Fixed, middle rolling and floor rolling ranges of circuit breaker and disconnector
Make the most of your energySM
36 kV Medium Voltage Vacuum circuit breaker
HVX SeriesCatalogue | 2015Medium Voltage Distribution
HVX series
NRJED314609EN 1
Contents
General overview 5
HVX Range 13
Complementary devices 33
Order form 39
HVX series
NRJED314609EN2
Your requirements
Ease of use
Reliability
Safety
NRJED314609EN 3
Our solution Ease of use
• Modular design can adapt to requirements• Compact, simple installation facilitates
integration• Straightforward operation • Environmentally friendly with no harmful gas
or oil released into the environment
Reliability• Robust and field proven technology• Limited maintenance• Extremely resistant to severe environments
due to its embedded pole construction• Excellent mechanical performance
Safety• Conformity with main standards• Fully tested equipment• Highly visible mechanical indicators• No hazardous tripping• Comprehensive Interlocks
General oveview
NRJED314609EN 5
General overviewHVX series
Application 6
Standards and certifications 7
Operating conditions 7
Presentation 8
NRJED314609EN6
PE
6050
2
HVX series
The result of a sustained development effort for application in air-insulated switchgear unitsThe HVX series vacuum circuit breaker is the technical result of SchneiderElectric’s one hundred years, experience in the medium-voltage field.The HVX series offers a proven state-of-the-art design to meet your specifications for power switching devices in air-insulated switchgear.
b a fixed, frontal version b a withdrawable, frontal version with a circuit breaker and its cradle or its cassette b a fixed version equipped with an integrated protection system b accessories supplied separately.
The HVX series circuit breaker is operated via a spring mechanism that provides an operating speed independent of the operator and that does not require an auxiliary power supply.When the operating mechanism is motorised the circuit breaker can include telecontrol functions and carry out rapid reclosing cycles.The circuit breaker versions are easy to integrate in a cubicle environment.An Installation Guide details the required procedure.
ApplicationsThe HVX series is our latest range of vacuum circuit breakers, which are mainly integrated in MV switchgear. The HVX series comprises core components of MV switchgear for panel builders, which are used to protect overhead cables, cables, motors, transformers or generators. The HVX series is suitable for mainstream air-insulated switching devices and is widely used in the Oil & Gas, Power distribution system, Transportation, Industry and Mining & Metal segaments.
Application
IndustryPower distribution
Mining & Metal
Oil & Gas
PE
5657
9
PE
5825
2
PE
5825
3
NRJED314609EN 7
Certified quality in accordance withISO 9001 and ISO 9002
Operating conditionsThe normal range of operating conditions for HVX circuit breakers is in line withIEC62271-100, IEC62271-1. Please consult the manufacturer for any requirement beyond the normal range of operating conditions.
Operating conditionsTemperature grade Optional:
-5°C indoor -25°C indoor
Minimum/maximum ambient temperature -5°/40°C
Average value over 24 hours (max) 35°C
Altitude above sea level 1000 m
(For installation at higher altitudes, please consult us.)
HVX series Standards and certifications& Operating conditions
StandardsHVX series vacuum circuit breakers conform to the following standards:IEC 62271-100, IEC 62271-1.
Quality & EnvironmentQuality production management The vacuum interrupter manufacturing units are certified ISO 9001, and employ a mature and robust Quality Management System (QMS).
Protection of the environmentSchneider Electric is committed to a long-term environmental approach. All necessary measures have been taken in connection with our services, suppliers and subcontractors to ensure that the materials used in the composition of the equipment do not contain any substances prohibited by regulations and directives.In order to help you protect the environment and relieve you of any concerns in terms of storage or dismantling, Schneider Electric Services offers to take back your equipment at the end of its life.
NRJED314609EN8
Tensioning the spring
Spring drum
Main shaft
Drive casing
Vacuum interrupter chamber
Vacuum interrupter chamber
Drive casing
Opening Closing
PM
1042
00HVX series Presentation
Operating mechanismThe operating mechanisms have been simplified to increase reliability and give extended life with very low maintenance.Instead of the traditional spring operating mechanism, the HVX series incorporates a single-shaft system and only one torsion spring, reducing the number of parts and increasing reliability.The cam output from three independent phases is ideal for the vacuum switch.The transmission mechanism's one-step output and the special axletree design provides optimum transmission efficiency to ensure energy saving and a stable, reliable mechanism.
Operating principleEnergy is stored in the spiral spring by means of the electric motor or manual crank. Opening and closing of the vacuum interrupter is controlled by the cam; upon closing, the spring automatically restores the energy for an integrated automatic on/off operating cycle.An on/off storage mechanism, with its special mechanism, can absorb the excess energy of the drive mechanism through a quick on/off operation.The operating mechanism has electric and manual charging devices. The relevant interlock prevents manipulation errors after energy storage.
