42_18_46_EN_I
Transcript of 42_18_46_EN_I
-
8/10/2019 42_18_46_EN_I
1/36
Operating Instruction42/18-46-EN
I/P signal converter TEIP11, TEIP11-PS
hab
-
8/10/2019 42_18_46_EN_I
2/36
Blinder Text
2 TEIP11, TEIP11-PS 42/18-46-EN
I/P signal converterTEIP11, TEIP11-PS
Operating Instruction42/18-46-EN
10.2012Rev. I
Translation of the original instruction
Manufacturer:ABB Automation Products GmbHProcess AutomationSchillerstrae 7232425 MindenGermanyTel.: +49 551 905-534Fax: +49 551 905-555
Customer service centerPhone: +49 180 5 222 580Fax: +49 621 381 [email protected]
Copyright 2012 by ABB Automation Products GmbHSubject to changes without noticeThis document is protected by copyright. It assists the user in safe and efficient operation of the device. The contents of thisdocument, whether whole or in part, may not be copied or reproduced without prior approval by the copyright holder.
Contents
-
8/10/2019 42_18_46_EN_I
3/36
-
8/10/2019 42_18_46_EN_I
4/36
Contents
4 TEIP11, TEIP11-PS 42/18-46-EN
9.3 TEIP11-PS ................................................................................................................................................... 23 9.3.1 Output (pneumatic) ............................................................................................................................... 23 9.3.2 Power supply (pneumatic) .................................................................................................................... 23 9.3.3 Transmission data and influences ........................................................................................................ 23 9.3.4 Operating conditions at installation site ................................................................................................ 24 9.3.5 Design for block mounting .................................................................................................................... 24
9.3.6
Design for field housing unit (plastic) .................................................................................................... 24
9.3.7 Accessories ........................................................................................................................................... 24 9.3.8 Spare parts ............................................................................................................................................ 24
10 Ex relevant specifications ......................................................................................................................... 25 10.1 TEIP11/TEIP11-PS ...................................................................................................................................... 25 10.2 ATEX / GOST ............................................................................................................................................... 25
10.2.1 Flameproof enclosure ........................................................................................................................... 25 10.3 Operation as intrinsically safe equipment .................................................................................................... 25
10.3.1 Intrinsically Safe FM .............................................................................................................................. 26 10.3.2 Non-Incendive FM ................................................................................................................................. 26 10.3.3 Intrinsically Safe CSA............................................................................................................................ 26 10.3.4 Non-Incendive CSA............................................................................................................................... 26
11 Dimensions ................................................................................................................................................. 27 11.1 TEIP11/TEIP11-PS ...................................................................................................................................... 27
11.1.1 Design for control room housing unit for rail mounting ......................................................................... 27 11.1.2 Design for aluminum or stainless steel field housing unit ..................................................................... 28
11.2 TEIP11-PS ................................................................................................................................................... 29 11.2.1 Design for control room housing unit for block mounting...................................................................... 29 11.2.2 Design for plastic field housing unit ...................................................................................................... 30
11.3 TEIP11 .......................................................................................................................................................... 31 11.3.1 Design for field housing unit as a mounting module for OEM applications .......................................... 31
12 Appendix ..................................................................................................................................................... 32 12.1 Approvals and certifications ......................................................................................................................... 32
-
8/10/2019 42_18_46_EN_I
5/36
Safety
42/18-46-EN TEIP11, TEIP11-PS 5
1 Safety
1.1 General information and notes for the reader
You must read these instructions carefully prior to installing and commissioning the device.These instructions are an important part of the product and must be kept for future reference.These instructions are intended as an overview and do not contain detailed information on alldesigns for this product or every possible aspect of installation, operation and maintenance.For additional information or if specific problems occur that are not discussed in theseinstructions, contact the manufacturer.The content of these instructions is neither part of any previous or existing agreement, promiseor legal relationship nor is it intended to change the same.This product is built based on state-of-the-art technology and is operationally safe. It has beentested and left the factory in perfect working order from a safety perspective. The information inthe manual must be observed and followed in order to maintain this state throughout the periodof operation.Modifications and repairs to the product may only be performed if expressly permitted by theseinstructions.
Only by observing all of the safety instructions and all safety/warning symbols in theseinstructions can optimum protection of both personnel and the environment, as well as safe andfault-free operation of the device, be ensured.Information and symbols directly on the product must be observed. They may not be removedand must be fully legible at all times.
