46927549 ASPE Sump Pump Sizing
-
Upload
goldenbluewizard -
Category
Documents
-
view
137 -
download
18
Transcript of 46927549 ASPE Sump Pump Sizing
![Page 1: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/1.jpg)
Sewage & Sump PumpsSystem Design
andEquipment Selection
By: Bill KapanenCalifornia Hydronics Corp
www.calhydro.com [email protected]
NorCal ASPE
Sept 9th 2008
![Page 2: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/2.jpg)
• Section 1: Centrifugal Pumps
• Section 2: System Sizing & Selection
• Section 3: Pump Stations
Seminar Overview
![Page 3: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/3.jpg)
Rotating
RestingPressure
HighVelocity
At Rest
LowVelocity
IncreasedPressure
Operation of Centrifugal Pumps
![Page 4: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/4.jpg)
Pump Impellers
Narrow
Wide
![Page 5: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/5.jpg)
Impeller Vanes
![Page 6: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/6.jpg)
Sanitary vs. Storm Pumps
5-VaneImpeller
2-VaneImpeller Sewage
Application
Clean WaterApplication
![Page 7: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/7.jpg)
Effluent/Storm Pumps
![Page 8: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/8.jpg)
Ball bearing
Sleave bearings
OverheadClearance
Sewage Pumps
![Page 9: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/9.jpg)
Grinder Pump
Solids reduced to 3/8” dia
![Page 10: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/10.jpg)
Outline: Section 2
• System Sizing & Selections:
– Sewage System
– Storm System
![Page 11: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/11.jpg)
Sanitary System• California Plumbing Code (CPC) Chapter 7
– Wastewater Fixture Units• Table 7-3: Drainage Fixture Unit Values
– Hunter Curves• Total Flow, Appendix A (A-2 & A-3)
– Pipe Sizing• Scouring Velocity
– 2 ft/sec minimum (to prevent sedimentation)– 8 ft/sec maximum
• Slope– ¼” Standard
• Invert– Pump Sizing– Duplex Requirements
![Page 12: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/12.jpg)
5.04.0Urinal, 1.0 GPF
1.01.01.01.01-1/4”Lavatory, single
2.02.02.01-1/2”Laundry Sink, 1 or 2 compartments
2.02.02.01-1/2”Kitchen Sink, domestic, with grinder
0.0Food Drain, emergency
3.02”Food-waste-grinder, commercial
0.51-1/4”Drinking Fountain or Watercooler
6.04.03.03.03”Water Closet, 1.6 GPF Gravity Tank
2.02.02.01-1/2”Dishwasher, domestic
1.01-1/4”Dental Unit, cuspidor
3.03.03.02”Clothes Washer, domestic
6.03”Clinical Sink
1.01.01-1/4”Bidet
3.03.01-1/2”Bathtub or Combination Bath/Shower
2.01.01.01-1/2”Bar Sink
Heavy-Use Assembly
General Use
3 or more Dwellings
Individual Dwelling
PublicPrivateMin. Size Trap and Trap ArmIndividual Fixtures
UPC Table 7-3: Sample
![Page 13: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/13.jpg)
Dem
and
GPM
100
80
60
40
20
0 20 40 60 80 100 120 140 160 180 200 220 240
1
2
1 - Flush Valve Curve
2 - Flush Tank Curve
Fixture Units
“Hunter” Curves for Total Load
![Page 14: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/14.jpg)
Fixture Units
Dem
and
GPM
500
400
300
200
100
0 500 1000 1500 2000 2500 3500
1
2
“Hunter” Curves for Total Load
![Page 15: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/15.jpg)
Pipe Sizing• Fluid Velocity Limitations
– 2 ft/sec minimum (Scouring Velocity)• EPA Title 35, Subtitle C, Section 370.470.1
– 8 ft/sec maximum (Erosion Prevention)
– Optimum velocity range = 3.5 to 5 ft/sec• Reduces maintenance costs and prevents sedimentation• “Criteria for Sewage Works Design” C2-3.2
– Minimum pipe size of 3” (Raw Sewage)
![Page 16: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/16.jpg)
Pipe Sizing
• Pipe Slope
– Plumbing Code Requirements• CPC 708.0: Grade of Horizontal Draining Piping
– Smaller than 4” pipe: Not less than ¼” per foot, or 2%– 4” pipe or larger: 1/8” per foot, or 1% when first approved
by the authority having jurisdiction.
