33kv Ct Calculations

download 33kv Ct Calculations

of 31

Transcript of 33kv Ct Calculations

  • 7/25/2019 33kv Ct Calculations

    1/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 2 of32Rev A

    Document Title : CT/VT calculations for 33kV Switchgear forADWEA contract no G1408

    TABLE OF CONTENTS

    SECTION TITLE PAGE NO

    1.0 OBJECTIVE......................................................................................................3

    2.0 REFERENCES..................................................................................................3

    3.0 SCOPE..............................................................................................................3

    4.0 CT SIZING CALCULATIONS............................................................................34.1 33kV Cable Feeder........................................................................................................... 34.1.1 CT's for Metering .............................................................................................................. 34.1.2 CT's for Pilot wire protection ............................................................................................. 44.1.3 CT's for Busbar protection................................................................................................. 44.1.4 CT's for Overcurrent and Earth fault protection ................................................................ 64.2 33/11.55kV,15& 20MVA Transformer Feeder................................................................ 84.2.1 CT's for Metering .............................................................................................................. 84.2.2 CT's for Differential protection......................................................................................... 104.2.3 CT's for Overcurrent and Earth fault protection .............................................................. 154.2.4 CT's for Busbar protection............................................................................................... 204.3 33kV Bus sect ion Feeder.............................................................................................. 20

    4.3.1 CT's for Metering ............................................................................................................ 204.3.2 CT's for Overcurrent and Earth fault protection .............................................................. 214.3.3 CT's for Busbar protection............................................................................................... 224.4 33kV Over head l ine(OHL) Feeder............................................................................... 224.4.1 CT's for Metering ............................................................................................................ 224.4.2 CT's for Distance protection............................................................................................ 234.4.3 CT's for Overcurrent and Earth fault protection .............................................................. 274.4.4 CT's for Busbar protection............................................................................................... 294.4.5 CT's for Sensitive Earth Fault protection......................................................................... 29

    5.0 VT SIZING CALCULATIONS.......................................................................... 31

    6.0 Conclusion ..................................................................................................... 32

    7.0 Summary Of Current Transformers (Annexure 1)......32

    8.0 Summary Of Voltage Transformers(Annexure 2) .......................................... 32

    NOTE:

    The catalogues of all the relays and cables are enclosed vide DTS no. 0012 dated15.11.2003 and DTS no. 0015 dated 23.11.2003.

  • 7/25/2019 33kv Ct Calculations

    2/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 3 of32Rev A

    Document Title : CT calculations for 33kV Switchgear for ADWEAcont ract no G1408

    1.0 OBJECTIVE

    To establish current transformer(CT) and Voltage transformer(VT) parameters at 33kV level for all the 5 new substations.

    2.0 REFERENCES

    a) Bay control unit REF542 Plus catalogue

    b) 33kV switchgear vendor (ABB Calor Emag) Single line diagram

    c) Ducab cable catalogue

    d) ESI standard 48-3 and Clients/Consultant Recommendations

    e) Relay catalogues Recommendations

    3.0 SCOPE

    To establish the requirements of CT/VT parameters such as CT/VT ratio, VA burden,knee point voltage, accuracy class and magnetising current for CTs on the 33 kVswitchgear at all the sub-stations.

    4.0 CT SIZING CALCULATIONS

    4.1 33kV Cable Feeder

    4.1.1 CTs for Metering

    CT Ratio:

    600-1200/1A.

    Type of Metering:

    Metering Through Bay Control Unit (BCU) typeREF542 Plus

    Burden of bay control unit = 0.1 VA (Refer REF542 Plus catalogue)

    The BCU is mounted on the 33kV switchgear.

    Minimum length of cable = 5 metersbetween CT and BCU

    Size of cable = 2.5 sqmm

    Resistance of cable per = 7.41 Ohms (Refer Ducab cable catalogue)km at 20 deg C

    Resistance of cable at = 7.41(1+0.00393 (55-20) )55 deg C, consideringtemperature correction factor

    = 8.429 ohm/km

    Total resistance = 2 x 8.429 x 5 / 1000

  • 7/25/2019 33kv Ct Calculations

    3/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 4 of32Rev A

    (Lead & Return conductors) = 0.08429

    Burden due to lead resistance = Total resistance x (CT secondary current)2

    = 0.08429 x 12

    = 0.08429 VA

    Total burden = Total burden of the BCU + Burden due to leadresistance

    = 0.1 + 0.08429

    = 0.18429 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.18429 = 0.23 VA

    Hence a standard burden rating of minimum 15 VA is chosen.

    The CT Accuracy Class selected is CL. 0.5 as per the specification requirements.

    The instrument security factor (ISF) selected is less than Five (5) as per thespecification requirements.

    Abstract:

    Therefore a CT of CL. 0.5,15VA is proposed for 600-1200/1A and CL. 0.5,30VA isproposed for 600-1200/1A.The CTs are with a factor of safety less than or equal to 5.

    The same is as per the specification.

    4.1.2 CTs for Pilot Wire Protection:

    The current transformer details for all the incoming cable feeders from differentsubstations are proposed to match with the remote end CT data.

    The calculation for pilot wire protection will be included in this document afterfinalization of remote end CT details.

    4.1.3 CTs for Bus Bar Protection:

    CT Ratio:

    2000/1 A

    Type of relay: REB 500 ( ABB make)

    Fault current rating of 33kV switchgear = 31.5kA

    This relay is mounted on 33kV busbar protection panel which is located in control

    room.Burden of relay = 0.1VA(Refer relay catalogue)

    Minimum length of cable = 30 metersbetween CT and relay

    Size of cable = 4 sqmm

    Resistance of cable per = 4.61 Ohms (Refer Ducab cable catalogue)km/phase at 20 deg C

    Resistance of cable at = 4.61(1+0.00393 (55-20) )55 deg C, considering

    temperature correction factor= 5.244ohm/km

  • 7/25/2019 33kv Ct Calculations

    4/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 5 of32Rev A

    Total resistance = 2 x 5.244 x 30 / 1000

    (Lead & Return conductors) = 0.314

    Burden due to lead resistance = Total resistance x (CT secondary current)2

    = 0.314 x 12

    = 0.314 VA

    Total burden = Burden of the relay + Burden due to leadresistance

    = 0.1 + 0.314 = 0.414 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.614 = 0.5175 VA

    Hence a standard burden rating of 15 VA is chosen.

