30XA080-500Air-Cooled Liquid Chillers
60 Hz
Controls, Start-Up, Operation, Serviceand Troubleshooting
CONTENTSPage
SAFETY CONSIDERATIONS ...................... 2GENERAL ...................................... 2-4Conventions Used in This Manual ................ 2Display Module Usage ........................... 3• NAVIGATOR TM DISPLAY MODULECONTROLS ................................... 4-41General .......................................... 4Main Base Board (MBB) .......................... 4Compressor Protection Module (CPM) ........... 6Electronic Expansion Valve (EXV) Board ......... 9Fan Boards ...................................... 11Enable-Off-Remote Contact Switch (SWl) ....... 13Emergency On/Off Switch (SW2) ................ 13Energy Management Module (EMM) ............. 13Local Equipment Network ....................... 14Board Addresses ................................ 14Control Module Communication ................. 14• RED LED• GREEN LED• YELLOW LEDCarrier Comfort Network® (CCN) Interface ...... 15Configuration Options .......................... 15• RAMP LOADING• MINUTES OFF TIMEDual Chiller Control ............................. 15• DUAL CHILLER PUMP CONTROL FOR PARALLEL
APPLICATIONS• DUAL CHILLER PUMP CONTROL FOR SERIES
CHILLER APPLICATIONSCapacity Control ................................ 16• EQUAL LOADING• STAGE LOADING• CAPACITY CONTROL OVERRIDESHead Pressure Control .......................... 22• LOW AMBIENT TEMPERATURE HEAD PRESSURE
CONTROL OFf'ION• LOW AMBIENT TEMPERATURE HEAD PRESSURE
CONTROL OPERATING INSTRUCTIONSMachine Control Methods ....................... 29• SWITCH CONTROL• TIME SCHEDULE• CCN CONTROL• UNITRUN STATUSCooling Set Point Selection ..................... 3O• SET POINT 1• SET POINT 2• 4 TO 20 mA INPUT• DUAL SWITCH• ICE MODE• SET POINT OCCUPANCYTemperature Reset .............................. 31Demand Limit ................................... 32• I-STEP SWITCH CONTROLLED• 2-STEP SWITCH CONTROLLED
Page• EXTERNALLY POWERED (4 to 20 mA Controlled)• CCN LOADSHED CONTROLLEDRemote Alarm and Alert Relays ................. 4OPRE-START-UP .................................. 41System Check ................................... 41START-UP .................................... 42-48Actual Start-Up .................................. 42Operating Limitations ........................... 42• TEMPERATURES• VOLTAGE• MINIMUM FLUID LOOP VOLUME• FLOW RATE REQUIREMENTSOPERATION .................................. 48-55Sequence of Operation .......................... 48• ACTUATED BALL VALVE (ABV)Dual Chiller Sequence of Operation ............. 49• PARALLEL PUMP OPERATIONOperating Modes ................................ 49Sensors ......................................... 52• THERMISTORS• TRANSDUCERSSERVICE ..................................... 56-66Economizer Assembly .......................... 56Electronic Expansion Valve (EXV) ............... 56• MAIN EXV CONTROL• ECONOMIZER EXV CONTROL• EXV TROUBLESHOOTING PROCEDURECompressor Assembly .......................... 59• COMPRESSOR OIL SYSTEMCooler ........................................... 61• SUCTION SERVICE VALVE• FREEZE PROTECTION• LOW FLUID TEMPERATURE• LOSS OF FLUID FLOW PROTECTION• TUBE PLUGGING• RETUBING• TIGHTENING COOLER HEAD BOLTS• INSPECTING/CLEANING HEAT EXHANGERS• WATER TREATMENT• CHILLED WATER FLOW SWITCHCondenser Coil Maintenance and Cleaning
Recommendations ............................ 64• REMOVE SURFACE LOADED FIBERS• PERIODIC CLEAN WATER RINSE• ROUTINE CLEANING OF COIL SURFACESCondenser Fans ................................ 65Refrigerant Circuit .............................. 65• LEAK TESTING• REFRIGERANT CHARGESafety Devices .................................. 66• COMPRESSOR PROTECTION• OIL SEPARATOR HEATERS• COOLER PROTECTIONRelief Devices ................................... 66• PRESSURE RELIEF VALVES
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 533-00069 Printed in U,S.A, Form 30XA-1T Pg 1 12-05 Replaces: New
CONTENTS (cont)
MAINTENANCE .................................. 66Recommended Maintenance Schedule .......... 66TROUBLESHOOTING ......................... 66-86Alarms and Alerts ............................... 67• DIAGNOSTIC ALARM CODES AND POSSIBLE
CAUSESService Test ..................................... 82APPENDIX A -- LOCAL DISPLAY TABLES... 87-100APPENDIX B -- CCN TABLES .............. 101-112APPENDIX C -- 30XA080-500 CPM
DIP SWITCH ADDRESSES ................ 113-116APPENDIX D -- PIPING AND
INSTRUMENTATION .......................... 117INDEX .......................................... 118START-UP CHECKLIST
FOR 30XA LIQUID CHILLERS ........ CL-I to CL-8
SAFETY CONSIDERATIONS
Inst_dling,starting up, and servicing this equipment can behazardous due to system pressures, electrical components, andequipment location (roof. elevated structures, etc.). Onlytrained, qu_dified installers and service technicians shouldinstall, start up, and service this equipment. When working onthis equipment, observe precautions in the literature, and ontags, stickers, and labels attached to the equipment, and anyother safety precautions that apply. Follow all safety codes.WEar safety glasses and work gloves. Use care in handling,rigging, and setting this equipment, and in handling _dlelectri-c_dcomponents.
This unit uses a microprocessor-based electronic controlsystem. Do not use jumpel.s or other tools to short out com-ponents, or to bypass or otherwise deDut from recom-mended procedures. Any short-to-ground of the controlbomd or accompanying wiring may destroy the electronicmodules or electric_d components.
To prevent potential damage to heat exchanger tubes,always run fluid through heat exchanger when adding orremoving refrigerant chm'ge. Use appropriate antifreezesolutions in cooler fluid loop to prevent the freezing of heatexchanger or interconnecting piping when the equipment isexposed to temperatures below 32 F (0° C). Proof of flowswitch is factory installed on all models. Do NOT removepower from this chiller during winter shut down periodswithout taking precaution to remove all water from heatexchangel: Failure to properly protect the system fromfreezing may constitute abuse and may void wammty.
Compressors require specific rotation. Test condenserfan(s) first to ensme proper phasing. Swap any two incom-ing power leads to correct condenser fan rotation beforestarting compressors. Operating the unit without testing thecondenser fan(s) for proper phasing could result in equip-ment damage.
Electrical shock can cause personal inju U and death. Shutoff all power to this equipment during installation and ser-vice. There may be morn than one disconnect switch. %gall disconnect locations to alert others not to restore poweruntil work is completed.
DO NOT VENT refrigerant relief valves within a building.Outlet from relief valves must be vented in accordancewith the latest edition of ANSI/ASHRAE (AmericanNational Standm'ds institute/American Society of Heating,Refrigerating and Air Conditioning Engineel.s) 15 (SafetyCode for Mechanical Refrigeration). The accumulation ofrefrigerant in an enclosed space can displace oxygen andcause asphyxiation. Provide adequate ventilation inenclosed or low overhead meas. Inhalation of high concen-trations of vapor is harmful and may cause heart irregulari-ties, unconsciousness or death. Misuse can be fatal. Vaporis heavier than air and reduces the mnount of oxygen avail-able for breathing. Product causes eye and skin irritation.Decomposition products am hazmdous.
DO NOT attempt to unbraze factory joints when servicingthis equipment. Compressor oil is flammable and there isno way to detect how much oil may be in gray of the refrig-erant lines. Cut lines with a tubing cutter as required whenperforming service. Use a pan to catch any oil that maycome out of the lines and as a gage for how much oil to addto system. DO NOT re-use compressor oil.
GENERAL
This publication contains Controls, Operation, Start-Up,Service and Troubleshooting information for the 30XA080-500 air-cooled liquid chillers with electronic controls. The30XA chillers are equipped with Co;@,-tLink TM controls andelectronic expansion valves.
Conventions Used in This Manual -- The follow-
ing conventions for discussing configuration points for theNavigator r_qmodule will be used in this manu_d.
Point names will be written with the mode name first, thenany sub-modes, then the point name, each sepm'ated by anarrow symbol (-+). Nmnes will _dso be shown in boldand it:dics. As an example, the Lead/Lag Circuit Select Point,which is located in the Configuration mode, Option sub-mode,would be written as Configuration -+OPTN-+LLCS.
This path name will show the user how to navigate through the
loc_d display to roach the desired configuration. The user would
scroll through the modes and sub-modes using the [] and []keys. The arrow symbol in the path nmne represents pressing
to move into the next level of the menu structure.
When a value is included as pan of the path name, it will beshown at the end of the path name after an equ_ds sign. If thevalue represents a configuration setting, an explanation willbe shown in parenthesis after the value. As an exmnple,Configuration-+OPTN-+LLCS = 1 (Circuit A leads).
Pressing the _ and _ keys simultaneouslywill scroll an expanded text description of the point nmne or value
across the display. The expgmded description is shown in the local
display tables but will not be shown with the path names in text.
The CCN (Cgurier Comfort Network®) point names arealso referenced in the local display tables for users configuringthe unit with CCN software instead of the local display. TheCCN tables are located in Appendix B of the manual.
Display Module Usage
NAVIGATOR TM DISPLAY MODULE -- The Navigator mod-ule provides a mobile user interface to the Con_fortLink TM
control system. The display has up and down arrow keys, an
key, and an _ key. These keys are used tonavigate through the different levels of the display structure.
Press the _ key until 'Select a Menu Item' is dis-
played to move through the top 11 mode levels indicated byLEDs on the left side of the display. See Fig. 1. See Table 1
and Appendix A for more details about the display menustructure.
Once within a Mode or sub-mode, a ">" indicates the cur-
rently selected item on the display scleen. Pressing the
___ and _ keys simultaneously will put the Nav-
igator module into expanded text mode where the full meaningof all sub-modes, items and their values can be displayed. Press-
ing file _ and _ keys when file display says
'Select Menu Item' (Mode LED level) will return the Navigatormodule to its default menu of rotating display items (those items
in Run Status --+VIEW). In addition, the password will be dis-
abled, lequiring that it be entered again befole changes can bemade to password protected items. Press the _ key to
exit out of the expanded text mode.
NOTE: When the Language Selection (Configuration---)DISP---)LANG), variable is chtmged, all appropriate displayexpansions will immediately change to the new language. Nopower-off or control reset is required when reconfiguringlanguages.
When a specific item is located, the item name appems on the
left of file display, the v_due will appear nero the middle of file
display and file units (if any) will appear on file fro"right of thedisplay. Press file _ key at a changeable item and file val-
ue will begin to flash. Use the up and down anow keys to change
the value, and confirm file v;due by pressing the _ key.
Changing item values or testing outputs is accomplished inthe same mannel: Ix_cate and display the desired item. Press
so that the item v_due flashes. Use the arrow keys to
the value or state and press the _ key tochange acceptit. Press the _ key to return to the next higher level of
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes me pass-
word protected. The words Enter Password will be displayed
when required, with 1111 also being displayed. The defaultpassword is 0111. Use the arrow keys to change each number
and press _ to enter the digit. Continue with the
remaining digits of the password. The password can only bechanged through CCN operator interface softwme such as
ComfortWORKS®, ComfortVlEW TM and Service Tool.
Adjusting the Contrast -- The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast ofthe Navigator module, press the _ key until the dis-
play reads, "Select a menu item." Using the arrow keys moveto the Configuration mode. Press _ to obtain access to
this mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
will cause the "OFF" to flash. Use thePressing up
down arrow to change "OFF" to "ON." Pressingor
will illuminate all LEDs and display all pixels in the view
screen. Pressing _ and _ simultaneously
_dlows the user to adjust the display contrast. The display willlead:
Adjust Contrast.... -1.
Use the up or down arrows to adjust file contrast. The
screen's contrast will change with the adjustment. Press
to accept the change. The Navigator module willl
keep this setting as long as it is plugged in to the LEN bus.
Adjusting the Backlight Brightness -- The backlight of the
display can be adjusted to suit ambient conditions. The factory
default is set to the highest level. To adjust file backlight of the
Navigator module, press the _ key until the displayreads, "Select a menu item." Using the anow keys move to the
mode. Press _ to obtain access to thisConfigurationmode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
Pressing 'e " "will cau. the OFF to flash. Use the up
or down re'row keys to change "OFF" to "ON". Pressing
will illuminate all LEDs and display all pixels in the
view screen. Pressing the up and down arrow keys simulta-neously allows the user to adjust the display brightness. The
display will read:
Adjust Brightness+
Use the up or down arrow keys to adjust screen brigNness.
Press _ to accept the change. The Navigator module
will keep this setting as long as it is plugged in to the LEN bus.
Fig. 1 -- Accessory Navigator Display Module
RUNSTATUS
Auto Display(VIEW)
RemoteUser Interface
(R.CCN)Machine
Starts/Hours(RUN)
CompressorRun Hours
(HOUR)
CompressorStarts
(STRT)
Fan RunHours(FAN)
CompressorDisable(CRUN)
PredictiveMaintenance
(MAIN)Software Versions
(VERS)
Table 1 -- ComfortLink TM Display Menu Structure
SERVICE TEMPERATURESTEST
Manual UnitTest Mode Temperatures
(TEST) (UNIT)Quick Circuit A
Test Mode Temperatures(QUIC) (CIR,A)
Circuit BTemperatures
(CIR,B)Circuit C
Temperatures(CIR.C)
MODE
SET INPUTS OUTPUTS CONFIGURATIONPRESSURES POINTS
Circuit A Cooling General Circuit A DisplayPressures Setpoints Inputs Outputs Configuration(PRC.A) (COOL) (GEM,I) (CIR.A) (DISP)
Circuit B Heating Circuit B UnitPressures Setpoints Outputs Configuration(PRC.B) (HEAT) (CIR.B) (UNIT)Circuit C Misc. Circuit C Service
Pressures Setpoints Outputs Configurations(PRC,C) (MISC) (CIR,C) (SERV)
General OptionsOutputs Configuration(GEM.O) (OPTN)
Reset,Demand Limit,Master/Slave
(RSET)
TIMECLOCK
Time of Day(TIME)
Day, Date(DATE)
Schedule 1(SCH1)
Schedule 2(SCH2)
Holidays(HOLI)
ServiceMaintenanceConfiguration
(MCFG)
OPERATINGMODES
OperatingControl Type
(SLCT)
OperatingModes
(MODE)
ALARMS
Reset CurrentAlarms(R.ALM)CurrentAlarms(ALRM)AlarmHistory
(H.ALM)
CONTROLS
General -- The 30XA air-cooled liquid chillers contain theCon_fbrtLink TM electronic control system that controls andmonitors all operations of the chillel: The control system iscomposed of several components as listed in the following sec-tions. All machines have at the ve U least a Main Base Board(MBB), Navigatoi r_'_module, electronic expansion valve board(EXV), fan board, Compressor Protection board, EmergencyOn/Off switch, an Enable-Off- Remote Contact switch.
Main Base Board (MBB) -- Tile MBB is tile heart ofthe Corqi0rtLink control system, which contains the majorportion of operating softwme and controls the operation of the
machine. See Fig. 2. The MBB continuously monitors input!output channel information received from its inputs and fromall other modules. The MBB receives inputs from status andfeedback switches, pressure transducers and thermistors. TheMBB also controls several outputs. Some inputs and outputs tocontrol the machine me located on other bo_uds, but are trans-mitted to or from the MBB via the internal communicationsbus. Information is transmitted between modules via a 3-wirecommunication bus or LEN (Ix)cal Equipment Network). TheCCN (Carrier Comfort Network®) bus is also supported. Con-nections to both LEN and CCN buses are made at TB3. For acomplete description of Main Base Board inputs and outputsand their channel identifications, see Table 2.
LOCATION OFSERIAL NUMBER
Fig. 2 -- Main Base Board
Table 2 -- Main Base Board Inputs and Outputs
DESCRIPTION
Power (24 vac supply)
Local Equipment Network
Carrier CommunicationNetwork
Chilled Water Flow Switch
Demand Limit Switch No. 1
Circuit A DischargePressure Transducer
Circuit B DischargePressure Transducer
Dual ChillerLWT Thermistor
Dual Set Point Input
Entering Water Thermistor
Leaving Water ThermistorOutdoor Air Thermistor
External ChilledWater Pump Interlock
Circuit A SuctionPressure Transducer
Circuit B SuctionPressure Transducer
Unit Status
Alarm Relay
Alert RelayCooler Heater
Isolation Valve A
Isolation Valve B
Isolation Valve C (Size 400-500
Oil Heater A (Size 080 only)
Oil Heater B (Size 080 only)
LEGEND
I/O -- Input or OutputLWT -- Leaving Water Temperature
INPU_OUTPUT
CWFS
Demand Limit SWl
DPTA
DPTB
DUAL
Dual Set Point
EWT
LWT
OAT
PMPI
SPTA
SPTB
Remote Contact-Off-Enable
ALM R
ALT R
CL-HT
ISVA
ISVBISVC
OIL HT A
OIL HTA
I/OTYPE
Switch
Switch
Pressure Transducer
Pressure Transducer
5k Thermistor
Switch
5k Thermistor
5k Thermistor
5k Thermistor
Switch
Pressure Transducer
Pressure Transducer
Switch
Relay
RelayContactor
Contactor
ContactorContactor
Contactor
Contactor
NAVIGATOR TM MODULEPOINT NAME
INPUTS_GEN.I_LOCK
INPUTS_GEN.I_DLS1
PRESSURES_PRC.A _DP.A
PRESSURES_PRC.B_DP.B
TEMPERATURES_UNIT_CHWS
INPUTS_GEN.I_DUAL
TEMPERATURES-_UNIT-_EWT
TEMPERATURES_UNIT_LWT
TEMPERATURES-_UNIT-_OAT
INPUTS_GEN.I_LOCK
PRESSURES_PRC.A_SP.A
PRESSURES_PRC.B_SP.B
INPUTS-_GEN.I-_ONOF
OUTPUTS_GEN. O_ALRM
OUTPUTS_GEN.O_ALRT
OUTPUTS--_GEN.O-_CO.HT
OUTPUTS-_GEN.O-_BVL.A
OUTPUTS-_GEN.O-_BVL.BOUTPUTS-_GEN. O-_B VL. C
OUTPUTS-_CIR.A --_HT.A
OUTPUTS_CIR.B_HT.B
CONNECTION POINT
Pin I NotationMBB-J1, MBB-J1A,
MBB-J1B
11 24 vac12 Ground
MBB-J9A, MBB-J9B,MBB-J9C
+
G
MBB-J12
+
G
MBB-J5B-CH 17
17
MBB-J4-CH13
MBB-J7A-CH6
5V 5 vdc Ref,
S SignalR Return
MBB-J7C-CH8
5V 5 vdc Ref,
S SignalR Return
MBB-J6-CH3
MBB-J4-CH12
MBB-J6-CH2
MBB-J6-CH1
MBB-J6-CH4
MBB-J4-CH 15A
MBB-J7B-CH7
5V 5 vdc Ref,
S SignalR Return
MBB-J7D-CH9
5V 5 vdc Ref,
S SignalR Return
MBB-J4-CH11
MBB-J3-CH24
MBB-J3-CH25
MBB-J3-CH26
MBB-J2A-CH 19
MBB-J2A-CH20MBB-J2C-CH22
MBB-J2C-CH22
MBB-J2C-CH23
Compressor Protection Module (CPM) -- Thereis one CPM per compressol: See Fig. 3. Tile device controls thecompressor contactol_, oil solenoid, loading/unloading thesolenoid, motor cooling solenoid (30XA080 only) and the oilseparator heater (30XA090-500). The CPM also monitorsthe compressor motor temperature, high pressure switch, oil lev-el switch, discharge gas temperature, oil pressure transducel:motor current, MTA setting and economizer pressure transduce1:The CPM responds to commands from the MBB (Main Base
Born'd) and sends the MBB the results of the channels it moni-tors via the LEN (Local Equipment Network). The CPM hasthree DIP switch input banks, Switch 1 (SI), Switch 2 ($2), andSwitch 3 ($3). The CPM board SI DIP switch configures thebo_ud for the type of st_utel: the location and type of the currenttransformer's and contactor failure instructions. See Table 3 fordescription of DIP switch 1 (SI) inputs. See Appendix C for DIPswitch settings.
DIPSWITCH 2
DIPSWITCH
(s3)
LOCATION OF
SERIAL NUMBER
J12 J1 J5
DIPSI© STATUS SWITCH 1
(LEN) ($1)
Fig. 3 -- Compressor Protection Module
DIP SWITCH POSITION
1
2,3
4,5,6
7
8
Table 3 -- DIP Switch 1 (Sl) Inputs
FUNCTION
Starter Configuration
Current Transformer (CT) Position
Current Transformer (CT) Selection
Contactor Failure Action
Not Used
SETTINGOFF
ON
OFF, OFF
OFF, ON
ON, OFF
ON, ON
OFF, OFF, OFF
OFF, OFF, ON
OFF, ON, OFF
OFF, ON, ON
ON, OFF, OFF
ON, OFF, ON
ON, ON, OFF
ON, ON, ONOFF
ON
MEANINGAcross-the-line Start
Y-Delta Start
CT is located in the main line
CT is located in the Delta of the motor
Reserved for future use
Invalid; will cause MTA configuration alarm100A/1V CT1
100A/0.503V CT2
100A/O. 16V CT3
Invalid; will cause MTA configuration alarm
Invalid; will cause MTA configuration alarm
Invalid; will cause MTA configuration alarm
Invalid; will cause MTA configuration alarm
Invalid; will cause MTA configuration alarmAll units should be off
Used when Shunt Trip is available in the unit
The CPM board dip switch $2 setting determines the musttrip mnps (MTA) setting. See Appendix C for DIP switch set-tings. The MTA setting which is calculated using the settings$2 must match the MTA setting in the software or an MTAalann will be generated.
See below for CPM bo_ud $3 address infommtion. SeeTable 4 for CPM inputs and outputs.
CPM-ADIP ] 1 ] :) ] ._ ] 4
Switch _Address: OFF
CPM-BO,P' J_LJ2_J2_[_4Switch
Address: I OFF I OFF I ON I OFF
CPM-C DIP ] 1 ] :2 ] R ] 4
Switch _Address: ON
NOTE: The CPM-A and CPM-B DIP switches m'e for _dlunits. Tile CPM-C DIP switches are for 30XA400-500 units.
Table 4 -- Compressor Protection Module Inputs and Outputs*
DESCRIPTION
Power (24 vac supply)
Local Equipment Network
Circuit X High Pressure Switch
Oil Level Switch
Must Trip Ampst
Configuration Switcht
Compressor X Motor Temperature
Compressor X Discharge Gas Temperature
Oil Pressure Transducer
Economizer Pressure Transducer
Compressor Current X Phase A**
Compressor Current X Phase B
Compressor Current X Phase C**
Compressor X 1M Contactor
Compressor X 2M Contactor
Compressor X S Contactor
Oil Heater Relay X (090-500)
Oil Solenoid X
Load Solenoid X
Unload Solenoid X
Motor Cooling Solenoid X (080)
*"X" denotes the circuit, A, B or C.l-See Appendix C for MTA settings.**Average current ,x depending on circuit A, B, or C.
INPUT/OUTPUT
HPS-X
Oil LS X
MTA
SW1
MTR-X
DGT X
OPT X
EPT X
CX1M
CX2M
CXS
Oil HTR X
Oil solenoid-X
Loading Solenoid-X
Unloading Solenoid-X
Gas Cooling Solenoid-X
I/O TYPE
Switch
Switch
8-PinDIP Switch
4-Pin DIP Switch
NTC Thermistor
NTC Thermistor
Pressure Transducer
Pressure Transducer
Current Sensor
Current Sensor
Current Sensor
Contactor
Contactor
Contactor
Contactor
Solenoid
Solenoid
Solenoid
Solenoid
NAVIGATOR TM MODULEPOINT NAME
Not available
OUTPUTS-_CIR.X-_OLS.X
CONFIGURATION-eUNIT MTA.X
Not available
TEMPERATURES-eCIR.X DGT:X
TEMPERATURES _CIR.X DG T_X
PRESSURES_PRC.X_Ot_X
PRESSURES_PRC.X_ECRX
Not available
INPUTS-eCUR.X
Not available
OUTPUTS_CIR.X_CRX
Not available
Not available
OUTPUTS_ClR.XHT:X
OUTPUTS_ClR.X_OLS.X
OUTPUTS_ClR.A_SLI.X
OUTPUTS_ClR.A_SL2.X
OUTPUTS-eClR.X-eDGT:X
CONNECTION POINT
Pin I NotationCPM-X-J1
11 I 24 vac
12 I GroundCPM-X-JP12
2 G
3CPM-×-J12
2 G
gCPM-×-J7-CH05
2
CPM-X-J6-CH06
2
II
CPM-X-J9-CH01
2
CPM-X-J9-CH02
2
CPM-X-JIOB-CH04
5V +, 5 vdc ref
S Signal
R Return
CPM-X-J10A
5V +, 5 vdc ref
S Signal
R Return
CPM-X-J8-CH01
2
CPM-×-J8-CH02
2
CPM-×-J8-CH3
2
CPM-×-J1-CH071
CPM-×-J2-CH8
1
CPM-X-J2-CH91
CPM-×-J2-CHIO
1
CPM-×-J2-CH121
CPM-×-J2-CH13
1 ICPM-X-J2-CH14
1
CPM-×-J2-CHIO
1
Electronic Expansion Valve (EXV) Board --The 30XA080 unit has one EXV bomd. The 30XA090-500units have one EXV botud per circuit. See Fig. 4. The bowd isresponsible for monitoring the suction gas temperature andeconomizer gas temperature thermistors. Tile board alsosignals the main EXV and economizer EXV (ECEXV) motorsto open or close. Tile electronic expansion valve boardresponds to commands from the MBB and sends the MBB theresults of the channels it monitors via the LEN (Local Equip-ment Network). See below for DIP switch information. SeeTables 5 and 6 for EXV inputs and outputs.
EXV BOARD A(080-450) 1 2 3 4 5 6 7 8
DIP SWITCH
Address: ON ON ON ON ON ON OFF ON
EXV BOARD B(090-500) 1 2
DIP SWITCHAddress: OFF ON
3 4 5 6 7 8
ON ON ON ON OFF ON
EXV BOARDC (400-500) 1 2 3
DIP SWITCH
Address: ON OFF ON
4 5 6 7 8
ON ON ON OFF ON
DIPSWITCH
LOCATION OF/ SERIAL NUMBER
Fig. 4 -- EXV Board
DESCRIPTION
Power (24 vac supply)
Local Equipment Network
Circuit A Suction Gas Thermistor
Circuit B Suction Gas Thermistor
Circuit A EXV
Circuit B EXV
Table 5 -- EXVA Board Inputs and Outputs (30XA080)
INPUWOUTPUT
SGTA
SGTB
EXV-A
EXV-B
I/OTYPE
5k Thermistor
5k Thermistor
Stepper Motor
Stepper Motor
NAVIGATOR TM MODULEPOINT NAME
TEMPERATURES_CIR.A _SGT.A
TEMPERATURES-_CIR.B-_SGT.B
OUTPUTS _CIR.A _EXV.A
OUTPUTS_CIR.B_EXV.B
CONNECTION POINT
Pin I NotationEXVA-J 1
11 24 vac12 Ground
EXVA-J4
1 +2 G
3EXVA-J3
TH
AEXVA-J3
TH
B
EXVA-J2A
1
2
3
4
EXVA-J2B
1
2
3
4
Table 6 -- EXV A,B,C Board Inputs and Outputs* (30XA090-500)
DESCRIPTION
Power (24 vac supply)
Local Equipment Network
Circuit X Suction Gas Thermistor
Circuit X Economizer GasThermistor
Circuit X EXV
Circuit X Economizer EXV
*"X" denotes the circuit, A, B or C.
