68 MX-F Series TEMPERATURE CONTROLLER TEMPERATURE CONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class 250ms RAMP function PID Auto-tuning Universal input ℃/℉, Reverse/Direct action selectable Remote/Local input selectable Model and suffix code (MX-F Series) MODEL MX һ CONTROL OUTPUT SUFFIX CODE DESCRIPTION F M C S V N Ӑ N P MX2/3/4/7/9 Normal PID Auto-tuning Relay contact Current(4~20㎃ DC) SSR drive pulse voltage(0/12V DC) Voltage(1~5V DC) None Refer to CODE None HBA function(CT separately) None Refer to CODE ҭOption is not valid in MX4-F. ҭIn current output(C), lamp signal of“OUT”does not flash. ① Retransmission output ② Heater Break Alarm(HBA) ③ Remote input Ҟ O P T I O N CODE ① DC 0~10㎷ ② DC 0~100㎷ ③ DC 0~1V ④ DC 0~5V ⑤ DC 0~10V ⑥ DC 1~5V ⑦ DC 0~20㎃ ⑧ DC 4~20㎃ N Ӑ

Transcript of 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4...

Page 1: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

68

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

Universal Input•Output and High Accuracy 0.5 class 250ms

RAMP function

PID Auto-tuning

Universal input

/, Reverse/Direct action selectable

Remote/Local input selectable

Model and suffix code (MX-F Series)

MODEL

MX

CONTROL

OUTPUT

SUFFIX CODE DESCRIPTION

F

M

C

S

V

N

N

P

MX2/3/4/7/9

Normal PID Auto-tuning

Relay contact

Current(4~20 DC)

SSR drive pulse voltage(0/12V DC)

Voltage(1~5V DC)

None

Refer to CODE

None

HBA function(CT separately)

None

Refer to CODE

Option is not valid in MX4-F.In current output(C), lamp signal of“OUT”does not flash.

① Retransmission output

② Heater Break Alarm(HBA)

③ Remote input

OPTION

CODE① DC 0~10 ② DC 0~100 ③ DC 0~1V ④ DC 0~5V

⑤ DC 0~10V ⑥ DC 1~5V ⑦ DC 0~20 ⑧ DC 4~20

N

Page 2: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

69

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

Functional Description

Input and Range

MX9-F

Auto tuning(AT)

Remote input(REM)

Control output(OUT)

Alarm1(AL-1)Mode(SET) key

Setting digit shift key

Process-value(PV)

Set-Value(SV)

Control loop break alarm(LBA)/Heater break alarm(HBA)

Alarm2(AL-2)

Set-Value increment keySet-Value decrement key

MODE

MX9

AT

PVC

REM

OUT AL-1 AL-2 H-LBA MAN

PV

SV

R

-50~1372(-50.0~999.9)

-50~1100(-50.0~999.9)

-199~750(-199.9~750.0)

-199~400(-199.9~400.0)

-199~649(-199.9~649.0)

-199~649(-199.9~649.0)

Signal Input Temperature range

K

J

E

T

Pt 100Ω

(DIN)

Pt 100Ω

(JIS)

-199~3200 (1 Mode)

-1999~9999 (0.1 Mode)

-199~3200 (1 Mode)

-1999~9999 (0.1 Mode)

1~5V

4~20mA

0~5V

0~20mA

0~1760

0~1760

0~1760

Signal Input Temperature range

PR(R)

PR(B)

PR(S)

-50~2500(-50.0~999.9)

-50~2000(-50.0~999.9)

-199~1400(-199.9~999.9)

-199.9~750(-199.9~750.0)

-199~1200(-199.9~999.9)

-199~1200(-199.9~999.9)

** Cautions for input selection

1) When you select input mode, you must shift jump switch inside of PCB to CORRECT position first.

2) Afterwards select each input mode by key operation.

