4) SiNext 3TR Technical Datasheet
-
Upload
deepak2628 -
Category
Documents
-
view
107 -
download
1
description
Transcript of 4) SiNext 3TR Technical Datasheet
-
ssinextD
atas
hee
t
Switch on your future...now!Switch on your future...now!
-
2Size S0 S1 S2Type Number 3TR30 3TR31 3TR32 3TR33 3TR34 3TR35
Conformance to standard IEC 60947-4-1, IS13947-4-1
Approvals UL, CSA, CE
Rated Insulation Voltage V 690
Rated Operational Voltage V 690
Rated impulse withstand Voltage kV 8
Permissible Ambient Temperature Storage C -55 to +80Service C -25 to +60
Mechanical Life in millions of operations AC Operation Cycles 15
Electrical Life in millions of operations at 415V, 50Hz, AC3 duty Cycles 24 2 2 2 2 2
Rated Operational Current Ie AC1 at 60C, up to 690V A 20 30 55
Rated Operational Current Ie AC2/\AC3 at 415V A 9 12 18 25 32 40 500V A 9 12 18 18 32 38690V A 6.6 8.8 12.2 12.2 27 27
Max rating of squirrel cage motors kW 4 5.5 9 12.5 17 21at 50/60Hz kW 5.5 7.5 11 12.5 21 25
kW 5.5 7.5 11 12.5 23 23
Rated Operational Current Ie AC4 up to 690V A 3.3 4.3 7.7 8.5 15.6 18.5for electrical life of 200,000 operations
Rating of squirrel cage motor at 50/60Hz at 415V kW 1.54 2.1 3.5 4 8.2 9.8(Max permitted rated operational current AC4=AC3 500V kW 1.7 2.5 4.6 5.2 9.8 11.8with reduced electrical life) 690V kW 2.54 3.45 6 6.6 13 15.5
Max Frequency of operation No load Cycle/Hr 10,000 10,000 5,000 5,000 5,000 5,000AC1 Cycle/Hr 2,000 2,000 1,500 1,500 1,200 1,200AC2 Cycle/Hr 1,000 1,000 750 750 750 600AC3 Cycle/Hr 1,000 1,000 750 750 750 600AC4 Cycle/Hr 250 250 250 250 250 200
Thermal Loading 10 sec current A 90 96 144 200 400 400
Coil Rating at 1.0 x Us Closing VA 68 101AC Operation 50 Hz closed VA 10 12.1
Type Number 3UR 5000 3UR 5200 3UR 5500
Suitable for mounting 3TR 30/31 3TR 32/33 3TR 34/35
Ambient Temperature Compensation C -25 to + 60
Trip Class 10A
Rated Insulation Voltage V 690
Rated Impulse withstand Voltage kV 6
Auxiliary Contacts 1NO+1NC
Technical Data
-
3S3 S4 S6 S8 S10 S123TR46 3TR47 3TR48 3TR49 3TR50 3TR51 3TR52 3TR53 3TR54 3TR55 3TR56 3TR57
IEC 60947-4-1, IS13947-4-1 IEC 60947-4-1, IS13947-4-1
UL, CSA, CE UL, CSA, CE
1000 1000
1000 1000
8 8
-55 to +80 -55 to +80-25 to +60 -25 to +60
10 10
2 16 16 16 16 14 14 12 14 14 14 1
80 90 100 100 160 160 210 220 300 300 400 550
45 65 75 85 110 140 170 205 250 300 400 47545 65 75 85 110 140 170 205 250 300 400 47545 65 75 75 110 140 170 170 250 250 400 400
24.6 35 42 49 63.3 78 98 120 147 174 236 27330 42.7 50.7 59 76.3 98 118 145 178 210 284 32940 59 70 70 105 105 163 163 245 245 392 392
24 28 34 45 54 68 75 96 110 125 150 150
13.1 15.3 18.6 23 29.5 38 42 54 63 72 88 8815.8 18.4 22.4 27 35.5 46 50 65 76 86 107 10721.8 25.4 30.9 38 49 63 69 90 105 119 147 147