Drive spring-charging mechanism using a crank
The HVX series is designed as a modular system, allowing it to be interchanged with similar products. The HVX series is available in a range of standard, fixed or withdrawable configurations, with plug-in or bolted connections.
The values below are given for normal operating conditions according to IEC62271-100, IEC62271-1.
Technical characteristicsRated voltage Ur (kV) 36
Rated lightning impulse withstand voltage Up (kV peak) 170
Rated short-time power-frequency voltage (kV) 70
Rated short-circuit making current (kA) 6380
Rated short-circuit breaking current (kA) 2531.5
Rated current(1) (A) 1,250-3,150
(1) When the rated current is 3150 A, force cooling is required.
DM
1033
91
DM
1033
92
NRJED314609EN 9
OFF button (rocker “O”) or push button “O” to switch circuit breaker OFF (open)
ON button (rocker “I”) or push button “I” to switch circuit breaker ON (close)
Rating plate
Operation counter
Circuit breaker position indicator
Closing spring position indicator
Insertion opening for charging the closing spring
HVX series Presentation
Vacuum interrupterThe Schneider Electric VG vacuum interrupter series achieves a truly optimal design, thanks to the latest computer modeling tools. With the most advanced one-stop sealing technology, the VG series minimizes artificial pollution during production.Based on our patent design and comprehensive knowledge of vacuum interrupter technology, Schneider Electric's vacuum interrupter is a standout in the medium-voltage field with its high reliability, small size and long service life.
Embedded-pole constructionThe embedded pole is another of Schneider Electric's contributions to medium voltage products, with its 10 years-plus experience in design and manufacture, and it has been tried and tested in the field for many years. Employing the embedding technology, it completely integrates the vacuum interrupter, the main circuit and the insulated shaft in an epoxy pole to totally isolate the main circuit from the outside. This gives the pole optimum environmental adaptability, since the circuit breaker can function normally under harsh conditions.
InterfaceFront face Compact and user-friendly design of the front face, integrating all important indications and statuses for clear understanding.
PM
1042
04
DM
1033
93
NRJED314609EN10
HVX series Presentation
TestIn compliance with the present standards of vacuum circuit breaker performance, HVX has been demonstrated through a series of R&D timing and type tests. These tests have been performed in the manufacturer’s own laboratory and authoritative institutions such as KEMA. The test content not only includes the general type test items but also covers different special requirements, for example, generator protection, capacitor bank switching, breaking of hyper-standards and short-circuit making current, very long electrical and mechanical endurance, etc.
Floor rolling designIn addition to the middle rolling, the floor rolling design is also available if preferred. It provides the necessary robust interlock suitable for your operational requirements, and can surely fulfil all your possible needs and ensure a high level of quality.
CradleWe can provide cradles for various kinds of cabinets, and can prepare bus grounding switches according to your specific requirements, which are suitable for various electrical performance and installation requirements.
Middle rolling designThe robust design of the middle rolling truck provides you with a reliable interlock with panels, and flexible racking-in and racking-out operations. The mechanical and electrical design effectively avoids handling errors.
DM
1033
95D
M10
3396
DM
1033
94
NRJED314609EN 11
UTX Disconnector truckThis device can be used to disconnect the upstream and downstream circuits in the cubicle. It is installed in the same location as the withdrawable circuit breaker in the cradle.It includes a device for locking it in the in-service position.
HVX series Presentation
Relationship between the permitted operating times of vacuum interrupter and breaking current applicationsThe following graph explains the relationship between the permitted VG operating times and breaking current.
Applications
b Rated short-circuit breaking current and non-full loaded current b Breaking of asymmetrical current b Automatic re-closing b Connection to no-load cables and overhead lines b Out-of-phase breaking b Connection to no-load transformer b Double earthing fault current breaking b Breaker transient recovery voltage gradient triggering significant
short-circuit current b Switching motors and inductance in a vacuum
MTX Voltage transformer truckMTX trolleys suitable for various kinds of voltage transformers, enabling you to configure the middle rolling chassis or floor rolling chassis according to the installation requirements.