    The CT Accuracy Class selected is CL. 5P20 as per the relay requirements.

    Therefore a CT of 2000/1A, CL. 5P20, 15VA is proposed.

    To ensure correct operation of the connected relay in case of faults, the CT must beable to transform the maximum symmetrical short circuit current without saturation.

    To satisfy the above, following condition to be checked:

    Koalf Iscc/ Ipn

    Where, Ipn = CT primary nominal current = 2000A

    Iscc = max. symmetrical short circuit current= 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limiting

    factor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the totalconnected burden (Pb).

    Pn+ Pi Koalf = Knalfx

    Pb+ Pi

    Where,

    Pn = Nominal CT burden = 15 VA

    Knalf = 20

    Pi = Internal CT burden

    = V * I= (I * Rct) * I

    = I2* Rct

    Rct = 9 Ohm (as per manufacturers recommendations)

    = 12x 9

    = 9 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314= 0.414 VA

  • 7/25/2019 33kv Ct Calculations

    5/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 6 of32Rev A

    15 + 9

    Koalf = 20 x0.414 + 9

    = 51

    Iscc/ Ipn = 31500 / 2000

    = 15.75

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 2000/1, 5P20, 15VA is adequate.

    Confirmations of Manufacturers Recommendations:

    As per REB 500 Catalogue theKoalf Should satisfy the following conditions:

    Condition 1:

    Koalf>= 1xI kmax

    5xI1N

    I kmax : Maximum through fault current

    I1N : Rated primary CT Current

    I kmax=31500A

    I1N = 2000A

    Hence we have: 31500

    5 x 2000

    = 31500

    10000

    = 3.15

    Hence Koalf(valued 51)proposed is greater than above calculated value of 3.15.

    Hence the condition 1 of the manufacturers recommendations is satis fied.

    Condition 2:

    Koalf>= 10 for TN = 20 for TN

  • 7/25/2019 33kv Ct Calculations

    6/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 7 of32Rev A

    The relay is mounted on 33kV relay panel which is located in control room.

    Burden of relay = 0.1VA(Refer relay catalogue)

    Lead burden = 0.314VA (As calculated in 4.1.3 above)

    Total burden = Burden of the relay + Burden due to leadresistance

    = 0.1 + 0.314

    = 0.414 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.414 = 0.5175VA

    Hence a standard burden rating of 15 VA is chosen for a 600 tap and a burden of30VA is chosen for a tap of 1200A.

    The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.

    For a Tap of 600A

    To ensure correct operation of the connected relay in case of faults, the CT must beable to transform the maximum symmetrical short circuit current without saturation.

    To satisfy the above, following condition to be checked :

    Koalf Iscc/ Ipn

    Where, Ipn = CT primary nominal current = 600A

    Iscc = max. symmetrical short circuit current = 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limitingfactor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the totalconnected burden (Pb).

    Pn+ PiKoalf = Knalfx

    Pb+ Pi

    Where,

    Pn = Nominal CT burden = 15 VA

    Knalf = 20

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 3 Ohm (as per manufacturers recommendations)

    = 12x 3

    = 3 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

  • 7/25/2019 33kv Ct Calculations

    7/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 8 of32Rev A

    15 + 3

    Koalf = 20 x0.414 + 3

    = 105.44

    Iscc/ Ipn = 31500 / 600

    = 52.5

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 600 1200 / 1, 5P20, 15VA is adequate.

    For a Tap of 1200A

    Pn = Nominal CT burden = 30 VA

    Knalf = 20

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 6 Ohm (Assumed)

    = 12x 6

    = 6 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

    15 + 6

    Koalf = 20 x0.414 + 6

    = 65

    Iscc/ Ipn = 31500 / 1200

    = 27

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 600 1200 / 1, 5P20, 30VA is adequate.

    Abstract:

    Therefore a CT of CL. 5P20, 15VA is proposed for 600-1200/1A and CL. 5P20, 30VAis proposed for 600-1200/1A.

    The same is as per the specification.

    4.2 33/11.55kV, 15MVA & 20MVA Transformer Feeder

    4.2.1 CTs for Metering

    CT Ratio: (For 20MVA Transformer)

    400-600/1A.

  • 7/25/2019 33kv Ct Calculations

    8/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 9 of32Rev A

    CT Ratio: (For 15MVA Transformer)

    300-600/1A.

    Type of Metering:

    Metering Through Bay Control Unit (BCU) typeREF542 Plus

    Total burden of bay control unit = 0.1 VA(Refer REF542 Plus catalogue)

    Minimum length of cable = 5 metersbetween CT and BCU

    Size of cable = 2.5 sqmm

    Resistance of cable per = 7.41 Ohms (Refer Ducab cable catalogue)km at 20 deg C

    Resistance of cable at = 7.41(1+0.00393 (55-20) )55 deg C, consideringtemperature correction factor

    = 8.429 ohm/km

    Total resistance = 2 x 8.429 x 5 / 1000

    (Lead & Return conductors) = 0.08429

    Burden due to lead resistance = Total resistance x (CT secondary current)2

    = 0.08429 x 12

    = 0.08429 VA

    Total burden = Total burden of the BCU + Burden due to lead

    resistance= 0.1 + 0.08429

    = 0.18429 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.18429 = 0.23 VA

    Hence a standard burden rating of minimum 15 VA is chosen.

    The CT Accuracy Class selected is CL. 0.5 as per the specification requirements.

    The instrument security factor (ISF) selected is less than Five(5) as per thespecification requirement

    Abstract (20MVA Transformer):

    Therefore a CT of CL. 0.5,15VA is proposed for 400-600/1A and CL. 0.5,30VA isproposed for 400-600/1A.The CTs are with a factor of safety less than or equal to 5.

    The same is as per the specification.

    Abstract (15MVA Transformer):

    Therefore a CT of CL. 0.5,15VA is proposed for 300-600/1A and CL. 0.5,30VA isproposed for 300-600/1A. The CTs are with a factor of safety less than or equal to 5.

