46032-700-09.pdf

94
Motorpact IEC Instructions for use 46032-700-09F Retain for future use.

description

MV Switchgear

Transcript of 46032-700-09.pdf

Page 1: 46032-700-09.pdf

Motorpact IEC

Instructions for use

46032-700-09FRetain for future use.

Page 2: 46032-700-09.pdf

0

2 46032-700-09F.fm

Page 3: 46032-700-09.pdf

0Contents

General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Standard tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Non-greased screws and bolts . . . . . . . . . . . . . . . . . . . . . . 7

Application methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Full voltage non-reversing starter (FVNR) . . . . . . . . . . . . . . . . 9

Full voltage reversing bidirectional starter (FVR), dual voltage

transfer starter (FVS), 2-Speed, 1-Winding (2S1W), and Star

Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

2-Speed, 2-Winding (2S2W) . . . . . . . . . . . . . . . . . . . . . . . . . 11

FVNR starter with Merlin Gerin Propivar power factor

correction capacitor (PFCC) . . . . . . . . . . . . . . . . . . . . . . . . . 12

Reduced voltage soft starter (RVSS) soft start section . . . . . 13

Dual disconnect section (DDS). . . . . . . . . . . . . . . . . . . . . . . . 14

Reduced voltage autotransformer (RVAT) section. . . . . . . . . 15

Incoming cable section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

FVNR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

FVR bidirectional, FVS, 2S1W, 2S2W, and Star Delta . . . 18

Front operator panel description . . . . . . . . . . . . . . . . . . . . . . 19

Procedure pictogram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Instructions for access to the inside of the section . . . . . . . 21Accessing the busbar compartment FVNR. . . . . . . . . . . . . . . . . 21

Steps to access the busbar compartment from the

rear of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Steps to access the busbar compartment from the front

of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Accessing the MV compartment . . . . . . . . . . . . . . . . . . . . . . 22

Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Access to LV cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Accessing the medium voltage compartment FVNR . . . . . . . 23

Opening the medium voltage compartment door . . . . . . . 23

Accessing the medium voltage compartments RVAT or

RVSS soft start section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Steps to OPEN the RVAT or RVSS soft start section MV

doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Steps to CLOSE the RVAT or RVSS soft start section

MV doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Accessing the busbar compartments—RVAT or RVSS

soft start section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Steps to access the busbar compartment from the front

of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Accessing the busbar compartment—DDS . . . . . . . . . . . . . . 26

Steps to access the busbar compartment . . . . . . . . . . . . 26

Accessing the reduced voltage soft starting MV cable

connector compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Steps to access the reduced voltage soft starting MV

cable connector compartment from the front of the

enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Installation and operation recommendation . . . . . . . . . . . . . 29Switchgear aging resistance . . . . . . . . . . . . . . . . . . . . . . . . . 29

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Steps for tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Preliminary operation check . . . . . . . . . . . . . . . . . . . . . . . 30

346032-700-09F.fm

Page 4: 46032-700-09.pdf

0Contents

Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Disconnector operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Opening the disconnector. . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Closing the disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Voltage presence on MV cables . . . . . . . . . . . . . . . . . . . . . . . 35

Section equipped with VPIS voltage indicator boxes . . . . 35

Instructions for use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

MV cable test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Steps to test conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Voltage injections on MV outgoing cable heads . . . . . . . . 35

Replacing the voltage indicator box . . . . . . . . . . . . . . . . . . . . 36

Steps for removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Steps for placing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Operating the contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Steps to CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Steps to OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Removing or installing the contactor. . . . . . . . . . . . . . . . . . . . 38

Starting status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Steps to remove the contactor. . . . . . . . . . . . . . . . . . . . . . 38

Steps to install the contactor . . . . . . . . . . . . . . . . . . . . . . . 39

Back light assembly (optional) . . . . . . . . . . . . . . . . . . . . . . . . 40

Battery replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Cable earthing switch operation (optional) . . . . . . . . . . . . . . . 41

Instructions for use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Cable earthing switch operating condition. . . . . . . . . . . . . 41

Closing the cable earthing switch . . . . . . . . . . . . . . . . . . . . . . 42

Opening the cable earthing switch . . . . . . . . . . . . . . . . . . . . . 42

Removing and installing fuses . . . . . . . . . . . . . . . . . . . . . . . . 43

Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Steps to install fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Fuse tool (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Steps to install rear and middle fuses . . . . . . . . . . . . . . . . 45

Steps to install front fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Blown fuse indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Removing and installing fuses of the Merlin Gerin PFCC

inside Motorpact enclosures . . . . . . . . . . . . . . . . . . . . . . . . . 52

Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Steps to install fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Removing and installing VT primary fuses . . . . . . . . . . . . . . . 53

Steps to replace fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Steps to disassemble the fuse tube. . . . . . . . . . . . . . . . . . 53

Steps to assemble the fuse tube . . . . . . . . . . . . . . . . . . . . 53

Steps to place back into operation . . . . . . . . . . . . . . . . . . 53

Locking using padlocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Number of possible padlocks per section type . . . . . . . . . 54

Padlocking the disconnector . . . . . . . . . . . . . . . . . . . . . . . 54

Padlocking the cable earthing switch . . . . . . . . . . . . . . . . 55

Padlocking the incoming cable section doors . . . . . . . . . . 55

Locking using keylocks (optional) . . . . . . . . . . . . . . . . . . . . . . 56

Number of possible locks per section type . . . . . . . . . . . . 56

Keylocking the disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Locking the disconnector open or closed with 1 keylock. . 56

Locking the disconnector open or closed with 2 keylocks. . . 56

Locking the cable earthing switch open or closed . . . . . . . 57

FVR (full voltage reversing bidirectional) . . . . . . . . . . . . . . 58

FVS (dual voltage transfer starter) . . . . . . . . . . . . . . . . . . 59

4 46032-700-09F.fm

Page 5: 46032-700-09.pdf

0Contents

Redundant smart sequence starter . . . . . . . . . . . . . . . . . . . . 60

DDS (dual disconnect section) . . . . . . . . . . . . . . . . . . . . . . . . 61

2-Speed, 1-Winding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

2-Speed, 2-Winding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Star Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

RVAT (reduced voltage autotransformer). . . . . . . . . . . . . . . . 66

Limited duty cycle rating . . . . . . . . . . . . . . . . . . . . . . . . . . 66

Keylocks on an RVAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Keylocking with disconnector (without cable earthing

switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Keylocking (with cable earthing switch). . . . . . . . . . . . . . . 67

RVAT operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Autotransformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Relay setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Tap setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Steps to CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Steps to OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Reduced voltage soft starter (RVSS) soft start section . . . . . 70

Keylocks on an RVSS soft start section . . . . . . . . . . . . . . . . . 71

Keylocking with disconnector (without cable earthing

switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Keylocking with cable earthing switch . . . . . . . . . . . . . . . . 71

Keylocking with redundant S3 . . . . . . . . . . . . . . . . . . . . . . 71

Keylocking with redundant S3 with dual disconnect

section (DDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Removing a contactor from an RVAT or RVSS soft start

section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Preliminary steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Steps to remove a start, run, or bypass contactor . . . . . . . . . 72

Installing a contactor in an RVAT or RVSS soft start section . 73

Preliminary steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Steps to install a start, run, or bypass contactor. . . . . . . . . . . 73

Using a lift truck (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

MDT107 thermal diagnostic system (optional) . . . . . . . . . . . . 75

Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Wiring and operation for MDT107 . . . . . . . . . . . . . . . . . . . 78

Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

MDT107 module location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

MDT107 sensors location. . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

Setting the temperature rise thresholds. . . . . . . . . . . . . . . 80

Setting the ambient temperature correction . . . . . . . . . . . 81

Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82Preventative maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 82

Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . 84

Inspecting the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

546032-700-09F.fm

Page 6: 46032-700-09.pdf

0

6 46032-700-09F.fm

Page 7: 46032-700-09.pdf

0General information

Standard tightening torquesNon-greased screws and bolts

Application methods The conical washers placed on the external sides of the busbars

ensure better distribution of stress regarding bolts tightened to the

recommended torques.

Marking It is strictly forbidden to walk on

the parts bearing this marking.

It is strictly forbidden to remove

the parts bearing this marking

when the equipment is

energized.

Screw Busbar torque in N•m Mech. torque in N•mØ 6 — 10

Ø 8 28 20

Ø 10 50 35

Ø 12 75 55

Ø 14 — 120

746032-700-09F.fm

Page 8: 46032-700-09.pdf

0

8 46032-700-09F.fm

Page 9: 46032-700-09.pdf

0General description

Full voltage non-reversing starter (FVNR)

A. MV power cable entry plate (optional

upper entry)

B. internal arc vent cover (optional)

C. LV control cable entry plate

D. LV cabinet door

E. Diagnostic thermal detection module

(optional)

F. Operation and locking panel

G. VPIS indicator box (optional)

H. Interlock shuttle

I. Blown fuse indicator (optional)

J. Cable earthing switch, load connection

lug pads

K. MV power fuses

L. MV compartment door

M. Vacuum contactor

N. Fuseholder, control power transformer

(CPT), and voltage transformer (VT)

O. LV inter-unit top wireway

P. Main busbar barrier

Q. Disconnector

R. Main busbars

S. Main earthing terminal

T. Surge arresters (optional)

U. Current transformers (CTs)

V. MV cable support clamps (bottom entry)

W. Voltage transformer (VT)

X. LV cable entry plate (bottom entry)

Load connection lug pad not required for

smart start sequence application.

B

C

D

E

F

G

J

K

L

M

O

P

R

T

S

U

A

V

W

NX

I

Q

H

946032-700-09F.fm

Page 10: 46032-700-09.pdf

0General description

Full voltage reversing bidirectional starter (FVR), dual voltage transfer starter (FVS), 2-Speed, 1-Winding (2S1W), and Star Delta

A. MV power cable entry plate

B. Internal arc vent cover (optional)

C. LV control cable entry plate

D. LV compartment door

E. Diagnostic thermal detection module

(optional)

F. Operation and locking panel

G. VPIS indicator box (optional)

H. Interlock shuttle

I. Blown fuse indicator (optional)

J. Cable earthing switch, load connection

lug pads

K. MV power fuses

L. MV compartment door

M. See table below

N. See table below

O. Fuseholder, control power transformer

(CPT), and voltage transformer (VT)

P. LV inter-unit top wireway

Q. Main busbar barrier

R. Disconnector

S. Main busbars

T. Main earthing terminal

Starter Type M NFVR bidirectional Forward contactor Reverse contactor

FVS dual voltage transfer starter Main contactor Soft start contactor

2S1W Slow-speed contactor Shorted contactor

Star Delta Star-connection contactor Delta-connection contactor

BC

D

E

FG

J

K

L

M O

P

R

T

S

A

N

I

Q

H

10 46032-700-09F.fm

Page 11: 46032-700-09.pdf

0General description

2-Speed, 2-Winding (2S2W)

A. MV power cable entry plate

B. Internal arc vent cover (optional)

C. LV control cable entry plate

D. LV compartment door

E. Diagnostic thermal detection module

(optional)

F. Operation and locking panel

G. VPIS indicator box (optional)

H. Interlock shuttle

I. Blown fuse indicator (optional)

J. Cable earthing switch load connection

lug pads (cables for fast speed winding)