INPUT/OUTPUT
SGTX
ECTX
EXV-X
ECEX_X
I/O TYPE
5k Thermistor
5k Thermistor
Stepper Motor
Stepper Motor
NAVIGATOR MODULEPOINT NAME
TEMPERATURES_CIR.X_SGT.X
TEMPERATURES-_CIR.X-_ECT.X
OUTPUTS _CIR.X _EXV.X
OUTPUTS_CIR.X_ECO.X
CONNECTION POINT
Pin I NotationEXVX_J1
11 24 vac12 Ground
EXVX-J4
1 +2 G
3
EXVX-J3
TH
A
EXVX-J3
TH
B
EXVX-J2A
1
2
3
4
EXVX-J2A
1
2
3
4
10
Fan Boards -- At least one f;m board is installed in each
unit. See Fig. 5A and 5B. There are two types of fan bomds,with and without an analog output signal for the low ambienttemperature head pressure control fan speed controllers. If aunit does not have low ambient temperature head pressure con-trol installed, it will not have the analog connection terminals.The fan bo;ud responds to commands from the MBB and sendsthe MBB the results of the channels it monitors via the Local
Equipment Network (LEN). See below for fan board A, B andC DIP switch addresses. See Tables 7-9 for inputs and outputs.
FAN BOARD(080) 1 2 3 4 5 6 7 8
DIP SWITCH
Address: OFF ON OFF OFF ON OFF ON OFF
FAN BOARD A(090-500) 1 2
DIP SWITCHAddress: OFF ON
3 4 5 6 7 8
OFF OFF ON OFF ON OFF
FAN BOARD B(140-500) 1 2
DIP SWITCH
Address: ON ON
3 4 5 6 7 8
OFF OFF ON OFF ON OFF
FAN BOARD C(400-500) 1 2
DIP SWITCH
Address: OFF OFF
3 4 5 6 7 8
ON OFF ON OFF ON OFF
LOCATION OF DIP SWITCH
JSERIALNUMBER /
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII.../7 _ _]TATUS SIC (LE_ _ _..IgN3NNl1345 _ _ [__ [_JFr_d@)
c _ C
TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8
J2 I/I
I®
I_
I+-
I®
Fig. 5A- Fan Board (AUX 1)with Low Ambient Temperature Head Pressure Control
LOCATION OF DIP SWITCH
cccccc QTB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8
/ cn_I cn_ I CH_I CH4I/ CHaI CH_I CHVI CHS IFig. 5B -- Fan Board (AUX 2) without Low Ambient Temperature Head Pressure Control
11
DESCRIPTION
Power (24 vac supply)
Local Equipment Network
Circuit A Low Ambient TemperatureHead Pressure Control Speed Signal
Circuit B Low Ambient TemperatureHead Pressure Control Speed Signal
Fan Contactor A1
Fan Contactor A2Fan Contactor A3
Fan Contactor A4
Fan Contactor B1
Fan Contactor B2
Fan Contactor B3
Fan Contactor B4
Table 7 -- Fan Board A Outputs (30XA080-120)
INPUT/OUTPUT I/O TYPE NAVIGATOR TM MODULEPOINT NAME
OUTPUTS-_CIR.A -_SPD.A
OUTPUTS_CIR.B _SPD.B
m m
m m
MM-A* 0-10 VDC
MM-B* 0-10 VDC
FCA1 Contactor
FCA2 ContactorFCA3 Contactor
FCA4 Contactor
FCB 1 Contactor
FCB2 Contactor
FCB3 Contactor
FCB4 Contactor
CONNECTION POINT
Pin J NotationFBA-J1
11 I 24 vac
12 I GroundFBA-J9
*Output only on low ambient temperature head pressure control (AUX1).
Table 8 -- Fan Board X Outputs (30XA140-350)
FBA-CH9
IFBA-CH10
IFBA-J2-CH 1
FBA-J2-CH2FBA-J2-CH3
FBA-J2-CH4(090-120)
FBA-J3-CH5
FBA-J3-CH6
FBA-J3-CH7
FBA-J3-CH8(090-120)
DESCRIPTION
Power (24 vac supply)
Local Equipment Network
Circuit X Low Ambient TemperatureHead Pressure Control
Speed Signal
Fan Contactor X1
Fan Contactor X2
Fan Contactor X3
Fan Contactor X4
Fan Contactor X5
Fan Contactor X6
Fan Contactor X7
Fan Contactor X8
INPUT/OUTPUT
MMm*
I/O TYPE
0-10 VDC
NAVIGATOR MODULEPOINT NAME
OUTPUTS_CIR.X_SPD.X
CONNECTION POINT
Pin Notation
FBX-J1
11 24 vac
12 Ground
FBX-J9
+
G
+
G
FBX-CH9
+
FCX1 Contactor FBX-J2-CH01
FCX2 Contactor FBX-J2-CH02
FCX3 Contactor FBX-J2-CH03
FCX4 Contactor FBX-J2-CH04
FCX5 Contactor FBX-J3-CH05
FCX6 Contactor FBX-J3-CH06
FCX7 Contactor FBX-J3-CH07
FCX8 Contactor FBX-J3-CH08
*Output only on units with low ambient temperature head pressure control installed (AUX1).NOTES:
1. Fan Board B used on 30XA140-350.2. "X" indicates circuit A or circuit B.3. See Fig. 9 for which contactor is used with circuit A or B.
12
DESCRIPTION
Power (24 vac supply)
Local Equipment Network
Circuit C DischargePressure Transducer
Circuit C SuctionPressure Transducer
Circuit C Low AmbientTemperature Head Pressure
Control Speed Signal
Fan Contactor C1
Fan Contactor C2
Fan Contactor C3
Fan Contactor C4
Fan Contactor C5
Fan Contactor C6
Fan Contactor C7
Fan Contactor C8
Table 9 -- Fan Board C Inputs and Outputs (30XA400-500)
INPUWOUTPUT I/O TYPE NAVIGATOR MODULEPOINT NAME
CONNECTION POINT(Unit Size)
Pin I NotationFBC-J1
11 24 vac12 Ground
FBC-J9
+
G
DPTC Pressure Transducer PRE$SURES-_PRC.C-_DP.C FBC-J7-CH 13
SPTC Pressure Transducer PRESSURES_PRC.C_SP.C
0-10 VDC
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
MM-C OUTPUTS-_CIR. C--_SPD. C
FCC1
FCC2
FCC3
FCC4
FCC5
FCC6
FCC7
FCC8
FBC-J8-CH14
FBC-CH9
FBC-J2-CH1FBC-J2-CH2FBC-J2-CH3FBC-J2-CH4FBC-J3-CH5FBC-J3-CH6FBC-J3-CH7
FBC-J3-CH8
Enable-Off-Remote Contact Switch (SWl) --This switch is installed in all units and provides the owner andservice person with a local means of enabling or disabling themachine. It is a 3-position switch used to control the chillel:When switched to tile Enable position the chiller is under itsown control. Move the switch to the Off position to shut thechiller down. Move tile switch to tile Remote Contact positionand a field-installed dry contact can be used to start tile chiller.The contacts must be capable of handling a 24-vac, 50-mAload. In the Enable and Remote Contact (dry contacts closed)positions, the chiller is allowed to operate and respond to thescheduling configuration, CCN configuration and set pointdata.
Emergency On/Off Switch (SW2) -- This switch isinstalled in ;til units. The Emergency On/Off switch shouldonly be used when it is required to shut the chiller off immedi-ately. Power to all modules is interrupted when this switch isoff"and all outputs from these modules will be turned off.
Energy Management Module (EMM) -- The EMMis available as a factory-installed option or as a field-installed
accessory. See Fig. 6. The EMM receives 4 to 20 mA inputs forthe tempemtme reset, cooling set point and demand limitfunctions. The EMM also receives tile switch inputs for thefield-installed second stage 2-step demand limit and ice donefunctions. The EMM communicates the status of all inputswith the MBB, and the MBB adjusts the control point, capacitylimit, and other functions according to tile inputs received. SeeTable 10.
Care should be taken when interfacing with other manufac-turer's control systems due to possible power supply differ-ences, full wave bridge versus half wave rectification,which could lead to equipment damage. The two diffelentpower supplies cannot be mixed. Crm_fortLink TM controlsuse half wave rectification. A signal isolation device shouldbe utilized if incorporating a full wave bridge rectifier sig-nal generating device is used.
13
©
INPUT
4-20 mA Demand Limit
4-20 mA TemperatureReset]Cooling Setpoint
Demand Limit SW2
Ice Done
Occupancy Override
Remote Lockout Switch
SPT
OUTPUT
% Total CapacityRUN R
SHD R
NOTE: Used on 30XA080-500.
Fig. 6 -- Energy Management Module
Table 10 -- Energy Management Module (EMM) Inputs and Outputs
DESCRIPTION I/O TYPE I/O POINT NAME CONNECTION POINT
4-20 mA Demand Limit 4-20 mA INPUTS-_GEN.I-_DMND EMM-J7B-CH6
4-20 mA Temperature Reset/ 4-20 mA INPUT$-_GEN.I-_RSET EMM-J7A-CH5Cooling Set point
Demand Limit Step 2 Switch Input INPUT$-_GEN.I-_DLS2 EMM-J4-CH9
Ice Done Switch Switch Input INPUTS-_GEN.I-MCE.D EMM-J4-CH 11A
Occupied Schedule Override Switch Input INPUTS-_GEN.I-_OCCS EMM-J4-CH8
Chiller Lockout Switch Input INPUT$-_GEN.I-_RLOC EMM-J4-CH 10
Space Temperature Thermistor 10k Thermistor TEMPERATURE-_UNIT-_$PT EMM-J6-CH2
DESCRIPTION I/O TYPE I/O POINT NAME CONNECTION POINT
0-10 vdc OUTPUTS-+GEN.O-+CATO EMM-J8-CH7
Run Relay Relay OUTPUT$-_GEN.O-_RUN EMM-J3-CH25
Shutdown Relay Relay OUTPUTS-_GEN.O-_SHUT EMM-J3-CH24
Local Equipment Network --Information is trans-mitted between modules via a 3-wire cornmunication bus or
LEN (Local Equipment Network). External connection to theLEN bus is made fit TB3.
Board Addresses -- All bofu'ds (except the Main Base
Board, Energy Management Module Board, find CompressorProtection Module Bornd) have 8-position DIP switches.
Addresses for all boards ate listed with the Input!Output Tablesfor each board,
Control Module Communication
RED LED -- Proper operation of the control boards can bevisually checked by looking at file red status LEDs (ligltt-emitting diodes). When operating correctly, the red statusLEDs will blink in unison at a rate of once every 2 seconds. Ifthe red LEDs are not blink in unison, verify that correct poweris being supplied to all modules. Be sure that the Main Base
Board (MBB) is supplied with the cunent soflwme. If neces-sary, teload current soflwate. If tlte problem still persists,replace the MBB. A red LED that is lit continuously or blink-ing at a rate of once per second or faster indicates that the bomdshould be replaced.
GREEN LED -- All boards have a green LEN (SIO) LEDwhich should be blinking whenever power is on. If the LEDsare not blinking as described check LEN connections forpotential communication errors fit the board connectot_. SeeInput/Output Table 2, and 4-10 for LEN Connector designa-tions. A 3-wire bus accomplishes communication betweenmodules. These 3 wires tun in parallel from module to module.The J9A connector on the MBB provides communication di-rectly to the Navigator :m display module.
YELLOW LED- Tlte MBB has one yellow LED. TheCmtier Comfort Network® (CCN) LED will blink duringtimes of network communication.
14
Carrier Comfort Network@ (CCN) Interface --All 30XA units can be connected to the CCN, if desired. Tilecommunication bus wiring is a shielded, 3-conductor cablewith &'ain wire and is field supplied and inst;flledi The systemelements are connected to the communication bus in a daisychain arrangement. The positive pin of each system elementcommunication connector must be wired to the positive pins ofthe system elements on either side of it, that is also required forthe negative and signal ground pins of each system element.Wiring connections for CCN should be made at TB3. Consultthe CCN Contractor's Manu;d for further information. SeeFig. 7.
NOTE: Conductors and &'ain wire must be 20 AWG (Ameri-can Wire Gage) minimum stranded, tinned coppel: Individualconductors must be insulated with PVC, PVC/nylon, vinyl,Teflon, or polyethylene. An aluminum/polyester 100% foilshield and an outer jacket of PVC, PVC/nylon, chrome vinyl,or Teflon with a minimum operating temperature range of-20 C to 60 C is required. See Table 11 for recommended wiremanufacturers and part numbers.
Table 11 -- CCN Communication Bus Wiring
MANUFACTURER
AlphaAmerican
Belden
ColumbiaManhattan
Quabik
PART NUMBER
Regular Wiring1895
A21451
8205
D6451M 13402
6130
Plenum Wiring
A48301884421
M64430
It is important when connecting to a CCN communicationbus that a color-coding scheme be used for the entire networkto simplify the installation. It is recommended that red be usedfor the signal positive, black for the signal negative, and whitefor the signal ground. Use a similar scheme for cables contain-ing different colored wires.
At each system element, the shields of its communicationbus cables must be tied togethel: If the communication bus isentirely within one building, the resulting continuous shieldmust be connected to a ground at one point only. If the commu-nication bus cable exits from one building and entel.s another.the shields must be connected to grounds at the lightningsuppressor in each building where the cable enters or exits thebuilding (one point per building only). To connect the unit tothe network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white(ground), and black (-) conductors. (Substitute appropri-ate colol.'s for different colored cables.)
3. Connect the red wire to (+) terlninal on TB3 of the plug,the white wire to COM termimd, and the black wire to the(-) terminal.
4. The RJI 4 CCN connector on TB3 can also be used, but isonly intended for temporary connection (for example, alaptop computer running Service Tool).
IMPORTANT: A shorted CCN bus cable will preventsome routines from running and may prevent the unitfrom starting. If abnormal conditions occur, discon-nect the CCN bus. If conditions return to normal,check the CCN connector and cable. Run new cable if
necessary. A short in one section of the bus can causeproblems with all system elements on the bus.
Configuration OptionsRAMP LOADING (Configuration_OPTN--_RL.S), limitsthe rate of change of leaving fluid temperature. If the unit is ina Cooling mode and configured for Ramp Ix_ading, the controlmakes 2 comparisons before deciding to change stages ofcapacity. The control c_dculates a temperature differencebetween the control point and leaving fluid temperature. If thedifference is greater than 4° F (2.2 ° C) and the rote of change(°F or °C per minute) is more than the configured Cool RampIx_ading (Setpoints_COOL_'RMP), the control does not_dlow any changes to the current stage of capacity.
MINUTES OFF TIME (Configuration _OPTN---_ DELY) isa time delay added to the start when the machine is com-manded ON. This is a field configurable item from 1 to15 minutes. The factory default is 1 minute. This feature isuseful when multiple units are installed. Staggering the startwill reduce the inrush potential.
Dual Chiller Control--The dual chiller routine isavailable for the control of two units installed in series orparallel supplying chilled fluid on a common loop. One chillermust be configured as the master chillel; the other as the slavechillel: For parallel chiller application, an additional leavingfluid temperature thermistor (Dual Chiller LWT) must beinstalled in the common chilled water piping as described inthe Installation Instructions for both the master and slave
chillel_. See the Field Wiring section in the 30XA InstallationInstructions for Dual Chiller LWT sensor control wiring. Achilled water flow switch is factory-installed for each chillel:DUAL CHILLER PUMP CONTROL FOR PARALLELAPPLICATIONS--It is recommended that a dedicated
pump be used for each unit. Chiller must st;ut and stop its ownwater pump located on its own piping. If pumps are not dedi-cated for each chillel: chiller isolation valves are required: eachchiller must open and close its own isolation v_dve.
CCN
(+) (C0t'd) (-) SHIELD
oDD oLEN CCN
Fig. 7 -- ComfortLink TM CCN Communication Wiring
To Next
DeYk:e
15
DUAL PUMPCONTROLFOR SERIESCHILLERAPPLICATIONS--If pumpcontrolis required, the chillerpump needs to be controlled by the master chiller only. Thecontrol of the slave chiller is directed through commandsemitted by the master chillel: The slave chiller has no action inmaster/slave operations; it shall only verify that CCN commu-nication with its master is present. See the Dual ChillerSequence of Operation section on page 49.
Use dual chiller control to designate a lead chiller betweenthe master and slave chillel: Configure the Lead/Lag BaltmceSelect (Configuration _RSET---)LLBL) to ENBL to base theselection on the Lead/Lag Balance Delta (Configuration_RSET--+LLBD) between the master and slave mn hours. Ifthe run hour difference between the master and the slave
remains less than LLBD, the chiller designated as the lead willremain the lead chillel: The Lead/Lag changeover between themaster and the slave chiller due to hour balance will occur dur-
ing chiller operating odd days, such as day 1, &_y 3, and &ty 5of the month, at 12:00 a.m. If a lead chiller is not designated,the master chiller will always be designated the lead chiller
The dual chiller control algorithm has the ability to be con-figured for series or parallel operation. To configure chillers inseries, set Configuration--_RSET---_S'ERI to YES for seriesoperation, or NO for parallel operation. Both the master andslave chiller must be configmed the same.
The dual chiller control algorithm has the ability to delaythe start of the lag chiller in two ways. The Lead PulldownTime (Configuration---)RSET---)LPUL) provides a field con-figurable time delay of 0 to 60 minutes. This time delay givesthe lead chiller a chance to remove the heat that the chilled wa-ter loop picked up while being inactive during an unoccupiedperiod. The Lead Pulldown Time pmameter is a one-time timedelay initiated after starting the lead chillel: manually or by aschedule, before checking whether to st_ul an additional chillel:This routine provides the lead chiller an opportunity to pulldown the loop temperature before starting another chillel: Thesecond time delay. Lead/Lag Delay (Configuratiml _RSET--+LLDY) is a time delay imposed between the last stage of thelead chiller and the start of the lag chillel: This preventsenabling the lag chiller until the lead/lag delay timer hasexpired. See Tables 12 and 13.
Capacity Control- The control system cycles com-pressors and positions the slide valve of each compressor tomaintain the user-configured leaving chilled fluid temperatureset point. Entering fluid temperature is used by the Main BaseBoard (MBB) to determine the temperature drop across thecooler and is used in determining the optimum time to add orsubtract capacity. Return fluid temperature, space temperature(requires additional sensor), or outdoor-air temperature resetfeatures can automatically reset the leaving chilled fluidtemperatme set point. It can also be reset fiom an external 4 to20-mA signal (requires Energy Management Module). Tem-peratme leset requires a temperature sensor and the EnergyManagement Module.
The control has an automatic lead-lag feature built in forcircuit and compressor starts. If enabled, the control will deter-mine which circuit (Configuration--cOPTN--cLLCS=O) andcompressor to start to even the wear The compressor wearfactor (combination of starts and run hours) is used to deter-mine which compressor starts.
Coml)ressor Wear Fa_or = (Coml)mssor Starts) + 0.1(Coml)ressor Run Hours)
In this case, the cimuit with the lowest compressor wearNctor is the cimuit that stags first. The following settings willdetermine what cimuit stags first:Configuratiml _OPTN---)LLCS=I, Circuit A startsConfiguration _OPTN---)LLCS'=2, Circuit B startsConfiguratiml _OPTN---)LLCS=3, Circuit C starts
If Minimum Ix)ad Control is enabled (Configuration---)UNIT---)HGBP=I), the valve will be opemtiomd only duringthe first stage of cooling.
EQUAL LOADING (Configuration _OPTN---_LOAD=O) --The circuit which has started will maintain minimum stage ofcapacity and slide valve fully unloaded; when additional capac-ity is required the next circuit with the lowest compressor wearfactor is st:u-ted with the slide valve at minimum position. Asadditiomd capacity is required the slide v_dve for a circuit willbe adjusted in approximately 5% increments to match capacityrequirements. The control will alternate between circuits tomaintain the same percentage of capacity on each circuit. SeeFig. 8.
STAGE LOADING -- If stage-loading is selected (Configu-ration _OPTN--+LOAD=I), the cimuit which has stmted willgradu_dly load the slide valve to match capacity requirementsuntil the circuit is fully loaded. Once the circuit is fully loadedand additional capacity is required, the control will stmt an ad-ditional circuit fully unloaded and gradu_dly unload the circuitwhich was lially loaded to match capacity requirements.
The capacity control algorithm runs every 30 seconds. Thealgorithm attempts to maintain the Control Point at the desiredset point. Each time the capacity control _dgorithm runs, thecontrol reads the entering and leaving fluid temperatures. Thecontrol determines the rate at which conditions are changingand calculates 2 variables based on these conditions. Next, acapacity ratio is calculated using the 2 variables to determinewhether or not to make any changes to the current stages of ca-pacity. This ratio v_due ranges from -100 to +100%. If the nextchange of capacity is a compressol: the control stmts (stops) acompressor when the ratio reaches + 100% (-100%). If the nextchange of capacity is to reposition the slide valve, the controlenergizes both slide valve solenoids when ratio is +60% anddeenergizes both slide valve solenoids when ratio is -60%. [finst_dled, the minimum load valve solenoid will be energizedwith the first stage of capacity. Minimum load valve value isfixed at 10 tons in the total capacity calculation. The controlwill also use the minimum load valve solenoid as the last stageof capacity before turning off the last compressol: A delay of90 seconds occurs after each capacity step change. A delay of3 minutes occm_ after each compressor capacity step change.
16
Table 12 -- Configuring the Master ChillerMODE KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION [] DISP
] UNIT
] SERV
] OPTN
] CCNA CCN Address Confirm address of chiller. The master and slave chiller musthave different addresses,
] 1 Factory default address is 1.
[] CCNA
] Confirm the bus number of the chiller. The master and slaveCCNB CCN Bus Number chiller must be on the same bus.
] 0 Factory default is o.
[] CCNB
] OPTN
] RSET Reset Cool and Heat Trnp
] CRST Cooling Reset Type
] x 5 MSSL Master/Slave Select
] o Disable
] O Disable Flashing to indicate Edit mode. May require Password.
] 1 Master Use up arrows to change value to 1.
] 1 Accepts the change.
] MSSL
] SLVA Slave Address
[] t] 1 Flashing to indicate Edit mode.
] Use up arrows to change value to 2. This address must2 match the address of the slave chiller.
] 2 Accepts the change.
] SLVA
] LLBL Lead/Lag Balance Select
] DSBL Factory Default is DSBL.
] LLBL
] LLBD Lead/Lag Balance Delta
] 168 Factory Default is 168.
] LLBD
] LLDY Lead/Lag Delay
] 10 Factory Default is 10.
] LLDY
] LAGP Lag Unit Pump Select
] O Off if U Stp Factory Default is O, Off if unit is stopped.
] LAGP
] LPUL Lead Pulldown Time
] 0 Factory Default is O.
[]] At mode level.
] SER1 Chillers in Series
OPERATINGMoDES [] OPER Operating Control Type
] o Switch Control Master chiller should be configured for job requirements,Switch Control, Time Schedule, or CCN.
] At mode level.
NOTE: Bold values indicate sub-mode level.
]7
Table 13 -- Configuring the Slave Chiller
MODE KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION [] DISP
] UNIT
] SERV
] OPTN
] CCNA CCN Address Confirm address of chiller. The master and slave chillermust have different addresses.
] 1 Factory default address is 1. The slave chiller addressmust match what was programmed in the Master ChillerSLVA item.
] 1 Flashing to indicate Edit Mode.
] 2 This item must match Master Chiller SLVA item.
] 2 Accepts the change.
] CCNA
] CCNB CCN Bus Number Confirm the bus number of the chiller. The master andslave chiller must be on the same bus.
] 0 Factory default bus number is 0.
[] CCNB
] OPTN
] RSET Reset Cool and Heat Tmp
] CRST Cooling Reset Type
] x 5 MSSL Master/Slave Select
] 0 Disable
] 0 Disable Flashing to indicate Edit mode. May require Password
] 2 Slave Use up arrows to change value to 2.
] 2 Accepts the change.
] MSSL
] SLVA Slave Address Not required.
] LLBL Lead/Lag Balance Select Not required.
] LLBD Lead/Lag Balance Delta Not required.
] LLDY Lead/Lag Delay Not required.
] LAGP Lag Unit Pump Select Not required.
] LPUL Lead Pulldown Time Not required.
] At mode level
] SER1 Chillers in Series
OPERATING MODES [] OPER Operating Control Type
] 0 Switch Control
] 0 Flashing to indicate Edit Mode.
] 2 CCN Control Use up arrows to change value to 2.NOTE: Must be configured for CCN.
] 2 Accepts the value.
] OPER
] At mode level
NOTE: Bold values indicate sub-mode level.
18
100 _ Lead compressor can fall anywhere in this area _Lead Compressor Loading[when load between 40%~65% fAN --Lag Compressor Loading
j//,/ _ --Lead Compressor Unloading
_Lag Compressor Unloading
8O
.___¢>, LOADING_ '_ LOx_ING _
c)
_- 40o
c)
20
Lag compressor can fail anywhere in this area Iwhen cad between 40%~65% I
I
0
0 100
Load (%)
Equal Circuit Loading
Unit Loading Unloading (Staged circuit loading)
100
8O
o_ 608
y__ 40
2O
1CO
Lead (%)
Staged Circuit Loading
Fig. 8 -- Compressor Loading and Unloading
19
CAPACITY CONTROL OVERRIDES (Run Status-+VIEW _CAP.S) -- The following ovemdes will modify thenorlnal operation routine. If any of the following override con-ditions listed below is satisfied, it shall determine the capacitychange instead of the normal control. Overrides are listed bypriority order and ale often linked to unit operating modes. SeeTable 14 for a list of operating modes and correspondingoverrides.
Override #1 : Cooler Freeze Protection -- This ovemde at-tempts to avoid the freeze protection alarm. If the LeavingWater Tempelature is less than Brine Freeze Set Point (Config-uration--¢SERV--cLOSP) + 2.0 ° F (1.1 ° C) then a stage of ca-pacity is removed.
NOTE: The freeze set point is 34 F (1.1 C) for fresh watersystems (Configuration ---_ERV---)FLUD=I). The freeze setpoint is Brine Freeze Set Point (Configuration--_S'ERV--_LOSP), for Medium Temperature Brine systems (Configu-ration ---_S'ERV--)FLUD=2 ).