    The same is as per the specification.

  • 7/25/2019 33kv Ct Calculations

    9/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 10 of32Rev A

    4.2.2 CTs for Differential Protection:

    Differential Core Calculations for 20MVA Transformer

    CT Ratio:

    400-600/1A.

    Type of relay: RET 316*4 (ABB make)

    Knee Point Voltage Calculations:

    Fault current rating of 33 kV switchgear = 31.5 kA

    As per ESI Standard 48-3 the formulae for calculating Knee Point Voltage is

    VK = If * N * (Rct+Rl)

    Where If = fault current

    N = Turns Ratio

    Rct= CT secondary resistance

    Rl = Lead resistance

    Maximum fault current carrying capacity of 33 kV switchgear is 31.5 kA, which can beconsidered for knee point calculation.

    For a Tap of 400A

    If= 31500 Amps

    N = 1/400

    Rct = 1.5 (As recommended by Manufacturer)

    The differential relay is mounted on 33kV relay panel, which is located in control-room.

    Minimum length of cable = 30 metersbetween CT and relay

    Size of cable = 4 sqmm

    Resistance of cable per = 4.61 Ohms (Refer Ducab cable catalogue)km/phase at 20 deg C

    Resistance of cable at = 4.61(1+0.00393 (55-20) )55 deg C, consideringtemperature correction factor

    = 5.244ohm/km

    Total resistance = 2 x 5.244 x 30 / 1000

    (Lead & Return conductors) = 0.314

    Burden due to lead resistance = Total resistance x (CT secondary current)2

    = 0.314 x 12

    = 0.314 VA

    Therefore, substituting the above values in the formula for Vk,

    VK= 31500* (1/400) * (1.5 + 0.314 )

    VK= 143V

    Therefore a CT of 400-600/1A, CL. X, VK> 250V is proposed.

  • 7/25/2019 33kv Ct Calculations

    10/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 11 of32Rev A

    For a Tap of 600A

    Rct = 3 (Assumed)

    VK= 31500* (1/600) * (3 + 0.314 )

    VK= 173.9V

    Therefore a CT of 400-600/1A, CL. X, VK> 250V is proposed .

    Recommendations f rom Consultant/Client :

    Further, to avoid mal-operation on energization of power transformer and inconnection with fault current that passes through power transformer, the ratedsecondary voltage has to satisfy the following conditions:

    Condition-1

    The core may not saturate for current lower than 30 times the PowerTransformer rated current at connected burden. This ensures stability alsowith heavy DC saturation.

    Vk 30 * Int* (Rct+ Rl+ Rr/ Ir2

    )Where,

    Int = Main CT secondary current corresponding to rated primary

    current of power transformer

    Rct = CT secondary resistance

    Rl = Lead resistance

    Rr = Relay burden

    Ir = Nominal relay current

    Full load current of the transformer = (20000 / 1.732 * 33) = 350 Amps.For a Tap of 400A

    Vk 30 * (350/400) * (1.5+ 0.314 + 0.1 / 12)

    Vk 50.24V

    The knee point voltage proposed by us is 250V.

    Hence this condition is Verified.

    For a Tap of 600A

    Vk 30 * (350/600) * (3+ 0.314 + 0.1 / 12)

    Vk 60V

    The knee point voltage proposed by us is 250V.

    Hence this condition is Verified.

    Condition-2

    The core may not saturate for current lower than 4 times the maximumthrough fault current at connected burden.

    Vk 4 * Ift* (Rct+ Rl+ Rr/ Ir2)

    Where,Ift = Maximum secondary side through fault current

  • 7/25/2019 33kv Ct Calculations

    11/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 12 of32Rev A

    Rct = CT secondary resistance

    Rl = Lead resistance

    Rr = Relay burden

    Ir = Nominal relay current

    Full load current of the transformer = (20000 / 1.732 * 33) = 350 Amps.

    Impedance of transformer = 10%

    Through fault current = 350 / 0.1 = 3500 Amps

    For a Tap of 400A

    Secondary side through fault current = 3500 / 400 = 8.75 Amps.

    Hence Vk 4 * 8.75 * (1.5+ 0.314 + 0.1 / 12)

    Vk 67 V

    The knee point voltage proposed by us is 250V.

    Hence this condition is Verified.

    For a Tap of 600A

    Secondary side through fault current = 3500 / 600 = 5.83 Amps.

    Hence Vk 4 * 5.83 * (3+ 0.314 + 0.1 / 12)

    Vk 80 V

    The knee point voltage proposed by us is 250V.

    Hence this condition is Verified.

    Abstract (20MVA Transformer):

    Therefore a CT of Vk > 250V is proposed for 400-600/1A and Vk > 250V is proposedfor 400-600/1A.Imag shall be 50mA @ Vk/2

    Differential Core calculations for 15MVA Transformer

    CT Ratio:

    300-600/1A.

    Type of relay: RET 316*4 (ABB make)

    Knee Point Voltage Calculations:

    Fault current rating of 33 kV switchgear = 31.5 kA

    As per ESI Standard 48-3 the formulae for calculating Knee Point Voltage is

    VK = If * N * (Rct+Rl)

    Where If= fault current

    N = Turns Ratio

    Rct= CT secondary resistance

    Rl= Lead resistance

    Maximum fault current carrying capacity of 33 kV switchgear is 31.5 kA, which can beconsidered for knee point calculation.

  • 7/25/2019 33kv Ct Calculations

    12/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 13 of32Rev A

    For a Tap of 300A

    If= 31500 Amps

    N = 1/300

    Rct = 1.5 (As recommended by Manufacturer)

    The differential relay is mounted on 33kV relay panel, which is located in control-room.