1.2 Intended use
The TEIP11, TEIP11-PS is used to control pneumatic actuators or pneumatic positioners forpositioning valves. It also converts input current proportionally into a compressed air signal. TheTEIP11, TEIP11-PS may be used in accordance with the "Ex relevant specifications" section,page 25 and the "Specifications" section, page 22. All other use is improper use.
1.3 Target groups and qualifications
Installation, commissioning, and maintenance of the product may only be performed by trainedspecialist personnel who have been authorized by the plant operator to do so. The specialistpersonnel must have read and understood the manual and comply with its instructions.Prior to using corrosive and abrasive materials for measurement purposes, the operator mustcheck the level of resistance of all parts coming into contact with the materials to be measured.
ABB Automation Products GmbH will gladly support you in selecting the materials, but cannotaccept any liability in doing so.The operators must strictly observe the applicable national regulations with regards toinstallation, function tests, repairs, and maintenance of electrical products.
-
8/10/2019 42_18_46_EN_I
6/36
Safety
6 TEIP11, TEIP11-PS 42/18-46-EN
1.4 Warranty provisions
Using the device in a manner that does not fall within the scope of its intended use, disregardingthis instruction, using underqualified personnel, or making unauthorized alterations releases themanufacturer from liability for any resulting damage. This renders the manufacturer's warrantynull and void.
1.5 Plates and symbols
1.5.1 Safety- / warning symbols, note symbols
DANGER This symbol in conjunction with the signal word "Danger" indicates an imminent danger.Failure to observe this safety information will result in death or severe injury.
DANGER This symbol in conjunction with the signal word "Danger" indicates an imminent electricalhazard. Failure to observe this safety information will result in death or severe injury.
WARNING This symbol in conjunction with the signal word Warning indicates a possibly dangeroussituation. Failure to observe this safety information may result in death or severe injury.WARNING This symbol in conjunction with the signal word "Warning" indicates a potential electricalhazard. Failure to observe this safety information may result in death or severe injury.
CAUTION This symbol in conjunction with the signal word Caution indicates a possibly dangeroussituation. Failure to observe this safety information may result in minor or moderate injury.This may also be used for property damage warnings.
NOTICE !The symbol indicates a potentially damaging situation.Failure to observe this safety information may result in damage to or destruction of the productand/or other system components.
IMPORTANT (NOTE)This symbol indicates operator tips, particularly useful information, or important informationabout the product or its further uses. It does not indicate a dangerous or damaging situation.
-
8/10/2019 42_18_46_EN_I
7/36
Safety
42/18-46-EN TEIP11, TEIP11-PS 7
1.6 Transport safety information
Check the devices for possible damage that may have occurred during transport. Damages intransit must be recorded on the transport documents. All claims for damages must be claimedwithout delay against the shipper and before the installation.
1.7 Storage conditions
The unit must be stored in dry and dust-free conditions. The unit is also protected by adessicant in the packaging.The storage temperature should be between -40 ... 85 C (-40 ... 185 F).The storage time is basically indefinite. However, the warranty conditions stipulated in the orderconfirmation of the supplier are valid.
-
8/10/2019 42_18_46_EN_I
8/36
Safety
8 TEIP11, TEIP11-PS 42/18-46-EN
1.8 Safety information for electrical installationo
The electrical connection may only be made by authorized specialist personnel and inaccordance with the electrical circuit diagrams.
The electrical connection information in the manual must be observed; otherwise, the type ofelectrical protection may be adversely affected.
Safe isolation of electrical circuits which are dangerous if touched is only guaranteed if theconnected devices satisfy the requirements of DIN EN 61140 (VDE 0140 Part 1) (basicrequirements for safe isolation).
To ensure safe isolation, install supply lines so that they are separate from electrical circuitswhich are dangerous if touched, or implement additional isolation measures for them.
1.9 Operating safety information
Before switching on the unit make sure that your installation complies with the environmentalconditions listed in the chapter "Technical data" or in the data sheet.If there is a chance that safe operation is no longer possible, take the unit out of operation andsecure against unintended startup.
When mounting the unit in areas that may be accessed by unauthorized persons, take therequired protective measures.
Prior to installation, check the devices for any damage that may have occurred as a result ofimproper transport. Details of any damage that has occurred in transit must be recorded on thetransport documents. All claims for damages must be submitted to the shipper without delayand before installation.
1.10 Returning devices
Use the original packaging or suitably secure shipping containers if you need to return thedevice for repair or recalibration purposes. Fill out the return form (see the Appendix) andinclude this with the device.
According to EC guidelines for hazardous materials, the owner of hazardous waste isresponsible for its disposal or must observe the following regulations for shipping purposes:
All devices delivered to ABB Automation Products GmbH must be free from any hazardousmaterials (acids, alkalis, solvents, etc.).