Override #2: Circuit A Low Saturated Suction Temperaturein CoolingOverride #3: Circuit B Low Saturated Suction Temperaturein CoolingOverride #4: Circuit C Low Saturated Suction Temperaturein Cooling -- These overrides attempt to avoid the low suctiontemperatme alarlns, and is active only when more than onecompressor in a circuit is ON. The slide valve in the affectedcircuit will be decreased in position if the Saturated SuctionTemperature is less than Brine Freeze Set Point (Configura-tion--+SERV--+LOSP) -18.0 F (-10 C) for 90 seconds, or theSaturated Suction Temperature is less than -4 F (-20 C).
Override #5: Ix_w Temperature Cooling and High Tempera-ture Heating -- This ovenide removes one stage of capacitywhen the difference between the Control Point (Run Status--)VIEW_CTPT) and the Leaving Water Temperature (RunStatus--+VIEW--+LWT) reaches a predetermined limit and therate of change of the water is 0 or still decreasing.
Override #6: Ix_w Temperature Cooling and High TemperatmeHeating -- This ovenide lemoves two stages of capacity whenthe Entering Water Temperature (Run Status--+VIEW--+EWT)is less than the Control Point (Run Status--+VIEW_CTPT.)
Override #7: Ramp Loading -- No capacity stage increasewill be made if the unit is configured for ramp loading (Cottfig-uration--)OPTN--)RL.S=ENBL) and if the diffelence be-tween the Leaving Water Temperatme trod the Control Point isgleater than 4° F (2.2 ° C) and the rate of change of the leavingwater is greater than Cool Rmnp Ix_ading Rate (Se&oints-eCOOL_CRMP). Operating mode 5 (MD05) will be in effect.Override #8: Service Manual Test Override -- The manu:d
test consists in adding a stage of capacity eve U 30 seconds, un-til the control enables all of the requested compressors andMinimum Ix_ad Control selected in the Crml/brtLink TM displayService Test menu. All safeties and higher priority overridesale monitored and acted upon.Override # 9: Demand Limit -- This override mode is ttctive
when a command to limit the capacity is received. If thecurrent unit capacity is gleater than the active capacity limitv:due, a stage is removed. If the current capacity is lower thanthe capacity limit value, the control will not add a stage thatwill result in the new capacity being gleater then the capacitylimit v_due. Operating mode 4 (MD04) will be in effect.
Override #10: Cooler Interlock Override -- This overrideprohibits compressor operation until the Cooler Interlock(hlputs _GEN.I---_LOCK) is closed.
Override #11 : High Temperature Cooling and Low Temper-ature Heating -- This override algorithm runs once when theunit is switched to ON. If the difference between the LeavingWater Temperatme (Run Status --+VIEW--+LWT) and the Con-trol Point (Run Status---_VIEW_42TPT) exceeds a c:dculated
value and the rate of change of the water temperatureis greaterthan -0.1 ° F/rain, a stage will be added.
Table 14 -- Operating Modes andCorresponding Overrides
1
2
3
4
5
67
8
9
10
11
12
13
14
15
1617
18
19
20
21
22
23
24
25
26
27
28
29
3O
31
32
33
34
35
OPERATING MODES
Startup Delay in Effect
Second Setpoint in UseReset in Effect
Demand Limit Active
Ramp Loading ActiveCooler Heater Active
Cooler Pumps Rotation
Pump Periodic Start
Night Low Noise Active
System Manager Active
Mast Slave Ctrl Active
Auto Changeover Active
Free Cooling ActiveReclaim Active
Electric Heat Active
Heating Low EWT Lockout
Condenser Pumps RotationIce Mode in Effect
Defrost Active on Cir A
Defrost Active on Cir B
Low Suction Circuit A
Low Suction Circuit B
Low Suction Circuit C
High DGT Circuit A
High DGT Circuit B
High DGT Circuit C
High Pres Override Cir A
High Pres Override Cir B
High Pres Override Cir C
Low Superheat Circuit A
Low Superheat Circuit B
Low Superheat Circuit C
High Compressor CurrentCircuit A
High Compressor CurrentCircuit B
High Compressor CurrentCircuit C
OVERRIDES
9 Demand Limit7 Ramp Loadng
13 Minimum On/Off andOff/On Time Delay
22 Minimum On Time Delay
m
m
m
m
m
23 Circuit A LowSaturated SuctionCircuit A LowRefrigerant
24 Circuit B LowSaturated SuctionCircuit B LowRefrigerant
25 Circuit C LowSaturated SuctionCircuit C LowRefrigerant
26 High Discharge GasOverride Circuit A
27 High Discharge GasOverride Circuit B
28 High Discharge GasOverride Circuit C
16 Circuit A HighPressure Override
17 Circuit B HighPressure Override
18 Circuit C HighPressure Override
41 Circuit A HighCurrent Override
42 Circuit B HighCurrent Override
43 Circuit C HighCurrent Override
Override #12: High Temperature Cooling and Low Temper-ature Heating -- This override runs only when MinimumLoad Control is Enabled, (Configuration ---)SERV--cHGBP) is1, 2 or 3. This ovenide will add a stage of capacity if the nextstage is Minimum Load Control, when the difference betweenthe Leaving Water Temperature (Run Status---)VIEW---)LWT)and the Control Point (Run Status --+VIEW_CTPT) exceeds acalculated value and the rate of change of the water tempera-ture is greater than a fixed value.
20
Override #13: Minimum On/Off and Off/On Time Delay --Whenever a capacity change has been made, the control willremain at this capacity stage for the next 90 seconds. Duringthis time, no capacity control algorithm cCdculations will bemade. If the capacity step is a compressor, an additional90-second delay is added to the previous hold time (see Over-ride #227. This override allows the system to stabilize beforeanother capacity stage is added or removed. If a condition of ahigher priority override occurs, the higher priolity override willtake precedence. Operating Mode 10 (MDI 0) will be in effect.
Override #14: Slow Change Override -- This override pre-vents compressor stage changes when the leaving temperatureis close to the control point and slowly moving towards thecontrol point.
Override #15: System Manager Capacity Control -- If aChillervisor module is controlling the unit and the Chillervisormodule is controlling multiple chillers, the unit will increasecapacity to attempt to load to the demand limited v_due.
Override #16: Circuit A High Pressme OverrideOverride #17: Circuit B High Pressure OverrideOverride #18: Circuit C High Pressure Override -- This over-ride attempts to avoid a high pressure failure. The algorithm isrun evely 4 seconds. If the Saturated Condensing Temperaturefor the circuit is above the High Pressure Threshold (Configu-ration--+ SERV--+HP.TH) then the position of slide valve willbe unloaded.
Override #19: Standby Mode -- This override algorithm willnot allow a compressor to run if the unit is in Standby mode,(Run Status--)VIEW--_HC.ST=2).
Override #22: Minimum On Time Delay -- In addition toOverride #13 Minimum On/Off and Off/On Time Delay, forcompressor capacity changes, an additional 90-second delaywill be added to Override #13 delay. No compressor will bedeenelgized until 3 minutes have elapsed since the last com-pressor has been turned ON. When this override is active, thecapacity control _dgorithm calculations will be perf(mned, butno capacity reduction will be made until the timer has expired.A control with higher precedence will override the MinimumOn Time Delay.Override #23: Circuit A Low Saturated Suction
Temperature in CoolingOverride #24: Circuit B Low Saturated SuctionTemperature in CoolingOverride #25: Circuit C Low Saturated Suction Tempera-ture in Cooling -- If the circuit is operating in an gu'ea close tothe operational limit of the compressol: the circuit capacity willremain at the same point or unload to raise the saturated suctiontemperatme. This _dgorithm will be active if at least 1 comples-sot in the circuit is on and one of the following conditions is tree:
1. Saturated Suction Temperature is less than the BrineFleeze Setpoint (Configuration --_;ERV--cLOSP) - 6° F(3.3 ° C).
2. Saturated Suction Telnperature is less than the BrineFleeze Setpoint (Configuration--cSERV--cLOSP) andthe circuit approach (Leaving Water Temperature - Satu-rated Suction Temperature) is greater than 15° F (8.3 ° C)and the Circuit Supoheat (Discharge Gas Temperatme -Saturated Discharge Temperatme) is greater than 25° F(13.9 ° C).
NOTE: The freeze set point is 34 F (1.1 C) for freshwater systems (Configuration ---_S'ERV---_FLUD=I). Thefreeze set point is Brine Freeze Set Point (Conjqguration--+SERV--+LOSP), for Medium Temperature Brinesystems (Configuration ---_SERV---_FLUD=2).
If any of these conditions gue met, the appropriate operatingmode, 21 (Circuit A), 22 (Circuit B) or 23 (Circuit C) will be ineffect.
Override #26: Circuit A High Discharge Gas OverrideOverride #27: Circuit B High Discharge Gas OverrideOverride #28: Circuit C High Discharge Gas Override --When the temperature is above the limit curve minus 2° F(1.1 ° C) increase in capacity will not be allowed. This ovemdewill remain active until the DG_" goes below the limit curve by-3 ° F (-1.7 ° C).
OvelTide #34: Circuit A Low Refi'igerant ChargeOverride #35: Circuit B Low Refiigerant ChargeOverride #36: Circuit C Low Refrigerant Charge -- The ca-pacity override attempts to protect the compressor from start-ing with no refiigemnt in the circuit. This algorithm runs onlywhen the circuit is not operational (no compressors are ON).There are several criteria that will enable this override:
1. The saturated suction temperature or saturated dischmgetemperature is less than -13 F (-10.6 C).
2. All of these conditions must be true:
a. The saturated suction temperature or saturateddischarge temperature is less than leaving watertemperature by more than 5.4 ° F (3.0 ° C).
b. Saturated suction temperature or saturated dis-charge temperature is less than 41 F (5 C).
c. Outdoor air temperature is less than 32 F (0 ° C).
d. Saturated suction temperature or saturated dischargetemperature is less than the outdoor air temperatureby more than 5.4 ° F (3.0 ° C).
3. All of these conditions must be true:
a. The saturated suction temperature or saturateddischarge temperature is less than leaving watertemperature by more than 5.4° F (3.0° C).
b. Saturated suction temperature or saturated dis-charge temperature is less than 41 F (5 C).
c. Saturated suction temperature or saturated dis-charge temperature is less than the brine freezepoint (Configuration--+SERV--+LOSP) by morethan 6° F (3.3° C).
NOTE: The freeze set point is 34 F (1.1 C)for fresh water systems (Configuration---)SERV
--+FLUD=I). The freeze set point is brine freezeset point (Configuration--_SERV--_LOSP), formedium temperature brine systems (Configura-tion --_SERV--)FLUD=2 ).
All of these conditions must be true:
a. The saturated suction temperature or saturateddischarge temperature is less than leaving watertemperature by more than 5.4 ° F (3.0 ° C).
b. Saturated suction temperature or saturated dischargetemperature is less than 41 F (5 C).
c. Saturated suction temperature or saturated dischargetemperature is less than the outdoor air temperatureby more than 9° F (5 ° C).
If any of these conditions 1,2, 3 or 4 are met, the appropri-ate operating mode, 21 (Circuit A), 22 (Circuit B) or 23(Circuit C) will be in effect.
Override #41 : Circuit A High Current OverrideOverride #42: Circuit B High Current OverrideOverride #43: Circuit C High Current Override
This override attempts to avoid an overcurrent failure. The_dgorithm is run every 4 seconds. If the compressor current isgreater than 79% of must trip amps (MTA) but less than 85%MTA then the capacity will be held at current capacity. If thecompressor current is greater than 85% MTA then capacitywill be reduced by repositioning the slide valve until thecurrent is less than 85% MTA (Configuration--cUNIT--€MTA.X).
21
Ovenide #44: Circuit A High Suction Superheat at Part LoadOverride #45: Circuit B High Suction Superheat at Part LoadOverride #46: Circuit C High Suction Superheat at Part Load-- If the compressor of the circuit is on, the compressor currentis no more than 30% of the MTA, main EXV is more than 90%open and the suction superheat is higher than the superheatcontrol point for mole than 5 minutes, the circuit will be shutdown.
Override #50: Circuit A MCHX MOP ControlOverride #51 : Circuit B MCHX MOP ControlOverride #52: Circuit C MCHX MOP Control -- This over-ride is not cmrently used or supported.
Override #53: Circuit A Delay for Unloading the Slide ValveOverride #54: Circuit B Delay for Unloading the Slide ValveOverride #55: Circuit C Delay for Unloading the SlideValve -- If the compressor is stopped normally, no slidevalve delay is applied. If the circuit is shut down by lockedrotor alarm, full delay is applied before the compressor isallowed to stmt (20 minutes for a compressor with 165 to185 tons of nominal capacity, 8 minutes for a compressor with90 to 120 tons of nominal capacity, and 5 minutes for acompressor with 45 to 60 tons of nominal capacity). If acompressor is shut off on an alarm, this delay is adjusted basedon the last nominal capacity of the last compressol:
NOTE: Refer to Tables IA and IB in the 30XA InstallationInstructions for unit compressor nominal capacity..
Override #56: Circuit A Delay for Refrigeration IsolationValve to OpenOverride #57: Circuit B Delay for Refrigeration IsolationValve to OpenOverride #58: Circuit C Delay for Refrigeration IsolationValve to Open -- This override allows the discharge motor-ized ball valve to open before the compressor st_uts. The delayis 2 minutes and 30 seconds.
Override #59: Circuit A Low Oil LevelOverride #60: Circuit B Low Oil LevelOverride #61 : Circuit C Low Oil Level -- This override isonly effective when the circuit is not running. It shall preventthe circuit from starting up with a low oil level. If this overrideoccuLs three times, the low oil level alarm will be tripped.
Head Pressure Control--The Main Base Board
(MBB) controls the condenser fans to maintain the lowestcondensing temperature possible, and thus the highest unit eflS-ciency. The MBB uses the saturated condensing temperatureinput from the discharge pressure transducer to control thefans. Head pressure control is maintained through a calculatedset point which is automatically adjusted based on actualsaturated condensing and saturated suction temperatures so thatthe compressor(s) is (_ue) always operating within the manu-facturer's specified envelope (see Fig. 9). Each time a f_m isadded the calculated head pressure set point will be raised
25 ° F (13.9 ° C) for 35 seconds to zdlow the system to stabilize.The control will automatically reduce the unit capacity as thesaturated condensing temperature approaches an upper limit.See capacity overrides 16-18. The control will indicate throughan operating mode that high ambient unloading is in effect. Ifthe saturated condensing temperature in a circuit exceeds thecalculated maximum, the circuit will be stopped. For thesereasons, there are no head pressure control methods or setpoints to entel: The control will turn off a fan stage when thecondensing temperature is below the minimum head pressurerequirement for the compressoc Fan sequences are shown inFig. 9.
LOW AMBIENT TEMPERATURE HEAD PRESSURECONTROL OPTION -- Units will st_ul and operate down to32 F C0° C) as standard. Operation to -20 F (-29 C) requiresoptional low ambient head pressure control as well as windbaffles (field fabricated and installed to _fllunits for operationbelow 32 F [0 ° C]) if wind velocity is anticipated to be greaterthan 5 mph (8 kp/h). Inhibited propylene glycol or other suit-able corrosion-resistant anti-freeze solution must be field sup-plied and installed in all units for unit operation below 34 F(1.1 C). Solution must be added to fluid loop to protect loopdown to 15° F (8.3 ° C) below minimum operating mnbienttemperature. Concentration should be based on expected mini-mum temperature and either "Burst" or "Freeze" protectionlevels. At least 6 gal per ton (6.5 l/kW) of water volume is therecommended minimum for a moderate system load.
For low-ambient temperature operation, the lead fan on acircuit can be equipped with low ambient temperature headpressure control option or accessory. The controller adjusts fanspeed to maintain the c_dculated head pressure set point.LOW AMBIENT TEMPERATURE HEAD PRESSURECONTROL OPERATING INSTRUCTIONS -- The 30XAlow ambient control is a vtuiable speed drive (VFD) that wuiesthe speed of the lead condenser fan in each circuit to maintainthe calculated head pressure control set point. The fan speedvaries in proporiion to the 0 to 10 vdc analog signal producedby the AUXI fan board. The display indicates motor speed inHz by default.
_eration -- The low ambient temperature head pressure con-troller is pre-configured to operate from a 0 to 10 vdc amfloginput signal present on terminals 3(AIN+) and 4(AIN-). Jump-ers between terminals 2 and 4 and terminals 5 and 8 (5 trod 9for 575-v drives) _ue lequired for proper operation. The diive isenabled based on an increase in the analog input signal above0 vdc. Output is varied from 0 Hz to 60 Hz as the analog signalincreases from 0 vdc to 10 vdc. When the signal is at 0 vdc thedrive holds the fan at 0 rpm. The head pressure control set pointis not adjustable. The MBB determines the control set point asrequired.
22
COMP B COMP A
g0XA080
COMP B COMP A
g0XA090-] 20
COMPB I PEB I COMPA
g0XA] 40, 160
COMPB I PEB I COMPA
g0XA180,200
COMP B I PEB I COMP A
@@@ @@@30XA220, 240
COMPB [ PEB l COMPA
@@@ @@@@30XA260
COMPB [ PEB I COMPA
30XA280
COMP B I PEB I COMP A
30XA300
COMPB I PEB l COMPA
@@@@@@@@@30XA325, 350
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
Fan Output Ckt A
Contactor Number
Fan Position
Fan Output Ckt B
Contactor Number
Fan Position
1 2 3 4 5 6 7 --
FC A1 FC A2 FC A_ -- FC B1 :C B2 FC B3
FM5 FM3 FM6 -- FM1 FM4 FM2
1 2 3 4 5 6 7 --
FC A1 FC A2 FC A_ -- FC B1 :C B2 FC B3
FM5 FM3 FM6 -- FM1 FM4 FM2
1 2 3 4 5 6 7 8
FC A1 FC A2 FC A_ :C A4 FC B1 :C B2 FC B3 FC B4
FM7 FM5 FM8 FM6 FM1 FM3 FM2 FM4
1 2 3 4 5 6 7 8
FC A1 FC A2 FC A_ :C A4 FC B1 :C B2 FC B3 FC B4
FM7 FM5 FM8 FM6 FM1 FM3 FM2 FM4
1 2 3 4 5 6 -- --
FC A1 FC A2 FC A_ :C A4 FC A_ :C A6 --
FM9 FM7 FM5 FM10 FM8 FM6 -- --
1 2 3 4 -- --
FC B1 FC B2 FC BS :C B4 -- --
FM1 FM2 FM3 FM4 -- --
1 2 3 4 5 6 -- --
FC A1 FC A2 FC AS :C A4 FC A_ :C A6 --
FM11 FM9 FM7 FM12 FM10 FM8 -- --
1 2 3 4 5 6 -- --
FC B1 FC B2 FC B_ :C B4 FC B_ :C B6 --
FM1 FM3 FM5 FM2 FM4 FM6 -- --
1 2 3 4 5 6 7 --
FC A1 FC A2 FC AS =C A4 FC A5 :C A6 FC A7
FM13 FM11 FM9 FM7 FM14 FM12 FM10
1 2 3 4 5 6 -- --
FC B1 FC B2 FC B_ =C B4 FC B_ :C B6 --
FM1 FM3 FM5 FM2 FM4 FM6 -- --
1 2 3 4 5 6 7 8
FC A1 FC A2 FC A_ :C A4 FC A_ :C A6 FC A7 FC A8 FC A9
FM15 FM13 FMll FM9 FM7 FM16 FM14 FM12 FM10
1 2 3 4 5 6 -- --
FC B1 FC B2 FC B_ :C B4 FC B_ :C B6 --
FM1 FM3 FM5 FM2 FM4 FM6 -- --
1 2 3 4 5 6 7 8
FC A1 FC A2 FC A_ :C A4 FC A5 :C A6 FC A7 FC A8 FC A9
FM15 FM13 FMll FM9 FM7 FM16 FM14 FM12 FM10
1 2 3 4 5 6 7 --
FC B1 FC B2 FC BS :C B4 FC B5 :C B6 FC B7
FM1 FM3 FM5 FM8 FM2 FM4 FM6
1 2 3 4 5 6 7 8
FCA1 FCA2 FCAS :CA4 FCA_ :CA6 FCA7 FCA_ :CA9 FCA10
FM15 FM13 FMll FM9 FM7 FM16 FM14 FM12 FM10 FM8
1 2 3 4 5 6 -- --
FC B1 FC B2 FC B_ :C B4 FC B_ :C B6 --
FM1 FM3 FM5 FM2 FM4 FM6 -- --
1 2 3 4 5 6 7 8
FC A1 FC A2 FC A_ :C A4 FC A5 :C A6 FC A7 FC A8 FC A9
FM17 FM15 FM13 FMll FM9 FM18 FM16 FM14 FM12
1 2 3 4 5 6 7 8
FC B1 FC B2 FC BS :C B4 FC B5 :C B6 FC B7 FC B8 FC B9
FM1 FM3 FM5 FM7 FM10 FM2 FM4 FM6 FM8
LEGEND
Ckt -- Circuit FM -- Fan MotorCOMP -- Compressor PEB -- R)werElectricalBoxFC -- Fan Contac_r
Fig. 9 -- Fan Staging
23
COMP B IPEB A/B I COMP A ] PEB [ COMP C
@@@@@@@@@@30XA400
COMP B I
g0XA450, 500
PEB A/B I COMPA I PEBC I COMPC
Fan Output Ckt A 1 2 3 4 5 6 --
Contactor Number FC A1 FC A2 FC A3 FC A4 =C A5 FC AC
Fail Position FM11 FM9 FM7 FM12 FM1O FM8 --
Fan Output Ckt B 1 2 3 4 5 6 --
Contactor Number FC B1 FC B2 FC B3 FC B4 =C B5 FC BE
Fan Position FM1 FM3 FM5 FM2 FM4 FM6 --
Fan Output Ckt C 1 2 3 4 5 6 7
Contactor Number FC O1 FC 02 FC 03 FC 04 =C 05 FC DE FC 07
Fan Position FM19 FM17 FM15 FM13 FM20 FM18 FM16
Fan Output Ckt A 1 2 3 4 5 6 7
Contactor Number FC A1 FC A2 FC A3 FC A4 =C A5 FC AE FC A7
Fan Position FM13 FM11 FM9 FM7 FM14 FM12 FM10
Fan Output Ckt B 1 2 3 4 5 6 --
Contactor Number FC B1 FC B2 FC B3 FC B4 =C B5 FC BE
Fan Position FM1 FM3 FM5 FM2 FM4 FM6 --
Fan Output Ckt C 1 2 3 4 5 6 7
Contactor Number FC O1 FC 02 FC 03 FC 04 =C 05 FC DE FC 07
Fan Position FM21 FM19 FM17 FM15 FM22 FM20 FM18
LEGEND
Ckt -- Circuit FM -- Fan MotorCOMP -- Compressor PEB -- Power Electrical BoxFC -- Fan Contactor
Fig. 9- Fan Staging (cont)
8
FC C8
FM14
8
FC A8
FM8
8
FC 08
FM16
Replacement -- If the controller is replaced tile pammetels inTable 15 must be configured. See Fig. 10 and 11.
Table 15 -- Head Pressure Control Parameters
PARAMETER
P0010
P0311
P3900
P0003**
P1210"*
P1310
*6-pole motors.t8-pole motors.
DESCRIPTION
Enter Quick Commissioning
Rated Motor Speed
End of Quick Commissioning
User Access Level
Automatic Restart
Continuous Boost
**Remove jumper from terminals 5 and 8 before configuring parameter.Reinstall jumper after configuration is complete.
DIP switch settings:
DIP switch 1 is not used.
DIP switch 2 is the motor fiequency. (OFF = 50 Hz,ON = 60 Hz)
Drive Programming -- Parameter values can be altered viathe operator panel. The operator panel features a five-digit,seven-segment display for displaying parameter numbers andvalues, alarm and fault messages, set points, and actual values.See Fig. 12 and 13. See Table 16 for additional information onthe operator panel.
NOTE: The operator panel motor control functions are dis-abled by default. To control the motor via the operator panel,ptu'ameter P0700 should be set to 1 and PI000 set to 1. Theoperator panel can be fitted to and removed from the diivewhile power is applied. If the operator panel has been set as theI/(i) control (P0700 = 1), the diive will stop if the operatorpanel is removed.
Changing Parameters with the Operator Panel -- See Fig. 13for the procedure for changing the value of parameter P0004.Modifying the value of an indexed parameter is illustrated inFig. 13 using the example of P0719. Follow the same proce-dure to alter other parameters using the operator panel.
NOTE: In some cases when changing ptu'ameter values the
display on the operator panel displays . This means the
drive is busy with tasks of higher priority.
L3
L2
L1
ENABLEJUMPER
T1 T2 T3
TO CONDENSERFAN MOTOR
Fig. 10 -- Low Ambient TemperatureControl Power Wiring
AOUT+ AOUT- P+ N-
-1- _
0-10 VDC SIGNAL FROM FAN BOARD
Fig. 11 -- Low Ambient TemperatureControl Signal Wiring
DIPSwi_h250/60 Hz
kW/hpON =60 Hz
24
Fig. 12- Low Ambient Temperature Controller
Changing Single Digits in Parameter Values -- For chang-ing the parametel_ value rapidly, the single digits of the displaycan be changed by performing the following actions:
Ensure the operator panel is in the ptuameter v_due chang-ing level as described in the Changing Parametel:s with theOperator Panel section.
1. Press Q (function button), which causes the farthest
right digit to blink.
Change the value of this digit by pressing O or O "2.
Pressing O (function button) again to cause3. tile next
digit to blink.
4. Perforln steps 2 to 4 until tile required value is displayed.
5. Press O (parameter button) to exit the parmneter v_flue
changing level.
NOTE: The lunction button may also be used to acknowledgea fault condition.
OuickCommissioning (P0010=I) -- It is important thatparameter P0010 is used for commissioning and P0003 is usedto select the number of parameters to be accessed. The P0010parameter allows a group of parameters to be selected that willenable quick commissioning. Parametel_ such as motor set-tings and ramp settings are included. At the end of the quickcommissioning sequences, P3900 should be selected, which,when set to 1, will carry out the necessary motor calculationsand clear all other parameters (not included in P0010=I to thedefault settings. This will only occur in Quick Commissioningmode. See Fig. 14.
Reset to FactoLy Default -- To reset all parameters to the fac-tory default settings, the following parameters should be set asfollows:
1. Jumpers must be in place from termimds 2 and 4 and 5and 8 (5 and 9 for 575v &'ives only).
2. Remove the keypad (pull out from top) and verify thatDIP switch 1 is OFF and 2 is ON. Replace keypad.
3. Power up the drive. Press Parameter t key. Pressto Parameter P0010.
4. Press Q, then O to change the 0 to a 1. Pless Q
again to accept the change.
5. Press _ to Parmneter P0311. Press _ and press
to change to 6-pole motorsthis value 1140 for
or 850 for units with 8-pole motors. Press _ to accept.
CHANGING P0004 -- PARAMETER FILTER FUNCTION
I StEP II RESULT°NDISPLAY
1 Press _ to access parameters
2 Press O until P0004 is displayed
Press Ovalue level
to access the parameter
4 Press _ or _ to the requiredvalue
5 Press A to confirm and store thevalue
6 Only the command parameters arevisible to the user.
CHANGING P0719 AN INDEXED PARAMETERSELECTION OF COMMAND/SETPOINT SOURCE
I
I STEP Jl °" I1 Press O to access parameters
2 Press 0 until P0719 is displayed
3 Press 0 to access the parametervalue level
Press 0 to display current set value
5 Press _ or _ to the requiredvalue
6 Press A to conform and store thevalue
7 Press 0 until rO000 is displayed
8 Press Q to return the display to the
standard drive display (as defined by
the customer)
Fig. 13- Changing Parameterswith the Operator Panel
25
6. Press O to Parmneter P3900. Press O and use O
to change this value to 1. Press O to accept.