    Minimum length of cable = 30 metersbetween CT and relay

    Size of cable = 4 sqmm

    Resistance of cable per = 4.61 Ohms (Refer Ducab cable catalogue)km/phase at 20 deg C

    Resistance of cable at = 4.61(1+0.00393 (55-20) )55 deg C, considering

    temperature correction factor= 5.244ohm/km

    Total resistance = 2 x 5.244 x 30 / 1000

    (Lead & Return conductors) = 0.314

    Burden due to lead resistance = Total resistance x (CT secondary current)2

    = 0.314 x 12

    = 0.314 VA

    Therefore, substituting the above values in the formula for Vk,

    VK= 31500* (1/300) * (1.5 + 0.314 )

    VK= 190V

    Therefore a CT of 300-600/1A, CL. X, VK> 250V is proposed.

    For a Tap of 600A

    Rct = 3 (Assumed)

    VK= 31500* (1/600) * (3 + 0.314 )

    VK= 173.9V

    Therefore a CT of 300-600/1A, CL. X, VK> 250V is proposed .

    Recommendations f rom Consultant/Client :

    Further, to avoid mal-operation on energization of power transformer and inconnection with fault current that passes through power transformer, the ratedsecondary voltage has to satisfy the following conditions:

    Condition-1

    The core may not saturate for current lower than 30 times the powertransformer rated current at connected burden. This ensures stability also withheavy DC saturation.

    Vk 30 * Int* (Rct+ Rl+ Rr/ Ir2)

    Where,

  • 7/25/2019 33kv Ct Calculations

    13/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 14 of32Rev A

    Int = Main CT secondary current corresponding to rated primary

    current of power transformer

    Rct = CT secondary resistance

    Rl = Lead resistance

    Rr = Relay burden

    Ir = Nominal relay current

    Full load current of the transformer = (15000 / 1.732 * 33) = 265 Amps.

    For a Tap of 300A

    Vk 30 * (265/300) * (1.5+ 0.314 + 0.1 / 12)

    Vk 51V

    The knee point voltage proposed by us is 250V.

    Hence this condition is Verified.

    For a Tap of 600A

    Vk 30 * (265/600) * (3+ 0.314 + 0.1 / 12)

    Vk 45V

    The knee point voltage proposed by us is 250V.

    Hence this condition is Verified.

    Condition-2

    The core may not saturate for current lower than 4 times the maximumthrough fault current at connected burden.

    Vk 4 * Ift* (Rct+ Rl+ Rr/ Ir2)

    Where,

    Ift = Maximum secondary side through fault current

    Rct = CT secondary resistance

    Rl = Lead resistance

    Rr = Relay burden

    Ir = Nominal relay current

    Full load current of the transformer = (15000 / 1.732 * 33) = 265 Amps.

    Impedance of transformer = 10%

    Through fault current = 265 / 0.1 = 2650 Amps

    For a Tap of 300A

    Secondary side through fault current = 2650 / 300 = 8.8 Amps.

    Hence Vk 4 * 8.8 * (1.5+ 0.314 + 0.1 / 12)

    Vk 67 V

    The knee point voltage selected is 250V.

    Hence this condition is verified.

  • 7/25/2019 33kv Ct Calculations

    14/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 15 of32Rev A

    For a Tap of 600A

    Secondary side through fault current = 2650 / 600 = 4.41 Amps.

    Hence Vk 4 * 4.41 * (3+ 0.314 + 0.1 / 12)

    Vk 60 V

    The knee point voltage proposed by us is 250V.

    Hence this condition is Verified.

    Abstract (15MVA Transformer):

    Therefore a CT of Vk > 250V is proposed for 300-600/1A and Vk > 250V is proposedfor 300-600/1A. Imag shall be 60mA @ Vk/2

    Differential Core Abstract:

    Abstract (20MVA Transformer):

    Therefore a CT of Vk > 250V is proposed for 400-600/1A and Vk > 250V is proposedfor 400-600/1A. Imag shall be 50mA @ Vk/2

    Abstract (15MVA Transformer):

    Therefore a CT of Vk > 250V is proposed for 300-600/1A and Vk > 250V is proposedfor 300-600/1A. Imag shall be 60mA @ Vk/2

    4.2.3 CTs for Overcurrent & Earth Fault Protection:

    CT Ratio (for 20MVA Transformer):

    400-600/1A

    Type of relay: REJ 525 (ABB make)

    Fault current rating of 33kV switchgear = 31.5kA

    The relay is mounted on 33kV relay panel which is located in control room.

    Burden of relay = 0.1VA(Refer relay catalogue)

    Lead burden = 0.314VA (As calculated in 4.2.2 above)

    Total burden = Burden of the relay + Burden due to leadresistance

    = 0.1 + 0.314

    = 0.414 VA

    Considering 25% future marginTotal burden required =1.25 x 0.414 = 0.5175VA

    Hence a standard burden rating of 15 VA is chosen for a Tap of 400A Tap and aburden of 30 VA is chosen for a Tap of 600A Tap.

    The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.

    To ensure correct operation of the connected relay in case of faults, the CT must beable to transform the maximum symmetrical short circuit current without saturation.

    To satisfy the above, following condition to be checked :

    Koalf Iscc/ Ipn

  • 7/25/2019 33kv Ct Calculations

    15/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 16 of32Rev A

    For a Tap of 400A

    Where, Ipn = CT primary nominal current = 400A

    Iscc = max. symmetrical short circuit current = 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limitingfactor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the totalconnected burden (Pb).

    Pn+ PiKoalf = Knalfx

    Pb+ Pi

    Where,

    Knalf = 20

    Pn = Nominal CT burden = 15 VA

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 1.5 (As recommended by Manufacturer)

    = 12x 1.5

    = 1.5 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

    15 + 1.5

    Koalf = 20 x0.414 + 1.5

    = 172.41

    Iscc/ Ipn = 31500 / 400

    = 78.75Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 400 600 / 1, 5P20, 15VA is adequate.

    For a Tap of 600A

    Where, Ipn = CT primary nominal current = 600A

    Iscc = max. symmetrical short circuit current = 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limitingfactor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the total

    connected burden (Pb).

  • 7/25/2019 33kv Ct Calculations

    16/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 17 of32Rev A

    Pn+ PiKoalf = Knalfx

    Pb+ Pi

    Where,

    Knalf = 20

    Pn = Nominal CT burden = 30 VA

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 3 (As recommended by Manufacturer)

    = 12x 3

    = 3 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

    15 + 3

    Koalf = 20 x0.414 + 3

    = 105

    Iscc/ Ipn = 31500 / 600

    = 53

    Koalf> Iscc/ Ipn

    Hence the selected CT wi th parameters 400 600 / 1, 5P20, 30VA is adequate.