Please
Please contact Customer Center Service acc. to page 2 for nearest service location.
-
8/10/2019 42_18_46_EN_I
9/36
Safety
42/18-46-EN TEIP11, TEIP11-PS 9
1.11 Integrated management system
ABB Automation Products GmbH operates an integrated management system, consisting of: Quality management system to ISO 9001:2008 Environmental management system to ISO 14001:2004 Occupational health and safety management system to BS OHSAS 18001:2007 and
Data and information protection management system
Environmental awareness is an important part of our company policy.Our products and solutions are intended to have a minimal impact on the environment and onpeople during manufacturing, storage, transport, use, and disposal.This includes the environmentally-friendly use of natural resources. We conducts an opendialog with the public through our publications.
1.12 Disposal
This product is manufactured from materials that can be reused by specialist recycling
companies.
1.12.1 Information on WEEE Directive 2002/96/EC (Waste Electrical and Electronic Equipment)
This product is not subject to WEEE Directive 2002/96/EC or relevant national laws(e.g., ElektroG in Germany).The product must be disposed of at a specialist recycling facility. Do not use municipal garbagecollection points. According to the WEEE Directive 2002/96/EC, only products used in privateapplications may be disposed of at municipal garbage facilities. Proper disposal preventsnegative effects on people and the environment, and supports the reuse of valuable rawmaterials.If it is not possible to dispose of old equipment properly, ABB Service can accept and dispose ofreturns for a fee.
1.12.2 RoHS Directive 2002/95/EC
With the Electrical and Electronic Equipment Act (ElektroG) in Germany, the EuropeanDirectives 2002/96/EC (WEEE) and 2002/95/EC (RoHS) are translated into national law.ElektroG defines the products that are subject to regulated collection and disposal or reuse inthe event of disposal or at the end of their service life. ElektroG also prohibits the marketing ofelectrical and electronic equipment that contains certain amounts of lead, cadmium, mercury,hexavalent chromium, polybrominated biphenyls (PBB), and polybrominated diphenyl ethers(PBDE) (also known as hazardous substances with restricted uses).The products provided by ABB Automation Products GmbH do not fall within the current scopeof the directive on waste from electrical and electronic equipment according to ElektroG. If thenecessary components are available on the market at the right time, in the future thesesubstances will no longer be used in new product development.
-
8/10/2019 42_18_46_EN_I
10/36
Technical Ex-relevant safety instructions - "Ex d"
10 TEIP11, TEIP11-PS 42/18-46-EN
2 Technical Ex-relevant safety instructions - "Ex d"
Requirements / prerequisites for safe use of the I/P signal converter in Ex version "Ex d"in a hazardous area design (type doc. 900771)
IMPORTANT (NOTE)
Prior to mounting, check to ensure that the I/P signal converter meets the measurement andsafety requirements that apply at the measuring point.
When making the electrical connections, characteristic values in the "Specifications" sectionand the information in the explosion protection certificate must be complied with.
The device may only be operated with instrument air that is free of oil, water, and dust. Donot use flammable gases, oxygen, or oxygen-enriched gas.
Never open the device immediately after switch-off: Wait for at least four minutes.
ATTENTION - component damage!Handle the cover with care. Damage to the cover thread results in loss of the "Ex d"protection.
IMPORTANT (NOTE)For "Ex d" operation only use cable glands with full "Ex d" approval.
Secure the cable and line entries against twisting and loosening by using a medium-strengthsecuring adhesive and self-locking elements.
If the I/P signal converter is used at an ambient temperature above 60C (140F) orbelow -20C (-4 F), use cable entries and cables suitable for an operating temperature of upto the maximum ambient temperature plus 10 K, or for an operating temperature down to theminimum ambient temperature.
ATTENTION - component damage!Devices that comply in new condition with "Ex ia" and "Ex d" protection classes should not beused in intrinsically safe "Ex ia" applications once they have been commissioned and used inan environment with Ex d protection, since the electronics may have been damaged.For this reason the devices must be permanently marked (e.g. cross out or mask over "Ex i").
-
8/10/2019 42_18_46_EN_I
11/36
Design and function
42/18-46-EN TEIP11, TEIP11-PS 11
3 Design and function
The TEIP11, TEIP11-PS signal converters transform electrical signals into pneumatic standardsignals, e.g., 4 20 mA into 0.2 1 bar (3 ... 15 psi). They represent, therefore, a connectinglink between electrical/electronic and pneumatic systems. The patented signal conversionprinciple is based on the force balance method.