5,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000 3,000 3,000 3,000 3,0001,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000600 400 400 350 400 300 300 250 300 250 200 170
1,200 1,000 1,000 850 1,000 750 700 500 700 500 500 420400 300 300 300 300 200 200 130 200 130 150 150
360 500 800 800 880 1140 1360 1640 2500 2500 3400 4200
183 330 550 910 1430 245017 32 39 58 84 115
3UR 5800 3UR 5830 3UR 6230 3UR 6830
3TR 46 to 49 3TR 50 Independent Mounting
-25 to + 60 -25 to + 60
10A 10A
1000 1000
8 8
1NO+1NC 1NO+1NC
-
4SiNext 3TR Power Contactors
ContactorRated current (A) With AC Coil With DC Coil
SizeIe AC3 at 415V, Auxiliary Type Auxiliary Type
50 Hz, 3 ph Contacts (Pls fill in coil voltage code) Contacts (Pls fill in coil voltage code)
91NO$ 3TR30 10-0A..0-0AA7 1NO$ 3TR30 10-0B..0-0AA7
01NC$ 3TR30 01-0A..0-0AA7 1NC$ 3TR30 01-0B..0-0AA7
121NO$ 3TR31 10-0A..0-0AA7 1NO$ 3TR31 10-0B..0-0AA71NC$ 3TR31 01-0A..0-0AA7 1NC$ 3TR31 01-0B..0-0AA7
118 -$ 3TR32 00-0A..0-0AA7 -$ 3TR32 00-0B..0-0AA7
25 -$ 3TR33 00-0A..0-0AA7 -$ 3TR33 00-0B..0-0AA7
232 -$ 3TR34 00-0A..0-0AA7 -$ 3TR34 00-0B..0-0AA7
40 -$ 3TR35 00-0A..0-0AA7 -$ 3TR35 00-0B..0-0AA7
345 2NO+2NC$ 3TR46 22-0A..0-0AA7@ 2NO+2NC 3TR46 22-0D..0-0AA7@
65 2NO+2NC$ 3TR47 22-0A..0-0AA7@ 2NO+2NC 3TR47 22-0D..0-0AA7@
475 2NO+2NC$ 3TR48 22-0A..0-0AA7@ 2NO+2NC 3TR48 22-0D..0-0AA7@
85 2NO+2NC$ 3TR49 22-0A..0-0AA7@ 2NO+2NC 3TR49 22-0D..0-0AA7@
6110 2NO+2NC$ 3TR50 22-0A..0-0AA7 2NO+2NC 3TR50 22-0D..0-0AA7
140 2NO+2NC$ 3TR51 22-0A..0-0AA7 2NO+2NC 3TR51 22-0D..0-0AA7
8170 2NO+2NC$ 3TR52 22-0A..0-0AA7 2NO+2NC 3TR52 22-0D..0-0AA7
205 2NO+2NC$ 3TR53 22-0A..0-0AA7 2NO+2NC 3TR53 22-0D..0-0AA7
10250 2NO+2NC$ 3TR54 22-0A..0-0AA7 2NO+2NC 3TR54 22-0D..0-0AA71)
300 2NO+2NC$ 3TR55 22-0A..0-0AA7 2NO+2NC 3TR55 22-0D..0-0AA71)
12400 2NO+2NC$ 3TR56 22-0A..0-0AA7 2NO+2NC 3TR56 22-0D..0-0AA71)
475 2NO+2NC$ 3TR57 22-0C..0-0AA7 2NO+2NC 3TR57 22-0D..0-0AA71)
Auxiliary contact block
ForDescription Type
Contactor
1NO 3TX4 010-2A
3TR30 to 351NC 3TX4 001-2A
1NO (Extd) 3TX4 010-4A
1NC (Extd) 3TX4 001-4A
First 1NO+1NC left 3TY7561-1AA00
3TR46 to 57First 1NO+1NC right 3TY7561-1BA00
Second 1NO+1NC left 3TY7561-1KA00
Second 1NO+1NC right 3TY7561-1LA00
Accessories for SiNext Power ContactorsInterlocking kit for two similar 3TR Contactors(inclusive of base plate and interlocking mechanism)
For Contactor TypeAC3 Rating Type
9/12/18/25/32/40A 3TR30 to 35 3TX4 091-1A#
45/65A 3TR46/47 3TX7 466-1YA0
75/85A 3TR48/49 3TX7 486-1YA0
110/140A 3TR50/51 3TX7 506-1YA0
170/205A 3TR52/53 3TX7 526-1YA0
250/300A 3TR54/55 3TX7 546-1YA0
400A 3TR56 3TX7 566-1YA0# W/o base plate (not required)
Spare Main Contacts, Coils and Arc Chambers of 3TR Power Contactorsavailable upon enquiry
1) Please connect DC coil circuit as recommended.@ For box type (SIGUT) terminals, order 2 nos 3TX7 460-OE.$ For more aux. contacts, pl. see table below.
