46032-700-09.pdf
-
Upload
brightstardust -
Category
Documents
-
view
79 -
download
16
description
Transcript of 46032-700-09.pdf
Motorpact IEC
Instructions for use
46032-700-09FRetain for future use.
0
2 46032-700-09F.fm
0Contents
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Standard tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Non-greased screws and bolts . . . . . . . . . . . . . . . . . . . . . . 7
Application methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Full voltage non-reversing starter (FVNR) . . . . . . . . . . . . . . . . 9
Full voltage reversing bidirectional starter (FVR), dual voltage
transfer starter (FVS), 2-Speed, 1-Winding (2S1W), and Star
Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-Speed, 2-Winding (2S2W) . . . . . . . . . . . . . . . . . . . . . . . . . 11
FVNR starter with Merlin Gerin Propivar power factor
correction capacitor (PFCC) . . . . . . . . . . . . . . . . . . . . . . . . . 12
Reduced voltage soft starter (RVSS) soft start section . . . . . 13
Dual disconnect section (DDS). . . . . . . . . . . . . . . . . . . . . . . . 14
Reduced voltage autotransformer (RVAT) section. . . . . . . . . 15
Incoming cable section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
FVNR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
FVR bidirectional, FVS, 2S1W, 2S2W, and Star Delta . . . 18
Front operator panel description . . . . . . . . . . . . . . . . . . . . . . 19
Procedure pictogram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Instructions for access to the inside of the section . . . . . . . 21Accessing the busbar compartment FVNR. . . . . . . . . . . . . . . . . 21
Steps to access the busbar compartment from the
rear of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Steps to access the busbar compartment from the front
of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Accessing the MV compartment . . . . . . . . . . . . . . . . . . . . . . 22
Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Access to LV cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Accessing the medium voltage compartment FVNR . . . . . . . 23
Opening the medium voltage compartment door . . . . . . . 23
Accessing the medium voltage compartments RVAT or
RVSS soft start section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Steps to OPEN the RVAT or RVSS soft start section MV
doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Steps to CLOSE the RVAT or RVSS soft start section
MV doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Accessing the busbar compartments—RVAT or RVSS
soft start section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Steps to access the busbar compartment from the front
of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Accessing the busbar compartment—DDS . . . . . . . . . . . . . . 26
Steps to access the busbar compartment . . . . . . . . . . . . 26
Accessing the reduced voltage soft starting MV cable
connector compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Steps to access the reduced voltage soft starting MV
cable connector compartment from the front of the
enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installation and operation recommendation . . . . . . . . . . . . . 29Switchgear aging resistance . . . . . . . . . . . . . . . . . . . . . . . . . 29
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Steps for tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Preliminary operation check . . . . . . . . . . . . . . . . . . . . . . . 30
346032-700-09F.fm
0Contents
Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Disconnector operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Opening the disconnector. . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Closing the disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Voltage presence on MV cables . . . . . . . . . . . . . . . . . . . . . . . 35
Section equipped with VPIS voltage indicator boxes . . . . 35
Instructions for use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
MV cable test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Steps to test conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Voltage injections on MV outgoing cable heads . . . . . . . . 35
Replacing the voltage indicator box . . . . . . . . . . . . . . . . . . . . 36
Steps for removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Steps for placing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Operating the contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Steps to CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Steps to OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Removing or installing the contactor. . . . . . . . . . . . . . . . . . . . 38
Starting status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Steps to remove the contactor. . . . . . . . . . . . . . . . . . . . . . 38
Steps to install the contactor . . . . . . . . . . . . . . . . . . . . . . . 39
Back light assembly (optional) . . . . . . . . . . . . . . . . . . . . . . . . 40
Battery replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Cable earthing switch operation (optional) . . . . . . . . . . . . . . . 41
Instructions for use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Cable earthing switch operating condition. . . . . . . . . . . . . 41
Closing the cable earthing switch . . . . . . . . . . . . . . . . . . . . . . 42
Opening the cable earthing switch . . . . . . . . . . . . . . . . . . . . . 42
Removing and installing fuses . . . . . . . . . . . . . . . . . . . . . . . . 43
Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Steps to install fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fuse tool (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Steps to install rear and middle fuses . . . . . . . . . . . . . . . . 45
Steps to install front fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Blown fuse indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Removing and installing fuses of the Merlin Gerin PFCC
inside Motorpact enclosures . . . . . . . . . . . . . . . . . . . . . . . . . 52
Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Steps to install fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Removing and installing VT primary fuses . . . . . . . . . . . . . . . 53
Steps to replace fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Steps to disassemble the fuse tube. . . . . . . . . . . . . . . . . . 53
Steps to assemble the fuse tube . . . . . . . . . . . . . . . . . . . . 53
Steps to place back into operation . . . . . . . . . . . . . . . . . . 53
Locking using padlocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Number of possible padlocks per section type . . . . . . . . . 54
Padlocking the disconnector . . . . . . . . . . . . . . . . . . . . . . . 54
Padlocking the cable earthing switch . . . . . . . . . . . . . . . . 55
Padlocking the incoming cable section doors . . . . . . . . . . 55
Locking using keylocks (optional) . . . . . . . . . . . . . . . . . . . . . . 56
Number of possible locks per section type . . . . . . . . . . . . 56
Keylocking the disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Locking the disconnector open or closed with 1 keylock. . 56
Locking the disconnector open or closed with 2 keylocks. . . 56
Locking the cable earthing switch open or closed . . . . . . . 57
FVR (full voltage reversing bidirectional) . . . . . . . . . . . . . . 58
FVS (dual voltage transfer starter) . . . . . . . . . . . . . . . . . . 59
4 46032-700-09F.fm
0Contents
Redundant smart sequence starter . . . . . . . . . . . . . . . . . . . . 60
DDS (dual disconnect section) . . . . . . . . . . . . . . . . . . . . . . . . 61
2-Speed, 1-Winding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
2-Speed, 2-Winding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Star Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
RVAT (reduced voltage autotransformer). . . . . . . . . . . . . . . . 66
Limited duty cycle rating . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Keylocks on an RVAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Keylocking with disconnector (without cable earthing
switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Keylocking (with cable earthing switch). . . . . . . . . . . . . . . 67
RVAT operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Autotransformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Relay setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Tap setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Steps to CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Steps to OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Reduced voltage soft starter (RVSS) soft start section . . . . . 70
Keylocks on an RVSS soft start section . . . . . . . . . . . . . . . . . 71
Keylocking with disconnector (without cable earthing
switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Keylocking with cable earthing switch . . . . . . . . . . . . . . . . 71
Keylocking with redundant S3 . . . . . . . . . . . . . . . . . . . . . . 71
Keylocking with redundant S3 with dual disconnect
section (DDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Removing a contactor from an RVAT or RVSS soft start
section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Preliminary steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Steps to remove a start, run, or bypass contactor . . . . . . . . . 72
Installing a contactor in an RVAT or RVSS soft start section . 73
Preliminary steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Steps to install a start, run, or bypass contactor. . . . . . . . . . . 73
Using a lift truck (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
MDT107 thermal diagnostic system (optional) . . . . . . . . . . . . 75
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Wiring and operation for MDT107 . . . . . . . . . . . . . . . . . . . 78
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
MDT107 module location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
MDT107 sensors location. . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Setting the temperature rise thresholds. . . . . . . . . . . . . . . 80
Setting the ambient temperature correction . . . . . . . . . . . 81
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82Preventative maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 82
Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . 84
Inspecting the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
546032-700-09F.fm
0
6 46032-700-09F.fm
0General information
Standard tightening torquesNon-greased screws and bolts
Application methods The conical washers placed on the external sides of the busbars
ensure better distribution of stress regarding bolts tightened to the
recommended torques.
Marking It is strictly forbidden to walk on
the parts bearing this marking.
It is strictly forbidden to remove
the parts bearing this marking
when the equipment is
energized.
Screw Busbar torque in N•m Mech. torque in N•mØ 6 — 10
Ø 8 28 20
Ø 10 50 35
Ø 12 75 55
Ø 14 — 120
746032-700-09F.fm
0
8 46032-700-09F.fm
0General description
Full voltage non-reversing starter (FVNR)
A. MV power cable entry plate (optional
upper entry)
B. internal arc vent cover (optional)
C. LV control cable entry plate
D. LV cabinet door
E. Diagnostic thermal detection module
(optional)
F. Operation and locking panel
G. VPIS indicator box (optional)
H. Interlock shuttle
I. Blown fuse indicator (optional)
J. Cable earthing switch, load connection
lug pads
K. MV power fuses
L. MV compartment door
M. Vacuum contactor
N. Fuseholder, control power transformer
(CPT), and voltage transformer (VT)
O. LV inter-unit top wireway
P. Main busbar barrier
Q. Disconnector
R. Main busbars
S. Main earthing terminal
T. Surge arresters (optional)
U. Current transformers (CTs)
V. MV cable support clamps (bottom entry)
W. Voltage transformer (VT)
X. LV cable entry plate (bottom entry)
Load connection lug pad not required for
smart start sequence application.