M00318
5
6
7
8
1213
9 4 3 2 1 11 1 0
0 20 / 4 20 mA
0,2 1 bar (3 15 psi)
1,4 bar (14.5 psi)
Fig. 11 Coil2 Yoke3 Air gap4 Magnet5 Flapper6 Nozzle7 Throttle
8 Converter stage9 Lever arm10 Potentiometer11 Resistor12 Filter13 Air supply
FunctionalityForce balancing takes place at the lever arm, which is pivoted with a tension band at (9). Thecoil (1) and yoke (2) generate a magnetic field in the air gap (3), which applies a force to themagnet (4) on the lever arm. The force changes in proportion to the current (input signal)flowing through the coil (1).
A counterforce is applied on the other side of the lever arm, through the dynamic air pressurepresent at the nozzle (6) and the flapper (5). The force is controlled in such a way that abalance of the two torques is achieved. If a torque imbalance occurs, the lever arm rotates. Thisrotation changes the air gap between the nozzle (6) and the flapper (5) and, thus, the dynamicair pressure. Air is permanently supplied to the nozzle (6) through the throttle (7). The converterstage (8) converts the dynamic air pressure into a 0.2 ... 1 bar or 3 ... 15 psi output signal.
-
8/10/2019 42_18_46_EN_I
12/36
Design and function
12 TEIP11, TEIP11-PS 42/18-46-EN
Supply airDuring operation the pneumatic unit needs a steady supply of air (13) according to unitspecifications. Zero position adjustment can be performed by turning the tension bandsuspension (9), and range adjustment via the potentiometer (10).
Special featuresSpecial features of the TEIP11, TEIP11-PS signal converter are its relatively small dimensionsand outstanding operational stability when subject to shock and vibration. The stability is due tothe light weight (only around 100 mg) of the moving system, which consists of the lever arm withthe magnet (4) and the flapper (5) with balancing weight.
FilterThe filter (12) prevents malfunctions caused by polluted air. Note that the filter capacity is onlysufficient for collecting dirt that occurs occasionally (e.g., residual dirt in the air pipes at firstcommissioning). It is no substitute for proper air conditioning.
Deliverables
For details on the deliverable signal converter models and their accessories, please refer to theappropriate data sheet, which also includes the order numbers of the individual items.
-
8/10/2019 42_18_46_EN_I
13/36
Mounting
42/18-46-EN TEIP11, TEIP11-PS 13
4 Mounting
4.1 Operating conditions at installation site
IMPORTANT (NOTE)Prior to mounting, check to ensure that the TEIP11, TEIP11-PS signal converter meets themeasurement and safety requirements that apply at the installation location.See the "Specifications" chapter, page 22.
4.2 Delivery scope
Check the delivery for completeness, signs of damage, model, and scope immediately uponarrival.
Check whether the delivery is in accordance with your order.
AccessoriesThe following loose accessories are delivered with the unit as extra items:
Mounting bracket for the aluminium or stainless steel field housing unit (for wall or 2" pipemounting)
Cable entry for signal converter with "Ex d" type of protection
4.3 TEIP11 / TEIP11-PS
4.3.1 Mo unting the control room housing unit for rail mounting
This design is snap-mounted onto a DIN top-hat rail.
M00324 Fig. 2: Control room housing unit for rail mounting
TheTEIP11, TEIP11-PS signal converter has a special mounting base. Due to its universaldesign, it is suitable for mounting onto EN 50022 - 35 x 7.5, EN 50045 - 15 x 5, and EN 50035 -G32 top-hat rails.
Top-hat rail mounted in a vertical positionFor top-hat rails that are mounted in a vertical position, the electrical connection for the unitshould preferably be on the left.
Top-hat rail mounted in a horizontal positionFor top-hat rails that are mounted in a horizontal position, the electrical connection for the unitshould preferably be facing up.
-
8/10/2019 42_18_46_EN_I
14/36
-
8/10/2019 42_18_46_EN_I
15/36
Mounting
42/18-46-EN TEIP11, TEIP11-PS 15
4.4 TEIP11
4.4.1 Mounting the field housing unit as a mounting module for OEM applications
M00539 Fig. 4: Aluminium / stainless steel field housing unit
MountingPosition the housing unit so that the cable gland is facing downwards or sideways, to preventmoisture from penetrating the unit.
Accessories A stainless steel mounting bracket is provided as an accessory for installation. The mountingbracket is available in two versions: For wall mounting only Universal for wall or 2" pipe mounting
-
8/10/2019 42_18_46_EN_I
16/36
Mounting
16 TEIP11, TEIP11-PS 42/18-46-EN
4.5 TEIP11-PS
4.5.1 Mounting the control room housing unit for block mounting
For this design, a special connection block is used to mount the unit.
