3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker...

42
Answers for infrastructure and cities. 3AH47 Vacuum Circuit-Breakers for Traction Applications Medium-Voltage Equipment · Catalog HG 11.52 · 2012 www.siemens.com/medium-voltage-switchgear

Transcript of 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker...

Page 1: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Answers for infrastructure and cities.

3AH47 Vacuum Circuit-Breakersfor Traction ApplicationsMedium-Voltage Equipment · Catalog HG 11.52 · 2012

www.siemens.com/medium-voltage-switchgear

Page 2: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 20122

3AH47 Vacuum Circuit-Breakers

R-HG

11-1

72.ti

f

Page 3: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 3

3AH47 Vacuum Circuit-Breakers

1

2

3

4

Description 5General 6

Construction and mode of operation, standards 7

Ambient conditions, current carrying capacityand dielectric strength 9

Product range overview and basic equipment 10

Equipment Selection 11Ordering data and confi guration example 12

Selection of basic types, circuit-breakers 13

Selection of secondary equipment 14

Selection of additional equipment 22

Accessories and spare parts 23

Technical Data 27Electrical data, dimensions and weights 28

Circuit diagrams 33

Operating times, short-circuit protection ofmotors, consumption data of releases 35

Annex 37Inquiry form 38

Confi guration instructions 39

Confi guration aid Foldout page

Contents Page

3AH47 Vacuum Circuit-Breakers

Medium-Voltage EquipmentCatalog HG 11.52 · 2012

Invalid: Catalog HG 11.52 · 2010

Contents

The products and systems described in this catalogare manufactured and sold according to a certifi edmanagement system (acc. to ISO 9001, ISO 14001and BS OHSAS 18001).

Page 4: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 20124

3AH47 Vacuum Circuit-Breakers

R-HG

11-2

14.ti

f

Page 5: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 5

3AH47 Vacuum Circuit-Breakers

1

DescriptionContents

Description 5

General 6

Construction and mode of operation, standards:

Switching medium 7

Pole assembly 7

Operating mechanism box 7

Operating mechanism 7

Trip-free mechanism 7

Releases 8

Closing 8

Circuit-breaker tripping signal 8

Interlocking 8

Standards 8

Ambient conditions 9

Current carrying capacity 9

Dielectric strength 9

Product range overview 10

Basic equipment 10

Contents Page

R-HG

11-2

15.ti

f

Railway control center

Page 6: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 20126

3AH47 Vacuum Circuit-Breakers

1

3AH47 circuit-breaker – The Specialfor railway electrifi cation applications at 17.5 kV and 27.5 kV

The electrical power supply for railway systems requires circuit-breakers with special features. Not only are there single-pole circuit-breakers in normal operation, but also

R-HG

11-2

07.ti

f

R-HG

11-2

06.ti

f

DescriptionGeneral

3AH47 vacuum circuit-breakers control up to 60,000 operating cycles. Minimum maintenance work, such as greasing of operating mechanisms after 10,000 operating cycles and replacement of vacuum interrupters after 30,000 operating cycles, preserves the reliability of these circuit-breakers throughout their entire service life.

3AH47 – impressive with one or two poles

the high requirements regarding operational reliability and number of operating cycles reach far beyond the standards of other applications.

The vacuum circuit-breaker series 3AH47 offers – both for 16.7 Hz at a rated voltage of 17.5 kV, for 25 Hz at a rated voltage of 25 kV and for 50/60 Hz at a rated voltage of 27.5 kV – an impressive product range with rated normal currents up to 2500 A and rated short-circuit breaking currents from 25 kA to 31.5 kA, and even up to 50 kA at 17.5 kV.

Page 7: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 7

3AH47 Vacuum Circuit-Breakers

1

DescriptionConstruction and mode of operation

The 3AH47 vacuum circuit-breaker consists of the pole assembly (1) and the operating mechanism box (2). The pole assembly is fi xed to the operating mechanism box via post insulators (3). The switching movement is transferred by means of operating rods (4) and levers.

Switching medium

The vacuum switching technology, proven and fully developed for more than 30 years, serves as arc-quenching principle by using vacuum interrupters.

Pole assembly

A pole assembly consists of the vacuum interrupter (6) and the interrupter supports. The vacuum interrupter is air-insulated and freely accessible. This makes it possible to clean the insulating parts easily in adverse ambient condi-tions. The vacuum interrupter is mounted rigidly to the upper interrupter support (5). The lower part of the interrupter is guided in the lower interrupter support (7), allowing axial movement. The braces absorb the external forces resulting from switching operations and the contact pressure.

Operating mechanism box

The whole operating mechanism with releases, auxiliary switches, indicators and actuating devices is accommodated in the operating mechanism box. The extent of the second-ary equipment depends on the case of application and offers a multiple variety of options in order to meet almost every requirement.

Operating mechanism

3AH47 vacuum circuit-breakers have a spring drive operating mechanism. The closing spring is charged either electrically or manually. It latches tight at the end of the charging process and serves as an energy store. The force is transmitted from the operating mechanism to the pole assembly via operating rods.

To close the breaker, the closing spring can be unlatched either mechanically by means of the local “ON” pushbutton or electrically by remote control. The closing spring charges the opening or contact pressure springs as the breaker closes. The now discharged closing spring will be charged again automatically by the mechanism motor or manually.Then the operating sequence OPEN-CLOSE-OPEN is stored in the springs. The charging state of the closing spring can be checked electrically by means of a position switch.

Trip-free mechanism

3AH47 vacuum circuit-breakers have a trip-free mechanism according to IEC 62271-100. In the event of an opening c ommand being given after a closing operation has been i nitiated, the moving contacts return to the open position and remain there even if the closing command is sustained. This means that the contacts of the vacuum circuit-breakers are momentarily in the closed position, which is permissible according to IEC 62271-100.

����������

1 Pole assembly

2 Operatingmechanism box

3 Post insulator

4 Operating rod

����

����

���

5 Upper interrupter support

6 Vacuum interrupter

7 Lower interrupter support

Front view of the single-pole circuit-breaker

Open operating mechanism box of the two-pole circuit-breaker

Structure of the traction circuit-breaker

R-HG

11-1

37.e

ps

R-HG

11-2

08.ti

f

Page 8: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 20128

3AH47 Vacuum Circuit-Breakers

1

Description Construction and mode of operation, standards

Circuit-breaker tripping signal

The NO contact makes brief contact while the vacuum circuit-breaker is opening, and this is often used to operate a hazard-warning system which, however, is only allowed to respond to automatic tripping of the vacuum circuit-breaker. Therefore, the signal from the NO contact must be interrupted when the circuit-breaker is being opened intentionally. This is accomplished under local control with the cut-out switch that is connected in series with the NO contact.

Interlocking

Mechanical interlocking

The switch position of the circuit-breaker is checked from the switchgear side, and its closing is blocked if the associated disconnector is in faulty position. On the other hand, dis-connector operation is prevented while the circuit-breaker is closed. Accordingly, the mechanical interlocking can also be used to interlock against circuit-breaker trucks or with-drawable parts.

Electrical interlocking

The vacuum circuit-breakers can be integrated in electro-magnetic feeder or switchgear interlocks. In case of electrical interlocking, the disconnector or its operating mechanism is equipped with a magnetic lock-out mechanism. This mecha-nism is controlled by an auxiliary contact of the circuit- breaker, so that the disconnector can only be operated when the circuit-breaker is open. On the other hand, the circuit-breaker is also controlled by the disconnector or its operating mechanism, so that it can only be closed when the discon-nector is in an end position. For this purpose, manual electri-cal closing must be provided in the circuit-breaker operating mechanism (see “Closing”).

Standards

3AH47 vacuum circuit-breakers conform to the following standards:

• EN 50152-1• IEC 62271-100 (former IEC 60056)• IEC 62271-1 (former IEC 60694)• BS 5311• VDE 0671 (former VDE 0670)• IEEE C37.09

All 3AH47 vacuum circuit-breakers fulfi ll the endurance classes E2 and C2 according to IEC 62271-100, and surpass the endurance class M2 six times (60,000 operating cycles).

Releases

A release is a device which transfers electrical commands from an external source, such as a control room, to the l atching mechanism of the vacuum circuit-breaker so that it can be opened or closed. How many releases are used and how they are combined is defi ned when the secondary equipment is selected.

• The closing solenoid unlatches the charged closing spring of the vacuum circuit-breaker, closing it by electrical means.• Shunt releases are used for tripping the circuit-breakers via protection relay and for manual tripping via electrical opera-tion. For this purpose they are operated with an auxiliary voltage (AC or DC) supplied by the protection relay or the control room.• Instantaneous releases are used for switching duties with extremely short breaking times, especially for applications in 16.7 Hz systems, in order to keep the arcing time short. For operation of the instantaneous release, an additional capaci-tor tripping system is required.• Undervoltage releases comprise a stored-energy mechanism, an unlatching mechanism and an electromag-netic system, which is permanently connected to voltage while the vacuum circuit-breaker is closed.

