark* IV, Mark* V,

    Mark* V LM and Mark* VI turbine controllers.

    This document, Volume I, covers HMI operation. It is written as a guide to help the

    operator in using applicable HMI and supported CIMPLICITY

    HMI functions with

    the SPEEDTRONIC Mark IV, Mark V, Mark V LM and, Mark VI turbine

    controllers. Volume II covers HMI maintenance features.

    HMI Overview

    The Human-Machine Interface (HMI) for SPEEDTRONIC turbine control is a

    operator interface for real-time control of power-plant processes and equipment. It

    runs on a pc-based workstation using client-server architecture. The HMI provides

    operator display and control for the Mark IV, Mark V, Mark V LM, and Mark VIturbine controllers.

    The HMI can be configured to operate with a variety of system devices, integrating

    plant operation at a single level. Plant operators and engineers can view and control

    plant equipment through a common interface.

    The HMI uses many different software packages to perform its functions. The

    primary package used for the operator interface is CIMPLICITY HMI.

    An operator can use the HMI for the following turbine control functions:

    Monitor one or more turbines through graphical displays (for example: alarms,

    wheelspace temperatures, and vibration levels).

    Issue commands to the selected turbine or driven device (for example: Start,Stop, Cooldown On, Auto, and Raise/Lower Output).

    NoteCIMPLICITY HMI is a product of GE Fanuc Automation.

    Product Features

    The HMI contains a number of product features important for power plant control:

    Dynamic graphics

    Alarm displays

    Process variable trending

    HMI access security

    Maintenance functions such as logic forcing and user-defined point displays

    C H A P T E R 1

    Chapter 1 Overview

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    10/134

    1-2 Chapter 1 Overview GEH-6126CVol I HMI Operators Guide

    HMI Components

    The turbine control HMI consists of the following functional components (Refer to

    figureData Flow between HMI Components):

    CIMPLICITY HMIis used primarily to display turbine status screens, whichenable an operator to monitor the unit(s). Refresh rate is typically 1 second.CIMPLICITY is not used to configure the turbine control.

    An HMI Serverconnects to the controllers to retrieve and display real-

    time data. It optionally makes this information available on the PlantData Highway. HMI Serverstypically also provide the

    programming toolsets for turbine controllers.

    An HMI Viewercontains the operator interface software, which allowsthe operator or maintenance personnel to view screen graphics, data

    values, alarms, and trends, as well as to issue commands, edit control

    coefficient values, and obtain system logs and reports. The HMIViewergets its real-time data over the Plant Data Highwayfrom anHMI Server.

    Note GFK-1180 provides a detailed description of the capabilities of theCIMPLICITY product.

    Turbine Control Interface (TCI)is a software package used to communicatewith Mark IV and Mark V controllers to retrieve real-time information and

    alarms. It also provides the programming toolset for the Mark V controllers.

    Specialized displays are included for specialty functions such as logic forcingand displaying high-speed data. TCI performs the following functions for the

    turbine controllers:

    Mark IV: Provides real-time interface for data and alarms

    Mark V: Provides real-time interface for data and alarms, specializeddisplays, and the programming toolset to configure a Mark V.

    Mark VI: Provides real-time interface for alarms.

    TCIMB(TCI/CIMPLICITY Bridge, previously called CIMBor CIMBridge) isan interface between the CIMPLICITY and TCI, as follows:

    Enables CIMPLICITY to collect data and alarms from controllerssupported by TCI.

    Forwards setpoint and alarm commands from CIMPLICITY to TCI for

    controllers supported by TCI.

    System database(Mark VI only) establishes signal management anddefinition for the control system. It provides a single repository for system alarm

    messages and definitions, and defines mapping between controller software and

    physical I/O. Additionally, it defines Ethernet Global Data(EGD)exchanges, which provide the HMI with controller real-time data. Access to thedatabase is required when configuring the system, but is not required while

    running.

    Depending on the size of the system, these elements can be combined into a single

    computer, or distributed in multiple units. The modular nature of the HMI allowsunits to be expanded incrementally as system needs change.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    11/134

    GEH-6126B Vol I HMI Operators Guide Chapter 1 Overview 1-3

    Point

    Database

    Alarm

    Queue

    Alarm

    Queue

    Data

    Dictionary

    Alarm

    Manager

    Point

    Manager

    Devcom(EGD...)

    External

    AlarmManager

    Mark V

    RP

    Device

    CollectorDevices

    PointDa

    ta

    PointA

    larm

    s

    Point Data

    Alarms

    Devices

    CIMPLICITY TCIMB TCI

    Data Flow between HMI Components

    Graphic Displays

    The HMI uses the graphics and alarm features of the CIMPLICITY software to

    provide an operator interface integrating many different types of controllers. The

    graphical displays offer representations of equipment in real-time.

    The HMI displays data and processes operator commands using screens that

    represent a variety of signals, their values, and units. Display items change color

    based on logic signals, while certain objects are dynamic and refresh with every dataupdate, like bar graphs. Normal viewing allows the displayed data to be updated

    once per second, and special tools allow collection and storage of data at faster rates.

    HMI graphic displays include main unit, vibration, sensor readings, control setpoints,

    alarms, permissives, logic forcing, demand display, sequence editor, dynamic rung

    display, trip history display, trending, and many others depending on the application.

    An operator can view alarms from any HMI on the network as they occur.

    NoteScreens are developed using preconfigured graphic building blocks that

    provide commonality to different plant applications that use the HMI.

    GEH-6126C Vol I HMI Operators Guide

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    12/134

    1-4 Chapter 1 Overview GEH-6126CVol I HMI Operators Guide

    The following figure Sample HMI Display for Gas Turbine and Generator Data

    displays a typical screen using graphics to display real-time turbine data.

    Alarms

    Click buttons and other

    animated objects to

    open additional

    displays or objects.

    Click to open an

    Alarm display which

    will display all alarms.

    Select an alarm listed on the

    alarm display, then click the

    button for the desired action.

    Sample HMI Display for Gas Turbine and Generator Data

    The graphic system performs key HMI functions and provides the operator with real-time process visualization and control using the following:

    CimEditis an object-oriented program that creates and edits the user graphicscreen displays

    CimViewis the HMI program that displays the process information in graphicalformats. Screens have a 1-second refresh rate

    Note GFK-1396 provides a detailed description of the CimEdit and CimViewapplications.

    CIMPLICITY Alarm Viewerprovides alarm management functions such assorting and filtering by priority, by unit, by time, or by source device. Also

    supported are configurable alarm field displays.

    The point control panelprovides a listing of points in the system with real-

    time values. The basic control engineallows users to run scripts in response to system

    events. The program editor is used to create Visual Basic

    for Applications

    scripts.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    13/134

    GEH-6126CVol I HMI Operators Guide Chapter 1 Overview 1-5

    Communications

    The following figure displays the networks used by the HMI to communicate within

    a SPEEDTRONIC turbine control system.