K. MV power fuses

L. MV compartment door

M. Fast-speed contactor

N. Slow-speed contactor

O. Fuseholder, control power transformer

(CPT), and voltage transformer (VT)

P. LV inter-unit top wireway

Q. Main busbar barrier

R. Disconnector

S. Main busbars

T. Main earthing terminal

U. Load connection lug pads (cables for

slow speed winding)

BC

D

E

FG

JK

L

M O

P

R

T

S

A

N

I

Q

H

U

1146032-700-09F.fm

Page 12: 46032-700-09.pdf

0General description

FVNR starter with Merlin Gerin Propivar power factor correction capacitor (PFCC)

A. LV cabinet door

B. Operation and locking panel

C. MV compartment door

D. Cable earthing switch, load connection

lug pads

E. MV power fuses

F. Vacuum contactor

G. Fuseholder, control power transformer

(CPT), and voltage transformer (VT)

H. Disconnector

I. Main busbars

J. Main earthing terminal

K. PFCC fuses

L. PFCC

A

B

D

F

E

C

G

H

IJ

K

L

12 46032-700-09F.fm

Page 13: 46032-700-09.pdf

0General description

Reduced voltage soft starter (RVSS) soft start sectionA. Internal arc vent cover (optional)

B. LV control entry plate

C. MV compartment door

D. LV door

E. Human machine interface (HMI) soft start

control interface modules

F. Soft start power compartment door

G. Heater (optional)

H. LV control entry plate

I. Customer conduit wireway

J. Bypass contactor or PLC mounted

(depending on application)

K. Ground fault board (optional)

L. Terminal control board

M. Main busbar compartment

N. Main earthing terminal

O. Control power, central processing unit

(CPU) boards, RTD board (optional)

P. Main busbar access cover

Q. LV cabinet

R. Door interlock

S. Ring transformers

T. Silicon control rectifier stacks

A

B

C

D

E

F

G

I

J

K

L

M

N

O

P

Q

R

S

TS

H

1346032-700-09F.fm

Page 14: 46032-700-09.pdf

0General description

Dual disconnect section (DDS)

A. Reduced voltage MV cable entry plate

B. Internal arc vent cover (optional)

C. LV cable entry plate

D. LV cabinet door

E. Access cover plate for reduced voltage

soft starting MV cable connectors

F. Main busbar access cover plate

G. Access cover plate for reduced voltage

soft starting MV cable connectors

H. Operation and locking panel

I. MV compartment door

J. Heater (optional)

K. LV inner-unit top wireway

L. Top entry main earthing terminal

M. Reduced voltage soft starting MV cable

terminals

N. Main busbars

O. Disconnectors

P. Bottom entry main earthing terminal

AB

C

E

G

H

J

I

K

L

M

N

O

P

D

F

M

14 46032-700-09F.fm

Page 15: 46032-700-09.pdf

0General description

Reduced voltage autotransformer (RVAT) section

A. Internal arc vent cover (optional)

B. LV control cable entry plate

C. MV compartment door

D. Run contactor

E. Start contactor

F. LV door

G. Autotransformer door

H. Surge arresters

I. Main busbar access cover

J. Door interlock

K. Main busbar compartment

L. Main earthing terminal

M. Autotransformer

AB

C

D

E

F

G

JI

K

L

M

H

1546032-700-09F.fm

Page 16: 46032-700-09.pdf

0General description

Incoming cable sectionA. Internal arc vent cover (optional)

B. LV control cable entry plate

C. MV upper barrier

D. MV upper door

E. MV lower door

F. Voltage presence indicator system

(VPIS) indicator box (optional)

G. MV lower barrier

H. LV inter-section top wireway

I. Capacitive divider, VPIS (optional)

J. Surge arresters (optional)

K. Main earthing terminal

L. Main busbar lug pad

M. Earth riser connection

N. Current transformers (CTs) (optional)

O. MV cable support clamps (bottom entry)

A

B

C

D

E

O

H

I

J

K

L

M

N

F G

16 46032-700-09F.fm

Page 17: 46032-700-09.pdf

0General description

Identification

FVNRA. Name of starter or section

B. Viewing port, disconnector

C. Characteristics,

designations, and serial

number

D. Interlock shuttle

E. Status window, blown fuse

indicator (see page 50)

F. Status window, cable

earthing switch (see

page 41)

G. Status window, contactor

contactor

H. Characteristics,

designations, and serial

number

I. Status indicator

A

BC

H

E

G

I

D

F

1746032-700-09F.fm

Page 18: 46032-700-09.pdf

0General description

FVR bidirectional, FVS, 2S1W, 2S2W, and Star DeltaA. Name of starter or section

B. Viewing port, disconnector

C. Characteristics, designations, and

serial number

D. Interlock shuttle

E. Status window, blown fuse

indicator (see page 50)

F. Status window, cable earthing

switch (see page 41)

G. Status window, contactor

Contactor

H. Characteristics, designations, and

serial number

I. Status indicator

A

BC

H

E

G

I

D

F

18 46032-700-09F.fm

Page 19: 46032-700-09.pdf

0General description

Front operator panel description

A. Contactor control panel

B. Voltage presence indicator system

(VPIS)

C. Pushbutton for back light (optional)

D. Disconnector viewing port

E. Disconnector status indicator

F. Location for cable earthing switch

operation padlock

G. Disconnector operating access

port

H. Cable earthing switch operating

access port

I. Location for disconnector operation

padlock

J. Procedure pictogram

K. Interlock shuttle

Procedure pictogramSteps for closing of circuit1. MV compartment door position, close

and latch

2. If the cable earthing switch is not

supplied, skip to step 5. If the cable

earthing switch is supplied, move the

cable earthing switch access port from

the locked to unlocked position. This

requires the interlock shuttle to be in

the right-hand position. See “Cable earthing switch operation (optional)”.

3. OPEN or un-earth the cable earthing

switch

4. Move the cable earthing switch access

port from the unlocked to locked

position; then move the interlock shuttle

from the right-hand to left-hand position.

See “Disconnector operation”.5. Move the disconnector access port

from the locked to unlocked position

6. CLOSE the disconnector

7. Move the disconnector access port

from the unlocked to locked position

8. CLOSE the contactor

A

B

C

D

EFH

I

G

J

K

1946032-700-09F.fm

Page 20: 46032-700-09.pdf

0

20 46032-700-09F.fm

Page 21: 46032-700-09.pdf

0Instructions for access to theinside of the section

2146032-700-09F.fm

Accessing the busbar compartment FVNR

Steps to access the busbar compartment from the rear of the enclosure

Steps to access the busbar compartment from the front of the enclosure

All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

Always remove all power from the section and use a properly rated testing device to confirm there is no voltage present.

Always look through the rear viewing window to verify that the MV compartment door is OPEN, before removing the MV cable compartment cover.

❏ Remove the upper MV

cable compartment cover.

4 M10x20 screws.

❏ Remove the rear main

busbar cover. 4 M10x20 screws.

❏ The busbar

compartment is

now accessible.

❏ Remove the main busbar access cover in the

floor of the LV cabinet. 8 M10x20 screws.❏ The busbar compartment is

now accessible.

Main busbar

access cover

After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 35 N•m.

Page 22: 46032-700-09.pdf

0Instructions for access to theinside of the section

Accessing the MV compartment (cables, busbars, CT, cable earthing switch, surge arresters, fuses, contactor, transformers)

Safety rules See “Accessing the medium voltage compartment FVNR” and “Accessing the medium voltage compartments RVAT or RVSS soft start section”.

cables See "cable connections" in the installation instruction guide.

busbars See "installing busbars" in the installation instruction guide.

CT (current transformer) See “General description”for

the mounting locations.

cable earthing switch See “Cable earthing switch operation (optional)”.

surge arresters See “General description”for

the mounting locations.

fuses See “Removing and installing fuses”.

contactor See “Removing or installing the contactor”.

transformers See “General description”for

the mounting locations.

Access to LV cabinet (instrument components, relays, and communication modules)

See "accessing the low voltage compartment" in the

installation instruction guide.

All operations described

hereafter must be carried

out in compliance with the

safety standards in force,

under the responsibility of a competent person.

All operations described

hereafter must be carried

out in compliance with

the safety standards in

force, under the responsibility of a competent person.

22 46032-700-09F.fm

Page 23: 46032-700-09.pdf

0Instructions for access to theinside of the section

2346032-700-09F.fm

Accessing the medium voltage compartment FVNRMotorpact™ motor starters are shipped with the disconnector in the

earthed/OPEN position.

The disconnector must be in the earthed/OPEN position to open the

medium voltage compartment door.

See “Disconnector operation”.

The cable earthing switch (optional) must be in the earthed/CLOSED

position to open the medium voltage compartment door.

See “Cable earthing switch operation (optional)”.

Opening the medium voltage compartment door

Accessing the cable compartment FVNR

Always look through the viewing window to verify the actual position of the disconnector switch blades before trying to open the MV compartment door.

Door closed, rotate handle 90° Door openHandle rotated

All operations described

hereafter must be

carried out in

compliance with the

safety standards in

force, under the responsibility of a competent person.

Always remove all power from the section and use a

properly rated testing device to confirm there is no voltage present.

Always look through the rear viewing window to verify that

the MV compartment door is OPEN, before removing the MV cable compartment cover.

MV compartment

door viewing

window

MV

compartment

door

(opened 90°)

Steps to access the cable compartment of an FVNR section

❏ Verify through the rear

viewing window that the MV

compartment door is OPEN,

the power has been removed

from the section, and the

load connections have been

properly earthed.

❏ Remove the lower MV cable

compartment cover.

4 M10x20 screws.

tightening torque: 35 N•m

After installation or maintenance, ensure all covers are replaced using the original hardware.

Rear view

Page 24: 46032-700-09.pdf

0Instructions for access to theinside of the section

24 46032-700-09F.fm

Accessing the medium voltage compartments RVAT or RVSS soft start section

The contactor and autotransformer compartments of an RVAT and the

contactor and soft start power compartments of an RVSS soft start

section are key interlocked with the main contactor disconnector or the

cable earthing switch, if supplied. If the optional dual disconnect section

(DDS) is being used, the RVSS will also be key interlocked with the

DDS.

For a description of key interlock operation, refer to the “Keylocks on an RVAT”or “Keylocks on an RVSS soft start section”section.

Steps to OPEN the RVAT or RVSS soft start section MV doors

❏ OPEN the middle LV doors to gain access to the key interlock.

❏ Insert and turn the interlock key to release the door latching mechanism.

❏ Insert the disconnector operating handle as shown below. Rotate

counter-clockwise to release the MV doors.

Steps to CLOSE the RVAT or RVSS soft start section MV doors

❏ CLOSE all MV doors. For RVAT, right side doors must be closed

before the left side doors.

❏ Push the release button next to the operator port to latch the MV doors.

❏ Insert the disconnector operating handle as shown below. Rotate

clockwise to lock the MV doors.

❏ Turn the interlock key to lock the door latching mechanism. Remove the

key, and return it to disconnector or cable earthing switch, if supplied.

❏ Close and latch the middle LV doors.