If the voltage falls below a predetermined value, unlatching of the release is enabled and the circuit-breaker is opened via the stored-energy mechanism.

Closing

In the standard version, the 3AH47 vacuum circuit-breakers can be remote-closed electrically. They can also be closed locally by mechanical unlatching of the closing spring via pushbutton.

Instead of this “manual mechanical closing”, “manual electrical closing” is also available. In this version, the closing circuit of the circuit-breaker is controlled electrically by a pushbutton instead of the mechanical button. In this way, switchgear-related interlocks can also be considered for local operation in order to prevent involuntary closing.

If constant CLOSE and OPEN commands are present at the vacuum circuit-breaker at the same time, the vacuum circuit-breaker will return to the open position after closing.It remains in this position until a new CLOSE command is given. In this manner, continuous closing and opening (= “pumping”) is prevented.

Page 9: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 9

3AH47 Vacuum Circuit-Breakers

1

DescriptionAmbient conditions, current carrying capacity and dielectric strength

Ambient conditions

The vacuum circuit-breakers are designed for the normal operating conditions defi ned in IEC 62271-100.

Condensation can occasionally occur under the ambient conditions shown opposite. 3AH47 vacuum circuit- breakers are suitable for use in the following climatic classes according to IEC 60721, Part 3-3:

Climatic ambient conditions: Class 3K4 1)

Biological ambient conditions: Class 3B1Mechanical ambient conditions: Class 3M2Chemically-active substances: Class 3C2 2)

Chemically-active substances: Class 3S2 3)

1) Low temperature limit: – 5 °C2) Without icing and wind-driven precipitation3) Restriction: Clean insulation parts

Current carrying capacity

The rated normal currents specifi ed in the opposite diagram have been defi ned according to IEC 62271-100 for an ambient air temperature of + 40 °C and apply to open switch-gear. For enclosed switchgear the data of the switchgear manufacturer applies. At ambient air temperatures below + 40 °C, higher normal currents can be carried (see diagram):

Characteristics curve 1 = Rated normal current 1250 ACharacteristics curve 2 = Rated normal current 2000 ACharacteristics curve 3 = Rated normal current 2500 A

Dielectric strength

The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 62271-1, the values of the rated lightning impulse withstand voltage and the rated short-duration power-frequency withstand voltage specifi ed in the chapter “ Technical Data” apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram.

The characteristic shown applies to both rated withstand voltages.

To select the devices, the following applies:

U ≥ U0 x Ka

U Rated withstand voltage under reference atmosphereU0 Rated withstand voltage requested for the place of installationKa Altitude correction factor according to the opposite diagram

Example

For a requested rated lightning impulse withstand voltageof 75 kV at an altitude of 2500 m, an insulation level of 90 kV under reference atmosphere is required as a minimum:

90 kV ≥ 75 kV x 1.2

����

����

��� ������������ ������������

����

����

����

���

��

�������

����

��������

����

���

����

����

����

����

����

���� � ���

������������������

������

���!"������

�������� "��

���

����������������

�#��

�#��

�#��

�#��

�#������ ���� �����

�#��

$����!������

�!�����

�" ���

"�� �%�"� �

Page 10: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201210

3AH47 Vacuum Circuit-Breakers

1

DescriptionProduct range overview and basic equipment

Product range overview

Ratedvoltage

Rated frequency

Rated short-circuit breakingcurrent

Rated normal current (A)

1250 2000 2500

kV Hz kA Single-pole Two-pole Single-pole Two-pole Single-pole Two-pole

17.5 16.7 25

31.5

40

50

25 25 25 *

27.5 50/60 25

31.5

* Other rating / data on request

Basic equipment

Features Minimum equipment Alternative equipment Remarks

Operatingmechanism Electrical operatingmechanism

Manual operatingmechanism(hand crank included in the scope of supply)

Hand crankalso available as accessory

Closing Closing solenoid andmanual mechanical closing

Manual electrical closing –

1st release Shunt release None –

2nd release Without Shunt release,undervoltage release,instantaneous release

When an instantaneousrelease is used, a capacitortripping unit is required

3rd release Without Undervoltage release Cannot be combined withan instantaneous release

Varistor circuit Available None For limiting switching overvoltagesdue to inductive loads

Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC –

Plug connector 24-pole terminal strip 24-pole plug,64-pole plug

Anti-pumping Available None –

Circuit-breaker tripping signal

Available None –

Operations counter Available None –

Interlocking Without Mechanical interlocking –

Page 11: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 11

3AH47 Vacuum Circuit-Breakers

2

Equipment Selection 11

Ordering data and confi guration example 12

Selection of basic types, circuit-breakers:

Voltage level 17.5 kV; 16.7 Hz 13

Voltage level 25 kV; 25 Hz 13

Voltage level 27.5 kV; 50 /60 Hz 14

Selection of secondary equipment:

Release combination 14

Operating voltage, closing solenoid 15

Operating voltage, 1st shunt release 16

Operating voltage, 2nd release 17

Operating voltage, 3rd release 18

Operating voltage of the operating mechanism 19

Auxiliary switch, secondary connection, interlocking 20

Languages and frequency 21

Selection of additional equipment 22

Accessories and spare parts 23

Contents Page

R-HG

11-2

09.ti

f

3AH47 vacuum circuit-breaker, single-pole

R-HG

11-2

10.ti

f

3AH47 vacuum circuit-breaker, two-pole

Equipment SelectionContents

Page 12: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201212

3AH47 Vacuum Circuit-Breakers

2

Equipment SelectionOrdering data and confi guration example

Order number structure

The 3AH47 vacuum circuit-breakers consist of a primary and a secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit-breaker.

Order codes

Individual equipment versions, marked with 9 or Z in the 9th or 16th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence.

Special versions ( )

In case of special versions, “- Z” is added to the order num-ber and a descriptive order code follows. If several special versions are required, the suffi x “- Z” is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identi-fi ed with Y 9 9 in clear text. This has to be agreed upon in advance with the responsible sales partner.

a: alphabetical n: numerical

Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A E 4 7 n n – n a a n n – n a a n –

Primary part1st position Superior group

Switching devices

2nd position Main groupCircuit-breaker

3rd position SubgroupCircuit-breaker type series

4th to 8th position Basic equipmentDesign and ratingsprimary part

Secondary part9th to 16th position Secondary equipment

Operatingmechanism, releases, operatingvoltages and further auxiliary equipment

Order codesGroup of 3 after the Order No.Format: a n a

Special versions ( )Initiated with “-Z”Group of 3 after the Order No.Format: a n n

Confi guration example

In order to simplify the selection of the correct order number for the requested circuit-breaker type, you will fi nd a con-fi guration example on each page of the chapter “Equipment Selection”. For the selection of the secondary part, always the last example of the primary part was taken over and continued, so that at the end of the equipment selection (page 22) a completely confi gured circuit-breaker results as an example.

On the foldout page we offer a confi guring aid.Here you can fi ll in the order number you have deter-mined for your circuit-breaker.

Example for Order No.: 3 A H 4 7 5 5 – 4 –

Order codes:

Page 13: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 13

3AH47 Vacuum Circuit-Breakers

2

Example for Order No.: 3 A H 4 7 5 6 – 6 –

Order codes:

Equipment SelectionSelection of basic types, circuit-breakers

17.5 kV Position:

Order No.:

1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

16.7 Hz, single-pole 3 A H 4 7 – – –

Rate

d v

olt

age

Rate

d li

gh

tnin

g im

pu

lse

wit

hst

and

vo

ltag

e

Rate

d s

ho

rt-d

ura

tio

np

ow

er-f

req

uen

cyw

ith

stan

d v

olt

age

Rate

d s

ho

rt-c

ircu

it

bre

akin

g c

urr

ent

at 3

6 %

DC

co

mp

on

ent

Rate

d s

ho

rt-c

ircu

it

mak

ing

cu

rren

t(a

t 5

0/6

0 H

z)