    TR

    HistorianHMI Server # 1HMI

    ViewerHMI Server # 2

    Mark VI Plant Data Highway (Ethernet)

    Mark VI Unit Data Highway (Ethernet)

    Data Data

    Mark IV Control System Freeway (CSF)

    Mark VI

    Turbine

    Control

    I/O

    Mark IV

    TurbineControl

    I/O

    Mark VTurbine

    Control

    I/O

    Mark V Stagelink

    Example of a Turbine Control Communications Network

    NoteRefer to GEH-6126 Vol. II and individual controller documents for more detailabout the networks and protocol used for HMI communication.

    For Ethernet TCP/IP communication to third party equipment, such as a distributed

    control system (DCS) the HMI provides GE Industrial Systems standard messages

    (GSM) and Modbus

    protocol. GSM application layer protocols support four classes

    of application-level messages: administration, event-driven, periodic data, and

    common request messages.

    Alternatively, communication to remote DCS equipment is available through aModbus interface, where the HMI acts as a slave to the DCS master. Such a system

    allows an operator at a remote location to initiate any operator command and to

    monitor turbine data.

    Optional FeaturesThe HMI supports a Windows-based Historiancomputer, which collects and stores

    data from the control units for later analysis. OSI Software, Inc.s PI-ProcessBook

    provides historical and real-time trending of all process data, and can run in theHistorian and/or HMI Viewer. The HMI communicates with the Historian through

    the Ethernet-based Plant Data Highway (PDH) and through RS-232C lines.

    Note Document GEH-6422 provides information about the Historian.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    14/134

    1-6 Chapter 1 Overview GEH-6126CVol I HMI Operators Guide

    The HMI includes a time synchronizationcapability in both low- and high-resolution forms. When redundant time masters are available, all turbine controllers

    and operator interface units on a system automatically select the same, highest

    quality time master.

    A Web Gatewayallows operators to access HMI data from any computer on thenetwork that includes the HMI. Third party interfaces allow the HMI to exchange

    data with the DCS, programmable logic controllers, I/O devices, and othercomputers.

    Application-Specific Features

    When the HMI is paired with either the Mark V or the Mark VI turbine controllers,

    the turbine control software tools can be added to as an integral part of the HMI. The

    Mark VI features are based on the GE Control System Toolbox(toolbox).

    When the HMI is used in our Integrated Control Systems(ICS) product line oras a Balance-of-Plant(BOP) control interface, the ICS/BOP toolset becomes partof the HMI.

    Technical SpecificationsExact hardware and software specifications for the HMI are determined according to

    the needs of the customer and purchased options. The HMI workstation is typicallysent to the customer with the HMI program already installed.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    15/134

    GEH-6126CVol I HMI Operators Guide Chapter 1 Overview 1-7

    Related Documentation

    The following documents apply to the HMI and SPEEDTRONIC turbine controllers

    and can help in understanding HMI operation:

    HMI-related documents:

    GEH-6126 Volume II,HMI for SPEEDTRONIC Turbine Control,Application

    Guide

    GEI-100165, GEDS Standard Message Format

    GEI-100279, SDB Exchange Users Guide for Control System Solutions

    GEI-100500, System Database Utilities for Control System Solutions

    GEI-100513,HMI Time Synchronization for SPEEDTRONIC Turbine Control

    GEI-100514,Power Block Control for SPEEDTRONIC Turbine Control,

    Product Description

    GEI-100515, Microsoft NetMeeting

    3.0 for SPEEDTRONIC Turbine Control,

    Installation and Setup

    GEI-100516, GE Industrial System Standard Messages(GSM)

    GEI-100517,Modbus for HMI Applications

    GEI-100535,Modbus Communication Interface for SPEEDTRONIC Mark VI

    Turbine Controllers

    GEH-6422, Turbine Historian System Guide

    GFK-1180, CIMPLICITY Base System User's Manual

    GFK-1181, CIMPLICITY HMI Plant Edition,Base System Device

    Communications Manual

    GFK-1396, CIMPLICITY HMI CimEdit Operation Manual

    GFK-1675, CIMPLICITY HMI, OPC Server Operation Manual

    Mark VI controller and related documents:

    GEH-6403, Control System Toolbox for Configuring a Mark VI TurbineController

    GEH-6408, Control System Toolbox for Configuring the Trend Recorder

    GEH-6421,SPEEDTRONIC Mark VI System Guide, Volumes I and II

    GEJ-7485, SPEEDTRONIC Mark VI Turbine Control, Software Maintenance

    GEI-100278,Data Historian

    Mark V and V LM controller and related documents:

    GEH-5979, SPEEDTRONIC Mark V Turbine Control Users Manual

    GEH-5980, SPEEDTRONIC Mark V Turbine Control Maintenance Manual

    GEH-6195, SPEEDTRONIC Mark V Turbine Control Application Manual

    Overview

    GEH-6354,Mark V LM SPEEDTRONIC Turbine Control Users Manual

    Note GEH-#### is the document identification number.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    16/134

    1-8 Chapter 1 Overview GEH-6126CVol I HMI Operators Guide

    How to find the 3V number

    The GE requisition or shop order number is referred to as the 3V number. These

    numbers should be recorded and retained for future reference. The GE job stickerwith this number is located on the equipment such as the controller cabinet and the

    HMI computers. Refer to figure Sample of GE Job Sticker.

    This 3V number is required for support issues.

    Sample 3V

    job number

    Sample of GE Job Sticker

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    17/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-1

    Introduction

    A facility typically receives the HMI pre-loaded with all the programs and

    customized software required for the customers application. It is configured duringinstallation to automatically log on and open to the main operator display when

    powered-up.

    This chapter provides basic startup procedures to help the operator use the HMI.

    Detail of these HMI features is covered in the other sections of this document.

    Starting Up the HMI To start up the HMI and open your application

    1 Power up the computer if it is off. If Auto Log Onis enabled the computershould start the CIMPLICITY application CimView and its associated main

    operation display automatically. If a Log Ondialog box appears, type in Operin the User Namefield (User names are not case sensitive) and its associated

    password (default is no password) in the Passwordfield.

    2 If the computer is already running, press the three keys Ctrl+Alt+Delete all atonce to bring up the Log Ondialog box to change the User to Oper.

    3 If the main operation display does not start automatically, double-click the

    desktop icon, typically Unit_Control.cim.

    When the computer starts up, it starts all CIMPLICITY programs (Refer to figure

    Typical Services Starting Display, below) and displays the main operation display

    (Refer to figureExample of a Typical HMI Display).

    Note GFK-1180 describes CimView in detail for the Mark V.

    Note The HMI displays for the user's system are CimView displays (*.cim files),which can open before CIMPLICITY finishes loading. If at first the display is not

    animated or setpoints fail, wait a few minutes for the startup to complete before

    beginning operation. During the startup process do not click any Cancel or Close

    buttons.

    C H A P T E R 2

    Chapter 2 Quick-Start Procedures

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    18/134

    2-2 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Do not click

    Closebutton

    as it may

    cancel the

    complete

    loading of

    essential

    services

    before the

    HMI starts.

    Click to manually start HMI

    if it does not start

    automatically.