B
C
D
E
F
G
J
K
L
M
O
P
R
T
S
U
A
V
W
NX
I
Q
H
946032-700-09F.fm
0General description
Full voltage reversing bidirectional starter (FVR), dual voltage transfer starter (FVS), 2-Speed, 1-Winding (2S1W), and Star Delta
A. MV power cable entry plate
B. Internal arc vent cover (optional)
C. LV control cable entry plate
D. LV compartment door
E. Diagnostic thermal detection module
(optional)
F. Operation and locking panel
G. VPIS indicator box (optional)
H. Interlock shuttle
I. Blown fuse indicator (optional)
J. Cable earthing switch, load connection
lug pads
K. MV power fuses
L. MV compartment door
M. See table below
N. See table below
O. Fuseholder, control power transformer
(CPT), and voltage transformer (VT)
P. LV inter-unit top wireway
Q. Main busbar barrier
R. Disconnector
S. Main busbars
T. Main earthing terminal
Starter Type M NFVR bidirectional Forward contactor Reverse contactor
FVS dual voltage transfer starter Main contactor Soft start contactor
2S1W Slow-speed contactor Shorted contactor
Star Delta Star-connection contactor Delta-connection contactor
BC
D
E
FG
J
K
L
M O
P
R
T
S
A
N
I
Q
H
10 46032-700-09F.fm
0General description
2-Speed, 2-Winding (2S2W)
A. MV power cable entry plate
B. Internal arc vent cover (optional)
C. LV control cable entry plate
D. LV compartment door
E. Diagnostic thermal detection module
(optional)
F. Operation and locking panel
G. VPIS indicator box (optional)
H. Interlock shuttle
I. Blown fuse indicator (optional)
J. Cable earthing switch load connection
lug pads (cables for fast speed winding)
K. MV power fuses
L. MV compartment door
M. Fast-speed contactor
N. Slow-speed contactor
O. Fuseholder, control power transformer
(CPT), and voltage transformer (VT)
P. LV inter-unit top wireway
Q. Main busbar barrier
R. Disconnector
S. Main busbars
T. Main earthing terminal
U. Load connection lug pads (cables for
slow speed winding)
BC
D
E
FG
JK
L
M O
P
R
T
S
A
N
I
Q
H
U
1146032-700-09F.fm
0General description
FVNR starter with Merlin Gerin Propivar power factor correction capacitor (PFCC)
A. LV cabinet door
B. Operation and locking panel
C. MV compartment door
D. Cable earthing switch, load connection
lug pads
E. MV power fuses
F. Vacuum contactor
G. Fuseholder, control power transformer
(CPT), and voltage transformer (VT)
H. Disconnector
I. Main busbars
J. Main earthing terminal
K. PFCC fuses
L. PFCC
A
B
D
F
E
C
G
H
IJ
K
L
12 46032-700-09F.fm
0General description
Reduced voltage soft starter (RVSS) soft start sectionA. Internal arc vent cover (optional)
B. LV control entry plate
C. MV compartment door
D. LV door
E. Human machine interface (HMI) soft start
control interface modules
F. Soft start power compartment door
G. Heater (optional)
H. LV control entry plate
I. Customer conduit wireway
J. Bypass contactor or PLC mounted
(depending on application)
K. Ground fault board (optional)
L. Terminal control board
M. Main busbar compartment
N. Main earthing terminal
O. Control power, central processing unit
(CPU) boards, RTD board (optional)
P. Main busbar access cover
Q. LV cabinet
R. Door interlock
S. Ring transformers
T. Silicon control rectifier stacks
A
B
C
D
E
F
G
I
J
K
L
M
N
O
P
Q
R
S
TS
H
1346032-700-09F.fm
0General description
Dual disconnect section (DDS)
A. Reduced voltage MV cable entry plate
B. Internal arc vent cover (optional)
C. LV cable entry plate
D. LV cabinet door
E. Access cover plate for reduced voltage
soft starting MV cable connectors
F. Main busbar access cover plate
G. Access cover plate for reduced voltage
soft starting MV cable connectors
H. Operation and locking panel
I. MV compartment door
J. Heater (optional)
K. LV inner-unit top wireway
L. Top entry main earthing terminal
M. Reduced voltage soft starting MV cable
terminals
N. Main busbars
O. Disconnectors
P. Bottom entry main earthing terminal
AB
C
E
G
H
J
I
K
L
M
N
O
P
D
F
M
14 46032-700-09F.fm
0General description
Reduced voltage autotransformer (RVAT) section
A. Internal arc vent cover (optional)
B. LV control cable entry plate
C. MV compartment door
D. Run contactor
E. Start contactor
F. LV door
G. Autotransformer door
H. Surge arresters
I. Main busbar access cover
J. Door interlock
K. Main busbar compartment
L. Main earthing terminal
M. Autotransformer
AB
C
D
E
F
G
JI
K
L
M
H
1546032-700-09F.fm
0General description
Incoming cable sectionA. Internal arc vent cover (optional)
B. LV control cable entry plate
C. MV upper barrier
D. MV upper door
E. MV lower door
F. Voltage presence indicator system
(VPIS) indicator box (optional)
G. MV lower barrier
H. LV inter-section top wireway
I. Capacitive divider, VPIS (optional)
J. Surge arresters (optional)
K. Main earthing terminal
L. Main busbar lug pad
M. Earth riser connection
N. Current transformers (CTs) (optional)
O. MV cable support clamps (bottom entry)
A
B
C
D
E
O
H
I
J
K
L
M
N
F G
16 46032-700-09F.fm
0General description
Identification
FVNRA. Name of starter or section
B. Viewing port, disconnector
C. Characteristics,
designations, and serial
number
D. Interlock shuttle
E. Status window, blown fuse
indicator (see page 50)
F. Status window, cable
earthing switch (see
page 41)
G. Status window, contactor
contactor
H. Characteristics,
designations, and serial
number
I. Status indicator
A
BC
H
E
G
I
D
F
1746032-700-09F.fm
0General description
FVR bidirectional, FVS, 2S1W, 2S2W, and Star DeltaA. Name of starter or section
B. Viewing port, disconnector
C. Characteristics, designations, and
serial number
D. Interlock shuttle
E. Status window, blown fuse
indicator (see page 50)
F. Status window, cable earthing
switch (see page 41)
G. Status window, contactor
Contactor
H. Characteristics, designations, and
serial number
I. Status indicator
A
BC
H
E
G
I
D
F
18 46032-700-09F.fm
0General description
Front operator panel description
A. Contactor control panel
B. Voltage presence indicator system
(VPIS)
C. Pushbutton for back light (optional)
D. Disconnector viewing port
E. Disconnector status indicator
F. Location for cable earthing switch
operation padlock
G. Disconnector operating access
port
H. Cable earthing switch operating
access port
I. Location for disconnector operation
padlock
J. Procedure pictogram
K. Interlock shuttle
Procedure pictogramSteps for closing of circuit1. MV compartment door position, close
and latch
2. If the cable earthing switch is not
supplied, skip to step 5. If the cable
earthing switch is supplied, move the
cable earthing switch access port from
the locked to unlocked position. This
requires the interlock shuttle to be in
the right-hand position. See “Cable earthing switch operation (optional)”.
3. OPEN or un-earth the cable earthing
switch
4. Move the cable earthing switch access
port from the unlocked to locked
position; then move the interlock shuttle
from the right-hand to left-hand position.
See “Disconnector operation”.5. Move the disconnector access port
from the locked to unlocked position
6. CLOSE the disconnector
7. Move the disconnector access port
from the unlocked to locked position
8. CLOSE the contactor
A
B
C
D
EFH
I
G
J
K
1946032-700-09F.fm
0
20 46032-700-09F.fm
0Instructions for access to theinside of the section
2146032-700-09F.fm
Accessing the busbar compartment FVNR
Steps to access the busbar compartment from the rear of the enclosure
Steps to access the busbar compartment from the front of the enclosure
All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.
Always remove all power from the section and use a properly rated testing device to confirm there is no voltage present.
Always look through the rear viewing window to verify that the MV compartment door is OPEN, before removing the MV cable compartment cover.
❏ Remove the upper MV
cable compartment cover.
4 M10x20 screws.
❏ Remove the rear main
busbar cover. 4 M10x20 screws.
❏ The busbar
compartment is
now accessible.
❏ Remove the main busbar access cover in the
floor of the LV cabinet. 8 M10x20 screws.❏ The busbar compartment is
now accessible.
Main busbar
access cover
After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 35 N•m.
0Instructions for access to theinside of the section
Accessing the MV compartment (cables, busbars, CT, cable earthing switch, surge arresters, fuses, contactor, transformers)
Safety rules See “Accessing the medium voltage compartment FVNR” and “Accessing the medium voltage compartments RVAT or RVSS soft start section”.
cables See "cable connections" in the installation instruction guide.
busbars See "installing busbars" in the installation instruction guide.
CT (current transformer) See “General description”for
the mounting locations.
cable earthing switch See “Cable earthing switch operation (optional)”.
surge arresters See “General description”for
the mounting locations.
fuses See “Removing and installing fuses”.
contactor See “Removing or installing the contactor”.
transformers See “General description”for
the mounting locations.
Access to LV cabinet (instrument components, relays, and communication modules)
See "accessing the low voltage compartment" in the
installation instruction guide.
All operations described
hereafter must be carried
out in compliance with the
safety standards in force,
under the responsibility of a competent person.
All operations described
hereafter must be carried
out in compliance with
the safety standards in
force, under the responsibility of a competent person.
22 46032-700-09F.fm
0Instructions for access to theinside of the section
2346032-700-09F.fm
Accessing the medium voltage compartment FVNRMotorpact™ motor starters are shipped with the disconnector in the
earthed/OPEN position.
The disconnector must be in the earthed/OPEN position to open the
medium voltage compartment door.
See “Disconnector operation”.
The cable earthing switch (optional) must be in the earthed/CLOSED
position to open the medium voltage compartment door.
See “Cable earthing switch operation (optional)”.
Opening the medium voltage compartment door
Accessing the cable compartment FVNR
Always look through the viewing window to verify the actual position of the disconnector switch blades before trying to open the MV compartment door.
Door closed, rotate handle 90° Door openHandle rotated
All operations described
hereafter must be
carried out in
compliance with the
safety standards in
force, under the responsibility of a competent person.
Always remove all power from the section and use a
properly rated testing device to confirm there is no voltage present.
Always look through the rear viewing window to verify that
the MV compartment door is OPEN, before removing the MV cable compartment cover.
MV compartment
door viewing
window
MV
compartment
door
(opened 90°)
Steps to access the cable compartment of an FVNR section
❏ Verify through the rear
viewing window that the MV
compartment door is OPEN,
the power has been removed
from the section, and the
load connections have been
properly earthed.
❏ Remove the lower MV cable
compartment cover.
4 M10x20 screws.
tightening torque: 35 N•m
After installation or maintenance, ensure all covers are replaced using the original hardware.
Rear view
0Instructions for access to theinside of the section
24 46032-700-09F.fm
Accessing the medium voltage compartments RVAT or RVSS soft start section
The contactor and autotransformer compartments of an RVAT and the
contactor and soft start power compartments of an RVSS soft start
section are key interlocked with the main contactor disconnector or the
cable earthing switch, if supplied. If the optional dual disconnect section
(DDS) is being used, the RVSS will also be key interlocked with the
DDS.
For a description of key interlock operation, refer to the “Keylocks on an RVAT”or “Keylocks on an RVSS soft start section”section.
Steps to OPEN the RVAT or RVSS soft start section MV doors
❏ OPEN the middle LV doors to gain access to the key interlock.
❏ Insert and turn the interlock key to release the door latching mechanism.
❏ Insert the disconnector operating handle as shown below. Rotate
counter-clockwise to release the MV doors.
Steps to CLOSE the RVAT or RVSS soft start section MV doors
❏ CLOSE all MV doors. For RVAT, right side doors must be closed
before the left side doors.
❏ Push the release button next to the operator port to latch the MV doors.
❏ Insert the disconnector operating handle as shown below. Rotate
clockwise to lock the MV doors.
❏ Turn the interlock key to lock the door latching mechanism. Remove the
key, and return it to disconnector or cable earthing switch, if supplied.
❏ Close and latch the middle LV doors.
Door latch keylock
Operating handle
Door latch keylock
Operating handle
Release
button
0Instructions for access to theinside of the section
Accessing the busbar compartments—RVAT or RVSS soft start section
The RVAT or RVSS soft start section main busbar compartment can be
accessed only from the front due to the cable arrangement in the rear of
these sections.