M00327 Fig. 5: Control room housing unit for block mounting
DesignThe connection block is designed for mounting a maximum of 4 I/P signal converters. Theconnection blocks can be expanded to units of 2, 3, or 4 blocks to create block units with 4, 8,12, or 16 I/P signal converters.
MountingThe material for forming the block units is delivered separately for self-installation; in addition tothe connection blocks, it includes the necessary screws and gaskets (O-rings).
Air supplyThe air supply for the connected units is provided via a central connection block. Theconnection block's air connector features a non-return coupling for every single I/P signalconverter. This allows connection sites to remain unused, and individual I/P signal converters tobe dismounted or mounted during operation.
-
8/10/2019 42_18_46_EN_I
17/36
Mounting
42/18-46-EN TEIP11, TEIP11-PS 17
4.5.2 Mounting of the plastic field housing
The plastic housing unit is suitable for mounting on-site.
M00326 Fig. 6: Plastic field housing unit
Mounting typesUnits can be mounted on walls or vertically on a 2" pipe.The connections for the input and output signals should face downwards, to prevent moisturefrom penetrating the unit.
DANGER - explosion hazard!The I/P converter type, doc. 901069 must be set up outdoors for operation with flammablegases as pneumatic auxiliary energy.The supplied gas must be kept free of air or oxygen, so that an explosive atmosphere doesnot form.The gas must always be dissipated to the outside.
-
8/10/2019 42_18_46_EN_I
18/36
Electrical connections
18 TEIP11, TEIP11-PS 42/18-46-EN
5 Electrical connections
IMPORTANT (NOTE)For electrical installation, the following standards, data, and documents must be compliedwith: The relevant regulations and safety standards pertaining to the installation and operation of
electrical systems The additional regulations, standards, and directives pertaining to the installation and
operation of explosion-proof systems, if explosion-proof units are used The values for the electrical connection in the "Specifications" section, page 22 For explosion-proof devices, also observe the information on the explosion protection
certificate
5.1 Signal cables
Do not the install the signal line together with power supply lines.
IMPORTANT (NOTE)
Power supply lines may produce interference in the immediate vicinity, which can impair themeasured values transmitted on the signal cable.
5.2 Cable glandss
The field housing units feature a Pg 11 cable entry.
Aluminum or stainless steel field housing unit
Normal / Ex ia Cable gland 1/2" NPT
Ex d Tapped bore M20 x 1.5
FM / CSA "Intrinsically Safe" / "Explosion Proof" Tapped bore 1/2 NPT
IMPORTANT (NOTE)Use only cable glands with full "Ex d" approval for "Ex d" operation (partially approved cableglands labeled "U" are not sufficient).Secure the screwed-in "Ex d" cable gland with adhesive (e.g. Loctite 242/243) to preventautonomous loosening.
-
8/10/2019 42_18_46_EN_I
19/36
Electrical connections
42/18-46-EN TEIP11, TEIP11-PS 19
5.3 Position of the terminals
The electrical connection is provided by 2-pole screw terminals for cables with a max. cross-sectional area of 2.5 mm 2 (14 AWG).
Control room housing unit for rail and block mountingThe terminals are located on the side of the housing unit.
Plastic, aluminium, or stainless steel field housing unitThe terminals are located inside the housing unit. Therefore, the field housing unit must beopened in order to connect the cable.
5.4 Connection
Do not reverse polarity when connecting the cable.
-
8/10/2019 42_18_46_EN_I
20/36
-
8/10/2019 42_18_46_EN_I
21/36
Maintenance
42/18-46-EN TEIP11, TEIP11-PS 21
8 Maintenance
8.1 Readjusting the signal conversion
The signal converters are delivered in an adjusted condition. After longer operating periods,however, the tolerance limits may be exceeded due to aging or drift. Overshoots of thetolerance limits can be undone through a readjustment.
0
1 2
M00317 Fig. 7: Adjustment screws
IMPORTANT (NOTE)When using a field housing unit first remove the cover to access the screws.
The readjustment is executed with two adjustment screws (see Fig. 7).
