4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will...

28
EXIT 1. Check all windows and doors are closed. 2. a) Fullguard - Press 'Away' then 'Arm'. or b) Partguard - Press 'Home' then 'Arm'. 3. Leave premises by entry/exit route. ENTRY 1. Enter premises by entry/exit route. 2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode. MAINS CLEAR 24Hr Zone 1 Zone 2 Zone 3 Zone 4 1 2 3 0 4 5 6 7 8 9 ARM OMIT RESET HOME ER AWAY Installation & Operating Manual PA4 4 Zone Wired Intruder Alarm System

Transcript of 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will...

Page 1: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

EXIT1. Check all windows and doors are closed.2. a) Fullguard - Press 'Away' then 'Arm'.or b) Partguard - Press 'Home' then 'Arm'.3. Leave premises by entry/exit route.ENTRY1. Enter premises by entry/exit route.2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode.

MAINS CLEAR 24Hr

Zone 1 Zone 2 Zone 3 Zone 4

1 2 3

0

4 5 6

7 8 9

ARM

OMIT

RESET

HOMEERAWAY

Installation & Operating Manual

PA44 Zone Wired Intruder

Alarm System

Page 2: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

FOREWORDYour decision to purchase a Response PA4 Wired

Intruder Alarm System represents a major and sensible

step towards total protection of your premises, its

contents and its occupants.

All components are designed and manufactured to

provide a high standard of security protection and long,

reliable service.

The PA4 Alarm System is designed for ease of

installation using only conventional domestic tools.

However, it is essential that the installer reads and fully

understands the advice and procedures contained in

this manual and plans the system before proceeding

with the installation.

During installation, it is important that the procedures

described in this manual are followed in sequence.

This manual should be retained in a safe place for

future reference.

IMPORTANT

All components, with the exception of the External Siren,

are suitable for mounting in dry interior locations only.

Tools and Equipment Required:

3mm flat bladed screwdriver

No.1 Philips screwdriver

No.2 Philips screwdriver

Wire Cutters & Strippers

Drill

5 & 6mm Masonry Drill Bits

Bradawl

Hammer

Small Spirit Level

Additional Requirements:

Terminal Strip or Insulating Tape

2 x 9 Volt PP3 Alkaline Back-up Batteries

LOCAL AUTHORITY REGULATIONSDepending on your location within the country, you

may be required by law to notify the Local Authorities

and Police of your new alarm installation.

Local Authority requirements differ from area to area,

therefore, we recommend that you contact your Local

Borough Environmental Officer to obtain full details of

your area's requirements.

SAFETY WARNINGSBefore proceeding with the installation, please note

the following safety warnings:

1. Always follow the manufacturers advice when

using power tools, steps, ladders etc. and wear

suitable protective equipment (e.g. safety goggles)

when drilling holes and hammering home cable

clips etc.

2. Before drilling holes in walls, check for hidden

cables and pipes. The use of a cable/pipe locator

may be advisable if in any doubt.

3. When using ladders, ensure that they are

positioned on a firm stable surface at the correct

angle and suitably secured before use.

4. The use of ear defenders is advisable when working

in close proximity to the Siren due to the high sound

level produced by this device.

SYSTEM SECURITYThis system has been designed to both detect intruders

and act as a strong deterrent to would-be intruders.

Please remember that, given adequate knowledge and

time, it is possible to overcome any alarm system and

we therefore recommend that an Intruder Alarm is used

in conjunction with good physical protection such as

security windows and door locks.

The system is operated from the Control Panel using a

4 digit User Access code. Care should be taken to

ensure that your User Access code does not become

known to other people as this will compromise the

security of your system. In this event the User Access

code should be changed as soon as possible.

PA4 Wired Intruder Alarm SystemFriedland

Page 3: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

1

CONTENTSPage No.

INTRODUCTION & OVERVIEWAlarm Control Panel 2System Operation After Power Failure 2Passive Infra Red Movement Detectors 2Magnetic Contacts 2External Siren 2

KIT CONTENTS 3

SYSTEM FEATURES

User Functions 4Arm/Disarm 4Quick Set 4Event Log 4Home and Zone Omit 4Reset 4

Installer Functions 4Programming 4Zones 424 Hour Tamper Circuit 4Siren/Anti Tamper Monitoring 4

Programmable Zone Options 4Entry/Exit 4Walk Through Zone 4

General System Programmable Options 5Entry Time 5Exit Time 5Zone Omit 5Alarm Duration 5System Reset 5User Access Code 5Installer Access Code 5Keypad Security 5

PLANNING THE INSTALLATIONLocating the Control Panel 6Detector Wiring 6Magnetic Contact Detectors 6PIR Movement Detectors 6External Siren 6Installation Example 7

INSTALLING THE CONTROL PANELTesting the Control Panel 8Wiring the Detection Zones 9

INSTALLING THE PIR MOVEMENT DETECTORSMounting the PIR Movement Detectors 10Wiring the PIR Movement Detectors 11Testing the PIR Movement Detectors at the Control Panel 11

Page No.

TYPICAL WIRING ARRANGEMENTS 12

INSTALLING THE MAGNETIC CONTACT DETECTORS

Wiring the Magnetic Contacts 14Testing Magnetic Contacts at the Control Panel 15

INSTALLING THE EXTERNAL SIRENFitting the External Siren Unit 15Wiring the Siren Unit 16

CONNECTING THE CONTROL PANELMAINS ADAPTOR AND OPTIONAL BACK-UP BATTERIES 16

PROGRAMMINGGeneral 17

INSTALLER PROGRAMMING MODE 17Changing The Installer Access Code 17Exit Delay Time Adjustment 17Entry Delay Time Adjustment 18Alarm Duration Adjustment 18Selecting ‘Home’ Feature Zones 18Selecting Walk Through Zones 18Selecting ‘Code Arming’ 19Reset System Defaults 19Lost Or Forgotten Installer Access Code 19

USER PROGRAMMING MODE 19Change The User Access Code 19

TESTING THE SYSTEM 20

OPERATING INSTRUCTIONS‘Away’ Arming All Zones 20‘Home’ Arming Pre-Selected Zones 21Arming with Occasional Zones Omitted 21Quick Arm 21Disarming the System 21Event Log 22

MAINTENANCEControl Panel and Detectors 22Back-up Batteries Batteries 22

ALARM RECORD 22

TROUBLE SHOOTING 23

EXTENDING YOUR PA4 WIRED INTRUDER ALARM SYSTEM 24

COMPONENT SPECIFICATION Back Cover

PA4 Alarm

Page 4: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INTR

OD

UC

TIO

N

The PA4 Alarm Package contains all components

necessary to install a complete system. The items

included in your Package are shown opposite. The

main components are as follows:-

ALARM CONTROL PANELThe Control Panel is the heart of the intruder alarm

system and contains the microprocessor and electronic

circuitry necessary to monitor the various detection

circuits (Zones) and to initiate an alarm condition in the

event of an intrusion into a protected area.

The complete system operates at 12 Volts powered

from the plug-in mains adaptor. In the event of a

mains failure, the system will operate from the

optional Back-up Batteries if these have been fitted.

The Control Panel is operated via the push buttons on the

front of the Control Panel allowing the user to ARM/

DISARM the system, Omit Zones, view the Event Log,

Test the system or Program the various system functions.

A four digit User Access Code ensures that only

authorised users can operate the system. The Control

Panel also contains a small speaker used to indicate

various conditions by means of a variety of tones.

The Control Panel incorporates a ‘Non Volatile Memory’,

(NVM) which records all program settings indefinitely

even when all power has been removed.

The Control Panel will also remember which mode it was

in when power was disconnected and revert to this

mode when power is restored, e.g. if the panel was in

Alarm Mode when the power was removed, the panel will

continue to be in Alarm Mode when power is restored.

All detectors and alarm circuits are wired from the

Control Panel and operate at 12 Volts dc.

PASSIVE INFRA RED MOVEMENTDETECTORSPassive Infra Red (PIR) detectors are designed to

detect movement in a protected area by detecting

changes in infra red radiation levels within its field of

vision. If movement is detected the PIR detector will

generating an alarm signal at the Control Panel, (if

the system is armed). PIR detectors will also detect

animals, so ensure that pets are not permitted

access to areas fitted with PIR Movement Detectors

when the system is armed.

Additional Passive Infra Red Movement Detectors

can be purchased separately, if required.

MAGNETIC CONTACT DETECTORSEach Magnetic Contact Detector comprises two parts;

a Magnetic Contact Switch and a Magnet. They are

designed to be fitted to either doors or windows with

the Magnet fixed to the moving/opening part and the

Contact Switch fixed to the door or window frame.

When the protected door or window is closed, the

Contact Switch is held closed by the magnetic field

from the Magnet. Opening the protected door or

window will remove the magnetic field and allow the

contact switch to open generating an alarm signal at

the Control Panel, (if the system is armed).

Additional Magnetic Contacts can be purchased

separately, if required.