Steps to access the busbar compartment from the front of the enclosure
❏ Remove the M6x10 screws holding the main busbar access covers.
The RVAT shown will have 2 covers. RVSS soft start section will have
only 1 cover.
Main busbar access cover Main busbar
access cover
❏ The busbar compartment is now accessible.
After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 6 N•m max.
2546032-700-09F.fm
0Instructions for access to theinside of the section
Accessing the busbar compartment—DDS
The DDS main busbar compartment can be accessed only from the
front due to the busbars being enclosed in a busbar tunnel.
Steps to access the busbar compartment
❏ Remove the M10x20 screws holding the main busbar access covers.
Main busbar access cover
❏ The busbar compartment is now accessible.
After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 25 N•m max.
26 46032-700-09F.fm
0Instructions for access to theinside of the section
Accessing the reduced voltage soft starting MV cable connector compartment
The reduced voltage MV cable connector compartment can be
accessed from the front or the back of the unit. To access this
compartment from the front of the unit, refer to the images below.
Steps to access the reduced voltage soft starting MV cable connector compartment from the front of the enclosure
❏ Remove the M10x20 screws holding the access cover.
Reduced voltage soft starting MV
cable connector access cover
❏ The compartment is now accessible.
After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 25 N•m max.
2746032-700-09F.fm
0
28 46032-700-09F.fm
0Installation and operationrecommendation
Switchgear aging resistance
The switchgear’s resistance to
aging depends upon 3 factors.
■ The necessity of correct
implementation of
connections:
New cold-shrink or slip-on
technology offers ease of
installation.■ The effect of the relative
humidity factor:
Heating resistor installation
is essential in climates with a
high rate of relative humidity
and with significant
temperature differentials.
■ Ventilation control:
Provide area ventilation,
heating, and air conditioning
to maintain the ambient
temperature around the
equipment between - 5 °C
and 40 °C.
Operation It is strongly advised to periodically carry out(minimum every 2 years) a few operation cycles on operating devices.
Outside normal conditions of use (between - 5 °C and 40 °C, absence of dust, corrosive gas, etc.), it is recommended to verify the steps to be taken in order to ensure correct functioning of the installation. Contact the Schneider Electric Service Center for help to do so.
The Service Center is able to
assist you at any time to offer
you:
■ installation diagnostics.
■ suitable maintenance
operations.
■ maintenance contracts.
■ adaptations.
2946032-700-09F.fm
0Installation and operationrecommendation
Steps for testsSafety rulesCarry out electric tests in
compliance with the standards
in force.
It is recommended that prior to
start-up and after maintenance
on this equipment, the 1 minute
dielectric test is always
performed. See "steps to be taken for test and inspections" in the installation
instruction guide.
Preliminary operation check
Verify that a 1 minute dielectric test has been performed recently. If a
dielectric test is required, see "hi-pot dielectric test" in the installation instruction guide.
Operate the disconnector a minimum of 5 operations. See “Disconnector operation”
Operate the cable earthing switch (if supplied) a minimum of 5
operations. see “Cable earthing switch operation (optional)”With the disconnector in the CLOSED position, verify the MV
compartment door cannot be opened.
If supplied, verify all key interlocks function properly according to
the drawing.
Verify that all low voltage plugs are connected.
Verify all tools and/or hardware have been removed from the MV
compartment.
Replace all devices, doors, and covers with their original
mounting hardware.
All operations described
hereafter must be carried
out in compliance with the
safety standards in force,
under the responsibility of a competent person.
If any operation checks provide unacceptable results, DO NOT ENERGIZE THE EQUIPMENT. Contact your local field sales
office or distributor.
30 46032-700-09F.fm
0
3146032-700-09F.fm
0Operating instructions
Disconnector operation
Interlock shuttle
An interlock shuttle is provided
on all FVNR starters with a
cable earthing switch.
This shuttle must be in the
left-hand position to operate the
disconnector.
Always look through the viewing window to verify the actual
position of the disconnector switch blades.
Operating
handle
The disconnector operating
handle is stored on the right-
or left-hand end sheet.
DescriptionThe disconnector is the isolation means between the main busbar
and the line side of the primary fuses. When the disconnector is
in the earthed or OPEN position, it disconnects or isolates the
contactor from the supply voltage.
Moving the disconnector to the OPEN position earths the switch
blades and the load side power circuit down to the line side of
the contactor.
In the earthed/OPEN position, the disconnector does not earth the load side of the contactor, cables, or any other components that are connected to the load side of the contactor.
OPEN (earth) CLOSED
switch blades
32 46032-700-09F.fm
0Operating instructions
Opening the disconnector
The interlock system requires the following conditions to be met before the disconnector can be OPENED:
■ If a cable earthing switch is supplied, the interlock shuttle must
be in the left-hand position to allow disconnector operation.
■ The optional cable earthing switch must be in the
OPEN position.
■ The contactor must be in the OPEN position.
■ The MV compartment door must be closed and latched.
■ The cable earthing switch access port, if equipped, must
be closed.
When the conditions above
have been satisfied:
❏ Slide the disconnector
operating access port to the
right to open.
❏ Insert the operating handle,
and rotate counter-clockwise
to open or earth.
After putting the disconnector
in the OPEN position:
❏ Remove the operating
handle.
❏ Slide the disconnector
operating access port to the
left to close. If the access
port cannot be closed, open
the disconnector further,
then close the access port.
❏ After completely opening the
disconnector and closing the
cable earthing switch, if
supplied, the MV
compartment door can be
opened.
Open disconnector access port
Position
indicator
OPEN
Closed position
Open position
Position
indicator
CLOSED
3346032-700-09F.fm
0Operating instructions
Closing the disconnector
The interlock system requires the following conditions to be met before the disconnector can be CLOSED:
■ If a cable earthing switch is supplied, the interlock shuttle must
be in the left-hand position to allow disconnector operation.
■ The optional cable earthing switch must be in the
OPEN position.
■ The contactor must be in the OPEN position.
■ The MV compartment door must be closed and latched.
■ The cable earthing switch access port, if equipped, must
be closed.
When the conditions above
have been satisfied:
❏ Slide the disconnector
operating access port to the
right to open.
❏ Insert the operating handle,
and rotate clockwise to
close.
After putting the disconnector
in the CLOSED position:
❏ Remove the operating
handle.
❏ Slide the disconnector
operating access port to the
left to close. If the access
port cannot be closed, close
the disconnector further,
then close the access port.
❏ After the disconnector is
completely closed, the
contactor can be closed.
Open disconnector access port
Position
indicator
CLOSED
Open position
Closed position
Position
indicator
OPEN (earth)
34 46032-700-09F.fm
0Operating instructions
Voltage presence on MV cablesSection equipped with VPIS voltage indicator boxes
VPIS: The Voltage Presence
Indicating System is a box with
three integrated lamps.
The definite "voltage presence"
indication is ensured on the
voltage range stipulated by
IEC 61958.
Instructions for use
The indication of a VPIS alone
will not ensure the system is
de-energized. If the operation
rules require this, then suitable
voltage detectors in compliance
with IEC 61243 must be used.
A. Voltage presence indicator
light (1 for each phase)
B. Connection points enabling
a phase concordance unit to
be connected.
Once the cables are energized,
the voltage indicator lights
should illuminate.
MV cable test
Steps to test conditions ❏ Open the cable earthing
switch.
❏ The cables are connected to
injection tools.
Voltage injections on MV outgoing cable heads
❏ Check voltage absence. The
voltage indicator lights are
not illuminated.
❏ Close the cable earthing
switch. See “Closing the cable earthing switch”.
VPIS must not be used as a VDS (Voltage Detecting
System).
Use a properly rated testing device to confirm there is no voltage present.
A
B
3546032-700-09F.fm
0Operating instructions
❏ Open MV compartment
door. See “Accessing the medium voltage compartment FVNR”.
❏ Connect the voltage
injection circuit to the
cable lugs.
❏ Open the cable earthing
switch. See “Cable earthing switch operation (optional)”then carry out
the tests.
At the end of the tests:
❏ Close the cable earthing
switch.
❏ Remove the accessories.
Replacing the voltage indicator boxSteps for removing
❏ Remove the 2 fastening
screws (A) from the voltage
indicator box.
❏ Remove the voltage
indicator box, and
disconnect the connector.
Steps for placing ❏ Verify that the characteristics
label (B) on the new box
corresponds to the rated
voltage of your network.
example: 3 kV to 7.2 kV
❏ Place the new voltage
indicator box in the reverse
order of removal.
tightening torque: 0.1 mdaN
Cable lugs
All operations described
hereafter must be carried
out in compliance with the
safety standards in force, under the responsibility of a competent person.
Caution: a static voltage will be present if the indicator box is replaced while the equipment is energized.
A
B
36 46032-700-09F.fm
0Operating instructions
Operating the contactor
For more information, see Schneider Electric bulletin 46032-700-02 (200 A / 400 A / 450 A vacuum contactors).
Description
The contactor is typically electrically maintained. However, an optional
mechanical latching mechanism is added to latched contactors to lock the
contactor CLOSED. This latched contactor can be opened at the operator
panel or by pressing a reset button located on the MV compartment door.
Steps to CLOSE❏ OPEN or un-earth the cable earthing switch, if supplied. See “Cable
earthing switch operation (optional)”.❏ CLOSE the disconnector. See “Disconnector operation”.❏ Press the START or CLOSE pushbutton on the operator panel.
Steps to OPEN❏ Press the STOP or OPEN pushbutton on the operator panel. A
latched contactor can also be opened by pressing the reset button
on the MV compartment door.
All operations described
hereafter must be carried
out in compliance with the
safety standards in force,
under the responsibility of a competent person.
Contact fingers
Control terminal
blocks
Vacuum interrupter
Auxiliary contacts
Truck handle
Status indicator
Operator
panel
Status
window
Reset
button
3746032-700-09F.fm
0Operating instructions
Removing or installing the contactorStarting status❏ Cubicle + contactor
Steps to remove the contactor
❏ OPEN the contactor by
pressing the STOP or OPEN
pushbutton on the operating
panel.
For a mechanically-latched
contactor, verify that the
contactor is in the OPEN
position. If necessary, press
the trip button.
❏ OPEN the disconnector to
the earthed position. See
“Disconnector operation”.❏ CLOSE the cable earthing
switch, if supplied, to the
earthed position. See “Cable earthing switch operation (optional)”.
❏ Open the MV compartment door.
See “Accessing the medium voltage compartment FVNR”.
❏ Pull the contactor rail down. This will
disengage the contactor from the line
and load busbar connections.
❏ Roll the contactor out of the
enclosure. Lift to remove (25 kg).
