CARRIER s.a USER’S GUIDE FOR PRO- DIALOG 30 RSB & RQS Chillers ECG–UG–09-001 Rev: original Page 33/102 CONFIGURATION SCREEN HMI Display menu location \\MAINMENU\CONFIG\MST_SLV "Master/Slave Menu \0", TABLE NAME: MST_SLV PIC TABLE TYPE : 13H, instance 6 DESCRIPTION STATUS DEFAULT UNITS POINT 1 MASTER/SLAVE CONTROL 2 3 Master/Slave Select: 0/1/2 0 - ms_sel 4 0 = Disable 5 1 = Master 6 2 = Slave 7 Master Control Type: 1/2/3 1 - ms_ctrl 8 1 = Local Control 9 2 = Remote Control 10 3 = CCN Control 11 Slave Address 1 to 236 2 - slv_addr 12 Lag Start Timer 2 to 30 10 minutes lstr_tim 13 Lead/Lag Balance Yes/No No - ll_bal 14 Lead/Lag Balance Delta 40 to 400 168 hours ll_bal_d 15 Lag Unit Pump Control 0/1 0 - lag_pump 16 0 = Stop if Unit Stops 17 1 = Run if Unit Stops 18 Lead Pulldown Time 0 to 60 0 minutes lead_pul CONFIGURATION SCREEN HMI Display menu location \\MAINMENU\CONFIG\SERVICE "Service Parameters Menu\0", TABLE NAME: SERVICE1 PIC TABLE TYPE : 13H, instance 7 DESCRIPTION STATUS DEFAULT UNITS POINT 1 Cooler Fluid Type 1/2/3 1 - flui_typ 2 Entering Fluid Control Yes/No No - ewt_opt 3 Prop PID Gain Varifan -20.0 to 20.0 2.0 - hd_pg 4 Int PID Gain Varifan -5.0 to 5.0 0.2 - hd_ig 5 Deri PID Gain Varifan -20.0 to 20.0 0.4 - hd_dg 6 EXV A Superheat Setpoint 5 to 15 7.2 ^F sh_sp_a 7 EXV B Superheat Setpoint 5 to 15 7.2 ^F sh_sp_b 8 EXV MOP Setpoint 40 to 55 55 °F mop_sp 9 High Pressure Threshold 500 to 640 609 psi hp_th 10 Cooler Heater Delta Spt 1.8 to 6.0 3.4 ^F heatersp 11 Pump Cycling Freeze Prot No/Yes Yes - pump_cyc 12 Brine Freeze Setpoint - 20 to 34 34.0 °F frezzesp 13 Brine Minimum LWT - 20 to 38 38.0 °F lmin_lwt 14 Auto Start When SM Lost Enable/Disable Disable - auto_sm 15 Auto Z Multiplier Setpt 4 to 8 6 - zm_spt 16 Maximum Z Multiplier 1.0 to 6.0 6.0 - hc_zm 17 Service Password 1 to 9999 88 - ser_pass 18 Water Pressure Control 19 Water Flow Ctrl Method 0 to 2 0 - water_ct 20 0 none, 1 delta T, 2 Prs 21 Water delta T Setpoint 5.4 to 16.2 9.0 ^F w_dt_spt 22 Water Disch Press Setpt 14.5 to 43.51 29.0 psi w_dp_spt 23 Water Pump Min Value 50 to 100 50.0 % wpmp_min

Transcript of 30RB 30RQ Master_SLave

Page 1: 30RB 30RQ Master_SLave

CARRIER s.a USER’S GUIDE FOR PRO-DIALOG

30 RSB & RQS Chillers

ECG–UG–09-001 Rev: original

Page 33/102

CONFIGURATION SCREEN

HMI Display menu location \\MAINMENU\CONFIG\MST_SLV

"Master/Slave Menu \0", TABLE NAME: MST_SLV PIC TABLE TYPE : 13H, instance 6 DESCRIPTION STATUS DEFAULT UNITS POINT 1 MASTER/SLAVE CONTROL 2 3 Master/Slave Select: 0/1/2 0 - ms_sel 4 0 = Disable 5 1 = Master 6 2 = Slave 7 Master Control Type: 1/2/3 1 - ms_ctrl 8 1 = Local Control 9 2 = Remote Control 10 3 = CCN Control 11 Slave Address 1 to 236 2 - slv_addr 12 Lag Start Timer 2 to 30 10 minutes lstr_tim 13 Lead/Lag Balance Yes/No No - ll_bal 14 Lead/Lag Balance Delta 40 to 400 168 hours ll_bal_d 15 Lag Unit Pump Control 0/1 0 - lag_pump 16 0 = Stop if Unit Stops 17 1 = Run if Unit Stops 18 Lead Pulldown Time 0 to 60 0 minutes lead_pul

CONFIGURATION SCREEN

HMI Display menu location \\MAINMENU\CONFIG\SERVICE

"Service Parameters Menu\0", TABLE NAME: SERVICE1 PIC TABLE TYPE : 13H, instance 7

DESCRIPTION STATUS DEFAULT UNITS POINT

1 Cooler Fluid Type 1/2/3 1 - flui_typ

2 Entering Fluid Control Yes/No No - ewt_opt

3 Prop PID Gain Varifan -20.0 to 20.0 2.0 - hd_pg

4 Int PID Gain Varifan -5.0 to 5.0 0.2 - hd_ig

5 Deri PID Gain Varifan -20.0 to 20.0 0.4 - hd_dg

6 EXV A Superheat Setpoint 5 to 15 7.2 ^F sh_sp_a

7 EXV B Superheat Setpoint 5 to 15 7.2 ^F sh_sp_b

8 EXV MOP Setpoint 40 to 55 55 °F mop_sp

9 High Pressure Threshold 500 to 640 609 psi hp_th

10 Cooler Heater Delta Spt 1.8 to 6.0 3.4 ^F heatersp

11 Pump Cycling Freeze Prot No/Yes Yes - pump_cyc

12 Brine Freeze Setpoint - 20 to 34 34.0 °F frezzesp

13 Brine Minimum LWT - 20 to 38 38.0 °F lmin_lwt

14 Auto Start When SM Lost Enable/Disable Disable - auto_sm

15 Auto Z Multiplier Setpt 4 to 8 6 - zm_spt

16 Maximum Z Multiplier 1.0 to 6.0 6.0 - hc_zm

17 Service Password 1 to 9999 88 - ser_pass

18 Water Pressure Control

19 Water Flow Ctrl Method 0 to 2 0 - water_ct

20 0 none, 1 delta T, 2 Prs

21 Water delta T Setpoint 5.4 to 16.2 9.0 ^F w_dt_spt

22 Water Disch Press Setpt 14.5 to 43.51 29.0 psi w_dp_spt

23 Water Pump Min Value 50 to 100 50.0 % wpmp_min