7. The &'ive will finish standard programming. Remove oneend of the jumper wire from terminal 8.
8. Press O again and go to Ptu'ameter P0003. Press O
and use O to change this value to 3. Press O to
accept.
9. Press O to Parmneter P1210. Press O and use O
to change this value to 6. Press O to accept.
10. Press O to Pmmneter PI310. Press O and use O
to change this value to 10%. Press O to accept.
11. Press the Function O key and then O" The displaywill read 0.00 Hz.
12.
13.
Replace the wire jumper in terminal 8.
The &'ive is now active. Check fan rotation prior to testing.
If the fan is spinning forward, further adjustment is needed.
Fan should sit still when commanded speed is 0%. If the
fan is spinning forward slightly, press O and _ to
Pmameter P0761. Press am and use a to change flais
value to 0.1. Press Q to'q_accept. Check1"the fan. If rotation
has stopped no further adjustment is required. If the fan
is still rotating forward, press_ O and use O to change
this value to 0.2. Press O to accept. Repeat as needed
until the fan is holding still or is just bmely moving in
either direction. Do NOT enter a v_due greater than 0.5
for this pm'ameter without th.'st contacting your Cturier
representative.
Table 16 -- Low Ambient Temperature Controller Operator Panel
PANEL/BUTTON FUNCTION DESCRIPTION
Indicates Status The LCD displays the settings currently used by the converter.
Start Converter The Start Converter button is disabled by default. To enable this button set P0700 = 1.OO Stop Converter Press the Stop Converter button to cause the motor to come to a standstill at the selected
ramp down rate. Disabled by default, to enable set P0700 = 1.
Press the Stop Converter button twice (or hold) to cause the motor to coast to a standstill.This function is always enabled.
O Change Direction Press the Change Direction button to change the direction of rotation of the motor.Reverse is indicated by a minus (-) sign or a flashing decimal point. Disabled by default, toenable set P0700 = 1.
O Jog Motor Press the Jog Motor button while the inverter has no output to cause the motor to start and
run at the preset jog frequency. The motor stops when the button is released. The JogMotor button is not enabled when the motor is running.
Functions The Functions button can be used to view additional information. Press and hold the but-ton to display the following information starting from any parameter during operation:
1. DC link voltage (indicated by d - units V).2. Output current. (A)3. Output frequency (Hz)4. Output voltage (indicated by o - units V).5. The value selected in P0005 (If P0005 is set to show any of the above [3, 4, or 5] then
this will not be shown when toggling through the menu).
Press the Functions button repeatedly to toggle through displayed values.
Jump Function
Press of the Fn button from any parameter (rXXXX or PXXXX) to immediately jump tor0000, when another parameter can be changed, if required. Return to r0000 and pressthe Functions button again to return.
Allows access to the parameters.Access ParametersOIncrease Value Press the Increase Value button to increase the displayed value. To change the Frequency
O Setpoint using the operator panel set P1000 = 1.
O Decrease Value Press the Decrease Value button to decrease the displayed value. To change the
Frequency Setpoint using the operating panel set P1000 = 1.
26
Troubleshooting with the Operating Panel -- Warnings andfaults are displayed on the operating panel with Axxx andFxxx. The individual messages are shown in Table 17.
If the motor fails to start, check the following:
• Power is present on TI, T2 and T3.• Configuration jumpers are in place.• Control signal between 1 vdc and 10 vdc is present on
terminals 3 and 4.• P0010 = 0.
• P0700 = 2.
Fault Messages (Tables 17 and 18) -- In the event of a fidl-ure, file &ive switches off and a fault code appears on thedisplay.
NOTE: To reset the fault code, one of the following methodscan be used:
1. Cycle the power to the drive.2. Press the a button on the operator panel.
P0010 Start Quick CommissioningReady to RunQuick CommissioningFactory Setting
NOTE: P0010 must always be set back to '0' before operatingthe motor. However if P3900 = 1 is set after commissioning thisis done automatically.
P0311 Rated Motor Speed*0 -- 4000 1/minNom na motor speed (rpm) from rat ng plate
[
*Motor-specific parameters -- see motor rating plate.
NOTE: Shaded boxes are for reference only.
I P3900 End Quick Commissioning0 End Quick Commissioning without motor calculation or
factory reset.1 End Quick Commissioning with motor calculation and
factory reset (Recommended)2 End Quick Commissioning with motor calculation and with
I/O reset3 End Quick Commissioning with motor calculation but
without I/O reset
Fig. 14 -- Low Ambient Temperature Controller Flow Chart Quick Commissioning
27
Table 17 -- Low Ambient Temperature Controller Fault Messages
FAULT POSSIBLE CAUSES TROUBLESHOOTING
F0001 • Motor power does not correspond to the Check the following:Overcurrent inverter power 1. Motor power (P0307) must correspond to inverter power (P0206)
• Motor lead short circuit 2. Motor cable and motor must have no short-circuits or ground faults• Ground fault 3. Motor parameters must match the motor in use
4. Motor must not be obstructed or overloaded
After Steps 1-4 have been checked, increase the ramp time (P1120) and reduce theboost level (P1310, P1311, P1312).
F0002 DC-link voltage (r0026) exceeds trip level Check the following:Overvoltage (P2172) 1. Supply voltage (P0210) must lie within limits indicated on rating plate
Overveltage can be caused either by too high 2. DC-link voltage controller must be enabled (P1240) and have parameters setmain supply voltage or if motor is in regenera- correctlytive mode 3. Ramp-down time (Pl121) must match inertia of loadRegenerative mode can be caused by fastramp downs or if the motor is driven from anactive load
F0003 • Main supply failed Check the following:Underveltage • Shock load outside specified limits 1. Supply voltage (P0210) must lie within limits indicated on rating plate
2. Supply must not be susceptible to temporary failures or voltage reductions
F0004 • Ambient temperature outside of limits Check the following:Drive • Fan failure 1. Fan must turn when inverter is running
Overtemperature 2. Pulse frequency must be set to default value3. Air inlet and outlet points are net obstructed4. Ambient temperature could be higher than specified for the drive.
F0005 • Drive overloaded Check the following:Drive 12t • Duty cycle too demanding 1. Load duty cycle must lie within specified limits
• Motor power (P0307) exceeds drive power 2. Motor power (P0307) must match drive power (P0206)capability (P0206)
F0011 • Motor overloaded 1. Check motor dataMotor • Motor data incorrect 2. Check loading on motor
Overtemperature 12t • Long time period operating at low speeds 3. Boost settings too high (P1310,P1311, P1312)4. Check parameter for motor thermal time constant5. Check parameter for motor 12twarning level
F0041 Stator resistance measurement failure 1. Check if the motor is connected to the driveStator Resistance 2. Check that the motor data has been entered correctly
Measurement Failure
F0051 Reading or writing of the non-volatile parameter 1. Factory reset and new parameters setParameter EEPROM Fault storage has failed 2. Replace drive
F0052 Reading of the powerstack information has Replace drivePowerstaek Fault failed or the data is invalid
F0060 Internal communications failure 1. Acknowledge faultAsic Timeout 2. Replace drive if repeated
F0070 No setpeint received from communications 1. Check connections to the communications boardCommunications board during telegram off time 2. Check the master
Board Bet Point Error
F0071 No response during telegram off time via 1. Check connections to the communications boardNo Data for BOP link 2. Check the master
BS232 Link DuringTelegram Off Time
F0072 No response during telegram off time via 1. Check connections to the communications boardNo Data from COM link 2. Check the master
BS485 Link DuringTelegram Off Time
F0080 • Broken wire Check connection to analog inputAnalog Input - • Signal out of limits
Lost Input Signal
F0085 External fault is triggered via terminal inputs Disable terminal input for fault triggerExternal Fault
F0101 Software error or processor failure 1. Run self test routinesStack Overflow 2. Replace drive
F0221 PID Feedback below minimum value P2268 1. Change value of P2268PI Feedback 2. Adjust feedback gain
Below Minimum Value
F0222 PID Feedback above maximum value P2267 1. Change value of P2267PI Feedback Above 2. Adjust feedback gain
Maximum Value
F0450 Fault value 1. Inverter may run but certain actions will not function correctly(Service Mode Only) 1 Some of the power section tests have failed 2. Replace drive
BIST Tests Failure 2 Some of the control board tests have failed
4 Some of the functional tests have failedSome of the IO module tests have failed16 The Internal RAM has failed its check on
power-up
LEGEND
ASIC -- Application Specific InstructionBIBT -- Built-in Self TestBOP -- Basic Operating Panel12t -- Current Squared TimePI -- Proportional IntegralPID -- Proportional Integral Derivative
NOTE: To reset the fault code, one of the following methods can be used:1. Cycle the power to the drive.
2. Press the O button on the operator panel.
28
Table 18- Alarm Messages
FAULT
A0501Current Limit
A0502Overvoltage Limit
POSSIBLE CAUSES
• Motor power does not correspond to thedrive power
• Motor leads are too short• Ground fault
• Mains supply too high• Load regenerative• Ramp-down time tee short
A0503 • Mains supply too lowUndervoltage Limit • Short mains interruption
A0504 Warning level of inverter heat-sink temperature 1. Check if ambient temperature is within specified limitsDrive (P0614) is exceeded, resulting in pulse fre- 2. Check load conditions and duty cycle
Overtemperature quency reduction and/or output frequency 3. Check if fan is turning when drive is runningreduction (depending on parameters set(P0610)
A0505 Warning level is exceeded; current will be Check if duty cycle is within specified limitsDrive 12t reduced if parameters set (P0610 = 1)
A0506 Heatsink temperature and thermal junction Check if duty cycle is within specified limitsDrive Duty Cycle model are outside of allowable range
A0511 Motor overloaded Check the following:Motor 1. P0611 (motor 12ttime constant) should be set to appropriate value
Overtemperature 12t 2. P0614 (motor 12toverload warning level) should be set to suitable level3. Are long periods of operation at low speed occurring4. Check that boost settings are not too high
A0541 Motor data identification (P1910) selected or Wait until motor identification is finishedMotor Data running
Identification Active
A0600 Software error
RTOS Overrun Warnin_
LEGEND
i2t -- Current Squared Time
TROUBLESHOOTING
1. Check whether the motor power corresponds to the drive power2. Check that the cable length limits have not been exceeded3. Check motor cable and motor for short-circuits and ground faults4. Check whether the motor parameters correspond with the motor being used5. Check the stator resistance6. Increase the ramp-up-time7. Reduce the boost8. Check whether the motor is obstructed or overloaded
1. Check that mains supply voltage is within allowable range2. Increase ramp down timesNOTE: If the vdc-max controller is active, ramp-down times will be automaticallyincreased
Check main supply voltage (P0210)
Machine Control Methods -- Tinge variables control
how the machine operates. One vmiable controls the machineOn-Off function. The second controls the set point operation.The third variable controls the Heat-Cool operation. Table 19illustrates how the control method and cooling set point selectvariables dilect file operation of the chiller and the set point towhich it controls. Table 19 _flso provides the On/Off state of themachine for the given combinations.
Machine On/Off control is determined by the configurationof the Operating Type Control (Operating Modes--+SLCT_OPER). Options to control the machine locally via a switch,from a local Time Schedule, or via a Carrier Comfort Networkcommand are offered.
SWITCH CONTROL --In this Operating Type Control, theEnable/Off/Remote Contact switch controls the machine locally.All models are factory configured with OPER=O (Switch Con-trol). With the OPER set to 0, simply switching the Enable/Off/Remote Contact switch to file Enable or Remote Contact posi-tion (external contacts closed) will put the chiller in tin occupiedstate. The unit Occupied Status (Run Status-+VIEW_OCC)will change fiom NO to YES. The Status Unit Control Type(Run Status--_VIEW_CTRL) will change fiom 0 (Ix_cal Off)when the switch is Off to 1 (Ix_cal On) when in the Enable posi-tion or Remote Contact position with external contacts closed.
TIME SCHEDULE- In this Operating Type Control, themachine operates under a local schedule programmed by theuser as long as the Enable/Off/Remote Contact switch is in theEnable or Remote Contact position (external contacts closed).To operate under this Operating Type Control, OperatingModes-+SLCT must be set to OPER=I. Two Internal TimeSchedules are available. Time Schedule 1 (Time Clock--_SCH1) is used for single set point On-Off control. Time Sched-ule 2 (Time Clock_SCH2) is used for dual set point On-Offand Occupied-Unoccupied set point control. The control willuse the operating schedules as defined under the Time Clockmode in the Navigato( r_'_display module.
CCN Global Time Schedule -- A CCN Global Schedule can
be utilized. The schedule number can be set anywhere from65 to 99 for operation under a CCN glob_d schedule. The30XA chillers can be configmed to follow a CCN GlobalTime Schedule broadcast by another system element. The
IMComfortVIEW Network Manager's Configure and Modilycommands or the Selwice Tool's Modify/Nmnes function mustbe used to change the number of the Occupancy EquipmentPart Table Name (OCCIP01E) to the Global ScheduleNumbel: The Schedule Number can be set from 65 to 99(OCC 1P65E to OCC 1P99E).
The Occupancy Supervisory Part table name (OCCIPOI S)number must be changed to configure the unit to broadcast aGlobal Time Schedule. The Schedule Number can be set from65 to 99 (OCCIP65S to OCCItX)9S). When OCCIPxxS is setto a v_due greater than 64, an occupancy flag is broadcast overthe CCN every time it transitions from occupied to unoccupiedor vice-versa. By configuring their appropriate Time Scheduledecisions to fl-_esame numbel, other devices on the network canfollow this same schedule. The Enable/Off/Remote Contactmust be in the Enable position or Remote Contact position withflae contacts closed for the unit to operate. The Status UnitControl Type (Run Status--cVIEW--cSTAT) will be 0 (Ix_calOff) when the switch is Off. The Status Unit Control Type willbe 2 (CCN) when the Enable/Off/Remote Contact switch inputis On.
CCN CONTROL -- An external CCN device such as Chill-ervisor controls the On/Off state of the machine. This CCNdevice forces the variable CHIL_S_S between Start/Stop tocontrol the chillel: The Status Unit Control Type (Run Status--€VIEWS'TAT) will be 0 (Loc_d Off) when the Enable/Off/Remote Contact switch is Off. The Status Unit Control Typewill be 2 (CCN) when the Enable/Off/Remote Contact switchinput is Closed and the CHIL_S_S variable is Stop or Start.
29
Table 19 -- Control Methods and Cooling Set Points
PARAMETERHeat Cool Ice Mode
Control Method Select Setpoint Select Enable( OPER) (HC.SE) (SP.SE) (ICE.M)
Enable
0(Switch Ctrl)
1(Time Sched)
2(CCN)
-- = No Effect
o(Cool)
o(Cool)
0(Cool)
1(Setpointl)
2(Setpoint2)
3(4-20mA Setp)
4(Dual Setp Sw)
0(Setpoint Occ)
Enable
Enable
Enable
Enable
Enable
Ice DoneUCE.D)
Open
Open
Open
Closed
OpenClosed
OpenClosed
Open
Dual SetpointSwitch (DUAL)
Closed
Closed
OpenClosed
Closed
OpenClosed
Closed
Closed
m
m
m
m
m
SetpointOccupied (SP.OC)
OccupiedUnoccupied
Unoccupied
OccupiedUnoccupiedUnoccupied
SETPOINT
CSP.1
CSP.3CSP.2CSP.3
4-20 mA
CSP.1CSP.3
CSP.2CSR1CSP.2CSP.3CSP.2CSR1C$P.2CSP.3CSP.2CSP.1CSP.2CSR3
UNIT RUN STATUS (Run Status--+VIEW_STAT)- As theunit transitions from off to on and back to off. the Unit RunStatus will change based on the unit's operational status. Thevariables ree: 0 (Oft), 1 (Running), 2 (Stopping), and 3 (Delay).
• 0 indicates the unit is Off due to the Enable/Off/RemoteContact Switch, a time schedule or CCN command.
• 1 indicates the unit is operational.• 2 indicates the unit is shutting down due to the command
to shut down fiom the Enable/Off/Remote ContactSwitch, a time schedule or CCN command.
• 3 indicates the unit has received a command to start fiomEnable/Off/Remote Contact Switch, a time schedule orCCN command, and is waiting for the start-up timer(Configuration _OPTN--+DELY) to expire.
Cooling Set Point Selection (Operating Modes
_SLCT_SP.SE)- Several options for controlling theLeaving Chilled Water Set Point are offered and are configuredby the Cooling Set Point Select vmiables. [n addition to theCooling Set Point Select, Ice Mode Enable (Configuration--OPTN---)ICE.M), and Heat Cool Select (OperatingModes---) SLCT---)HCSE) vmiables also have a role in deter-mining the set point of the machine. All units are shipped fromthe factory with the Heat Cool Select variable set to HC.SE=O(Cooling). All set points me based on Leaving Water Control,(Configuration ---)SER V---)EWTO=NO ).
In ;dl cases, there are limits on what values are allowed foreach set point. These values depend on the Cooler Fluid Type(Cot_guration--_SERV--+FLUD) and the Brine Freeze Setpoint (Cot_guration --+SERV--+LOSP). See Table 20.
Table 20 -- Configuration Set Point Limits
SET POINT LIMIT
Minimum*
Maximum
COOLER FLUID TYPE, FLUD
1 =Water ] 2 = Medium Brine
38 F (3.3 C) I 14 F (-10.0 C)
60 F (15.5 C)
*The minimum set point for Medium Temperature Brine applicationsis related to the Brine Freeze Point. The set point is limited to be noless than the Brine Freeze Point +5 ° F (2.8 ° C). See Table 19.
SET PO[NT 1 (Operating Modes--_LCT-+SP.SE=I) --When Set Point Select is configured to 1, the unit's activeset point is based on Cooling Set Point 1 (Set Point_'OOL _CSP. 1).
SET POINT 2 (Operating Modes--_S'LCT-+SP.SE=2) --When Set Point Select is configured to 2, the unit's activeset point is based on Cooling Set Point 2 (Set Point_4JOOL _CSP.2).
4 TO 20 mA INPUT (Operating Modes--+SLCT---)SP.SE=3) -- When Set Point Select is configured to 3, theunit's active set point is based on an external 4 to 20 mA signalinput to the Energy Management Module (EMM).
See Table 19 for Control Methods and Cooling Set Points.The following equation is used to control the set point. SeeFig. 15.
Set Point = 10 + 70(mA - 4)/16 (deg F)Set Point = - 12.2 + 38.9(mA - 4)/16 (deg C)
DUAL SWITCH (Operating Modes--)SLCT--_S'P.SE=4) --When Set Point Select is configured to 4, the unit's active setpoint is based on Cooling Set Point 1 (Set Point_COOL-eCSP.I) when the Dual Set Point switch contacts me open andCooling Set Point 2 (Set Point_ZJOOL_ZJSP.2) when theyare closed.
ICE MODE -- Operation of the machine to make and storeice can be accomplished many ways. The Energy ManagementModule and an [ce Done Switch is requiled for operation in theIce Mode. [n this configuration, the machine can operate withup to three cooling set points: Cooling Set Point 1 (Occupied)(Set Point_COOL_CSP.I), Cooling Set Point 2 (Unoccu-pied) (Set Point_COOL_CSP.2), and Ice Set Point(Set Point _COOL _CSP.3).
SET PO[NT OCCUPANCY (Operating ModesSLCT-+SP.SE=O) -- When Set point Select is configured to0, the unit's active set point is based on Cooling Set Point 1(Set Point_'OOL _CSP.I) during the occupied period whileoperating under Time Cloek-+SCHI. ff the Time Clock-eSCH2 is in use, the unit's active set point is based onCooling Set Point 1 (Set Point_COOL_CSP.I) duringthe occupied period and Cooling Set Point 2 (Set Pohlt_4JOOL _CSP.2) during the unoccupied period.
3O
4-20 mA Set Point Control
GO
LI.
O3o
"o
n
¢q
90 (32.2)
80 (26.7)
70 (21.1)
60 (15.6)
50 (10)
MI XlM JM
40 (4.4) ....................... ;_41N MUr FI UD=1/
30 (-1.1) /
,,I20 (-6.7) f
J
10 (-12.2) ..................................................................7fry INII4UIV FLLD=
I'J
jr
0
0 10 15
mA Signal
Fig. 15 -- Set Point Control
/
20
--Equation 1
.............Medium Temperature Brine]
- - Fresh Water ]
--, Maximum Temperature ]
Temperature Reset--Temperature reset is a valueadded to the basic leaving fluid temperature set point. The sumof these values is the control point. When a non-zero tempera-ture reset is applied, the chiller controls to the control point,not the set point. The control system is capable of handlingleaving-fluid temperature reset based on cooler fluid tempera-ture diffetence. Because the change in temperatute through thecooler is a measure of the building load, the temperature differ-ence reset is in effect an average building load reset method.The control system is also capable of temperature reset basedon outdoor-air temperature (OAT), space temperature (SPT), orfrom an externally powered 4 to 20 mA signal. An accessorysensor must be used for SPT reset (33ZCT55SP?). The EnergyManagement Module (EMM) is required for temperature tesetusing space temperature or a 4 to 20 mA signal.
Under normal operation, the chiller will maintain a constantleaving fluid temperature approximately equal to the chilledfluid set point. As the cooler load varies, the cooler fluidtemperature difference will change in proportion to the load asshown in Fig. 16. Usually the chiller size and leaving-fluidtempet;tture set point ate selected based on a full-load condi-tion. At part load, the fluid temperature set point may be lowerthan tequited. If the leaving fluid tempet:_tute were allowed toincrease at part load, the efficiency of the machine wouldincrease.
Delta T teset allows for the leaving temperature set point tobe reset upward as a function of the fluid temperature differ-ence ot, in effect, the building load.NOTE: Delta T reset should not be used with vtuiable Cooler
Flow Rate Systems.
To use Delta T Reset, four variables must be configured.They are: Cooling Reset Type (Configuration--eRSET_CRST), Delta T No Reset Temp (Setpoints_COOL_CRTI), Delta T Full Reset Temp (Setpoints_COOL--+CRT2) and Degrees Cool Reset (Setpoints_COOL--eDGRC). In the following example using Delta T Reset, the
chilled water temperature will be reset by 5.0 ° F (2.8 ° C)when the AT is 2° F (1.1 ° C) and 0 ° F (0 ° C) reset whenthe AT is 10° E The variable (_RT1 should be set to the
cooler temperature difference (AT) where no chilled watertemperature reset should occur. The variable CRT2 should beset to the cooler temperature difference where the maximumchilled water temperature reset should occur. The variableDGRC should be set to the maximum amount of reset
desired. To verify that reset is functioning correctly proceedto Run Status--eVIEW. and subtract the active set point(SETP) fi'om the control point (CTPT) to determine thedegrees reset. See Fig. 16 and Table 21.
Other. indirect means of estimating building load and con-trolling temperatures reset ate also av_dlable and are discussedbelow. See Fig. 17.
To use Outdoor Air Temperature Reset, four variables mustbe configured. They are: Cooling Reset Type (Cmlfiguration_RSET_CRST), ()AT No Reset Telnp (Setpoints--+COOL_CROI), ()AT Full Reset Temp (Setl_oints----_COOL_'R02) and Degrees Cool Reset (Setpoints--eCOOL--eDGRC). In the following example, the outdoor airtemperature reset example provides 0° F (0 ° C) chilled waterset point reset at 85.0 F (29.4 C) outdoor-air temperature and10.0 ° F (5.5 ° C) reset at 55.0 F (12.8 C) outdoor-air tempera-ture. See Fig. 18 and Table 22.
To use Space Temperatute Reset in addition to the EnergyManagement Module and a space temperatute sensot: fourvariables must be configured. They are: Cooling Reset Type(Configuration--eRSET_CRST), Space T No Reset Temp(Setpoints_COOL_CRSl), Space T Full Reset Temp(Setpoints_COOL_CRS2) and Degrees Cool Reset (Set-points _COOL--eDGRC). In the following space temperaturereset example, 0 ° F (0 ° C) chilled water set point reset at 72.0 F(22.2 C) space temperature and 6.0 ° F (3.3 ° C) reset at 68.0 F(20.0 C) space temperature. See Fig. 19 and Table 23.
31
Water Temperature Difference Reset
LI..
"O
(/)
rrg)
c_
3
(EXAMPLE)2
1
0
0 4 10
Entering - Leaving Water Temperature (deg F)
Fig. 16 -- Water Temperature Difference (Delta T) Reset
To use 4 to 20 mA Temperature Reset in addition to theEnergy Management Module, four variables must be config-ured. They are: Cooling Reset Type (Collfiguration _RSET_CRST), CmTent No Reset Val (Setpoints _COOL _CR VI ),Current Full Reset Val (Setpoints_COOL_CRV2) andDegrees Cool Reset (Setpoints_COOL_DGRC). In thefollowing example, at 4 mA no reset takes place. At 20 mA,5° F (2.8 ° C) chilled water set point reset is required. SeeFig. 20 and Table 24.
Cme should be taken when intell"acing with other controlsystems due to possible power supply differences such as afull wave bridge versus a half wave rectification. Connec-tion of control devices with different power supplies mayresult in pemlanent damage. Col_fhrtLink TM controlsincorporate power supplies with half wave rectification. Asignal isolation device should be utilized if the signalgenerator incorporates a full wave bridge rectifiel:
Demand Limit -- Demand Limit is a feature that allows
the unit capacity to be limited during periods of peak energyusage. There are three types of demand limiting that canbe configured. The first type is through 2-step switchcontrol, which will reduce the maximum capacity to 2 user-configurable percentages. The second type is by 4 to 20 mAsignal input which will reduce the maximum capacity linearlybetween 100% at a 4 mA input signal (no reduction) down tothe user-configurable level at a 20 mA input signal. The thirdtype uses the CCN I_adshed module and has the ability tolimit the cmTent operating capacity to maximum and furtherreduce the capacity if required.
NOTE: One-step Demand Limit is stan&ud.
The 2-step switch control and 4 to 20-mA input signal typesof demand limiting require the Energy Management Module(EMM).
To use Demand Limit, select the type of demand limiting touse. Then configure the Demand Limit set points based on thetype selected.
1-STEP SWITCH CONTROLLED -- One-step Demand Lim-it control does not require the Energy Management Module. Toconfigure Demand Limit for 1-step switch control two par_mle-ters must be configured: Demand Limit Select (Configura-tion _RSET--eDMDC), and Switch Limit Setpoint 1(Seq_oints--+MISC--eDLSI). Demand Limit step is controlledby a relay switch input field wired to TB5-5 and TB5-14for Switch 1. See the 2-Step Switch Controlled section forexample.
2-STEP SWITCH CONTROLLED-- If using 2-step De-mand Limit control, an Energy Management Module must beinstalled. One-step Demand Limit control does not require theEnergy Management Module. To configure Demand Limit for2-step switch control, three parameters must be configured:Demand Limit Select (Configuration--eRSET--eDMDC),Switch Limit Setpoint 1 (Se&oints--eMISC--eDLSI) andSwitch Limit Setpoint 2 (Se&oints--eMISC--eDLS2). In thefollowing exm_lple, Demand Limit Switch 1 is 60% andDemand Limit Switch 2 is 40%. Demand Limit steps arecontrolled by two relay switch inputs field wired to TB5-5 andTB5-14 for Switch 1 and TB6-14 and TB6-15 for Switch 2.See Table 25.