Rate

d n

orm

al c

urr

ent

Nu

mb

er o

f V

acu

um

in

terr

up

ters

per

po

le

See

pag

e 1

4

See

pag

e 1

5

See

pag

e 1

6

See

pag

e 1

7

See

pag

e 1

8

See

pag

e 1

9

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

Ur Up Ud Isc Ima Ir VI

kV kV kV kA kA A /Pol

17.5 125 50 25 63 2000 1 3 A H 4 7 5 4 – 4

31.5 80 2000 1 3 A H 4 7 5 5 – 4

40 100 2500 1 3 A H 4 7 6 6 – 6

40 100 2500 2 3 A H 4 7 5 6 – 6

50 125 2500 2 3 A H 4 7 5 7 – 6

170 70 40 100 2500 2 3 A H 4 7 5 6 – 6 – Z D 6 5

1) 20,000 operating cycles

25 kV25 Hz, single-pole

Ur Up Ud Isc 2) Ima Ir VI

kV kV kV kA kA A /Pol

25 185 85 25 80 1250 1 3 A H 4 7 1 4 – 2

2000 1 3 A H 4 7 1 4 – 4

2500 1 3 A H 4 7 1 4 – 6

25 200 95 25 80 1250 1 3 A H 4 7 1 4 – 2 – Z E 2 6

2000 1 3 A H 4 7 1 4 – 4 – Z E 2 6

2500 1 3 A H 4 7 1 4 – 6 – Z E 2 6

25 kV25 Hz, two-pole

Ur Up Ud Isc 2) Ima Ir VI

kV kV kV kA kA A /Pol

25 185 85 25 80 1250 1 3 A H 4 7 1 4 – 2 – Z D 3 1

2000 1 3 A H 4 7 1 4 – 4 – Z D 3 1

2500 1 3 A H 4 7 1 4 – 6 – Z D 3 1

25 200 95 25 80 1250 1 3 A H 4 7 1 4 – 2 – Z D 3 1

+ E 2 7

2000 1 3 A H 4 7 1 4 – 4 – Z D 3 1

+ E 2 7

2500 1 3 A H 4 7 1 4 – 6 – Z D 3 1

+ E 2 7

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

Rated voltage Ur = 17.5 kV, 16.7 Hz

Rated lightning impulse withstand voltage Up = 125 kV

Rated short-circuit breaking current ISC = 40 kA

Rated normal current Ir = 2500 A 5 6 – 6

2) Other rating / data on request

1)

1)

1)

1)

Page 14: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201214

3AH47 Vacuum Circuit-Breakers

2

27.5 kV Position:

Order No.:

1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz, single-pole 3 A H 4 7 – – –

Rate

d v

olt

age

Rate

d li

gh

tnin

g im

pu

lse

wit

hst

and

vo

ltag

e

Rate

d s

ho

rt-d

ura

tio

np

ow

er-f

req

uen

cyw

ith

stan

d v

olt

age

Rate

d s

ho

rt-c

ircu

it

bre

akin

g c

urr

ent

at 3

6 %

DC

co

mp

on

ent

Rate

d s

ho

rt-c

ircu

it

mak

ing

cu

rren

t(a

t 5

0/6

0 H

z)

Rate

d n

orm

al c

urr

ent

Nu

mb

er o

f V

acu

um

in

terr

up

ters

per

po

le

See

pag

e 1

5

See

pag

e 1

6

See

pag

e 1

7

See

pag

e 1

8

See

pag

e 1

9

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

Ur Up Ud Isc Ima Ir VI

kV kV kV kA kA A /Pol

27.5 185 85 25 63 1250 1 3 A H 4 7 8 4 – 2

2000 1 3 A H 4 7 8 4 – 4

2500 1 3 A H 4 7 8 4 – 6

31.5 80 1250 2 3 A H 4 7 8 5 – 2

2500 1 3 A H 4 7 8 5 – 6

200 95 25 63 1250 1 3 A H 4 7 8 4 – 2 – Z E 2 6

2000 1 3 A H 4 7 8 4 – 4 – Z E 2 6

31.5 80 1250 1 3 A H 4 7 8 5 – 2 – Z E 2 6

2000 1 3 A H 4 7 8 5 – 4 – Z E 2 6

2500 1 3 A H 4 7 8 5 – 6 – Z E 2 6

250 105 25 63 1250 2 3 A H 4 7 9 4 – 2

2000 2 3 A H 4 7 9 4 – 4

1) 20,000 operating cycles

27.5 kV50/60 Hz, two-pole

Ur Up Ud Isc Ima Ir VI

kV kV kV kA kA A /Pol

27.5 185 85 25 63 1250 1 3 A H 4 7 8 4 – 2 – Z D 3 1

31.5 80 1250 1 3 A H 4 7 8 5 – 2 – Z D 3 1

2500 1 3 A H 4 7 8 5 – 6 – Z D 3 1

200 95 25 63 2000 1 3 A H 4 7 8 4 – 4 – Z D 3 1

+ E 2 7

31.5 80 2500 1 3 A H 4 7 8 5 – 6 – Z D 3 1

+ E 2 7

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

(Ur = 17.5 kV, 16,7 Hz, Up = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6 – 6

Closing solenoid, 1st shunt release, instantaneous release Y

9th position Release combination

Clo

sin

g s

ole

no

id

1st

sh

un

t re

leas

e

2n

d s

hu

nt

rele

ase

Un

der

volt

age

rele

ase

Inst

anta

neo

us

rele

ase

(cap

acit

or

trip

pin

g u

nit

as a

cces

sory

)

See

pag

e 1

5

See

pag

e 1

6

See

pag

e 1

7

See

pag

e 1

8

See

pag

e 1

9

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

M

N

T

R

Y

Example for Order No.: 3 A H 4 7 5 6 – 6 Y –

Order codes:

Equipment SelectionSelection of secondary equipment

1)

1)

Page 15: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 15

3AH47 Vacuum Circuit-Breakers

2

10th position

Operating voltage of the closing solenoidPosition: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A H 4 7 – – –

Standard voltages Special voltages

See

pag

e 1

6

See

pag

e 1

7

See

pag

e 1

8

See

pag

e 1

9

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

Mechanical closing at the circuit-breaker

24 V DC B

48 V DC C

60 V DC D

110 V DC E

220 V DC F

100 V AC 50 / 60 Hz 1) H

110 V AC 50 / 60 Hz 1) J

230 V AC 50 / 60 Hz 1) K

30 V DC Z With order code K 1 A

32 V DC Z With order code K 1 B

120 V DC Z With order code K 1 C

125 V DC Z With order code K 1 D

127 V DC Z With order code K 1 E

240 V DC Z With order code K 1 F

120 V AC 50 / 60 Hz 1) Z With order code K 1 K

125 V AC 50 / 60 Hz 1) Z With order code K 1 L

240 V AC 50 / 60 Hz 1) Z With order code K 1 M

Manual electrical closing at the circuit-breaker

24 V DC M

48 V DC N

60 V DC P

110 V DC Q

220 V DC R

100 V AC 50 / 60 Hz 1) T

110 V AC 50 / 60 Hz 1) U

230 V AC 50 / 60 Hz 1) V

30 V DC Z With order code K 2 A

32 V DC Z With order code K 2 B

120 V DC Z With order code K 2 C

125 V DC Z With order code K 2 D

127 V DC Z With order code K 2 E

240 V DC Z With order code K 1 F

120 V AC 50 / 60 Hz 1) Z With order code K 2 K

125 V AC 50 / 60 Hz 1) Z With order code K 1 L

240 V AC 50 / 60 Hz 1) Z With order code K 2 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 21)

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

(Ur = 17.5 kV, 16.7 Hz, Up = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6 – 6 Y

Manual electrical closing at the circuit-breaker,

operating voltage of the closing solenoid 32 V DC Z K 2 B

Equipment Selection Selection of secondary equipment

Example for Order No.: 3 A H 4 7 5 6 – 6 Y Z –

Order codes: K 2 B

Page 16: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201216

3AH47 Vacuum Circuit-Breakers

2

11th position

Operating voltage of the 1st shunt releasePosition: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A H 4 7 – – –

Standard voltages Special voltages

See

pag

e 1

7

See

pag

e 1

8

See

pag

e 1

9

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

24 V DC 1

48 V DC 2

60 V DC 3

110 V DC 4

220 V DC 5

100 V AC 50 / 60 Hz 1) 6

110 V AC 50 / 60 Hz 1) 7

230 V AC 50 / 60 Hz 1) 8

30 V DC 9 With order code L 1 A

32 V DC 9 With order code L 1 B

120 V DC 9 With order code L 1 C

125 V DC 9 With order code L 1 D

127 V DC 9 With order code L 1 E

240 V DC 9 With order code L 1 F

120 V AC 50 / 60 Hz 1) 9 With order code L 1 K

125 V AC 50 / 60 Hz 1) 9 With order code L 1 L

240 V AC 50 / 60 Hz 1) 9 With order code L 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 21)

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

(Ur = 17.5 kV, 16.7 Hz, Up = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6 – 6 Y Z

Operating voltage of the 1st shunt release 48 V DC 2

Equipment SelectionSelection of secondary equipment

Example for Order No.: 3 A H 4 7 5 6 – 6 Y Z 2 –

Order codes: K 2 B

Page 17: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 17

3AH47 Vacuum Circuit-Breakers

2

12th position

Operating voltage of the 2nd releasePosition: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A H 4 7 – – –