EXTERNAL SIRENThe External Siren enclosure houses the Siren, which

when assembled, installed and wired to the Control

Panel will activate in the event of an intrusion with the

system armed. In the event of the cable to the Siren

Unit being deliberately cut an alarm will be generated

at the control panel, provided that the tamper circuit

to the Siren has been connected.

INTRODUCTION & OVERVIEW

2 PA4 Alarm

SYSTEM OPERATION AFTER POWER FAILUREIf a power failure occurs while the system is

armed and backup batteries are not fitted (or flat)

then when power is restored the system will be in

its previously armed state. If there are any PIR

detectors wired to any active zone then an alarm

will initially occur. The siren will sound for the set

alarm duration after the 3-4 minutes required for

the PIR detectors to stabilise.

This is because the PIR detectors require a period

of 3-4 minutes to stabilise before they operate

correctly and during this period they effectively

generate an alarm signal to the Control Panel.

Note: Although optional, it is strongly recommended

that backup batteries are fitted.

Page 5: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INTR

OD

UC

TIO

N

KIT CONTENTSThe PA4 Wired Intruder Alarm System contains the

following components.

1 x 4 Zone Control Panel

1 x Mains Adaptor

1 x External Siren

1 x External Siren Enclosure

2 x Passive Infra Red Movement Detectors

2 x Magnetic Contact Detectors

1 x 50 metres (approx) of 6 Core Cable

1 x Cable Clips and Fixings

Also included:-

Installation & Operating Manual

Window Warning Stickers

IMPORTANTPlease check all items are present BEFORE breaking

the packaging warranty seals. No claims for missing

parts will be accepted unless pack seals are in place

and intact.

EXTENDING THE PA4 ALARM SYSTEMThe following additional accessories are available to

enhance your system and provide further protection

and a higher level of security where required.

Important: The PA4 system can be expanded to

contain maximum of 7 PIR detectors.

Component Order Code

Accessory Pack

comprising the following:

2 x Passive Infra Red Movement Detectors

2 x Magnetic Contact Detectors

25 metres (approx.) of 6 Core Cable PU1

Passive Infra Red Movement Detectors

(Twin Pack) PU2

Full details of these accessories are given on page 24.

External Siren Enclosure

EXIT1. Check all windows and doors are closed.2. a) Fullguard - Press 'Away' then 'Arm'.or b) Partguard - Press 'Home' then 'Arm'.3. Leave premises by entry/exit route.ENTRY1. Enter premises by entry/exit route.2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode.

MAINS CLEAR 24Hr

Zone 1 Zone 2 Zone 3 Zone 4

1 2 3

0

4 5 6

7 8 9

ARM

OMIT

RESET

HOMEERAWAY

Control Panel

2 x Magnetic ContactDetectors

Mains Adaptor

2 x PIR Movement Detectors

ExternalSiren

3PA4 Alarm

Page 6: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INTR

OD

UC

TIO

N

SYSTEM FEATURES

USER FUNCTIONS

ARM/DISARMThe system has an easy arming facility. To fully arm

the system simply press the button or to partially

arm the system, omitting preselected Zones; press

the button. Then press .

QUICK SETThe final arming of the system can be quicker. This is

useful for night setting when the Entry/Exit sounder

can be silenced after just a few seconds.

EVENT LOGThe Control Panel incorporates an Event Log memory

capable of storing the last 4 alarm events. The Event

Log replay will enable the user to establish which

Zones have been activated if an alarm has occurred.

HOME AND ZONE OMIT

The button is used if you are remaining on the

premises and require to arm the system while omitting

pre-selected Zones.

The button enables you to omit any Zone

combination you require on a once only or temporary

basis.

Note: The Entry/Exit Zone cannot be omitted.

RESETPressing the button clears any previously entered

information at the keypad, e.g. incorrect buttons

pressed and also clears Fault Lights, and resets the

system after an alarm.

INSTALLER FUNCTIONS

PROGRAMMINGWhen a valid installer code has been entered, access to

programming the various system options will be permitted.

ZONESThe Control Panel incorporates four detection Zones

for the connection of the system detectors. Zone 1 is

intended for exclusive connection to the detector(s)

which are located on the Entry/Exit route and will

operate the Entry/Exit timers and associated tones.

The Magnetic Contacts on the front door would

normally be connected to Zone 1.

Other Detectors can be connected to Zones 2, 3 and

4 to protect the remaining areas within the property, as

required.

24 HOUR TAMPER CIRCUITMany system components incorporate tamper

protection facilities and the associated wiring can be

monitored on a 24 hour basis to generate an alarm

condition if the equipment or wiring is interfered with.

It is recommended that all system components with

tamper facilities are monitored for tamper.

SIREN ANTI TAMPER MONITORINGWiring to the External Siren is monitored on a 24 hour

basis. In the event of the wiring to the External Siren

being damaged or deliberately cut, an alarm will be

initiated at the Control Panel.

PROGRAMMABLE ZONE OPTIONS

ENTRY/EXITZone 1 is programmed as Entry/Exit to allow the user

a preselected (adjustable) time delay to exit and enter

the premises without creating an alarm. During the

Entry/Exit procedures, a low audible warning tone will

be emitted from the Control Panel speaker. Normally

the front door of the property would be the Entry/Exit

route and would be connected to Zone 1.

WALK THROUGH ZONEZone 2 is programmed for a detector which is fitted

between the Entry/Exit door and the Control Panel,

e.g. in the downstairs hallway. When the Entry/Exit

door is opened and the entry procedure begins, the

‘Walk Through Zone’ is inhibited for the duration of the

entry time, allowing the system to be disarmed without

creating an alarm. However, if the ‘Walk Through

Zone’ is violated before the entry procedure is

initiated, a full alarm will instantly occur.

Note 1: It is advisable to change Zone 2 to an ‘Instant’

Zone if this facility is not required.

Note 2: Zone(s) selected as ‘Walk Through’, cannot

also be selected to operate on the ‘HOME’ feature.

PA4 Alarm4

OMIT

RESET

HOME

HOME

AWAY

ARM

Page 7: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INTR

OD

UC

TIO

N

GENERAL SYSTEM PROGRAMMABLEOPTIONS

ENTRY TIMEThis is the time programmed to allow the user to

reach the Control Panel to disarm the system before

an alarm occurs. The Entry Time may be set between

01 - 99 seconds, depending on your own requirements.

The default Entry Time is 30 seconds. If the system is

not disarmed during the Entry delay period, a full

alarm will occur when the Entry time expires.

EXIT TIMEThis is the time programmed to allow the user to

exit the premises before the system finally arms. The

default Exit Time is 30 seconds however, this time

may be set between 01 - 99 seconds, depending

on your requirements. You will need to leave all

protected areas and close protected doors/windows

before the Exit time expires or a full alarm condition

will occur.

Note: If a Zone is open when the system is armed

the Control Panel will emit a series of beeps

(different to the Entry/Exit tone) to indicate which

Zone is open, (i.e. 1 beep = Zone 1 open). It is not

possible to Arm the system until the Zone is clear or

omitted before arming.

ZONE OMITIt is possible to pre-program a section of Zones for

regular Zone omitting ie: night setting where ground

floor Zones are armed whilst first floor Zones are

omitted. Once programmed, the use of the

button will Arm the system omitting the selected Zones.

It is also possible to omit a specified Zone(s) different

to the ‘Home’ setting on a once only/temporary basis

using the button.

ALARM DURATIONThis is the time that the External Siren will sound for

following an alarm activation. The program Alarm

Duration time is 20 minutes, however this can be set

to between 01 - 20 minutes, depending on individual

requirements.

Note: Most Local Authority noise pollution requirements

set limits acceptable for alarm duration. You should

therefore check your Local Authority requirements.

SYSTEM RESET (RETURN ALL OPTIONS TOFACTORY SETTINGS)If the User/Installer Access Codes have been lost or

forgotten, or the installer is unsure of the programmed

options, it is possible to return the Control Panel

program to the factory default settings. All previously

programmed options will be cleared and the system

will require to be re-programmed to the user’s

requirements.

USER ACCESS CODETo Arm and Disarm the system and perform other

functions, the user must enter a unique 4-digit User

Access Code at the Control Panel keypad. The

default User Access Code is but

this should be changed to your own unique code

which only you and other system users know, once

installation is complete.

INSTALLER ACCESS CODETo allow programming of the system options, a unique

Installer Access Code must be entered at the Control

Panel keypad. If the user is installing the system, you

may choose your own code. However, if the system

has been installed for you by an approved installer, the

installation code may not be available. The factory

default Installer Access Code is but

this should be changed when the programming has

been completed.

KEYPAD SECURITYThe Control Panel is protected from unauthorised

disarming by means of initiating an alarm if more

than 4 incorrect attempts to enter the User Access

Code are made. In addition, if any button is pressed

when the system is armed, the Entry timer will start.