38 46032-700-09F.fm
0Operating instructions
Steps to install the contactor
❏ Verify the disconnector is in
the OPEN and earthed
position. See “Disconnector operation”.
❏ If supplied, verify the cable
earthing switch is in the
CLOSED and earthed
position. See “Cable earthing switch operation (optional)”.
❏ Open the MV compartment
door. See “Accessing the medium voltage compartment FVNR”.
❏ Pull the contactor rail down.
❏ Seat the contactor truck wheels onto the
contactor rail.
❏ By gripping the handles (A) shown,
slowly roll the contactor into the
enclosure until it reaches the wheel stop.
❏ Lift the contactor rail to the vertical
position, engaging the contactor.
A
Wheel stop
3946032-700-09F.fm
0Operating instructions
Back light assembly (optional)
The back light assembly consists of LEDs, a pushbutton, and batteries. It is
used to help view the inside of the disconnector and the MV compartment.
When the back light pushbutton is pressed, the light illuminates.
A. The inside of the disconnector for viewing the switch blade position.
B. The inside of the MV compartment for viewing the indicators of the
cable earthing switch and the blown fuse indicator, if supplied.
Battery replacement The batteries should be replaced every 4 years to maintain proper
operation. Two AA alkaline batteries are required.
Steps for removal
❏ Remove all power from the section. See “Operating instructions”.❏ After opening the MV compartment door, remove 2 screws holding
the bottom of the operator cover to the tie channel.
❏ Open the LV door, and remove the 2 screws holding the top of the
operator cover to the operator panel. Remove the cover.
❏ The back light assembly can now be accessed to replace the batteries.
❏ Remove the batteries by pulling them straight down from their spring clips.
❏ When replacing batteries, insert the left-side battery with the
negative end nearest to the operator and the right-side battery with
the positive end nearest to the operator.
Steps to place back into operation❏ Replace the operator cover (4 M6 screws). tightening torque: 10 N•m.❏ Complete these operations in reverse order. See “Operating
instructions”.❏ Complete these electric tests in compliance with the standards
in force.
All operations described
hereafter must be carried
out in compliance with
the safety standards in
force, under the responsibility of a competent person.
Tie
channel
Operator panel
Back light pushbutton
Operator coverA
B
Left
battery
Right
battery
Negative
Positive
Front
40 46032-700-09F.fm
0Operating instructions
Cable earthing switch operation (optional)
DescriptionThe cable earthing switch is used to earth the customer load connection cables when the switch is in the
CLOSED or discharged position. It is mechanically interlocked with the disconnector and is actuated by using
the same operating handle.
Connection to earth is accomplished when the spring operated earthing bar is connected across all three phases
of the customer load terminals.
Instructions for use
Cable earthing switch operating condition
Interlock shuttle
An interlock shuttle is provided on all
FVNR starters with a cable earthing
switch.
This shuttle must be in the right-hand
position to operate the cable earthing
switch.
The interlock system requires the following conditions to be met before
the cable earthing switch can be operated:
■ The interlock shuttle must be in the right-hand position.
■ The contactor must be in the OPEN position.
■ The disconnector must be in the DISCONNECTED and EARTHED
position.
■ The MV compartment door must be closed and latched.
?
Earthing
bar
Status
window
The indicator for the cable earthing switch can be
viewed through a status window in the MV
compartment door.
Operating
handle
Un-earthed
positionEarthed
position
The cable earthing switch
operating handle is stored on
the right- or left-hand end sheet.
The cable earthing switch has no interrupting capability and is not capable of closing on the full fault current available on the system.
When used with a power transformer, key interlocks should be used between the main secondary disconnect device and the cable earthing switch to ensure proper sequencing of operation.
4146032-700-09F.fm
0Operating instructions
Closing the cable earthing switch
Opening the cable earthing switchThe interlock system requires the MV compartment door to be shut and
latched. See “Cable earthing switch operating condition”.
For performing cable injection testing, the cable earthing switch can be opened
with the MV compartment door open, however the cable earthing switch must
be returned to the closed position to allow the MV compartment door to be
closed. See “MV cable test”.
When the cable earthing switch
operating conditions have
been satisfied:
❏ Slide the cable earthing
switch access port down.
❏ Insert and rotate the handle
counter-clockwise
approximately 10 turns, or
until the handle stops.
❏ The mechanism makes a
sharp sound when it trips,
and the position indicator
moves upward to the
earthing position.
❏ The MV compartment door
can now be opened.
Open position
Closed position
Access port
When the cable earthing switch
operating conditions have
been satisfied:
❏ Slide the cable earthing
switch access port down.
❏ Insert and rotate the handle
clockwise approximately 10
turns to charge and latch
the mechanism back in the
open or unearthed position.
Continue rotating the
handle until it stops.
❏ The cable earthing switch
access port may now be
closed, allowing the
disconnector and the
contactor to be operated.
Closed position
Open position
Access port
42 46032-700-09F.fm
0Operating instructions
Removing and installing fuses
An optional fuse tool is available to
help in the removal and installation of
power fuses. Contact a field sales representative or distributor. See “Fuse tool (optional)”.
Steps to remove fuses ❏ Always remove the lower end of the fuse first. Twist the fuse while
pulling the ferrule out of the lower fuse clip.
❏ Pull the fuse down to remove it from the upper fuse clip.
See “Accessing the medium voltage compartment FVNR”.
All operations described
hereafter must be carried out
in compliance with the safety
standards in force, under the responsibility of a competent person.
Always remove all power from
the section, and use a
properly rated testing device
to confirm there is no voltage present.
IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown.
4346032-700-09F.fm
0Operating instructions
Fuse characteristics
The fuse characteristics and direction
of mounting are printed on the fuse.
When replacing the fuse, turn it so that
the label is in the front, and the striker pin is at the top.
Steps to install fuses ❏ Always insert the upper end of the fuse first. Grasp the fuse by the
upper ferrule, insert it into the upper fuse clip, and twist it while pushing
upward.
❏ Insert the lower end into the lower fuse clip.
❏ Rotate the fuse so that the label is facing the front.
All operations described
hereafter must be carried
out in compliance with the
safety standards in force,
under the responsibility of a competent person.
Always remove all power
from the section and use
a properly rated testing
device to confirm there is no voltage present.
IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown.
To ease installation,
lubricate fuse clips with
red Mobilgrease® 28.
44 46032-700-09F.fm
0Operating instructions
Fuse tool (optional) The fuse tool is an ergonomic aid for inserting and extracting fuses in
de-energized Motorpact™ motor starters. It does not protect the
operator in any way from contacting live parts.
Steps to install rear and middle fuses
The process is the same for installing fuses in the rear and middle
fuseholders. Begin by installing the rear fuses.
NOTE: Always wear gloves when
working with fuses. The fuses could
be hot and will burn unprotected
hands. The photos on these pages
are factory demonstrations.
❏ Align the fuse tool so that the hook and the pusher are toward the
handle end of the tool.
❏ Insert the hinge in the narrow vertical space in front of the
fuseholder, between the fuse holder and the fuse tray. In some
cases, this may be a tight fit. The handle should be horizontal and
extend towards the door.
hinge
handle
lifting rod
hook
pusher
hook
pusher
handle
hinge
handle
lifting
rod
fuse
holder
fuse
tray
4546032-700-09F.fm
0Operating instructions
❏ Bring the fuse into the enclosure. With the upper end of the fuse
behind the upper fuse holder, bring the lower end of the fuse to rest
on the lifting rod.
❏ Visually align the upper end of the fuse with the upper fuse clip, and
raise the tool handle to push the fuse into the upper clip. Verify that
the fuse is fully inserted into the upper clip.
❏ Lower the handle. If the fuse was fully inserted at the top, the lower
end will naturally swing into place against the opening of the lower
fuse clip.
Upper
end of
fuse
Lower
end of
fuse
Upper
fuse
holderFuse
clip
Upper fuse clip
Handle
Lower
fuse clip
Lower
end of
fuse
46 46032-700-09F.fm
0Operating instructions
❏ Rotate the pusher into position toward the hinge.
❏ Raise the handle again to push the fuse into the lower fuse clip.
PusherHinge
HandleFuse
Lower fuse clip
4746032-700-09F.fm
0Operating instructions
Steps to install front fuses
NOTE: Always wear gloves when
working with fuses. The fuses could
be hot and will burn unprotected
hands. The photos on these pages
are factory demonstrations.
❏ Align the fuse tool so that the hook is toward the handle end and the
pusher is in the opposite position, toward the hinge.
❏ Insert the hinge in the narrow vertical space in front of the
fuseholder, between the holder and the fuse tray. In some cases, this
may be a tight fit. The tool should rest on the fuse tray, and the
handle should hang down.
❏ Bring the fuse into the enclosure. With the upper end of the fuse
behind the upper fuseholder, bring the lower end of the fuse to rest
on the V-notch in the pusher. The bulk of the fuse should be on the
hinge side of the pusher.
Pusher
Handle
Fuse tray
Fuse end
restingon
V-notch
Pusher
48 46032-700-09F.fm
0Operating instructions
❏ Visually align the upper end of the fuse with the upper clip, and raise
the tool handle to push the fuse into the upper clip. Verify that the
fuse is fully inserted into the upper clip.
❏ Lower the handle. If the fuse was fully inserted at the top, the lower
end will naturally swing into place against the opening of the lower
fuse clip.
❏ Raise the handle again to push the fuse into the lower fuse clip.
Lower
fuse clip
Fuse tool
Fuse
Handle
4946032-700-09F.fm
0Operating instructions
Blown fuse indicator
The blown fuse indicator assembly is located on the line side of the MV
power fuses. Should a blown fuse occur, the power fuse striker pin will
pop up and activate the assembly. When activated, a flag is operated
that is visible through the upper window of the contactor door.
Two sets of contacts change state when the assembly is triggered. One
set of contacts sends a direct trip signal to the contactor. The second set
of contacts is available for remote indication.
Flag indicator
Blown fuse Good fuse
Flag indicator
Striker pin, top
of fuse
50 46032-700-09F.fm
0Operating instructions
Steps to remove fuses This process is the same for all fuses.
NOTE: Always wear gloves when
working with fuses. The fuses could
be hot and will burn unprotected
hands. The photos on these pages
are factory demonstrations.
❏ Align the fuse tool so that the hook is toward the hinge end of the tool
and the pusher rests in the opposite direction, toward the handle.
❏ Insert the hinge in the narrow vertical space in front of the
fuseholder, between the holder and the fuse tray. In some cases, this
may be a tight fit.
❏ Support the handle in one hand, and place the hook around the back
of the fuse as low as possible.
❏ Lower the handle to extract the fuse from the lower fuse clip.
