4.1 Transfomer-Less vs Transformer-Based UPS 080224

download 4.1 Transfomer-Less vs Transformer-Based UPS 080224

of 23

Transcript of 4.1 Transfomer-Less vs Transformer-Based UPS 080224

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    1/23

    Newave SA, Switzerland [email protected] - www.newaveups.com28/02/2006 ML3-49 1

    Newave TransformerlessNewave Transformerless

    Double Conversion TopologyDouble Conversion Topologyvversusersus

    DoubleDouble Conversion TopologyConversion Topology

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    2/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 2

    TRADITIONAL TOPOLOGY

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    3/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 3

    Large physical size

    Physically heavy:120kVA (6pulse) from 700 to 1200 kg

    120kVA (12pulse) from 1200 to 1800 kg

    Large footprint120kVA (6pulse) from 0.64 to 1.1 m2

    120kVA (12pulse) from 1.30 to 2.2 m2

    More space required to extract

    additional hot air due to

    additional losses

    Size and weight increases withthe addition of input filters

    ca.1000 mm

    120 kVA (6pulse)

    V = 1.44 m3

    Footprint = 0.80 m2 800

    mm

    1800mm

    800mm

    ca.2000 mm

    120 kVA (with 12pulse)

    1800mm

    V = 2.88 m3

    Footprint = 1.6 m2

    DOUBLE CONVERSION TOPOLOGYTHE FACTS: TRANSFORMER BASED

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    4/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 4

    Double Conversion with output transformer Internal battery up to a maximum of 30 kVA only

    Only a fixed number of batteries allowed

    Batteries subjected to high ripple during charging

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS: TRANSFORMER BASED

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    5/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 5

    High input current distortion (> 30%)

    Addition of input filters or 12 pulse rectifiers is expensive,

    space consuming and decreases efficiency further to < 90%

    Low input power factor; 0.6 to 0.86 depending on load

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS: TRANSFORMER BASED

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    6/23

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    7/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 7

    Low Efficiency (< 92%) Output distortion with non-linear loads is inherently poor

    and must be corrected electronically

    Neutral is directly connected to the load without

    protection

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS: TRANSFORMER BASED

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    8/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 8

    Input Power On

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS : TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    9/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 9

    DC Filter Pre-charging

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS : TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    10/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 10

    Booster in Operation

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS : TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    11/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 11

    Battery Charging

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS : TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    12/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 12

    Inverter Operation

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS : TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    13/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 13

    Normal Operation

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS : TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    14/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 14

    Battery Operation

    DOUBLE CONVERSION TOPOLOGY

    THE FACTS : TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    15/23

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    16/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 16

    Conceptpower DPA , THDi < 2 %Conceptpower DPA , THDi < 2 %

    Small physical size

    Light weight:120 kW (150 kVA) = 407 kg

    Small footprint

    120kW (150 kVA) = 0.58 m2

    DOUBLE CONVERSION TOPOLOGY

    FEATURES: TRANSFORMER-LESS

    730 mm

    120 kW

    V = 1.15 m3

    Footprint = 0.58 m2

    1975

    mm

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    17/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 17

    Double Conversion, transformerless technology

    Variation in number of blocks (40-50) allowed in order to

    adjust autonomy times

    Separate battery chargers provide improved rippleless

    charging

    DOUBLE CONVERSION TOPOLOGY

    FEATURES: TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    18/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 18

    High input power factor (0.99), independent of the load applied

    Fast diode input rectifier with input filter and PFC control does notcreate incompatibility problems with input supplies

    Input emergency alternators do not need to be oversized

    1997/06/0310:54:36

    5ms/div

    (5ms/div)

    NORM:200kS/s

    CH1=50V

    DC 100:1

    CH2=100V

    DC 100:1

    DT 5.55ms

    =Filter=Smoothing:ONBW:FULL

    =Offset=C H 1 : 0 . 0 VC H2 : 0 VC H 3 : 0 . 0 VC H 4 : 0 . 0 V

    =RecordLength=Main:10KZoom:1K

    =Trigger=Mode:AUTOType:EDGE LINEDelay: 0.0nsHoldOff: MINIMUM

    Low input current distortion (< 2 % with 400V input voltage)