Shunt release, undervoltage release or instantaneous release 2)

Standard voltages Special voltages

See

pag

e 1

8

See

pag

e 1

9

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

Without 2nd release 0

24 V DC 1

48 V DC 2

60 V DC 3

110 V DC 4

220 V DC 5

100 V AC 50 / 60 Hz 1) 6

110 V AC 50 / 60 Hz 1) 7

230 V AC 50 / 60 Hz 1) 8

DC 30 V 9 With order code M 1 A

DC 32 V 9 With order code M 1 B

DC 120 V 9 With order code M 1 C

DC 125 V 9 With order code M 1 D

DC 127 V 9 With order code M 1 E

DC 240 V 9 With order code M 1 F

AC 120 V 50 / 60 Hz 1) 9 With order code M 1 K

AC 125 V 50 / 60 Hz 1) 9 With order code M 1 L

AC 240 V 50 / 60 Hz 1) 9 With order code M 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 21)

2) Instantaneous release only available for aux. voltages: 60 V DC, 110 V DC and 220 V DC

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

(Ur = 17.5 kV, 16.7 Hz, Up = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6 – 6 Y Z

Operating voltage of the 1st shunt release 48 V DC 2

2nd release as instantaneous release with operating voltage 60 V DC 3

Example for Order No.: 3 A H 4 7 5 6 – 6 Y Z 2 3 –

Order codes: K 2 B

Equipment Selection Selection of secondary equipment

Page 18: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201218

3AH47 Vacuum Circuit-Breakers

2

13th position

Operating voltage of the 3rd releasePosition: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A H 4 7 – – –

Undervoltage release

Standard voltages Special voltages

See

pag

e 1

9

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

Without 3rd release 0

24 V DC 1

48 V DC 2

60 V DC 3

110 V DC 4

220 V DC 5

100 V AC 50 / 60 Hz 1) 6

110 V AC 50 / 60 Hz 1) 7

230 V AC 50 / 60 Hz 1) 8

30 V DC 9 With order code N 1 A

32 V DC 9 With order code N 1 B

120 V DC 9 With order code N 1 C

125 V DC 9 With order code N 1 D

127 V DC 9 With order code N 1 E

240 V DC 9 With order code N 1 F

120 V AC 50 / 60 Hz 1) 9 With order code N 1 K

125 V AC 50 / 60 Hz 1) 9 With order code N 1 L

240 V AC 50 / 60 Hz 1) 9 With order code N 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 21)

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

(Ur = 17.5 kV, 16.7 Hz, Up = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6 – 6 Y Z 2 3

Without 3rd release – 0

Example for Order No.: 3 A H 4 7 5 6 – 6 Y Z 2 3 – 0

Order codes: K 2 B

Equipment SelectionSelection of secondary equipment

Page 19: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 19

3AH47 Vacuum Circuit-Breakers

2

Equipment Selection Selection of secondary equipment

14th position

Operating voltage of the operating mechanismPosition: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A H 4 7 – – –

Standard voltages Special voltages

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

Manual operating mechanism(hand crank included in the scope of supply)

A

24 V DC B

48 V DC C

60 V DC D

110 V DC E

220 V DC F

100 V AC 50 / 60 Hz 1) H

110 V AC 50 / 60 Hz 1) J

230 V AC 50 / 60 Hz 1) K

30 V DC Z With order code P 1 A

32 V DC Z With order code P 1 B

120 V DC Z With order code P 1 C

125 V DC Z With order code P 1 D

127 V DC Z With order code P 1 E

240 V DC Z With order code P 1 F

120 V AC 50 / 60 Hz 1) Z With order code P 1 K

125 V AC 50 / 60 Hz 1) Z With order code P 1 L

240 V AC 50 / 60 Hz 1) Z With order code P 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of theorder number together with the language (see page 21)

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

(Ur = 17.5 kV, 16.7 Hz, Up = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6 – 6 Y Z 2 3 – 0

Operating voltage of the operating mechanism 48 V DC C

Example for Order No.: 3 A H 4 7 5 6 – 6 Y Z 2 3 – 0 C

Order codes: K 2 B

Page 20: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201220

3AH47 Vacuum Circuit-Breakers

2

15th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Auxiliary switch, secondary connection, interlocking Order No.: 3 A H 4 7 – – –

Mec

han

ical

in

terl

ock

ing

Au

xilia

ry s

wit

ch6

NO

+ 6

NC

Au

xilia

ry s

wit

ch

12

NO

+ 1

2 N

C

64

-po

le p

lug

1)

24

-po

le p

lug

2)

24

-po

le

term

inal

str

ip 2

)

See

pag

e 2

1

See

pag

e 2

2

A

E

G

C

M

B

F

H

D

N

Special version

Auxiliary switch 12 NO + 12 NC and 24-pole plug (E or F) – Z A 2 6

Special versions gold-plated auxiliary switch contacts

Auxiliary switch 6 NO + 6 NC and 24-pole terminal strip (G or H) – Z A 1 7

Auxiliary switch 12 NO + 12 NC and 24-pole terminal strip (M or N) – Z A 1 8

Special versions gold-plated auxiliary switch contacts and plug pins

Auxiliary switch 6 NO + 6 NC and 64-pole plug (A or B) – Z A 2 0

Auxiliary switch 12 NO + 12 NC and 64-pole plug (C or D) – Z A 2 1

1) Depending on the equipment, some connections of the 64-pole plugconnector remain free. These can be connected to free auxiliary switchcontacts by the customer. Prefabricated wires are available as accessories.

2) Auxiliary switch contacts are not wired to the plug/terminal strip andmust therefore be connected directly.

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

(Ur = 17.5 kV, 16.7 Hz, Up = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6 – 6 Y Z 2 3 – 0 C

Auxiliary switch 6 NO + 6 NC, 64-pole plug, without mechanical interlocking A

Equipment SelectionSelection of secondary equipment

Example for Order No.: 3 A H 4 7 5 6 – 6 Y Z 2 3 – 0 C A

Order codes: K 2 B

Page 21: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 21

3AH47 Vacuum Circuit-Breakers

2

Example for Order No.: 3 A H 4 7 5 6 – 6 Y Z 2 3 – 0 C A 2

Order codes: K 2 B

16th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

AC frequency of operating voltages Order No.: 3 A H 4 7 – – –

Languages of operating instructions and rating plate

Language selection Frequency selection

Ger

man

Eng

lish

Fren

ch

Span

ish

DC

50

Hz

50

Hz

and

DC

60

Hz

60

Hz

and

DC

See

pag

e 2

2

0

1

2

3

4

5

6

7

Other languages on request

Special versions

Additional information on the rating plate. Information in clear text. – Z Y 1 2

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

(Ur = 17.5 kV, 16.7 Hz, Up = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6 – 6 Y Z 2 3 – 0 C

Auxiliary switch 6 NO + 6 NC, 64-pole plug, without mechanical interlocking A

Frequency 50 Hz or DC, operating instructions and rating plate in English 2

Equipment Selection Selection of secondary equipment

Page 22: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201222

3AH47 Vacuum Circuit-Breakers

2

Equipment SelectionSelection of secondary equipment

Additional equipment Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A H 4 7 – – –

Options

Wiring cables, halogen-free and fl ame-retardant – Z A 1 0

Condensation protection, for 230 V AC, 50 W – Z A 3 0

Additional rating plate, loose delivery – Z B 0 0

Routine test certifi cate enclosed – Z F 2 0

Hand crank (also formotor operatingmechanism)formanual charging of the closing spring – Z F 3 0

Further special versions on request. Information in clear text – Z Y 9 9

Confi guration example

3AH47 vacuum circuit-breaker, single-pole 3 A H 4 7

Rated voltage Ur = 17.5 kV, 16.7 Hz

Rated lightning impulse withstand voltage Up = 125 kV

Rated short-circuit breaking current ISC = 40 kA

Rated normal current Ir = 2500 A 5 6 – 6

Closing solenoid, 1st shunt release, instantaneous release Y

Manual electrical closing at the circuit-breaker, operating voltage

of the closing solenoid 32 V DC Z K 2 B

Operating voltage of the 1st shunt release 48 V DC 2

2nd release as instantaneous release with operating voltage DC 60 V 3

Without 3rd release – 0

Operating voltage of the operating mechanism 48 V DC C

Auxiliary switch 6 NO + 6 NC, 64-pole plug, without mechanical interlocking A

Frequency 50 Hz or DC, operating instructions and rating plate in English 2

Routine test certifi cate enclosed – Z F 2 0

Example for Order No.: 3 A H 4 7 5 6 – 6 Y Z 2 3 – 0 C A 2 – Z

Order codes: K 2 B + F 2 0

Page 23: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 23

3AH47 Vacuum Circuit-Breakers

2

Equipment Selection Selection of secondary equipment

Ordering information for accessories and spare parts

The order numbers in the spare part overview are appli-cable to vacuum circuit-breakers of current manufacture. When mounting parts or spare parts are being ordered for an existing vacuum circuit-breaker, always quote the type designation, serial number and the year of manufacture of the circuit-breaker to be sure to get the correct delivery.