Designation Description
1 Setting of range
2 Setting of zero point
-
8/10/2019 42_18_46_EN_I
22/36
Specifications
22 TEIP11, TEIP11-PS 42/18-46-EN
9 Specifications
9.1 TEIP11 / TEIP11-PSChangefromonetotwocolumns
9.1.1 Inputwohl
Signal range
0 ... 20 mA or 4 ... 20 mA0 ... 10 mA or 10 ... 20 mA4 ... 12 mA or 12 ... 20 mA(additional ranges available upon request)
Input resistanceRi = 260 at 20 C (68 F), Tk + 0.4 %/K
Overload limit30 mA (for explosion-proof units, see the information contained inthe "Ex relevant specifications" section, page 25)
Capacitance/InductanceNegligible
9.1.2 Environmental capabilities
Climate classGPF or FPF acc. to DIN 40040Temperature:-55 85 C (-67 ... 185 F)-45 85 C (-49 ... 185 F)Relative humidity for operation, storage, or transport:75 % mean, 95 % short-term,no condensation
9.1.3 Design for rail mounting
Material / Ingress protectionIP 20 aluminum housing unit, with plastic cover
MountingRail mounting:EN 50022 - 35 x 7.5EN 50035 - G 32EN 50045 - 15 x 5
Electrical connection2-pole screw terminal for 2.5 mm 2 (14 AWG)
Pneumatic connection1/8 NPT tap hole for air supply and output
Weight0.25 kg (0.55 lb)
DimensionsSee Section 11, "Dimensions"
9.1.4 Design for field housing unit (aluminum /stainless steel)
r
Material / Ingress protectionIP 65 aluminum or stainless steel housing unit
Surface Aluminum housing,painted with dual component coating,lower section, black, RAL 9005,screw-on cover, Pantone 420,stainless steel housing unit,electrolytically polished
MountingWall or 2" pipe mountingWith stainless steel mounting bracket (accessory)
Electrical connection2-pole screw terminal for 2.5 mm 2 (14 AWG) in housing unit,NPT 1/2" cable gland for cable entryFor ATEX "intrinsically safe":M20 x 1.5 tap hole for cable entryFor ATEX "Ex d":(Cable gland with Ex d approval available as an accessory onrequest)NPT 1/2" tap hole for cable entry with FM/CSA
Pneumatic connection1/4" NPT tap hole for air supply and output
Weight0.62 kg (1.37 lb) with aluminum housing unit1.20 kg (2.65 lb) with stainless steel housing unit
DimensionsSee Section 11, "Dimensions"
-
8/10/2019 42_18_46_EN_I
23/36
-
8/10/2019 42_18_46_EN_I
24/36
Specifications
24 TEIP11, TEIP11-PS 42/18-46-EN
9.3.4 Operating conditions at installation site
Ambient temperatureDepending on the ordered model:-40 85 C (-40 ... 185 F)-55 85 C (-67 ... 185 F)For Ex d:-40 85 C (-40 ... 185 F)
Required protection
IP 20 for control room housing unit for rail or block mounting,IP 54 for plastic housing unit,IP 65 for aluminum or stainless steel field housing unit
Installation position Any
9.3.5 Design for block mounting
Material / Ingress protectionIP 20 aluminum housing unit, with plastic cover
MountingIn block format with special connection block (accessory),max. 4 connection blocks each with 4 signal converters
Electrical connection2-pole screw terminal for 2.5 mm 2 (14 AWG)
Pneumatic connection3/8 NPT tap hole for air supply(main connection to connection block)1/8 NPT tap hole for output(on each individual signal converter)
Installation position Any
Weight0.3 kg (0.66 lb)
DimensionsSee Section 11, "Dimensions"
9.3.6 Design for field housing unit (plastic)
Material / Ingress protectionPolyester housing unit, black, IP 54
MountingWall or 2" pipe mounting(2" pipe mounting for vertical pipes only)
Electrical connection2-pole screw terminal for 2.5 mm 2 (14 AWG) in housing unit,Pg 11 cable gland for cable entry
Pneumatic connection1/8 NPT tap hole for air supply and output
Air outletFor gas exhaust with 6 mm (0.24 inch) cut or crimp connection
Installation position Any
Weight1.0 kg (2.20 lb)
DimensionsSee Section 11, "Dimensions"
9.3.7 Accessories
"Ex d" cable glandBrass, with M20 x 1.5 threadStainless steel mounting bracket for wall or 2" pipe mounting
For aluminum or stainless steel field housing unitMaterial for block mounting
Connection block for 4 signal converters,panel with central air connector 3/8 NPT,dummy panel
9.3.8 Spare parts
Except for the textile filter, the signal converter is wear free and doesnot require maintenance.