5PA4 Alarm

1 2 3 4

9 9 9 9

HOME

OMIT

Page 8: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

GENERALBefore attempting to install any wiring or system

components, it is recommended that a plan of the

proposed installation is prepared. This should help the

installation to be completed using the most unobtrusive

and effective methods. The following guidelines should

be followed and used in conjunction with the example

provided when preparing your own system plan.

LOCATING THE CONTROL PANELThe Control Panel should be located out of obvious

sight of potential intruders and in a safe location, but

easily accessible for system operation.

Typically, the Control Panel may be located close to the

main entry door or in a small cupboard under the stairs

(or similar) close to a mains socket. An ideal mounting

height would be the same as a household light switch

or similar. If small children are in the household, a

further consideration should be given to keeping the

Panel out of reach.

Also consider the user’s ability to hear the Entry/Exit

Tone emitted by the Control Panel effectively when

setting the system. It is preferable that the Exit Tone

can be heard from outside the property when arming

the system.

The final position of the Control Panel will depend on

the individual user requirements.

Note: If using the Home Arm feature the Control Panel

must not be located within an area protected by a PIR

Movement detector unless this detector is not

activated during Home Arm.

DETECTOR WIRINGWhere only one detector per Zone is to be connected,

the cable should be run directly to the detector.

However, if more than one detector is to be connected

to a Zone, either (a) run all cables back to the Control

Panel or (b) run one cable to the Control Panel and link

the detector contacts in ‘SERIES’ and power supplies

in ‘PARALLEL’, (refer to example installation wiring

diagrams on pages 15-16).

MAGNETIC CONTACT DETECTORSThe Magnetic Contact Detectors are suitable for

mounting in dry interior locations only.

Decide which doors and windows are to be protected by

fitting the Magnetic Contact Detectors. Normally the

front and back doors will have Magnetic Contact

Detectors fitted. Additional detectors may be fitted

where required to other more vulnerable doors or

windows, e.g. garage, patio and conservatory doors etc.

Note: It is not recommended to connect more than

four Magnetic Contacts to one Zone, as this may

cause difficulty in wiring and hinder any attempt to

remedy wiring faults efficiently.

PIR MOVEMENT DETECTORSThe PIR Detectors are suitable for mounting in dry

interior locations only.

When considering and deciding upon the mounting

position for the detector the following points should be

considered to ensure trouble free operation:

1. Ideally the detector should be positioned in a corner

of the room to be protected where the logical path

of an intruder would cut across the fan detection

pattern of the device. PIR detectors respond more

effectively to movement across the device than to

movement directly towards it.

2. Do not position the detector facing a window or

where it is exposed to direct sunlight. PIR detectors

are not suitable for use in conservatories.

3. Do not position the detector where it is exposed to

draughts.

4. Do not position the detector directly above a heat

source, (e.g. fire, radiator, boiler, etc).

5. Do not position the detector in a position where it is

subject to excessive vibration.

Note: When the system is armed, household pets

should not be allowed into an area protected by a PIR

as their movement would trigger the PIR and activate

the alarm. Alternatively a PIR protected Zone may be

'Omitted' to allow for pet movement.

EXTERNAL SIRENThe external housing should be located as high as

possible in a prominent position so that it can be

easily seen and heard. When running the cable to the

siren, the cable should pass through a hole in the

external wall and enter through the rear of the casing.

PLANNING THE INSTALLATION

PA4 Alarm6

Page 9: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

7PA4 Alarm

Bedroom 1

Landing Bedroom 3

Bedroom 2(Zone 4)

(omitted during night setting)

Front Door(Entry/Exit

Zone 1)

Back Door(Zone 2)

(Zone 3)

ControlPanel

Dining Room

External Siren

Living Room

Kitchen

Hallway

MagneticContactDetector

MagneticContact Detector

(Zone 3)

ControlPanel

PIR MovementDetector

PIR MovementDetector

PIR MovementDetector

EXIT1. Check all windows and doors are closed.2. a) Fullguard - Press 'Away' then 'Arm'.or b) Partguard - Press 'Home' then 'Arm'.3. Leave premises by entry/exit route.ENTRY1. Enter premises by entry/exit route.2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode.

MAINS CLEAR 24Hr

Zone 1 Zone 2 Zone 3 Zone 4

1 2 3

0

4 5 6

7 8 9

ARM

OMIT

RESET

HOMEERAWAY

TYPICALGROUND

FLOOR PLAN

TYPICAL FIRST FLOOR PLAN

Surface wiring to the External Siren is not recommended

unless it is mechanically protected, e.g. in steel tubing

or equivalent. However, if surface wiring is unavoidable,

the 24 hour monitoring will activate the Control Panel

sounder if damage occurs. However, if the system is

armed at the time a full alarm will occur.

FURTHER CONSIDERATIONSIf the system is to be armed at night ie. (Zones

omitted) while the occupants remain in the household,

make sure that any detectors which are to be omitted

are wired exclusively to those Zone(s).

(Remember that a ‘Walk Through Zone’ cannot also

be selected on the ‘Home’ setting). Pay particular

attention to the most vulnerable points of entry to

your property, which are the doors and windows to

the side and rear of the property.

Plan your cable runs for ease of installation and

neatness of final appearance, allowing for concealing

cables where necessary.

INSTALLATION EXAMPLEThe following example shows typical floor plans for a two

storey domestic property incorporating the suggested

positions for the Control Panel, External Siren and

Detectors, for optimum security. Use this as a guide for

your installation in conjunction with the recommendations

for planning your intruder alarm system.

In this example, the front door is the Entry/Exit route to

the property and is connected to Zone 1.

The side door is also fitted with a Magnetic Contact

and is connected to Zone 2.

The Living Room and Dining Room are fitted with PIR

Movement Detectors detecting entry into the rooms

from any angle and are connected to Zone 3.

An additional PIR has been fitted on the upstairs

landing. The upstairs PIR Movement Detector will

detect entry into the first floor and is connected to

Zone 4 (This is the Zone which will be intentionally

omitted when the system is armed at night).

Page 10: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

8 PA4 Alarm

Leads and Connectors forOptional Back-up Batteries

CoverFixing

Screws

BottomCover

SpeakerLeads

Detection and AlarmWiring Terminal Blocks

CoverTamperSwitch

Keypad

NVM Reset Pinsand Link

Top KeyholeFixings

Mains AdaptorSocket

Bottom FixingHole

12

34

56

711

812

1314

1718

2122

SPEAKERD BELL B

AUX24Hr

Z1Z2

Z3Z4 1 2 3

0

4 5 6

7 8 9

ARM

OMIT

RESET

HOMEERAWAY

NVM RESET

Choose a suitable position to locate the Control Panel

as described in ‘Planning The Installation’.

Note: The Control Panel should be mounted on an

even flat surface to prevent the possibility of distortion

to the Control Panel casing.

1. There is no need to completely remove the front

cover screws, simply loosen the screws, then hinge

open and lift the cover from the top lip and place

safely to one side.

2. Hold the Control Panel in position and mark the

location of the three mounting holes on the wall. A

small spirit level placed on the casing will ensure a

perfect level.

Note the position of the cable entries that you may

require before fixing the Control Panel. The final

use of cable entries will depend on the individual

installation requirements.

3. Remove the Control Panel, drill 3 x 6mm holes and

insert the 30mm plastic wall plugs supplied. Using

the 30mm No.8 screws fix the Control Panel loosely

onto the two slotted holes at the top. The top

screws may be tightened and the remaining bottom

screw inserted when the installation is complete.

Important: Do not drill the fixing holes with the

Control Panel in position, as the resulting dust could

seriously affect the system electronics and invalidate

the guarantee.

TESTING THE CONTROL PANELThe Control Panel is factory fitted with small wire links

inserted to the Zone and 24Hr Tamper connections.

These can be removed, then replaced when testing

the Control Panel to simulate a detector switch

opening and closing.

Note: If the front cover tamper switch is not bypassed,

the Control Panel will indicate a 24 hour fault, indicated

by the 24 Hr LED and internal sounder activating. To

temporarily bypass the Control Panel Anti Tamper

Switch, connect a short piece of the alarm cable

(approx. 100 mm) between terminals 11 and 21, while

you test the Zones. Leave this wire connected

throughout the installation and whilst you connect the

detectors to the Control Panel.

Should the panel speaker sound during testing,

press followed by to silence

the tone, followed by , then continue.

INSTALLING THE CONTROL PANEL

Control Panel Internal Physical Layout

or Current User Access Code

1 2 3 4RESET

RESET

Page 11: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

1. Connect the plug in Mains Adaptor and switch on

the supply.

2. Press then press . The clear LED will

illuminate.

3. Remove the factory fitted link from Zone 1 terminals.

The Zone 1 LED will flash and the internal speaker will

intermittently beep once. Refit the link to extinguish

the Zone 1 LED and silence the tone.

4. Repeat this procedure for Zones 2, 3 and 4. The

Control Panel will intermittently beep twice for Zone

2, three times for Zone 3 and four times for Zone 4.