Input T.C./Voltage RTD Current

Switch position

TC RPT

32~3200

32~3200

32~3200

Page 3: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

70

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

MODEL

Appearance

Externaldimension

Input

Accuracy

Power supply

Control action

Control output

Alarm output

Ambient

temperature

Net weight

Connection

MX9-F MX7-F

10

9

8

7

20

19

18

17

16

15

14

13

6

5

4

3

2

1

12

11

AL-2

100- 240VAC50/60Hz

12VA

B

B

A

LBA/HBA

COM

TRANSMIT4 - 20mADC

RT

D

4 - 20mA DC 12VDC

C.T

REM+

-

+

-

T.C

+

-

HC

L

++

19

18

17

16

15

14

13

5

4

3

6

100 240VAC50/60Hz12VA

AL 1

MA

IN

H

L

C

LBA/

COM

A

B

B

T.C

RT

D

2

1 12VDC

4 20mADC

7

12

11

10

9

8

C.T

4 20mADCTRANSMIT

VOLTAGECURRENT

+

HBA+

REM

AL 2

96X96mm(1/4 DIN), mounting depth:100mm 72X72mm, mounting depth:100mm

11 Kinds of input (See input range)

[Setting accuracy] T/C: Within±(0.3% of SV + 1 digit) or ±2(Whichever is larger)R.S: ±4 + 1 digitR.T.D: Within±(0.3% of SV + 1 digit) or ± 0.8(Whichever is larger)

[Display accuracy] Same as setting accuracy.

100 to 240V AC (Common to 50/60Hz) (Excluding power supply voltage variation)

PID (Auto-tuning function), ON/OFF, P.PI.PD

Relay contact: AC 250V 3A (Resistive load) 1C(NO/NC) contactSSR driving:12V DC (Constant voltage pulse) [load resistance more than 800Ω]Current: 4-20mA DC [load resistance less than 600Ω]Voltage: 0-10V DC [load resistance less than 1]

Deviation or process settingRelay contact output: AC 250V 0.5A (AL-2), 3A (AL-1)

0 ~ 50(32 ~ 122) ※Ambient humidity:35 ~ 85% RH

Approx 375g Approx 300g

Page 4: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

71

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

Relay contact:AC 250V 3A(Resistive load) 1C(NO/NC) contactSSR driving :12V DC(Constant voltage pulse)〔load resistance more than 800Ω〕Current :4-20mA DC〔load resistance less than 600Ω〕Voltage :0-10V DC〔load resistance less than 1 KΩ〕

〔Setting accuracy〕T/C :Within±(0.3% of SV+1 digit) or±2(Whichever is larger)R.S :±4 + 1 digitR.T.D :Within±(0.3% of SV+1 digit) or±0.8(Whichever is larger)

〔Display accuracy〕 Same as setting accuracy

100 to 240V AC(Common to 50/60Hz)(Excluding power supply voltage variation)

PID (Auto-tuning function), ON/OFF, P.PI.PD

11 Kinds of input (See input range)

Deviation or process settingRelay contact output:AC 250 0.5A (AL-2), 3A (AL-1)

Deviation or process settingRelay contact output:AC 250V 3A (Resistive load)

A

AL-1H

CL

+

AL-

2

LBA

/HB

A

C.T

B B T.C

RTD

+

+

CURRENTSOLIDSTATE

10 9 8 7

20 18 17 16 15

6 5

19 14 13

4 3 2 1

12 11

TRANSMIT4-20mA/DC

REM

100-240VAC50/60Hz12VA

+

+

MAIN

CO

M CURRENT VOLTATE

HC

L

10

9

8

7

20

19

18

17

16

15

14

13

6

5

4

3

2

1

12

11

+

LBA/HBA

MAIN

AL 2

AL 1

TRANSMIT4 20mA DC

COM

+

C.T

REM

RT

D

B

B

A

+

T.CCURRENT

SOLIDSTATE

+

100 240VAC50/60Hz12VA

CURRENTVOLTAGE

MX4-F

1

2

6

7

3 8

4 9

5 10

ALM

MAIN T.C

+

100 240 VAC50/60Hz 12VA

3A250VAC

3A250VAC

T.C

+

7

9

10RTD

B

B

A

8

4

5

CURRENTSOLIDSTATE

+

MX2-F MX3-F

Approx 310g

0~50(32~122) ※Ambient humidity : 35~85% RH

Approx 310g Approx 235g

48×96mm(1/8 DIN), mounting depth : 100mm 96×48mm(Horizontal), mounting depth : 100mm 48×48mm(1/16 DIN)

