30RB 30RQ Master_SLave
Transcript of 30RB 30RQ Master_SLave
![Page 1: 30RB 30RQ Master_SLave](https://reader035.fdocuments.us/reader035/viewer/2022073116/5536121755034679668b4855/html5/thumbnails/1.jpg)
CARRIER s.a USER’S GUIDE FOR PRO-DIALOG
30 RSB & RQS Chillers
ECG–UG–09-001 Rev: original
Page 33/102
CONFIGURATION SCREEN
HMI Display menu location \\MAINMENU\CONFIG\MST_SLV
"Master/Slave Menu \0", TABLE NAME: MST_SLV PIC TABLE TYPE : 13H, instance 6 DESCRIPTION STATUS DEFAULT UNITS POINT 1 MASTER/SLAVE CONTROL 2 3 Master/Slave Select: 0/1/2 0 - ms_sel 4 0 = Disable 5 1 = Master 6 2 = Slave 7 Master Control Type: 1/2/3 1 - ms_ctrl 8 1 = Local Control 9 2 = Remote Control 10 3 = CCN Control 11 Slave Address 1 to 236 2 - slv_addr 12 Lag Start Timer 2 to 30 10 minutes lstr_tim 13 Lead/Lag Balance Yes/No No - ll_bal 14 Lead/Lag Balance Delta 40 to 400 168 hours ll_bal_d 15 Lag Unit Pump Control 0/1 0 - lag_pump 16 0 = Stop if Unit Stops 17 1 = Run if Unit Stops 18 Lead Pulldown Time 0 to 60 0 minutes lead_pul
CONFIGURATION SCREEN
HMI Display menu location \\MAINMENU\CONFIG\SERVICE
"Service Parameters Menu\0", TABLE NAME: SERVICE1 PIC TABLE TYPE : 13H, instance 7
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Cooler Fluid Type 1/2/3 1 - flui_typ
2 Entering Fluid Control Yes/No No - ewt_opt
3 Prop PID Gain Varifan -20.0 to 20.0 2.0 - hd_pg
4 Int PID Gain Varifan -5.0 to 5.0 0.2 - hd_ig
5 Deri PID Gain Varifan -20.0 to 20.0 0.4 - hd_dg
6 EXV A Superheat Setpoint 5 to 15 7.2 ^F sh_sp_a
7 EXV B Superheat Setpoint 5 to 15 7.2 ^F sh_sp_b
8 EXV MOP Setpoint 40 to 55 55 °F mop_sp
9 High Pressure Threshold 500 to 640 609 psi hp_th
10 Cooler Heater Delta Spt 1.8 to 6.0 3.4 ^F heatersp
11 Pump Cycling Freeze Prot No/Yes Yes - pump_cyc
12 Brine Freeze Setpoint - 20 to 34 34.0 °F frezzesp
13 Brine Minimum LWT - 20 to 38 38.0 °F lmin_lwt
14 Auto Start When SM Lost Enable/Disable Disable - auto_sm
15 Auto Z Multiplier Setpt 4 to 8 6 - zm_spt
16 Maximum Z Multiplier 1.0 to 6.0 6.0 - hc_zm
17 Service Password 1 to 9999 88 - ser_pass
18 Water Pressure Control
19 Water Flow Ctrl Method 0 to 2 0 - water_ct
20 0 none, 1 delta T, 2 Prs
21 Water delta T Setpoint 5.4 to 16.2 9.0 ^F w_dt_spt
22 Water Disch Press Setpt 14.5 to 43.51 29.0 psi w_dp_spt
23 Water Pump Min Value 50 to 100 50.0 % wpmp_min