5. To test the 24 Hr Zone, first ensure the temporary

link is removed between the terminals 11 and

21. Make sure you hold down the panel tamper

switch spring, press . Remove the factory

link between terminals 11 and 12 to activate the

internal speaker. Replace the link, then enter

.

Check the 24 Hr Zone LED is illuminated, then

press . Replace the temporary link between

terminals 11 and 21.

6. To end the test sequence, press .

7. The plug in Mains Adaptor must now be

disconnected, but will be re-connected when

testing each detector as it is installed.

WIRING THE DETECTION ZONESIn order to keep wiring consistent and aid

installation/connections, it is recommended that the

following wiring code is adhered to throughout the

installation:-

Red12V +ve supply to each

PIR Movement Detector

Black0V -ve supply to each

PIR Movement Detector

Yellow Normally closed detector contact alarmBlue Zone circuit

Green24 Hr normally closed Tamper CircuitWhite

The power supply to each PIR Movement Detector

should ideally be taken direct from the Control Panel

to each detector, so that a break in the cable only

results in one detector being out of service.

However, the power supply can be taken from one

detector to the next if required, up to a maximum of

four detectors or 50 metres of cable per Zone.

All Zone and Tamper circuit wiring must be wired in a

‘SERIES’ loop from the appropriate terminals in the

Control Panel. Where ‘Series’ connections are made

terminal blocks or insulating tape must be used to

prevent bare wires touching each other.

Surface cabling should be clipped at 1m intervals using

the clips supplied.

Please refer to the appropriate circuit wiring diagrams for

typical wiring arrangements for the detectors supplied.

PA4 Alarm 9

Zones TamperCircuit

PIR DetectorPower Supply Mains Adaptor

Factory Links

Note: Remove factory wire links before connecting circuit wiring. Leave the factory wire links in place where a zone/circuit is unused.

ExternalSiren

1 2 3 4 5 6 7 118 12 13 14 17 18 21 22SPEAKER D BELL B AUX24HrZ1 Z2 Z3 Z4

Control Panel Schematic Wiring Diagram Showing Factory Links Fitted

RESET

RESET

RESET

RESET

or Current User Access Code

1 2 3 4

AWAY

Page 12: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

INSTALLING THE PIRMOVEMENT DETECTORSThe Passive Infra Red (PIR) Movement Detectors

supplied with this kit are suitable for mounting in dry

interior locations only.

It is recommended that the PIR Detector is mounted in

the corner of a room, approximately 2.2m above floor

level. At this height the detector will have a 12m range

with a 90º spread. If required the detector may be

mounted at an 8° angle to tilt downwards and reduce

the detection pattern range.

Before fitting the detector, observe the environmental

considerations as described in ‘Planning The Installation’.

Note: A maximum of 7 PIR Movement Detectors can

be connected to the system in total.

PIR Detection Zone Patterns

MOUNTING THE PIR MOVEMENTDETECTORS

1. Having chosen a suitable position to locate the PIR

Detector, run the required length of 6-core cable

back to the Control Panel. Do not make any

connections at this stage.

2. Slightly loosen the cover retaining screw on the PIR

and remove the cover. Carefully remove the PCB by

un-clipping the PCB retaining clip at the bottom left

of the PCB.

Important: Do not touch the PIR sensor in the

middle of the PCB as any marking may impair the

unit’s performance. If accidentally touched, clean

with a lint-free cloth.

3. The unit can be mounted for the standard 12m

range by using the top two side holes, or tilted down

by 8° using the bottom two side holes. Alternatively,

the unit can be ceiling mounted using the two holes

at the extreme top of the casing. Cable entry cut

outs are provided top and bottom, as required.

4. Carefully cut (or drill) out the required mounting

holes and cable entry. Only remove the minimum

required number of screw or cable holes, to avoid

insects entering the detector and causing false

triggering. Mount the unit using two 18mm No.4

screws and 25mm wall plugs as required, (a 5mm

hole will be required for the wall plugs).

Note: Do not over tighten or use larger headed

screws when mounting the unit, as this may distort

the casing.

PIR Movement Detector PCB Layout

2.2metres

2.2metres

8° Tilt

Distance (metres)2 4 6 8 10 12

90° angle

Distance (metres)2 4 6 8 10 12

PIR Sensor (Do Not Touch)

Anti-TamperSwitch

AlarmLED

PulseCountJumperLink

PIR

LED

N/C 24HR 1 2 3

RetainingClip

ConnectionTerminals

CoverRetaining

Screw

10 PA4 Alarm

Top Mount

VerticalMount

Angled Mount 8°

Page 13: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

WIRING THE PIR MOVEMENTDETECTOR(S)

1. Thread the cable through the entry on the base,

then strip back 5 mm of each core, twist the strand

ends then fold over and wire into the appropriate

terminals on the PIR Movement Detector.

The terminals on the PIR and the wires in the cable

are colour coded. The correct colour coding

should be followed throughout the entire system.

Red +ve power supply to each PIR Movement Detector.

Black 0V power supply to each PIR Movement Detector.

Yellow/Blue Detector normally closed Alarm Contact

Zone circuit.

Green/White 24 Hr normally closed Tamper circuit.

2. Carefully refit the PCB into the casing taking care

not to touch the PIR detector lens.

3. The PIR Detector incorporates an anti false alarm

feature designed to compensate for situations where

the detector may be affected by environmental

changes, (e.g. insects, hot air thermals from

radiators, etc). This feature is called ‘Pulse Count’

and may be selected for 1, 2 or 3 pulse detection.

The factory default and recommended setting is for

2 Pulse detection. However, in cases of extreme

environmental problems, or if unattributable false

alarms are experienced, it may be necessary to set

"Pulse Count" 3.

Note: The higher the ‘Pulse Count’, the more

movement will be necessary before the PIR

detector will trigger the alarm.

Pulse Count jumper link positions

4. Select the required ‘Pulse Count’. Refit the cover and

tighten the retaining screw. The PIR Movement Detector

is now ready to be connected at the Control Panel.

5. Bring the detector cable(s) though the cable entry

slot in the rear of the Control Panel and strip back

5 mm on each core.

6. Ensure that the Mains Adaptor is disconnected

from the Control Panel. Remove the appropriate

wire links, then connect the wires to the terminals

as shown in the diagrams on pages 13 - 15.

7. When the wiring has been completed, connect the

plug in Mains Adaptor. Wait 4 minutes for the

detectors to stabilise. Only the ‘Mains’ LED should

be ‘ON’ at the Control Panel.

Note: If any Zone or 24 Hr LEDs are illuminated,

refer to ‘Fault Finding’.

TESTING THE PIR MOVEMENTDETECTORS AT THE CONTROL PANEL

1. Test the PIR Movement Detectors one at a time.

Important: When testing a PIR Movement Detector,

ensure that no movement occurs in any other area

protected by PIR Movement Detector.

2. Press . The ‘Clear’ LED will illuminate.

Slowly walk across the PIR Movement Detector’s

field of view. As you are detected, the LED on the

PIR Movement detector will illuminate and the

Control Panel will emit a number of beeps

corresponding to the Zone number the detector is

connected to and the relevant Zone LED will flash.

3. When clear of the detector, the beeps will cease

and the Zone and PIR detector LEDs will extinguish.

4. Allow ten seconds for the detector to settle, then

move again to confirm that the PIR detector gives

the desired protection within the area required.

5. Repeat the above test sequence for each PIR

Movement Detector fitted.

6. When all the PIR Movement Detectors have been

tested successfully, press to return to the

Standby Mode.

7. Disconnect the Mains Adaptor before continuing

with the installation.1 Pulse 2 Pulses 3 Pulses

1 2 3 1 2 3 1 2 3

PA4 Alarm 11

SIMPLE TROUBLE SHOOTING

If the PIR Movement Detector is not operating,ie. LED not illuminating, the following simplechecks should be carried out;

1. Allow 4 minutes for the detector to stabilise thenretest.

2. If the PIR Movement Detector LED does notilluminate, check the power supply to the PIR.Check for a damaged cable or poor termination.

3. If the PIR Movement Detector false alarms, the unitmay be positioned incorrectly. Re-position the unitand adjust the ‘Pulse Count’ if necessary.

4. If the PIR Movement Detector LED is operating, butnot activating an alarm, check that the relevant Zonewire link has been removed at the Control Panel.