Door latch keylock

Operating handle

Door latch keylock

Operating handle

Release

button

Page 25: 46032-700-09.pdf

0Instructions for access to theinside of the section

Accessing the busbar compartments—RVAT or RVSS soft start section

The RVAT or RVSS soft start section main busbar compartment can be

accessed only from the front due to the cable arrangement in the rear of

these sections.

Steps to access the busbar compartment from the front of the enclosure

❏ Remove the M6x10 screws holding the main busbar access covers.

The RVAT shown will have 2 covers. RVSS soft start section will have

only 1 cover.

Main busbar access cover Main busbar

access cover

❏ The busbar compartment is now accessible.

After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 6 N•m max.

2546032-700-09F.fm

Page 26: 46032-700-09.pdf

0Instructions for access to theinside of the section

Accessing the busbar compartment—DDS

The DDS main busbar compartment can be accessed only from the

front due to the busbars being enclosed in a busbar tunnel.

Steps to access the busbar compartment

❏ Remove the M10x20 screws holding the main busbar access covers.

Main busbar access cover

❏ The busbar compartment is now accessible.

After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 25 N•m max.

26 46032-700-09F.fm

Page 27: 46032-700-09.pdf

0Instructions for access to theinside of the section

Accessing the reduced voltage soft starting MV cable connector compartment

The reduced voltage MV cable connector compartment can be

accessed from the front or the back of the unit. To access this

compartment from the front of the unit, refer to the images below.

Steps to access the reduced voltage soft starting MV cable connector compartment from the front of the enclosure

❏ Remove the M10x20 screws holding the access cover.

Reduced voltage soft starting MV

cable connector access cover

❏ The compartment is now accessible.

After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 25 N•m max.

2746032-700-09F.fm

Page 28: 46032-700-09.pdf

0

28 46032-700-09F.fm

Page 29: 46032-700-09.pdf

0Installation and operationrecommendation

Switchgear aging resistance

The switchgear’s resistance to

aging depends upon 3 factors.

■ The necessity of correct

implementation of

connections:

New cold-shrink or slip-on

technology offers ease of

installation.■ The effect of the relative

humidity factor:

Heating resistor installation

is essential in climates with a

high rate of relative humidity

and with significant

temperature differentials.

■ Ventilation control:

Provide area ventilation,

heating, and air conditioning

to maintain the ambient

temperature around the

equipment between - 5 °C

and 40 °C.

Operation It is strongly advised to periodically carry out(minimum every 2 years) a few operation cycles on operating devices.

Outside normal conditions of use (between - 5 °C and 40 °C, absence of dust, corrosive gas, etc.), it is recommended to verify the steps to be taken in order to ensure correct functioning of the installation. Contact the Schneider Electric Service Center for help to do so.

The Service Center is able to

assist you at any time to offer

you:

■ installation diagnostics.

■ suitable maintenance

operations.

■ maintenance contracts.

■ adaptations.

2946032-700-09F.fm

Page 30: 46032-700-09.pdf

0Installation and operationrecommendation

Steps for testsSafety rulesCarry out electric tests in

compliance with the standards

in force.

It is recommended that prior to

start-up and after maintenance

on this equipment, the 1 minute

dielectric test is always

performed. See "steps to be taken for test and inspections" in the installation

instruction guide.

Preliminary operation check

Verify that a 1 minute dielectric test has been performed recently. If a

dielectric test is required, see "hi-pot dielectric test" in the installation instruction guide.

Operate the disconnector a minimum of 5 operations. See “Disconnector operation”

Operate the cable earthing switch (if supplied) a minimum of 5

operations. see “Cable earthing switch operation (optional)”With the disconnector in the CLOSED position, verify the MV

compartment door cannot be opened.

If supplied, verify all key interlocks function properly according to

the drawing.

Verify that all low voltage plugs are connected.

Verify all tools and/or hardware have been removed from the MV

compartment.

Replace all devices, doors, and covers with their original

mounting hardware.

All operations described

hereafter must be carried

out in compliance with the

safety standards in force,

under the responsibility of a competent person.

If any operation checks provide unacceptable results, DO NOT ENERGIZE THE EQUIPMENT. Contact your local field sales

office or distributor.

30 46032-700-09F.fm

Page 31: 46032-700-09.pdf

0

3146032-700-09F.fm

Page 32: 46032-700-09.pdf

0Operating instructions

Disconnector operation

Interlock shuttle

An interlock shuttle is provided

on all FVNR starters with a

cable earthing switch.

This shuttle must be in the

left-hand position to operate the

disconnector.

Always look through the viewing window to verify the actual

position of the disconnector switch blades.

Operating

handle

The disconnector operating

handle is stored on the right-

or left-hand end sheet.

DescriptionThe disconnector is the isolation means between the main busbar

and the line side of the primary fuses. When the disconnector is

in the earthed or OPEN position, it disconnects or isolates the

contactor from the supply voltage.

Moving the disconnector to the OPEN position earths the switch

blades and the load side power circuit down to the line side of

the contactor.

In the earthed/OPEN position, the disconnector does not earth the load side of the contactor, cables, or any other components that are connected to the load side of the contactor.

OPEN (earth) CLOSED

switch blades

32 46032-700-09F.fm

Page 33: 46032-700-09.pdf

0Operating instructions

Opening the disconnector

The interlock system requires the following conditions to be met before the disconnector can be OPENED:

■ If a cable earthing switch is supplied, the interlock shuttle must

be in the left-hand position to allow disconnector operation.

■ The optional cable earthing switch must be in the

OPEN position.

■ The contactor must be in the OPEN position.

■ The MV compartment door must be closed and latched.

■ The cable earthing switch access port, if equipped, must

be closed.

When the conditions above

have been satisfied:

❏ Slide the disconnector

operating access port to the

right to open.

❏ Insert the operating handle,

and rotate counter-clockwise

to open or earth.

After putting the disconnector

in the OPEN position:

❏ Remove the operating

handle.

❏ Slide the disconnector

operating access port to the

left to close. If the access

port cannot be closed, open

the disconnector further,

then close the access port.

❏ After completely opening the

disconnector and closing the

cable earthing switch, if

supplied, the MV

compartment door can be

opened.

Open disconnector access port

Position

indicator

OPEN

Closed position

Open position

Position

indicator

CLOSED

3346032-700-09F.fm

Page 34: 46032-700-09.pdf

0Operating instructions

Closing the disconnector

The interlock system requires the following conditions to be met before the disconnector can be CLOSED:

■ If a cable earthing switch is supplied, the interlock shuttle must

be in the left-hand position to allow disconnector operation.

■ The optional cable earthing switch must be in the

OPEN position.

■ The contactor must be in the OPEN position.

■ The MV compartment door must be closed and latched.

■ The cable earthing switch access port, if equipped, must

be closed.

When the conditions above

have been satisfied:

❏ Slide the disconnector

operating access port to the

right to open.

❏ Insert the operating handle,

and rotate clockwise to

close.

After putting the disconnector

in the CLOSED position:

❏ Remove the operating

handle.

❏ Slide the disconnector

operating access port to the

left to close. If the access

port cannot be closed, close

the disconnector further,

then close the access port.

❏ After the disconnector is

completely closed, the

contactor can be closed.

Open disconnector access port

Position

indicator

CLOSED

Open position

Closed position

Position

indicator

OPEN (earth)

34 46032-700-09F.fm

Page 35: 46032-700-09.pdf

0Operating instructions

Voltage presence on MV cablesSection equipped with VPIS voltage indicator boxes

VPIS: The Voltage Presence

Indicating System is a box with

three integrated lamps.

The definite "voltage presence"

indication is ensured on the

voltage range stipulated by

IEC 61958.

Instructions for use

The indication of a VPIS alone

will not ensure the system is

de-energized. If the operation

rules require this, then suitable

voltage detectors in compliance

with IEC 61243 must be used.

A. Voltage presence indicator

light (1 for each phase)

B. Connection points enabling

a phase concordance unit to

be connected.

Once the cables are energized,

the voltage indicator lights

should illuminate.

MV cable test

Steps to test conditions ❏ Open the cable earthing

switch.

❏ The cables are connected to

injection tools.

Voltage injections on MV outgoing cable heads

❏ Check voltage absence. The

voltage indicator lights are

not illuminated.

❏ Close the cable earthing

switch. See “Closing the cable earthing switch”.

VPIS must not be used as a VDS (Voltage Detecting

System).

Use a properly rated testing device to confirm there is no voltage present.

A

B

3546032-700-09F.fm

Page 36: 46032-700-09.pdf

0Operating instructions

❏ Open MV compartment

door. See “Accessing the medium voltage compartment FVNR”.

❏ Connect the voltage

injection circuit to the

cable lugs.

❏ Open the cable earthing

switch. See “Cable earthing switch operation (optional)”then carry out

the tests.

At the end of the tests:

❏ Close the cable earthing

switch.

❏ Remove the accessories.

Replacing the voltage indicator boxSteps for removing

❏ Remove the 2 fastening

screws (A) from the voltage

indicator box.

❏ Remove the voltage

indicator box, and

disconnect the connector.

Steps for placing ❏ Verify that the characteristics

label (B) on the new box

corresponds to the rated

voltage of your network.

example: 3 kV to 7.2 kV

❏ Place the new voltage

indicator box in the reverse

order of removal.

tightening torque: 0.1 mdaN

Cable lugs

All operations described

hereafter must be carried

out in compliance with the

safety standards in force, under the responsibility of a competent person.

Caution: a static voltage will be present if the indicator box is replaced while the equipment is energized.

A

B

36 46032-700-09F.fm

Page 37: 46032-700-09.pdf

0Operating instructions

Operating the contactor

For more information, see Schneider Electric bulletin 46032-700-02 (200 A / 400 A / 450 A vacuum contactors).

Description

The contactor is typically electrically maintained. However, an optional

mechanical latching mechanism is added to latched contactors to lock the

contactor CLOSED. This latched contactor can be opened at the operator

panel or by pressing a reset button located on the MV compartment door.

Steps to CLOSE❏ OPEN or un-earth the cable earthing switch, if supplied. See “Cable

earthing switch operation (optional)”.❏ CLOSE the disconnector. See “Disconnector operation”.❏ Press the START or CLOSE pushbutton on the operator panel.

Steps to OPEN❏ Press the STOP or OPEN pushbutton on the operator panel. A

latched contactor can also be opened by pressing the reset button

on the MV compartment door.

All operations described

hereafter must be carried

out in compliance with the

safety standards in force,

under the responsibility of a competent person.

Contact fingers

Control terminal

blocks

Vacuum interrupter

Auxiliary contacts

Truck handle

Status indicator

Operator

panel

Status

window

Reset

button

3746032-700-09F.fm

Page 38: 46032-700-09.pdf

0Operating instructions

Removing or installing the contactorStarting status❏ Cubicle + contactor

Steps to remove the contactor

❏ OPEN the contactor by

pressing the STOP or OPEN

pushbutton on the operating

panel.

For a mechanically-latched

contactor, verify that the

contactor is in the OPEN

position. If necessary, press

the trip button.

❏ OPEN the disconnector to

the earthed position. See

“Disconnector operation”.❏ CLOSE the cable earthing

switch, if supplied, to the

earthed position. See “Cable earthing switch operation (optional)”.

❏ Open the MV compartment door.

See “Accessing the medium voltage compartment FVNR”.