    CT Ratio (for 15MVA Transformer)

    300-600/1A

    Type of relay: REJ 525 ( ABB make)

    Fault current rating of 33kV switchgear = 31.5kA

    The relay is mounted on 33kV relay panel which is located in control room.

    Burden of relay = 0.1VA(Refer relay catalogue)

    Lead burden = 0.314VA (As calculated in 4.2.2 above)

    Total burden = Burden of the relay + Burden due to leadresistance

    = 0.1 + 0.314

    = 0.414 VA

    Considering 25% future marginTotal burden required =1.25 x 0.414 = 0.5175VA

  • 7/25/2019 33kv Ct Calculations

    17/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 18 of32Rev A

    Hence a standard burden rating of 15 VA is chosen for a Tap of 400A Tap and aburden of 30 VA is chosen for a Tap of 600A Tap.

    The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.

    To ensure correct operation of the connected relay in case of faults, the CT must be

    able to transform the maximum symmetrical short circuit current without saturation.To satisfy the above, following condition to be checked :

    Koalf Iscc/ Ipn

    For a Tap of 300A

    Where, Ipn = CT primary nominal current = 300A

    Iscc = max. symmetrical short circuit current = 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limitingfactor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the totalconnected burden (Pb).

    Pn+ PiKoalf = Knalfx

    Pb+ Pi

    Where,

    Knalf = 20

    Pn = Nominal CT burden = 15 VA

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 1.5 (As recommended by Manufacturer)

    = 12x 1.5

    = 1.5 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

    15 + 1.5

    Koalf = 20 x0.414 + 1.5

    = 172.41

    Iscc/ Ipn = 31500 / 300

    = 105

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 300 600 / 1, 5P20, 15VA is adequate.

  • 7/25/2019 33kv Ct Calculations

    18/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 19 of32Rev A

    For a Tap of 600A

    Where, Ipn = CT primary nominal current = 600A

    Iscc = max. symmetrical short circuit current = 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limitingfactor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the totalconnected burden (Pb).

    Pn+ PiKoalf = Knalfx

    Pb+ Pi

    Where,

    Knalf = 20

    Pn = Nominal CT burden = 30 VA

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 3 (As recommended by Manufacturer)

    = 12x 3

    = 3 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

    15 + 3

    Koalf = 20 x0.414 + 3

    = 105

    Iscc/ Ipn = 31500 / 600

    = 53

    Koalf>

    Iscc/ Ipn

    Hence the selected CT wi th parameters 400 600 / 1, 5P20, 30VA is adequate.

    Abstract (20MVA Transformer):

    Therefore a CT of CL. 5P20,15VA is proposed for 400-600/1A and CL. 5P20,30VA isproposed for 400-600/1A.

    The same is as per the specification.

    Abstract (15MVA Transformer):

    Therefore a CT of CL. 5P20,15VA is proposed for 300-600/1A and CL. 5P20,30VA isproposed for 300-600/1A.

    The same is as per the specification.

  • 7/25/2019 33kv Ct Calculations

    19/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 20 of32Rev A

    4.2.4 CTs for Bus Bar Protection

    A CT of 2000/1A, 5P20, 15VA is proposed as calculated in 4.1.3above.

    4.3 33kV Bus-section Feeder

    4.3.1 CTs for Metering

    CT Ratio:

    2000/1A.

    Type of Metering:

    Metering Through Bay Control Unit (BCU) typeREF542 Plus

    Burden of bay control unit = 0.1 VA (Refer REF542 Plus catalogue)

    Minimum length of cable = 5 metersbetween CT and BCU

    Size of cable = 2.5 sqmm

    Resistance of cable per = 7.41 Ohms (Refer Ducab cable catalogue)km at 20 deg C

    Resistance of cable at = 7.41(1+0.00393 (55-20) )55 deg C, consideringtemperature correction factor

    = 8.429 ohm/km

    Total resistance = 2 x 8.429 x 5 / 1000

    (Lead & Return conductors) = 0.08429

    Burden due to lead resistance = Total resistance x (CT secondary current)2

    = 0.08429 x 12

    = 0.08429 VA

    Total burden = Total burden of the BCU + Burden due to leadresistance

    = 0.1 + 0.08429

    = 0.18429 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.18429 = 0.23 VA

    Hence a standard burden rating of 15 VA is chosen.

    The CT Accuracy Class selected is CL. 0.5 as per the specification requirements.

    The instrument security factor (ISF) selected is less than Five(5) as per thespecification requirements.

    Therefore a CT of 2000/1A, CL. 0.5FS5, 15VA is proposed.

    Abstract:

    Therefore a CT of CL. 0.5,15VA is proposed for 2000/1A .The CTs are with a factor ofsafety less than or equal to 5.

  • 7/25/2019 33kv Ct Calculations

    20/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 21 of32Rev A

    4.3.2 CTs for Overcurrent & Earth Fault Protection:

    CT Ratio:

    2000/1A

    Type of relay: REJ 525 ( ABB make)

    Fault current rating of 33kV switchgear = 31.5kA

    The relay is mounted on 33kV relay panel which is located in control room.

    Burden of relay = 0.1VA(Refer relay catalogue)

    Lead burden = 0.314VA (As calculated in 4.2.2 above)

    Total burden = Burden of the relay + Burden due to leadresistance

    = 0.1 + 0.314

    = 0.414 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.414 = 0.5175 VA

    Hence a standard burden rating of 15 VA is chosen.

    The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.

    Therefore a CT of 2000/1A, CL. 5P20, 15VA is proposed.

    To ensure correct operation of the connected relay in case of faults, the CT must beable to transform the maximum symmetrical short circuit current without saturation.

    To satisfy the above, following condition to be checked :

    Koalf Iscc/ IpnWhere, Ipn = CT primary nominal current = 2000A

    Iscc = max. symmetrical short circuit current = 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limitingfactor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the totalconnected burden (Pb).