AWAY

RESET

Page 14: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

12 PA4 Alarm

PIR MOVEMENTDETECTOR

GREEN

WHITE

BLACK

3 4Z 2

1 2Z1

5 6Z3

7 8Z4

11 1224Hr

13- 14+SPEAKER

17+ -18D BELL B

21- +22AUX

CONTROL PANEL

+ -N/C 24 Hr

BLUE

YELLOW

RED

CONNECT TO REQUIRED ZONE

PIR MOVEMENTDETECTOR

GREEN

BLACK

RED

YELLOW

BLUE YELLOW

BLUE

WHITE

+ -N/C 24 Hr

RED

+ -

N/C

24 Hr

BLACK

TWIST AND INSULATE

CONNECT TO REQUIRED ZONE

GREEN

TWIST AND INSULATE

3 4Z 2

1 2Z1

5 6Z3

7 8Z4

11 1224Hr

13- 14+SPEAKER

17+ -18D BELL B

21- +22AUX

CONTROL PANEL

PIR

MO

VE

ME

NT

DE

TE

CT

ORWHITE

Wiring diagram for a Single PIR Detector on a zone

Wiring diagram for two PIR Detectors to a single zone with all cables returning to the Control Panel

TYPICAL WIRING ARRANGEMENTS

PIR MOVEMENTDETECTOR

GREEN

BLACK

RED

YELLOW

BLUE YELLOW

BLUE

WHITE

WHITE

+ -N/C 24 Hr

GREEN

3 4Z 2

1 2Z1

5 6Z3

7 8Z4

11 1224Hr

13- 14+SPEAKER

17+ -18D BELL B

21- +22AUX

CONTROL PANEL

MAGNETICCONTACTBLACK

RED

Twist (or Solder)cable cores together

and insulate

Wiring diagram for PIR Detector and Magnetic Contact Detector on different zones with all cables returning to the Control Panel

Page 15: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

PA4 Alarm 13

3 4Z 2

1 2Z1

5 6Z3

7 8Z4

11 1224Hr

13- 14+SPEAKER

17+ -18D BELL B

21- +22AUX

CONTROL PANEL

"24-Hour"Wiring fromDetector 1

"24-Hour"Wiring fromDetector 2

"24-Hour"Wiring fromDetector 3

"24-Hour"Wiring fromDetector 4

"24-Hour"Wiring from

Siren TamperConnections

Zone Wiring from

Detector 1

Zone Wiring from

Detector 2

Zone Wiring from

Detector 3

Zone Wiring from

Detector 4

Twist (or Solder)cable cores together

and insulate

Twist (or Solder)cable cores together

and insulate

YELLOW

YELLOW YELLOW YELLOW

BLUE BLUE BLUE

BLUE WHITE

WHITE WHITE WHITE

GREEN GREEN GREEN

GREEN

WHITE

GREEN

Series wiring of zone connections frommultiple detectors on a single zone

Series wiring of 24-hour connections from multiple detectors

PIR MOVEMENTDETECTOR

+ -N/C 24 HrBLUE YELLOW

GREENWHITE

3 4Z 2

1 2Z1

5 6Z3

7 8Z4

11 1224Hr

13- 14+SPEAKER

17+ -18D BELL B

21- +22AUX

CONTROL PANEL

REDBLACK

PIR MOVEMENTDETECTOR

+ -N/C 24 Hr

BLUE

YELLOW

WHITE

GREEN

BLACK

RED

Twist (or Solder)cable cores together

and insulate

CONNECT TO REQUIRED ZONE

Wiring diagram for multiple detectors (connected in series) on a single zone with one cable returning to the Control Panel

Wiring diagram with zones 1-4 used with allcables returning to the Control Panel MAGNETIC

CONTACT

3 4Z 2

1 2Z1

5 6Z3

7 8Z4

11 1224Hr

13- 14+SPEAKER

17+ -18D BELL B

21- +22AUX

CONTROL PANEL

+ -N/C 24 Hr

PIR MOVEMENTDETECTOR

GREEN

WHITE

BLACK

RED

BLUE

YELLOW

+ -N/C 24 Hr

PIR MOVEMENTDETECTOR

WHITE

GREEN

BLACK

RED

YELLOW

BLUE

WHITE

GREEN

YELLOW

BLUE

MAGNETICCONTACT

BLUE

YELLOW

WHITE

Twist (or Solder)cable cores together

and insulate

GREEN

Page 16: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

14 PA4 Alarm

Decide which doors and windows are to be protected

by Magnetic Contact Detectors, usually the front and

back doors will have Magnetic Contact Switches fitted.

Additional contacts may be fitted where required to

other vulnerable doors or windows, e.g. garage, patio

and conservatory doors etc.

Note: It is not recommended to connect more than 4

Magnetic Contacts in any one zone, as this may cause

difficulty in wiring and hinder any attempt to efficiently

remedy any wiring faults and locate the device that

initiated the alarm.

1. Having chosen a suitable position to locate the

Magnetic Contact, run the required length of 6 core

cable back to the Control Panel.

Alternatively, Magnetic Contact(s) may be wired in

series with each other and terminated appropriately.

However, working space within the Magnetic Contact

is limited and more than two or three termination's

may prove difficult.

Do not make any connections at this stage.

2. Fit the Magnet to the moving part of the window or

door (on the opening edge opposite the hinge) and

make sure that the parallel gap to where the Contact

Switch is fitted on the frame is no more than 9mm.

Typical position of contact fitted to door

WIRING THE MAGNETIC CONTACTS1. Remove one of the cable entry cut-outs on the

Contact Switch and thread the cable through the

entry into the Contact Switch housing.

2. Carefully remove the outer sheath of the cable and then

strip 5mm of insulation from the Yellow and Blue wires.

Connect the Yellow and Blue wires to the Contact

Switch terminals as shown.

3. Strip off 5 mm of the insulation from the Green and

White wires and connect together using a spare

terminal in the contact housing.

Note: If the spare contact terminals are not present in

the contact then the ends of the wires should be

securely twisted (or soldered) together and insulated.

If connecting multiple contacts the Tamper circuit

wiring should be continued in a series loop in a

similar way to the zone wiring.

The remaining wires should be trimmed back and

insulated to prevent short circuits and then tucked

away in the Contact Switch housing.

4. Fix the Contact Switch to the fixed part of the door/

window frame immediately beside and parallel to the

Magnet using two 25mm Counter-sunk fixing screws.

Ensure that the parallel gap between the Magnet and

Contact Switch positions is no greater than 9mm.

5. Bring the contact cable(s) through the cable entry

slot in the rear of the Control Panel and strip back

5mm of each core and twist the strand ends.

INSTALLING THE MAGNETIC CONTACT DETECTORS

MagnetMagnet Contact

SwitchContactSwitch

WindowMounting

DoorMounting

Max Gap9mm

(door/windowclosed)

Note: If spare terminalsare not present in theContact Switch, ends ofwires should be twisted(or soldered) togetherand insulated.

WHITE

BLUE

YELLOW

GREEN

MULTIPLE CONTACTSWired in series

SINGLE CONTACT

WHITE

BLUE

GREEN

YELLOW

Page 17: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

6. Ensure the Mains Adaptor is disconnected at the

Control Panel. Remove the appropriate Zone wire

link and then connect the wires to the Control Panel

terminals as shown in the diagrams on pages 13 - 15.

7. When the wiring has been completed, re-connect

the Mains Adaptor.

8. Wait 4 minutes for any PIR Movement Detectors to

stabilise, and then clear all protected area(s).

9. No Zone or 24 Hr LEDs should be ‘ON’ at the

Control Panel at this stage.

TESTING MAGNETIC CONTACTS ATTHE CONTROL PANEL1. First, ensure that all doors and windows fitted with

Magnetic Contacts are closed.

2. Press and the ‘Clear’ LED will illuminate

Note: At this stage, if any Magnetic Contacts are

open or PIR Movement Detectors are activated,

the relevant Zone LED(s) will be illuminated and

the panel will beep, The number of beeps will

indicate which Zone is open. You should ensure

that no movement occurs in areas fitted with PIR

Movement Detectors, as this may cause

confusion during the test sequence. If walking

past a PIR Movement Detector is unavoidable,

allow 10 seconds at the Control Panel for the PIR

Movement Detector to settle.

3. Open the first contact, the Control Panel will emit a

number of beeps corresponding to the Zone

number the detector is connected to and the

relevant Zone LED will flash.

Close the contact to silence the beeps and

extinguish the LED.

4. Repeat the test sequence for all Magnetic

Contacts fitted.

5. When the Magnetic Contacts have been tested

successfully, press to return to the Standby

Mode.

6. Now disconnect the Mains Adaptor before

continuing with the installation.

INSTALLING THEEXTERNAL SIRENThe External Siren should be fitted to the outside of

the building in a prominent position that is clearly

visible and at a height that is relatively inaccessible

to an intruder.

Consideration should also be given to the cable

route to the siren, with the cable preferably passing

directly through the external wall into the back of

the siren housing.

FITTING THE EXTERNAL SIREN UNIT

IMPORTANT: If ladders are required to reach the

mounting position of the Siren they should be

positioned on a firm stable surface at the correct

angle and suitably secured before use.

1. Undo the two front cover retaining screws and

remove the front cover by sliding up and away

from the backplate.

2. Fix the siren mounting bracket to the backplate

using the M3 screws, nuts and washers supplied.