    - no additional input filtering required

    DOUBLE CONVERSION TOPOLOGY

    FEATURES: TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    19/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 19

    High efficiency (> 95%) due to transformerless technology and ESIS

    1997/06/0310:54:36

    5ms/div

    (5ms/div)

    NORM:200kS/s

    CH1=50V

    DC 100:1

    CH2=100V

    DC 100:1

    DT 5.55ms

    =Filter=Smoothing:ONBW:FULL

    =Offset=C H 1 : 0 . 0 VC H2 : 0 VC H 3 : 0 . 0 VC H 4 : 0 . 0 V

    =RecordLength=Main:10KZoom:1K

    =Trigger=Mode:AUTOType:EDGE LINEDelay:0.0nsHoldOff: MINIMUM

    Reduced switching stress on power components higher reliability

    ESIS (Energy Saving Inverter Switching) also reduces EMI effects

    High efficiency means longer autonomy times as well

    as cost savings

    DOUBLE CONVERSION TOPOLOGY

    FEATURES: TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    20/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 20

    Very low output impedance (< 1%) excellent dynamicperformance and no corrections needed for unbalanced loads

    Low harmonic distortion at the output (< 2% with non-linear loads)

    Output neutral is decoupled from the mains neutral during

    disturbances

    1997/06/0310:54:36

    5ms/div

    (5ms/div)

    NORM:200kS/s

    CH1=50V

    DC 100:1

    CH2=100V

    DC 100:1

    DT 5.55ms

    =Filter=Smoothing:ONBW:FULL

    =Offset=C H 1 : 0 . 0 VC H2 : 0 VC H 3 : 0 . 0 VC H 4 : 0 . 0 V

    =RecordLength=Main:10KZoom:1K

    =Trigger=Mode:AUTOType:EDGE LINEDelay:0.0nsHoldOff: MINIMUM

    DOUBLE CONVERSION TOPOLOGY

    FEATURES: TRANSFORMER-LESS

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    21/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 21

    Efficiency < 92% - additional

    cooling may be necessary

    Large physical size

    Heavy: 120 kVA: 700-1200 kg

    Large footprint 1.1 m2 +additional cabinet for 12-pulse +

    battery cabinet needed

    Number of battery cells is fixed

    Batteries subjected to highripple voltage during charging.

    Low input power factor (0.6-0.8).

    Input current distortion > 30%

    - additional input filter required.

    Efficiency > 95% - no or little

    additional cooling necessary.

    Small physical size.

    Light weight: 120 kVA = 407 kg.

    Small footprint 0.58 m2 noadditional cabinet for 12pulse or

    battery cabinet needed.

    Variation of number of battery

    blocks allowed.

    Separate battery charger ensurescorrect rippleless charging.

    High input power factor (0.99).

    Input current distortion < 2%

    - no additional input filters.

    Traditional Topology Newave Transformerless Topology

    UPS TOPOLOGY COPMARISONOVERVIEW

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    22/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 22

    Slow switching controlled rect-

    ifier may cause incompatibility

    with other equipment.

    Emergency generator must beoversized.

    High output impedance (typ.

    8%) - poor dynamic response and

    additional corrective circuits

    required for unbalanced loads

    Higher inherent Output distortion

    with non-linear loads

    Switching elements switch on at

    full load current; increased stress

    Fast switching diode rectifier

    does not create incompatibility

    problems with input supply

    No need to oversize emergencygenerator

    Low output impedance (< 1%)

    - excellent dynamic response

    and excellent performance with

    unbalanced loads

    Low output distortion on all

    types of loads

    Increased reliability due to

    reduced switching stress

    Traditional Topology Newave Transformerless Topology

    UPS TOPOLOGY COPMARISONOVERVIEW

  • 8/3/2019 4.1 Transfomer-Less vs Transformer-Based UPS 080224

    23/23

    Newave SA [email protected] - www.newaveups.com28/02/2006 ML3-49 23