❏ Pull the contactor rail down. This will

disengage the contactor from the line

and load busbar connections.

❏ Roll the contactor out of the

enclosure. Lift to remove (25 kg).

38 46032-700-09F.fm

Page 39: 46032-700-09.pdf

0Operating instructions

Steps to install the contactor

❏ Verify the disconnector is in

the OPEN and earthed

position. See “Disconnector operation”.

❏ If supplied, verify the cable

earthing switch is in the

CLOSED and earthed

position. See “Cable earthing switch operation (optional)”.

❏ Open the MV compartment

door. See “Accessing the medium voltage compartment FVNR”.

❏ Pull the contactor rail down.

❏ Seat the contactor truck wheels onto the

contactor rail.

❏ By gripping the handles (A) shown,

slowly roll the contactor into the

enclosure until it reaches the wheel stop.

❏ Lift the contactor rail to the vertical

position, engaging the contactor.

A

Wheel stop

3946032-700-09F.fm

Page 40: 46032-700-09.pdf

0Operating instructions

Back light assembly (optional)

The back light assembly consists of LEDs, a pushbutton, and batteries. It is

used to help view the inside of the disconnector and the MV compartment.

When the back light pushbutton is pressed, the light illuminates.

A. The inside of the disconnector for viewing the switch blade position.

B. The inside of the MV compartment for viewing the indicators of the

cable earthing switch and the blown fuse indicator, if supplied.

Battery replacement The batteries should be replaced every 4 years to maintain proper

operation. Two AA alkaline batteries are required.

Steps for removal

❏ Remove all power from the section. See “Operating instructions”.❏ After opening the MV compartment door, remove 2 screws holding

the bottom of the operator cover to the tie channel.

❏ Open the LV door, and remove the 2 screws holding the top of the

operator cover to the operator panel. Remove the cover.

❏ The back light assembly can now be accessed to replace the batteries.

❏ Remove the batteries by pulling them straight down from their spring clips.

❏ When replacing batteries, insert the left-side battery with the

negative end nearest to the operator and the right-side battery with

the positive end nearest to the operator.

Steps to place back into operation❏ Replace the operator cover (4 M6 screws). tightening torque: 10 N•m.❏ Complete these operations in reverse order. See “Operating

instructions”.❏ Complete these electric tests in compliance with the standards

in force.

All operations described

hereafter must be carried

out in compliance with

the safety standards in

force, under the responsibility of a competent person.

Tie

channel

Operator panel

Back light pushbutton

Operator coverA

B

Left

battery

Right

battery

Negative

Positive

Front

40 46032-700-09F.fm

Page 41: 46032-700-09.pdf

0Operating instructions

Cable earthing switch operation (optional)

DescriptionThe cable earthing switch is used to earth the customer load connection cables when the switch is in the

CLOSED or discharged position. It is mechanically interlocked with the disconnector and is actuated by using

the same operating handle.

Connection to earth is accomplished when the spring operated earthing bar is connected across all three phases

of the customer load terminals.

Instructions for use

Cable earthing switch operating condition

Interlock shuttle

An interlock shuttle is provided on all

FVNR starters with a cable earthing

switch.

This shuttle must be in the right-hand

position to operate the cable earthing

switch.

The interlock system requires the following conditions to be met before

the cable earthing switch can be operated:

■ The interlock shuttle must be in the right-hand position.

■ The contactor must be in the OPEN position.

■ The disconnector must be in the DISCONNECTED and EARTHED

position.

■ The MV compartment door must be closed and latched.

?

Earthing

bar

Status

window

The indicator for the cable earthing switch can be

viewed through a status window in the MV

compartment door.

Operating

handle

Un-earthed

positionEarthed

position

The cable earthing switch

operating handle is stored on

the right- or left-hand end sheet.

The cable earthing switch has no interrupting capability and is not capable of closing on the full fault current available on the system.

When used with a power transformer, key interlocks should be used between the main secondary disconnect device and the cable earthing switch to ensure proper sequencing of operation.

4146032-700-09F.fm

Page 42: 46032-700-09.pdf

0Operating instructions

Closing the cable earthing switch

Opening the cable earthing switchThe interlock system requires the MV compartment door to be shut and

latched. See “Cable earthing switch operating condition”.

For performing cable injection testing, the cable earthing switch can be opened

with the MV compartment door open, however the cable earthing switch must

be returned to the closed position to allow the MV compartment door to be

closed. See “MV cable test”.

When the cable earthing switch

operating conditions have

been satisfied:

❏ Slide the cable earthing

switch access port down.

❏ Insert and rotate the handle

counter-clockwise

approximately 10 turns, or

until the handle stops.

❏ The mechanism makes a

sharp sound when it trips,

and the position indicator

moves upward to the

earthing position.

❏ The MV compartment door

can now be opened.

Open position

Closed position

Access port

When the cable earthing switch

operating conditions have

been satisfied:

❏ Slide the cable earthing

switch access port down.

❏ Insert and rotate the handle

clockwise approximately 10

turns to charge and latch

the mechanism back in the

open or unearthed position.

Continue rotating the

handle until it stops.

❏ The cable earthing switch

access port may now be

closed, allowing the

disconnector and the

contactor to be operated.

Closed position

Open position

Access port

42 46032-700-09F.fm

Page 43: 46032-700-09.pdf

0Operating instructions

Removing and installing fuses

An optional fuse tool is available to

help in the removal and installation of

power fuses. Contact a field sales representative or distributor. See “Fuse tool (optional)”.

Steps to remove fuses ❏ Always remove the lower end of the fuse first. Twist the fuse while

pulling the ferrule out of the lower fuse clip.

❏ Pull the fuse down to remove it from the upper fuse clip.

See “Accessing the medium voltage compartment FVNR”.

All operations described

hereafter must be carried out

in compliance with the safety

standards in force, under the responsibility of a competent person.

Always remove all power from

the section, and use a

properly rated testing device

to confirm there is no voltage present.

IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown.

4346032-700-09F.fm

Page 44: 46032-700-09.pdf

0Operating instructions

Fuse characteristics

The fuse characteristics and direction

of mounting are printed on the fuse.

When replacing the fuse, turn it so that

the label is in the front, and the striker pin is at the top.

Steps to install fuses ❏ Always insert the upper end of the fuse first. Grasp the fuse by the

upper ferrule, insert it into the upper fuse clip, and twist it while pushing

upward.

❏ Insert the lower end into the lower fuse clip.

❏ Rotate the fuse so that the label is facing the front.

All operations described

hereafter must be carried

out in compliance with the

safety standards in force,

under the responsibility of a competent person.

Always remove all power

from the section and use

a properly rated testing

device to confirm there is no voltage present.

IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown.

To ease installation,

lubricate fuse clips with

red Mobilgrease® 28.

44 46032-700-09F.fm

Page 45: 46032-700-09.pdf

0Operating instructions

Fuse tool (optional) The fuse tool is an ergonomic aid for inserting and extracting fuses in

de-energized Motorpact™ motor starters. It does not protect the

operator in any way from contacting live parts.

Steps to install rear and middle fuses

The process is the same for installing fuses in the rear and middle

fuseholders. Begin by installing the rear fuses.

NOTE: Always wear gloves when

working with fuses. The fuses could

be hot and will burn unprotected

hands. The photos on these pages

are factory demonstrations.

❏ Align the fuse tool so that the hook and the pusher are toward the

handle end of the tool.

❏ Insert the hinge in the narrow vertical space in front of the

fuseholder, between the fuse holder and the fuse tray. In some

cases, this may be a tight fit. The handle should be horizontal and

extend towards the door.

hinge

handle

lifting rod

hook

pusher

hook

pusher

handle

hinge

handle

lifting

rod

fuse

holder

fuse

tray

4546032-700-09F.fm

Page 46: 46032-700-09.pdf

0Operating instructions

❏ Bring the fuse into the enclosure. With the upper end of the fuse

behind the upper fuse holder, bring the lower end of the fuse to rest

on the lifting rod.

❏ Visually align the upper end of the fuse with the upper fuse clip, and

raise the tool handle to push the fuse into the upper clip. Verify that

the fuse is fully inserted into the upper clip.

❏ Lower the handle. If the fuse was fully inserted at the top, the lower

end will naturally swing into place against the opening of the lower

fuse clip.

Upper

end of

fuse

Lower

end of

fuse

Upper

fuse

holderFuse

clip

Upper fuse clip

Handle

Lower

fuse clip

Lower

end of

fuse

46 46032-700-09F.fm

Page 47: 46032-700-09.pdf

0Operating instructions

❏ Rotate the pusher into position toward the hinge.

❏ Raise the handle again to push the fuse into the lower fuse clip.

PusherHinge

HandleFuse

Lower fuse clip

4746032-700-09F.fm

Page 48: 46032-700-09.pdf

0Operating instructions

Steps to install front fuses

NOTE: Always wear gloves when

working with fuses. The fuses could

be hot and will burn unprotected

hands. The photos on these pages

are factory demonstrations.

❏ Align the fuse tool so that the hook is toward the handle end and the

pusher is in the opposite position, toward the hinge.

❏ Insert the hinge in the narrow vertical space in front of the

fuseholder, between the holder and the fuse tray. In some cases, this

may be a tight fit. The tool should rest on the fuse tray, and the

handle should hang down.

❏ Bring the fuse into the enclosure. With the upper end of the fuse

behind the upper fuseholder, bring the lower end of the fuse to rest

on the V-notch in the pusher. The bulk of the fuse should be on the

hinge side of the pusher.

Pusher

Handle

Fuse tray

Fuse end

restingon

V-notch

Pusher

48 46032-700-09F.fm

Page 49: 46032-700-09.pdf

0Operating instructions

❏ Visually align the upper end of the fuse with the upper clip, and raise

the tool handle to push the fuse into the upper clip. Verify that the

fuse is fully inserted into the upper clip.

❏ Lower the handle. If the fuse was fully inserted at the top, the lower

end will naturally swing into place against the opening of the lower

fuse clip.

❏ Raise the handle again to push the fuse into the lower fuse clip.

Lower

fuse clip

Fuse tool

Fuse

Handle

4946032-700-09F.fm

Page 50: 46032-700-09.pdf

0Operating instructions

Blown fuse indicator

The blown fuse indicator assembly is located on the line side of the MV

power fuses. Should a blown fuse occur, the power fuse striker pin will

pop up and activate the assembly. When activated, a flag is operated

that is visible through the upper window of the contactor door.

Two sets of contacts change state when the assembly is triggered. One

set of contacts sends a direct trip signal to the contactor. The second set

of contacts is available for remote indication.

Flag indicator

Blown fuse Good fuse

Flag indicator

Striker pin, top

of fuse

50 46032-700-09F.fm

Page 51: 46032-700-09.pdf

0Operating instructions

Steps to remove fuses This process is the same for all fuses.

NOTE: Always wear gloves when

working with fuses. The fuses could

be hot and will burn unprotected

hands. The photos on these pages

are factory demonstrations.

❏ Align the fuse tool so that the hook is toward the hinge end of the tool

and the pusher rests in the opposite direction, toward the handle.

❏ Insert the hinge in the narrow vertical space in front of the

fuseholder, between the holder and the fuse tray. In some cases, this

may be a tight fit.

❏ Support the handle in one hand, and place the hook around the back

of the fuse as low as possible.