3. Run the required length of cable from the Control

Panel to the External Siren position. Drill a

suitable hole through the wall so that the cable

enters through the rear of the housing without

showing on the outside of the property.

PA4 Alarm 15

BACK-PLATE

CABLEENTRYHOLE

SIRENBRACKET

SIREN

SIREN COVER

AWAY

RESET

Page 18: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

INSTA

LLATIO

N

16 PA4 Alarm

4. Hold the backplate in position so that the hole

drilled for the cable is aligned with the cable

entry aperture and Mark the positions of the four

mounting holes. A spirit level placed on the

casing will ensure a perfect level.

5. Mount the backplate using four 35mm No.10

screws and 30mm wall plugs supplied, (a 6mm

hole will be required for the wall plugs).

WIRING THE SIREN UNIT

1. Ensure the Mains Adaptor is disconnected at the

Control Panel.

2. Strip back 5mm of insulation from the Red, Black,

Green and White wires.

3. Twist and double over the end of each wire, then

connect to the terminal blocks in the Siren and

Control Panel as shown below.

External Siren Wiring Arrangement

Note: The Green and White Tamper circuit wires

should be wired in series with the Green and White

tamper circuit wires from the detectors at the

Control Panel terminal block.

4. Refit the External Siren cover.

CONNECTING THECONTROL PANEL MAINSADAPTOR AND OPTIONALBACK-UP BATTERIES

1. Connect the Mains Adaptor to the plug in

connector in the Control Panel.

2. Plug the adaptor into a 13A socket and switch ON.

The mains LED will illuminate when the Control

Panel is powered from the mains.

(It is normal for the Mains Adaptor to appear warm

to the touch when in use).

Note: Ensure that the adaptor will not be removed

from the socket or accidently switched off, when

the system is in use.

Optional Back-up Batteries

The Control Panel has the facility to connect

Optional Back-up Batteries which will power the

system for up to 4 hours in the event of a mains

failure. Fit 2 x 9 volt PP3 Alkaline Batteries

(not supplied) to the battery connectors in the

Control Panel housing.

Note: The Back-up Batteries are NOT recharged

upon restoration of the mains supply and should be

replaced after any mains failure. The batteries

should also be changed every year to prevent

leakage and possible damage to the Control Panel.

3. The Control Panel fixing screws may now be finally

tightened. Do not over tighten the screws as this

may damage the casing.

4. Remove the temporary Anti-Tamper wire link from

terminals 11 and 21. In doing so, the internal

speaker will sound. Refit the cover and secure the

cover retaining screws, then enter

to silence the alarm.

Press to return to Standby Mode.

1124Hr 1217D BELL B 18

+–

Terminalsin Control

Panel

RED

GREEN

WHITE

BLACK

External Siren

RED

BLACK

Terminal Block

Tamper CircuitWiring to Other

Detectors

GREEN

WHITE

Twist (or Solder)cable cores together

and insulate

RESET

or Current User Access Code

1 2 3 4

Note: Although optional, it is strongly

recommended that backup batteries are fitted.

Page 19: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

PR

OG

RA

MM

ING

PROGRAMMINGGENERALProgramming of the Control Panel options is divided

into two distinct categories, User Programming and

Installer Programming. User programming is used

when the system is fully operational, whilst Installer

Programming is only carried out when the system is

new or when subsequent changes are required.

Access to either programming mode requires a valid

User or Installer Access Code to be entered. The more

complex and infrequently required programmable

options are available in Installer Programming Mode

only. This prevents the major system functions from

being accidentally changed by a general User.

The Control Panel has most of the options factory

pre-set at the most common settings, please

consider whether you really need to change them

before re-programming.

Programmable options accessed via Installer

Programming Mode are;

a) Selecting Walk Through Zone(s)

b) Entry Time Adjustment

c) Exit Time Adjustment

d) Selecting ‘Home’ Zones (Part Setting)

e) Alarm Duration

f) Select User Access Code arming

g) Change Installer Access Code

h) Reset System Defaults

Programmable options accessed via User

Programming Mode are;

Change User Access Code

Note: The User Access code can only be changed

if the "Code Arming" feature is disabled.

INSTALLERPROGRAMMING MODEBefore changing any installer programmable options,

the Control Panel must be set to Installer Programming

Mode. This is shown by the ‘Clear’ LED flashing.

Enter the default or current Installer Acess Code.

The ‘Clear’ LED will flash to indicate that the system is

now in the Installer Programming Mode.

Once programming is complete press to return

to Standby Mode.

Note: When selecting options, the system will allow

30 seconds to make a selection. If this time is exceeded,

the Control Panel will exit the function and revert to

Installer Programming Mode and the option button will

have to be pressed again. Once a selection is made the

system will allow 10 seconds for a valid key to be

pressed. If this time is exceeded the system will return

to the top level of the installer mode and the selection

will have to be made again.

Before starting programming any feature read all the

steps first.

CHANGING THE INSTALLER ACCESS CODE

Factory default Setting: 9 9 9 9

To maintain the security of your system the Installer

Access code should be changed from the factory

default to your own unique 4-digit code. The Installer

Access code must not be the same as the User

Access code. Make a note of the new Installer Access

Code in the Alarm Record section.

To change the setting proceed as follows:

With the Control Panel already in the Installer

programming Mode (‘Clear’ LED flashing),

Press .

The 4 Zone LEDs will illuminate.

Enter the new 4-digit Installer Access code

As each digit is entered, a Zone LED will extinguish in

sequence.

Press to save the new setting or

Press to exit without saving.

The system will return to the top level Installer

Programming Mode with only the Clear LED flashing.

EXIT DELAY TIME ADJUSTMENT

Factory default Setting: 30 seconds

To change the setting proceed as follows:

With the Control Panel already in the Installer

programming Mode (‘Clear’ LED flashing),

PA4 Alarm 17

or Current Installer Access Code

9 9 9 9

RESET

ARM

RESET

1

? ? ? ?

Page 20: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

PR

OG

RA

MM

ING

Press .

Zone 1 and 2 LEDs will illuminate.

Enter the required Exit Delay time (1-99), e.g. enter “01”

for a 1s delay, enter “99” for a 99s delay.

Press to save the new setting or

Press to exit without saving.

The system will return to the top level Installer

Programming Mode with only the Clear LED flashing.

ENTRY DELAY TIME ADJUSTMENT

Factory default Setting: 30 seconds

To change the setting proceed as follows:

With the Control Panel already in the Installer

programming Mode (‘Clear’ LED flashing),

Press .

Zone 1 and 2 LEDs will illuminate.

Enter the required Entry Delay time (1-99), e.g. enter

“01” for a 1s delay, enter “99” for a 99s delay.

Press to save the new setting or

Press to exit without saving.

The system will return to the top level Installer

Programming Mode with only the Clear LED flashing.

ALARM DURATION ADJUSTMENT

Factory default Setting: 20 minutes

To change the setting proceed as follows:

With the Control Panel already in the Installer

programming Mode (‘Clear’ LED flashing),

Press .

Zone 1 and 2 LEDs will illuminate.

Enter the required Alarm Period (1-20), e.g. enter “01” for

a 1 minute duration, enter “15” for a 15 minutes duration.

Press to save the new setting or

Press to exit without saving.

The system will return to the top level Installer

Programming Mode with only the Clear LED flashing.

SELECTING “HOME” FEATUREZONES

The button can be used to part-arm the system

omitting a selection of pre-selected Zones. This feature

is useful if you have a regular requirement to arm the

system with a permanent selection Zone(s) omitted.

For example at night when you may wish to have the

detectors on the ground floor armed, whilst the

detectors on the first floor are disarmed.

Note: The Entry/Exit Zone (Zone 1) and any zones

configured as ‘Walk Through’ cannot be omitted from

"Home" Arm.

To select the Zones to be omitted when using the

‘HOME’ feature proceed as follows:

With the Control Panel already in the Installer

programming Mode (‘Clear’ LED flashing),

Press .

The zone LEDs corresponding to the Zones currently

selected to be omitted during "Home" operation will be

illuminated.

LED ON Zone omitted during "Home" arm

LED OFF Zone active during "Home" arm.

To change the setting of a zone press the button

corresponding to the zone number. The zone will

toggle between omitted and active each time the

button is pressed. Remember, Zone 1 and any "Walk

Through" zones cannot be omitted.

Press to save the new setting or

Press to exit without saving.

The system will return to the top level Installer

Programming Mode with only the Clear LED flashing.

SELECTING WALK THROUGH ZONESZones which are located between the Entry/Exit door

and Control Panel should be configured as "Walk

Through" zones.

Zone 1 cannot be configured as a ‘Walk Through’ zone.

Zone 2 is factory set as a ‘Walk Through’ zone. It is

advisable to change Zone 2 to an ‘Instant’ Zone if this

facility is not required.