    Pn+ Pi

    Koalf = Knalfx Pb+ Pi

    Where,

    Pn = Nominal CT burden = 15 VA

    Knalf = 20

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 9Ohm (As confirmed by the Manufacturer)

  • 7/25/2019 33kv Ct Calculations

    21/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 22 of32Rev A

    = 12x 9

    = 9 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

    15 + 9

    Koalf = 20 x0.414 + 9

    = 51

    Iscc/ Ipn = 31500 / 2000

    = 15.75

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 2000 / 1, 5P20, 15VA is adequate.

    Abstract:

    Therefore a CT of CL. 5P20, 15VA is proposed for 2000/1A.

    The same is as per the specification.

    4.3.3 CTs for Bus Bar Protection:

    A CT of 2000/1A, 5P20, 15VA is proposed as calculated in 4.1.3 above.

    4.4 33kV Over Head Line(OHL) Feeder

    4.4.1 CTs for Metering

    CT Ratio:

    600-1200/1A.

    Type of Metering:

    Metering Through Bay Control Unit (BCU) typeREF542 Plus

    Burden of bay control unit = 0.1 VA (Refer REF542 Plus catalogue)

    The BCU is mounted on the 33kV switchgear.

    Minimum length of cable = 5 metersbetween CT and BCU

    Size of cable = 2.5 sqmm

    Resistance of cable per = 7.41 Ohms (Refer Ducab cable catalogue)km at 20 deg C

    Resistance of cable at = 7.41(1+0.00393 (55-20) )55 deg C, consideringtemperature correction factor

    = 8.429 ohm/km

  • 7/25/2019 33kv Ct Calculations

    22/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 23 of32Rev A

    Total resistance = 2 x 8.429 x 5 / 1000

    (Lead & Return conductors) = 0.08429

    Burden due to lead resistance = Total resistance x (CT secondary current)2

    = 0.08429 x 12

    = 0.08429 VA

    Total burden = Total burden of the BCU + Burden due to leadresistance

    = 0.1 + 0.08429

    = 0.18429 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.18429 = 0.23 VA

    Hence a standard burden rating of minimum 15 VA is chosen.

    The CT Accuracy Class selected is CL. 0.5 as per the specification requirements.The instrument security factor (ISF) selected is less than Five (5) as per thespecification requirements.

    Abstract:

    Therefore a CT of CL. 0.5,15VA is proposed for 600-1200/1A and CL. 0.5,30VA isproposed for 600-1200/1A.The CTs are with a factor of safety less than or equal to 5.

    The same is as per the specification.

    4.4.2 CTs for Distance Protection:

    CT Ratio:

    600-1200 / 1A.

    Type of relay: REL 316*4 (ABB make)

    Knee Point Voltage Calculations:

    Fault current rating of 33 kV switchgear = 31.5 kA

    Since the distance relay of type REL 316*4 and transformer differential relay of typeRET 316*4 works on the same principle, the knee point voltage formulae used fortransformer differential relay is applicable for distance relay also.

    As per ESI Standard 48-3 the formulae for calculating Knee Point Voltage is

    VK = If * N * (Rct+Rl)

    Where If= fault current

    N = Turns Ratio

    Rct= CT secondary resistance

    Rl= Lead resistance

    For a Tap of 600A

    Maximum fault current carrying capacity of 33 kV switchgear is 31.5 kA which can beconsidered for knee point calculation.

    If= 31500 Amps

    N = 1/600

  • 7/25/2019 33kv Ct Calculations

    23/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 24 of32Rev A

    Rct = 3 (As per Manufacturers Recommendations)

    The distance relay is mounted on 33kV relay panel which is located in control room.

    Minimum length of cable = 30 metersbetween CT and relay

    Size of cable = 4 sqmm

    Resistance of cable per = 4.61Ohms (Refer Ducab cable catalogue)km/phase at 20 deg C

    Resistance of cable at = 4.61(1+0.00393 (55-20)) = 5.244 ohm/km55 deg C, consideringtemperature correction factorTotal resistance = 2 x 5.244 x 30 / 1000

    (Lead & Return conductors) = 0.314

    Burden due to lead resistance = Total resistance x (CT secondary current)2

    = 0.314 x 12

    = 0.314 VA

    Therefore, substituting the above values in the formula for Vk,

    VK= 31500* (1/600) * (3 + 0.314)

    VK= 174V

    Therefore a CT of 600-1200 /1A, CL. X, VK> 300V is proposed. The choice of usingthe same shall be verified by the following recommendations:

    Recommendations from Consultant/Client/Relay Manufacturers :

    Further, the CT rated secondary voltage has to satisfy the following conditions:

    Condition 1:

    Faults close to the relay location

    Vk If* (Isn/ Ipn) * a* (Rct+ Rl+ Rr/ Ir2)

    Where,

    If = Maximum primary fundamental frequency component

    Rct = CT secondary resistance

    Rl = Lead resistance

    Rr = Relay burden

    Ir = Nominal relay current

    Isn = Secondary Nominal CT current

    Ipn = Primary Nominal CT current

    a = Time constant for DC component

    Kindly refer the Graph (Figure-1) Attached in Annexure 3 for the value of a.

    For a 30ms DC Time constant, its value is 4.3 (for system frequency of 50Hz).

  • 7/25/2019 33kv Ct Calculations

    24/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 25 of32Rev A

    Hence Vk 31500 * (1/600) * 4.3 * (3+ 0.314 + 0.2 / 12)

    Vk 793V

    We shall proceed with the Condition2 recommendations to confirm the usageof maximum of Condition 1 and Condition 2 knee point values, as theRecommended values for CT.

    Condition 2:

    Faults at Zone 1 reach

    Vk Ifzone1* (Isn/ Ipn) * k * (Rct+ Rl+ Rr/ Ir2)

    Where,

    Ifzone-1 = Maximum primary fundamental frequency component

    Rct = CT secondary resistance

    Rl = Lead resistance

    Rr = Relay burden

    Ir = Nominal relay current

    Isn = Secondary Nominal CT current

    Ipn = Primary Nominal CT current

    k = Time constant for DC component

    Kindly refer the Graph (Figure-2) Attached in Annexure 3 for the value of k.For a 30ms DC Time constant, its value is 7.6 (for system frequency of 50Hz).