DM
1033
98
DM
1033
99D
M10
3400
HVX Range
NRJED314609EN 13
HVX RangeHVX series
Overview 14
HVX series Vacuum circuit breaker Selection guide 16Dimensions HVX 36 kV series fixed type 17HVX 36 kV series middle rolling type 18HVX 36 kV series Floor rolling type 19Cradle - For HVX 36 kV series middle rolling type 20Electrical circuit diagram HVX 36 kV vacuum circuit breaker, fixed type with anti-pumping relay 21HVX 36 kV vacuum circuit breaker, withdrawable type with anti-pumping relay 22
UTX Disconnector truck Selection guide 23Dimensions UTX 36 kV middle rolling type 24UTX 36 kV floor rolling type 25Cradle - For UTX 36 kV series middle rolling type 26
MTX Voltage transformer truck Selection guide 27Dimensions MTX 36 kV middle rolling type 28MTX 36 kV floor rolling type 29Cradle - For MTX 36 kV series middle rolling type 30
NRJED314609EN14
OverviewHVX series
HVX series design type Fixed Middle rolling Floor rolling
Type Fixed type Middle rolling type Floor rolling typeRated voltage 36 kV 36 kV 36 kV
Rated short-circuit current Up to 31.5 kA Up to 31.5 kA Up to 31.5 kA
Rated current(1) Up to 3150 A Up to 3150 A Up to 3150 A
Benefits
Fixed Vacuum Circuit Breaker.Embedded pole for better dielectric and environmental pollution withstand.
Middle rolling Vacuum Circuit Breaker.Embedded pole for better dielectric and environmental pollution withstand.
Floor rolling Vacuum Circuit Breaker.Embedded pole for better dielectric and environmental pollution withstand.
(1) When the rated current is 3150 A, force cooling is required.
UTX design type Middle rolling Floor rolling
Type Middle rolling type Floor rolling typeRated voltage 36 kV 36 kV
Rated short-circuit current Up to 31.5 kA Up to 31.5 kA
Rated current(1) Up to 3150 A Up to 3150 A
Benefits
Middle rolling Disconnector Truck.Embedded pole for better dielectric and environmental pollution withstand.
Floor rolling Disconnector Truck.Embedded pole for better dielectric and environmental pollution withstand.
(1) When the rated current is 3150 A, force cooling is required.
DM
1033
94
DM
1033
95
DM
1034
01D
M10
3399
DM
1034
02
NRJED314609EN 15
OverviewHVX series
MTX Design type Middle rolling Floor rolling
Type Middle rolling type Floor rolling typeRated voltage 36 kV 36 kV
Power frequency withstand voltage Up to 70 kV Up to 70 kV
Lightning impulse withstand voltage Up to 170 kV Up to 170 kV
BenefitsMiddle rolling voltage transformer truck, suitable for various installation requirements.
Floor rolling voltage transformer truck, suitable for various installation requirements.
DM
1034
00
DM
1034
03
NRJED314609EN16
Selection guideHVX series Vacuum circuit breaker
Type
HVX
36-
25-1
2
HVX
36-
25-1
6
HVX
36-
25-2
0
HVX
36-
25-2
5
HVX
36-
25-3
1(1)
HVX
36-
31-1
2
HVX
36-
31-1
6
HVX
36-
31-2
0
HVX
36-
31-2
5
HVX
36-
31-3
1(1)
Phase distance mm 275/300
Rated voltage kV 36
Rated insulation level
Power frequency withstand voltage kV 70
Lightning impulse withstand voltage kV 170
Rated frequency Hz 50/60
Rated current A 1250 1600 2000 2500 3150(1) 1250 1600 2000 2500 3150(1)
Rated peak current withstand current (50/60 Hz) kA 63 80
Rated short time withstand current (4 s) kA 25 31.5
Rated short-circuit breaking current
Rated short-circuit breaking current kA 25 31.5
Direct current component percentage % 36
No-load cable breaking current A 50
Rated operation sequence
0-0.3 s-CO-180 s-CO b
0-180 s-CO-180 s-CO b
Switch operating cycles (electrical/mechanical)
Drive mechanism operations Per numbers 10,000
Vacuum interrupter operations Per numbers 30,000
Rated current operations Per numbers 10,000
Minimum/Maximum closing time ms 40/63
Minimum/Maximum opening time ms 35/53
Contact eroding bedding mm 3.5
Charging time s 4~12
Arc time ms 2~15
Weight(2)
Fixed kg 280
Middle rolling kg 375
Floor rolling kg 415
(1) When the rated current is 3150 A, forced cooling is required.(2) The net weight of the product is for reference only.For special requirements, please consult us.
HVX 36 kV vacuum circuit breaker
HVX 36 - 31 - 12 - E
HVX type F: Fixed typeE: Middle rolling typeG: Floor rolling type
Rated voltage kV
Rated short-circuit breaking current kA
Rated current (x100 A)
DM
1033
94
NRJED314609EN 17
Dimensions HVX 36 kV series fixed type
HVX series Vacuum circuit breaker
36 kV, ...2500/3150(1), ...31.5 kA
P (mm) D (mm) E (mm) H (mm)
275 800 850 400
275 800 850 400
300 850 900 325
300 850 900 400
(1) When the rated current is 3150 A, forced cooling is required.
DM
1034
04
NRJED314609EN18
1
2
Rated current (A) 1250 1600 2000 2500 3150(1)
ØM mm 88 118 118 148 148
ØW mm 49 79 79 109 109
(1) When the rated current is 3150 A, forced cooling is required.For special requirements, please consult us.