    Typical Services Starting Display

    Click buttons

    and other

    animated objects

    to open

    additional

    displays or

    objects.

    Select an alarm listed on the

    alarm display, then click the

    button for the desired action.

    Alarms

    Click to open

    an Alarm

    display whichwill display allalarms.

    Example of a Typical HMI Display

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    19/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-3

    Example of a Typical Alarm Display

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    20/134

    2-4 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Other HMI Displays

    NoteThe following HMI displays are not intended to be a guide to operating aturbine. It is not a comprehensive list. Only typical displays are listed.

    Lockout Function Master Reset - Mark IV, Mark V,

    Mark V LM and Mark VI

    The Master Reset does not reset diagnostic alarms. It typically is performed after a

    turbine trip and all trip causes understood and corrected.

    Master Reset Dialog

    BoxMaster Reset

    buttonProcess alarm that has

    returned to normal state.

    Example of Master Reset

    The Master Reset clears any latched process alarms that have returned to a normal

    condition. The operator can also remove an alarm from the alarm queue by

    Selecting the alarm by clicking on it.

    Clicking the Ackbutton.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    21/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-5

    Trip Diagram Display - Mark IV, Mark V, Mark V LMand Mark VI

    The Trip Diagram display enables operators and maintenance personnel to determine

    the causes of a turbine trip. The trip causes will remain displayed until a MasterResetis performed. A Master Resetdoes not cancel any problem that is notcorrected.

    Examples of

    causes of a trip.

    Click Gen

    Capability

    button to

    open the

    Reactive

    Capability

    window.

    Not all causes for a trip will

    appear on this display.

    Typical Trip Diagram Display

    NoteTrips are displayed in RED. Some signals are not latched. The operator mustcheck the trip history for an accurate chain of events leading to any trips that appear

    on the display. Refer toViewing the Trip Historyin this chapter for more

    information.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    22/134

    2-6 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Lockout Function Diagnostic Reset - Mark V,Mark V LM and Mark VI

    The Diagnostic Resetfunction does not reset process alarms.

    Sycronization

    display

    Startup Trend

    display

    Diagnostic

    Resetbutton

    Diagnostic alarm exampleDiagnostic Reset dialog

    box

    Example of Diagnostic Reset Function

    The Diagnostic Reset clears any latched diagnostic alarms that have returned to a

    normal condition. The operator can also remove an alarm from the alarm queue by

    Selecting the alarm by clicking on it.

    Clicking the Ackbutton.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    23/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-7

    Start Checks Display - Mark V, Mark V LM andMark VI

    The Start Checksdisplay presents the turbine conditions that prevent the operatorfrom starting the turbine.

    First select

    Aux then

    Start Check

    Turbine start status

    Signals

    which will

    inhibit thestart of the

    turbine.

    Example of a Typical Start Check Display

    NoteSignals in the proper state to permit a start are displayed in GREEN. Signalswhich are RED inhibit start requests.

    The Diagnostic Resetclears any latched diagnostic alarms that have returned to anormal condition. The operator can also remove an alarm from the alarm queue by

    Selecting the alarm by clicking on it.

    Clicking the Ackbutton.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    24/134

    2-8 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Alarm Setup - Mark IV, Mark V, Mark V LM andMark VI

    There can be many non-critical alarms displayed. The alarm list can be filtered sothat only a portion of the alarms is displayed. For example the operator may select

    only process alarms to be displayed. This does not affect or change any alarms that

    are not displayed. By selecting the operator can display all

    alarms. The alarm filters are configured using CIMPLICITY. Refer to Chapter 3for

    more information.

    SetupbuttonAlarm Setups

    dialog box.

    Previously

    defined

    CIMPLICITY

    alarm filters.

    Example of a Typical Alarm Setups Dialog Box

    The Alarm Setupsdialog box is used to select alarms to be displayed based onfiltering criteria defined using CIMPLICITY.

    Click Setupbutton.

    Select filter.

    Click Load. Click Doneto apply the filter to the alarm queue.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    25/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-9

    Turbine Startup Trend Display - Mark IV, Mark V,Mark V LM and Mark VI

    Clicking on the Startup Trendbutton (Refer to figureExample of Diagnostic ResetFunction) opens a new window displaying the pre-defined Startup Trend display.

    Slider to

    select a time

    for process

    value to be

    displayed.

    Process

    values

    Time frame for

    display

    information

    Options buttons

    add/remove signals

    from the display.

    Typical Startup Trend Display

    The Turbine Startup Trenddisplay is available to the operators to monitor criticalturbine parameters during the startup phase of the turbine.

    Click Startup Trend(Refer to figureExample of Diagnostic Reset Functionfor the location of this control).

    Select Options.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    26/134

    2-10 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Synchronization Display - Mark IV, Mark V,Mark V LM and Mark VI

    Clicking on the Synchbutton (Refer to figureExample of Diagnostic ResetFunction) opens the Synchdisplay. Refer to figure Typical Mark V AutoSynchronizationDisplay.

    Synch Mode

    command

    buttons.

    Auto synch

    permissives

    Typical Mark V Auto Synchronization Display

    Refer to Optional HMI Displays,Manual Synchronizing Display, in this chapter for

    more information.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    27/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-11

    Optional HMI Displays

    Note The following HMI displays are not intended to be a guide to operating aturbine. The HMI displays are optional add-ons to CIMPLICITY. Only common

    optional displays are included.

    Reactive Capability Display - Mark IV, Mark V,Mark V LM and Mark VI

    The Reactive Capability Displayis a real-time graphic that displays the turbinegenerator's current MW and MVAR operating point (Refer to figureExample of

    Reactive Capability Display). The plot displays three lines of generator capability asa function of generator coolant temperature or hydrogen pressure.

    The operator can use this display to check how close the generator is operating to its

    thermal limits. To prevent the generator from overheating, the current operatingpoint must be kept within the dynamic envelope displayed for the current conditions.

    Note The ratings curves are different for each application. They are displayed as anexample only and should not be used unless they match the generator ratings.Displaying the wrong curves can cause operation outside the machines rated limits.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    28/134

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    29/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-13

    Synch Mode

    command button

    Manualsynch

    mode button

    Autosynch

    mode button

    Synch mode

    change

    confirmation

    box

    Manual BreakerClose button.

    Example of Manual Synchronizing Display for Mark V

    Breaker Close Command Button

    Auto Synch Mode Confirmation Dialog Window

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    30/134

    2-14 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Manual Synchronizing Display Mark VI

    For Mark VI, some data in the Manual Synchronizingdisplay object is updated atthe frame rate of the controller. It must run on a server due to its fast update rate.

    If the Manual Synchronizationoption is enabled then both Automatic andManual Synchronization share the same window for synchronization control.

    Refer to GEH-6421 Mark VI Control System Guide, for more information.

    Auto synch

    permissivesAuto Sync

    mode button

    Manual

    Syncmode

    button.

    Close Breakerbutton

    visible when Manual Synch

    mode is enabled.