To select the Zones to be configured as "Walk Through"

zones proceed as follows:

18 PA4 Alarm

2

4

ARM

RESET

HOME

6

ARM

RESET

ARM

RESET

ARM

RESET

3

Page 21: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

With the Control Panel already in the Installer

programming Mode (‘Clear’ LED flashing),

Press .

The zone LEDs corresponding to the Zones currently

set as "Walk Through" zones will be illuminated.

LED ON Walk Through ON

LED OFF Walk Through OFF (i.e. Instant).

To change the setting of a zone press the button

corresponding to the zone number. The zone will

toggle between "Walk Through" and "Instant "each

time the button is pressed. Remember, Zone 1 cannot

be set as "Walk Through".

Press to save the new setting or

Press to exit without saving.

The system will return to the top level Installer

Programming Mode with only the Clear LED flashing.

SELECTING ‘CODE ARMING’For convenience the Control Panel is factory set to be

able to be armed without first entering the User

Access Code. To avoid accidental arming, or if there

is a concern regarding children arming the system, it

is possible to program the Control Panel to require the

User Access Code to be entered before allowing the

system to be armed.

Important: The User Access Code should be changed

from the factory default before activating this functionality.

To activate or de-activate the code arming feature

proceed as follows:

With the Control Panel already in the Installer

programming Mode (‘Clear’ LED flashing),

Press .

Zone LED 2 will indicate the current status of the code

arming feature.

Zone 2 LED ON Code Arming Enabled

Zone 2 LED OFF Code Arming Disabled

To change the setting press to toggle code arming

ON and OFF each time the button is pressed.

Press to save the new setting or

Press to exit without saving.

RESET SYSTEM DEFAULTSIf the User Access Code has been lost or forgotten, or

the installer is unsure of the options programmed, the

system may be returned to the factory settings by the

following method;

With the Control Panel already in the Installer

programming Mode (‘Clear’ LED flashing),

Press .

Zone 1 led will flash briefly to indicate that all system

default settings have been restored.

LOST OR FORGOTTEN INSTALLER ACCESS CODE1. Switch off mains power and remove the Control

Panel front cover. The alarm will sound on tamper

if backup batteries are fitted.

2. If fitted disconnect the Control Panel Back-up

Batteries.

Important: The mains and battery power supply

must be removed before continuing.

3. Place the Jumper Link across both of the NVM

RESET pins positioned on the Control Panel PCB.

4. Wait for 30 seconds and then switch on the mains

supply adaptor.

The Clear and 24Hr LEDs will flash and after

approximately 5 s the alarm will sound on tamper,

Enter the default User Access code,

, to cancel the alarm.

5. Remove the Jumper Link (store on one Pin) replace

the front cover and reconnect the mains.

The Control Panel has been returned to factory

settings and will require programming to your

requirements.

USER PROGRAMMINGMODECHANGING THE USER ACCESS CODE

Factory default Setting: 1 2 3 4

PR

OG

RA

MM

ING

PA4 Alarm 19

1 2 3 4

7

0

8

2

ARM

RESET

ARM

RESET

Note: The User Access code can only be

changed if the "Code Arming" feature is disabled.

Page 22: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

To maintain the security of your system the User

Access code should be changed from the factory

default to your own unique 4-digit code. The User

Access code must not be the same as the Installer

Access code. Make a note of the new Installer Access

Code in the Alarm Record section.

Note: If no key is pressed for a period of 10s while

within the function the system will return to Standby

mode without any changes being made.

To change the User Access Code proceed as follows:

With the Control Panel in Standby Mode (Mains LED

only On),

Enter the default or current User Access Code code

.

All zone LEDs will illuminate and the Clear LED will flash.

Enter the new 4-digit User Access code

As each digit is entered, a Zone LED will extinguish in

sequence.

Press to save the new setting or

Press to exit without saving.

The system will return to Standby Mode.

TESTING THE SYSTEMTo test the system

1. ‘Arm’ the system, by pressing then , the

Exit Timer will start, press again to quick set

the system.

2. Walk in front of a PIR Movement Detector or open

a door or window fitted with a Magnetic Contact

Detector. The Control Panel Sounder & External

Siren will activate. (You can open a contact in the

Entry/Exit route, however you will have to wait for

the selected Entry Time to end before the system

will activate).

3. Return to the Control Panel and enter the User

Access Code .

The alarm will cease and the relevant Zone LED will

be illuminated.

You may test your system at any time, however, it is

recommended that the system is tested at regular

intervals not exceeding three months. Test a different

PIR /Magnetic Contact on each test occasion.

OPERATINGINSTRUCTIONS The following procedures for Arming and Disarming

the system are based upon having the "Code Arming"

feature disabled. If "Code Arming" has been enabled

during installation programming the User Access

Code will have to be correctly entered at the keypad

before the following procedures will have any effect.

‘AWAY’ ARMING ALL ZONESBefore arming the system, ensure all detectors are

unobstructed and that all doors and windows are

closed and secure.

Press .

If any Zone LED are ‘ON’, this indicates that a

door/window contact is open or movement is

being detected by a PIR on a zone being armed.

Check that all doors/windows are closed and

that PIR protected areas are clear of movement

so that only the clear LED is illuminated before

continuing the arming sequence.

When the ‘Clear’ LED only is ‘ON’, press .

The Exit tone will start. During the last ten seconds

of the Exit Delay, the tone will change pitch.

You must leave the property via the Entry/Exit

route before the Exit Delay expires, when the

tone will stop and the system will be armed.

Note: If a detector on Exit zone (zone 1) is

triggered (e.g. the exit door is opened) during the

exit delay an interrupted exit tone will be heard.

When the zone is closed again the normal exit

tone will be heard. If any detector on Zones 2, 3,

or 4 is triggered during the exit delay and warning

tone will be heard and the exit delay period will be

Note: If Code Arming has been enabled, the User

Access Code must be entered before proceding

with the following sequnce.

20 PA4 Alarm

or Current User Access Code

1 2 3 4

ARM

RESET

? ? ? ?

ARM

ARM

AWAY

ARM

AWAY

Current User Access Code

? ? ? ?

OP

ER

ATIO

N

Page 23: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

suspended until the zone is cleared when the exit

delay will continue. All zones must be closed

when the exit delay expires or an alarm will occur.

‘HOME’ ARMING PRE-SELECTEDZONESThe ‘Home’ facility can be used to arm the system

with regularly used pre-selected Zones programmed

to be omitted.

Before arming the system, ensure all detectors are

unobstructed and that all doors and windows are

closed and secure.

Press .

If any Zone LEDs are ‘ON’, this indicates that a

door/window contact is open or movement is

being detected by a PIR on a zone being armed.

Check that all doors/windows are closed and

that PIR protected areas are clear of movement

so that only the clear LED is illuminated before

continuing the arming sequence.

When the ‘Clear’ LED only is ‘ON’, press .

The Exit tone will start. During the last ten seconds

of the Exit Delay, the tone will change pitch.

When the tone stops and the system will be armed.

ARMING WITH OCCASIONAL ZONESOMITTEDIf a system needs to be armed with a Zone

combination different to that configured for the

‘HOME’ arm setting, it is possible to select a Zone(s)

to be omitted on a temporary (one time) basis.

Before arming the system, ensure all detectors are

unobstructed and that all doors and windows are

closed and secure.

Press .

If any Zone LEDs are ‘ON’, this indicates that a

door/window contact is open or movement is

being detected by a PIR on a zone being armed.

Check that all doors/windows are closed and that

PIR protected areas are clear of movement so

that only the clear LED is illuminated before

continuing the arming sequence.

When the ‘Clear’ LED only is ‘ON’, press .

The 24Hr LED will flash.

Press buttons , or to select the

Zone(s) you wish to omit. The zone LEDs will

illuminate to indicate if the zone is omitted.

Note: The Entry/Exit Zone (Zone 1) cannot be omitted.

When the zones required to be omitted have been

selected press .

The Exit tone will start. During the last ten seconds

of the Exit Delay, the tone will change pitch.

When the tone stops and the system will be armed.

QUICK ARMAfter arming the system in either "Home" or "Away"

modes using the procedures described above the

"Quick Arm" feature may be used to cancel any

remaining exit delay period and Arm the system within

5s. This is useful for setting the system at night to

silence the exit tone after just a few seconds.

Press again while the exit tone is running to Quick

Arm the system after a few seconds.

DISARMING THE SYSTEMEnter the premises via the designated Entry route.

The Entry tone will start. During the last ten seconds

of the Entry Delay, the tone will change pitch.

Proceed directly to the Control Panel and Disarm

the system by entering the User Access Code

.

The system will disarm and the Entry tone will stop.

Note 1: To Disarm the system during Home Arming

proceed directly to the Control Panel and enter the

User Access code.

If an alarm has occurred while the system was Armed

the zone LED(s) of the zone(s)that triggered the alarm

will be illuminated, take note of Zones.

To clear any illuminated zone LEDs press .

? ? ? ?