Dimensions HVX 36 kV series middle rolling type
HVX series Vacuum circuit breaker
1 This connecting arm is used for 2500 A.2 This connecting arm is used for <2000 A.
DM
1034
05
NRJED314609EN 19
1
2
Dimensions HVX 36 kV series floor rolling type
HVX series Vacuum circuit breaker
Rated current (A) 1250 1600 2000 2500 3150(1)
ØM mm 88 118 118 148 148
ØW mm 49 79 79 109 109
(1) When the rated current is 3150 A, forced cooling is required.For special requirements, please consult us.
1 This connecting arm is used for 2500 A.2 This connecting arm is used for <1250 A.
DM
1034
06
NRJED314609EN20
1200
L
1333
367.
536
7.5
1097
1137
1765
647
491
460
275 275
1325
120
325
10
1
Dimensions Cradle - For HVX 36 kV series middle rolling type
HVX series Vacuum circuit breaker
Rated working current (A)
Rated short-circuit breaking current (kA)
Dimensions(mm)L Contacts
1250 25...31.5 2400 Ø49 x 120
2000 31.5 2490 Ø79 x 102
2500 31.5 2490 Ø109 x 102
1 The earthing switch is optional.
DM
1034
07
NRJED314609EN 21
-Q0
-Q0
OI
9 10
-S12
1 2
3 4 16
21
22
611
38
28
12
11
24
13
14
34
1 2 U1
U2
-M1
M
4 3 35
25
36
26
-S2
65
D1
D2
-F4
U< 4
4
43
C1
C2
-F3
I>
42
32
9 10
-S2
C1
C2
-F2
14
4 21
22
31
32
13
14
-S12
87 A2-K
01
A1
truck
3 4
-S11
C1
C2
-F12
2313
1 2
-S11
C1
C2
-F11
30
31
41
13
14
-S11
5 6
15
16
7 8 17
19
15
-X01
18
9-X
01
87
51
40
12
15
16
-S2
9 10
-S11
E1
E2
-Y1
20
13
14
-S12
11
12
-S11
5 6
39
16
15
29
10
-S61
41 1 2
-S6 -+
04
1
1
Electrical circuit diagramHVX 36 kV vacuum circuit breaker, fixed type with anti-pumping relay
HVX series Vacuum circuit breaker
1. T
his
circ
uit d
iagr
am s
how
s th
e m
axim
um s
witc
hgea
r equ
ipm
ent.
The
stan
dard
eq
uipm
ent d
oesn
't in
clud
e op
tiona
l ite
ms.
If th
e cu
stom
er re
quire
s op
tiona
l ite
ms,
pl
ease
sta
te th
is w
hen
plac
ing
the
orde
r.2.
Circ
uit b
reak
er is
dis
char
ged
and
in o
pen
posi
tion,
trol
ley
is in
ser
vice
pos
ition
.
3. If
Circ
uit b
reak
er w
ithou
t blo
ckin
g m
agne
t for
clo
sing
Y1,
circ
uit d
iagr
am
acco
rdin
g to
das
h s
how
n.
-Q0
Uni
ts in
corp
orat
ed in
the
circ
uit b
reak
er in
com
plia
nce
with
ord
er
-M1
Mot
or fo
r ene
rgy
stor
ing
devi
ce-S
11/1
2
Aux
iliar
y sw
itch
posi
tion
indi
cato
r
-S2
Mic
ro-s
witc
h fo
r mot
or c
ontro
l -S
6 M
icro
-sw
itch
for b
lock
ing
mag
net
-Y1
Blo
ckin
g m
agne
t for
clo
sing
(opt
iona
l)-F
11
1. A
uxili
ary
open
ing
rele
ase
-F12
2.