Surge suppressor (Varistor) for 3TR30 to 35Coil Voltage
TypeAC DC
24 - 48 V 24 - 70 V 3TX7 402-3GY1
48 - 127V 70 - 150V 3TX7 402-3HY1
127 - 240V 150 - 250V 3TX7 402-3JY1
240 - 400V 3TX7 402-3KY1
400 - 600V 3TX7 402-3LY1
Surge suppressor (Varistor) for 3TR46-56Less than 48V 24 - 70V 3TX7 462-3GY1
48 - 127V 70 - 150V 3TX7 462-3HY1
127 - 240V 150 - 250V 3TX7 462-3JY1
240 - 400V 3TX7 462-3KY1
400 - 600V 3TX7 462-3LY1
Surge suppressor (RC Unit) for 3TR30 to 3524 - 48 V 24 - 70 V 3TX7 402-3RY2
48 - 127V 70 - 150V 3TX7 402-3SY2
127 - 240V 150 - 250V 3TX7 402-3TY2
240 - 400V 3TX7 402-3UY2
400 - 600V 3TX7 402-3VY2
AC coil codes : 3TR30 to 35
Coil Voltage24V 110V 220V 230V 415V
50Hz 50/60Hz 50Hz 50/60Hz 50Hz
Code B0 G2 M0 L2 R0
AC coil codes : 3TR46 to 56
Coil Voltage24V 110V 220V 240V 415V
50Hz 50Hz 50Hz 50Hz 50Hz
Code B0 F0 M0 U0 R0
Coils suitable for 50/60 Hz upon enquiry
AC coil codes : 3TR57
Coil Voltage110-132 220-240V 380-460V50/60Hz 50/60Hz 50/60Hz
Code F7 M7 Q7
DC coil codes : 3TR30 to 57
Coil Voltage (V) 24 42 48 110 220
Code B4 D4 W4 F4 M4
Add-on pneumatic timers for 3TR3 available upon request
-
5SiNext 3UR Bimetal RelaysCurrent
Setting Range Type Reference(A)
3UR 5000For direct mounting on contactor 3TR30/31 or individual mountingwith 3UX1418
0.1 - 0.16 3UR50 00-0A A00-0AA7
0.16 - 0.25 3UR50 00-0C A00-0AA7
0.25 - 0.4 3UR50 00-0E A00-0AA7
0.4 - 0.63 3UR50 00-0G A00-0AA7
0.63 - 1 3UR50 00-0J A00-0AA7
0.8 - 1.25 3UR50 00-0K A00-0AA7
1 - 1.6 3UR50 00-1A A00-0AA7
1.25 - 2 3UR50 00-1B A00-0AA7
1.6 - 2.5 3UR50 00-1C A00-0AA7
2 - 3.2 3UR50 00-1D A00-0AA7
2.5 - 4 3UR50 00-1E A00-0AA7
3.2 - 5 3UR50 00-1F A00-0AA7
4 - 6.3 3UR50 00-1G A00-0AA7
5 - 8 3UR50 00-1H A00-0AA7
6.3 - 10 3UR50 00-1J A00-0AA7
8 - 12.5 3UR50 00-1K A00-0AA7
10 - 14.5 3UR50 00-2S A00-0AA7
3UR 5200For direct mounting on contactor 3TR32/33 or individual mountingwith 3UX1420
1 - 1.6 3UR52 00-1A A00-0AA7
1.25 - 2 3UR52 00-1B A00-0AA7
1.6 - 2.5 3UR52 00-1C A00-0AA7
2 - 3.2 3UR52 00-1D A00-0AA7
2.5 - 4 3UR52 00-1E A00-0AA7
3.2 - 5 3UR52 00-1F A00-0AA7
4 - 6.3 3UR52 00-1G A00-0AA7
5 - 8 3UR52 00-1H A00-0AA7
6.3 - 10 3UR52 00-1J A00-0AA7
8 - 12.5 3UR52 00-1K A00-0AA7
10 - 16 3UR52 00-2A A00-0AA7
12.5 - 20 3UR52 00-2B A00-0AA7
16 - 25 3UR52 00-2C A00-0AA7
3UR55 00For direct mounting on contactor 3TR34/35 or individual mountingwith 3UX1425
10 - 16 3UR55 00-2A A00-0AA7
12.5 - 20 3UR55 00-2B A00-0AA7
16 - 25 3UR55 00-2C A00-0AA7
20 - 32 3UR55 00-2D A00-0AA7
25 - 36 3UR55 00-2Q A00-0AA7
32 - 40 3UR55 00-2R A00-0AA7
36 - 45 3UR55 00-8M A00-0AA7
CurrentSetting Range Type Reference
(A)
3UR58 00For direct mounting on contactor 3TR46 to 49 or individual mountingwith 3UX1421
16 - 25 3UR58 00-2C A00-0AA7