PA4 Alarm 21

HOME

ARM

ARM

ARM

RESET

2 3 4

AWAY

OMIT

Note: If Code Arming has been enabled, the User

Access Code must be entered before proceding

with the following sequnce.

Note: If Code Arming has been enabled, the User

Access Code must be entered before proceding

with the following sequnce.

OP

ER

ATIO

N

Page 24: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

EVENT LOGIf an alarm has occurred, the Event Log will enable the

user to recall the Zone(s) that have triggered the alarm.

The Event Log will record the last 4 alarm events.

Press .

The zone that triggered the most recent alarm will

be illuminated.

The zone that triggered the most recent alarm will

be illuminated.

Press again up to 3 times to recall the

previous 3 alarm events in sequence.

Press to return to show the most recent

alarm.

Press again to return the system to ‘Standby’

mode.

MAINTENANCEYour PA4 Intruder Alarm system requires very little

maintenance. However, a few simple tasks will ensure

its continued reliability and operation.

CONTROL PANEL AND DETECTORSThe Control Panel and detectors require no

maintenance. If cleaning is required, wipe the outside

of the casings with a soft damp cloth. Do not use

aerosols or sprays or proprietary cleaners. Do not

attempt to clean inside the units or allow water to

enter the units.

BACK-UP BATTERIESThe Optional Back-up Batteries in the Control Panel

should be replaced every 12 months or after a

prolonged power failure.

OP

ER

ATIO

N

Settings

Complete the following information during installation for future reference when adding to your system

and to assist Trouble Shooting.

PA4 ALARM RECORD

Zone Detector Type(s) Location(s) Instant/ Walk Home Delay Through Zone Omit

1 Delay N/A N/A

2

3

4

24HrTamper N/A N/A N/A

This information is highly confidential and should be kept in a very safe location.

You may make a note of your User Access Code and Installer Access Code below.

User Access Code

Purchase Date/Installation Date

Installer Access Code

Control Panel Serial Number

22 PA4 Alarm

ER

ER

RESET

RESET

Page 25: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

24 hour fault (Internal Sounder or full alarm ifsystem is armed).

1. PIR Detector Anti-Tamper Switch not closed fully -check/refit detector cover.

2. External Siren cable connections loose or a cabledamaged.

3. 24 hour Zone wiring open eg. damaged or incorrectwiring or poor terminations.

Passive Infra Red Movement Detector notdetecting a person’s movement

1. Allow up to 4 minutes for the detector to settle downand retest.

2. ‘Pulse Count’ set too high - reset to one or two‘Pulse Count’ detection.

3. Ensure that detector is mounted the correct way up(with the cover fixing screw at the bottom).

4. Ensure that the detector is mounted at the correctheight 2.2 metres from floor.

5. Check that the detector is correctly wired.

Passive Infra Red Movement Detector false alarming

1. Ensure that the detector is not pointing at a source ofheat or a moving object.

2. Ensure that the detector is not mounted above aradiator or heater.

3. Ensure that the detector is not facing a window or indirect sunlight.

4. Check Zone wiring to detector alarm contacts.

Magnetic Contacts false alarming

1. Check that door/window closes firmly and thatmovement cannot trigger the contacts.

Magnetic Contacts not operating

1. Check that gap between Magnet and Switch Contactblocks is less than 9 mm.

2. Check Zone wiring to contacts. (All contacts on aZone must be wired in ‘Series’).

External Siren Sounding continuously (24 hourLED NOT illuminated)

1. Check for incorrect wiring to External Siren.2. Check for short-circuits in cable to siren, causing

siren to be permanently energised.

False Alarms when the system is Armed

1. Carefully note the Zone which activated the alarmbefore pressing ‘Reset’. Only the detector(s) andwiring on that Zone will need to be checked.

2. Check all Zone wiring and connectors for security.3. For PIR false alarms, consider increasing ‘Pulse

Count’ settings on suspect detector.

Mains LED is not illuminated

1. Check mains power supply.2. Check Mains Adaptor cable and connection onto

PCB.3. Mains power failure - check if other electrical circuits

are operable.

Detection Zone has been triggered but noalarm is sounding

1. Entry Delay Zone(s) triggered - alarm will sound whenthe Entry Delay Time expires.

2. Zone omitted on ‘Home’ setting.3. Zone temporarily omitted before arming.

Symptom / Recommendation Symptom / Recommendation

TROUBLE SHOOTING

PA4 Alarm 23

HELPLINEIf you have a problem with your alarm,

please call the helpline on:

01268 563273(Lines open 9.00am to 5.00pm, Monday to Friday)

Page 26: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

ACCESSORIES

EXTENDING YOUR PA4 WIRED INTRUDERALARM SYSTEMYour system may be expanded to give additional protection by adding additional PIR Movement Detectors and

Magnetic Contact Sets.

PU2

PU3

PU1

ACCESSORY PACK - PU1The PU1 Accessory Pack comprises 2 PIR Movement Detectors, 2 Magnetic

Contact Sets and approx. 25 metres of 6 Core Cable.

PASSIVE INFRA RED MOVEMENT DETECTORS(TWIN PACK) - PU22 additional PIR Movement Detectors.

DUMMY SIREN - PU3Siren box for added visual deterant.

24 PA4 Alarm

Page 27: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

PA4 Wired Intruder Alarm System Friedland

If you have a problem with your Alarm, please call the Helpline on:

01268 563273(Lines open 9.00am to 5.00pm, Monday to Friday).

GUARANTEENovar ED&S undertakes to replace or repair at its discretion goods

(excluding non rechargeable batteries) should they become defective

within 1 year solely as a result of faulty materials and workmanship.

Understandably if the product has not been installed, operated or

maintained in accordance with the instructions, has not been used

appropriately or if any attempt has been made to rectify, dismantle or

alter the product in any way the guarantee will be invalidated.

The guarantee states Novar ED&S entire liability. It does not extend to

cover consequential loss or damage or installation costs arising from

the defective product. This guarantee does not in any way affect the

statutory or other rights of a consumer and applies to products installed

within the UK and Eire only

If If an item develops a fault, the product must be returned to the point

of sale with:

1. Proof of purchase.

2. A full description of the fault.

3. All relevant batteries (disconnected).

Friedland is a trade mark of Novar ED&S.

Friedland, Novar Electrical Devices and SystemsThe Arnold Centre, Paycocke Road

Basildon, Essex SS14 3EA

Page 28: 4 Zone Wired Intruder Alarm System - Response Electronics … … · mains failure, the system will ... at the control panel, provided that the tamper circuit ... 2 PA4 Alarm SYSTEM

Control Panel

● Four Detection Zones

● Tamper Zone

● Front Cover Anti-Tamper

● Zone(s) programmable for

- Entry Delay

- Walk Through

- Zone Omit

● Temporary Zone Omit facility

● Entry Delay variable 01 - 99 seconds

● Exit Delay variable 01 - 99 seconds

● Non volatile memory

● Quick arm facility

● Code arm facility selectable ON/OFF

● Individual Zone alarm activation LEDs

● Back-up Battery facilities

● Hard wired siren facility

● 4-Digit User Access Code

● 4-Digit Installer Access Code

● Plug in Mains Adaptor

External Siren

● Case material white plastic

● Piezo sounder

● Blue Lens

Magnetic ContactDetectors

● Magnetic Reed Switch operation

● Operating gap up to 9mm

● Door or window mounted

● Surface mounting, white plastic finish

PIR MovementDetectors

● Detection range up to 12 metres at 90°

● Integral Detection LED

● 1, 2, 3 ‘Pulse Count’ facility

● Anti-Tamper

● Corner or surface mount, with tilt facility

● 12 Volt dc operated, powered from the

Control Panel.

260 mm

50 mm

150 mm

MAINS CLEAR 24Hr

Zone 1 Zone 2 Zone 3 Zone 4

1 2 3

0

4 5 6

7 8 9

ARM

OMIT

RESET

HOMEERAWAY

EXIT1. Check all windows and doors are closed.2. a) Fullguard - Press 'Away' then 'Arm'.or b) Partguard - Press 'Home' then 'Arm'.3. Leave premises by entry/exit route.ENTRY1. Enter premises by entry/exit route.2. Enter your 4 digit password. If a mistake is made re-enter the correct passcode.

200 mm

75 mm

350 mm

68 mm

44 mm

58 mm

14 mm

12 mm

67 mm

45165PL Ed.3© Novar ED&S, 2004

Friedland, Novar Electrical Devices and Systems. The Arnold Centre, Paycocke Road, Basildon, Essex SS14 3EA. UK.

Novar Electrical Devices and Systems are

Quality Assurance Registered to BS EN ISO9001:2000,

by Asta

01268 563273(Lines open 9.00am to 5.00pm,

Monday to Friday).

If you have aproblem with yourAlarm, please callthe Helpline on:

RESEARCH &DEVELOPMENT

Our R & D Department is constantly

developing new products.

We practice a policy of continued

improvement and reserve the right

to change specifications without

prior notice.

COMPONENT SPECIFICATION