Aux
iliar
y op
enin
g re
leas
e (o
ptio
nal)
-F2
Aux
iliar
y cl
osin
g re
leas
e
-F3
Indi
rect
ove
r-cu
rren
t rel
ease
(opt
iona
l) -F
4 U
nder
-vol
tage
rele
ase
(opt
iona
l) -K
01
Ant
i-pum
ping
-rel
ay-S
61
Mic
ro-s
witc
h ac
tuat
ed b
y op
erat
ion
DM
1034
08
NRJED314609EN22
-S11
10
9-Q
0
-Q0
9 10
-S12
1 2
11 12
D4
B4
B3
D3
B2
A8
A7
13
14
-S2
65
B16
B15
B8
3 4B7
D6
5 6D5
D16
D15
1 2 U1
U2
-M1
M
4 3 A2
A1
11 12
9 10
-S2
C1
C2
-F2
A6
A5
21
22
-S61
41
13
14
-S12
87 A2-K
01
A1
truck
13
14
-S11
5 6
15
16
7 8 B1
A16
A14
-X01
A13
A15
-X01
A12
1 2
-S11
C1
C2
-F11
A4
A3
D11
11 12
A9
D1
B9
15
16
B10
13
14
S8
13
14
13
14
23
24
33
34
C6
X01
C3
D14
C10
6
14
13
S9
16
24
23
15
53
-Q1
14
2
D13
53
54
43
44
C13
C14
12
13
34
33
14
44
43
11
8
-Y0
17
54
53
18
97
B5
B6
B13
B14
C8
C5
X01
B12
C12
C11
A11
E1
E2
-Y1
13
14
-S12
C9
B11
31
32
C2
C1
C2
-F12
3 4
-S11
D10
C1
1 2
-S6
OI
C15
C16
C4
C7
3 4
-S42
1 2
-S41
C1
C2
-F3
I>
C1
C2
-F4 U
<
D2
D7
D8
D9
15
16
-S2
1 2
-S43 -+
test
po
sitio
n
se
rvic
e
po
sitio
n
02
Electrical circuit diagramHVX 36 kV vacuum circuit breaker, withdrawable type with anti-pumping relay
HVX series Vacuum circuit breaker
1. T
his
circ
uit d
iagr
am s
how
s th
e m
axim
um s
witc
hgea
r equ
ipm
ent.
The
stan
dard
eq
uipm
ent d
oesn
't in
clud
e op
tiona
l ite
ms.
If th
e cu
stom
er re
quire
s op
tiona
l ite
ms,
pl
ease
sta
te th
is w
hen
plac
ing
the
orde
r.2.
Circ
uit b
reak
er is
dis
char
ged
and
in o
pen
posi
tion,
trol
ley
is in
ser
vice
pos
ition
, bl
ocki
ng m
agne
t for
clo
sing
is d
e-en
ergi
sed.
-Q0
Uni
ts in
corp
orat
ed in
the
circ
uit b
reak
er in
com
plia
nce
with
ord
er-M
1 M
otor
for e
nerg
y st
orin
g de
vice
-S
11/1
2 A
uxili
ary
switc
h po
sitio
n in
dica
tor
-S2
Mic
ro-s
witc
h fo
r mot
or c
ontro
l-S
41/4
2 M
icro
-sw
itch
actu
ated
by
push
but
ton
On/
off (
optio
nal)
-S43
M
icro
-sw
itch
actu
ated
by
brea
k bu
tton
(opt
iona
l)-S
6 M
icro
-sw
itch
for b
lock
ing
mag
net
-Y1
Blo
ckin
g m
agne
t for
clo
sing
(opt
iona
l)-F
11
1. A
uxili
ary
open
ing
rele
ase
-F12
2.
Aux
iliar
y op
enin
g re
leas
e (o
ptio
nal)
-F3
Indi
rect
ove
r-cu
rren
t rel
ease
(opt
iona
l)-F
4 U
nder
-vol
tage
rele
ase
(opt
iona
l) -S
61
Mic
ro-s
witc
h ac
tuat
ed b
y tru
ck o
pera
tion
or tr
uck
not i
n en
d po
sitio
n-F
2
Aux
iliar
y cl
osin
g re
leas
e-K
01
Ant
i-pum
ping
-rel
ay-Q
1 U
nits
inco
rpor
ated
in th
e sw
itchg
ear t
ruck
in
com
plia
nce
with
ord
er-S
8 Te
st p
ositi
on s
witc
h -S
9 S
ervi
ce p
ositi
on s
witc
h-Y
0 B
lock
ing
mag
net b
lock
ing
for t
rolle
y (o
ptio
nal)
DM
1034
09
NRJED314609EN 23
Selection guideUTX Disconnector truck
Type
UTX
36-
25-1
2
UTX
36-
25-1
6
UTX
36-
25-2
0
UTX
36-
25-2
5
UTX
36-
25-3
1(1)
UTX
36-
31-1
2
UTX
36-
31-1
6
UTX
36-
31-2
0
UTX
36-
31-2
5
HVX
36-
31-3
1(1)
Phase distance mm 275
Rated voltage kV 36
Rated insulation level
Power frequency withstand voltage kV 70
Lightning impulse withstand voltage kV 170
Rated frequency Hz 50/60
Rated curent A 1250 1600 2000 2500 3150(1) 1250 1600 2000 2500 3150(1)
Rated short-circuit breaking current kA 25 31.5
Weight(2)
Middle rolling kg 255 260 280 290 310 255 260 280 290 310
Floor rolling kg 320 325 345 355 385 320 325 345 355 385
(1) When the rated current is 3150 A, forced cooling is required.(2) The net weight of the product is for reference only.For special requirements, please consult us.