❏ Manually pull the fuse from the upper fuse clip.
hook
5146032-700-09F.fm
0Operating instructions
52 46032-700-09F.fm
Removing and installing fuses of the Merlin Gerin Propivar power factor correction capacitors (PFCC) inside Motorpact enclosures
Steps to remove fuses Remove and replace each fuse individually to avoid swapping wires.
❏ Remove and retain the screw from the top of the connector.
❏ Remove and retain the washer.
❏ Remove and retain the connector from the top of the fuse.
❏ Loosen the jam nut at the bottom of the fuse.
❏ Unscrew the fuse from the PFCC threaded rod.
Steps to install fuses ❏ Screw the fuse onto the PFCC threaded rod. Torque the fuse
following fuse supplier specifications.
❏ Torque the jam nut against the fuse according to the fuse supplier
specifications.
❏ Screw the connector on the fuse. Torque the connector according to
the fuse supplier specifications.
❏ Install the wire lug, the washer, and the screw at the top of the
connector as shown in the figure.
❏ Torque the screw to 3 N•m.
All operations described
hereafter must be carried
out in compliance with
the safety standards in
force, under the responsibility of a competent person.
Always remove all power
from the section and use
a properly rated testing
device to confirm there is no voltage present.
Always wear gloves when working with fuses. The body of a fuse that has blown or carried load current can be extremely hot and will burn unprotected hands.
IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown.
WasherScrew
Wire lug
Connector
Fuse
PFCC threaded rod
Jam nut
PFCC
0Operating instructions
Removing and installing VT primary fuses
Steps to replace fuses ❏ Remove the load from the contactor. See “Operating the contactor”.❏ OPEN the disconnector to the earthed position. See “Opening the
disconnector”.❏ CLOSE the cable earthing switch, if supplied, to the earthed position.
See “Closing the cable earthing switch”.❏ Open the MV compartment door. See “Opening the medium
voltage compartment door”.
Steps to disassemble the fuse tube
❏ Push tube end A, and rotate counter-clockwise
❏ Loosen screw holding fuse retainer plate B.
❏ Remove fuse C.
Steps to assemble the fuse tube
❏ Replace fuse C.
❏ Tighten screw holding fuse retainer plate B to a 1 N•m torque.
❏ Align tube A in housing slot; push and rotate clockwise.
Steps to place back into operation
❏ Complete these operations in the reverse order of removal. See“Operating instructions”
❏ Complete these electric tests in compliance with the standards in force.
All operations described hereafter must be carried out in
compliance with the safety standards in force, under the responsibility of a competent person.
Always remove all power from the section and use a properly
rated testing device to confirm there is no voltage present.
A
BC
5346032-700-09F.fm
0Operating instructions
Locking using padlocks
Number of possible padlocks per section type Use Ø6 to Ø8 padlocks.
■ 1 padlock on each
disconnector—for
preventing operation.
■ 1 padlock on each cable
earthing switch—for
preventing operation.
■ 1 padlock on each incoming
cable section door—for
preventing access.
Padlocking the disconnector
❏ Place 1 padlock on the disconnector operating access port.
This lock can be used to prevent operation of the disconnector in either
the CLOSED or OPEN/earthed position.
The pictogram on the
operator cover is a
reminder of the operations.
54 46032-700-09F.fm
0Operating instructions
Padlocking the cable earthing switch
❏ Place 1 padlock on the cable earthing switch operating access port.
This lock can be used to prevent operation of the cable earthing switch
in either the CLOSED/earthed or OPEN position.
Padlocking the incoming cable section doors
❏ Place 1 padlock on each padlockable incoming cable section door,
upper and lower.
This lock can be used to prevent MV access whenever a key lock is
not requested.
5546032-700-09F.fm
0Operating instructions
Locking using keylocks (optional)
Motorpact™ can be provided with various keylock schemes based on customer needs. The typical keylock
arrangement is shown. However, for the actual arrangement, see "equipment drawings" provided with each line-up.
Number of possible locks per section type
■ 1 or 2 keylocks on each disconnector—for preventing operation
■ 1 keylock on each cable earthing switch—for preventing operation
■ 1 keylock on each RVSS soft start section or RVAT section—for
preventing access
Keylocking the disconnectorLocking the disconnector open or closed with 1 keylock
■ A keylock used to lock the disconnector OPEN or CLOSED
■ Disconnector locked OPEN:
Can be keyed to allow RVSS soft start section or RVAT MV
compartment door to be opened. Can be keyed to allow cable
earthing switch operation, if supplied
■ Disconnector locked CLOSED
■ Can be keyed to prevent disconnector from being OPENED
Can be keyed to be OPENED only if power source is de-energized
Locking the disconnector open or closed with 2 keylocks
■ B double keylock used to lock the disconnector OPEN or CLOSED
■ Disconnector locked OPEN:
Can be keyed to allow cable earthing switch operation, if supplied
Can be keyed to allow RVSS soft start section or RVAT MV
compartment door to be opened
■ Disconnector locked CLOSED:
Can be keyed to prevent disconnector from being OPENED
Can be keyed to be OPENED only if power source is de-energized
A
B
56 46032-700-09F.fm
0Operating instructions
Locking the cable earthing switch open or closed
■ C keylock used to lock the cable earthing switch OPEN or
CLOSED
■ Cable earthing switch locked OPEN:
Can be keyed to allow disconnector operation
■ Cable earthing switch locked CLOSED:
Can be keyed to allow RVSS soft start section or RVAT MV
compartment door to be opened
C
5746032-700-09F.fm
0Operating instructions
FVR (full voltage reversing bidirectional)
Description The full voltage reversing (FVR) starter is a full voltage, bidirectional
motor starter with an operating range of 2300–7200 V. This product will
deliver the highest starting torque (about 150% of full load torque) to the
motor terminals in either direction: forward or reverse. This starter bases
interrupting ratings on fused applications.
Forward contactorReverse contactor
58 46032-700-09F.fm
0Operating instructions
FVS (dual voltage transfer starter)
Description The dual voltage transfer starter (FVS) is designed to operate as part of
a smart sequence starter application or multiple motor soft starting
application.
A smart sequence starter application is a system to start multiple
motors, one at a time, with a predetermined minimum start time
between each motor start.
The FVS is part of a line-up that also includes a full voltage non-reversing
starter (FVNR) and an RVSS. One FVS is required per motor.
Main contactor
Soft start contactor
Full voltage bus Soft start flexible connector (600 A max.)
FVNR RVSS FVS FVS FVS
Soft startprotectionrelay Sepam
protectionrelay
Sepamprotectionrelay
Sepamprotectionrelay
M M M
5946032-700-09F.fm
0Operating instructions
Redundant smart sequence starter
Description The redundant smart sequence starter application takes the smart
sequence starter and adds a second RVSS soft start section. The
second RVSS section can be used as a back up to the first RVSS section
or motor starting can be toggled betweeen the two RVSS soft start sections
to allow one to cool down while the other is starting motors.
The second RVSS section also allows for one remote line-up of dual
voltage transfer starters (FVS) to be connected in addition to the close
coupled FVS line-up.
Full voltage bus Soft start flexible connector (600 A max.)
FVNR RVSS FVS FVSM MFVNR RVSS
60 46032-700-09F.fm
0Operating instructions
DDS (dual disconnect section)
Description The dual disconnect section (DDS) is designed to operate as part of a
redundant smart sequence starter application or multiple motor soft
starting application.
A smart sequence starter application is a system to start multiple
motors, one at a time, with a predetermined minimum start time
between each motor start.
The optional DDS is part of a line-up that includes two full voltage
non-reversing starters (FVNR), two RVSS soft start sections, and
multiple dual voltage starters (FVS). The DDS is located between the
RVSS and FVS sections in order to provide isolation between these
sections when maintenance is being done on the RVSS sections. The
DDS also provides cable landing for up to four remote FVS line-ups, as
well as a close coupled FVS line-up.
6146032-700-09F.fm
0Operating instructions
Full voltage bus Soft start flexible connector (600 A max.)
FVNR RVSS DDSFVNR RVSS
62 46032-700-09F.fm
0Operating instructions
2-Speed, 1-Winding
Description The 2-speed, 1-winding starter (2S1W) is designed for the control of
two-speed AC motors that have a single winding. Since the motor is
single winding, the speed change is accomplished by changing the
wiring configuration using a third contactor.
The 2S1W is part of a line-up that also includes a full voltage
non-reversing starter (FVNR).
Slow-speed contactor
Shorted contactor
6346032-700-09F.fm
0Operating instructions
2-Speed, 2-Winding
Description The 2-speed, 2-winding starter (2S2W) is designed for the control of AC
motors that have separate windings for high- and low-speed operation.
Two interlocked contactors are used, with overload protection included
for each motor winding.
Fast-speed contactor
Slow-speed contactor
64 46032-700-09F.fm
0Operating instructions
Star Delta
Description Star Delta starters are designed for the reduced voltage starting of
medium voltage motors by changing the configuration of the motor
windings from a Star to a Delta AC configuration without lowering the
current.
The Star Delta is part of a line-up that also includes a full voltage
non-reversing starter (FVNR).
Star-connection contactor
Delta-connection contactor
6546032-700-09F.fm
0Operating instructions
RVAT (reduced voltage autotransformer)
Description The Reduced Voltage Autotransformer (RVAT) is used to provide a
reduced voltage to the motor terminals during starting. This is achieved
by the use of an autotransformer. Typically two types of
autotransformers are available.
■ Tapped—permits changing taps to change the output voltage to the
motor terminals
■ Non-tapped—specifically designed for the application and motor
In this manual, the tapped autotransformer is shown and discussed. For
an application using a non-tapped autotransformer, all information
provided is applicable other than the instruction for changing the tap
settings.
The section size of an RVAT is dependent upon the transformer rating.
The RVAT is always controlled from a main contactor section adjacent
to the left and the motor cable connections are made in this line
contactor section.
Each RVAT section is equipped with the following:
■ run contactor
■ start contactor
■ autotransformer
■ surge arresters
Limited duty cycle rating The reduced voltage starters contain an autotransformer with a limited
duty cycle rating. Unless otherwise noted, these devices are rated per
IEC 60076-11. Longer start times or more frequent starts will shorten
the life of this device.
RVAT interiorRVAT exterior
Start contactor
Run contactor
Autotransformer
Door latch keylock
66 46032-700-09F.fm
0Operating instructions
Keylocks on an RVAT
Keylocking with disconnector (without cable earthing switch)
The RVAT section is supplied with key interlocks between the
disconnector in the main contactor section and the start and run
contactor compartments and the autotransformer compartment.
With the disconnector in the CLOSED position, the key is held
captive. During maintenance, the disconnector can be OPENED/
earthed and the key removed for access to the RVAT section. See“Disconnector operation” and “Accessing the medium voltage compartments RVAT or RVSS soft start section”.