    Since the fault is at the End of Zone 1.The impedance of the Transmission lineshall come in play, hence the Fault current shall be reduced to a very lowvalue. Hence assuming the fault current is 75% of the Rated fault current ofthe switchgear (the actual fault current shall be much less than this value).The recommendations from Relay manufacturers show that the value of faultcurrent is in the range of 15 20kA only for a Zone 1 fault in a 33kV system.

    Hence

    I Ifzone-1 = 0.75 x 31500 = 23.625kA

    Assuming the same as 24kA for Calculations, we get

    Vk 24000* (1/600) * 7.6 * (3+ 0.314 + 0.2 / 12)

    Vk 1068V

    Since the Value calculated in Condition 2 is Greater than the one proposed by ESIStandard and as calculated for Condition 1,we propose the usage of the value of CTas calculated through Condition 2 as the final Recommended Value.

    Therefore a CT of 600-1200/1A, CL. X, VK> 1068V is proposed.

    For a Tap of 1200A

    Vk as per ESI Recommendations is:VK= 31500* (1/1200) * (6 + 0.314)

  • 7/25/2019 33kv Ct Calculations

    25/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 26 of32Rev A

    VK= 165V

    Rct = 6Ohm (Assumed)

    Therefore a CT of 600-1200 /1A, CL. X, VK> 300V is proposed.

    Condition 1:

    Faults close to the relay location

    Vk If* (Isn/ Ipn) * a* (Rct+ Rl+ Rr/ Ir2)

    Where,

    If = Maximum primary fundamental frequency component

    Rct = CT secondary resistance

    Rl = Lead resistance

    Rr = Relay burden

    Ir = Nominal relay current

    Isn = Secondary Nominal CT current

    Ipn = Primary Nominal CT current

    a = Time constant for DC component

    Kindly refer the Graph (Figure-1) Attached in Annexure 3 for the value of a.For a 30ms DC Time constant, its value is 4.3 (for system frequency of 50Hz).

    Hence Vk 31500 * (1/1200) * 4.3 * (6+ 0.314 + 0.2 / 12)

    Vk 735V

    We shall proceed with the Condition2 recommendations to confirm the usageof maximum of Condition 1 and Condition 2 knee point values, as theRecommended values for CT.

    Condition 2:

    Faults at Zone 1 reach

    Vk Ifzone1* (Isn/ Ipn) * k * (Rct+ Rl+ Rr/ Ir2)

    Where,

    Ifzone-1 = Maximum primary fundamental frequency component

    Rct = CT secondary resistance

    Rl = Lead resistance

    Rr = Relay burden

    Ir = Nominal relay current

    Isn = Secondary Nominal CT current

    Ipn = Primary Nominal CT current

    k = Time constant for DC component

    Kindly refer the Graph (Figure-2) Attached in Annexure 3 for the value of k.

    For a 30ms DC Time constant, its value is 7.6 (for system frequency of 50Hz).

  • 7/25/2019 33kv Ct Calculations

    26/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 27 of32Rev A

    Since the fault is at the End of Zone 1.The impedance of the Transmission lineshall come in play, hence the Fault current shall be reduced to a very lowvalue. Hence assuming the fault current is 75% of the Rated fault current ofthe switchgear (the actual fault current shall be much less than this value).The recommendations from Relay manufacturers show that the value of faultcurrent is in the range of 15 20kA only for a Zone 1 fault in a 33kV system.

    Hence

    I Ifzone-1 = 0.75 x 31500 = 23.625kA

    Assuming the same as 24kA for Calculations, we get

    Vk 24000* (1/1200) * 7.6 * (6+ 0.314 + 0.2 / 12)

    Vk 990V

    Since the Value calculated in Condition 2 is Greater than the one proposed by ESIStandard and as calculated for Condition 1,we propose the usage of the value of CTas calculated through Condition 2 as the final Recommended Value.

    Therefore a CT of 600-1200/1A, CL. X, VK> 990V is proposed.

    Abstract

    Therefore a CT of CL. X, Vk >1068V is proposed for 600-1200/1A and CL. X, Vk >990V is proposed for 600-1200/1A.

    4.4.3 CTs for Overcurrent & Earth Fault Protection:

    CT Ratio:

    600-1200/1AType of relay: REJ 527 and SPAS348C3 ( ABB make)

    Fault current rating of 33kV switchgear = 31.5kA

    The relay is mounted on 33kV relay panel which is located in control room.

    Burden of relay = 0.2VA(Refer relay catalogue)

    Lead burden = 0.314VA (As calculated in 4.4.2 above)

    Total burden = Burden of the relay + Burden due to leadresistance

    = 0.2 + 0.314

    = 0.514 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.514 = 0.6425VA

    Hence a standard burden rating of 15 VA is chosen for a 600A Tap and a burden of30VA is chosen for a Tap of 1200A.

    The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.

    For a Tap of 600A

    To ensure correct operation of the connected relay in case of faults, the CT must beable to transform the maximum symmetrical short circuit current without saturation.

    To satisfy the above, following condition to be checked :

  • 7/25/2019 33kv Ct Calculations

    27/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 28 of32Rev A

    Koalf Iscc/ Ipn

    Where, Ipn = CT primary nominal current = 600A

    Iscc = max. symmetrical short circuit current = 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limitingfactor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the totalconnected burden (Pb).

    Pn+ PiKoalf = Knalfx

    Pb+ Pi

    Where,

    Pn = Nominal CT burden = 15 VA

    Knalf = 20

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 3 Ohm (as per manufacturers recommendations)

    = 12x 3

    = 3 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.2 + 0.314

    = 0.514 VA

    15 + 3

    Koalf = 20 x0.514 + 3

    = 102.44

    Iscc/ Ipn = 31500 / 600

    = 52.5

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 600 1200 / 1, 5P20, 15VA is adequate.