UTX 36 kV disconnector truck
UTX 36 - 31 - 12 - E
UTX type E: Middle rolling typeG: Floor rolling typeRated voltage (kV)
Rated short-circuit breaking current
Rated current (x100 A)
DM
1033
99
NRJED314609EN24
1044
106013.5 13.5
1051
952.
5
410555
440
275 275
1025
.5
780
325
520
ØM
410 356Ø
W
1
2
Dimensions UTX 36 kV middle rolling type
UTX Disconnector truck
Rated current (A) 1250 1600 2000 2500 3150(1)
ØM mm 88 118 118 148 148
ØW mm 49 79 79 109 109
(1) When the rated current is 3150 A, forced cooling is required.For special requirements, please consult us.
1 This connecting arm is used for 2500 A.2 This connecting arm is used for <1250 A.
DM
1034
10
NRJED314609EN 25
750
1051275 275
966
1060
1044
13.5 13.5
507410 356.5
440
1571
620
410
780
325
520
760.5
ØM
ØW
1
2
Dimensions UTX 36 kV floor rolling type
UTX Disconnector truck
Rated current (A) 1250 1600 2000 2500 3150(1)
ØM mm 88 118 118 148 148
ØW mm 49 79 79 109 109
(1) When the rated current is 3150 A, forced cooling is required.For special requirements, please consult us.
1 This connecting arm is used for 2500 A.2 This connecting arm is used for <1250 A.
DM
1034
11
NRJED314609EN26
1200
L
1333
367.
536
7.5
1097
1137
1765
647
491
460
Ø13
275 275
1325
L44X120
M12,1250AM21,2000A
120
325
10
1
Dimensions Cradle - For UTX 36 kV series middle rolling type
UTX Disconnector truck
Rated working current(A)
Rated short-circuit breaking current (kA)
Dimensions(mm)L Contacts
1250 25...31.5 2400 Ø49 x 120
2000 31.5 2490 Ø79 x 102
2500 31.5 2490 Ø109 x 102
1 The earthing switch is optional.
DM
1034
14
NRJED314609EN 27
Selection guideMTX Voltage transformer truck
Type Truck Phase distance(mm)
Rated voltage(kV)
Rated insulation level Rated frequency(Hz)
Weight(1)
(kg)Power frequency withstand voltage(kV)
Lightning impulse withstand voltage(kV)
MTX36-E275 Middle rollingtruck
275 36 95 185 50/60 390
MTX36-G275 Floor rollingtruck
275 36 95 185 50/60 455
(1) The net weight for product is for reference only.For special requests, please consult us.
MTX 36 kV Voltage transformer truck
MTX 36 - E - 275
Phase distance (mm)MTX type
Rated voltage (kV) E: Middle rolling typeG: Floor rolling type
DM
1034
00
NRJED314609EN28
1052275275
1060
1044
13.5 13.5
462
845
242
760.6
1025
.5
555
410
286.5 440
DimensionsMTX 36 kV middle rolling type
MTX Voltage transformer truck
DM
1034
15
NRJED314609EN 29
845
1052
940750
275275
966
1044
106013.5 13.5
802
1572
.5
555410
242760.5
440
DimensionsMTX 36 kV floor rolling type
MTX Voltage transformer truck
DM
1034
16
NRJED314609EN30
1200
2400
1333
367.
5
1097
1137
1765
647
491
460
Ø13
275 275
1325
L44X120
M12
122
162.
5
10
1
DimensionsCradle - For MTX 36 kV series middle rolling type
MTX Voltage transformer truck
1 The earthing switch is optional.
DM
1034
17
NRJED314609EN 31
NRJED314609EN32
Complementary devices
NRJED314609EN 33
Complementary devicesHVX seriesComplementary devices
HVX series Complementary devices 33
NRJED314609EN34
Complementary devicesHVX series
ReleaseAuxiliary release F2, F11/F12The auxiliary release coil is actuated by the auxiliary power supply. The coil is designed for short-term operation only; its main circuit is therefore routed via an auxiliary switch contact controlled by the circuit breaker shaft, and upon release it interrupts the current circuit.
Over-current release F3(Transformer-type over-current release) Over-current releases are used for automatic release of switching devices in the event of short-circuits and over-currents. Once the protection device reacts, the release is actuated by the transformer current, thus causing the switch to be tripped. These releases are supplied for transformer secondary currents of 0.5 A, 1 A and 5 A.
Under-voltage release F4Under-voltage releases are used for the auxiliary boost voltage return circuit.Whenever the auxiliary current is interrupted or its voltage drops significantly, the switching device is immediately tripped.
Auxiliary switchAuxiliary switch in switching position S11/S12Auxiliary switches are always actuated directly by the switch shaft via an intermediate linkage, the position of which always corresponds to the position of the main contacts, indicating the breaker's on and off position status; during wiring, the interlock assists the release to prevent handling errors. Generally speaking, the circuit breaker is equipped with two auxiliary switches with a total of eight contact elements.