Keylocking (with cable earthing switch)
When a cable earthing switch is supplied, the RVAT section is
supplied with key interlocks between the cable earthing switch in
the main contactor section and the start and run contactor
compartments, and the autotransformer compartment.
With the cable earthing switch in the OPEN or unearthed position,
the key is held captive. During maintenance, the cable earthing
switch can be CLOSED/earthed and the key removed for access to
the RVAT section. See “Cable earthing switch operation (optional)” and “Accessing the medium voltage compartments RVAT or RVSS soft start section”.
A spare key is supplied with every RVAT section. For safe operation, only 1 key should be used. The spare key should be stored away from the equipment and only used if 1 key is lost.
Using both keys could give access to live parts and could cause death or serious injury.
6746032-700-09F.fm
0Operating instructions
RVAT operation
Autotransformers Autotransformers are normally tapped at 50%–65%–80%. The standard
factory setting used is 65%. Standard reduced-voltage starters make
the transition from reduced to full voltage based on the operation of a
current transition relay. As the motor accelerates, the current drawn will
decrease. When the motor is near full speed, the relay will sense the
drop in current and initiate the transition to full voltage.
Relay setting The current transition relay setting is user selectable with 100% being
the recommended default setting. An incomplete sequence timer will
open the starter if the current relay has not initiated transition before the
timer times out. The timer should be set to a maximum of 30 seconds.
The current relay setting may be increased to its maximum value of
120% if transition does not occur.
Tap setting If the starter does not transition in 30 seconds with the current relay set
at its maximum of 120%, the motor does not have sufficient starting
torque for the connected load. The motor must be unloaded or the
starting torque increased.
To increase starting torque, the autotransformer must be moved from
the 65% tap setting to the 80% tap setting.
steps to change tap settings
❏ OPEN the main contactor controlling the equipment by pressing the
STOP or OPEN pushbutton on the operating panel of the main
contactor. See “Operating the contactor”.❏ OPEN the disconnector in the main contactor to the earthed position.
See “Disconnector operation”.❏ If supplied, CLOSE the cable earthing switch to the earthed position.
See “Cable earthing switch operation (optional)”.❏ Using the key from the main disconnector or cable earthing switch if
supplied, OPEN the keylock allowing access to the MV
compartments. See “Accessing the medium voltage compartments RVAT or RVSS soft start section”.
❏ Change tap setting cable connections as needed. See "autotransformer cable connections" in the installation instruction guide.
All operations described
hereafter must be carried
out in compliance with the
safety standards in force,
under the responsibility of a competent person.
Autotransformer taps
Transition based on a simple timing relay is not recommended. Increased loads may be placed on the power system, starter, motor, and driven equipment if a transition occurs before the motor is up to speed. If this method is used, refer to the electrical schematics provided with the line-up.
68 46032-700-09F.fm
0Operating instructions
S
The transition between the start and
run contactors is made through the
electrical control package; therefore,
the operational steps are the same as
an FVNR.
Steps to CLOSE❏ OPEN or unearth the cable
earthing switch, if supplied. See “Cable earthing switch operation (optional)”.
❏ CLOSE the disconnector. See“Disconnector operation”.
❏ Press the START or CLOSE
pushbutton on the operator panel.
Steps to OPEN❏ Press the STOP or OPEN
pushbutton on the operator panel.
All operations described hereafter must be carried out in compliance with the
safety standards in force, under the responsibility of a competent person.
$( 4 $+ + 4 0
4# 4" "
34* 3
Operator panel main contactor section
Operator panel
Main contactor
RVAT
6946032-700-09F.fm
0Operating instructions
Reduced voltage soft starter (RVSS) soft start section
Description The RVSS soft start section is designed with heavy duty components to
provide a soft motor start suitable form most demanding applications.
Typical applications are as follows:
■ conveyor motor
■ fans
■ pumps
■ mining equipment
■ crushers
■ grinders
■ chillers
■ compressors
Like the RVAT section, the soft start section is always controlled from an
FVNR starter adjacent to the left of the RVSS soft start section. All
motor cable connections are made in this main FVNR. See "loadbox cable connection" in the installation instruction guide for cable
connection information.
For specific detailed instruction on ratings, operation, programming,
control connections, start-up, maintenance, replacement parts and
troubleshooting, see Schneider Electric bulletin 46032-700-10_.
Each RVSS soft start section is equipped with the following:
■ bypass contactor
■ silicon starter rectifier
■ microprocessor-based control system
■ digital display
RVSS soft start section interiorRVSS soft start section exterior
Bypass contactor or
PLC (depending on
application)
Digital
display
Microprocessor
based control
system
SCR
assembly
Door latch
keylock
70 46032-700-09F.fm
0Operating instructions
Keylocks on an RVSS soft start sectionKeylocking with disconnector (without cable earthing switch)
The RVSS soft start section is supplied with key interlocks
between the disconnector in the main contactor section and the
bypass contactor compartment.
With the disconnector in the CLOSED position, the key is held
captive. During maintenance, the disconnector can be OPENED/
earthed and the key removed for access to the RVSS soft start
section. See “Disconnector operation” and “Accessing the busbar compartments—RVAT or RVSS soft start section”.
Keylocking with cable earthing switch
When a cable earthing switch is supplied, the RVSS soft start
section is supplied with key interlocks between the cable earthing
switch in the main contactor section and the bypass contactor
compartment and soft start power compartment.
With the cable earthing switch in the OPEN or unearthed position,
the key is held captive. During maintenance, the cable earthing
switch can be CLOSED/earthed and the key removed for access to
the RVSS soft start section. See “Cable earthing switch operation (optional)” and “Accessing the medium voltage compartments RVAT or RVSS soft start section”.
Keylocking with redundant S3 The RVSS soft start sections in a redundant S3 line-up are
supplied with key interlocks between the disconnectors in the main contactor sections and the FVS sections. It is important that the
key interlocking scheme agreed upon between the customer and
Schneider Electric is followed to make sure the RVSS soft start section MV doors cannot be opened unless the disconnectors in
both main contactors and the FVS sections are all open.
Keylocking with redundant S3 with dual disconnect section (DDS)
The RVSS soft start sections in a redundant S3 line-up are
supplied with key interlocks between the disconnectors in the main contactor sections and the DDS. It is important that the key
interlocking scheme agreed upon between the customer and
Schneider Electric is followed to make sure the RVSS soft start section MV doors cannot be opened unless the disconnectors in
both main contactors and the DDS are all open.
A spare key is supplied with every RVSS soft start section. For safe operation, only 1 key should be used. The spare key should be stored away from the equipment and only used if 1 key is lost.
Using both keys could give access to live parts and could cause death or serious injury.
7146032-700-09F.fm
0Operating instructions
Removing a contactor from an RVAT section or RVSS soft start section
Preliminary steps ❏ OPEN the main contactor section controlling the equipment by
pressing the STOP or OPEN pushbutton on the operating panel
of the main contactor section. See “Operating the contactor”.❏ OPEN the disconnector in the main contactor section to the
earthed position. See “Disconnector operation”.❏ If supplied, CLOSE the cable earthing switch to the earthed
position. See “Cable earthing switch operation (optional)”.❏ Using the key from the main disconnector or cable earthing
switch if supplied, OPEN the keylock allowing access to the MV
compartments. See “Accessing the medium voltage compartments RVAT or RVSS soft start section”.
Steps to remove a start, run, or bypass contactor
An RVAT section is shown. However, the
process is the same for RVSS soft start
sections.
❏ Pull the contactor rail down. This will disengage the contactor
from the line and load busbar connections.
❏ Roll the contactor slowly out of the
section until it rests in the wheel slot at
the end of the contactor rail.
❏ Carefully lift the contactor out of the
guide holding the rear wheel, and off
of the contactor rail.
All operations described hereafter must be carried out in
compliance with the safety standards in force, under the responsibility of a competent person.
Use extreme caution wile handling the contactor (25 kg) during this process. An optional lift truck is available. See "using a lift truck."
Wheel slotContactor
rail
Guide
72 46032-700-09F.fm
0Operating instructions
Installing a contactor in an RVAT section or RVSS soft start section
Preliminary steps ❏ OPEN the main contactor section controlling the equipment by
pressing the STOP or OPEN pushbutton on the operating panel
of the main contactor. See “Operating the contactor”.❏ OPEN the disconnector in the main contactor to the earthed
position. See “Disconnector operation”.❏ If supplied, CLOSE the cable earthing switch to the earthed
position. See “Cable earthing switch operation (optional)”.❏ Using the key from the main disconnector or cable earthing
switch if supplied, OPEN the keylock allowing access to the MV
compartments. See “Accessing the medium voltage compartments RVAT or RVSS soft start section”.
Steps to install a start, run, or bypass contactor
An RVAT section is shown; however, the process is the same for
RVSS soft start section.
❏ Pull the contactor rail down.
❏ Seat the rear wheel of the contactor
between the contactor rail and the
guide.
❏ Rest the front of the contactor onto
the contactor rails.
❏ Slowly roll the contactor into the
section until it reaches the wheel stop.
❏Lift the contactor rail to the vertical position, engaging
the contactor.
All operations described hereafter must be carried out in
compliance with the safety standards in force, under the responsibility of a competent person.
A locking plate is used to prevent a contactor from being
installed in the wrong section. If insertion is blocked, verify that the amperage and contactor type are correct.
Use extreme caution while handling the contactor (25 kg)during this process. An optional lift truck is available. See "using a lift truck."
Contactor
rail Guide
Wheel stop
7346032-700-09F.fm
0Operating instructions
Using a lift truck (optional) A lift truck is available for removing or installing contactors in an RVAT
section or RVSS soft start section. Contact your local field sales
office or distributor.
Use this device with all guidelines and processes explained in:
❏ “Removing a contactor from an RVAT section or RVSS soft start section”
Removing contactor with a lift truck
contactor
lift truck
74 46032-700-09F.fm
0Operating instructions
MDT107 thermal diagnostic system (optional)
The MDT107 Thermal Diagnostic System is mounted in the equipment
at the factory for shipping. Wiring connections must be completed and
tested on site before putting the equipment into service.
Description The MDT107 Thermal Diagnostic system is used to measure the
temperature of medium voltage circuits. Using Schneider Electric
patented technology, the MDT107 system provides:
■ continuous monitoring of temperature rise of power circuits at upper
fuse holders and customer cable connections.
■ triggering of a pre-alarm, then an alarm by activation of outputs on
dry contacts.
■ visual indication of the zone and phase in which a temperature rise
exceeds a set threshold.
The MDT107 system includes:
■ An MDT107 electronic module mounted on a DIN rail in the LV
cabinet of the Motorpact™ unit. The module transmits calibrated
impulses to 1 or more circuits via optical fibers. The calculation of a
circuit’s temperature is based on the impulses the circuit sends back
to the module.