Retrofi tting

When releases/solenoids are retrofi tted, the order numbers of the mounting parts must also be specifi ed. For other addi-tional equipment, the required mounting parts are included in the delivery.

Spare pole assemblies

As spare parts, the vacuum interrupters are always supplied as a complete pole including post insulator.

Vacuum pole assemblies and other spare parts must only be replaced by instructed personnel.

Data on the rating plate

�������&"��

���

Designation Remarks Order No.

Hand crank 3AX15 30-2B

Lubricant (for special application conditions)

180 g Klüber-Isofl ex Topas L32N 3AX11 33-3H

1 kg Klüber-Isofl ex Topas L32N 3AX11 33-3E

1 kg Shell Tellus oil 32 (special oil) 3AX11 33-2D

Wire bundle With 10 wires for auxiliary switch connection to

– 64-pole plug connector 3AX11 34-2D

– 24-pole plug connector 3AX11 34-2B

– 24-pole terminal strip 3AX11 34-2C

Accessories for plug connector (for wire cross-section 1.5 mm2)

Crimp pins for lower part of plug 24-pole 3AX11 34-3A

64-pole 3AX11 34-4B

Crimp sockets for upper part of plug 64-pole 3AX11 34-4C

Crimping pliers 3AX11 34-4D

Disassembly tool 3AX11 34-4G

Accessories for the plug connector

Included in the scope of supply of the basic equipment for 3AH47 vacuum circuit-breakers:

For 24-pole plug connector– Lower part of plug– Crimp sockets according to number of contacts– Upper part of plug with screwed contacts

(no crimp sockets required)

For 64-pole plug connector– Lower part of plug– Upper part of plug– Crimp sockets according to number of contacts

Note:For any query regarding spare parts,subsequent deliveries, etc. the followingthree details are necessary:

– Type designation – Serial No. – Year of manufacture

Page 24: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201224

3AH47 Vacuum Circuit-Breakers

2

Equipment SelectionSelection of secondary equipment

Designation Remarks Operating voltage Order No.

Including varistor Used as closing solenoid or 24 V DC 3AX15 10-5B

1st shunt release (Including varistor) 30/32 V DC 3AX15 10-5M

48 V DC 3AX15 10-5C

60 V DC 3AX15 10-5D

110/120 V DC 3AX15 10-5E

125/127 V DC 3AX15 10-5N

220/240 V DC 3AX15 10-5F

Including varistor and rectifi er 100 – 125 V AC, 50/60 Hz 3AX15 10-5E

230/240 V AC, 50/60 Hz 3AX15 10-5F

2nd shunt release Without varistor, without rectifi er 24 – 32 V DC 3AX11 01-2B

Including varistor 48 – 60 V DC 3AX11 01-2C

110 – 127 V DC 3AX11 01-2E

220 – 240 V DC 3AX11 01-2F

Including varistor and rectifi er 100 – 125 V AC, 50 Hz 3AX11 01-2G

230 – 240 V AC, 50 Hz 3AX11 01-2J

100 – 125 V AC, 60 Hz 3AX11 01-3G

230 – 240 V AC, 60 Hz 3AX11 01-3J

Instantaneous release (Attention: Instantaneous releases cannot be retrofi tted 60 V DC 3AX60 13-0A

if there is a 2nd and/or 3rd release available) 110 V DC 3AX60 12-0A

220 V DC 3AX60 11-0A

Capacitor tripping unit Required for operation of the instantaneous release. 60 V DC 3AX15 50-0D 1)

The rated voltage of the tripping unit must be 110 V DC 3AX15 50-0E 1)

selected in accordance with the operating voltage 220 V DC 3AX15 50-0F 1)

of the instantaneous release.

Undervoltage release Without varistor, without rectifi er 24 V DC 3AX11 03-2B

30/32 V DC 3AX11 03-2L

48 V DC 3AX11 03-2C

Including varistor 60 V DC 3AX11 03-2D

110 V DC 3AX11 03-2E

120 V – 127 V DC 3AX11 03-2N

220 V DC 3AX11 03-2F

240 V DC 3AX11 03-2P

Including varistor and rectifi er 100 V AC, 50 Hz 3AX11 03-2G

110 V – 125 V AC, 50 Hz 3AX11 03-2H

230 V AC, 50 Hz 3AX11 03-2J

240 V AC, 50 Hz 3AX11 03-2M

100 V AC, 60 Hz 3AX11 03-2G

110 V – 125 V AC, 60 Hz 3AX11 03-2H

230 V AC, 60 Hz 3AX11 03-2J

240 V AC, 60 Hz 3AX11 03-2M

Mounting parts For 2nd shunt release or undervoltage release

With 1 existing shunt release 3AX17 11-3A

With 2 existing releases (shunt release or 3AX17 11-3B

untervoltage release)

Drive motor 24/30/32 V DC 3AX15 11-3B

48 V DC 3AX15 11-3C

From 60 V DC with integrated varistor 60 V DC 3AX15 11-3D

For AC, rectifi er required 100/110/125/127 V DC/AC 3AX15 11-3E

220 V DC/230 V AC 3AX15 11-3F

240 V – 250 V DC/AC 3AX15 11-3G

1) To be ordered at Fa. FEAG Sangerhausen GmbH

Page 25: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 25

3AH47 Vacuum Circuit-Breakers

2

Designation Remarks Operating voltage Order No.

Rectifi er module For drive motor with AC operation 100 V – 250 V AC 3AX15 25-1F

Auxiliary contactor Typ 3TH20 22-7 24/30/32 V DC SWB: 48683

For anti-pumping 48 V DC SWB: 48687

60 V DC SWB: 48684

100/120 V DC SWB: 48685

125 V – 127 V DC SWB: 47730

220 V – 240 V DC SWB: 48686

100 – 125 V AC, 50 Hz SWB: 48680

230 – 240 V AC, 50 Hz SWB: 55550

100 – 125 V AC, 60 Hz SWB: 48679

230 – 240 V AC, 60 Hz SWB: 55550

Position switch Type 3SE4 (as spare part), without installation accessories

Used for: Nos. 3AX42 06-0A

– Electrical anti-pumping (-S3) 1

– Motor control (-S21, -S22) 2

– Cling spring charged (-S4) 1

– Circuit-breaker tripping signal (-S6, -S7) 2

– Electrical closing lock-out (-S5) 1

Auxiliary switch (-S1) 6 NO + 6 NC 3SV92 73-2AA0

12 NO + 12 NC 3SV92 74-2AA0

Mechanical interlocking 3AX15 20-3C

Protection elements e.g. spring washers and splint pins for switch maintenance

1 set for each traction circuit-breaker

3AY15 50-1A

Replacement vacuum interrupters 1) 3AH4714-2/4/6, 3AH4714-2/4/6 Z E26, 3AH4714-2/4/6 Z D31, 3AH4714-2/4/6 Z D31 + E27 3AY17 15-1M

3AH4754-4, 3AH4755-4 3AY17 15-2M

3AH4756-6, 3AH4757-6 3AY17 15-5J

3AH4756-6 Z D65 3AY17 15-3N

3AH4766-6 3AY17 15-2J

3AH4784-2/4/6, 3AH4784-2/4 Z E26, 3AH4784-2 Z D31, 3AH4784-4 Z D31 + E27 3AY17 15-1L

3AH4785-2/6, 3AH4785-2/4/6 Z E26, 3AH4785-2/6 Z D31, 3AH4785-6 Z D31 + E27 3AY17 15-1M

3AH4794-2/4 3AY17 15-1K

Equipment Selection Selection of secondary equipment

1) In traction circuit-breaker with two interrupters, both have to be replaced

Page 26: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

R-HG

11-2

13.ti

f

Siemens HG 11.52 · 201226

3AH47 Vacuum Circuit-Breakers

Page 27: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 27

3AH47 Vacuum Circuit-Breakers

3

Technical Data 27

Electrical data, dimensions and weights:

Voltage level 17.5 kV 28

Voltage level 25 kV (single-pole) 28

Voltage level 25 kV (two-pole) 28

Voltage level 27.5 kV (single-pole) 29

Voltage level 27.5 kV (two-pole) 29

Circuit diagrams 33

Operating times 35

Short-circuit protection of motors 35

Consumption data of releases 35

Contents Page

R-HG

11-2

11.ti

fR-

HG11

-212

.tif

Technical DataContents

Post insulator and pole assembly

Operating shaft and operating rod

Page 28: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201228

3AH47 Vacuum Circuit-Breakers

3

Technical DataElectrical data, dimensions and weights

17.5 kV16.7 Hz, single-pole

Ra

ted

no

rma

l cu

rre

nt

Nu

mb

er

of

Va

cuu

m in

terr

up

ters

pe

r p

ole

Rate

d o

per

atin

g s

equ

ence

: 1

)