ChangefromonetotwocolumnsChangefromonetotwocolumns
-
8/10/2019 42_18_46_EN_I
25/36
-
8/10/2019 42_18_46_EN_I
26/36
Ex relevant specifications
26 TEIP11, TEIP11-PS 42/18-46-EN
10.3.1 Intrinsically Safe FM
FM "Intrinsically Safe" (not for the metal field housing)I.S.: CL I / Div 1 / Grp A B C D
FM "Intrinsically Safe" (only for the metal field housing)I.S.: CL I-II-II / Div 1 / Grp A B C D E F GS.: CL II / Div 2 / Grp GS.: CL III / Div 2
10.3.2 Non-Incendive FM
N.I.: CL I / Div 2 / Grp A B C D (not for the metal field housing)N.I.: CL I / Div 2 / Grp A B C (not for metal field housing units)
10.3.3 Intrinsically Safe CSA
CSA "Intrinsically Safe" (not for the metal field housing)I.S.: CL I / Div 1 / Grp A B C DCL I / Div 2 / Grp A B C D
CSA "Intrinsically Safe" (only for the metal field housing)I.S.: CL I / Div 1 / Grp A B C DCL II / Div 1 / Grp E F G
CL IIICL I / Div 2 / Grp A B C DCL II / Div 2 / Grp E F G
10.3.4 Non-Incendive CSA
FM "Explosion Proof" (only for the metal field housing)X.P.: CL I / Div 1 / Grp B C DD.I.P.: CL II III / Div 2 / Grp E F G
CSA "Explosion Proof" (only for the metal field housing)X.P.: CL I / Div 1 / Grp B C D
Changefromonetotwocolumns
-
8/10/2019 42_18_46_EN_I
27/36
Dimensions
42/18-46-EN TEIP11, TEIP11-PS 27
11 Dimensions
11.1 TEIP11 / TEIP11-PS
11.1.1 Design for control room housing unit for rail mounting
M00323
3 6
( 1 . 4 2
)
20 (0.79) 32 (1.26) 3
( 0 . 1 2
)
3,3 (0.13)
3,3 (0.13)
20 (0.79)
36 (1.42)
4 0
( 1 . 5 7
)
2 5
( 0 . 9 8
)
9 7
( 3
. 8 2 )
8 6
( 3
. 3 9 ) *
1
1
4
3
2 5
Fig. 8: Dimensions in mm (inch)1 Electrical connections2 Filter3 Output
4 Supply air5 Mounting bracket for DIN rail mounting
*TEIP11 only
-
8/10/2019 42_18_46_EN_I
28/36
Dimensions
28 TEIP11, TEIP11-PS 42/18-46-EN
11.1.2 Design for aluminum or stainless steel field housing unit
100 (3.94)
75 (2.95)36 (1.42)
62 (2.44)
100 (3.94)
1 5 2
( 5
. 9 8 )
2 3 2
( 9
. 1 3 )
1 3 6
( 5
. 3 5 )
1 1
( 0
. 4 3 )
5 7
( 2
. 2 4 )
70 (2.76)
2 8
( 1
. 1 0 )
9
( 0
. 3 5 )
1 2
3
4
5
5
4
7
6M00322
Fig. 9: Dimensions in mm (inch)1 Ground terminal2 Electrical connections3 Output
4 Supply air5 Filter6 Profiled sheet for wall mounting7 Cable gland
-
8/10/2019 42_18_46_EN_I
29/36
Dimensions
42/18-46-EN TEIP11, TEIP11-PS 29
11.2 TEIP11-PS
11.2.1 Design for control room housing unit for block mounting
M00320
12,4 (0.49)
n x 80 (3.15) 3)
80 (3.15)
25 (0.98)
1 1 5
( 4
. 5 3 )
2 )
7 , 5
( 0
. 3 0 )
25 (0.98)
4 0
( 1
. 5 7 )
1 0
( 0
. 3 9 )
4
1
2
3
5
7
6
8 0
( 3
. 1 5 )
6 4
( 2
. 5 2 )
6 , 4
( 0
. 2 5 )
5 0
( 1
. 9 7 )
1 1 5
( 4
. 5 3 )
2 0
, 5
( 0
. 8 1 )
6,4 (0.25)
Fig. 10: Dimensions in mm (inch)1 Output2 Supply air3 Filter4 Electrical connections
5 Panel with central air connector6 Connection blocks7 Dummy panel
1) 0.2 ... 1 bar (2.90 ... 14.50 psi) version2) 0.4 ... 1 bar (5.80 ... 14.50 psi) version3) Length 80 mm (3.15 inch) for each connection block
-
8/10/2019 42_18_46_EN_I
30/36
Dimensions
30 TEIP11, TEIP11-PS 42/18-46-EN
11.2.2 Design for plastic field housing unit
66 (2.60)
1 0 0
( 3
. 9 4
)
9 4
( 3
. 7 0 )
69 (2.72 )
35 (1 .3 8)24 ,5 (0 .9 6)
128 (5 .04)
1 2 8
( 5
. 0 4 )
2 0
( 0
. 7 9 )
98 ,5 (3. 88)69 (2.72 )
25 ( 0.98)
20 (0.79 )
72 (2 .83)7 (0.28 )
1
234
M00321
Fig. 11: Dimensions in mm (inch)1 Electrical connections2 Connection only with version for operation with flammable gas for