■ 2 CFO733 temperature sensors. Each of these factory-built
assemblies includes 3 sensor heads, 3 optical fibers, and the
connector for connecting to the readout module. The sensor heads
are made from a light-sensitive material whose fluorescence time
depends on temperature. The connector incorporates an optical-
electric conversion circuit, eliminating the need for optical
connections during installation.
■ Accessories for factory installation of the sensors in the MV panel.
7546032-700-09F.fm
0Operating instructions
Functions The MDT107 module performs the following functions:
Monitoring of temperature buildup in 2 zones
Each CFO733 sensor corresponds to a 3-point zone to be monitored in
the panel, monitoring being based on temperature rise. The module
measures the temperature at 3 points per zone, as well as the ambient
temperature in order to calculate the temperature rise for each point.
Given the temperature differences between the inside of the LV cabinet
and the outside of the enclosure, correction of the ambient temperature
measured by the module is configured by means of an additional
setting.
Comparison monitoring is used with a maximum temperature rise
threshold, which may be adjusted separately for each zone and is
common to the 3 measurement points. This form of monitoring is
completed by a fixed maximum absolute sensor temperature threshold.
Therefore, the module includes 3 settings, to which access is sealed after
the ambient temperature settings are made on site.
Triggering of a pre-alarm When the temperature rise at 1 of the 3 points reaches a first set point
equal to 85% (1) of the preset threshold for the zone, or when 1 of the 3
points reaches the maximum absolute temperature of 115 °C
(239 °F), a pre-alarm is generated that results in:
— activation of the pre-alarm indication relay common to the
2 zones.
— activation in flashing mode of 1 of the 6 front panel indicators that identify
the zone and related point.
Triggering of an alarm When the temperature rise at 1 of the 3 points reaches the preset
maximum threshold (2) for the zone, or when 1 of the 3 points reaches
the maximum absolute temperature of 120 °C (248 °F), an alarm is
generated that results in:
— activation of the alarm power relay common to the 2 zones.
— activation in constant mode of 1 of the 6 front panel indicators that
identify the zone and related point.
(1) This is a fixed value; it can not be modified.
(2) These 7 setting values are defined at the factory. They are identified as A to G. See “Wiring and operation for MDT107”.
76 46032-700-09F.fm
0Operating instructions
Self-monitoring of the module The MDT107 module has internal self-tests and is equipped with an
indicator that indicates availability:
Availability
indicator
— each time the module is initialized. The indicator
turns on in constant mode when the module is
switched on and then turns off after the module
initialization phase is successfully completed,
unless the required sensors are missing (see “Self-monitoring of sensors”below).
— in steady-state operation. If a fault is detected, the
indicator turns on in constant mode.
In both cases, the pre-alarm output contact is also
activated when the indicator is steadily on.
Self-monitoring of sensors The module provides continuous monitoring of the connected sensor(s).
An “Off” position is included in the settings for each zone for the various
situations that can occur:
■ If no sensors are connected to the module, the:
— indicator is on and flashes
— pre-alarm output contact is activated
— 6 sensor identification indicators are off
■ If 1 of the 3 points of each sensor is detected as being faulty (cut or
damaged fibers, malfunction of sensor-embedded electronics, etc.), the:
— indicator is on and flashes
— pre-alarm output contact is activated
— indicator linked to the faulty measurement point flashes
■ When only 1 zone is connected, the unused zone should be set to
“Off”. If this is not done, the 3 points of the related zone are detected
as being faulty.
7746032-700-09F.fm
0Operating instructions
WiringWiring and operation for MDT107
Ratings
7
offG
F
EC
B
A
D
offG
F
EC
B
A
D
Zone B
Zone A
DT° build-upsetting
-18-16
-14
-12-8
-6-4
-10
Ambient T°correction(°C)
Zone B Zone A
L3
L1
L2
on
AB
Terminals
25 and 26
not used
5 relay output, dry contact,
connection terminals
Pre-alarm (1NO, 20-21) Alarm
(1NCNO; 22-23-24)
24–250 Vdc and 110–240
Vac power supply
connection terminals
6 red indicators identifying
the sensor (zone A or B)
and the circuit/sensor at
the origin of the alarm
Green “power on” indicator
and red “availability”
indicator
Ambient
temperature
correction
setting switch
Module grounding terminal
via green/yellow wire
(PE, safety of personnel)
Temperature
rise threshold
setting
switches
NOTE: The module's screw type
connectors can receive 2 wires with
maximum cross-section of 2.5 mm2
with or without fittings.
Optical fiber probes CFO733highest voltage for the equipment 17.5kV
rated power frequency voltage 38kV
impulse voltage 95 kV
maximum fiber/sensor temperature 120 °C (248 °F)
MDT107 moduletemperature rise setting factory set
operating and storage temperature- 25 °C to +70 °C
(-13 °F to +158 °F)
absolute maximum
threshold values
pre-alarm = 115 °C (239 °F)
alarm = 120 °C (248 °F)
Multi9 profile width 10.5 cm (4.13 in.)
module power supply 24/250 Vdc, 110/240 Vac
dry contacts voltage24, 48, 127, 220 Vdc,100 to 240 Vac
continuous current5A permanent (pre-alarm)
8A permanent (trip)
consumption (standby to max.)
ACDC
< 1.2 W (stby) to < 3.4 W (max)< 4.4 W (stby) to < 6.6 W (max)
78 46032-700-09F.fm
0Operating instructions
MDT107 module location
Precaution: Use caution when working in the enclosure near the MDT107 sensors. The sensor heads can be damaged easily.
Fieldshapers
Loadbox
7946032-700-09F.fm
0Operating instructions
MDT107 sensors location
Setting the temperature rise thresholds
The module is equipped with 2 mechanical selector switches for setting
the temperature rise threshold for each zone. Each switch has 8
possible setting positions. The factory settings are shown in the table below.
The selector switches are accessible from the front panel. They are
protected by a sealed cover. To change the setting for a zone:
Steps to set the temperature rise thresholds
❏ Remove the protective cover.
❏ Insert the tip of a screwdriver into one of the arrow-shaped slots.
NOTE: Use a flathead screwdriver with a tip width of 0.15 in. (4 mm).
❏ Turn the switch to the desired setting.
❏ Replace the protective cover.
Load Box
Field Shapers
Zone B
Zone A
offG
F
E
C
BA
D
offG
F
E
C
BA
D
ΔT° build-upsetting
Contactor rated current (A)
Zone Afield shapers connection
Zone Bload box connection
200 C B
400 E D
450 F D
720 G C
80 46032-700-09F.fm
0Operating instructions
Setting the ambient temperature correction
The module contains a mechanical selector switch for correcting the
ambient temperature measured on the MDT107 module. The switch has
8 possible setting positions. It is accessible from the front panel and is
protected by a sealed cover. To change a setting:
Steps to set the ambient temperature
❏ Measure the temperature in the LV cabinet where the MDT107
module is located, then measure the ambient temperature outside
the switchgear. Note the difference in temperature between the two
locations.
❏ Remove the protective cover.
❏ Insert the tip of a screwdriver into the arrow-shaped slot.
NOTE: Use a flathead screwdriver with a blade width of 0.15 in. (4 mm).
❏ Turn the switch to the setting closest to the temperature difference
measured in step 1.
❏ Replace the protective cover.
Ambient T°correction(°C)
-18 -4-6
-8
-10-12
-14
-16
8146032-700-09F.fm
0Operating instructions
Troubleshooting The following troubleshooting chart is provided to help minimize
downtime. If the proposed solutions do not correct the problem, please
contact the Schneider Electric Service Center.
Symptoms Faulty devices Probable causes and solutions
green indicator
is offexternal power supply
ensure the power supply is present and
connected
insufficient voltage
(out of range)
MDT107 module is faulty and must be
replaced
red indicator
remains on
after energizing
setting selection switches if indicators L1
to L3 are flashing
incorrect positioning of selector switches
(for example, 1or more switches is
between 2 positions)
indicators L1 to L3 Zones A and B are offMDT107 module is faulty and must be
replaced
red indicator
is flashing
probe connection
the probe(s) are not connected, or the
associated selector switch is in the "Off"
position
probes or sensorsfaulty probe or sensor that must be
replaced
MaintenancePreventative maintenance Inspect the equipment periodically to determine the conditions to which
the units are subjected. After determining the environmental conditions
according to the guidelines in this section (see “Environmental conditions”below), perform inspections and maintenance according to
the following table.
Recommended inspection/maintenance guidelines
Component Ideal conditions Standard conditions
Aggressive conditions
polyester disconnector housing
housing interior (busbar and mechanism)
housing
every 5 years every 2 years once per year
See “Environmental conditions” for definitions.
Inspect the equipment immediately after abnormal or stressful operating
conditions occur, or after the equipment experiences a fault current.
These inspection/maintenance guidelines cover only the starter. If
conditions cannot be established and documented, assume the
operating conditions are aggressive.
These inspection/maintenance guidelines do not warrant any field
connections, field modifications, or supersede any maintenance
procedures or schedules recommended by component manufacturers.
82 46032-700-09F.fm
0
8346032-700-09F.fm
0Maintenance
Environmental conditionsIdeal conditions ■ Unit is installed and commissioned in accordance with the
manufacturer’s instructions.
■ Humidity is below 40%, and there is no dripping water
■ Indoor, protected from the weather
■ Minimum of dust and air circulation
■ Ambient temperature is between - 5 °C and 40 °C
■ Altitude less than or equal to 1000 m, if above 1000 m, a derating
coefficient will be applied (please consult us)
■ No contact with any chemical agents (salt, H2S, etc.)
■ No infestation of any animal life (rodents, insects, etc.)
■ No contact with any plant life (mold, etc.)
■ No earth movements
■ No damage to the unit of any kind
■ No operating problems of any kind
■ No abnormally high number of operations
■ No abnormally high number of faults
■ No overvoltage or overcurrent (above ratings)
■ Thermal scanning of the joints (where possible) at least once a year,
or optional thermal diagnostics unit is installed
Standard conditions Same as "ideal conditions" with the following exceptions:
■ Humidity below 60%
■ The unit must not be subjected to regular extremes of temperatures
greater than 40 °C or less than - 30 °C
■ No regular thick covering of leaves or other debris
Aggressive conditions Any environmental conditions that have:
■ Humidity above 60%
■ Unit subjected to temperatures greater than 40 °C or less than - 30 °C
84 46032-700-09F.fm
0Maintenance
Inspecting the equipment
This product is warranted per “Square D Conditions of Sale”, see Schneider Electric document 0100PL0041, and has been tested
under ideal laboratory conditions to the values listed below:
■ 1000 mechanical no load operations
■ 3 fuse fault transfer current operations (see IEC 62271-105C for
application)
Motorpact™ has been designed and tested to IEC 60470 and related
IEC standards. The mechanical life of the disconnector is 5000
operations.