For Demand Limit by percent capacity switch control, clos-ing the % capacity demand limit contact will put the unit on thefirst demand limit level. The unit will not exceed the percent-age of capacity entered as Demand Limit Switch 1 set point.Closing contacts on the second demand limit switch preventsthe unit from exceeding the capacity entered as Demand LimitSwitch 2 set point. The demand limit % capacity that is set tothe lowest demand takes priority if both demand limit inputsare closed. If the demtmd limit percentage does not match unitstaging, the unit will limit capacity to the closest capacity stepwithout exceeding the value. To disable demand limit config-ure DMDC to 0.
32
Table 21 -- Return Water Reset Configuration
MODE KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION [] DISP
] UNIT
] SERV
] OPTN
] RSET Reset Cool and Heat Tmp
] CRST Cooling Reset Type
] 0 No Reset
] 0 No Reset Flashing to indicate Edit mode. May require Password
]/_ 2 Delta T Temp Use up or down arrows to change value to 2.
] 2 Accepts the change.
[] CRST
] At mode level
SETPOINTS [] / [] Change to Setpoints Mode
] COOL Cooling Setpoints
] CSR1 Cooling Setpoint 1
] x 4 CRV.2
] CRT1 Delta T No Reset Temp Cooler Temperature difference where no temperaturereset is required.
] 0 Value of CRT1
] 0 Flashing to indicate Edit mode
] 10.0 Value of No Temperature Reset, 10 from the example.
] 10.0 Accepts the change.
] CRT1
] CRT2 Delta T Full Reset Temp Cooler Temperature difference where full temperaturereset, DGRC is required.
] 0 Value of CRT2.
] 0 Flashing to indicate Edit mode
] 2.0 Value of full Temperature Reset, 2 from the example.
] 2.0 Accepts the change.
] CRT2
] x 4 CRS2
] DGRC Degrees Cool Reset Amount of temperature reset required.
] 0 Value of DGRC
] 0 Flashing to indicate Edit mode
.[_]. 5.0 Amount of Temperature Reset required, 5 from the example.
] 5.0 Accepts the change.
] DGRC
NOTE: Bold values indicate sub-mode level.
33
Chilled Water Temperature Control
56
54
u. 52
"O50
_ 48
E_ 46I--
'5• - 44
EWT
LWT
DesignRise
(typical)
42
4O
0 10 20
LEGEND
EWT -- Entering Water TemperatureLWT -- Leaving Water Temperature
30 40 50 60 70 80
% Loading
Fig. 17 -- Chilled Water Temperature Control
90 100
16
OAT Temperature Reset
14
.-.12I.I.
-a 10
Eo 8E
_ 6
_: 4
(EXAMPLE)
2O
X\
\40 60 80 100
Outdoor Temperature (deg F)
Fig. 18 -- OAT Reset
120
34
Table 22 -- OAT Reset Configuration
MODE KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION [] DISP
] UNIT
] SERV
] OPTN
] RSET Reset Cool and Heat Tmp
] CRST Cooling Reset Type
] 0 No Reset
] 0 No Reset Flashing to indicate Edit mode. May require Password
]/[] 1 Out AirTemp Use up or down arrows to change value to 1.
] 1 Accepts the change.
CRST
At mode level
SETPOINTS [] / [] Change to Setpoints Mode
] COOL Cooling Setpoints
] CSR1 Cooling Setpoint 1
] x 6 CRT.2
] CRO1 OAT No Reset Temp Outdoor Temperature where no temperature reset isrequired.
] 0 Value of CRO1
] 0 Flashing to indicate Edit mode
] 85.0 Value of No Temperature Reset, 85 from the example.
] 85.0 Accepts the change.
CRO1
] CRO2 OAT Full Reset Temp Outdoor Temperature where full temperature reset,DGRC is required.
] 0 Value of CRO2.
] 0 Flashing to indicate Edit mode
] 55.0 Value of full Temperature Reset, 55 from the example.
] 55.0 Accepts the change.
CRO2
] CRS1
] CRS2
] DGRC Degrees Cool Reset Amount of temperature reset required.
] 0 Value of DGRC
] 0 Flashing to indicate Edit mode
] 10.0 Amount of Temperature Reset required, 10 from theexample.
] 10.0 Accepts the change.
DGRC
NOTE: Bold values indicate sub-mode level.
35
Space Temperature Reset
IJ=
O_
"O
o_oJn-o_oJ,=O_oJa
7
6
5
4
3
2
1
0
60
I(EXAMPLE)
62 64 66 68 70 72 74
Space Temperature (deg F)
Fig. 19 i Space Temperature Reset
76 78 80
4-20 mA Temperature Reset
ii
03
"o
<n0J
n-u)0J,=030J
a
5
4
3
2
1
0
4 6 8 10 12 14 16 18 20
mA Signal
Fig. 20 -- 4 to 20 mA Temperature Reset
36
Table 23 -- Space Temperature Reset Configuration
MODE KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION [] DISP
] UNIT
] SERV
] OPTN
] RSET Reset Cool and Heat Tmp
] CRST Cooling Reset Type
] 0 No Reset
] 0 No Reset Flashing to indicate Edit mode. May require Password
]/[] 4 Space Temp Use up or down arrows to change value to 4.
] 4 Accepts the change.
CRST
At mode level
SETPOINTS [] / [] Change to Setpoints Mode
] COOL Cooling Setpoints
] CSR1 Cooling Setpoint 1
] x 8 CRO2
] CRS1 Space T No Reset Temp Space Temperature where no temperature reset isrequired.
] 0 Value of CRS1
] 0 Flashing to indicate Edit mode
] 72.0 Value of No Temperature Reset, 72 from the example.
] 72.0 Accepts the change.
CRS1
] CRS2 Space T Full Reset Temp Space Temperature where full temperature reset,DGRC is required.
] 0 Value of CRS2.
] 0 Flashing to indicate Edit mode
] 68.0 Value of full Temperature Reset, 68 from the example.
] 68.0 Accepts the change.
CRS2
] DGRC Degrees Cool Reset Amount of temperature reset required.
] 0 Value of DGRC
] 0 Flashing to indicate Edit mode
] 6.0 Amount of Temperature Reset required, 6 from theexample.
] 6.0 Accepts the change.
DGRC
NOTE: Bold values indicate sub-mode level.
37
Table 24 -- 4 to 20 mA Temperature Reset Configuration
MODE KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION [] DISP
] UNIT
] SERV
] OPTN
] RSET Reset Cool and Heat Tmp
] CRST Cooling Reset Type
] 0 No Reset
] 0 No Reset Flashing to indicate Edit mode. May require Password
]/[] 3 4-20 mA Input Use up or down arrows to change value to 3.
] 3 Accepts the change.
] CRST
] At mode level
SETPOINTS [] / [] Change to Setpoints Mode
] COOL Cooling Setpoints
] CSR1 Cooling Setpoint 1
] x 2 CSR3 Cooling Setpoint 3
] CRV1 Current No Reset Val Outdoor Temperature where no temperature reset isrequired.
] 0 Value of CRV1
] 0 Flashing to indicate Edit mode
] 4.0 Value of No Temperature Reset, 4 from the example.
] 4.0 Accepts the change.
] CRV1
] CRV2 Current Full Reset Val Current value where full temperature reset, DGRC isrequired.
] 0 Value of CRV2.
] 0 Flashing to indicate Edit mode
] 20.0 Value of full Temperature Reset, 20 from the example.
] 20.0 Accepts the change.
] CRV2
] x 6 CRS2
] DGRC Degrees Cool Reset Amount of temperature reset required.
] 0 Value of DGRC
] 0 Flashing to indicate Edit mode
] 5.0 Amount of Temperature Reset required, 5 from theexample.
] 5.0 Accepts the change.
] DGRC
NOTE: Bold values indicate sub-mode level.
38
Table 25 -- 2-Step Demand Limit Configuration
MODE KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION [] DISP
] UNIT
] SERV
] OPTN
] RSET Reset Cool and Heat Tmp
] CRST
] HRST
] DMDC Demand Limit Select
] 0 None
] 0 None Flashing to indicate Edit mode. May require Password
]/[] 1 Switch Use up or down arrows to change value to 1.
] 1 Accepts the change.
[] DMDC
] At mode level
SETPOINTS [] / [] Change to Setpoints Mode
] COOL Cooling Setpoints
] HEAT
] MISC Miscellaneous Setpoints
] DLS1 Switch Limit Setpoint 1
] 0 None Current value for DLS1.
] 0 None Flashing to indicate Edit mode. May require Password
] 60 Switch Use arrows to change value to 60 from the example.
] 60 Accepts the change.
] DLSI
] DLS2 Switch Limit Setpoint 2
] 0 Current value of DLS2
] 0 Flashing to indicate Edit mode
] 40 Use arrows to change the value for DLS2 to 40 from theexample.
] 40 Accepts the change.
] DLS2
] x 2 DGRC SETPOINTS
NOTE: Bold values indicate sub-mode level.
39
EXTERNALLY POWERED (4 to 20 mA Controlled) -- TheEnergy Management Module is required for 4 to 20 mAdemand limit control. To configure demand limit for 4 to20 mA control three parameters must be configured. They are:Demand Limit Select (Configuration _RSET--+DMDC), mAfor 100% Demand Limit (Configuration---)RSET-cDMMX)and mA for 0% Demand Limit (Configuration---)RSET---)DMZE). In the following example, a 4 mA sigmd is DemandLimit 100% and a 20 mA Demand Limit signal is 0%. The 4 to20 mA signal is connected to TB6-1 and TB6-2. The demandlimit is a linear intelpolation between the two values entered.See Table 26 and Fig. 21.
Ctue should be taken when interfacing with other controlsystems due to possible power supply differences such as afull wave bridge versus a half wave rectification. Connec-tion of control devices with different power supplies mayresult in pemmnent damage. Col@)rtLink TM controlsincorporate power supplies wifll half wave rectification. Asignal isolation device should be utilized if the signal gen-erator incorporates a full wave bridge rectifiel:
In Fig. 21, if the machine receives a 12 mA signal, themachine controls will limit the capacity to 50%.
CCN LOADSHED CONTROLLED -- To configure DemandLimit for CCN Ix)adshed control the unit Operating TypeControl must be in CCN control, (Operating Modes---)SLCT---)SP.SE=2) and be controlled by a Chillervisor module.The Chillervisor module can force the demand limit variable
and directly control the capacity of the machine. Additionally.the unit's set point will be artificially lowered to force the chill-er to load to the demand limit v:due.
Remote Alarm and Alert Relays -- The 30XA chill-er can be equipped with a remote alert and remote alarmannunciator contacts. Both relays connected to these contactsmust be rated for a maximum power draw of 10 va setded,25 va inrush tit 24 volts. The almm relay, indicating that thecomplete unit has been shut down can be connected to TB5-12and TB5-13. Refer to unit wiring diagrams. For an alert relay,indicating that tit least 1 circuit is off due to the alert, a field-supplied and insttdled relay must be connected between MBB-J3-CH25-3 and TB5-13.
Table 26 -- Externally Powered Demand Limit Configuration
MODE KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION [] DISP
] UNIT
] SERV
] OPTN
] RSET Reset Cool and Heat Tmp
] CRST
] HRST
] DMDC DemandLimitSelect
] 0 None
] 0 None Flashing to indicateEdit mode.May require Password
] 2 4-20mA Input Useuparrowsto change valueto 2.
] 2 Accepts the change.
DMDC
] DMMX mAfor 100%DemandLimit
[] o] 0 Flashing to indicate Edit mode
] 4.0 Use uparrowsto changethe valueto 4.
DMMX
] DMZE mAfor 0% DemandLimit
[] o] 0 Flashing to indicate Edit mode
] 20.0 Useuparrowsto changevalueto 20.
] DMZE
NOTE: Bold values indicate sub-mode level.
4O
4-20 mA Demand Limit
100
90
80
70
.-_ 60,,,,,.I
"0
soE
r"t 40
3O
20
10
I
10 12
mA Demand Limit Signal
Fig. 21 -- Demand Limit
14 16 18 2O
PRE-START-UP
IMPORTANT: Complete the Stall-Up Checklistfor 30XA Liquid Chillers at the end of this publication.
The Checklist assures proper start-up of a unit, andprovides a record of unit condition, applicationrequirements, system information, and operation atinitial start-up.
Do not attempt to start the chiller until the following checkshave been completed.
System Check
I. Check auxiliary components, such as the chilled fluidcirculating pump, air-handling equipment, or otherequipment to which the chiller supplies liquid ale opela-tional. Consult manufacturer's instructions. If the unit has
field-installed accessories, be sure _11 are properlyinstalled and wired correctly. Refer to unit wiringdiagrams.
2. Open compressor suction (if equipped) and dischargeshutoff v_dyes.
3. Open liquid line, oil line, and economizer service valves.
4. Fill the chiller fluid circuit with clean water (with recom-mended inhibitor added) or other non-corrosive fluid to becooled. Bleed all air out of high points of system. An airvent is included with the coolel: If outdoor temperatures
5.
6.
7.
tue expected to be below 32 F (0° C), sufficient inhibitedpropylene glycol or other suitable corrosion inhibitedantifreeze should be added to the chiller water circuit toprevent possible fieeze-up.
The chilled water loop must be cleaned before the unit isconnected. Units supplied with the accessory hydronicpackage include a run-in screen. If the run-in screen is leftin the suction guide/strainel: it is recommended that theService Maintenance be set to alert the operator within24 hours of stall-up to be sure that the run-in screen in thesuction guide/strainer is removed. To set the time for theparameter, go to Time Cloek---)MCFG---)W.FIL. Valuesfor this item me counted as &tys. Refer to the hydronicpump package literature if unit is equipped with theoptional hydronic pump package.
Check tightness of all electrical connections.
Electrical power source must agree with unit nameplate.
Oil separator heaters must be firmly seated under the oilseptu'atol: and must be energized for 24 hours prior tostart-up.
Verify power supply phase sequence. Fan motors are 3phase. Check rotation of fans by using the quick test. Fanrotation is counterclockwise as viewed from top of unit.If fan is not turning counterclockwise, reverse 2 of thepower wires at the main terminal block.
Perform service test to verify proper operation.
41
START-UP
Do not manu_dly operate contactors. Serious damage to themachine may result.
Actual Start-Up- Actual start-_q) should be done onlyunder Sul)eia'ision o/ a quali/ied r@'igerution Wchniciun.
1. Be sure all oil, discharge, suction service valves (ifequipped) and liquid line service valves are open.
2. Using the Navigato( r_'rdisplay, set leaving-fluid set point(Set PoOlt_COOL_4JSP.I). No cooling range adjust-ment is necess_uy.
3. If optional control functions or accessories _ue beingused, the unit must be properly configured. Refer toConfiguration Options section for details.
4. Complete the Start-Up Checklist to verily all componentsale operating properly.
5. Turn Enable/Off/Remote contact switch to Enable position.
6. Allow unit to operate and confirm that everything isfunctioning properly. Check to see that leaving fluidtemperature aglees with leaving set point Control Point(Run Status ---)VIEW_4JTPT).
Operating Limitations
TEMPERATURES- Unit operating temperature limits arelisted in Table 27.
Table 27 -- Temperature Limits for Standard Units
TEMPERATURE 1F5 CMaximum Ambient Temperature 52
Minimum Ambient Temperature 32 0
Maximum Cooler EWT* _095 35Maximum Cooler LWT 60 15
Minimum Cooler LWTt 4.4
LEGEND
EWT -- Entering Fluid (Water) TemperatureLWT -- Leaving Fluid (Water) Temperature
*For sustained operation, EWT should not exceed 85 F (29.4 C).1-Unit requires brine modification for operation below this
temperature.
Low Ambient Temperature Operation -- If unit operatingtemperatures below 32 F (0 ° C) are expected, refer to separateunit installation instructions for low ambient temperature oper-ation using accessory low ambient temperature head pressurecontrol, if not equipped. Contact your C_urier representative fordetails.
NOTE: If wind velocity is expected to be greater than 5 mph(8 kin/h) wind baffles and brackets must be field-fabricatedand installed for all units using accessory low ambient headpressure control. See the 30XA Installation Instructions or thelow ambient temperature head pressure control accessoryinstallation instructions for more information.
Brine duty application (below 40 F [4.4 C] LCWT) forchiller normally requires factory modification. Contact aCanier Representative for details regarding specificapplications. Operation below 40 F (4.4 C) LCWT with-out modification can result in compressor failure.
VOLTAGE
Muin Power Supply -- Minimum and maximum acceptablesupply voltages are listed in the Inst_dlation Instructions.
Unbalanced 3-Phase Supply Voltuge -- Never operate a motorwhere a phase imb_dance between phases is greater than 2%.
To determine percent voltage imb_dance:
max voltage deviation fromavg voltage
% Voltage Imbalance = 100 xaverage voltage
The maximum voltage deviation is the largest differencebetween a voltage measurement across 2 legs and the averageacross _dl 3 legs.
Example: Supply voltage is 240-3-60.
AB = 243v A B C
BC = 236v K I "_
AC = 238v
1. Determine average voltage:
Average voltage =
m
z
243+236+238
3
717
3
239
2. Determine maximum deviation from average voltage:
(AB) 243 - 239 = 4 v(BC) 239 - 236 = 3 v(AC) 239 - 238 = 1 v
Maximum deviation is 4 v.
3. Determine percent voltage imbalance:
4% Voltage hnbalance = 100 x 23----7
= 1.7%
This voltage imbalance is satisfactory as it is below themaximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbal-ance is more than 2%, contact the local electricutility company immediately. Do not operate unituntil imbalance condition is corrected.
MINIMUM FLUID LOOP VOLUME -- To obtain propertemperature control, loop fluid volume must be at least 3 gal-lons per ton (3.25 L per kW) of chiller nominal capacity for airconditioning and at least 6 gallons per ton (6.5 L per kW) forprocess applications or systems that must operate at low ambi-ent temperatures (below 32 F [0 ° C]). Refer to application in-formation in Product Data literature for details.
FLOW RATE REQUIREMENTS -- Standard chillers shouldbe applied with nominal flow rates within those listed in theMinimum and Maximum Cooler Flow Rates table. Higher orlower flow rates are permissible to obtain lower or highertemperature rises. Minimum flow rates must be exceeded toassure turbulent flow and proper heat transfer in the coolel: SeeTable 28. See Fig. 22A-22C for cooler pressure drop curves.
Operation below minimum flow rate could generatealarms, which could result in &_mage to the coolel:
Consult application &_ta section in the Product Dataliterature and job design requirements to determine flow raterequirements for a particular inst:dlation.
42
Table 28 -- 30XA Minimum and Maximum Cooler Flow Rates
30XAUNIT SIZE
080
090
100
110
120
140
160
180
200
220
24O
260
28O
30O
325
35O
40O
45O
50O
ITEM
Cooler Leaving Water Temperature*
Cooler Enterin_ Water TemperaturetNumber of
Passes
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
1
1
1
MINIMUM
40 F (4.4 C)
45 F <7.2 C)Minimum Flow Rate
f_pm) <L/s)95 6.0
43 2.7
196 12.4
101 6.4
43 2.7
229 14.4
101 6.4
43 2.7
229 14.4
125 7.9
61 3.8
254 16.0
125 7.9
73 4.6
281 17.7
134 8.5
73 4.6
324 20.4
165 10.4
98 6.2
354 22.3
202 12.7
73 4.6
416 26.2
223 14.1
98 6.2
458 28.9
235 14.8
Cooler
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one passStandard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one passStandard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one passStandard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one passStandard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one passStandard
Plus one pass
Minus one pass
7.7
31.6
16.8
9.3
33.9
16.2
8.9
36.8
18.5
8.9
39.1
20.6
11.0
43.3
22.8
13.3
45.7
23.9
15.4
48.4
31.6
MAXIMUM
60 F (15 C)
70 F (21.1 C)Maximum Flow Rate
fL/s)23.9
12.1
49.3
25.4
12.6
57.9
25.4
12.6
57.9
31.6
15.4
64.0
31.6
18.5
70.9
33.9
18.5
81.8
41.6
24.7
89,5
50.9
24.7
104.9
56.3
24.7
115.6
59.4
30.9
126.4
67.1
37.0
135.7
64.8
35.5
147.3
74.0
35.5
156.5
82.5
44.0
173.5
91.0
53.2
182.8
95.6
61.7
193.6
126.4
<_pm)379
192
782
403
200
917
403
200
917
5Ol
244
lO14
6Ol
293
1124
638
293
1296
660
391
1418
807
391
1662
892
391
1833
941
489
2004
1063
587
2151
1027
662
2334
1173
662
2481
1308
697
2750
1442
843
2897
1516
978
3068
2004
2004
2004
m m
m m
m
m
<_pm)
180.4
201.9
225.5
244.9
264.8
317.8
365.1
409.6
463.9
505.9
545.8
600.3
_2.2
687.5
733.4
775.4
917.6
1019.3
1092.8
122
501
266
147
538
257
141
584
293
141
620
327
174
687
361
211
724
379
244
767
501
501
501
*For applications requiring cooler leaving water temperature operation at less than40 F 4.4 C), the units require the use of antifreeze and application may require oneof the speca order brne opton. Contact a oca Carter representatve for moreinformation.
1-For applications requiring cooler entering water temperature operation at less than45 F (7.2 C), contact a local Carrier representative for unit selection using theCarrier electronic catalog.
m
m
NOTES:
NOMINAL
Nominal Flow Rate
/u_)
11.4
12.7
14.2
15.5
16.7
20.1
23.0
25.8
29.3
31.9
34.4
37.9
40.5
43.4
46.3
48.9
57.9
64.3
68.9
1. The 30XA units will start with loop temperatures up to 95 F (35 C).2. Nominal flow rates required at ARI conditions 44 F (7 C) leaving fluid tempera-
ture, 54 F 12 C entering water temperature, 95 F 35 C) ambient. Fouling factor0.00010 t2-hr-F/Btu 0.000018 m2-K/kW.
3. To obtain proper temperature control, cooler loop fluid volume must be at least3 gal/ton 3.23 L/kW of chiller nominal capacity for air conditioning and at least6 gal/ton (6.5 L/kW) for process applications or systems that must operate in lowambient temperatures (below 32 F [0 ° C]).
43
50(149.5)
45(134.6)
40(119.6)
_ 11o4._
£ 25a (74.8)
_ 20(69.8)
_" (44.1_
10(29.9)
5(16)
O
30XA080-120
/ 09// 10011_
12o
100(6.3)
200 300 400(12.6) (18.9) (25.2)
Cooler Flow, GPM (I/s)
5OO(31.6)
6OO(37.9)
60(179.4)
50(149.5)
8.
40
_'_(119.6)
0
,_ 3o(89.7)
-I
_ 2on (59.8)
10(29.9)
O
O
30XA140-240
J
//
¢
/
/
160 24O
200 400 600 800 1000(12.6) (25.2) (37.9) (50.5) (63.1)
Cooler Flow, GPM (I/s)
Fig. 22A -- Cooler Pressure Drop Curves, Standard
1200(75.7)
1400(88.3)
44
60(179.41
50(149.5:
n
4o(119.6:
O
_ 3o(89.7)
._ 2oa. (59.8)
10(29.9)
30XA260-500
260 280
--]o 50
400
500
450 /
Y
500 1OO0 1500 2000 2500(31.6) (63.1) (94.6) (126.2) (157.7)
Cooler Flow, GPM (I/s)
Fig. 22A -- Cooler Pressure Drop Curves, Standard (cont)
3OOO(189.3)
30XA080-120
O.
£E3
o_o_
8.
50(149.5)
45(134.5)
40(119.6)
35(104.7)
(8937_
25(74.8)
(5928_
(44!4
10(29.9)
5(15.0)
0
O8O
/
Y
O9O,10O
// 11(/120
/
100 200 300 400 500
(6.3) (12.6) (18.9) (25.2) (31.6)
Cooler Flow, GPM (I/s)
Fig. 22B -- Cooler Pressure Drop Curves, Plus One-Pass
600
(37.9)
45
6O(179.4)
5O(149.5)
4O(119.6)
ff 30t_ (89.7)
._ 20(59.8)
lO(29.9)
30XA140-240
J
160
/40//
240
<
200(12.6)
400 600 800(25.2) (37.9) (50.5)
Cooler Flow, GPM (I/s)
tooo(63.1)
t2oo(75.7)
30XA260-350
6O
(179.4)
5O
(149.5)
4ov (119.6)
o 3o
I_ (89.7)
_ 26L.. (59.8)r,
10
(29.9)
/i.
260 280
_ 30032_
/
200 400 600 800 1000 120( 1400
(12.6) (25.2) (37.9) (50.5) (63.1) (75.7) (66.3)
Cooler Flow, GPM (I/s)
NOTE: Plus-one-pass coolers are not available for 30XA400-500 units.
Fig. 22B -- Cooler Pressure Drop Curves, Plus One-Pass (cont)
1600
(100.9)
350
/
1800
(114.0)
46
v
£a
n
250
(747.5)
2OO(596)
150(489.5)
100(299)
50(149.5)
30XA080-120
/
08090,100
110
/
J
120
100 200 300 400 500 600(6.3) (12.6) (18.9) (25.2) (31.6) (37.9)
Cooler Flow, GPM (I/s)
30XA140-240
25O(747.5)
2OO(598)
r,
150(489.5)
£Q
._ lOO= (299)
U)
Q.
50(149.5)
/
180
/200
220 240
¢/
200 400 600 800 1000 1200(12.6) (25.2) (37.9) (50.5) (63.1) (75.7)
Cooler Flow, GPM (I/s)
NOTE: Minus-one-pass coolers are not available for 30XA400-500 units.
Fig. 220 -- Cooler Pressure Drop Curves, Minus One-Pass
47
25O
(747.5)
2OO(598.0)
Q,.
15o-_ (488.5)
o
9100
(299.0)Q,.
50
(149.5)
0
30XA260-500
/
280
300 325
350/
200 400 600 800 1000 1200 1400 1600 1800
(12.6) (25.2) (379) (50.5) (63.1) (75.7) (88.3) (100.9) (113.6)
Cooler Flow, GPM (I/s)
NOTE: Minus-one-pass coolers are not available for 30XA400-500 units.
Fig. 220 -- Cooler Pressure Drop Curves, Minus One-Pass (cont)
OPERATION
Sequence of Operation --With a command to sttul
the chillel: the cooler pump will start. After verifying water
flow, file control will monitor the entering and leaving water
temperature. If the need for mechanical cooling is determined,
the control decides which cimuit and compressor to stmt. The
control will start file required compressor completely unloaded
and deenergize the oil separator heater (if already energized).
The control will continue to load this cimuit by moving the
slide vfdve to satisfy cooling requirements. Once fully loaded,
the control will stmt additional cimuits to satisfy the load as
required. Shutdown of each cimuit under nomlfd conditions
occm.s in the opposite sequence to loading. Once file A cimuit
is fully unloaded the compressor is shut off and the EXV will
close completely.