❏ Lower the handle to extract the fuse from the lower fuse clip.

❏ Manually pull the fuse from the upper fuse clip.

hook

5146032-700-09F.fm

Page 52: 46032-700-09.pdf

0Operating instructions

52 46032-700-09F.fm

Removing and installing fuses of the Merlin Gerin Propivar power factor correction capacitors (PFCC) inside Motorpact enclosures

Steps to remove fuses Remove and replace each fuse individually to avoid swapping wires.

❏ Remove and retain the screw from the top of the connector.

❏ Remove and retain the washer.

❏ Remove and retain the connector from the top of the fuse.

❏ Loosen the jam nut at the bottom of the fuse.

❏ Unscrew the fuse from the PFCC threaded rod.

Steps to install fuses ❏ Screw the fuse onto the PFCC threaded rod. Torque the fuse

following fuse supplier specifications.

❏ Torque the jam nut against the fuse according to the fuse supplier

specifications.

❏ Screw the connector on the fuse. Torque the connector according to

the fuse supplier specifications.

❏ Install the wire lug, the washer, and the screw at the top of the

connector as shown in the figure.

❏ Torque the screw to 3 N•m.

All operations described

hereafter must be carried

out in compliance with

the safety standards in

force, under the responsibility of a competent person.

Always remove all power

from the section and use

a properly rated testing

device to confirm there is no voltage present.

Always wear gloves when working with fuses. The body of a fuse that has blown or carried load current can be extremely hot and will burn unprotected hands.

IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown.

WasherScrew

Wire lug

Connector

Fuse

PFCC threaded rod

Jam nut

PFCC

Page 53: 46032-700-09.pdf

0Operating instructions

Removing and installing VT primary fuses

Steps to replace fuses ❏ Remove the load from the contactor. See “Operating the contactor”.❏ OPEN the disconnector to the earthed position. See “Opening the

disconnector”.❏ CLOSE the cable earthing switch, if supplied, to the earthed position.

See “Closing the cable earthing switch”.❏ Open the MV compartment door. See “Opening the medium

voltage compartment door”.

Steps to disassemble the fuse tube

❏ Push tube end A, and rotate counter-clockwise

❏ Loosen screw holding fuse retainer plate B.

❏ Remove fuse C.

Steps to assemble the fuse tube

❏ Replace fuse C.

❏ Tighten screw holding fuse retainer plate B to a 1 N•m torque.

❏ Align tube A in housing slot; push and rotate clockwise.

Steps to place back into operation

❏ Complete these operations in the reverse order of removal. See“Operating instructions”

❏ Complete these electric tests in compliance with the standards in force.

All operations described hereafter must be carried out in

compliance with the safety standards in force, under the responsibility of a competent person.

Always remove all power from the section and use a properly

rated testing device to confirm there is no voltage present.

A

BC

5346032-700-09F.fm

Page 54: 46032-700-09.pdf

0Operating instructions

Locking using padlocks

Number of possible padlocks per section type Use Ø6 to Ø8 padlocks.

■ 1 padlock on each

disconnector—for

preventing operation.

■ 1 padlock on each cable

earthing switch—for

preventing operation.

■ 1 padlock on each incoming

cable section door—for

preventing access.

Padlocking the disconnector

❏ Place 1 padlock on the disconnector operating access port.

This lock can be used to prevent operation of the disconnector in either

the CLOSED or OPEN/earthed position.

The pictogram on the

operator cover is a

reminder of the operations.

54 46032-700-09F.fm

Page 55: 46032-700-09.pdf

0Operating instructions

Padlocking the cable earthing switch

❏ Place 1 padlock on the cable earthing switch operating access port.

This lock can be used to prevent operation of the cable earthing switch

in either the CLOSED/earthed or OPEN position.

Padlocking the incoming cable section doors

❏ Place 1 padlock on each padlockable incoming cable section door,

upper and lower.

This lock can be used to prevent MV access whenever a key lock is

not requested.

5546032-700-09F.fm

Page 56: 46032-700-09.pdf

0Operating instructions

Locking using keylocks (optional)

Motorpact™ can be provided with various keylock schemes based on customer needs. The typical keylock

arrangement is shown. However, for the actual arrangement, see "equipment drawings" provided with each line-up.

Number of possible locks per section type

■ 1 or 2 keylocks on each disconnector—for preventing operation

■ 1 keylock on each cable earthing switch—for preventing operation

■ 1 keylock on each RVSS soft start section or RVAT section—for

preventing access

Keylocking the disconnectorLocking the disconnector open or closed with 1 keylock

■ A keylock used to lock the disconnector OPEN or CLOSED

■ Disconnector locked OPEN:

Can be keyed to allow RVSS soft start section or RVAT MV

compartment door to be opened. Can be keyed to allow cable

earthing switch operation, if supplied

■ Disconnector locked CLOSED

■ Can be keyed to prevent disconnector from being OPENED

Can be keyed to be OPENED only if power source is de-energized

Locking the disconnector open or closed with 2 keylocks

■ B double keylock used to lock the disconnector OPEN or CLOSED

■ Disconnector locked OPEN:

Can be keyed to allow cable earthing switch operation, if supplied

Can be keyed to allow RVSS soft start section or RVAT MV

compartment door to be opened

■ Disconnector locked CLOSED:

Can be keyed to prevent disconnector from being OPENED

Can be keyed to be OPENED only if power source is de-energized

A

B

56 46032-700-09F.fm

Page 57: 46032-700-09.pdf

0Operating instructions

Locking the cable earthing switch open or closed

■ C keylock used to lock the cable earthing switch OPEN or

CLOSED

■ Cable earthing switch locked OPEN:

Can be keyed to allow disconnector operation

■ Cable earthing switch locked CLOSED:

Can be keyed to allow RVSS soft start section or RVAT MV

compartment door to be opened

C

5746032-700-09F.fm

Page 58: 46032-700-09.pdf

0Operating instructions

FVR (full voltage reversing bidirectional)

Description The full voltage reversing (FVR) starter is a full voltage, bidirectional

motor starter with an operating range of 2300–7200 V. This product will

deliver the highest starting torque (about 150% of full load torque) to the

motor terminals in either direction: forward or reverse. This starter bases

interrupting ratings on fused applications.

Forward contactorReverse contactor

58 46032-700-09F.fm

Page 59: 46032-700-09.pdf

0Operating instructions

FVS (dual voltage transfer starter)

Description The dual voltage transfer starter (FVS) is designed to operate as part of

a smart sequence starter application or multiple motor soft starting

application.

A smart sequence starter application is a system to start multiple

motors, one at a time, with a predetermined minimum start time

between each motor start.

The FVS is part of a line-up that also includes a full voltage non-reversing

starter (FVNR) and an RVSS. One FVS is required per motor.

Main contactor

Soft start contactor

Full voltage bus Soft start flexible connector (600 A max.)

FVNR RVSS FVS FVS FVS

Soft startprotectionrelay Sepam

protectionrelay

Sepamprotectionrelay

Sepamprotectionrelay

M M M

5946032-700-09F.fm

Page 60: 46032-700-09.pdf

0Operating instructions

Redundant smart sequence starter

Description The redundant smart sequence starter application takes the smart

sequence starter and adds a second RVSS soft start section. The

second RVSS section can be used as a back up to the first RVSS section

or motor starting can be toggled betweeen the two RVSS soft start sections

to allow one to cool down while the other is starting motors.

The second RVSS section also allows for one remote line-up of dual

voltage transfer starters (FVS) to be connected in addition to the close

coupled FVS line-up.

Full voltage bus Soft start flexible connector (600 A max.)

FVNR RVSS FVS FVSM MFVNR RVSS

60 46032-700-09F.fm

Page 61: 46032-700-09.pdf

0Operating instructions

DDS (dual disconnect section)

Description The dual disconnect section (DDS) is designed to operate as part of a

redundant smart sequence starter application or multiple motor soft

starting application.

A smart sequence starter application is a system to start multiple

motors, one at a time, with a predetermined minimum start time

between each motor start.

The optional DDS is part of a line-up that includes two full voltage

non-reversing starters (FVNR), two RVSS soft start sections, and

multiple dual voltage starters (FVS). The DDS is located between the

RVSS and FVS sections in order to provide isolation between these

sections when maintenance is being done on the RVSS sections. The

DDS also provides cable landing for up to four remote FVS line-ups, as

well as a close coupled FVS line-up.

6146032-700-09F.fm

Page 62: 46032-700-09.pdf

0Operating instructions

Full voltage bus Soft start flexible connector (600 A max.)

FVNR RVSS DDSFVNR RVSS

62 46032-700-09F.fm

Page 63: 46032-700-09.pdf

0Operating instructions

2-Speed, 1-Winding

Description The 2-speed, 1-winding starter (2S1W) is designed for the control of

two-speed AC motors that have a single winding. Since the motor is

single winding, the speed change is accomplished by changing the

wiring configuration using a third contactor.

The 2S1W is part of a line-up that also includes a full voltage

non-reversing starter (FVNR).

Slow-speed contactor

Shorted contactor

6346032-700-09F.fm

Page 64: 46032-700-09.pdf

0Operating instructions

2-Speed, 2-Winding

Description The 2-speed, 2-winding starter (2S2W) is designed for the control of AC

motors that have separate windings for high- and low-speed operation.

Two interlocked contactors are used, with overload protection included

for each motor winding.

Fast-speed contactor

Slow-speed contactor

64 46032-700-09F.fm

Page 65: 46032-700-09.pdf

0Operating instructions

Star Delta

Description Star Delta starters are designed for the reduced voltage starting of

medium voltage motors by changing the configuration of the motor

windings from a Star to a Delta AC configuration without lowering the

current.

The Star Delta is part of a line-up that also includes a full voltage

non-reversing starter (FVNR).

Star-connection contactor

Delta-connection contactor

6546032-700-09F.fm

Page 66: 46032-700-09.pdf

0Operating instructions

RVAT (reduced voltage autotransformer)

Description The Reduced Voltage Autotransformer (RVAT) is used to provide a

reduced voltage to the motor terminals during starting. This is achieved

by the use of an autotransformer. Typically two types of

autotransformers are available.

■ Tapped—permits changing taps to change the output voltage to the

motor terminals

■ Non-tapped—specifically designed for the application and motor

In this manual, the tapped autotransformer is shown and discussed. For

an application using a non-tapped autotransformer, all information

provided is applicable other than the instruction for changing the tap

settings.

The section size of an RVAT is dependent upon the transformer rating.

The RVAT is always controlled from a main contactor section adjacent

to the left and the motor cable connections are made in this line

contactor section.

Each RVAT section is equipped with the following:

■ run contactor

■ start contactor

■ autotransformer

■ surge arresters

Limited duty cycle rating The reduced voltage starters contain an autotransformer with a limited

duty cycle rating. Unless otherwise noted, these devices are rated per

IEC 60076-11. Longer start times or more frequent starts will shorten

the life of this device.

RVAT interiorRVAT exterior

Start contactor

Run contactor

Autotransformer

Door latch keylock

66 46032-700-09F.fm

Page 67: 46032-700-09.pdf

0Operating instructions

Keylocks on an RVAT

Keylocking with disconnector (without cable earthing switch)

The RVAT section is supplied with key interlocks between the

disconnector in the main contactor section and the start and run

contactor compartments and the autotransformer compartment.