    Manual Synchronizing Display for Mark VI

    Manual Synchronizing Confirmation Window

    Auto Synchronizing Confirmation Window

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    31/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-15

    Triggered Plot Display

    Triggered Plot Display Mark V and Mark V LM

    The Triggered Plot function provides a graph of high-speed turbine data. The graph

    can be triggered by the change in state of a logic signal in the unit. Turbine

    commands can be sent from this display, making it useful for initiating turbine tests

    (such as valve travel tests).

    Note The Triggered Plotfunction is run only from a HMI server. It is not runfrom a HMI viewer. It uses high-speed data (up to frame rate) that is only available

    from a HMI server.

    Only qualified personnel knowledgeable about turbine

    control and protection should create and execute

    commands. The commands can affect the control state and

    action of the unitcontrol.

    Example of Triggered Plot Display

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    32/134

    2-16 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Other Tools

    The following sections provide instructions for performing HMI functions, such as

    viewing sequencing information and performing logic forcing.

    Viewing Sequencing Information

    Viewing Sequencing Information - Mark IV

    Mark IV has no sequencing information and no Dynamic Rung Displaycapability in an HMI. Sequencing information is available on the panel-mountedOperator Interface.

    NoteRefer to GEK-83865and GEK-83866.

    Viewing Sequencing Information - Mark V and Mark V LM

    Both Mark V and Mark V LM use the Dynamic Rungdisplay function for viewing

    sequencing information. The Dynamic Rungdisplay is a tool for stepping throughthe control programming of a Mark V and Mark V LM controller. The DynamicRung display is used for monitoring purposes only. The units control sequence

    program cannot be altered using this program.

    NoteRefer to Chapter 3for more information. Refer toAppendix A for functionsand applicability.

    To open the Dynamic Rung Display for Mark V and Mark V LM

    1 From the Start menu, select Programs, Turbine ControlMaintenance, Unit T#, then Dynamic Rung Display.

    OrFrom the Windows desktop, click the Dynamic Rung Display icon.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    33/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-17

    Programs

    Start

    Turbine Control

    Maintenance

    Unit T#

    Utilitieslist

    2 From the HMI click Toolsto display Turbine Control Maintenanceutilities.

    DynamicRungdisplay

    Click to openTurbine ControlMaintenanceutilities

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    34/134

    2-18 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Title bar

    displays unit

    name and

    segment name

    Header, which displays

    the following data

    Unit, site, and segment

    name.Rung number, and

    Timetag.The Header can scroll off

    the screen or be hidden

    by other windows.

    However, it is good

    practice to keep it visible

    because it contains

    valuable process

    information.

    Viewing Sequencing Information - Mark VI

    The Mark VI controller uses the Control System Toolboxapplication to displayall sequencing information.

    NoteRefer to GEH-6403 Toolbox for a Mark VI Turbine Controller and Chapter 3

    for more information.

    This feature is similar to the Dynamic Rung Display for the, Mark V and Mark VLM.

    When a controller is configured and downloaded, the live signal values can be

    viewed. This section defines how to go online to monitor these values and certain

    Summary Views when the controller is being monitored. These views are displayed

    when the Trackingbutton is on and an item is selected in the Outline View.

    Typically toolbox opens the controller at a privilege

    level of 0, which permits Read Only functions in

    toolbox. Operators typically run using this lowestprivilege level to prevent inadvertent changes to the

    controller.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    35/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-19

    To open the Monitor Display for Mark VI

    1 From the Start menu, select Programs, GE Control SystemSolutions, then Control System Toolbox.

    Or

    From the Windows desktop, click the Control System Toolbox icon.The toolbox Work Areadisplays an empty window until a device is created oropened.

    2 From the toolbox Filemenu, open a previously saved configuration file.

    3 Click the Tracking button to turn tracking on.

    4 Click the Go Online/Offline button. Select the item of interest in theOutline View. It appears in the Summary View with live signal values.

    Titlebar

    Toolbar

    Outline

    View

    Live signal values

    displayed in

    Summary View

    Control Block

    Privilege

    Level

    Tracking

    ButtonFinder

    Go On/

    Offline

    Signal

    connections

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    36/134

    2-20 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    To find all occurrences of a control signal

    1 Click the Finderbutton displayed in above figure.

    2 Enter control signal in dialog box and click Find.

    3 Click on a location in the Contextwindow to go to that location of the signal inthe Summary View. A signal marked with an * is the location where the signal

    is written.

    Always on

    top button

    Goto

    button

    Unit

    Signal

    Asterisk (*)

    denotes location

    where signal is

    written.

    Location of each

    occurrence of the

    signal.

    User Defined Displays - Mark IV, Mark V, and Mark V LM

    CIMPLICITY HMI uses the Demand Displayfunction for the Mark IV. Thisfunction is also available on the panel-mounted Operator Interface. The DemandDisplayfunction is used for Mark V and Mark V LM. Demand Displayis a

    program that offers flexible monitoring and control of a variety of datapoints and of

    multiple units. It provides the following turbine control features:

    Ability to monitor several datapoints at a time.

    Ability to issue process commands to the unit(s).

    Alterable displays that conform to the user needs.

    Easy to configure displays for testing and special procedures.

    Control of unit functions while monitoring associated data.

    Ability to accommodate different types of units in one Demand Display.

    NoteRefer to Chapter 3for more information

    Only qualified personnel knowledgeable about turbine

    control and protection should create and execute

    commands. The commands can affect the control state

    and action of the unit control.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    37/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-21

    To load an existing Demand Display file

    1 From the Start menu, select Programs, Turbine ControlMaintenance, Unit T#, then Dynamic Rung Display.

    2 From the Filemenu, select Open.

    3 Select the desired file. If no existing file is specified, the default file

    DEMAND01.DM2 (located in theF:\RUNTIMEdirectory) loads.

    To load a desired display

    Double click on the display name in the display menu.

    List of Demand

    Displays.

    Double click to

    open.

    Header

    Legend

    Data Area

    Command Target Field

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    38/134

    2-22 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    User Defined Displays - Mark VI

    Mark VI uses toolbox and its Watch Windowsfunction to provide user-defineddisplays. The Watch Windowsfunction creates a quick reference list containingnames, values, units, and description of the online values of signals. Each controller

    document can contain multiple, uniquely named watch windows.

    NoteRefer to GEH-6403 Toolbox for a Mark VI Turbine Controllerand Chapter 3for more information.

    Typically toolbox opens the controller at a privilege level of

    0, which permits Read Only functions in toolbox. Operators

    typically run using this lowest privilege level to prevent

    inadvertent changes to the controller.

    To open a Watch Window

    From the toolbox toolbar, click View and select Watch Windows. The SelectWatch Windowdialog box displays.

    Select View

    Select

    Watch

    Windows

    Verify these fields are green orincorrect data may be

    presented.

    On / Offline Must be online

    to view values.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    39/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-23

    To open a Watch Window

    From Select Watch Windowdialog box, click an existing Watch Windowand click View.

    All Watch

    Windownames are

    listed here.

    Click a name

    to highlight or

    double click

    to open.

    Click to

    View

    highlighted

    Watch

    Window

    NoteRefer to Chapter 3for more information.