20 - 32 3UR58 00-2D A00-0AA7
25 - 40 3UR58 00-2E A00-0AA7
32 - 50 3UR58 00-2F A00-0AA7
40 - 57 3UR58 00-2T A00-0AA7
50 - 63 3UR58 00-2P A00-0AA7
57 - 70 3UR58 00-2V A00-0AA7
63 - 80 3UR58 00-2U A00-0AA7
70 - 95 3UR58 00-8Y A00-0AA7
3UR58 30For direct mounting on contactor 3TR50 or individual mounting with3UX1421 0XA
70 - 95 3UR58 30-5B A00-0AA7
85 - 105 3UR58 30-5C A00-0AA7
95 - 120 3UR58 30-5D A00-0AA7
3UR62 30Individual mounting
85 - 135 3UR62 30-5A A00-0AA7
115 - 180 3UR62 30-5B A00-0AA7
160 - 250 3UR62 30-5C A00-0AA7
200 - 320 3UR62 30-5D A00-0AA7
250 - 400 3UR62 30-5E A00-0AA7
3UR68 30Individual mounting
320 - 500 3UR68 30-5F A00-0AA7
400 - 630 3UR68 30-5G A00-0AA7
Accessories for SiNext BirelaysDescription For Relay type Type
3UR50 3UX14 18Accessory for 3UR52 3UX14 20independent 3UR55 3UX14 25mounting 3UR58 3UX14 21
3UR58 30 3UX14 21-0XA
Resetting Plunger 3UR 3UX10 11Funnel 3UX10 13
Reset cord + holder:400 mm length 3UR 3UX10 15600 mm length 3UX10 16
-
6Dimension Drawings
3TR30/31 with AC coil + 3UR50
* With Aux. Contact block type 3TX4...** With Relay type 3UR50...
3TR30/31 with DC coil
* With Aux. Contact block type 3TX4...
3TR32/33 with AC coil + 3UR52
* With Aux. Contact block type 3TX4...** With Relay type 3UR52...
* With Aux. Contact block type 3TX4...
3TR32/33 with DC coil
3TR34/35 with AC coil + 3UR55 3TR34/35 with DC coil
* With Aux. Contact block type 3TX4...** With Relay type 3UR55...
* With Aux. Contact block type 3TX4...
-
7Dimension Drawings
3TR46 and 47 3TR52 and 53
3TR48 and 49 3TR54 and 55
3TR50 and 51 3TR56 and 57
a1 a2 b c
3TR52 20 42 174 154
3TR53 25 48 184 159
a1 a2 b c
3TR48 10,5 26,5 127 116
3TR49 10,5 26,5 127 116
a1 a2 b1 b2 b3 b4 c
3TR56 25 48 203 200 178
3TR57 30 52 215 110,5 100 182
a1 a2 b c
3TR50 15 37 149 134
3TR51 20 42 159 139
-
Siemens Ltd.Automation and Drives DivisionLV Control & Distribution ProductsThane Belapur RoadThane 400601Fax : +91 22 27623729e-mail : A&[email protected]
Siemens Ltd.SGR-01-101-084
Product development is a continuous process. Consequently,the data indicated in this datasheet is subject to change withoutprior notice. For latest issue contact our Sales Offices.
3TR46-49 + 3UR5800
Dimension Drawings
3TR50 + 3UR5830
3UR6230 and 3UR6830CT operated relay
3UR5800 a1 a2 a3 b1 b2 b3 c1 d1 d2 d3 e e1 f1 f2 f3 g g1 g2
3TR46, 3TR47 90 113 70 117 175 100 126 10.5 26.5 25 102 31.5 80 63 122 28 4.8 6.1
3TR48, 3TR49 100 123 80 127 194 110 143 10.5 26.5 25 116 31.5 89 71 132 39 5.5 6.1
** Dimension for square OFF-button (Stroke 3mm)Dimension for round RESET-button (Stroke 2.5mm) less 2.5
Relay Type Range A B C
85 135 A 20 4 134.5115 180 A
3UR62 160 250 A200 320 A 25 4 134.5250 400 A
3UR68 320 600 A 30 5 137.5400 630 A