With the disconnector in the CLOSED position, the key is held

captive. During maintenance, the disconnector can be OPENED/

earthed and the key removed for access to the RVAT section. See“Disconnector operation” and “Accessing the medium voltage compartments RVAT or RVSS soft start section”.

Keylocking (with cable earthing switch)

When a cable earthing switch is supplied, the RVAT section is

supplied with key interlocks between the cable earthing switch in

the main contactor section and the start and run contactor

compartments, and the autotransformer compartment.

With the cable earthing switch in the OPEN or unearthed position,

the key is held captive. During maintenance, the cable earthing

switch can be CLOSED/earthed and the key removed for access to

the RVAT section. See “Cable earthing switch operation (optional)” and “Accessing the medium voltage compartments RVAT or RVSS soft start section”.

A spare key is supplied with every RVAT section. For safe operation, only 1 key should be used. The spare key should be stored away from the equipment and only used if 1 key is lost.

Using both keys could give access to live parts and could cause death or serious injury.

6746032-700-09F.fm

Page 68: 46032-700-09.pdf

0Operating instructions

RVAT operation

Autotransformers Autotransformers are normally tapped at 50%–65%–80%. The standard

factory setting used is 65%. Standard reduced-voltage starters make

the transition from reduced to full voltage based on the operation of a

current transition relay. As the motor accelerates, the current drawn will

decrease. When the motor is near full speed, the relay will sense the

drop in current and initiate the transition to full voltage.

Relay setting The current transition relay setting is user selectable with 100% being

the recommended default setting. An incomplete sequence timer will

open the starter if the current relay has not initiated transition before the

timer times out. The timer should be set to a maximum of 30 seconds.

The current relay setting may be increased to its maximum value of

120% if transition does not occur.

Tap setting If the starter does not transition in 30 seconds with the current relay set

at its maximum of 120%, the motor does not have sufficient starting

torque for the connected load. The motor must be unloaded or the

starting torque increased.

To increase starting torque, the autotransformer must be moved from

the 65% tap setting to the 80% tap setting.

steps to change tap settings

❏ OPEN the main contactor controlling the equipment by pressing the

STOP or OPEN pushbutton on the operating panel of the main

contactor. See “Operating the contactor”.❏ OPEN the disconnector in the main contactor to the earthed position.

See “Disconnector operation”.❏ If supplied, CLOSE the cable earthing switch to the earthed position.

See “Cable earthing switch operation (optional)”.❏ Using the key from the main disconnector or cable earthing switch if

supplied, OPEN the keylock allowing access to the MV

compartments. See “Accessing the medium voltage compartments RVAT or RVSS soft start section”.

❏ Change tap setting cable connections as needed. See "autotransformer cable connections" in the installation instruction guide.

All operations described

hereafter must be carried

out in compliance with the

safety standards in force,

under the responsibility of a competent person.

Autotransformer taps

Transition based on a simple timing relay is not recommended. Increased loads may be placed on the power system, starter, motor, and driven equipment if a transition occurs before the motor is up to speed. If this method is used, refer to the electrical schematics provided with the line-up.

68 46032-700-09F.fm

Page 69: 46032-700-09.pdf

0Operating instructions

S

The transition between the start and

run contactors is made through the

electrical control package; therefore,

the operational steps are the same as

an FVNR.

Steps to CLOSE❏ OPEN or unearth the cable

earthing switch, if supplied. See “Cable earthing switch operation (optional)”.

❏ CLOSE the disconnector. See“Disconnector operation”.

❏ Press the START or CLOSE

pushbutton on the operator panel.

Steps to OPEN❏ Press the STOP or OPEN

pushbutton on the operator panel.

All operations described hereafter must be carried out in compliance with the

safety standards in force, under the responsibility of a competent person.

$( 4 $+ + 4 0

4# 4" "

34* 3

Operator panel main contactor section

Operator panel

Main contactor

RVAT

6946032-700-09F.fm

Page 70: 46032-700-09.pdf

0Operating instructions

Reduced voltage soft starter (RVSS) soft start section

Description The RVSS soft start section is designed with heavy duty components to

provide a soft motor start suitable form most demanding applications.

Typical applications are as follows:

■ conveyor motor

■ fans

■ pumps

■ mining equipment

■ crushers

■ grinders

■ chillers

■ compressors

Like the RVAT section, the soft start section is always controlled from an

FVNR starter adjacent to the left of the RVSS soft start section. All

motor cable connections are made in this main FVNR. See "loadbox cable connection" in the installation instruction guide for cable

connection information.

For specific detailed instruction on ratings, operation, programming,

control connections, start-up, maintenance, replacement parts and

troubleshooting, see Schneider Electric bulletin 46032-700-10_.

Each RVSS soft start section is equipped with the following:

■ bypass contactor

■ silicon starter rectifier

■ microprocessor-based control system

■ digital display

RVSS soft start section interiorRVSS soft start section exterior

Bypass contactor or

PLC (depending on

application)

Digital

display

Microprocessor

based control

system

SCR

assembly

Door latch

keylock

70 46032-700-09F.fm

Page 71: 46032-700-09.pdf

0Operating instructions

Keylocks on an RVSS soft start sectionKeylocking with disconnector (without cable earthing switch)

The RVSS soft start section is supplied with key interlocks

between the disconnector in the main contactor section and the

bypass contactor compartment.

With the disconnector in the CLOSED position, the key is held

captive. During maintenance, the disconnector can be OPENED/

earthed and the key removed for access to the RVSS soft start

section. See “Disconnector operation” and “Accessing the busbar compartments—RVAT or RVSS soft start section”.

Keylocking with cable earthing switch

When a cable earthing switch is supplied, the RVSS soft start

section is supplied with key interlocks between the cable earthing

switch in the main contactor section and the bypass contactor

compartment and soft start power compartment.

With the cable earthing switch in the OPEN or unearthed position,

the key is held captive. During maintenance, the cable earthing

switch can be CLOSED/earthed and the key removed for access to

the RVSS soft start section. See “Cable earthing switch operation (optional)” and “Accessing the medium voltage compartments RVAT or RVSS soft start section”.

Keylocking with redundant S3 The RVSS soft start sections in a redundant S3 line-up are

supplied with key interlocks between the disconnectors in the main contactor sections and the FVS sections. It is important that the

key interlocking scheme agreed upon between the customer and

Schneider Electric is followed to make sure the RVSS soft start section MV doors cannot be opened unless the disconnectors in

both main contactors and the FVS sections are all open.

Keylocking with redundant S3 with dual disconnect section (DDS)

The RVSS soft start sections in a redundant S3 line-up are

supplied with key interlocks between the disconnectors in the main contactor sections and the DDS. It is important that the key

interlocking scheme agreed upon between the customer and

Schneider Electric is followed to make sure the RVSS soft start section MV doors cannot be opened unless the disconnectors in

both main contactors and the DDS are all open.

A spare key is supplied with every RVSS soft start section. For safe operation, only 1 key should be used. The spare key should be stored away from the equipment and only used if 1 key is lost.

Using both keys could give access to live parts and could cause death or serious injury.

7146032-700-09F.fm

Page 72: 46032-700-09.pdf

0Operating instructions

Removing a contactor from an RVAT section or RVSS soft start section

Preliminary steps ❏ OPEN the main contactor section controlling the equipment by

pressing the STOP or OPEN pushbutton on the operating panel

of the main contactor section. See “Operating the contactor”.❏ OPEN the disconnector in the main contactor section to the

earthed position. See “Disconnector operation”.❏ If supplied, CLOSE the cable earthing switch to the earthed

position. See “Cable earthing switch operation (optional)”.❏ Using the key from the main disconnector or cable earthing

switch if supplied, OPEN the keylock allowing access to the MV

compartments. See “Accessing the medium voltage compartments RVAT or RVSS soft start section”.

Steps to remove a start, run, or bypass contactor

An RVAT section is shown. However, the

process is the same for RVSS soft start

sections.

❏ Pull the contactor rail down. This will disengage the contactor

from the line and load busbar connections.

❏ Roll the contactor slowly out of the

section until it rests in the wheel slot at

the end of the contactor rail.

❏ Carefully lift the contactor out of the

guide holding the rear wheel, and off

of the contactor rail.

All operations described hereafter must be carried out in

compliance with the safety standards in force, under the responsibility of a competent person.

Use extreme caution wile handling the contactor (25 kg) during this process. An optional lift truck is available. See "using a lift truck."

Wheel slotContactor

rail

Guide

72 46032-700-09F.fm

Page 73: 46032-700-09.pdf

0Operating instructions

Installing a contactor in an RVAT section or RVSS soft start section

Preliminary steps ❏ OPEN the main contactor section controlling the equipment by

pressing the STOP or OPEN pushbutton on the operating panel

of the main contactor. See “Operating the contactor”.❏ OPEN the disconnector in the main contactor to the earthed

position. See “Disconnector operation”.❏ If supplied, CLOSE the cable earthing switch to the earthed

position. See “Cable earthing switch operation (optional)”.❏ Using the key from the main disconnector or cable earthing

switch if supplied, OPEN the keylock allowing access to the MV

compartments. See “Accessing the medium voltage compartments RVAT or RVSS soft start section”.

Steps to install a start, run, or bypass contactor

An RVAT section is shown; however, the process is the same for

RVSS soft start section.

❏ Pull the contactor rail down.

❏ Seat the rear wheel of the contactor

between the contactor rail and the

guide.

❏ Rest the front of the contactor onto

the contactor rails.

❏ Slowly roll the contactor into the

section until it reaches the wheel stop.

❏Lift the contactor rail to the vertical position, engaging

the contactor.

All operations described hereafter must be carried out in

compliance with the safety standards in force, under the responsibility of a competent person.

A locking plate is used to prevent a contactor from being

installed in the wrong section. If insertion is blocked, verify that the amperage and contactor type are correct.

Use extreme caution while handling the contactor (25 kg)during this process. An optional lift truck is available. See "using a lift truck."

Contactor

rail Guide

Wheel stop

7346032-700-09F.fm

Page 74: 46032-700-09.pdf

0Operating instructions

Using a lift truck (optional) A lift truck is available for removing or installing contactors in an RVAT

section or RVSS soft start section. Contact your local field sales

office or distributor.

Use this device with all guidelines and processes explained in:

❏ “Removing a contactor from an RVAT section or RVSS soft start section”

Removing contactor with a lift truck

contactor

lift truck

74 46032-700-09F.fm

Page 75: 46032-700-09.pdf

0Operating instructions

MDT107 thermal diagnostic system (optional)

The MDT107 Thermal Diagnostic System is mounted in the equipment

at the factory for shipping. Wiring connections must be completed and

tested on site before putting the equipment into service.

Description The MDT107 Thermal Diagnostic system is used to measure the

temperature of medium voltage circuits. Using Schneider Electric

patented technology, the MDT107 system provides:

■ continuous monitoring of temperature rise of power circuits at upper

fuse holders and customer cable connections.

■ triggering of a pre-alarm, then an alarm by activation of outputs on

dry contacts.

■ visual indication of the zone and phase in which a temperature rise

exceeds a set threshold.