If the outside air temperature is less than file brine freeze
point plus 17 ° F (9.4 ° C) then the cimuit will perform a pump
down cycle. The EXV will be closed and file compressor con-
tinued to operate until the saturated suction temperature (SST)
is 10 ° F (5.6 ° C) lower than the starting SST or 10 ° F (5.6 ° C)
less than the brine freeze point. Once the compressor is shut off
the actuated ball vfdve (located in the discharge line) will beclosed.
ACTUATED BALL VALVE (ABV) -- There is either one
or two discharge ABVs located in the discharge line of each
cimuit of the unit. See Fig. 23 for a typical ABV assembly withenclosure. Tile ABV is a motorized ball valve, which is used to
close the discharge line to prevent refrigerant migrating fromcondenser to the cooler when the cimuit is off. The valve will
be opened before the compressor is started and will normally
close when pressure equalizes between suction and discharge
lines. [f the outside air temperature is less than the brine freezepoint plus 17 ° F (9.4 ° C) then the valve will close immediately
wifl3out waiting for pressure equalization.
See Fig. 24 for a view of a fully open ball valve with the ac-
tuator removed. The fiat surface at the top of the valve shaft isparallel to the discharge line. The ball valve motor mounting
plate should be perpendiculm to the discharge line fit fill times.
If not, adjust it by loosening file set screw on the side of thevalve, mposition assembly and tighten set screw.
See Fig. 25 for a view of the ball valve motor mountingwifll a lully open valve. The motor actuator arm should be at a
countemlockwise position, with the valve shaft in a pm'allel po-
sition. If not in a parallel position, loosen the clamping screw
and push the disengagement button to rotate the actuator armuntil it stops. Retighten the clmnping screw.
ABV Manual Operation -- The ABV can be operated manu-ally as a discharge service valve by completing file following
steps:
1. Remove file actuator cover
2. With file compressor off hold down file Push button.
3. Close the ABV by turning file shaft adapter by hand orwifll a wrench so that the fiats on the end of the shaft am
perpendiculm to file discharge line.
4. Release the Push button.
48
VALVE MOTOR COVER_
VALVE MOTOR
Fig. 23 -- Typical ABV Assembly with Enclosure
Fig. 24- Fully Open Ball Valvewith Actuator Removed
@MOUNTING - FULLY CLOSED
/_ -N DISENGAGEMENT
ACTUATOR ARM_ BUTTON
CLA_
MOUNTING - FULLY OPEN
Fig. 25 -- Ball Valve Motor
Dual Chiller Sequence of Operation --With a com-mand to start the chiller, the master chiller determines which
chiller will become the lead chiller based on the configuration
of Configuration _RSET---_LLBL and CottfigurationRSET---_LLBD. The lead chiller is always started fil_t and thelag chiller is held at zero percent capacity by the master chillerforcing the lag demand limit value to 0%. If Lead PulldownTime (_bnfiguration---_RSET---_LPUL) has been configmed,the lead chiller will continue to operate alone for that specifiedtime. After the Lead Pulldown Time (Configuration---_RSET
---_LPUL)timer has elapsed and when the lead chiller is fullyloaded, either all available compression is on OFat the masterdemand limit value, then the lag start timer (¢;bnfiguration_RSET--_ LLDY) is initiated. When the pulldown timeF andlag st_u-ttimer has elapsed and the Combined Leaving ChilledWater Temperature is more than 3° F (1.7° C) above flae setpoint, then the lag chiller is started. If the lag chiller's waterpump was not started when the machines went into occupiedmode, the lag chiller water pump will be started. The lag chillerwill start with the master chiller forcing the lag chiller demandlimit value (LAG LIM) to flaemaster's demand limit value. Iflead/lag capacity balance is selected, once the lag chilleF hasstarted, the master shall try to keep the difference in capacitybetween lead and lag less than 20%. The master shall then beresponsible for water loop capacity calculation, and will deter-mine which chillel: the lead OFlag, will increase OFdecrease ca-pacity. When the load reduces, the lag chiller will be the fil_tchiller to unload. To accomplish this, the lead chiller set point isdecreased by 4° F (-2.2 ° C) until the lag chiller unloads.
To configure the two chillers for dual chiller operation,follow the example shown Dual Chiller Control section. Bothchillers must have the Control Method variable (OperatingModes_SLCT_OPER) set to 2 (CCN Control). In theexample the master chiller will be configured wifla a CCNaddress of '1' and the slave chiller with a CCN address of '2'(_bnfiguration--_OPTN_C(NA). The master and slavechillel_ can be addlessed from 1 to 239. Each device connectedto the network must have its own unique ad&ess. Both chillersmust have the same CCN Bus Number (Configuration_OPTN_CCNB). Lead/Lag Chiller Enable must be set forboth chillers by configuring Master/Slave Select (Configura-tion_RSET---_ MSSL). The master chiller Master/SlaveSelect must be set to 1 (Master). The slave chiller Master/SlaveSelect must be set to 2 (Slave). Also in this example, themaster chiller will be configured to use Lead/Lag Balance(_bl_guration--_RSET--+LLBL) to rotate the lead chillerafter 168 hours of operation. The Lag StaFtDelay (Configura-tion_RSET--_LLBD) will be set for 10 minutes. Thisprevents the Lag chiller from st_u-tinguntil the lead chiller isfully loaded and the delay has elapsed.
PARALLEL PUMP OPERATION -- For series chiller oper-ation, the pump is always controlled by the master chillel: Thelead chiller's water pump will be started. The lag chiller'swater pump shall be maintained off if Configuration---_RSET---_LAGP=O. The internal algorithm of lead chiller willcontrol capacity of the lead chillel:
Operating ModesOperating modes correspond to some capacity control over-rides in the Capacity Control Override section.
See Table 14 on page 20 for a list of operating modes andwhich capacity control ovenide (if any) applies to the follow-ing operating modes.
MODE 1 (MD01) -- Staaup Delay in Effect
Criteria for Mode -- Tested when the unit is st_u-ted.Thismode is active when the Minutes Off Time (ConfigurationOPTN---_DELY) timer is active.
Action Taken -- The unit will not start until the timer hasexpired.
49
Termination -- The mode will terminate when the timer
expires.
Possible Causes -- This mode is in effect only due to the Min-utes Off Time timel:
MODE 2 (MD02) -- Second Setpoint in UseCriteria for Mode -- Tested when the unit is ON. This modeis active when Cooling Setpoint 2 (Setpoints--cCOOL--€CSP.2) or Ice Setpoint (Setpoints_COOL_CSP3) is inuse. While in this mode, the Active Setpoint (Run Status--+VIEW--cSETP) will show the CSP.2 or CSP.3 value.
Action Taken -- The unit will operate to the Cooling Setpoint2 (CSP.2) or Ice Setpoint (CSP.3).
Termination -- This mode will terminate when the CoolingSetpoint 2 (CSP.2) or Ice Setpoint (CSP.3) is no longer in use.
Possible Causes -- This mode is in effect only due to pro-grmnming options.
MODE 3 (MD03) -- Reset in Effect
Criteria for Mode -- Tested when the unit is ON. This modeis active when Temperature Reset (Configuration--¢RSET--€CRST) is enabled either by CRST=I (Outside Air Tempera-ture), CRST=2 (Return Water), CRST=3 (4-20 mA Input), orCRST=4 (Space Temperature) and is active.
Action Taken -- The Active Setpoint (Run Status--cVIEW---_S'ETP) will be modified according to the progrmnmedinformation and will be displayed as the Control Point (RunStatus --+VIEW _CTPT).
Termination -- This mode will terminate when the Tempera-ture Reset is not modifying the active leaving water set point,so SETP is the same as CTPT.
Possible Causes -- This mode is in effect only due to pro-grmnming options.
MODE 4 (MD04) -- Demand Limit Active
Criteria for Mode -- Tested when the unit is ON. This modeis active when Demand Limit (Configuration--cRSET--€DMDC) is enabled either by DMDC=I (Switch), DMDC=2(4-20 mA Input) or the Night Time Low Sound Capacity Limit((;bnfiguration _OPTN ---)LS.LT).
Action Taken -- The Active Demand Limit Value (RunStatus--_VIEW--_LIM) will display the current demand limitaccording to the progrmnmed information and the unit's capac-ity will be reduced to the mnount shown or lowerTermination -- This mode will terminate when the DemandLimit command has been lemoved.
Possible Causes -- This mode is in effect only due to pro-grmnming options.
MODE 5 (MD05) -- Ramp Ixmding ActiveCriteria for Mode -- Tested when the unit is ON. This modeis active when Ramp Loading (Cot_guration_OPTN_RLS) is enabled and the following conditions are met:
1. The leaving water temperature is more than 4° F (2.2 ° C)from the Control Point (Run Status-+VIEW_CTPT),and
2. The rate of change of the leaving water temperature isgleater than the Cool Ramp Ixmding (Set Points--+COOL _CRMP).
Action Taken -- The control will limit the percent capacity in-crease until one of the two conditions in Mode 5 is no longer tree.
Termination -- This mode will terminate once either condi-tions in Mode 5 is no longer tree.
Possible Causes -- This mode is in effect only due to pro-grmnming options.
MODE 6 (MD06) -- Cooler Heater Active
Criteria for Mode -- Tested whether the unit is ON or OFF.This mode is active when the cooler heater is energized, if the
Outdoor Air Temperature (Temperature_UNIT_OAT) isless than the calculated wdue, (Freeze Setpoint + Cooler HeaterDelta T Setpoint [Configuration_SERV--cHTR] default- 2° F [1.1° C]) and either the Leaving Water Temperature(Temperature --+UNIT --+LWT)or the Entering Water Ternper-ature (Temperature--+UNIT--+EWT) are less than or equ:d tothe Freeze Setpoint + Cooler Heater Delta T Setpoint (HTR).
The Freeze Setpoint is 34 F (1.1 C), for fresh water systems(Configuration _SERV--)FLUD=I). The Freeze Setpoint isBrine Freeze Setpoint (Configuration_SERV--_LOSP), forMedium Temperature Brine systems, ((_bnfiguration ---_SERV-+FLUD=2).
Action Taken -- The cooler heater will be energized.
Termination -- The cooler heater will be deenergized whenboth the Entering Water Temperature (EWT) and LeavingWater Temperature (LWT) are above the Freeze Setpoint +Cooler Heater Delta T Setpoint (HTR).
Possible Causes -- This mode will be enabled for fieeze pro-tection. If the temperatures tu'e not as described above, checkthe accuracy of the outside ail; entering and leaving waterthermistors.
MODE 7 (MD07) -- Cooler Pumps RotationCriteria for Mode -- Tested whether the unit is ON or OFEThis mode is active when the Cooler Pump Sequence (Configu-ration _OPTN---)PUMP=2) (2 Pumps Automatic Changeover)and the Pump Rotation Delta Timer ((_bnfiguration _OPTN--¢ROZP) has expired.
Action Taken -- The control will switch the operation of thepumps. The lead pump will be operating normally. The lagpump will be stmted, becoming the lead, and then the origimdlead pump will be shut down.
Termination -- This mode will terminate when the pumpoperation has been completed.
Possible Causes -- This mode is in effect only due to pro-gmmming options.
MODE 8 (MD08) -- Pump Periodic StartCriteria for Mode -- This mode is active when the cooler
pump is started for the Periodic Pump Start configuration(Configuration Mode --€ OPTN---)PM.PS=YES).
Action Taken -- If the pump has not run that day, a pump willbe started and will run for 2 seconds at 2:00 PM. If the machine
is equipped with dual pumps, Pump no. 1 will mn on even &tys(such as day 2, 4, 6 of the month). Pump no. 2 will run on odddays (such as day 1,3, 5 of the month).
Termination -- This mode will terminate when the pumpshuts down.
Possible Causes -- This mode is in effect only due to pro-gramming options.
MODE 9 (MD09) -- Night Ix_w Noise Active
Criteria for Mode -- This mode is active when the NightTime Low Noise Option has been configured and the time iswithin the configured time. Programming a Night Low NoiseStart Time (Configuration_OPTN--)LS.ST) and a NightLow Noise End Time (Configuration Mode_OPTN-+LS.ND) configures the option.
Action Taken -- The control will raise the head pressure setpoint to reduce the number of condenser fans on, therebyreducing file sound of the machine. Additionally, if file NightTime Ix_w Sound Capacity Limit ((;bnfiguration_OPTN-¢LS.LT) has been configured, the unit's capacity will be lim-ited to the programmed level.
Termination -- This mode will terminate once the Night LowNoise End Time (LS.ND) has been reached.
Possible Causes -- This mode is in effect only due to pro-gramming options.
5O
MODE10(MD10)-- SystemManagerActiveCriteriaforMode-- TestedwhentheunitisONorOFEThismodeisactiveif aSystemManagersuchasBuildingSupervi-sol.ChillelwisorSystemManager,oranotherCCNdeviceiscontrollingthemachine.Action Taken -- The machine will respond to the specificcommand received from the System Managel:
Termination -- The mode will be terminated if the SystemManager control is released.
Possible Causes -- This mode is in effect only due to pro-gramming options.
MODE 11 (MDI 1) -- Mast Slave Ctrl Active
Criteria for Mode -- Tested if the machine is ON. This modeis active if the Master Slave Control has been enabled. Having2 machines programmed, one as the master (Configuration--+RSET--+MSSL=I [Masterl) and the other as a slave(Configuration _RSET---_MSSL=2 [Slavel).
Action Taken -- Both the master and slave machine will re-spond to the capacity control commands issued by the mastercontrollel: This may include control point changes and demandlimit commands.
Termination -- This mode will terminate when the Master
Slave Contl_)l has been disabled.
Possible Causes -- This mode is in effect only due to pro-
grammmg options.
MODE 12 (MDI 2) -- Auto Changeover Active
Criteria for Mode -- This mode is not supported for Cooling
Only units.
Action Taken -- None.
Termination -- None.
Possible Causes -- This mode is in effect only due to plo-grammmg options,
MODE 13 (MDI 3) -- Free Cooling Active
Criteria for Mode -- This mode is not supported for CoolingOnly units.
Action Taken -- None,
Termination -- None.
Possible Causes -- This mode is in effect only due to pro-grammmg options.
MODE 14 (MDI4) -- Reclaim Active
Criteria for Mode -- This mode is not supported for CoolingOnly units.
Action Taken -- None.
Termination -- None.
Possible Causes -- This mode is in effect only due to pro-grammmg options.
MODE 15 (MDI5) -- Electric Heat Active
Criteria for Mode -- This mode is not supported for CoolingOnly units.Action Taken -- None.
Termination -- None.
Possible Causes -- This mode is in effect only due to pro-grammmg options.
MODE 16 (MDI6) -- Heating Low EWT L_ckout
Criteria for Mode -- This mode is not supported for CoolingOnly units.Action Taken -- None.
Termination -- None.
Possible Causes -- This mode is in effect only due to pro-grammmg options.
MODE 17 (MDI 7) -- Condenser Pumps Rotation
Criteria for Mode -- This mode is not supported for CoolingOnly units.
Action Taken -- None.
Termination -- None.
Possible Causes -- This mode is in effect only due to pro-gramming options.
MODE 18 (MDI 8) -- Ice Mode in Effect
Criteria for Mode -- Tested when the unit is ON. This modeis active when Ice Setpoint (Setpoints_COOL_'SP.3) isin use. While in this mode, the Active Setpoint (Run Status--)VIEW--)SETP) will show the CSP.3 value.
Action Taken -- The unit will operate to the Ice Setpoint(CSE3).
Termination -- This mode will terminate when the Ice Set-point (CSP.3) is no longer in use.
Possible Causes -- This mode is in effect only due to pro-gmmming options.
MODE 19 (MD 19) -- Defi_st Active on Cir A
MODE 20 (MD20) -- Defi_st Active on Cir B
Criteria for Mode -- This mode is not supported for CoolingOnly units.
Action Taken -- None.
Termination -- None.
Possible Causes -- This mode is in effect only due to pro-gramming options,
MODE 21 (MD21 ) -- L_w Suction Circuit A
MODE 22 (MD22) -- L_w Suction Circuit B
MODE 23 (MD23) -- L_w Suction Circuit C
Criteria for Mode -- The criteria me tested when the cimuit is
ON, The appropriate cimuit mode will be active if one of thefollowing conditions is tree:
1. If the cimuit's saturated suction temperature (SST) ismorn than 6 ° F (3,3 ° C) less than the freeze point andboth the cooler approach (Leaving Water Temperature -SST) and supeflleat (Suction Gas Temperature - SST) amgreater than 15° F (8.3 ° C).
2. ff the circuit is ON and the circuit's SST is more than18° F (10.0 ° C) below the freeze point for more than90 seconds.
3. ff the circuit's saturated suction temperature is molethan 6° F (3.3 ° C) below the fieeze point for more than3 minutes.
For a fiesh water system (Configuration ---_S'ERV--+FLUD=1), the fieeze point is 34 ° F (1.1 o C). For medium temperaturebrine systems, (Col_guration ---_S'ERV--+FLUD=2), the freezepoint is Brine Freeze Set Point (Configuration--+SERV--+LOSP).
Action Taken -- For criterion 1, no additional capacity will beadded. For criteria 2 and 3 capacity will be decreased on thecircuit.
Termination -- The mode will terminate when the cimuit'sSST is greater than the freeze point minus 6° F (3.3 ° C) or thecircuit has alarmed.
Possible Causes --If this condition is encountered, see Possi-ble Causes for Aimms 56-58 on page 75.
MODE 24 (MD24) -- High DGT Circuit A
MODE 25 (MD25) -- High DGT Circuit B
MODE 26 (MD26) -- High DGT Circuit C
Criteria for Mode -- This mode is not supported for CoolingOnly units.
51
Action Taken -- None.
Termination -- None.
Possible Causes -- This mode is in effect only due to pro-grmnming options.
MODE 27 (MD27) -- High Pres Override CirA
MODE 28 (MD28) -- High Pres Ovemde CirB
MODE 29 (MD29) -- High Pres OveMde Cir C
Criteria for Mode -- Tested when the circuit is ON. Theappropriate circuit mode will be active if the discharge pressurefor the circuit, Discharge Pressure Circuit A (Pressure---)PRC.A---)DPA), Dischalge Pressure Circuit B (Pressure--+PRC.B--+DP.B), or Discharge Pressure Circuit C (Pressure--+PRC.A--+DP.C), is greater than the High Pressure Threshold(Cotffiguration -_SER V--_HP. TH).
Action Taken -- The capacity of the affected circuit will bereduced. Two minutes following the capacity reduction, the cir-cuit's saturated condensing temperature (SCT_+2) is calculatedand stored. The affected circuit will not be allowed to addcapacity for at least 5 minutes following the capacity reduction.If after 5 minutes, the circuit's saturated condensing tempera-ture is less than SCTt+: -3 ° F (1.7 ° C), and then if required,percent capacity will be added.
If additional capacity is required, the control will look forother circuits to add capacity.
Termination -- This mode will terminate once the circuit'ssaturated condensing temperatme is less than SCTt+ 2 -3 ° F(1.7° c).
Possible Causes --If this condition is encountered, see Possi-ble Causes for Alarm A1.03. on page 80.
MODE 30 (MD30) -- Low Superheat Circuit AMODE 31 (MD31 ) --Low Superheat Circuit BMODE 32 (MD32) -- Ix_w Superheat Circuit C
Criteria for Mode -- Tested when the circuit is ON. The ap-propriate cimuit mode will be active if the circuit's superheat(discharge gas temperature- SCT) is less than 18° F (10 ° C).
Action Taken -- No additiomd capacity will be added until thecircuit's supedaeat is greater than 18° F (10 ° C).
The control will look for other circuits to add capacity ifadditional steps of capacity are required.
Termination -- This mode will terminate once the affectedcircuit's superheat is greater than 18° F (10 ° C).
Possible Causes -- If this condition is encountered, see Possi-ble Causes for Alarms R 11, R 12 and R 13 on page 76.
MODE 33 (MD33) -- High Compressor Current Circuit AMODE 34 (MD34) -- High Compressor Current Circuit BMODE 35 (MD35) -- High Compressor Current Circuit CCriteria for Mode -- Tested when the circuit is ON with at
least one compressor ON. The appropriate circuit mode will beactive if the circuit's current is great than 79% of MTA valuefor the compressol:
Action Taken -- No additional circuit capacity will be addedif the circuit's current is greater than 79% of MTA value for thecompressoE
If additional capacity is required, the control will look forother circuits to add capacity.Termination -- This mode will terminate once the affectedcircuit compressor current is less than 79% MTA value.
Possible Causes --If this condition is encountered, see Possi-ble Causes for Alarms R 11, R 12 and R 13 on page 76.
Sensors -- _ae electronic control uses up to 17 therlnistorsto sense temperatures and up to 12 transducers to sensepressure for controlling chiller operation. These sensors areoutlined below.
THERMISTORS (Tables 29-30B)-- Thermistols that memonitoring the chiller's operation include: Cooler EnteringW_lter. Cooler Leaving Wato: Du;d Chiller Leaving Watel:Complessor Suction Gas Temperature, Compressor DischargeGas Temperature, Economizer Temperature, Complessor MotorTemperature, and Outdoor Air Temperature Thermistols. Thesethermistors me 5 k_2 at 77 F (25 C) and _u'e identical in tempera-ture versus resistance. The Space Temperature Thermistor is10 k_2 at 77 F (25 C) and has a diffoent temperature vs.resistance.
Cooler Leaving Water Sensor -- On all sizes, this thermistoris installed in a friction fit well in the leaving water nozzle ofthe coolo: See Fig. 26 and 27.
Cooler Entering Water Sensor -- On all sizes, this thermistoris factory-installed in a friction fit well in the entering waternozzle of the coolel:
Compressor Return Gas Temperature-- On all sizes, thisthermistor is factolT-installed in a friction fit well located onthe compressor of each circuit. Thele is one thermistor for eachcircuit.
Compressor Discharge Gas Temperature -- On _dl sizes, thisthermistor is factory-installed in a friction fit well located in thedischarge end of the compressor for the circuit. There is onethermistor for each circuit.
Economizer Temperature- On all sizes, this thermistor isfactory-installed in a friction fit well located in the economizerline for the circuit. There is one thermistor for each circuit.
Compressor Motor Temperature -- On all sizes, this ther-mistor is embedded in the motor windings. There are two ther-mistors in each compressoc One spare is provided.
Outdoor Air Temperature -- This sensor is factory-installedto the back of the control box.
Remote Space Temperature -- This sensor (part no.33ZCT55SPT) is a field-installed accessory mounted in the in-door space and is used for water temperature reset. The sensorshould be installed as a wall-mounted thermostat would be (inthe conditioned space where it will not be subjected to either acooling or heating source or direct exposure to sunlight, and 4to 5 II above the floor).
Space temperatme sensor wires me to be connected toterminals in the unit main control box. See Fig. 28. The spacetemperature sensor includes a terminal block (SEN) and a RJI 1female connector. The RJII connector is used access into
the Carrier Comfort Network® (CCN) at the sensol: SeeFig. 26 and 27.
To connect the space temperatme sensor (see Fig. 287:
1. Using a 20 AWG twisted pair conductor cable rated forthe application, connect one wire of the twisted pair toone SEN terminal and connect the other wire to the other
SEN terminal located under the cover of the spacetemperatme sensoE
2. Connect the other ends of the wires to termin:ds 7 and 8on TB6 located in the unit control box.
Units on the CCN can be monitored from the space at thesensor through the RJI 1 connectol: if desired. To wire the RJI 1connector into the CCN:
1. Cut the CCN wire and strip ends of the red (+), white(ground), and black (-) conductors. (If another wire colorscheme is used, strip ends of appropriate wires.)
52
2. [nsert and secure the led (+) wire to terminal 5 of thespace temperature sensor terminal block.
3. [nsert and secure the white (ground) wire to terminal 4 ofthe space temperature sensol:
4. Insert and secure the black (-) wire to terminal 2 of thespace temperatme sensor
IMPORTANT: The cable selected for the RJllconnector wiring MUST be identical to the CCNcommunication bus wire used for the entire network.
Refer to Table 11 for acceptable wiring.
5. Connect the other end of the communication bus cable tothe remainder of the CCN communication bus.
NOTE: The Energy Management Module (EMM) is requiredfor this accessoly.
TRANSDUCERS -- There are four pressure transducers percircuit, and two different types of transducers: low pressure(green connector) and high pressure (black connector).
Ix>w Pressure Type: Suction Pressme Transducer (SPT), Econ-omizer Pressure Transducer (EPT).
High Pressure Type: Dischmge Pressure Transducer (DPT),Oil Pressure Transducer (OPT). See Fig. 29 for transducerlocations.
Table 29 -- Thermistor Identification
THERMISTOR ID DESCRIPTION RESISTANCE AT 77 F (25 C) CONNECTION POINT
EWT Entering Water Thermistor 5k £! MBB-J6-CH2
LWT Leaving Water Thermistor 5k £2 MBB-J6-CH1OAT Outdoor Air Thermistor 5k £2 MBB-J6-CH4
SGTA* Circuit A Suction Gas Thermistor 5k £2 EXVA-J3-THA
SGTB* Circuit B Suction Gas Thermistor 5k £2 EXVB-J3-THA
SGTC Circuit C Suction Gas Thermistor 5k £! EXVC-J3-THA
DGTA Circuit A Discharge Gas Thermistor 5k £2 CPM-A-J9-CH02
DGTB Circuit B Discharge Gas Thermistor 5k £! CPM-B-J9-CH02
DGTC Circuit C Discharge Gas Thermistor 5k £2 CPM-C-J9-CH02ECTA Circuit A Economizer Thermistor 5k £! EXVA-J3-THB
ECTB Circuit B Economizer Thermistor 5k £2 EXVB-J3-THBECTB Circuit C Economizer Thermistor 5k £2 EXVC-J3-THB
DUAL Dual Chiller LWT Thermistor 5k £2 MBB-J6-CH3
CAMT Circuit A Motor Temperature 5k £2 CPM-A-J9-CH01
CBMT Circuit B Motor Temperature 5k £2 CPM-B-J9-CH01
CCMT Circuit C Motor Temperature 5k £2 CPM-C-J9-CH01
SPT Space Temperature Thermistor 1Ok £! EMM-J6-CH2
*SGTA and SGTB for 30XA080 units are connected to the EXVA board.
O-R_ASSNUT 3'8 B24FO S ELL
Fig. 26 -- 5K Thermistor (Sensor 00PG000008105A, Connector: HY06AM016)
j_,/1/4-18 NPT
6" MINIMUM
_CL¢222_R_4._1.188 ,n._ 2.315 in._ I
REMOVAL
Fig. 27 -- Dual Leaving Water Thermistor Well (00PPG00000800A)
ISENSOR I
i-I
I
I--v-
!