    Click a column header

    to change the order of

    the headings

    Signal

    User-added

    comment.

    NoteIt is possible to minimize any watch window by clicking the minimize symbolin the upper right hand part of the dialog.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    40/134

    2-24 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Viewing Trip Information

    Viewing Trip Information - Mark IV

    Mark IV has no trip information display capability in an HMI. This information is

    available from the panel-mounted Operator Interface.

    NoteRefer to GEK-83865and GEK-83866.

    Viewing Trip Information - Mark V and Mark V LM

    Trip information is automatically gathered by the HMI from the controller. The last

    ten trips are stored on the HMI and can be viewed by using the Trip Log Viewer.

    The information about the last trip can be manually uploaded at any time, or the

    current accumulated data can be uploaded even without a trip.

    Mark V trip history information about the last trip is stored in the controller, and is

    lost if the controller is reset or rebooted. The HMI runs the automatic collection scan

    typically every five minutes, but the trip information can be uploaded manually

    before the controller is reset or rebooted.

    Mark V LM trip history information is stored in non-volatile memory and is not lost

    if the controller is reset or rebooted.

    Viewing Automatically Collected Trip Logs

    The Trip Log Vieweris used to view the trip log data. The user selects a valid unitand chooses a file from the list presented. The trips are identified by their date and

    time stamps. The latest trips are listed at the top of the list. After selecting the trip to

    be viewed, the results are displayed in a Notepadwindow. The data is organizedaccording to pre-trip, post-trip, and alarm categories.

    To view a Mark V or a Mark V LM Trip log

    1 From the Start menu, select Programs, Turbine ControlMaintenance, Unit T#, then Trip Log Viewer.

    2 From the Trip Log Viewerdialog box, select a unit from the Select Unitlistbox.

    3 From the Select a Previous Trip Loglist, select a log to display byhighlighting it.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    41/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-25

    4 Click the Go Tobutton to display the selected log file.

    Select a unit

    from this list.

    List of Trip

    Logs

    arranged by

    date and

    time. The

    latest trip is at

    the top of the

    list.

    Select one to

    view.

    5 The selected log file displays in a Notepad window.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    42/134

    2-26 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Viewing Manually Collected Trip Logs - Mark V and Mark V LM

    If the Mark V controller is rebooted or restarted before the Trip Log data is uploaded

    to the HMI the information can be lost. The unit is scanned every five minutes and if

    there is a new trip the trip information is collected and saved as a new Trip Log by

    the HMI.

    The Mark V LM controller has non-volatile memory for the Trip Log queue and can

    save the contents of the trip information across restarts or reboots of the controller.

    The Trip Historyprogram allows the user to manually retrieve data from the unitcontrol and view it on the operator interface. The data can be collected and saved

    even if the unit is running (has not tripped).

    To view a Trip History for Mark V or Mark V LM

    1 From the Start menu, select Programs, Turbine ControlMaintenance, Unit T#, then Trip History.

    2 From the Trip History dialog box, select a unit from the Select Unitlist.

    SelectUnit

    3 Click a Select Logoption button for the type of historical data to be collectedfrom the controller. Only one button can be selected.

    4 Click the Collectbutton to retrieve the data or click the Stopbutton tocancel.

    Trip History DataThis function enables the operator to view the contents of theTrip Log buffer immediately after a trip. This is useful when the HMI has not yet

    uploaded the trip data from the controller. Refer to figure Typical Trip History.

    Saved History DataThis function enables the operator to view previouslyuploaded and saved trip files. It opens the dialog box displayed in figureExample of

    Triggered PlotDisplay. The list appears in chronological order with the latest at the

    top of the list. Refer to figure Typical Saved History Data.

    New DataThis function enables the operator to take a snapshot of the accumulatingdata while the unit is running (not tripped). This data can be used in comparison of

    data gathered by a trip condition. Refer to figure Typical New History Data.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    43/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-27

    The resulting data is displayed in a Notepad window. The displayed data can be

    saved using File: Save Asmenu option in Notepad and specifying a file name andlocation.

    Typical Trip History

    Typical Saved History Data

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    44/134

    2-28 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Typical New History Data

    Viewing Trip Information - Mark VI

    The Mark VI controller uses the toolbox Data Historianto collect trip history data.The Data Historian trip log is a combination of historical analog and discrete data.

    This trip history data is viewed using the toolbox Trend Recorder. The trip logsignals are trended on a full-page screen. Alarms, events, and SOEs can also be

    viewed in a list format displaying the logic state and time of the event.

    NoteRefer toData Historian document GEI-100278and Trend Recorder documentGEH-6408for more information.

    To view Trip Logs for Mark VI

    1 From the Start menu, select Programs, GE Control SystemSolutions, then Control System Toolbox.

    Or

    From the Windows desktop, click the Control System Toolbox icon. The Control

    System Toolbox opens.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    45/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-29

    2 From the toolbox Filemenu click Opento open a Trip Log file.

    List of trip

    logs

    Select one of the trip log files to view.

    Trip Logs identified

    by unit, TripLog,

    date and time.

    Select Files of type All

    Files (*.*) to populate

    list with trip logs.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    46/134

    2-30 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    The Trip Log file opens in the Trend display.

    Alarm Logger Control

    Alarm Logger Control - Mark IV, Mark V, Mark V LM, and Mark VI

    Several classes of turbine control actions can be automatically logged to a printer as

    they occur. The HMIs Alarm Loggerallows the operator to select any of thefollowing to output to the printer using the Alarm Logger Controldialog box.

    Process alarms

    Diagnostic alarms

    Events

    SOEs

    NoteThis program is used with Mark IV, Mark V, Mark V LM, and Mark VI.Refer to Chapter 3for more information. Also Refer to GEH-6126 Vol IIfor

    additional information.

    To enable printing of alarms or events

    1 From the Start menu, select Programs, Turbine ControlMaintenance, Unit T#, then Alarm Logger Control.

    2 From the blank Alarm Logger Controlbox select the Unit and the LoggerFunction.

    3 Click OK.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    47/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-31

    Process identification data

    Click on drop-down box arrow toselect unit (displayed in alpha -numeric order).

    There are four functions (catagories)

    of information that can be printed.Click on a box to select. (Blank isunselected; a check is selected.)

    You can select each function on aunit basis by selecting the Unit and

    Function(s), then the OK button.

    Exits dialog box without savingchanges.

    Saves selections and exits.

    Cancels changes and exits.

    Applies current units settings to allunits.

    Immediately deletes all pendingalarm print jobs for all units from

    the Alarm Printer (does not requireOKto be selected).

    Hold List Display (Steam Turbine Applications)

    Hold List Display - Mark V and Mark VI

    The Hold Listdisplay is required for the HMI to support large and medium steamturbine controls on systems that have Automatic Turbine Startup (ATS).

    Turbine operating conditions can cause a hold, which prevents ATS from setting thespeed or load target to a higher value. The Hold Listdisplay is accessed from anavigation button on the CIMPLICITY screen.