Auxiliary switch in charging position S2The auxiliary switch is mainly used to check and indicate the charging status. It is connected by the charging mechanism to ensure that, during the closing operation, the driving mechanism can automatically store energy. When charging is complete, it breaks the electrical charging circuit. Generally speaking, the circuit breaker is equipped with an auxiliary switch with eight contact elements.
DM
1034
18
DM
1034
19D
M10
3420
DM
1034
21D
M10
3422
DM
1034
23
NRJED314609EN 35
Anti-pumping relay K01If both ON and OFF commands are permanently present on the circuit breaker at the same time, the latter returns to open position after closing; it remains in this open position until the ON command is issued again. This prevents continuous closing and opening (i.e. “anti-pumping”).
HVX series Complementary devices
Operation counterThe operation counter installed on the operating interface records the circuit breaker operating frequency.
Charging motor M1This electrically stores energy for the circuit breaker operating mechanism, preparing energy for the next closing operation.
Blocking magnetBlocking magnet for closing Y1If the secondary controlling power supply is lost, the circuit breaker cannot perform the normal closing operation (including manual closing).
Blocking magnet for trolley Y0If the secondary controlling power supply is lost, the trolley cannot perform the normal manual operation.
DM
1034
24D
M10
3425
DM
1034
26D
M10
3427
DM
1034
28
NRJED314609EN36
Devices Designation No. in configuration
Rated operating voltage Ua (V) Working voltage Ua (V)
Rated power(W)
Charging motor M1 1 DC 2448110220
85~110% Ua Approx. 100
AC 110220
Closing coil F2 DC 2448110220
85~110% Ua 180
AC 110220
85~110% Ua
Opening coil F11F12
DC 2448110220
70~110% Ua 180
AC 110220
85~110% Ua
Under-voltage release F4 1 DC 2448110220
35~0% Ua Approx. 12
AC 110220
Devices Designation No. in configuration Working voltage Ua (V) Rated powerOver-current release F3 2 0.5
15
90~110% Ua
Auxiliary switch technical parametersRated voltage ofauxiliary switch
Unit DC ACV ≤ 48 125 220 120 230
Breaking capacity A 10 3.8 2 10
Time constant T=L/R 10
Rated short-circuit withstand current 250 A/3 s
Rated current 15
Operating time of coil and motorDuration of the minimum opening command 20 ms
Duration of the minimum closing command 20 ms
Motor charging time 4~12 s
HVX series Complementary devicesD
M10
3426
DM
1034
19D
M10
3419
DM
1034
21D
M10
3420
NRJED314609EN 37
NRJED314609EN38
Order form
NRJED314609EN 39
Order formHVX 36 kV vacuum circuit breaker
HVX36Ordering unit: Project name: Customer's order number:
Basic configuration:
Product model Quantity
Installation method □ Fixed type (F type) □ Middle rolling type (E type) □ Floor rolling type (G type)
Rated voltage □ 36 kV
Rated current □ 1250 A □ 1600 A □ 2000 A □ 2500 A □ 3150 A
Rated short-circuit breaking current □ 25 kA □ 31.5 kA
Phase distance (P) □ 275 mm □ 300 mm
Charging motor (M1) □ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 110 VAC □ 220-230 VAC
Opening release (F11) □ 24 VDC □ 48-60 VDC □ 110-125 VDC □ 220 VDC □ 110-120 VAC □ 220-230 VAC
Closing release (F2) □ 24 VDC □ 48-60 VDC □ 110-125 VDC □ 220 VDC □ 110-120 VAC □ 220-230 VAC
Anti-pumping relay (K01) □ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 220 VDC □ 110-120 VAC □ 220-230 VAC
Auxiliary contact □ 8 NO+8 NC □ 12 NO+12 NC
Secondary wiring mode □ Installation of 58-pin low voltage plug, with slots
□ Installation of 64-pin low voltage plug, with slots
□ Other
Withdrawable type (E type, G type)
Trolley and earthing method
□ Middle rolling trolley with copper earthing bar (E type)
□ Floor rolling trolley with copper earthing bar (G type)
Optional configuration:
Secondary opening release (F12) □ 24 VDC □ 48-60 VDC □ 110-125 VDC □ 220 VDC □ 110-120 VAC □ 220-230 VAC □ Other
Over-current release (F3) □ 0.5 A □ 1 A □ 5 A
Secondary over-current release (F32)
□ 5 A
Under-voltage release (F4) □ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC
□ 100-110 VAC □ 230 VAC □ Other
Blocking magnet for closing circuit (Y1)
□ 24 VDC □ 30 VDC □ 48 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 230 VDC □ Other
□ 24 VAC □ 30 VAC □ 48 VAC □ 110 VAC □ 125 VAC □ 220 VAC □ 230 VAC □ Other
Manual C/O button micro-switch (S41-S43)
□ One control output and one signal output □ One control output and two signal outputs □ None
Withdrawable type (E type, G type)
Blocking magnet for trolley (Y0)
□ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 230 VDC
□ 24 VAC □ 48 VAC □ 60 VAC □ 110 VAC □ 125 VAC □ 220 VAC □ 230 VAC
Other special requirements 1
2
3
4
5
(If there are any other special requirements, please list them in the column and attach the corresponding drawing or attachment.)