O –

3 m

in –

CO

– 3

min

– C

O

O –

5 s

– C

O

O –

8 s

– C

O –

30

s –

CO

Rate

d d

ura

tio

n o

f sh

ort

-cir

cuit

Rate

d s

ho

rt-c

ircu

it b

reak

ing

cu

rren

t

DC

co

mp

on

ent

in %

of

the

rate

d s

ho

rt-c

ircu

it b

reak

ing

cu

rren

t

Asy

mm

etri

cal b

reak

ing

cu

rren

t

Rate

d s

ho

rt-c

ircu

it m

akin

g c

urr

ent

Rate

d li

gh

tnin

g im

pu

lse

wit

hst

and

vo

ltag

e

Rate

d s

ho

rt-d

ura

tio

n p

ow

er-f

req

uen

cyw

ith

stan

d v

olt

age

Vo

ltag

e d

rop

ΔU

bet

wee

n c

on

nec

tio

ns

(acc

ord

ing

to

IEC

62

27

1-1

at

DC

10

0 A

)

Min

imu

mcr

eep

age

dis

tan

ce,

inte

rru

pter

Min

imu

mcr

eep

age

dis

tan

ce,

ph

ase-

to-e

arth

Min

imu

m c

lear

ance

,p

has

e-to

-ear

th

Wei

gh

ts

Det

aile

d d

imen

sio

n d

raw

ing

(can

be

ord

ered

)

Op

erat

ing

cyc

le d

iag

ram

no

. (s

ee p

age

29

)

Cat

alo

g d

imen

sio

n d

raw

ing

no

.(s

ee p

ages

30

an

d 3

1)

Ord

er

No

.

Ir VI/ tk Isc Ima Up Ud

A Pol s kA % kA kA kV kV mV mm mm mm kg

3AH47 54-4... 2000 1 3 25 65 33.9 63 125 50 2.2 360 220 160 90 S_325 00021 1 1

3AH47 55-4... 2000 1 3 31.5 65 42.8 80 125 50 2.2 360 220 160 90 S_325 00021 2 1

3AH47 66-6... 2500 1 3 40 65 54.3 100 125 50 2.0 276 205 165 110 S_325 00025 3 3

3AH47 56-6... 2500 2 3 40 65 54.3 100 125 50 3.2 320 210 210 138 S_325 00022 3 3

3AH47 57-6... 2500 2 3 50 65 67.9 125 125 50 3.2 320 210 210 138 S_325 00022 4 2

3AH47 56-6-Z D65 2500 2 3 40 80 60.4 100 170 70 3.2 320 340 300 138 S_325 00507 3 2

Standard according to IEC 62271-100 Possible

25 kV25 Hz, single-pole

O –

0.3

s –

CO

– 3

min

– O

Ir VI/ tk Isc Ima Up Ud

A Pol s kA % kA kA kV kV mV mm mm mm kg

3AH47 14-2... 1250 1 3 25 36 28 63 185 85 2.2 360 409 270 100 S_325 00527 1 5

3AH47 14-4... 2000 1 3 25 36 28 63 185 85 2.2 360 409 270 100 S_325 00527 1 5

3AH47 14-6... 2500 1 3 25 36 28 63 185 85 2.2 360 409 270 100 S_325 00527 1 5

3AH47 14-2-Z E26 1250 1 3 25 36 28 63 200 95 2.2 360 409 270 100 S_325 00527 1 5

3AH47 14-4-Z E26 2000 1 3 25 36 28 63 200 95 2.2 360 409 270 100 S_325 00527 1 5

3AH47 14-6-Z E26 2500 1 3 25 36 28 63 200 95 2.2 360 409 270 100 S_325 00527 1 5

25 kV25 Hz, two-pole

O –

0.3

s –

CO

– 3

min

– O

Ir VI/ tk Isc Ima Up Ud

A Pol s kA % kA kA kV kV mV mm mm mm kg

3AH47 14-2-Z D31 1250 1 3 25 36 28 63 185 85 2.2 360 409 270 135 S_325 00529 1 8

3AH47 14-4-Z D31 2000 1 3 25 36 28 63 185 85 2.2 360 409 270 135 S_325 00529 1 8

3AH47 14-6-Z D31 2500 1 3 25 36 28 63 185 85 2.2 360 409 270 135 S_325 00529 1 8

3AH47 14-2-Z D31+E27 1250 1 3 25 36 28 63 200 95 2.2 360 409 270 135 S_325 00529 1 8

3AH47 14-4-Z D31+E27 2000 1 3 25 36 28 63 200 95 2.2 360 409 270 135 S_325 00529 1 8

3AH47 14-6-Z D31+E27 2500 1 3 25 36 28 63 200 95 2.2 360 409 270 135 S_325 00529 1 8

Standard according to IEEE C37.09 1) Further operating sequences on request

1) Further operating sequences on request

Page 29: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 29

3AH47 Vacuum Circuit-Breakers

3

27.5 kV50/60 Hz, single-pole

Ra

ted

no

rma

l cu

rre

nt

Nu

mb

er

of

Va

cuu

m in

terr

up

ters

pe

r p

ole

Rate

d o

per

atin

g s

equ

ence

: 1

)

O –

3 m

in –

CO

– 3

min

– C

O

O –

0.3

s –

CO

– 3

min

– O

Rate

d d

ura

tio

n o

f sh

ort

-cir

cuit

Rate

d s

ho

rt-c

ircu

it b

reak

ing

cu

rren

t

DC

co

mp

on

ent

in %

of

the

rate

d s

ho

rt-c

ircu

it b

reak

ing

cu

rren

t

Asy

mm

etri

cal b

reak

ing

cu

rren

t

Rate

d s

ho

rt-c

ircu

it m

akin

g c

urr

ent

Rate

d li

gh

tnin

g im

pu

lse

wit

hst

and

vo

ltag

e

Rate

d s

ho

rt-d

ura

tio

n p

ow

er-f

req

uen

cyw

ith

stan

d v

olt

age

Vo

ltag

e d

rop

ΔU

bet

wee

n c

on

nec

tio

ns

(acc

ord

ing

to

IEC

62

27

1-1

at

DC

10

0 A

)

Min

imu

mcr

eep

age

dis

tan

ce,

inte

rru

pter

Min

imu

mcr

eep

age

dis

tan

ce,

ph

ase-

to-e

arth

Min

imu

m c

lear

ance

,p

has

e-to

-ear

th

Wei

gh

ts

Det

aile

d d

imen

sio

n d

raw

ing

(can

be

ord

ered

)

Op

erat

ing

cyc

le d

iag

ram

no

. (s

ee p

age

29

)

Cat

alo

g d

imen

sio

n d

raw

ing

no

.(s

ee p

ages

30

an

d 3

1)

Be

ste

ll-N

r.