    Overridehold Cancel Override

    hold

    Typical Hold List

    The CIMPLICITY Alarm Viewerdisplays the Hold Liston the HMI, used to viewand override the current hold points.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    48/134

    2-32 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Accessing the Web-Based Displays- Mark IV,Mark V, Mark V LM, Mark VI

    Accessing the Web-Based Displays

    The HMI provides Webdisplays to view certain types of information. These Webdisplays can be viewed locally, or from other computers connected to the HMI

    through a network.

    To access the Web displays from the HMI

    1 From the Start menu, select Programsthen the Web browser (usuallyInternet Explorer).

    2 TheWebbrowser displays.

    3 If the page is not already configured as the Homepage, in the address area,type: http://localhost

    4 The TCI InformationWeb Home page displays.

    If the user is not at the HMI, but at another computer connected to the HMI by a

    network, the Webdisplays can be accessed from the user's Webbrowser by typing:

    http://

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    49/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-33

    Web Historical Alarm and Event Exception Report

    The Historical Alarm and Event Exception Report is a tool for analyzing exception

    data stored on the HMI. An Exception occurs when one of the Process Alarm, Event,

    or SOE points scanned by the controller changes state. A change in state is a point

    pickup or dropout, or a change in the lockout state of a Process Alarm. This data isreported to the HMI whenever a change occurs.

    Historical Alarm and Event Exception Report

    The report contains a header, which displays the users form input selections:

    The Site name and the Unit names selected. The Data types selected.

    The Time format.

    The Reports Start time and End time.

    The Report type.

    The output page contains the following data on each line:

    The Time tag of the exception; this time comes from the controller.

    The Unit name

    The Status of the alarm or discrete event, indicated as follows:

    1 indicates Pickup, and 0 indicates Dropout. L indicates Lock, and U indicates Unlock.

    The Point name for SOEs and Events, or processor and drop number for alarms.

    The Data type indicated as follows:

    ALM for Alarms

    EVT for Events

    SOE for Sequence of Events

    Descriptive text

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    50/134

    2-34 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    The report begins with the oldest data and has the newest data at the end. It can be

    printed or saved as a text file from the browser window. To return to the query form,

    use the Backbutton on the web browser.

    Historical Alarm and Event Summary Report

    The Historical Alarm and Event Summary Report is useful for analyzing the

    frequency of exception data, especially nuisance alarms and edge conditions(chattering SOEs). It is important to eliminate frequently occurring nuisance alarms

    and edge conditions since they crowd up the exception report without adding usefulinformation, making it difficult to interpret the relevant data.

    Historical Alarm and Event Summary Report

    The report contains a header that displays the users form input selections:

    The Site name and the Unit names selected.

    The Data types selected.

    The Time format

    The reports Start time and End time.

    The Report type

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    51/134

    GEH-6126CVol I HMI Operators Guide Chapter 2 Quick-Start Procedures 2-35

    The report data is listed separately for each unit, and each data type within that unit.

    Data is listed in the order of drop number for alarms and events, and in point number

    order for events and SOEs. The output page contains the following data on each linefor process alarms:

    The number of pickups and the number of dropouts.

    The number of locks and the number of unlocks.

    The Unit name

    The processor

    The drop number

    Descriptive text

    The output page contains the following data on each line for Events and SOEs:

    The number of pickups and the number of dropouts.

    The Unit name

    The point name for SOEs and Events.

    Descriptive text

    It can be printed or saved as a text file from the browser window. To return to the

    query form, use the Backbutton on the web browser.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    52/134

    2-36 Chapter 2 Quick-Start Procedures GEH-6126CVol I HMI Operators Guide

    Notes

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    53/134

    GEH-6126CVol I HMI Operators Guide Chapter 3 Display and Control (Command) Programs 3-1

    IntroductionThe HMI provides an online database for collecting and storing data from multiple

    controllers. Refer to the controller documentation for description of the online

    database.

    The HMIs display-only programs allow the user to view turbine control data asneeded to monitor the system. User cannot, however, send control commands from

    these displays.

    The HMIs control (command) programs allow the user to send commands to the

    turbine control.

    Viewing Sequencing Information

    The program running in the controller that defines its control actions is called itssequencing. Sequencing typically consists of individual AND/OR logic operations

    (called relay-ladder logic rungs) and calls to library functions that do analog or

    complex operations (called primitive blocks or big blocks).

    Some controllers (such as the Mark V) use separate programs in the HMI to edit the

    sequencing and view the running sequencing. Other controllers (such as the Mark

    VI) use the same program for both, with a privilege level controlling whetherchanges to the sequencing are allowed. Both schemes allow the user to view the

    current running sequencing overlaid with the real-time data that is driving that

    sequencing. This is often useful for determining what conditions are driving aparticular condition, such as what is preventing the unit from being ready to start, or

    what conditions are driving a particular alarm.

    Viewing Sequencing Information - Mark IV

    The HMI has no knowledge of the sequencing running in the Mark IV controller, and

    as such has no sequencing display capability. Sequencing displays are available fromthe Mark IV controller's panel-mounted Operator Interface. The HMI does provide a

    Demand Displayfor Mark IV data, but it does not display the sequencing thatcreates the values.

    Note Refer to GEK-83865and GEK-83866.

    C H A P T E R 3

    Chapter 3 Display and Control(Command) Programs

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    54/134

    3-2 Chapter 3 Display and Control (Command) Programs GEH-6126CVol I HMI Operators Guide

    Viewing Sequencing Information - Mark V andMark V LM

    The sequencing running in a Mark V controller is referred to as the ControlSequence Program(CSP). The HMI's Dynamic Rungdisplay is used to viewthe CSP overlaid with the current values from the controller.

    The Dynamic Rungdisplay program includes:

    Animation to display the current state of the control.

    Relay Ladder Diagram (RLD) rungs.

    Primitive and Big Block rungs. Some blocks include pictures of the sequencing

    inside the block.

    Starting a Demanddisplay with all of the signal names and values from thecurrent rung.

    A Findutility to display the locations and usage of all occurrences of a signal.

    The following rules apply to the Dynamic Rungdisplay:

    Can only display control segments from a single unit at any time.

    Can display multiple control segments from the given unit.

    Cannot be used to alter the units CSP.

    The Dynamic Rung Display does not independently

    verify that the operator interface files match the unit

    control files. If these files do not match, the Dynamic

    Rung Display can display data that does not reflect the

    state of the unit control.

    The Dynamic Rungdisplay can save picture file displays in a text format for futurereference. Any text editor can open these text files, but it should use the

    MSLineDrawfont distributed with the TCI product.

    Dynamic Rung Display Windows

    The Dynamic Rungdisplay is a multiple document interface that allows the user toopen windows with different segments or the same segment. The user can also have

    picture file windows and sub rung windows open.

    Starting the Dynamic Rung Display

    To Start the Dynamic Rung Display

    From theStart menu, select Turbine Control Maintenance, Unit T#,then Dynamic Rung Display.

    Or

    From the Windows desktop, click the Dynamic Rung Display icon.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    55/134

    GEH-6126CVol I HMI Operators Guide Chapter 3 Display and Control (Command) Programs 3-3

    Click to selectDynamic Rungdisplay.