Page 5: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

72

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

Setting of constants in display

Alarm mode

Signal on PV display Name Description Setting range Initial set

Temp. range

Ramp

Proportional band

Anti-reset windup

Integral time

Derivative time

Hysteresis(in ON/OFF action)

Proportioning cycle

Temperature range in ramp

Ramp(Rate) time setting

Set when proportional controlis performed.

Prevents overshoot and/orundershoot caused by integralaction effect.

Eliminates offset occurring inproportional control. Integralaction turns OFF with thisaction set to“O”.

Prevents ripples by predictingoutput change therebyimproving control stability.Derivative action turns OFFwith this action set to“O”.

Displays hysteresis Set-Valuefor main output.

Displays manipulated outputcycle(sec.).

-199~3200(-199.9~999.9)

0~540 minutes

1 to span ()0.1~999.9 ()

0~100()

0 to 3600 sec.

0 to 3600 sec.

0.1~100.0

1 to 100 sec.

(0.1 to 100.0 sec.)

-

-

20 ()

100()

240 sec.

60 sec.

1()

Relay contactoutput : 20 sec.Voltage pulseoutput : 2sec.

*Automatically set by Auto-tuning

None

Deviation high alarm

Deviation low alarm

Hold function of high alarm

Hold function of low alarm

Band alarm

High and low alarm

Low alarm hold function of high/lowalarm

High alarm hold function of high/lowalarm

Hold function of high/low alarm

Process high alarm

Hold function of process high alarm

Process low alarm

Hold function of process low alarm

*

*

*

Page 6: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

73

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

Operation Manual

MODE

MODE

(Power ON)

Display in Ramp function

Display in HBAfunction only

P,A,I,D,C: No display in ON/OFF mode

Temp. high limit

Temp. low limit

Output limit range:0~100%

Manual output set (Select in SL-3 mode to display this mode)range:0~100%

Remote function mode(Select inSL-3 mode to display this mode)Set 1 for operation

3sec. 3sec.

3sec.

3sec.

(PV)

(SV)

(Input type) (Temp. range)

Power supply

MODE

MODE

MODE MODEMODE

MODEMODE

MODE

Operates only in :1000 position.When flickers, Press to stop.Press and key simultaneously for3 sec. to enter

SYSTEM SET MODE

Display inON/OFF mode

NoteIn case of Current and Voltageoutput, PID Auto-tuning does notoperate by Auto-tuning key. Initial values of P.I and Dare Programmed and you may usethe unit in ordinary applications. Ifyou are not satisfied with givenvalues, you can change values of Iand D slightly in normal mode bymanual adjustment.

Normal mode

Page 7: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

74

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

(System mode) (HBA mode)(Alarm mode)(Retransmission output mode)

MODE 3sec. MODE 3sec. MODE 3sec.

MODEMODEMODE

MODE

MODE

Note : Press and key simultaneously for 3 sec.

and return to initial PV/SV mode in every step.

※ Press key for 3 sec. in and return

to .

MODE

MODE MODE

3sec.

MODE

MODE

3sec. 3sec.