Ir VI/ tk Isc Ima Up Ud

A Pol s kA % kA kA kV kV mV mm mm mm kg

3AH47 84-2... 1250 1 3 25 36 28 63 185 85 2.6 360 409 255 100 S_325 00027 5 4

3AH47 84-4... 2000 1 3 25 36 28 63 185 85 2.6 360 409 255 100 S_325 00027 5 4

3AH47 84-6... 2500 1 3 25 36 28 63 185 85 2.6 360 409 255 100 S_325 00027 5 4

3AH47 85-2... 1250 1 3 31.5 36 35.4 80 185 85 2.2 360 409 255 100 S_325 00027 6 4

3AH47 85-6... 2500 1 3 31.5 36 35.4 80 185 85 2.2 360 409 255 100 S_325 00027 6 4

3AH47 84-2...-Z E26 1250 1 3 25 36 28 63 200 95 2.6 360 409 270 100 S_325 00527 5 5

3AH47 84-4...-Z E26 2000 1 3 25 36 28 63 200 95 2.6 360 409 270 100 S_325 00527 5 5

3AH47 85-2...-Z E26 1250 1 3 31.5 36 35.4 80 200 95 2.2 360 409 270 100 S_325 00527 6 5

3AH47 85-4...-Z E26 2000 1 3 31.5 36 35.4 80 200 95 2.2 360 409 270 100 S_325 00527 6 5

3AH47 85-6...-Z E26 2500 1 3 31.5 36 35.4 80 200 95 2.2 360 409 270 100 S_325 00527 6 5

3AH47 94-2... 1250 2 3 25 36 28 63 250 105 4.0 480 480 400 135 S_325 00024 7 6

3AH47 94-4... 2000 2 3 25 36 28 63 250 105 4.0 480 480 400 135 S_325 00024 7 7

27.5 kV50/60 Hz, two-pole

O –

3 m

in –

CO

– 3

min

– C

O

O –

0.3

s –

CO

– 3

min

– O

Ir VI/ tk Isc Ima Up Ud

A Pol s kA % kA kA kV kV mV mm mm mm kg

3AH47 84-2...-Z D31 1250 1 3 25 36 28 63 185 85 2.6 360 409 255 135 S_325 00026 5 8

3AH47 85-2...-Z D31 1250 1 3 31.5 36 35.4 80 185 85 2.2 360 409 255 135 S_325 00026 6 8

3AH47 85-6...-Z D31 2500 1 3 31.5 36 35.4 80 185 85 2.2 360 409 255 135 S_325 00026 6 8

3AH47 84-4...-Z D31+E27 2000 1 3 25 36 28 63 200 95 2.6 360 409 270 135 S_325 00529 5 8

3AH47 85-6...-Z D31+E27 2500 1 3 31.5 36 35.4 80 200 95 2.2 360 409 270 135 S_325 00529 6 8

Standard according to IEC 62271-100 Possible

Technical DataElectrical data, dimensions and weights

1) Further operating sequences on request

Page 30: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201230

3AH47 Vacuum Circuit-Breakers

3

Technical DataElectrical data, dimensions and weights

Operating cycle diagrams for 27.5 kV, single-pole and two-pole

The permissible number of

electrical operating cycles

is shown as a function

of the breaking current

(r.m.s. value). All vacuum

circuit-breakers fulfi l the

endurance classes E2,

M2 and C2 according

to IEC 62271-100. The

curve shape beyond the

parameters defi ned in

IEC 62271-100 is based on

average experience data.

The number of operating

cycles that can actually be

reached can be different

depending on the respective

application.'���(��)"������*�#�##+�!��,

-�������)"."!�

�����

����

����

����

���

���

��

��� � � �� �� (���

�����������

���

���

���

������

�����

��

��

�� ����'���(��)"������*�#�##+�!��,

�����������

���

-�������)"."!�

����

����

����

���

���

���

��

��� � � �� (��� ���

��

�����

�����������

��

Operating cycle diagrams for 17.5 kV

The permissible number of

electrical operating cycles

is shown as a function

of the breaking current

(r.m.s. value). All vacuum

circuit-breakers fulfi l the

endurance classes E2,

M2 and C2 according

to IEC 62271-100. The

curve shape beyond the

parameters defi ned in

IEC 62271-100 is based on

average experience data.

The number of operating

cycles that can actually be

reached can be different

depending on the respective

application.

�����

����

����

����

���

���

���

��

��� � � �� �� (���

�����������

���

���

����

������

�����

��

���

��'���(��)"������*�#�##+�!��,

-�������)"."!�

'���(��)"������*�#�##+�!��,

�����

����

����

����

���

���

���

��

��� � � �� (���

�������&�

����

���

�����

������

��

��

-�������)"."!�

���

Page 31: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 31

3AH47 Vacuum Circuit-Breakers

3

Technical DataElectrical data, dimensions and weights

Dimension drawing 1

3AH47 54-43AH47 55-4

Dimension drawing 3

3AH47 66-6

Dimension drawing 4

3AH47 84-2 1)

3AH47 84-4 1)

3AH47 84-6 2) 3AH47 85-2 3AH47 85-6 2)

Dimension drawing 2

3AH47 56-63AH47 56-6 -Z D65 1)

3AH47 57-6

Dimension drawing 5

3AH47 84-2 -Z E26 1)

3AH47 84-4 -Z E26 1)

3AH47 85-2 -Z E26 3AH47 85-4 -Z E26 3AH47 85-6 -Z E26 2)

Dimension drawings for 17.5 kV

Dimension drawings for 25 and 27.5 kV

�&�

���

���

�����������

���

��

���

�&�

���

���

���/����,

�����������

���

� / � �,

��/

����

,

���

�&�

���

��

�� /���,

�����������

���

��

/�����

,

�/ ��, ���

�&�

���

���

���/����,

�����������

���

�/����

,

��� ��/ ��,

�&�

���

��

����������

���

��

&�

���

���

3AH47 14-2 2)

3AH47 14-4 2)

3AH47 14-6 2)

3AH47 14-2 -Z E26 2)

3AH47 14-4 -Z E26 2)

3AH47 14-6 -Z E26 2)

Page 32: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201232

3AH47 Vacuum Circuit-Breakers

3

Technical DataElectrical data, dimensions and weights

Dimension drawing 6

3AH47 94-2

Dimension drawing 8

3AH47 84-2 -Z D313AH47 84-4 -Z D313AH47 85-2 -Z D313AH47 85-4 -Z D31 + E27 1)

3AH47 85-6 -Z D31 + E27 1)

Dimension drawing 7

3AH47 94-4

Dimension drawings for 27.5 kV

�&�

���

���

�����������

���

&��

����

���

����������

���

���

���

���

������

�������

�������� �����

�&�

�&�

���

���

����������

���

&��

����

���

3AH47 14-2 -Z D31 1)

3AH47 14-4 -Z D31 1)

3AH47 14-6 -Z D31 1)

3AH47 14-2 -Z D31 + E27 1)

3AH47 14-4 -Z D31 + E27 1)

3AH47 14-6 -Z D31 + E27 1)

Page 33: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 33

3AH47 Vacuum Circuit-Breakers

3

���� ����

0

���� ���� ��� ���� ����

�1

��

�2�

�� ���

�2�

3�0�

�����������

���������

����

��

����

4�

������

��

�5�

��

��

����

��

��

��

����

��

��

��

��

��

������

��

��

�6�

�6�

�6�

����

�0�

����

����

�5�

0

���������� ��

���2�

�7

Circuit diagramsThe circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.

Circuit-breakertripping-signal

Signal“closing springcharged“

1th shunt release

��

��

��

�����

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

�5�

�5� �����������

����

��

�5�

�5�

��

�����

��

��

��

��

��

��

���� ����

���

����������� ��

���2�

Contacts available for customer 5 NO + 5 NCManual closing – manual opening with auxiliary switch 6 NO + 6 NC

Motor operating mechanism with mechanical closing

Technical DataCircuit diagrams

A1 Capacitor tripping unitHA Manual openingHE Manual closingK1 Contactor (anti-pumping)M1 Motor operating mechanismP Energy storeR1 Resistance

S1 Auxiliary switchS3 Position switch (opens when closing spring is charged)S6 Circuit-breaker tripping signalS7 Cutout switch for circuit- breaker tripping signalS10, Anti-pumping forS11 manual closing

S14, Anti-pumpingS15S21, Position switchesS22 (to de-energize the motor operating mechanism after charging)S41, Position switchesS42 (to indicate the charging state)

X0 Lower part of plug/ terminal stripY1 1st shunt releaseY2 2nd shunt releaseY7 Undervoltage releaseY9 Closing solenoid

Motors and release coils and/or closing solenoids are equipped with varistor circuits.

For use of AC voltage, commutators are integrated.

Legend (also for page 34)

Page 34: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201234

3AH47 Vacuum Circuit-Breakers

3

Additional equipment: Motor operating mechanism with manual electrical closing

��

��

��

�����

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

���

���

���

���

���

���

���

���

���

���

���

���

�5�

�5� ������������

�����

��

�����������

�5�

�5�

�2���

��

�����

��

����

�24�

4�

�����������

�5�

�5�

� 8

���$�

��

�����������

���

���

���

�����

�����

��

��

����

Additional equipment: Auxiliary switch

Additional equipment: Releases

Contacts available for customer with basic circuit-breaker equipmentAuxiliary switch –S1 (12 NO + 12 NC) instead of auxiliary switch 6 NO + 6 NC

2nd shunt release

Legend see page 34

Instantaneous releaseUndervoltage release

Technical DataCircuit diagrams

������� �

����

�$�� �$��

�$�� �$�� �$� �$�� �$��

��

��&

�$ �$

���

!���

����� �������

�5�

��

��

��

����

��

��

��

��

��

��

��

������

��

��

�6�

�6�

�2� �6�

�5�

��

������

��

������

������������

������

��

�5�

��

������

�5�

������������

��

4�

�0� 0�7

Manual electrical closing

Closing andanti-pumping

Motor operating mechanism

Page 35: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 35

3AH47 Vacuum Circuit-Breakers

3

Technical DataOperating times, short-circuit protection of motors, consumption data of releases

Operating times

Operating times at rated voltageof the secondary circuit

Equipment of circuit-breakerOperating time

of circuit-breaker

Closing time – < 80 ms

Opening time 1st shunt release < 65 ms

Additional release < 50 ms

Instantaneous release < 17 ms

Arcing time (50/60 Hz; 25 Hz; 16.7 Hz) – (15 ms; 25 ms; 33 ms)

Break time 1st shunt release < 80 ms

Additional release < 60 ms

Instantaneous release (at 16.7 Hz) < 50 ms

Dead time – 300 ms

CLOSE/OPEN contact time 1st shunt release < 90 ms

Instantaneous release < 70 ms

Minimum command duration Closing solenoid (CLOSED) 45 ms

1st shunt release (OPEN) 40 ms

Additional release (OPEN) 20 ms

Pulse time for circuit-breaker tripping signal 1st shunt release > 15 ms

2nd shunt release > 10 ms

Charging time for electrical operation – < 15 s

Short-circuit protection of motors (fuse protection of drive motors)

Rated voltageof the motor

Operating voltage Power consumption of the motor

Smallest possible ratedcurrent 1) of the m.c.b.(miniature circuit-breaker)with C-characteristic

V max. V min. V W (at DC) VA (at AC) A

24 DC 26 20 500 – 16

48 DC 53 41 500 – 10

60 DC 66 51 500 – 6

110 DC 121 93 500 – 4

220 DC 242 187 500 – 2

110 AC 121 93 – 650 6

230 AC 244 187 – 650 3

1) The current inrush in the drive motor can be neglected due to its very short presence.