    Click one to selectunit. More than one

    unit may be available

    The Dynamic Rungdisplay is started with no segments opened. To open asegment:

    From the File menu select Open.

    Click FileOpento

    open Sequence

    Segment Selection

    dialog box.

    Main Display

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    56/134

    3-4 Chapter 3 Display and Control (Command) Programs GEH-6126CVol I HMI Operators Guide

    Select a Segment to view from the list.

    Selected unit

    Click to select a

    Segment to

    View.

    ClickOKto

    load segment

    into the

    Dynamic Rung

    Display.

    Navigation

    Buttons

    Click button to Find All

    instances of a

    Pointname in all

    Segments.

    Click button to Find

    next instance of a

    point name in the

    current Segment.

    There are three major types of windows: mainframe, rung, and picture described

    below:

    Main Frame This is the outer container display that contains the rung and picturefile displays.

    RungRung displays enable the user to view the control programming with live data.User can view control rungs and blocks in a control sequence segment for a given

    unit. This function includes a Findutility.

    PicturePicture file windows display a picture representation of non-sequencing

    BBLs, which are used to perform analog type calculations.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    57/134

    GEH-6126CVol I HMI Operators Guide Chapter 3 Display and Control (Command) Programs 3-5

    Main Frame Window

    This is the display that opens when Dynamic Rung Display is clicked. Upon opening

    this display is empty and its display title is Dynamic Rung Display. It can containmultiple rung displays and picture displays.

    Rung Windows

    Rung displays (Refer to figureExample of a Dynamic Rung Display) are used to

    display the animation of the control sequencing and navigate through the control

    sequencing segments. They can display data from main sequencing rungs or sub

    rungs that are predefined in Big Blocks.

    Title bar

    displays unit

    name and

    segment name

    Header, which displays

    the following data

    Unit, site, and segment

    name.

    Rung number, and

    Timetag.

    The Header can scroll off

    the screen or be hiddenby other windows.

    However, it is good

    practice to keep it visible

    because it contains

    valuable process

    information.

    Example of a Dynamic Rung Display

    The Rung Window can contain the following types of rungs:

    RLD rungs

    Primitive rungs

    Big blocks Comment rungs

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    58/134

    3-6 Chapter 3 Display and Control (Command) Programs GEH-6126CVol I HMI Operators Guide

    The type of information in the header timetag depends on the type of display:

    In both the RLDand Primitive Rungdisplays, the timetag provides the oldestpiece of data being displayed in the RLD portions of the rung. If it has not

    received data from the unit the timetag display isNo Valid Data. If the oldestpiece of data in the rung has not been updated for at least five seconds, the

    timetag is highlighted. Rung animation occurs once per second (Refer to Table

    Animation Rules for Both RLD and Primitive Rungs).

    In both the Big Blockand Comment Rungdisplays (where there is nodynamic data) the timetag indicates the operator interface time when the rung

    was displayed. The time does not update.

    NoteHeader data is located in the upper left of the window.

    Animation Rules for Both RLD and Primitive Rungs

    Rung Component Animation Rule

    Normally Open Contacts A green rectangle between the contacts displays continuity.

    No rectangle between the contacts displays an open circuit.

    A > symbol between the contacts means forced signals.

    A rectangle outline around the > symbol highlights contacts that are forced

    to the open condition.

    Normally Closed Contacts A slash through the contact indicates normally closed.

    A green rectangle between the contacts displays continuity.

    No rectangle between the contacts means an open circuit.

    A rectangle outline around the > symbol highlights contacts that are forcedto the open condition. The slash through the contacts is broken in the middle tohighlight the > symbol.

    Normal Coils A coil circle filled with green is energized.

    A coil circle filled with the window background color is de-energized.

    A > symbol in the coil circle indicates forced signals.

    Inverted Coils A slash through the coil indicates that it is inverted.

    A coil circle filled with green is energized.

    A coil circle filled with the window background color is de-energized.

    A > symbol in the coil circle indicates forced signals. The slash through thecontacts is broken in the middle to highlight the > symbol.

    To update the Primitive Block Rung or Big Block Rung display todisplay passed parameters

    From the Viewmenu, select either Picture Fileor Demand Display.

    To update Big Block Rung display to display automatic parameters

    From the Viewmenu, select Demand Display.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    59/134

    GEH-6126CVol I HMI Operators Guide Chapter 3 Display and Control (Command) Programs 3-7

    Picture File Windows

    Picture file windows (Refer to figureDynamic Rung Displays Picture File Window)

    are used to display the picture file and animation of the passed parameters forPrimitive and Big Blocks.

    Title bar displays:

    Unit name

    Segment name

    Rung number

    Picture file name

    Header, which displaysthe following data:

    Unit, site, segment, andpicture file name

    Rung number

    Timetag (differs for Staticand Values displays)

    The Header can scroll off the screen or behidden by other windows. However, it is goodpractice to keep it visible because it containsvaluable process information.

    Dynamic Rung Displays Picture File Window

    The type of information in the header timetag depends on the type of display:

    For a values display, the timetag provides the oldest piece of data beingdisplayed as a passed parameter. This includes the coil output for primitive

    blocks. If it has not received data from the unit, the timetag display isNo Valid

    Data. If the oldest piece of data in the rung has not been updated for at least five

    seconds, the timetag is highlighted.

    For a static display, the header timetag provides the operator interface time ofwhen the rung was displayed.

    NotePicture files cannot be opened directly by selecting Openfrom the Filemenu.

    To open a picture file

    1 Open a sequencing segment.

    2 Navigate to the rung that contains the applicable Primitive or Big Block.

    3 From the Viewmenu, select Picture File. A static picture file window displayswith the passed parameter point names represented as inputs and outputs to the

    block.

    4 From the Viewmenu, select Values to change to a values type display.

    The parameter point names are replaced with their current values from the real-time database. The data is updated once per second.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    60/134

    3-8 Chapter 3 Display and Control (Command) Programs GEH-6126CVol I HMI Operators Guide

    The following rules also apply to the picture file displays:

    To toggle between the values display and the static display, select Valuesfromthe Viewmenu.

    Big Block automatic parameters are not animated in the picture file window.

    You can only view their values by selecting View- Demand Displayfrom themenu.

    You cannot navigate to other rungs or picture file windows from a picture file

    window.

    A picture file window remains open until you close it by selecting File Closefrom the menu.

    Selecting a Sequencing Display Screen

    Sequencing files contain the Control Sequence for each control segment. The

    following rules apply when opening these files:

    Selecting File- Openfrom the menu can only open a regular sequencingsegment from the files listed in the MSTR_SEQ.CFG.

    Select a unit before opening a sequencing file.

    You can open more than one segment at a time, or have multiple views of the same

    segment. Use the Windowmenu to change between views.

    To navigate within a segment, use the Rungmenu and toolbar buttons.