– ¼” per foot standard
![Page 17: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/17.jpg)
Pipe Sizing
• Invert Location
– Result of Slope Requirements
• Affects Depth of Wet Pit (Basin)
• Limits Maximum Water Level
![Page 18: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/18.jpg)
Pump Sizing
Pump Selection Considerations:1. Flow Rate (Q)2. Size of Pipe and Pump Discharge
• Solid Size3. Total Dynamic Head (TDH)4. Type of Pump
• Submersible, Vertical, Grinder
![Page 19: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/19.jpg)
Pump Sizing
• Section 710.3 CPC*: Sewage Ejectors
– Sewage Ejectors (710.3.1): Minimum pump capacity = 20 GPM
– Sewage Ejectors (710.3.3) : Must pass 2”diameter solid ball & pump discharge requires backwater and gate valves with minimum size of 3” in diameter
– Grinder pumps (710.12) may be used * CPC= 2007 California Plumbing Code
![Page 20: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/20.jpg)
Pump Sizing
• Select Pipe and Pump Discharge Size
For Rangeof Q =
18 - 85 gpm45 - 180 gpm80 - 320 gpm180 - 700 gpm
UsePipe Size
2 inch3 inch4 inch6 inch
Note: Maintains velocity of 2 - 8 feet per second
![Page 21: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/21.jpg)
Pump Sizing
• Total Dynamic Head (TDH)
1. Static Head
2. Friction Loss through piping + valves
3. Back Pressure
![Page 22: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/22.jpg)
Pump Sizing
• Type of Pump
– Ease of maintenance
– Explosion proof requirements
– Size and depth of basin
– Size of solids vs. size of pipe
![Page 23: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/23.jpg)
Duplex Requirements
• Section 710.9 (CPC) Duplex Equipment:
– Any “public use” occupancy shall be provided with dual pumps.
– Pumps to be arranged to function alternately in normal use and independently in case of overload or mechanical failure.
![Page 24: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/24.jpg)
Storm System
• Storm Drainage (CPC) Chapter 11– Total Flow
• Appendix D• No less than 15 GPM (CPC1101.5.3)
– Pipe Sizing• 1 ½” minimum discharge (CPC1101.5.3)
– Pump Sizing– Recommend Duplex System– Combining Systems
![Page 25: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/25.jpg)
Total FlowCalifornia Plumbing Code (CPC)
D1: Roof DrainageTable D-1: Maximum Rates of Rainfall for Various Cities
Anchorage, AK 0.6 0.006San Francisco, CA 1.5 0.016Boise, ID 1.0 0.010Billings, MT 1.8 0.019Reno, NV 1.2 0.012Portland, OR 1.3 0.014Seattle, WA 1.0 0.010
City, State Inches/Hr. GPM/SqFt.
![Page 26: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/26.jpg)
Total Flow
• Section 1101.5.3 CPC: Subsoil Drains
– Sized for all calculated area
– Minimum pump capacity of 15 GPM
![Page 27: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/27.jpg)
Pump Sizing
Pump Selection Considerations:1. Flow Rate (Q)2. Size of Pipe and Pump Discharge
• Solid Size3. Total Dynamic Head (TDH)4. Type of Pump
• Submersible, Vertical, Grinder
![Page 28: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/28.jpg)
Combining Systems
• Section 1104.3 CPC: Combining Storm with Sanitary Drainage
– Sanitary and storm must be separated
![Page 29: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/29.jpg)
Outline: Section 3
• Pump Stations– Basin Selection and Sizing– Level Detection– Control Panel– Slide Rails– Basin Cover– Discharge Piping
![Page 30: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/30.jpg)
• Epoxy Lined Steel
• Cement-pre-cast, water pipe
• Fiberglass
• Cast Iron
Basin Construction
![Page 31: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/31.jpg)
Sump Construction
• Section 710.8 CPC: Drainage of Fixtures
– Sumps shall be watertight and shall be constructed of concrete, metal, or other approved materials.
– Metal tanks shall be treated internally and externally to resist corrosion.
![Page 32: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/32.jpg)
Basin Sizing
FIRST – What is the invert of the inlet pipe?
CPC 710.9: “The lowest inlet shall have a minimum clearance of 2” from the high water, or starting level, of the sump.”
Inlet
![Page 33: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/33.jpg)
Basin Sizing
• Sizing Considerations
– Diameter to accommodate the pumps
– 3 to 6” between high water alarm and inlet
– Influential factors for depth and diameter• Building site constraints
![Page 34: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/34.jpg)
Basin Sizing
• Sizing Considerations
– Prevent Pump Short Cycling• Pump run time = 1.5 minutes (duplex)• Longer run time = Larger basin
– Recommend 10 Starts per Hour Maximum• Increased pump life• 1 start every 6 minutes• (Pump run time of 3 minutes for a simplex pump)
![Page 35: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/35.jpg)
Basin Sizing
• Pump Down Volume (V)
V = T x Q
Where (T) is the desired minimum run time and (Q) is the flow rate in GPM.
![Page 36: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/36.jpg)
Cylindrical Basin Capacities
Diameter,in.
Capacity per Ftdepth, gal
18243036424860728496
142438537795150212290375
dia.
12”
![Page 37: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/37.jpg)
Finalize Basin Depth
1. Top of Basin to Invert of the Inlet Pipe = ________ inchesCodes may specify minimum
2. Inlet to “Alarm” Float = ________ inches3 to 6 inches, Codes may specify
3. “Alarm” to “Lag” Float = ________ inches3 to 6 inches
4. “Lag” to “On” Float = ________ inches3 to 6 inches
5. Pump Down = ________ inches
6. Floor of Basin to Top of Pump Case = ________ inches2” Removal Pumps - 10 inches3” Removal Pumps - 12 inches4” Removal Pumps - 15 inches6” Removal Pumps - 19 inches Small to Medium Sized Floor Mounted Pumps - 10 inchesLarge Floor Mounted Pumps - 16 inches
Total Basin Depth ________ inches(Note: depths vary - consult pump manufacturer)
![Page 38: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/38.jpg)
Inlet at calculateddepth as required bylocal plumbing code
Finished floor level Basin
24 inch or as specified
3 to 6 in.