    For a Tap of 1200A

    Pn = Nominal CT burden = 30 VA

    Knalf = 20

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 6 Ohm (Assumed)

  • 7/25/2019 33kv Ct Calculations

    28/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 29 of32Rev A

    = 12x 6

    = 6 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.2 + 0.314

    = 0.514 VA

    15 + 6

    Koalf = 20 x0.514 + 6

    = 65

    Iscc/ Ipn = 31500 / 1200

    = 27

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 600 1200 / 1, 5P20, 30VA is adequate.

    Abstract:

    Therefore a CT of CL. 5P20, 15VA is proposed for 600-1200/1A and CL. 5P20, 30VAis proposed for 600-1200/1A.

    The same is as per the specification.

    4.4.4 CTs for Bus Bar Protection:

    A CT of 2000/1A, 5P20, 15VA is proposed as calculated in 4.1.3 above.

    4.4.5 CTs for Sensitive Earth Fault Protection:

    CT Ratio:

    Ratio is considered as 600-1200/1A

    Type of relay: SPAJ 111C ( ABB make)

    Fault current rating of 33kV switchgear = 31.5kA

    The relay is mounted on 33kV relay panel which is located in control room.

    Burden of relay = 0.1VA(Refer relay catalogue)

    Lead burden = 0.314VA (As calculated in 4.4.2 above)

    Total burden = Burden of the relay + Burden due to leadresistance

    = 0.1 + 0.314

    = 0.414 VA

    Considering 25% future margin

    Total burden required =1.25 x 0.414 = 0.5175 VA

    Hence a standard burden rating of 15 VA is chosen for a Tap of 600A and 30VA ischosen for a Tap of 1200A Tap.

    The CT Accuracy Class selected is CL. 5P20 as per the specification requirements.

  • 7/25/2019 33kv Ct Calculations

    29/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 30 of32Rev A

    For a Tap of 600A

    To ensure correct operation of the connected relay in case of faults, the CT must beable to transform the maximum symmetrical short circuit current without saturation.

    To satisfy the above, following condition to be checked :

    Koalf Iscc/ Ipn

    Where, Ipn = CT primary nominal current = 600A

    Iscc = max. symmetrical short circuit current = 31.5kA

    Koalf = Operating accuracy limiting factor

    The operating accuracy limiting factor (Koalf) depends on the nominal accuracy limitingfactor (Knalf), the nominal CT burden (Pn), the internal CT burden (P i) and the totalconnected burden (Pb).

    Pn+ PiKoalf = Knalfx

    Pb+ Pi

    Where,Knalf = 20

    Pn = Nominal CT burden = 15 VA

    Pi = Internal CT burden

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 3Ohm (As confirmed by Manufacturer)

    = 12x 3

    = 3 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

    15 + 3

    Koalf = 20 x0.414 + 3

    = 105.448Iscc/ Ipn = 31500 / 600

    = 52.5

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 600 - 1200 / 1, 5P20, 15VA is adequate.

    For a Tap of 1200A

    Pn = Nominal CT burden = 30 VA

    Knalf = 20

    Pi = Internal CT burden

  • 7/25/2019 33kv Ct Calculations

    30/31

    ABB Transmission & Dist ribution LTD.

    Doc-No:G1408-AA-2030-J-0-102 Page 31 of32Rev A

    = V * I

    = (I * Rct) * I

    = I2* Rct

    Rct = 6 Ohm (as per manufacturers recommendations)

    = 12x 6

    = 6 VA

    Pb = Total connected burden

    = Pr+ PL

    = 0.1 + 0.314

    = 0.414 VA

    15 + 6

    Koalf = 20 x0.414 + 6

    = 65

    Iscc/ Ipn = 31500 / 1200

    = 27

    Koalf> Iscc/ Ipn

    Hence the selected CT with parameters 600 1200 / 1, 5P20, 30VA is adequate

    Abstract:

    Therefore a CT of CL. 5P20, 15VA is proposed for 600-1200/1A and CL. 5P20, 30VA

    is proposed for 600-1200/1A.

    The same is as per the specification.

    5.0 VT SIZING CALCULATIONS

    The VTs considered are as follows:

    Line VT:

    The devices connected on winding 1of line VTs are BCU, synchronising devices andVoltage Transducer.

    The burden of the same are as given below:

    BCU: 0.25VA 2VA Maximum ConsideredVoltage Transducers: 2VA max. 2VA Maximum ConsideredSynchronising devices: 25VA 25VA Maximum Considered

    Total 29 VA max.

    The devices connected on winding 2of line VTs are various relays. The maximumburden for the same is 10VA.

    The devices connected on winding 3of line VTs are Directional O/C relay.

  • 7/25/2019 33kv Ct Calculations

    31/31

    ABB Transmission & Dist ribution LTD.

    The burden of the same are as given below:

    Directional O/C relay: 0.2VA 2 VA Maximum Considered(Only for OHL lines)

    Hence the VT considered for line is of fo llowing parameters:

    33kV/

    3 / 110V /

    3 / 110V / 3 / 110V / 3 Winding 1 - 50VA , 0.5SWinding 2 - 50VA , 3PWinding 3 - 50VA , 3P

    Bus VT

    The devices connected on winding 1of line VTs are BCU, synchronising devices andVoltage Transducer.

    The burden of the same are as given below:

    BCU: 0.25 VA 2VA Maximum ConsideredVoltage Transducers: 2 VA 2VA Maximum ConsideredSynchronising devices: 25 VA 25VA Maximum Considered

    Total 29 VA max.

    The devices connected on winding 2of line VTs are various relays. The maximumburden for the same is 10VA.

    Hence to standardise the parameters of VT, following parameters areconsidered.

    33kV/

    3 / 110V /

    3 / 110V / 3 / 110V / 3 Winding 1 - 50VA , 0.5SWinding 2 - 50VA , 3PWinding 3 - 50VA , 3P

    6.0 CONCLUSION

    The CT/VT parameters recommended are as calculated above. The Manufacturerhas confirmed the values at the Principle/Usage Tap.

    7.0 SUMMARY OF CURRENT TRANSFORMERS

    The Summary of the Current transformers for all the sub-stations is given inAnnexure 1.

    8.0 SUMMARY OF VOLTAGE TRANSFORMERS

    The Summary of the Voltage transformers for all the sub-stations is given inAnnexure 2.