The MDT107 system includes:

■ An MDT107 electronic module mounted on a DIN rail in the LV

cabinet of the Motorpact™ unit. The module transmits calibrated

impulses to 1 or more circuits via optical fibers. The calculation of a

circuit’s temperature is based on the impulses the circuit sends back

to the module.

■ 2 CFO733 temperature sensors. Each of these factory-built

assemblies includes 3 sensor heads, 3 optical fibers, and the

connector for connecting to the readout module. The sensor heads

are made from a light-sensitive material whose fluorescence time

depends on temperature. The connector incorporates an optical-

electric conversion circuit, eliminating the need for optical

connections during installation.

■ Accessories for factory installation of the sensors in the MV panel.

7546032-700-09F.fm

Page 76: 46032-700-09.pdf

0Operating instructions

Functions The MDT107 module performs the following functions:

Monitoring of temperature buildup in 2 zones

Each CFO733 sensor corresponds to a 3-point zone to be monitored in

the panel, monitoring being based on temperature rise. The module

measures the temperature at 3 points per zone, as well as the ambient

temperature in order to calculate the temperature rise for each point.

Given the temperature differences between the inside of the LV cabinet

and the outside of the enclosure, correction of the ambient temperature

measured by the module is configured by means of an additional

setting.

Comparison monitoring is used with a maximum temperature rise

threshold, which may be adjusted separately for each zone and is

common to the 3 measurement points. This form of monitoring is

completed by a fixed maximum absolute sensor temperature threshold.

Therefore, the module includes 3 settings, to which access is sealed after

the ambient temperature settings are made on site.

Triggering of a pre-alarm When the temperature rise at 1 of the 3 points reaches a first set point

equal to 85% (1) of the preset threshold for the zone, or when 1 of the 3

points reaches the maximum absolute temperature of 115 °C

(239 °F), a pre-alarm is generated that results in:

— activation of the pre-alarm indication relay common to the

2 zones.

— activation in flashing mode of 1 of the 6 front panel indicators that identify

the zone and related point.

Triggering of an alarm When the temperature rise at 1 of the 3 points reaches the preset

maximum threshold (2) for the zone, or when 1 of the 3 points reaches

the maximum absolute temperature of 120 °C (248 °F), an alarm is

generated that results in:

— activation of the alarm power relay common to the 2 zones.

— activation in constant mode of 1 of the 6 front panel indicators that

identify the zone and related point.

(1) This is a fixed value; it can not be modified.

(2) These 7 setting values are defined at the factory. They are identified as A to G. See “Wiring and operation for MDT107”.

76 46032-700-09F.fm

Page 77: 46032-700-09.pdf

0Operating instructions

Self-monitoring of the module The MDT107 module has internal self-tests and is equipped with an

indicator that indicates availability:

Availability

indicator

— each time the module is initialized. The indicator

turns on in constant mode when the module is

switched on and then turns off after the module

initialization phase is successfully completed,

unless the required sensors are missing (see “Self-monitoring of sensors”below).

— in steady-state operation. If a fault is detected, the

indicator turns on in constant mode.

In both cases, the pre-alarm output contact is also

activated when the indicator is steadily on.

Self-monitoring of sensors The module provides continuous monitoring of the connected sensor(s).

An “Off” position is included in the settings for each zone for the various

situations that can occur:

■ If no sensors are connected to the module, the:

— indicator is on and flashes

— pre-alarm output contact is activated

— 6 sensor identification indicators are off

■ If 1 of the 3 points of each sensor is detected as being faulty (cut or

damaged fibers, malfunction of sensor-embedded electronics, etc.), the:

— indicator is on and flashes

— pre-alarm output contact is activated

— indicator linked to the faulty measurement point flashes

■ When only 1 zone is connected, the unused zone should be set to

“Off”. If this is not done, the 3 points of the related zone are detected

as being faulty.

7746032-700-09F.fm

Page 78: 46032-700-09.pdf

0Operating instructions

WiringWiring and operation for MDT107

Ratings

7

offG

F

EC

B

A

D

offG

F

EC

B

A

D

Zone B

Zone A

DT° build-upsetting

-18-16

-14

-12-8

-6-4

-10

Ambient T°correction(°C)

Zone B Zone A

L3

L1

L2

on

AB

Terminals

25 and 26

not used

5 relay output, dry contact,

connection terminals

Pre-alarm (1NO, 20-21) Alarm

(1NCNO; 22-23-24)

24–250 Vdc and 110–240

Vac power supply

connection terminals

6 red indicators identifying

the sensor (zone A or B)

and the circuit/sensor at

the origin of the alarm

Green “power on” indicator

and red “availability”

indicator

Ambient

temperature

correction

setting switch

Module grounding terminal

via green/yellow wire

(PE, safety of personnel)

Temperature

rise threshold

setting

switches

NOTE: The module's screw type

connectors can receive 2 wires with

maximum cross-section of 2.5 mm2

with or without fittings.

Optical fiber probes CFO733highest voltage for the equipment 17.5kV

rated power frequency voltage 38kV

impulse voltage 95 kV

maximum fiber/sensor temperature 120 °C (248 °F)

MDT107 moduletemperature rise setting factory set

operating and storage temperature- 25 °C to +70 °C

(-13 °F to +158 °F)

absolute maximum

threshold values

pre-alarm = 115 °C (239 °F)

alarm = 120 °C (248 °F)

Multi9 profile width 10.5 cm (4.13 in.)

module power supply 24/250 Vdc, 110/240 Vac

dry contacts voltage24, 48, 127, 220 Vdc,100 to 240 Vac

continuous current5A permanent (pre-alarm)

8A permanent (trip)

consumption (standby to max.)

ACDC

< 1.2 W (stby) to < 3.4 W (max)< 4.4 W (stby) to < 6.6 W (max)

78 46032-700-09F.fm

Page 79: 46032-700-09.pdf

0Operating instructions

MDT107 module location

Precaution: Use caution when working in the enclosure near the MDT107 sensors. The sensor heads can be damaged easily.

Fieldshapers

Loadbox

7946032-700-09F.fm

Page 80: 46032-700-09.pdf

0Operating instructions

MDT107 sensors location

Setting the temperature rise thresholds

The module is equipped with 2 mechanical selector switches for setting

the temperature rise threshold for each zone. Each switch has 8

possible setting positions. The factory settings are shown in the table below.

The selector switches are accessible from the front panel. They are

protected by a sealed cover. To change the setting for a zone:

Steps to set the temperature rise thresholds

❏ Remove the protective cover.

❏ Insert the tip of a screwdriver into one of the arrow-shaped slots.

NOTE: Use a flathead screwdriver with a tip width of 0.15 in. (4 mm).

❏ Turn the switch to the desired setting.

❏ Replace the protective cover.

Load Box

Field Shapers

Zone B

Zone A

offG

F

E

C

BA

D

offG

F

E

C

BA

D

ΔT° build-upsetting

Contactor rated current (A)

Zone Afield shapers connection

Zone Bload box connection

200 C B

400 E D

450 F D

720 G C

80 46032-700-09F.fm

Page 81: 46032-700-09.pdf

0Operating instructions

Setting the ambient temperature correction

The module contains a mechanical selector switch for correcting the

ambient temperature measured on the MDT107 module. The switch has

8 possible setting positions. It is accessible from the front panel and is

protected by a sealed cover. To change a setting:

Steps to set the ambient temperature

❏ Measure the temperature in the LV cabinet where the MDT107

module is located, then measure the ambient temperature outside

the switchgear. Note the difference in temperature between the two

locations.

❏ Remove the protective cover.

❏ Insert the tip of a screwdriver into the arrow-shaped slot.

NOTE: Use a flathead screwdriver with a blade width of 0.15 in. (4 mm).

❏ Turn the switch to the setting closest to the temperature difference

measured in step 1.

❏ Replace the protective cover.

Ambient T°correction(°C)

-18 -4-6

-8

-10-12

-14

-16

8146032-700-09F.fm

Page 82: 46032-700-09.pdf

0Operating instructions

Troubleshooting The following troubleshooting chart is provided to help minimize

downtime. If the proposed solutions do not correct the problem, please

contact the Schneider Electric Service Center.

Symptoms Faulty devices Probable causes and solutions

green indicator

is offexternal power supply

ensure the power supply is present and

connected

insufficient voltage

(out of range)

MDT107 module is faulty and must be

replaced

red indicator

remains on

after energizing

setting selection switches if indicators L1

to L3 are flashing

incorrect positioning of selector switches

(for example, 1or more switches is

between 2 positions)

indicators L1 to L3 Zones A and B are offMDT107 module is faulty and must be

replaced

red indicator

is flashing

probe connection

the probe(s) are not connected, or the

associated selector switch is in the "Off"

position

probes or sensorsfaulty probe or sensor that must be

replaced

MaintenancePreventative maintenance Inspect the equipment periodically to determine the conditions to which

the units are subjected. After determining the environmental conditions

according to the guidelines in this section (see “Environmental conditions”below), perform inspections and maintenance according to

the following table.

Recommended inspection/maintenance guidelines

Component Ideal conditions Standard conditions

Aggressive conditions

polyester disconnector housing

housing interior (busbar and mechanism)

housing

every 5 years every 2 years once per year

See “Environmental conditions” for definitions.

Inspect the equipment immediately after abnormal or stressful operating

conditions occur, or after the equipment experiences a fault current.

These inspection/maintenance guidelines cover only the starter. If

conditions cannot be established and documented, assume the

operating conditions are aggressive.

These inspection/maintenance guidelines do not warrant any field

connections, field modifications, or supersede any maintenance

procedures or schedules recommended by component manufacturers.

82 46032-700-09F.fm

Page 83: 46032-700-09.pdf

0

8346032-700-09F.fm

Page 84: 46032-700-09.pdf

0Maintenance

Environmental conditionsIdeal conditions ■ Unit is installed and commissioned in accordance with the

manufacturer’s instructions.

■ Humidity is below 40%, and there is no dripping water

■ Indoor, protected from the weather

■ Minimum of dust and air circulation

■ Ambient temperature is between - 5 °C and 40 °C

■ Altitude less than or equal to 1000 m, if above 1000 m, a derating

coefficient will be applied (please consult us)

■ No contact with any chemical agents (salt, H2S, etc.)

■ No infestation of any animal life (rodents, insects, etc.)

■ No contact with any plant life (mold, etc.)

■ No earth movements

■ No damage to the unit of any kind

■ No operating problems of any kind

■ No abnormally high number of operations

■ No abnormally high number of faults

■ No overvoltage or overcurrent (above ratings)

■ Thermal scanning of the joints (where possible) at least once a year,

or optional thermal diagnostics unit is installed

Standard conditions Same as "ideal conditions" with the following exceptions:

■ Humidity below 60%

■ The unit must not be subjected to regular extremes of temperatures

greater than 40 °C or less than - 30 °C

■ No regular thick covering of leaves or other debris

Aggressive conditions Any environmental conditions that have:

■ Humidity above 60%

■ Unit subjected to temperatures greater than 40 °C or less than - 30 °C

84 46032-700-09F.fm

Page 85: 46032-700-09.pdf

0Maintenance

Inspecting the equipment

This product is warranted per “Square D Conditions of Sale”, see Schneider Electric document 0100PL0041, and has been tested

under ideal laboratory conditions to the values listed below:

■ 1000 mechanical no load operations

■ 3 fuse fault transfer current operations (see IEC 62271-105C for

application)

Motorpact™ has been designed and tested to IEC 60470 and related

IEC standards. The mechanical life of the disconnector is 5000

operations.