I I I
..... i 7 i
I I
Fig. 28 -- Typical Remote Space Temperature Sensor (33ZCT55SPT) Wiring
53
Table 30A -- 5K Thermistor Temperature (°F) vs Resistance
TEMP
(F)-25-24-23-22-21-20-19-18-17-16-15-14-13-12-11-10
-9-8-7-6-5-4-3-2-10123456789
101112131415161718192O2122232425262728293031323334353637383940414243444546474849505152535455565758
RESISTANCE
(Ohms)
98,01094,70791,52288,44985,48682,62779,87177,21274,64872,17569,79067,49065,27263,13361,07059,08157,16255,31153,52651,80450,14348,54146,99645,50544,06642,67941,33940,04738,80037,59636,43535,31334,23133,18532,17631,20230,26029,35128,47327,62426,80426,01125,24524,50523,78923,09622,42721,77921,15320,54719,96019,39318,84318,31117,79617,29716,81416,34615,89215,45315,02714,61414,21413,82613,44913,08412,73012,38712,05311,73011,41611,11210,81610,52910,250
9,9799,7179,4619,2138,9738,7398,5118,2918,076
TEMP(F)5960616263646566676869707172737475767778798O81828384858687888990919293949596979899
100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142
RESISTANCE(Ohms)
7,6867,6657,4687,2777,0916,9116,7356,5646,3996,2386,0815,9295,7815,6375,4975,3615,2295,1014,9764,8554,7374,6224,5114,4034,2984,1964,0964,0003,9063,8143,7263,6403,5563,4743,3953,3183,2433,1703,0993,0312,9642,8982,8352,7732,7132,6552,5972,5422,4882,4362,3852,3352,2862,2392,1922,1472,1032,0602,0181,9771,9371,8981,8601,8221,7861,7501,7151,6801,6471,6141,5821,5501,5191,4891,4591,4301,4011,3731,3451,3181,2911,2651,2401,214
TEMP(F)
1431441451461471481491501511521531541551561571581591601611621631641651661671681691701711721731741751761771781791801811821831841851861871881891901911921931941951961971981992O02012O22032O42052062072O8209210211212213214215216217218219220221222223224225
RESISTANCE(Ohms)
1,1901,1651,1411,1181,0951,0721,0501,0291,007
98696594592590688786885O83281579878276575O7347197O569067766365O6386266146O259158157O5615515425335245165O850149448748O47346746145645O4454394344294244194154104O540139639138638237737236736135635O3443383323253183113O4297289282
54
Table 30B -- 5K Thermistor Temperature (°C) vs Resistance/Voltage
TEMP RESISTANCE(C) (Ohms)
-32 100,260-31 94,165-30 88,480-29 83,170-28 78,125-27 73,580-26 69,250-25 65,205-24 61,420-23 57,875-22 54,555-21 51,450-20 48,536-19 45,807-18 43,247-17 40,845-16 38,592-15 38,476-14 34,489-13 32,621-12 30,866-11 29,216-10 27,633
-9 26,202-8 24,827-7 23,532-6 22,313-5 21,163-4 20,079-3 19,058-2 18,094-1 17,184
0 16,3251 15,5152 14,7493 14,0264 13,3425 12,6966 12,0857 11,5068 10,9599 10,441
10 9,94911 9,48512 9,04413 8,62714 8,231
TEMP RESISTANCE
(C) (Ohms)
15 7,85516 7,49917 7,16118 6,84019 6,53620 6,24621 5,97122 5,71023 5,46124 5,22525 5,00026 4,78627 4,58328 4,38929 4,20430 4,02831 3,86132 3,70133 3,54934 3,40435 3,26636 3,13437 3,00838 2,88839 2,77340 2,66341 2,55942 2,45943 2,36344 2,27245 2,18446 2,10147 2,02148 1,94449 1,87150 1,80151 1,73452 1,67053 1,60954 1,55055 1,49356 1,43957 1,38758 1,33759 1,29060 1,24461 1,200
TEMP RESISTANCE
(C) (Ohms)
62 1,15863 1,11864 1,07965 1,04166 1_00667 97168 93869 90670 87671 83672 80573 77574 74775 71976 69377 66978 64579 62380 60281 58382 56483 54784 53185 51686 50287 48988 47789 46690 45691 44692 43693 42794 41995 41096 40297 39398 38599 376
100 367101 357102 346103 335104 324105 312106 299107 285
SUCTION PRESSURETRANSDUCER
ECONOMIZER PRESSURE
TRANSDUCER (EPT A)
ECONOMIZER PRESSURE
TRANSDUCER (EPT B)SUCTION PRESSURE
TRANSDUCER (SPT B)
DISCHARGE
TRANSDUCER (DPT A)
CIRCUIT B
F
DISCHARGE PRESSURE
TRANSDUCER (DPT B)
OIL PRESSURE TRANSDUCER OIL PRESSURE TRANSDUCER
(OPT A) (OPT B)
Fig. 29 -- Transducer Locations
55
SERVICE
Economizer Assembly -- Each circuit on 30XA090-500 units have an economizer assembly. The 30XA080 unit isnon-economized and has one main electronic expansion valve.Tile 30XA080 unit is controlled the same way as units with aseparate economizer assembly. See Fig. 30.
Electronic Expansion Valve (EXV) -- See Fig. 31for a cutaway view of the EXV. High-pressure liquid refriger-ant enters valve through the top. As refi'igerant passes throughthe orifice, pressure drops and refrigerant changes to a 2-phasecondition (liquid and vapor). To control refrigerant flow for dif-ferent operating conditions, an actuator moves up and downover the orifice and modulates the orifice size. A sleeve ismoved by a linear stepper motol: The stepper motor moves inincrements and is controlled directly by the EXV module. Asthe stepper motor rotates, motion is transferred into linearmovement by a the lead screw. Tile large number of steps andlong stroke results in veU accurate control of the refiigerantflow. The stepper motor has either 3690 (main) or 2785 (econ-omizer) steps.MAIN EXV CONTROL -- Each circuit has a thermistor lo-cated in a well in the discharge line of the compressor (DGF)and another one located in the compressor motor cavity (SGT).Each circuit also has discharge and suction pressure tmnsducel:Discharge and suction pressure as measured by the tmnsducel_am converted to saturated temperatures. The main control logicfor the EXV uses dischmge superheat to control the position ofthe EXV. The difference between the temperature of thedischarge gas and the saturated dischm'ge temperature is thesuperheat. The EXV module controls the position of the elec-tronic expansion valve stepper motor to maintain the dischargesuperheat set point.
Tile EXV control logic has several ovemdes, which am alsoused to control the position of the EXV.
• Approach between SST and LWT• Maximum Operating Pressure (MOP)
_roach -- If the approach (pinch), which is the differencebetween leaving fluid temperature and saturated suction tem-perature, is equal to or less than the pinch set point then theEXV will not open any further even though discharge super-heat set point is not met. Pinch set point is calculated usingsuction superheat, discharge supeflleat and pinch offset. Pinchoffset is used to adjust calculated pinch set point do to accuracyof transducers and thermistors.
MOP -- The EXV is also used to limit cooler saturated suction
temperature to 55 F (12.8 C). This makes it possible for thechiller to stmt at higher cooler fluid temperatures without over-loading the compressol: This is commonly referred to as MOP(maximum operating pressure). If the SST is equal to or greaterthan the MOP set point then the MBB will try to control theEXV position to maintain the MOP set point which will resultin dischguge supeflleat to meet the set point.
Tile dischguge supeflleat leaving the compressor is main-tained between approximately 18° and 25 ° F (10 ° and 14 ° C),or less. Because EXV status is communicated to the Main BaseBomd (MBB) and is controlled by the EXV modules, it is pos-sible to track the valve position. The unit is then protectedagainst loss of charge and a faulty valve. During initial start-up,the EXV is fully closed. After an initialization period, valveposition is tracked by the EXV module by constantly monitor-ing the amount of valve movement.
ECONOMIZERRELIEF
ECONOMIZER
COMPRESSOR
ECONOMIZER
RELIEF MAIN LINE.SHUT OFF
BRAZE PLATEHEAT EXCHANGER
FILTER DRIER
MAIN EXV
*SIGHT GLASS
*Economizer EXV has sight glasson opposite side of valve shown.
MAIN FLOWTO COOLER
Fig. 30 -- Economizer Assembly
56
1. Cable2. Glass Seal3. Motor Housing4. Stepper Motor5. Bearing6. Lead Screw7. Insert8. Valve Piston9. Valve Seat
10. Valve Port
8\
9,
10\
5 4 3 2 1, \,, \
\\ \\ , \\
1
2
i7_. \
Fig. 31 -- Cutaway Views of the Electronic Expansion Valve
ECONOM[ZER EXV CONTROL -- The economizer EXV
is controlled by the circuit EXV bomd. There is an economizergas temperature thermistor and economizer pressure transducerlocated in the line, which runs from the economizer assembly tothe compressol: The economizer pressure is converted to satu-rated temperature and is used to c_dculate economizer supeflleat.Economizer superheat equals economizer temperature minussaturated economizer tempelature. The economizer EXV onlyoperates during normal conditions when the capacity of thecircuit is approximately 75% plus or minus 5% capacity. Oncethe capacity of the circuit is greater than 75% the MBB will stmtcontrolling the economizer EXV to maintain economizer super-heat set point, which is approximately 8° to 12° F (4.4 ° to6.7 ° C). If the circuit capacity is less than 75%, the economizerEXV will be closed.
The economizer EXV has one override. If the dischmge gastemperature exceeds 195 F (90.6 C) the economizer EXV willstart to open. The EXV will be controlled to maintain dischargegas temperature at approximately 195 F (90.6 C).
If it appears that main EXV or economizer EXV is notproperly controlling circuit operation to maintain correct super-heat, there are a number of dlecks that can be made using testfunctions and initialization features built into the microproces-sor control. See the Service Test section to test EXVs.
EXV TROUBLESHOOTING PROCEDURE-- There aretwo different economizer EXVs. Both of the economizer
EXVs have a total of 2785 steps. There are three different mainEXVs, which _11have a toted of 3690 steps. The EXV motormoves at 150 steps per second. Commanding the valve toeither 0% or 100% will add an additiomfl 160 steps to themove, to ensure the valve is open or closed completely.
Follow the steps below to diagnose and correct EXV prob-
lems. Check EXV motor operation first. Switch the Enable/Off/Remote (EOR) Contact switch to the Off position. Press
on the Navigator TM module until the highest operat-
ing level is displayed. Use the rerow keys to select the Service
Test mode and press ------_ . The display will read TEST.
Use the arrow keys until display shows QUIC. Press
(password entry may be required) and use [] or [] tochange OFF to ON. The Quick Test sub-mode is now enabled.
Move the arrow down to the appropriate circuit EXV. Circuit A
EXV % Open (Service Test-cQUIC--_EXV.A), Circuit B EXV% Open (Service Test-)QUIC-+EXV.B), or Circuit C EXV %
Open (Service Test--)QUIC-+EXV.C), and press _.
The current v_lue of 0 will be displayed. Press _ and
the value will be flashing. Using the [] increase the EXV
position to select 100% valve position (hold [] for quickmovement) and press _. The actuator should be felt
moving through the EXV. Press _ again twice if neces-
sary to confirm this has occurred. This will attempt to force the
EXV to 100% again. To close the valve, press _, select
0% with [] and press _. The actuator should knockwhen it reaches the bottom of its stroke. See Table 31 for a list
of EXV modes and submodes.
Table 31 -- EXV Modes and Submodes
EXV TYPE AND CIRCUIT NAVIGATOR TM PATH
EXV, Circuit A Service Test Mode--_QUIC--_EXV.A
EXV, Circuit B Service Test Mode--_QUIC--_EXV.B
EXV, Circuit C Service Test Mode--_QUIC--_EXVC
Economizer EXV, Circuit A Service Test Mode--_QUIC--_ECO.A
Economizer EXV, Circuit B Service Test Mode--_QUIC--_ECO.B
Economizer EXV, Circuit C Service Test Mode--_QUIC--_ECO.C
If the valve is not working properly, continue with the fol-lowing test procedure:
Check the 8-position DIP switch on the board for the properaddress (see page 9). Check the EXV output signals at appro-priate terminals on the EXV module. For 30XA080 units,connect the positive test lead to EXV-J2A terminal 5 for CircuitA and to EXV-J2B terminal 5 for Circuit B.
57
For 30XA090-500unitsconnectpositivetestleadtoEXV(X)-J2Aterminal5forEXV(X)andEXV(X)-J2Btermi-md5forEconomizerEXV(X).UsingtheServiceTestproce-dureonpage57,movethevalveoutputundertestto 100%.DONOTshortmeterleadstogetherorpin5toanyotherpin,asbomd&_magewilloccm:Duringthenextseveralseconds,c;uefullyconnectthenegativetestleadtopins1,2,3and4insuccession.Digitalvoltmetel.swill averagethissignalanddisplayapproximately6vdc.If theoutputremainsataconstantvoltageotherthan6vdcorshows0volts,removetheconnec-tortothevalveandrecheck.
Press_ andselect0%toclosethev_flve.NOTE:12vdcis theoutputfiomtheEXVboardwhenthev_dveisstationary.
SeeTables4 and5.If aproblemstillexists,replacetheEXVboard.If thereadingiscorrect,theexpansionvalveandEXVwiringshouldbechecked.ChecktheEXVconnectorandinterconnectingwiring.
1. Checkcolor-codingandwireconnections.MakesuretheyareconnectedtothecorrectterminalsattheEXVboardandEXVplugandthatthecablestuenotcrossed.
2. Checkfor continuityandtightconnectionat _dlpinterminals.
Checkthelesistanceof theEXVmotorwindings.For30XA080unitsremovetheEXVmoduleplugEXV-J2AforCircuitA EXV andEXV-J2Bfor CircuitB EXV.For30XA090-500unitsremovetheEXVmoduleplugEXV(X)-J2AformainEXVandEXV(X)-J2BforeconomizerEXV.Checktheresistanceofthetwowindingsbetweenpins1and3foronewindingandpins2and4fortheotherwinding.Theresistanceshouldbe52ohms(_+5.2ohlns).Alsocheckpins1-4foranyshortstoground.Inspecting/Opening Electronic Expansion Valves
!
IMPORTANT: Obtain replacement gaskets before Iopening EXV. Do not re-use gaskets. ITo check the physical operation of an EXV. the following
steps must be performed.
1. Close the liquid line service valve of the circuit to bechecked. Put the Enable/Off/Remote Contact switch in
the Off position. Using the Navigator module, enter theService Test mode and change Service Test-+TEST
-+T.REQ from OFF to ON. A password may be
required. Switch the EOR switch to the Enable position.Under the COMP sub-mode, enable one of the compres-
sors (Service Test-+TEST_CPxn) for the circuit. Let
compressor mn until gage on suction pressure port reads
10 psig (68.9 kPa). Press _, [] and _ toturn the compressor off. The compressor will turn off. Im-
mediately after the compressor shuts off. manually closethe actuated ball valve (ABV) (See the Actuated B_dl
Valve section for instructions), close the discharge valve
and liquid line service valve. If the unit is equipped withsuction service valves and economizer service v_dves,
close both valves. Closing the valves will minimize the
amount of charge that will have to be removed from thesystem after pump down.
2. Remove any remaining refi'igerant from the system lowside using proper recovering techniques. The economizerassembly has a I/4 Schraeder connection which can be
used to remove charge from the inlet of the EXVs. Turnoff the line voltage power supply to the compressoLs.
Ensure refrigerant is removed from both the inlet and outletof EXV assemblies. Equipment &image could result.
3. The expansion valve motor is hermetically sealed insidethe top portion of the valve. See Fig. 31. Disconnect theEXV plug. Carefully unscrew the motor portion from thebody of the valve. The EXV operator will come out withthe motor portion of the device. Reconnect the EXV plug.
4. Enter the appropriate EXV test step under the (Service
Test-cQUIC) sub-mode in the Service Test mode.
Locate the desired item Service Test-cQUIC--+EXV.A,
Service Test-RQUIC-REXV.B, or Service Test-9
QUIC-+EXV.C. Press _ twice to make the valve
position of 0% flash. Press and hold [] until 100% isdisplayed and press _. Observe the operation of
the lead screw. See Fig. 31. The motor should be turning,
raising the operator closer to the motol: Motor actuator
movement should be smooth and uniform from lhlly
closed to fully open position. Press _ twice, use
[] to select 0% and press _ again to check opento closed operation. If the v_dve is properly connected to
the processor and receiving correct sigmds, yet does not
operate as described above, the sealed motor portion of
the valve should be replaced.
Installing EXV Motor
IMPORTANT: Obtain replacement gasket beforeopening EXV. Do not re-use gaskets.
If re-installing the motol, be sum to use a new gasket in theassembly. See Fig. 32. It is easier to install the motor assemblywith the piston in the lhlly closed position. Insert the motor intothe body of the EXV. Tighten the motor to the body to 36 ft-lb(50 N-m) and then tighten the valve another 30 degrees.
Moisture Liquid Indicator -- Clear flow of liquid refrigerantindicates sufficient charge in system. Bubbles in the sight glassindicate undercharged system or presence of noncondensables.Moisture in system, measured in parts per million (ppm),changes color of indicatol: See Table 32. Change filter diier atfirst sign of moisture in system.
Table 32 -- Color Indicators whenMoisture is Present in Refrigerant
R-134A, R-134A,COLOR 75 F(24 C) 125 F(52 C)
INDICATOR (ppm) (ppm)
Green -- Dry <8 <12
Yellow-green -- Caution 8-66 12-95Yellow -- Wet >66 >95
IMPORTANT: Unit must be in operation at least
12 hours before moisture indicator can give an accu-
rate reading.
With unit running, indicating element must be in con-
tact with liquid refrigerant to give true reading.
58
Cl??d
DISASSEMBLY
NOTE: Open valve in Quick Test sub-mode before disassembling.
ASSEMBLY
Closed
50Nm (36 ft-lb)+ 30 _
EF05BD271NV3Z5mmEF05BD331NV36mm
NOTES:1. Push down on valve piston to close valve before assembling,2. After valve is assembled close valve in Quick Test sub-mode or cycle power before opening service valve.
Fig. 32 -- Disassembly and Assembly of EXV Motor
27ram / 11/t_'
GASKET
Filter DHer -- Whenever moisture-liquid indicator showspresence of moisture, replace filter &ier(s). There is one filterdrier assembly on each circuit with either one or two cores.The 30XA080-120 units have one core per circuit. The30XAI40 and 160 units have two cores, one for circuit A andone for circuit B. Tile 30XA180-500 units have two cores percircuit. Refer to the Carrier Stan&ud Service TechniquesManual, Chapter 1, Refrigerants, for details on servicing filterdriel.s.
Liquid Line Sen'ice _dve -- This valve is located immediatelyahead of filter drier, and has a l/4-in. Schmder connection forfield chmging. In combination with compressor dischargeservice valve, each circuit can be pumped down into the highside for servicing.
Compressor Assembly--The 30XA units utilizescrew compmssol_ with a modulating slide wflve which varies
capacity from 30% to 100% of compressor capacity for each
cimuit. See Fig. 33 for a view of a typical 06T compmssol:
The slide v¢flve position is varied by opening and closing the
2 solenoid valves located on the compressol: To unload the
compressor, both solenoids am deenergized. To increase in
capacity both solenoid valves me energized together which
will cause the slide valve to slide towards the fully loaded posi-
tion. To stop the loading process solenoid 2 is energized and
solenoid 1 is deenergized. This will cause the slide valve to
maintain its current position. Them is no positive feedback for
the position of the slide valve. The control utilizes compressor
cunent as an indicator of the slide valve position. Once the
calculated position of the slide valve roaches 100% circuitcapacity, the control will try to increase capacity again if thecompressor current continues to inclease. The control willcontinue to load the compressor until the compressor currentno longer increases. At that time the control will energize bothsolenoids and the circuit will be considered fully loaded.
COMPRESSOR OIL SYSTEM -- Each compressor/circuithas its own oil system which includes an oil filteL oil solenoid,check valve, oil level switch, oil sep_u'ator heatel: oil pressuretransducer, and an oil shut-off valve. A typical oil system isshown in Fig. 34. See Table 33.
Table 33 -- Unit Oil Quantities
30XA UNIT SIZE
080-120
140,160
180,200220
24O
260
280,300
325,35040O
450
50O
OIL CHANGE (gal,Circuit A Circuit B
5.5 [20.8] 5.5 [20.8]
6.25 [23.7] 5.5 [20.8]
6.25 [23.7] 6.25 [23.7]
6.75 [25.6] 6.25 [23.7]6.75 [25.6] 6.75 [25.6]
7.50 [28.4] 6.75 [25.6]
7.50 [28.4] 6.75 [25.6]
7.50 [28.4] 7.50 [28.4]
6.75 [25.6] 6.75 [25.6]6.75 [25.6] 6.25 [23.7]
7.50 [28.4] 6.75 [25.6]
[liters])Circuit C
7.50 [28.4]
7.50 [28.4]
7.50 [28.4]
59
ACCESSFITTING
DISCHARGEGAS HERMISTOR
OIL PRESSURE SUCTIONTRANSDUCER TEMPERATURELOCATION
SENSOR1
SENSOR2
HPS, DISCHARGEGAS TEMPERATURESENSOR LOCATION
SOLENOIDSOLENOID 2
Enerqiz_ Energized
NO FLOW FLOW
Valve #2 (NO) Val_ #1 (NC)
FULLY LOADED OPERATION
C_mpressionProces_
_2o_,_,_0_ox
High Pressure Oil
D_energized De energizedFLOW NO FLOW
Valve #2 (NO) Valve #1 (NC)
FULLY UNLOADED OPERATION
Fig. 33 -- Typical 06T Compressor
Bleed Line to Low Pressure Suction
I High Pressure Oil
Ene_izud De-energizedNO FLOW NO FLOW
Valve #2 (NO) V_ve#1 (NC)
MAINTAIN POSITION
HIGHPRESSURE
TRANSDUCER
OIL
OIL
PRESSURETRANSDUCER
OILSOLENOID
VALVE
CHECKVALVE o oo o oo
Fig. 34 -- Typical Oil System
OIL
SEPARATORHEATER
OM)
OIL LEVELSWITCH
(BOqq-OM)
60
Oil Charge_ -- When additional oil or a complete charge isrequired it must meet the following specifications:• Manufacturer .......... Castrol Icematic® SW-220XL• Oil Type ................ Inhibited polyolester-basedsynthetic compressor lubricant for use with screw compressors.
• [SO Viscosity Grade .......................... 220
Do not reuse drained oil or any oil that has been exposed to theatmosphere.
Oil is available in the following quantities from your localC_mier lepresentative:
OUANTITY TOTALINE PART NO.1 Quart P903-23251 Gallon P903-23015 Gallon P903-2305
If unsure if there is low oil charge in file system, follow thesteps below:
1. If the unit shuts off repeatedly from a low oil level ale]l itmay be an indication of inadequate oil charge; howevek itcould also indicate that the oil is not being reclaimed fromthe low-side of the system.
2. Begin running the unit at lull load for 11/2 hours. Use themanual Test Mode featme of Service Test if the unit does
not normally run at full load.
NOTE: An adequate load must be available.
3. After running the unit for 11/2hours at full load, allow theunit to restart and run normally. If low oil akums persist,continue with the following steps.
4. Close the liquid line service valve and place a pressuregage on top of the coolel: Enable the Service Test featureusing the Navigator TM module and turn the Enable/Off/Remote switch to the enable position. Start the desiredcircuit by turning it on under the TEST lunction: CRAfor compressor A, CRB for complessor B, or CRC forcompressor C.
5. When the complessor stmts successfully observe thecooler pressure when the pressure reads 10 psig(68.9 kPa), turn the Emergency Switch (SW2) to the OFFposition. The complessor should stop within 10 seconds.
6. Open the liquid line service valve and allow the unit torestart normally. If low oil level aimms persist, continuewith the following steps.
7. If none of the previous steps were successlul, the unit islow on oil charge. Add oil to the oil separator using the_/4 in. Schrader-type fitting that the discharge pressuretransducer is mounted to.
8. To facilitate the oil charging process, ensure that the unitis not running when adding oil. The system is under pies-sure even when the unit is not running, so it is necessaryto use a suitable pump to add oil to the system.
9. Using a suitable pump, add I/2 gal (1.9 1) of oil to thesystem. Continue adding oil in I/2 gal (1.9 1) incrementsuntil the problem is lesolved, up to a maximum of 1.5 gal(5.7 1). If it is necessary to add factory oil charge levels tothe system contact your local Carrier representative.
Oil Filter Maintenance -- Each circuit has one oil filter locat-
ed externally to the compressol: Oil line pressure drop ismonitored by the control. Oil line pressure drop is calcukitedby subtracting oil pressure (OP) from discharge pressme (DP).If the oil line pressure diop exceeds 30 psi (206.8 kPa) for5 minutes file control will generate a High Oil Filter PressureDrop alert. The High Oil Filter Pressure Drop _dert willnot shut down the compressor, but instead indicates that theoil filter is dirty. If oil pressure line losses exceed 50 psi
(344.7 kPa) then the control will shut down the circuit onMaximum Oil Filter Differenti_d Pressme Failure.
Compressor oil is pressurized. Use proper safety precau-tions when relieving pressure.
Replacing the Oil Filter -- Close the oil line ball valve locat-ed in front of the oil filtel: Connect a charging hose to theSchmder port located downstleam of the valve and bleed off oiltrapped between file service valve and the oil solenoid valve. Aquart of oil is typically what is removed during this process.Remove the charging hose. Unscrew the nuts from both endsof the oil filter and remove the oil filte]: Remove the protectivecaps from the new oil filter and install, being carelul not to loseor damage the new O-ring located on the new oil filtel: Draw avacuum at the Schmder port. Remove the charging hose andopen the oil line ball valve. Check both fittings for leaks.
Cooler
SUCTION SERVICE VALVE -- The suction service valve
is a factory-installed option for 30XA units. It is located in thesuction outlet of the coolel: The suction service valve is bolted
between the cooler outlet and the suction flange piping. Thesuction service valve shaft has a locking device located on theshaft to lock the valve in either a lully open position or a fullyclosed position. The locking device must be pulled out prior tomoving the wtlve handle to a fully open or a fully closed posi-tion. See Fig. 35A and 35B.
Fig. 35A -- Suction Service Valve Locking Device,Closed and Unlocked
VALVELOCKED
OPEN
Fig. 35B -- Suction Service Valve Locking Device,Open and Locked
61
FREEZE PROTECTION--All coolers am equipped withcooler heaters and tue controlled by file Main Base Board. Thecontrol logic uses the unit status, outdoor air temperature, andthe saturated suction temperatures for all circuits to decide ifthe cooler heater should be energized.
Tile cooler heaters can only be energized when the state ofthe unit is OFF. The cooler heaters will be energized if theoutdoor-air temperature is less than the Cooler Heater Set Pointand the lowest circuit Saturated Suction Temperature is lessthan the heater set point plus 6° F (3.3° C). See Table 34.
Tile cooler heater set point = freeze point + Cooler HeaterDT Setp (Cotlfiguration --¢SERV--)HTR ).
If the entering or leaving waIer temperature is less than theHeater Set Point and the outdoor air temperature is less thanthe HeaIer Set Point -2 ° F (1.1° C), then the heater will beturned on.
If the Entering or Leaving Water Temperature is less thanthe Brine Freeze Setpoint (Cot_guration--cSERV--cLOSP)+1.0° F (0.5° C), then the heater will be turned on along withthe pump.
Tile entire cooler is covered with closed-cell insulationapplied over the heater The heater plus insulation protectscooler against low ambient temperature fieeze-up to 0° F(-17.8 C).
IMPORTANT: If unit is installed in an area whereambient temperatures fidl below 32 F (0° C), a suitablecorrosion-inhibited antifreeze solution or cooler heatermust be used in the chilled water circuit.