To verify the contact life of the contactor, see Schneider Electric bulletin 46032-700-02, Motorpact™ 200/400/450 A Vacuum Contactors.
To ensure the starter is properly maintained, perform at least the
following inspection procedures:
Busbar connections: De-energize the primary and secondary
circuits. Perform a standard hi-pot test to measure busbar insulation
integrity (see "hi-pot dielectric test" in Schneider Electric bulletin 46032-700-08_, Motorpact IEC Installation Guide).
Inspect the connections for symptoms that indicate overheating or
weakened insulation. Remove dust from the surfaces of the busbars,
connections, supports, and enclosures. Wipe clean with a solvent
such as denatured alcohol. Vacuum the equipment. Do not use
compressed air to blow dust from the surfaces inside the starter.
Maintain the instruments, relays, and other devices according to the
specific instructions supplied. Inspect the devices and their contacts
for dust or dirt; wipe clean as necessary. The maintenance schedule
for individual devices such as meters and relays should be based
upon recommendations contained in the individual instruction guide
for each device. Coordinate the various schedules with the overall
maintenance program.
Inspect control wiring connections for tightness and damage.
Manually operate mechanical moving parts such as switch
assemblies, interlocks, and doors.
Make sure all busbar areas are well ventilated. Inspect grille work
and air passages on starters to make sure they are free from
obstruction and dirt accumulation.
Verify all tools and/or hardware have been removed from the
MV compartment.
Replace all devices, doors, and covers with their original
mounting hardware.
All operations described hereafter must be carried out in
compliance with the safety standards in force, under the responsibility of a competent person.
8546032-700-09F.fm
0
86 46032-700-09F.fm
0Replacement parts
Replacement parts
Corrective maintenance
operations allow for
malfunctioning subassemblies
to be replaced.
The operations mentioned in
the summary table hereafter
can be carried out by the
customer or by Schneider Electric After Sales agents.
For any other intervention, call upon the nearest Schneider Electric group agents.
After each maintenance, carry out electric tests in compliance with the standards in force.
Careful: During replacement,
all the following accessories
must absolutely be replaced by
new equipment.
— nylstop (self-locking nut)
— contact washer
— stop rings
— mechanical pin
description part number catalog numberauxiliary switch (blown-fuse indicator) 25713203 AAF00956
auxiliary switch-contacts (disconnector) S48198 AAF00955
auxiliary switch-terminal blocks (disconnector) S47074 AAF00955
control plug–contactor (female) MIP30F00830-359.0 AAF00950
control plug–contactor (male) MIP30M0000-0233 AAF00950
control plug–7 pin (female) 1925744 AAF00952
control plug–7 pin (male) 1925919 AAF00952
control plug–7 pin assembly frame 1852079 AAF00951
control plug–12 pin (female) 1925799 AAF00953
control plug–12 pin (male) 1925964 AAF00953
control plug–12 pin assembly frame 1852121 AAF00951
fuse tool (removal, installation) 46033-250-51 AAF00174
handle, operator 3728693 AAF00954
heater, one-high 46028-126-03 AAF00006
Mobilgrease® 28, red 1615-100950 consult us
VPIS/LLI module 51193386F0 consult us
contactor partsauxiliary contact block-contactor (latched) PR00620P70 consult us
auxiliary contact block-contactor (magnetically held, standard) PC18601P012 AAF00967
closing coil kit-contactor (120/240 Vac) PC18601P020 AAF00963
contact spring kit PC18601P121 AAF00968
drive unit-contactor (printed circuit board) PC18601P016 AAF00962
latched kit-contactor (24 Vdc) 3Z9G0119G003 AAF00346
latched kit-contactor (32 Vdc) 3Z9G0119G004 AAF00347
latched kit-contactor (48 Vdc) 3Z9G0119G005 AAF00350
latched kit-contactor (125 Vdc) 3Z9G0119G001 AAF00351
latched kit-contactor (250 Vdc) 3Z9G0119G002 AAF00348
line/load connector 46032-243-01 AAF00903
opening spring-contactor PR01109P70 Included in latched-kit
replacement of main fuses consult a Schneider Electric representative consult us
replacement of VT fuses consult a Schneider Electric representative consult us
shunt lead kit-contactor PC18601P101SQ AAF00964
trip coil-contactor (24 Vdc) PC18601P015 Included in latched-kit
trip coil-contactor (48 Vdc) PC18601P015 Included in latched-kit
trip coil-contactor (125 Vdc, standard) PC18601P003 Included in latched-kit
trip coil-contactor (250 Vdc) PC18601P004 Included in latched-kit
vacuum interrupter bottle-contactor PC18601P007 AAF00961
wear gauge-contactor PC18601P115 AAF00965
other electrical components refer to specific order bill of materials
8746032-700-09F.fm
0
88 46032-700-09F.fm
0Troubleshooting
Troubleshooting
❏ MV compartment doorcannot be opened
Check that the disconnector is in the OPEN/earthed position.
Check that the disconnector access port is CLOSED.
❏ Disconnector cannot be
operated
Check that the MV compartment door is CLOSED and the handle
latched.
Check that the contactor is in the OPEN position.
Check that the earthing switch (if supplied) is OPEN and the access
port is CLOSED.
❏ Disconnector access portcannot be CLOSED
Check that the disconnector is fully OPEN or earthed.
Check that the key interlock keys (if supplied) are in the proper position.
❏ Disconnector access portcannot be OPENED
Check that the disconnector is fully OPEN or earthed.
Check that the key interlock keys (if supplied) are in the proper position.
❏ Cable earthing switchcannot be operated
Check that the contactor is in the OPEN position.
Check that the disconnector is in the OPEN/earthed position.
Check that the MV compartment door is CLOSED and the handle is
latched.
Check that the disconnector operating access port is OPEN.
❏ Contactor will not CLOSE
electrically
Check that the disconnector is CLOSED.
Check that the disconnector access port is CLOSED.
Check the control fuses.
Check the closing coil circuit.
Check for loose terminal connections.
Check for a loose plug connection in the LV cabinet.
Check the electrical interlocks. See "equipment drawings" provided with each line-up.
Check the interlock linkage to the contactor.
❏ Latched contactor will not
OPEN electrically
Check the control fuses.
Check the trip coil circuit.
Check for loose terminal connections.
Check for loose plug connections in the LV cabinet.
Check the electrical interlocks. See "equipment drawings"provided with each line-up.
❏ Voltage presence indicatordoes not illuminate
Test for voltage on 2 of the test ports on the indicating box. Verify the
MV voltage is truly present.
All operations described hereafter must be carried out in
compliance with the safety standards in force, under the responsibility of a competent person.
8946032-700-09F.fm
0
90 46032-700-09F.fm
0Glossary
auxiliary contacts Sets of contacts mechanically operated by the disconnector or
the contactor.
auxiliary section A section that contains either low voltage or medium voltage components
that require a different mounting than a typical starter section.
busbar compartment The compartment isolating the through or main busbars in a
Motorpact™ switchboard line-up.
cable earthing switch A sliding 2-position device (CLOSED position earthed). Designed to
discharge the capacitance to earth up to a 5 kA fault.
capacitive divider A capacitor attached to the phase busbar that is used to send a reduced
voltage signal to a neon light for voltage presence indication.
contactor The mobile vacuum interrupting device used for establishing and
interrupting the medium voltage power in the circuit.
control power transformer (CPT) A transformer that reduces medium voltage to low voltage for control circuit
use.
current transformer (CT) An instrument transformer intended to have its primary winding connected
in series with the conductor carrying the current to be measured or
controlled.
disconnector A rotating, 2-position switch that is used to connect the main power source
in the closed position and to connect to the equipment earth in the open
position.
enclosure The external surface of a section that prevents access to the section’s
internal parts.
full voltage starter A motor starter which connects the line voltage across the motor terminals
in one step.
fuse, medium voltage A medium voltage fuse capable of interrupting all currents from the rated
breaking capacity to the minimum breaking current I3.
fuse ferrule A cylindrical fuse terminal at the end of a cartridge fuse.
fuseholder An assembly of insulated fuse tubes that house the primary contacts of the
medium voltage fuse connection for the CPT and VT fuses.
insulator A device intended to insulate and give rigid support to busbars throughout
the equipment.
interlocks A device actuated by the operation of some other device to govern
succeeding operations. The interlocks are classified into three main
divisions: mechanical, electrical, and key interlocks.
9146032-700-09F.fm
0Glossary
internal arc tunnel An air chamber or compartment attached to the roof of the switchboard line-
up. This compartment is designed for containing or distributing the gases
should an internal arc event occur.
internal arc withstand A description for the added features of the enclosure which help in the
withstand or containment of a gas discharge should an internal arc event
occur.
low power current transformer (LPCT)
A device that transforms a medium voltage circuit current into a
proportional low voltage signal.
medium voltage compartment A switchboard compartment which houses any medium voltage devices.
power factor correction capacitor (PFCC)
A device that counteracts the undesirable effects of electric loads which
create a power factor less than 1.
shipping section Any combination of Motorpact™ units shipped together.
starter The combination of all the switching means necessary to start and stop a
motor with suitable overload protection, i.e., a section mounting a contactor
and fuses that is used for starting motors.
stress cone Pre-manufactured insulated cable termination recommended for all
incoming/outgoing and load connections.
surge arrester A device intended to protect equipment from electrical overvoltage.
voltage presence indication system (VPIS)
The VPIS is a light module mounted on the front of the equipment that gives
an indication when voltage is present on the MV cables. Energy is provided
from a capacitive divider (see definition for capacitive divider).
voltage transformer (VT) An instrument transformer intended to have its primary winding connected
in shunt with a power supply circuit for measuring the voltage.
wiring harness Pre-manufactured wiring bundles or connections.
92 46032-700-09F.fm
9346032-700-09F.fm
S
3
C
F
T
R
Cw
4
The Schneider group service centers are at your service for:
-engineering and technical assistance,
-commissioning,
-training,
-preventive and corrective maintenance,
-adaptation, and
-spare parts.
Contact your sales representative who will put you in touch with your nearestSchneider group service center or call us on 33 (0)4 76 57 60 60 (Grenoble, France).
46032-7
00-0
9F
©2004–201
1S
chneid
er
Ele
ctr
icA
llrights
reserv
ed.
chneider Electric Industries SAS
5, rue Joseph Monier
S 30323
- 92506 Rueil Malmaison Cedex (France)
él. : +33 (0)1 41 29 70 00
CS Nanterre 954 503 439
apital social 896 313 776 €ww.schneider-electric.com
6032-700-09F 11/2011
As standards, specifications, and designs change from time to time, please ask for confirmationof the information given in this publication.
This document has been printed on ecological paper.