Pumpdown
Low waterlevel
15 inches or as requiredby pump manufacturer
SlopeInlet
Off Float
3 to 6 in.
3 to 6 in.
Alarm FloatLag FloatOn Float
Basin Elevations
![Page 39: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/39.jpg)
Basin Sizing ExampleD
eman
d G
PM
100
80
60
40
20
0 20 40 60 80 100 120 140 160 180 200 220 240
1
2
Fixture Units
• 145 Fixture Units (FU) with Flush ValvesDemand Flow (Q) = 80 GPM
![Page 40: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/40.jpg)
Basin Sizing
• Pump Down Volume (V)
V = T x Q
Where (T) is the desired minimum run time and (Q) is the flow rate in GPM.
V = 1.5 x 80 = 120 gallons
![Page 41: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/41.jpg)
Cylindrical Basin Capacities
Diameter,in.
Capacity per Ftdepth, gal
18243036424860728496
142438537795150212290375
48”
16”120 gals95 gals/ft
= 16”
![Page 42: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/42.jpg)
Finalize Basin Depth
1. Top of Basin to Invert of the Inlet Pipe = ________ inchesCodes may specify minimum
2. Inlet to “Alarm” Float = ________ inches3 to 6 inches, Codes may specify
3. “Alarm” to “Lag” Float = ________ inches3 to 6 inches
4. “Lag” to “On” Float = ________ inches3 to 6 inches
5. Pump Down = ________ inches
6. Floor of Basin to Top of Pump Case = ________ inches2” Removal Pumps - 10 inches3” Removal Pumps - 12 inches4” Removal Pumps - 15 inches6” Removal Pumps - 19 inches Small to Medium Sized Floor Mounted Pumps - 10 inchesLarge Floor Mounted Pumps - 16 inches
Total Basin Depth ________ inches(Note: consult mfgr)
12
3
3
3
16
15
52
![Page 43: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/43.jpg)
Level Detection
Low waterlevel
Inlet
Off Float
Alarm FloatLag Float
On Float
![Page 44: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/44.jpg)
Level Detection
Tethered Floats
![Page 45: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/45.jpg)
Level Detection
Pressure DiaphragmPedestal Mounted
![Page 46: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/46.jpg)
![Page 47: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/47.jpg)
Control Panel
• Pump Control Panel
– Disconnects– Starters with Overload Protection– H.O.A. Switches– Alarm Systems– Elapsed Time Meters– Lead/Lag Alternation for Duplex Systems
![Page 48: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/48.jpg)
4
3
2
1
HighLevelAlarm
LagPump
OnLeadPump
On
PumpOff
Control Panel
Pump StationControls
![Page 49: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/49.jpg)
Slide Rails
• Pump Removal System
![Page 50: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/50.jpg)
4
3
2
1
Control Panel
Inlet
Guide RailHolder
Pumps must be mounted onto a removal system to prevent entry into wet well “confined”space, as defined by OSHA.
Removal System slide rail system – allows pump removal without entry into wet well.
Removal System
![Page 51: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/51.jpg)
Basin Covers
• Covers, Frames and Hatches
– Pump Access
– Control Openings
– Discharge Openings
– Vent Openings
![Page 52: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/52.jpg)
Traffic Rated Cover
• Load Category = “H20”
– Parking Garage
– Parking Lots
– Access Roads
![Page 53: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/53.jpg)
H20 Rated Cover
• Traffic Rated Cover
– Parking Garage
– Parking Lots
– Access Roads
![Page 54: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/54.jpg)
Discharge Piping
• Section 710.6 CPC:
– Backwater valves, gate valves…unions…shall be located where they will be accessible for inspection and repair at all times….
![Page 55: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/55.jpg)
DresserCoupling
Valve Box
4”04”0
4”0
PortableHoist
Foundation
PortableHoist
MountingSocket
Inlet
Wet Well
![Page 56: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/56.jpg)
• Motor/Panel Options:
– Explosion Proof Motors
– Intrinsically Safe Control Circuits
![Page 57: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/57.jpg)
Intrinsically Safe
• Control Panel– Intrinsically safe control circuits– 9VDC Circuit inside floats
![Page 58: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/58.jpg)
Motor Options
• Moisture Sensor– Used to sense failure of mechanical seal
• Temperature Sensor– Protect motor from overheating
• Explosion Proof– Required for Division 1 applications
![Page 59: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/59.jpg)
Submersible Pump Options
![Page 60: 46927549 ASPE Sump Pump Sizing](https://reader033.fdocuments.us/reader033/viewer/2022050704/552e27014a79593c578b481d/html5/thumbnails/60.jpg)
Sewage & Sump Pumps
Thank You!
NorCal ASPE