    Using the Find All Function

    The Dynamic Rungdisplay includes a Find Allfunction, which allows you to findthe occurrence of a particular signal anywhere within the control sequencing. This

    function will find the following:

    Signal names in RLD rungs

    Signal names as passed parameters

    Signal names as automatic parameters

    Primitive names

    Big Block names

    Find Alldoes not do the following:

    Locate signals and block names used in sub rungs

    Search Comment Rungs. The Find AllFunction is available only after a validunit has been selected.

    To display results using the Find All function

    1 From the Editmenu, select Find All.

    2 In the dialog box, enter the desired signal or block name.

    3 Select Findto display the results.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    61/134

    GEH-6126CVol I HMI Operators Guide Chapter 3 Display and Control (Command) Programs 3-9

    The Find All Resultsdialog box contains four columns, as follows:

    The first column displays the rung number where the rung was found.

    The second column displays the segment name.

    The third column displays the rung type.

    The fourth column displays how the signal is used in the rung.

    To open a segment from the Find All results with the desired rungdisplayed

    Double-click on the rung number,

    -Or-

    Highlight the rung number and click the Gotobutton.

    NoteThe Find All Resultsdialog box remains open until you select theClosebutton or change units.

    Viewing Tabular Data

    Viewing tabular data can be useful when studying the behavior of a BBL with

    automatic parameters.

    The Dynamic Rung Display allows you to launch the Demand Display to view RLDelements, Big Block and Primitive passed parameters, and Big Block automatic

    parameters. The data is in tabular form ( Refer to figure Viewing Tabular Data).

    NoteThe Demand Displayis a separate program outside of the Dynamic Rungdisplay.

    Current rung

    Tabular Data fo

    current rung

    Viewing Tabular Data

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    62/134

    3-10 Chapter 3 Display and Control (Command) Programs GEH-6126CVol I HMI Operators Guide

    Viewing Sequencing Information - Mark VI

    The sequencing running in a Mark VI controller is viewed using the ControlSystem Toolboxprogram. This is the same program used to create and edit thesequencing, but changes to the sequencing are only allowed if the user is running at a

    suitable privilege level. At the lowest privilege level the user can view the

    sequencing overlaid with the current values from the controller.

    NoteRefer to Control System Toolbox for a Mark VI Turbine Controllerfor more

    information.

    When a controller is configured and downloaded, the live signal values can beviewed. This section defines how to go online to monitor these values and certain

    Summary Views when the controller is being monitored. These views are displayed

    when the Trackingbutton is on and an item is selected in the Outline View.

    NoteRefer to Toolbox Documentationfor more information.

    Typically toolbox opens the controller at a privilege level

    of 0, which permits Read Only functions. Operators

    typically run using this lowest privilege level to preventinadvertent changes to the controller.

    To open the Toolbox window for the Mark VI

    1 From the Start menu, select Programs, GE Control SystemSolutions, then Control System Toolbox.

    Or

    From the Windows desktop, click the Control System Toolbox icon.The toolbox Work Areadisplays an empty window until a device is created oropened.

    2 From the Filemenu, select Opento open a previously saved configuration file.

    3 Click the Tracking button to turn tracking on.

    4 Click the Go Online/Offline button.

    5 From the Outline View, select the item of interest. It appears in the SummaryView with live signal values.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    63/134

    GEH-6126CVol I HMI Operators Guide Chapter 3 Display and Control (Command) Programs 3-11

    Toolbar

    TrackingButton FinderbuttonGo On/

    Offline

    Outline

    View

    SummaryView

    Signal Connections Privilege Level Verify these fields

    are green or incorrect

    data may be

    presented.

    Summary View See Mark VI Logic

    Forcing for changing

    signal values

    Live signal values

    To find all occurrences of a control signal

    1 From the Toolbox toolbar, click the Finderbutton.

    2 From the Finder dialog box, type or select the control signal from the Text drop-down list and click Find.

    3 From the Contextwindow click on a signal location to go to that signallocation in the Summary View. A signal marked with an * is the locationwhere the signal is written.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    64/134

    3-12 Chapter 3 Display and Control (Command) Programs GEH-6126CVol I HMI Operators Guide

    Always On Top

    pin. Clicking

    outside the Finder

    Window will close

    it.

    Gotobutton will

    go to the

    highlighted

    location.

    Finderbutton willhide the tabs.

    Signal name

    Asterisk (*)

    denotes

    location where

    signal is

    written.

    Output View with

    all locations of

    the signal.

    Tabs

    Select Unit for

    location of

    signal.

    Always On

    Top pin.

    Clicking outside

    the Finder

    Window will notclose it.

    Finderbutton will

    show/hide the tabs.

    Output View

    with a list of all

    locations of the

    signal.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    65/134

    GEH-6126CVol I HMI Operators Guide Chapter 3 Display and Control (Command) Programs 3-13

    Location

    where

    signal is

    written to.

    Location of

    signal in outline

    view.

    Click To

    If this pushpin is displayed, the Finder Window closes whenever the area outside the FinderWindow is clicked. Search information cleared from the Finder Window will be lost. Click thepushpin to keep the Finder Window on top of the Device Window in toolbox. The buttonchanges to the button displayed below.

    This pushpin is displayed when the pushpin (described previously) is clicked. The FinderWindow remains open when this button is displayed even when working in another toolboxwindow.

    The Goto button is enabled only after a signal location is highlighted in the Outline View byclicking on the signal. If the Goto button is clicked, Finder goes to the signal location in thetoolbox project.

    This button is not to be confused with the similar button on the toolbox toolbar. If this button isclicked it hides the Finder Window tabs. If it is clicked again the tabs are displayed.

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    66/134

    3-14 Chapter 3 Display and Control (Command) Programs GEH-6126CVol I HMI Operators Guide

    Viewing Trip Information

    Trips are defined as the unplanned (usually not requested) shutdown of the turbine

    while the unit is running. A normal shutdown is not considered a trip.

    Viewing Trip Information - Mark IV

    An HMI has no Mark IV trip information display capability. A Trip Display isavailable from the panel-mounted Operator Interface.

    NoteRefer to GEK-83865and GEK-83866.

    Viewing Trip Information Mark V and Mark V LM

    Trip information is automatically gathered by the HMI from the controller. The last

    ten trips are stored on the HMI and can be viewed by using the Trip Log Viewer.

    The information about the last trip can be manually uploaded at any time, or thecurrent accumulated data can be uploaded even without a trip. The information is

    viewed using Trip History.

    Mark V trip history information about the last trip is stored in the controller, and is

    lost if the controller is reset or rebooted. The HMI runs the automatic collection scantypically every five minutes, but the trip information can be uploaded manually

    before the controller is reset or rebooted.

    Mark V LM trip history information is stored in non-volatile memory and is not lost

    if the controller is reset or rebooted.

    Select

    unit

    Trip History

    Manual trip log

    collection.

    Trip Log Viewer

    Automatic trip log

    collection.

    Starting Trip History or Trip Log Viewer

  • 8/10/2019 5 - Geh-6126c_vol_i Hmi Manual

    67/134

    GEH-6126CVol I HMI Operators Guide Chapter 3 Disp