diverting the escaping gas / 6 mm (0.24) screw terminalconnection
3 Supply air4 Output5 Cable gland
-
8/10/2019 42_18_46_EN_I
31/36
Dimensions
42/18-46-EN TEIP11, TEIP11-PS 31
11.3 TEIP11
11.3.1 Design for field housing unit as a mounting module for OEM applications
5 , 6
( 0
. 2 2 )
75 (2.95)
22 (0.87)
6 , 7
( 0
, 2 6 )
8 , 5
2 3
, 5
( 0
. 9 3 )
2 1
, 5
( 0
. 8 5 )
10,5 (0.41)
25,5 (1.00)
11 (0.43)
36 (1.42)
1 0 7
( 4
. 2 1 )
1 1
( 0
. 4 3 )
+ -1,6
( 0 , 3
3 )
(0.06)
14
23
M00351
Fig. 12: Dimensions in mm (inch)1 Electrical connections2 Output
3 Supply air4 Cable gland
-
8/10/2019 42_18_46_EN_I
32/36
Appendix
32 TEIP11, TEIP11-PS 42/18-46-EN
12 Appendix
12.1 Approvals and certifications
CE mark The version of the meter in your possession meets the requirements of thefollowing European directives:
- EMC directive 2004/108/EC- ATEX directive 94/9/EC
ExplosionProtection
Identification for intended use in potentially explosive atmospheres accordingto:
- ATEX directive (marking in addition to CE marking)
- FM Approvals (US)
- CSA International (Canada)
IMPORTANT (NOTE) All documentation, declarations of conformity and certificates are available in ABB's downloadarea.www.abb.com/instrumentation
-
8/10/2019 42_18_46_EN_I
33/36
Appendix
42/18-46-EN TEIP11, TEIP11-PS 33
-
8/10/2019 42_18_46_EN_I
34/36
Appendix
34 TEIP11, TEIP11-PS 42/18-46-EN
Statement on the contamination of devices and components
Repair and / or maintenance work will only be performed on devices and components if a statement form has beencompleted and submitted.Otherwise, the device / component returned may be rejected. This statement form may only be completed andsigned by authorized specialist personnel employed by the operator.
Customer details:
Company:
Address:
Contact person: Telephone:
Fax: E-mail:
Device details:
Type: Serial no.:
Reason for the return/description of the defect:
Was this device used in conjunction with substances which pose a threat or risk to health? Yes No
If yes, which type of contamination (please place an X next to the applicable items)?
Biological Corrosive / irritating Combustible (highly / extremely combustible)
Toxic Explosive Other toxic substances
Radioactive
Which substances have come into contact with the device?
1.
2.
3.
We hereby state that the devices / components shipped have been cleaned and are free from any dangerous orpoisonous substances.
Town/city, date Signature and company stamp
n
-
8/10/2019 42_18_46_EN_I
35/36
Notes
42/18-46-EN TEIP11, TEIP11-PS 35
Notes
-
8/10/2019 42_18_46_EN_I
36/36
ABB has Sales & Customer Support expertise in over100 countries worldwide.
www.abb.com/instrumentation
The Companys policy is one of continuous productimprovement and the right is reserved to modify the
information contained herein without notice.
Printed in the Fed. Rep. of Germany (10.2012)
ABB 2012
4 2 / 1 8 - 4
6 - E
N
R e v .
I 3KXE311001R4201
ABB Ltd.Process AutomationSalterbeck Trading EstateWorkington, CumbriaCA14 5DSUK
Tel: +44 (0)1946 830 611Fax: +44 (0)1946 832 661
ABB Inc.Process Automation125 E. County Line RoadWarminster, PA 18974USATel: +1 215 674 6000
Fax: +1 215 674 7183measurement@us abb com
ABB Automation Products GmbHProcess AutomationSchillerstr. 7232425 MindenGermanyTel: +49 551 905-534
Fax: +49 551 905-555