Consumption data of releases

Release Power consumption Tripping ranges 1)

Operation atTripping voltage

DCapprox. W

AC 50 / 60 Hzapprox. VA

at DC at AC 50 / 60 Hz

Closing solenoid 3AY15 10 140 140 85 to 110 % U 85 to 110 % U

1st shunt release(without energy store) 3AY15 10

140 140 70 to 110 % U 85 to 110 % U

2nd shunt release(with energy store) 3AX11 01

70 50 70 to 110 % U 85 to 110 % U

Undervoltage release 3AX11 03 20 20 35 to 0 % U 35 to 0 % U

1) According to IEC standards. Tripping ranges according to ANSI are available on request.

Page 36: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201236

3AH47 Vacuum Circuit-Breakers

R-HG

11-1

81.ti

f

Page 37: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 2012 37

3AH47 Vacuum Circuit-Breakers

4

Annex 37

Inquiry form 38

Confi guration instructions 39

Confi guration aid Foldout page

Contents Page

R-HG

11-1

80.e

ps

Switchgear Factory in Berlin, Germany

AnnexContents

Page 38: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

Siemens HG 11.52 · 201238

3AH47 Vacuum Circuit-Breakers

4

AnnexInquiry form

Please copy, fi ll in and returnto your Siemens partner.

Inquiry concerning

3AH47 circuit-breaker

Please

Submit an offer Call us Visit us

Your address

Company

Dept.

Name

Street

Postal code/city

Phone

Fax

E-mail

Siemens AG

Dept.

Name

Street

Postal code/city

Fax

Technical data Other values

Rated voltage 17.5 kV, 16.7 Hz 27.5 kV, 50/60 Hz 25 kV, 25 Hz ___ kV

Rated lightning impulse 125 kV 170 kV 185 kV withstand voltage 200 kV 250 kV ___ kV

Rated short-duration power- 50 kV 70 kV 85 kV frequency withstand voltage 95 kV 105 kV ___ kV

Rated short-circuit 25 kA 31.5 kA breaking current 40 kA 50 kA ___ kA

Rated normal current 1250 A 2000 A 2500 A ___ A

Number of poles Single-pole Two-pole

Secondary equipmentFor possible combinations see pages 14 to 21

Manual mechanical closing Circuit-breaker equipment Manual electrical closing Manual operating mechanism

Motor Operating mechanism ___ V DC ___ V AC, ___ Hz

Closing solenoid ___ V DC ___ V AC, ___ Hz

1st shunt release ___ V DC ___ V AC, ___ Hz

2nd shunt release ___ V DC ___ V AC, ___ Hz

Instantaneous release 60 V DC 110 V DC 220 V DC

Undervoltage release ___ V DC ___ V AC, ___ Hz

Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC

Low-voltage connection 24-pole 24-pole 64-pole terminal strip plug plug

Mechanical interlocking

Operating instructions English German French Spanish

Application and other requirements

Please check off ___ Please fi ll in

Page 39: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

You prefer to confi gure your 3AH47 traction circuit-breaker on your own?Please follow the steps for confi guration and enter the order number in the confi guration aid.

Instructions for confi guration of the 3AH47 traction circuit-breaker

1st step: Defi nition of the primary part (see page 13)

Please specify the following ratings: Possible options:

Rated voltage (Ur) Ur: 17.5 kV (16.7 Hz), 25 kV (25 Hz), 27.5 kV (50/60 Hz)

Rated lightning impulse withstand voltage (Up) Up: 125 kV, 170 kV, 185 kV, 200 kV, 250 kV

Rated short-duration power-frequency withstand voltage (Ud) Ud: 50 kV, 70 kV, 85 kV, 95 kV, 105 kV

Rated short-circuit breaking current (Isc) Isc: 25 kA, 31,5 kA, 40 kA, 50 kA

Rated normal current (Ir) Ir: 1250 A, 2000 A, 2500 A

Number of poles Single-pole, two-pole

These ratings defi ne the positions 6 to 8 of the order number.

2nd step: Defi nition of the secondary equipment (see pages 14 to 21)

Please specify the following equipment features: Possible options:

Release combination(position 9)

Shunt release, instantaneous releaseand undervoltage release

Closing solenoid(position 10)

Operating voltages from 24 V DC to 240 V AC

Operating voltage of the releases (positions 11 / 12/13)

Operating voltages from 24 V DC to 240 V AC

Type of local closing(position 10)

Mechanical closing,manual electrical closing

Type of operatingmechanism and operating voltage of amotor, if available (position 14)

Manual operating stored-energy mechanism, motor operating stored-energymechanism with operating voltages from 24 V DC to 240 V AC

Number of auxiliary contacts(position 15)

6 NO + 6 NC, 12 NO + 12 NC

Design of the secondary connection(position 15)

24-pole terminal strip, 24-pole plug connector,64-pole plug connector

Language of the documentation(position 15)

English, German, French, Spanish, other languages on request

Frequency of the operating voltage of the secondary equipment at AC(position 16)

50 Hz/60 Hz

These equipment features defi ne the positions 9 to 16 of the order number.

3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 22)

Should you still need more options than the possible special equipment like halogen-free andfl ame-retardant or silicone-free version, condensation protection or an additional rating plate, etc.,please contact your responsible sales partner.

Siemens HG 11.52 · 2012 39

Page 40: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

For confi guration of your3AH47 vacuum circuit-breaker

1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16

3 A H 4 7 – – – Z

See

pag

e 1

3

See

pag

e 1

3

See

pag

e 1

3

See

pag

e 1

4

See

pag

e 1

5

See

pag

e 1

6

See

pag

e 1

7

See

pag

e 1

8

See

pag

e 1

9

See

pag

e 2

0

See

pag

e 2

1

See

pag

e 2

2

3 A H 4 7 – –

+ + + +

+ + + +

3 A H 4 7 – –

+ + + +

+ + + +

3 A H 4 7 – –

+ + + +

+ + + +

3 A H 4 7 – –

+ + + +

+ + + +

3 A H 4 7 – –

+ + + +

+ + + +

3 A H 4 7 – –

+ + + +

+ + + +

3 A H 4 7 – –

+ + + +

+ + + +

3 A H 4 7 – –

+ + + +

+ + + +

Page 41: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...
Page 42: 3AH47 … · 3AH47 Vacuum Circuit-Breakers for Traction Applications ... The vacuum circuit-breaker series 3AH47 offers ... ambient air temperature of + 40 °C and apply to open ...

For more information,

please contact our

Customer Support Center.

Phone: +49 180 524 84 37

Fax: +49 180 524 24 71

(Charges depending on provider)

E-mail: [email protected]

Order No. E50001-K1511-A521-A3-7600

Printed in Germany

KG 09.12 0.0 44 En

7400 / 43852

Printed on elementary chlorine-free bleached paper.

Published by and copyright © 2012:

Siemens AG

Infrastructure & Cities Sector

Wittelsbacherplatz 2

80333 Munich, Germany

Siemens AG

Infrastructure & Cities Sector

Low and Medium Voltage Division

Nonnendammallee 104

13629 Berlin, Germany

www.siemens.com

All rights reserved.

If not stated otherwise on the individual pages

of this catalog, we reserve the right to include

modifications, especially regarding the

stated values, dimensions and weights.

Drawings are not binding.

All product designations used are trademarks or

product names of Siemens AG or other suppliers.

If not stated otherwise, all dimensions in this

catalog are given in mm.

Subject to change without prior notice.

The information in this document contains

general descriptions of the technical options

available, which may not apply in all cases.

The required technical options should

therefore be specified in the contract.