Function set mode

Page 8: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

75

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

: Input mode

: Input shift valuerange: within free scale range

: Decimal point selectionrange : 0 ~ 3(0001 → 000.0 in PV mode)

0: Indicator1: Controller0: ON/OFF1: PID0: Direct control action for cooling1: Reverse control action for heatingMX -F Normal type

0: 1: 0: 0.1 resolution1: 1 resolutionNo function key (Do not modify)0: Current output1: Relay or Voltage, Pulse

0: None1: AL-1 output → AL-1 terminal(Initial value)2: AL-1 output → AL-2 terminal3: AL-1 output → LBA/HBA terminal

: Span of free scalerange: -199~3200 -1/1 MODE

(-1999~9999) -1/10 MODE

: Zero of free scalerange: -199~3200 -1/1 MODE

(-1999~9999) -1/10 MODE

: Alarm-1 (Refer to alarm mode)initial value : Deviation high alarm

: Dead band of AL-1initial value : 1

: Alarm-2 (Refer to alarm mode)initial value: Hold function of low alarm

: Dead band of AL-2initial value : 1.0

: Output terminal of AL-2

: LBA/HBA function

: Dead band of HBA(A)

: Output terminal of LBA/HBA

: Retransmission display

: Span of retransmission outputrange : 0~4095 initial value :3500(Do not modify)

: Zero of retransmission outputrange : 0~4095 initial value :500(Do not modify)

: Remote input calibration(Do not modify)

(None) (PV) (SV)

(None) (LBA) (25A HBA)(50A HBA)

: Output terminal of AL-1

0: Remote input function1: No remote input function0: Manual output function1: No manual output functionNo function key (Do not modify)0: Ramp function1: No ramp function

0: None1: AL-2 output → AL-1 terminal(Initial value)2: AL-2 output → AL-2 terminal3: AL-2 output → LBA/HBA terminal

0: None1: LBA/HBA output → AL-1 terminal2: LBA/HBA output → AL-2 terminal3: LBA/HBA output → LBA/HBA terminal

Page 9: 4. MX Series-67~84¿µ - Electrocontrol MX-F Series TEMPERATURE CONTROLLER TEMPERATURECONTROLLER 4 Universal Input•Output and High Accuracy 0.5 class …

76

MX-F Series

TEMPERATURE CONTROLLER

TEMPERATURE

CONTROLLER

4

Ramp rate can be adjusted.

(0~540 minutes)

Model CT-25 Model CT-50

Time

Set

MODE

MODE

MODE

RAMP RATE

252299

13 31

34.5

16

Ramp function

CT(Current Transformer)

PID Auto-Tuning (Valid in Relay and SSR output only)

• Press the key and key at the same time. Then,

AT indication lamp flashes to start the Auto-tuning

function.

• If Auto-tuning function ends, the AT indication lamp

stops flashing automatically.

When checking the auto-tuned value, press the key

and conform in turn.

• When you want Auto-tuning function to be suspended,

press the key and key simultaneously, then the

AT indication lamp stops flashing to release Auto-tuning

function. In this case P.I.D and ARW values are not

changed (Maintain the value before the Auto-tuning

starts).

• When you want to change the SV(set-value) during Auto-

tuning, suspend it and perform PID control using the

values before Auto-tuning starts.

Control loop break alarm(LBA)

LBA function starts to measure time from the moment

that the PID Computed Value (Output ON time/cycle)

become 0% or 100%, and detects the amount of Process

Value change at each LBA setting time, and determines by

the amount of change whether LBA is to be ON or OFF.

• When the status at a 100% PID computed value

continues beyond the LBA setting time, the LBA turns

ON if the measured-value(PV) does not rise by 2()

or more.

(In direct action, the above alarm turns ON if the

measured-value does not fall by 2() or more.

• When the status at 0% PID computed value continues

beyond the LBA setting time, the LBA turns ON if the

measured-value(PV) does not fall by 2() or more.

Remote input

Set-value of controller can be set or changed from outside

of the controller by direct voltage/current signal.

But the external signal should be input continuously.

(Auto-tuning function is not operated while the external

signal is set)

Heater break alarm(HBA)

Set-value of HBA to be set about 85% to input of CT but

the set-value should be less in case that the ratio of

voltage variation is high.

If several heaters are connected in parallel, the alarm may

be turned ON even though one circuit is broken.

In such a case, set the value of HBA to be slightly high.

No HBA operates at “O” setting, but HBA operates at

“25.0”or“50.0”setting.