Complete (signature/seal):
Notes: 1. This form is completed by the ordering unit. Please enter a “ √ ” in the selected item “□”. 2. Attachment configuration: Each circuit breaker is equipped with a secondary slot and a compatible secondary contact pin; the trolley crank
configuration is based on the project; that is, five circuit breakers in one project are equipped with a set of trolley cranks (fewer than five circuit breakers are equipped in the same way as projects with five circuit breakers). If additional requirements are expressed, the corresponding fees will be charged according to the price stated in the attachment.
3. The above "standards" refer to the standard plans in the samples; with regard to non-standard plans or specific concerns, please contact the Customer Care Centre hotline.
4. If the customer does not choose the optional configuration program, the circuit breaker configuration will not incorporate this component. However, if the customer chooses an optional configuration or other non-standard program, certain fees will be charged and the date of delivery will be extended appropriately. For the specific costs, please refer to our company's price list or consult our salesperson.
NRJED314609EN40
Order formUTX 36 kV disconnector truck
UTX36Ordering unit: Project name: Customer's order number:
Basic configuration:
Product model Quantity
Installation method □ Middle rolling type (E type) □ Floor rolling type (G type)
Rated voltage □ 36 kV
Rated current □ 1250 A □ 2500 A
Rated short time withstand current □ 25 kA □ 31.5 kA
Phase distance (P) □ 275 mm □ 300 mm
Secondary wiring mode □ Installation of 64-pin low voltage plug, with slots □ Other
Withdrawable type (E type, G type)
Trolley and earthing method
□ Middle rolling trolley with copper earthing bar (E type) □ Floor rolling trolley with copper earthing bar (G type)
Optional configuration:
Withdrawable type (E type, G type)
Blocking magnet for trolley
□ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 230 VDC □ 24 VAC
□ 48 VAC □ 60 VAC □ 110 VAC □ 125 VAC □ 220 VAC □ 230 VAC □ 230 VAC
Other special requirements 1
2
3
4
5
(If there are any other special requirements, please list them in the column and attach the corresponding drawing or attachment.)
Complete (signature/seal):
Notes: 1. This form is completed by the ordering unit. Please enter a “ √ ” in the selected item “□”. 2. The above "standards" refer to the standard plans in the samples; with regard to non-standard plans or specific concerns, please contact the
Customer Care Centre hotline. 3. If the customer does not choose the optional configuration program, the circuit breaker configuration will not incorporate this component. However, if
the customer chooses an optional configuration or other non-standard program, certain fees will be charged and the date of delivery will be extended appropriately. For the specific costs, please refer to our company's price list or consult our salesperson.
NRJED314609EN 41
Order formMTX 36 kV disconnector truck
Complete (signature/seal):
Notes: 1. This form is completed by the ordering unit. Please enter a “ √ ” in the selected item “□”. 2. The above "standards" refer to the standard plans in the samples; with regard to non-standard plans or specific concerns, please contact the
Customer Care Centre hotline. 3. If the customer does not choose the optional configuration program, the circuit breaker configuration will not incorporate this component. However, if
the customer chooses an optional configuration or other non-standard program, certain fees will be charged and the date of delivery will be extended appropriately. For the specific costs, please refer to our company's price list or consult our salesperson.
MTX36Ordering unit: Project name: Customer's order number:
Basic configuration:
Product model Quantity:
Installation method □ Middle rolling type (E type) □ Floor rolling type (G type)
Rated voltage □ 36 kV
Phase distance (P) □ 275 mm
Secondary wiring mode □ Installation of 64-pin low voltage plug, with slots □ Other
Withdrawable type (E type, G type)
Trolley and earthing method
□ Middle rolling trolley with contacts on both sides and VT earthing (E type)
□ Floor rolling trolley with contacts on both sides and VT earthing (G type)
Optional configuration:
Withdrawable type (E type, G type)
Blocking magnet for trolley
□ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 230 VDC □ 24 VAC
□ 48 VAC □ 60 VAC □ 110 VAC □ 125 VAC □ 220 VAC □ 230 VAC □ 230 VAC
Other special requirements 1
2
3
4
5
(If there are any other special requirments, please list them in the column and attch the corresponding drawing or attachment.)
Make the most of your energy™
www.schneider-electric.com
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
This document has been printed on ecological paper.