To verify the contact life of the contactor, see Schneider Electric bulletin 46032-700-02, Motorpact™ 200/400/450 A Vacuum Contactors.

To ensure the starter is properly maintained, perform at least the

following inspection procedures:

Busbar connections: De-energize the primary and secondary

circuits. Perform a standard hi-pot test to measure busbar insulation

integrity (see "hi-pot dielectric test" in Schneider Electric bulletin 46032-700-08_, Motorpact IEC Installation Guide).

Inspect the connections for symptoms that indicate overheating or

weakened insulation. Remove dust from the surfaces of the busbars,

connections, supports, and enclosures. Wipe clean with a solvent

such as denatured alcohol. Vacuum the equipment. Do not use

compressed air to blow dust from the surfaces inside the starter.

Maintain the instruments, relays, and other devices according to the

specific instructions supplied. Inspect the devices and their contacts

for dust or dirt; wipe clean as necessary. The maintenance schedule

for individual devices such as meters and relays should be based

upon recommendations contained in the individual instruction guide

for each device. Coordinate the various schedules with the overall

maintenance program.

Inspect control wiring connections for tightness and damage.

Manually operate mechanical moving parts such as switch

assemblies, interlocks, and doors.

Make sure all busbar areas are well ventilated. Inspect grille work

and air passages on starters to make sure they are free from

obstruction and dirt accumulation.

Verify all tools and/or hardware have been removed from the

MV compartment.

Replace all devices, doors, and covers with their original

mounting hardware.

All operations described hereafter must be carried out in

compliance with the safety standards in force, under the responsibility of a competent person.

8546032-700-09F.fm

Page 86: 46032-700-09.pdf

0

86 46032-700-09F.fm

Page 87: 46032-700-09.pdf

0Replacement parts

Replacement parts

Corrective maintenance

operations allow for

malfunctioning subassemblies

to be replaced.

The operations mentioned in

the summary table hereafter

can be carried out by the

customer or by Schneider Electric After Sales agents.

For any other intervention, call upon the nearest Schneider Electric group agents.

After each maintenance, carry out electric tests in compliance with the standards in force.

Careful: During replacement,

all the following accessories

must absolutely be replaced by

new equipment.

— nylstop (self-locking nut)

— contact washer

— stop rings

— mechanical pin

description part number catalog numberauxiliary switch (blown-fuse indicator) 25713203 AAF00956

auxiliary switch-contacts (disconnector) S48198 AAF00955

auxiliary switch-terminal blocks (disconnector) S47074 AAF00955

control plug–contactor (female) MIP30F00830-359.0 AAF00950

control plug–contactor (male) MIP30M0000-0233 AAF00950

control plug–7 pin (female) 1925744 AAF00952

control plug–7 pin (male) 1925919 AAF00952

control plug–7 pin assembly frame 1852079 AAF00951

control plug–12 pin (female) 1925799 AAF00953

control plug–12 pin (male) 1925964 AAF00953

control plug–12 pin assembly frame 1852121 AAF00951

fuse tool (removal, installation) 46033-250-51 AAF00174

handle, operator 3728693 AAF00954

heater, one-high 46028-126-03 AAF00006

Mobilgrease® 28, red 1615-100950 consult us

VPIS/LLI module 51193386F0 consult us

contactor partsauxiliary contact block-contactor (latched) PR00620P70 consult us

auxiliary contact block-contactor (magnetically held, standard) PC18601P012 AAF00967

closing coil kit-contactor (120/240 Vac) PC18601P020 AAF00963

contact spring kit PC18601P121 AAF00968

drive unit-contactor (printed circuit board) PC18601P016 AAF00962

latched kit-contactor (24 Vdc) 3Z9G0119G003 AAF00346

latched kit-contactor (32 Vdc) 3Z9G0119G004 AAF00347

latched kit-contactor (48 Vdc) 3Z9G0119G005 AAF00350

latched kit-contactor (125 Vdc) 3Z9G0119G001 AAF00351

latched kit-contactor (250 Vdc) 3Z9G0119G002 AAF00348

line/load connector 46032-243-01 AAF00903

opening spring-contactor PR01109P70 Included in latched-kit

replacement of main fuses consult a Schneider Electric representative consult us

replacement of VT fuses consult a Schneider Electric representative consult us

shunt lead kit-contactor PC18601P101SQ AAF00964

trip coil-contactor (24 Vdc) PC18601P015 Included in latched-kit

trip coil-contactor (48 Vdc) PC18601P015 Included in latched-kit

trip coil-contactor (125 Vdc, standard) PC18601P003 Included in latched-kit

trip coil-contactor (250 Vdc) PC18601P004 Included in latched-kit

vacuum interrupter bottle-contactor PC18601P007 AAF00961

wear gauge-contactor PC18601P115 AAF00965

other electrical components refer to specific order bill of materials

8746032-700-09F.fm

Page 88: 46032-700-09.pdf

0

88 46032-700-09F.fm

Page 89: 46032-700-09.pdf

0Troubleshooting

Troubleshooting

❏ MV compartment doorcannot be opened

Check that the disconnector is in the OPEN/earthed position.

Check that the disconnector access port is CLOSED.

❏ Disconnector cannot be

operated

Check that the MV compartment door is CLOSED and the handle

latched.

Check that the contactor is in the OPEN position.

Check that the earthing switch (if supplied) is OPEN and the access

port is CLOSED.

❏ Disconnector access portcannot be CLOSED

Check that the disconnector is fully OPEN or earthed.

Check that the key interlock keys (if supplied) are in the proper position.

❏ Disconnector access portcannot be OPENED

Check that the disconnector is fully OPEN or earthed.

Check that the key interlock keys (if supplied) are in the proper position.

❏ Cable earthing switchcannot be operated

Check that the contactor is in the OPEN position.

Check that the disconnector is in the OPEN/earthed position.

Check that the MV compartment door is CLOSED and the handle is

latched.

Check that the disconnector operating access port is OPEN.

❏ Contactor will not CLOSE

electrically

Check that the disconnector is CLOSED.

Check that the disconnector access port is CLOSED.

Check the control fuses.

Check the closing coil circuit.

Check for loose terminal connections.

Check for a loose plug connection in the LV cabinet.

Check the electrical interlocks. See "equipment drawings" provided with each line-up.

Check the interlock linkage to the contactor.

❏ Latched contactor will not

OPEN electrically

Check the control fuses.

Check the trip coil circuit.

Check for loose terminal connections.

Check for loose plug connections in the LV cabinet.

Check the electrical interlocks. See "equipment drawings"provided with each line-up.

❏ Voltage presence indicatordoes not illuminate

Test for voltage on 2 of the test ports on the indicating box. Verify the

MV voltage is truly present.

All operations described hereafter must be carried out in

compliance with the safety standards in force, under the responsibility of a competent person.

8946032-700-09F.fm

Page 90: 46032-700-09.pdf

0

90 46032-700-09F.fm

Page 91: 46032-700-09.pdf

0Glossary

auxiliary contacts Sets of contacts mechanically operated by the disconnector or

the contactor.

auxiliary section A section that contains either low voltage or medium voltage components

that require a different mounting than a typical starter section.

busbar compartment The compartment isolating the through or main busbars in a

Motorpact™ switchboard line-up.

cable earthing switch A sliding 2-position device (CLOSED position earthed). Designed to

discharge the capacitance to earth up to a 5 kA fault.

capacitive divider A capacitor attached to the phase busbar that is used to send a reduced

voltage signal to a neon light for voltage presence indication.

contactor The mobile vacuum interrupting device used for establishing and

interrupting the medium voltage power in the circuit.

control power transformer (CPT) A transformer that reduces medium voltage to low voltage for control circuit

use.

current transformer (CT) An instrument transformer intended to have its primary winding connected

in series with the conductor carrying the current to be measured or

controlled.

disconnector A rotating, 2-position switch that is used to connect the main power source

in the closed position and to connect to the equipment earth in the open

position.

enclosure The external surface of a section that prevents access to the section’s

internal parts.

full voltage starter A motor starter which connects the line voltage across the motor terminals

in one step.

fuse, medium voltage A medium voltage fuse capable of interrupting all currents from the rated

breaking capacity to the minimum breaking current I3.

fuse ferrule A cylindrical fuse terminal at the end of a cartridge fuse.

fuseholder An assembly of insulated fuse tubes that house the primary contacts of the

medium voltage fuse connection for the CPT and VT fuses.

insulator A device intended to insulate and give rigid support to busbars throughout

the equipment.

interlocks A device actuated by the operation of some other device to govern

succeeding operations. The interlocks are classified into three main

divisions: mechanical, electrical, and key interlocks.

9146032-700-09F.fm

Page 92: 46032-700-09.pdf

0Glossary

internal arc tunnel An air chamber or compartment attached to the roof of the switchboard line-

up. This compartment is designed for containing or distributing the gases

should an internal arc event occur.

internal arc withstand A description for the added features of the enclosure which help in the

withstand or containment of a gas discharge should an internal arc event

occur.

low power current transformer (LPCT)

A device that transforms a medium voltage circuit current into a

proportional low voltage signal.

medium voltage compartment A switchboard compartment which houses any medium voltage devices.

power factor correction capacitor (PFCC)

A device that counteracts the undesirable effects of electric loads which

create a power factor less than 1.

shipping section Any combination of Motorpact™ units shipped together.

starter The combination of all the switching means necessary to start and stop a

motor with suitable overload protection, i.e., a section mounting a contactor

and fuses that is used for starting motors.

stress cone Pre-manufactured insulated cable termination recommended for all

incoming/outgoing and load connections.

surge arrester A device intended to protect equipment from electrical overvoltage.

voltage presence indication system (VPIS)

The VPIS is a light module mounted on the front of the equipment that gives

an indication when voltage is present on the MV cables. Energy is provided

from a capacitive divider (see definition for capacitive divider).

voltage transformer (VT) An instrument transformer intended to have its primary winding connected

in shunt with a power supply circuit for measuring the voltage.

wiring harness Pre-manufactured wiring bundles or connections.

92 46032-700-09F.fm

Page 93: 46032-700-09.pdf

9346032-700-09F.fm

Page 94: 46032-700-09.pdf

S

3

C

F

T

R

Cw

4

The Schneider group service centers are at your service for:

-engineering and technical assistance,

-commissioning,

-training,

-preventive and corrective maintenance,

-adaptation, and

-spare parts.

Contact your sales representative who will put you in touch with your nearestSchneider group service center or call us on 33 (0)4 76 57 60 60 (Grenoble, France).

46032-7

00-0

9F

©2004–201

1S

chneid

er

Ele

ctr

icA

llrights

reserv

ed.

chneider Electric Industries SAS

5, rue Joseph Monier

S 30323

- 92506 Rueil Malmaison Cedex (France)

él. : +33 (0)1 41 29 70 00

CS Nanterre 954 503 439

apital social 896 313 776 €ww.schneider-electric.com

6032-700-09F 11/2011

As standards, specifications, and designs change from time to time, please ask for confirmationof the information given in this publication.

This document has been printed on ecological paper.