LOW FLUID TEMPERATURE -- Main Base Board is pro-grmnmed to shut chiller down if leaving fluid temperaturedrops below 34 F (1.1 C) for cooler fluid type water or belowBrine Freeze Setpoint (Cot_guration_SERV--cLOSP) forcooler fluid type brine. The unit will shut down without apumpout. When fluid temperature rises to 6° F (3.3° C) abovethe leaving fluid set point, safety resets and chiller restarts.Reset is automatic as long as this is the first occurrence.LOSS OF FLUID FLOW PROTECTION -- All 30XA ma-chines include an integral flow switch that protects the cooleragainst loss of cooler flow.TUBE PLUGGING- A leaky tube can be plugged untilretubing can be done. The number of tubes plugged determineshow soon the cooler must be retubed. All tubes in the coolermay be removed. Ix_ss of unit capacity and efficiency as wellas increased pump power will result fiom plugging tubes.Failed tubes should be replaced as soon as possible. Up to 10%of the total number of tubes can be plugged before retubing isnecessary. Fig. 36 shows an Elliott tube plug and a cross-sec-tiomd view of a plug in place. See Tables 35 and 36 for plugcomponents. If the tube failure occurs in both circuits usingtube plugs will not con'ect the problem. Contact your localC_urier representative for assistance.
Use extreme care when installing plugs to prevent &tmageto the tube sheet section between the holes.
Table 34 -- Cooler Heater Operation Examples
OATF (C)
50(10)
40(4.4)
40(4.4)
40(4.4)
40(4.4)
UNITSTATUS
OFF
OFF
OFF
OFF
ON
BRINEFREEZE
POINTF (C)
36(2.2)
36(2.2)
15(-9.4)
OAT
36(2.2)
36(2.2)
LEGEND
-- Outdoor-Air Temperature
COOLERDELTA T
F (C)
6(3.3)
6(3.3)
6(3.3)
6(3.3)
6(3.3)
SSTA -- Saturated Suction Temperature, Circuit ASSTB -- Saturated Suction Temperature, Circuit BSSTC -- Saturated Suction Temperature, Circuit C
COOLER COOLERHEATER SSTA SSTB SSTC HEATER
SETPOINT F (C) F (C) F (C) STATUSF (C)
42 N/A N/A N/A OFF(5.6)
42 41 N/A N/A ON(5.6) (5)
21 41(-6.1) (5) N/A N/A OFF
42 52.1 52.1 52.1 OFF(5.6) (11.2) (1 1.2) (11.2)
42 N/A N/A N/A OFF(6.6)
COMMENTS
OAT>42 F(6.6c)SSTA<42 F(5.6 C)
SSTA>21 F
(-6.1 C)
All SSTTemperatures
>52 F(11.2 C)
Unit StatusON
62
TUBE SHEET
Fig. 36 -- Elliott Tube Plug
Table 35 -- Plug Component Parts
COMPONENTS FOR PLUGGING PART NUMBER
For Tubes
Brass Pin 853103-1"
853002-640 or 657*Brass Ring (measure tube
before ordering)For Holes without tubes
Brass Pin 853103-1A
Brass Ring 85102-738
Loctite No. 675 1-
Locquic "N"I-Roller Extension S82-112/11
*Order directly from Elliot Tube Company, Dayton, OH or RCD.1-Can be obtained locally.
Table 36 -- Plug Parts
PLUG COMPONENT
Tube sheet hole diameter
Tube OD
Tube ID after rolling (includesexpansion due to clearance.)
in,
0.756
0.750
0.650 to0.667
SIZE
mm
19.20
19.05
16.51 to 16.94
NOTE: Tubes replaced along heat exchanger head partitions mustbe flush with tube sheet (both ends).
RETUBING --When mtubing is required, obtain service of
qu_flified personnel experienced in boiler maintenance and
mpail: Most standard procedures can be followed when retub-
ing file coolers. An 8% crush is recommended when rolling
replacement tubes into the tubesheet.
The following Elliott Co. tube rolling tools am required:
• Expander Assembly (113123)
• Cage (2134123)• Mandrel (213123)
• Rolls (2115122)
Place one drop of Ix)ctite No. 675 or equivalent on top of
tube prior to rolling. This materi_fl is intended to "wick" into file
area of the tube that is not rolled into the tube sheet, and prevent
fluid from accumulating between the tube and the tube sheet.New tubes must also be rolled into the center tubesheet to
prevent cimuit to cimuit leaks.
TIGHTENING COOLER HEAD BOLTS
Preparation -- When reassembling cooler heads, always
check the condition of the O-rings ilLst. The O-ring should be
replaced if them is visible signs of deterioration, cuts or
damage. Apply a thin film of grease to the O-ring before
installation. This will aid in holding the O-ring in the groove
while the head is installed. Torque all bolts to file following
specification and in sequence:
3/4-in. Diameter Perimeter Bolts (Grade 5) .... 200 to 225 ft-lb
(271 to 305 N-m)
1. Install zfllbolts finger tight.
2. Bolt tightening sequence is outlined in Fig. 37. Followfile numbering or lettering sequence so that pressure isevenly applied to O-ring.
3. Apply torque in one-third steps until required torque isroached. Ix)ad all bolts to each one-third step before pro-ceeding to next one-third step.
4. No less than one hour latel: mtighten all bolts to requiredtorque values.
5. After refrigerant is restored to system, check for rel]iger-ant le_tks using recommended industry practices.
6. Replace cooler insulation.
INSPECTING/CLEANING HEAT EXCHANGERS --In-spect and clean cooler tubes at the end of the first operatingseason. Because these tubes have internal ridges, a rotary-typetube cleaning system is necessary to fully clean the tubes. Tubecondition in the cooler will determine the scheduled frequencyfor cleaning, and will indicate whether water treatment isadequate in the chilled water/brine circuit. Inspect the enteringand leaving water thermistor wells for signs of conosion orscale. Replace the well if corroded or remove any scale iffound.
Hard sc_fle may require chemical treatment for its preven-tion or removal. Consult a water treatment specialist forproper treatment procedures.
WATER TREATMENT- Untreated or improperly treatedwater may result in corrosion, scaling, erosion or algae. The
services of a qualified water treatment specialist should be
obtained to develop and monitor a treatment program.
WiLter must be within design flow limits, clean and treatedto ensure proper machine performance and reduce filepotential of tubing dmnage due to corrosion, sc_fling, andalgae. Career assumes no responsibility for cooler d_unageresulting from untreated or improperly treated watel:
®
Fig. 37- Cooler Head RecommendedBolt Torque Sequence
SINGLE
ONLY
63
CHILLED WATER FLOW SWITCH -- A factory-installedflow switch is installed in the entering water nozzle for allmachines. See Fig. 38 and 39. This is a thermal-dispersion flowswitch. Figure 38 shows typical installation. If nuisance trips ofthe sensor me occurnng, follow the steps below to correct:
When power is supplied to the device, a warm-up period isinitiated. During this pedod, the green LED is lit trod turned offas each LED to the left is successively lit until the left most redLED is lit. The warm-up period may take up to 30 seconds.When some flow is detected but not enough for machineoperation, a red LED illuminates tit the fro left. With increasingflow, successive red LEDs illuminate. When the switch deter-mines flow is present, an amber LED illuminates indicating theswitch has closed. This is not an indication that minimum flow
has been met. Increasing flow above the amber LED indicationilluminates the first green LED. Each successive green LEDindicates greater flow. The switch closure does not indicateminimum flow requirements have been met for the machine.One green LED lit can indicate minor fluctuations in flow.while an increase in flashing green LEDs can indicate higherflow rate, with a lower instance of nuisance alarms.
1. Check to confirm that all strainers are clean, valves meopen and pumps are running. For the case of vtuiablefrequency drive (VFD) controlled pumps, ensure theminimum speed setting has not been changed.
2. Measure the pressure drop across the coolel: Use thecooler pressure drop curves on pages 44-48 to ctdculatethe flow and compare this to system requirements.
3. If the measured flow rate through the cooler agrees withthe system lequirements. The green LED should be lit aminimum of 2 bras away from the amber light.
4. If the contacts do not close with the amber LED lit thencheck the wiring connection to the MBB. If the inputsignal is not closed, then the switch needs to be replaced.
Condenser Coil Maintenance and CleaningRecommendation -- Routine cleaning of coil surfacesis essential to maintain proper operation of the unit. Elimina-tion of contamination and removal of harmful residues willgreatly increase the life of the coil and extend the life of theunit. The following maintenance and cleaning procedures arerecommended as part of the routine maintenance activities toextend the life of the coil.
REMOVE SURFACE LOADED FIBERS -- Surface loadedfibers or dirt should be removed with a vacuum cleanel: If avacuum cleaner is not av_filable, a soft non-metallic bristlebrush may be used. In either case, the tool should be applied inthe direction of file fins. Coil surfaces can be easily damaged(fin edges can be easily bent over and damage to the coating ofa protected coil) if the tool is applied across file fins.
NOTE: Use of a water stream, such as a garden hose, against asurface loaded coil will drive the fibers and dirt into file coil.
This will make cleaning efforts more dift]cult. Surface loadedfibers must be completely removed prior to using low velocityclean water rinse.
PERIODIC CLEAN WATER RINSE -- A periodic cleanwater rinse is very beneficial for coils that me applied in coastalor industrial environments. Howevel, it is very important thatthe water rinse is made with ve q low velocity water stream toavoid &imaging the fin edges. Monthly cleaning as describedbelow is recommended.
ROUTINE CLEANING OF COIL SURFACES -- Month-
ly cleaning wifll Totaline® environmentally sound coil cleaneris essential to extend the life of coils. This cleaner is available
from Carrier Replacement parts division as ptut numbertx)02-0301 for a one gallon container, and part numbertx)02-0305 for a 5 gallon conttfiner It is lecommended that tdlcoils, including stan&trd aluminum, pre-coated, copper/copperor E-coated coils be cleaned with the Totaline environmentally
sound coil cleaner as described below. Coil cleaning should bepart of the unit's regularly scheduled maintenance proceduresto ensure long life of the coil. Failure to clean the coils mayresult in reduced durability in the environment.
Avoid the use of:• coil brighteners• acid cleaning prior to painting• high pressure washers• poor quality water for cleaning
Tottdine environmentally sound coil cleaner is non-flammable, hypo allergenic, non bacterial, and a USDAaccepted biodegra&tble agent that will not harm the coil orsurrounding components such as electrical wiring, paintedmetal surfaces, or insulation. Use of non-recommended coilcleaners is strongly discouraged since coil and unit durabilitycould be affected.
M12 X 4 PIN MALE
1
2@43
......................L1--BRN----o/i _............................................I c_ WHT---o 2--
24 VAC _BLK__OI_ _
N B,u i
RED AMBER GREENI 1 I I
.................................v ..................................I I _ J
FLOW BELOW OUTPUT FLOW ABOVESET POINT ENERGIZED SET POINT
Fig. 38 -- Chilled Water Flow Switch LED Display
FLOW SWITCH STANDARD COOLER
Fig. 39 -- Flow Switch
64
Totaline® Environmentally Sound Coil Cleaner Application_ment
• 21/2 gallon garden sprayer• Water rinse with low velocity spray nozzle
Harsh chemicals, household bleach or acid or basic clean-ers should not be used to clean outdoor or indoor coils of
tiny kind. These cleaners can be very difficult to rinse outof the coil and can accelerate corrosion fit the fin/tube inter-face where dissimilar materitfls are in contact. If there isdirt below the surface of the coil, use file Totaline environ-mentally sound coil cleaner as described above.
High velocity water from a pressure washer, gtuden hose,or compressed air should never be used to clean a coil. Theforce of the water or air jet will bend the fin edges andincrease airside pressure drop. Reduced unit performanceor nuisance unit shutdown may occm:
Totaline Environmentally Sound Coil Cleaner ApplicationInstructions
1. Proper eye protection such as safety glasses is recom-mended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuumcleaner as described above.
3. Thoroughly wet finned surfaces with clean water trod alow velocity garden hose, being careful not to bend fins.
4. Mix Totaline environmentally sound coil cleaner in a2112gallon garden sprayer according to the instructionsincluded with the cleaner. The optimum solution temper-ature is 100 E
NOTE: Do NOT USE water in excess of 130 E as the enzy-matic activity will be destroyed.
5. Thoroughly apply Totaline environmentally sound coilcleaner solution to all coil surfaces including finned tuea,tube sheets and coil headers.
6. Hold gmden sprayer nozzle close to finned areas andapply cleaner with a vertical, up-and-down motion. Avoidspraying in horizontal pattern to minimize potential forfin damage.
7. Ensure cleaner thoroughly penetrates deep into finnedtueas.
8. Interior and exterior finned tueas must be thoroughlycleaned.
9. Finned surfaces should remain wet with cleaning solutionfor 10 minutes.
10. Ensure surfaces are not allowed to dU before rinsing.Reapplying cleaner as needed to ensure I0-minute satura-tion is achieved.
11. Thoroughly rinse tdl surfaces with low velocity cleanwater using downwmd rinsing motion of water spraynozzle. Protect fins from damage from the spray nozzle.
Condenser Fans -- A formed metal mount bolted to fandeck supports each fan and motor assembly. A shroud and awire gutud provide protection from the rotating fan. SeeFig. 40. The exposed end of the fan motor shall is protectedfi_m weather by grease. If fan motor must be removed forservice or repkicement, be sure to regrease fan shall andreinstall fan guard. The fan motor has a step in the motor shall.For proper performance, fan should be positioned such that it issecurely seated on this step. Tighten the bolt.
Refrigerant Circuit
LEAK TESTING -- Units are shipped with complete operat-ing charge of refrigerant R-134a (see Physical Data tablessupplied in the 30XA insttdlation instructions) and should beunder sufficient pressure to conduct a leak test. If there is nopressure in the system, introduce enough nitrogen to search forfile leak. Repair the leak using good refrigeration practices.After leaks are repaired, system must be evacuated anddehydrated.
REFRIGERANT CHARGE -- Refer to Physical Data tablessupplied in the 30XA installation instructions). Immediatelyahead of filter diier in each circuit is a factory-installed liquidline service valve. Each valve has a l/4-in. Schmder connectionfor charging liquid refrigerant.
METALMOUNT
FAN DECK
WIRE GUARD X
MOTOR
Fig. 40- Fan Mounting
65
Charging with Unit Off and Evacuated -- Close liquid lineservice valve before charging. Weigh in charge shown on unitnameplate. Open liquid line service valve; start unit and allowit to run several minutes fully loaded. Check for a clear sightglass. Be sure clear condition is liquid and not vapoc
Charging with Unit Running -- If charge is to be added whileunit is operating, all condenser fans and compressol_ must beoperating. It may be necessa U to block condenser coils at lowambient temperatures to raise condensing pressure to approxi-mately 198 psig (1365 kPa) to turn all condenser fans on. Do nottotally block a coil to do this. Partially block all coils in unif(mnpattern. Chtu_ge each circuit until sight glass shows dear liquid,and has a liquid line temperature of 103 F (39 C) for 30XA080-350 units and 108 F (42 C) for 30XA400-500 units.
Add 5 lb (2.3 kg) of liquid chtu_ge into the entering filterdrier using the fitting located on the tube entering the bottom ofthe coolec This fitting is located between the electronic expan-sion valve (EXV) and the coolel:
Allow the system to stabilize trod then recheck the liquidtemperature. If needed, add additional liquid charge, 5 lb(Z3 kg) at a time, allowing the system to stabilize betweeneach charge addition. Slowly add charge as the sight glassbegins to clear to avoid overcharging.
IMPORTANT: When adjusting refrigerant chtuge, circu-late fluid through cooler continuously to prevent freezingand possible dmnage to the coolel: Do not overcharge, andnever charge liquid into the low-pressure side of system.
Safety DeviceS--The 30XA chillers cont;fin manysafety devices and protection logic built into the electroniccontrol Following is a description of the major safeties.COMPRESSOR PROTECTION
Motor Overload -- The compressor protection modules(CPM) protect each compressor against overcurrent. Do notbypass the current transducel_ or make any changes to thefactory-installed and configured headers. The configuration ofthese headers defines the Must Trip Amps (MTA) at which theCPM will turn the compressors off. Determine the c;mse fortrouble and correct the problem before resetting the CPM. SeeAppendix C for MTA settings and configuration headers.
Each CPM bo;ud also reads the status of each compressor'shigh-pressure switch. All compressors have factory-installedhigh-pressure switches. See Table 37.
Table 37 -- High-pressure Switch SettingsSWITCH SETTING
UNIT
psig ] kPa30XA 304.5 _+14.5 2099 _+100
If the switch opens during operation, the compressor will beshut down. The CPM will reset automatic_flly when the switchcloses, however, a manual reset of the control is required torestart the compressor:
OIL SEPARATOR HEATERS -- Each oil separator circuithas a heater mounted on the underside of the vessel. The heater
is deenergized anytime the compressor is on. If the compressoris off and outdoor-air temperature (OAT) is greater than 100 F(37.8 C) the heater is deenergized. The heater will also bedeenergized if OAT - SST >32 F (17.8 ° C) and the OAT -LWT > 32F (17.8° C).
COOLER PROTECTION
Low Water Temperature -- Microprocessor is programmedto shut the chiller down if the leaving fluid temperature dropsbelow 34 F (1.1 C) for water or more than 8° F (4.4 ° C) belowset point for Fluid Type = brine. When the fluid temperaturerises 6° F (3.3 ° C) above the leaving fluid set point, the safetyresets and the chiller restarts. Reset is automatic as long as thisis the first occurrence of the day.
IMPORTANT: If unit is installed in an area whereambient temperatures fall below 32 F (0 ° C), a suit-able corrosion-inhibited antifreeze solution or coolerheater must be used in the chilled water circuit.
Relief Devices -- Fusible plugs are located in each cir-cuit between the condenser and the liquid line shutoff valve.PRESSURE RELIEF VALVES -- Valves ;ue installed in eachcircuit and are located on all coolers. These valves are
designed to relieve if an abnormal pressure condition _uises.Relief valves on _fll coolers lelieve at 220 psi (1517 kPa).These valves should not be capped. If a valve lelieves, itshould be replaced. If the valve is not replaced, it may relieveat a lower pressure, or leak due to trapped dirt from the systemwhich may prevent resealing.
Plessure relief valves located on cooler shells have 3/4-in.NPT connections for lelief. Some local building codes requirethat relieved gases be exhausted to a specific location. Thisconnection _fllows conformance to this requirement.
MAINTENANCE
Recommended Maintenance Schedule -- The fol-lowing are only recolmnended guidelines. Jobsite conditionsmay dictate that maintenance schedule is performed more oftenthan recommended.
Routine:
For machines with E-coat condenser coils:
• Check condenser coils for debris; clean as necessary withCarrier approved coil cleaner.
• Periodic clean water rinse, especially in coastal andindustrial applications.
Every month:• Check condenser coils for debris; clean as necessary with
Carrier approved coil cleaner.• Check moisture indicating sight glass for possible refrig-
erant loss and presence of moisture.Every 3 months (for all machines):• Check refrigerant charge.• Check all refrigerant joints and valves for refrigerant
leaks; repair as necessary.• Check chilled water flow switch operation.• Check all condenser fans for proper operation.• Check oil filter pressure drop.• Check oil separator heater operation.Every 12 months (for all machines):• Check all electrical connections; tighten as necessary.• Inspect all contactors and relays; replace as necessary.• Check accuracy of thermistors; replace if greater than
_+2° F (1.2 ° C) variance fiom calibrated thermometer.• Check accuracy of transducers; replace if greater than
_+5psi (34.47 kPa) variance.• Check to be sure that the proper concentration of anti-
freeze is present in the chilled water loop, if applicable.• Verify that the chilled water loop is properly treated.• Check refrigerant filter driers for excessive pressure
drop; replace as necessary.• Check chilled water strainers, clean as necessary.• Check cooler heater operation.• Check condition of condenser fan blades and that they
are securely fastened to the motor shaft.• Perform Service Test to confirln operation of all components.• Check for excessive cooler approach (Leaving Chilled
Water Temperature - Saturated Suction Temperature) whichmay indicate fouling. Clean cooler vessel if necessary.
• Obtain oil analysis; change as necessmy.
TROUBLESHOOTING
See Table 38 for an abbreviated list of sylllptolllS, possiblecauses and possible remedies.
66
Table 38 -- Troubleshooting
SYMPTOM POSSIBLE CAUSE POSSIBLE REMEDY
Unit Does Not Run Check for power to unit • Check overcurrent protection device.• Check non-fused disconnect (if equipped).• Restore power to unit.
Wrong or incorrect unit configuration Check unit configuration,Active alarm Check Alarm status. See the Alarms and Alerts section and follow
troubleshooting instructions,
Active operating mode Check for Operating Modes, See the Operating Modes section and follow trouble-shooting instructions
Unit Operates too Long or Low refrigerant charge Check for leak and add refrigerant.Continuously Compressor or control contacts welded Replace contactor or relay.
Air in chilled water loop Purge water loop.
Non-condensables in refrigerant circuit, Remove refrigerant and recharge.
Inoperative EXV • Check EXV, clean or replace,• Check EXV cable, replace if necessary.• Check EXV board for output signal,
Load too high Unit may be undersized for applicationCircuit Does Not Bun Active alarm Check Alarm status. See the Alarms and Alerts section and follow
troubleshooting instructions.
Active operating mode Check for Operating Modes, See the Operating Modes section and follow trouble-shooting instructions.
Circuit Does Not Load Active alarm Check Alarm status. See the Alarms and Alerts section and followtroubleshooting instructions.
Active operating mode Check for Operating Modes, See the Operating Modes section and follow trouble-shooting instructions.
Low saturated suction temperature See Operating Modes 21,22 and 23.
High circuit suction superheat The circuit capacity is not allowed increase if circuit superheat is greater than 36 F(20 C). See Alarms 59-61 for potential causes,
Low suction superheat The circuit capacity is net allowed to increase if the circuit superheat is less than18° F (10 ° C). See Alarms 62-64 for potential causes.
Compressor Does Not Bun Active alarm Check Alarm status. See the Alarms and Alerts section and followtroubleshooting instructions,
Active operating mode Check for Operating Modes, See the Operating Modes section and follow trouble-shooting instructions.
Inoperative compressor contactor • Check control wiring.• Check scroll protection module,• Check centactor operation, replace if necessary.
Chilled Water Pump is ON, but Cooler freeze protection Chilled water loop temperature too low. Check cooler heater.the Machine is OFF
LEGEND
EXV -- Electronic Expansion Valve
Alarms and Alerts -- Tire integral control system con-stantly monitors tile unit and generates warnings when abnor-mal or fault conditions occur Altu'ms may cause either a circuit(Alert) or the whole machine (Alarm) to shut down. Alarmsand Aletls are assigned codes as described in Fig. 41. Tilealarm/alert indicator LED on the Navigator :r_'_ module isilluminated when tiny alarm or alert condition is present. If anAlert is active, the Alarm Indicator LED will blink. If an Alannis active, the Altu_m Indicator LED will remain on. Cunentlyactive Alerts and Alamts can be found in Alarms-_ALRM-_ALMI to ALMS.
Tire controller generates two types of alarms. Automaticreset ahu_ms will reset without any intervention if the conditionthat caused the ahum corrects itself. Manual reset alarms
require the service technician to check for tile alamt cause andreset the alamt. Tire following method must be followed toreset manual alarms:
Before resetting any alarm, first detemtine the cause of the
alarm and correct it. Enter the Alarms mode indicated by the
LED on the side of the Navigator display. Press _ and
sub-mode Alarm _R.ALM (Reset All Current Alamts) is dis-
played. Press _. The control will prompt the user for a
password, by displaying PASS WORD. Press _ to dis-
play 1111. Press _ for each chmactet: Tile default pass-word is 0111. Use the rerow keys to change each individual
character Use the up or down an'ow keys to toggle the display
to YES and press _. The _tiarms will be reset. Indica-tor light will be turned off when switched correctly. Do not
reset tile chiller at random without first investigating and
correcting the cause(s) of the failure.
Each alarm is described by a three or four-digit code. Thefirst one or two digits indicate tile alarm source and ate listed inFig. 41. The last two digits pinpoint the problem. See Table 39.
An alarm example is shown in Fig. 41.
Alarm Descriptor
Alarm Prefix
A1 - Compressor A1 FailureB1 - Compressor B1 FailureC1 - Compressor C1 FailureCo - Communication Failure
FC - Factory Configuration ErrorMC - Master Chiller Configuration ErrorP - Process FailurePr- Pressure Transducer FailureSr- Service Notificationth - Thermistor Failure
Alarm Suffix
Code Number to identify source
Fig. 41 -- Alarm Description
67
Table 39 -- Alarm Codes
PREFIXCODE
th
Pr
SUFFIXCODE
01
O2
O3
O4
O6
O7
O8
O9
10
11
12
13
14
15
16
17
18
19
21
23
24
25
26
01
O2
O3
O4
O5
O6
O7
O8
10
11
12
13
14
ALARMNUMBER
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
2O
21
22
23
24
25
26
27
28
29
3O
31
32
33
34
35
36
CON J Carrier Comfort Network@CPM J Compressor Protection ModuleEMM J Energy Management ModuleEXV J Electronic Expansion ValveMOP J Maximum Operating Pressure
*NRCP2 is the Energy Management Board.
ALARM DESCRIPTION
Cooler Entering FluidThermistor
Cooler Leaving FluidThermistorCircuit A Defrost ThermistorCircuit B Defrost Thermistor
Condenser EnteringFluid Thermistor
Condenser LeavingFluid ThermistorReclaim CondenserEntering ThermistorReclaim CondenserLeaving ThermistorOAT Thermistor
Master/Slave Common FluidThermistor
Circuit A Suction GasThermistorCircuit B Suction GasThermistorCircuit C Suction GasThermistor
Circuit A Discharge GasThermistor
Circuit B Discharge GasThermistor
Circuit C Discharge GasThermistorCircuit A Condenser Sub-cooling Liquid ThermistorCircuit B Condenser Sub-cooling Liquid ThermistorSpace TemperatureThermistor
Cooler heater feedbackthermistorCircuit A Economizer GasThermistorCircuit B Economizer GasThermistorCircuit C Economizer GasThermistor
Circuit A DischargeTransducer
Circuit B DischargeTransducer
Circuit C DischargeTransducerCircuit A Suction TransducerCircuit B Suction TransducerCircuit C Suction Transducer
Circuit A Reclaim Pump-down Pressure Transducer
Circuit B Reclaim Pump-down Pressure TransducerCircuit A Oil PressureTransducerCircuit B Oil PressureTransducerCircuit C Oil PressureTransducerCircuit A EconomizerPressure TransducerCircuit B EconomizerPressure Transducer
LEGEND
MTAOATSSTUL
REASON FOR ALARM PROBABLE CAUSE
Temperature measuredby the controller is
outside of the rangeof -40 F to 245 F
Measured voltage is0 dc
i Must Trip Ampsi Outdoor Air Temperaturei Saturated Suction Temperaturei Underwriters' Laboratories
ACTION TAKENBY CONTROL
Unit be shut down ornot allowed to start
None
Unit be shut down ornot allowed to startDual chiller deacti-vated. Master and
slave machinesoperate in stand-
alone modeCircuit shut down ornot allowed to start
None
Alarm tripped
None
Circuit economizerfunction disabled
Circuit shut down ornot allowed to start
None
Circuit shut down ornot allowed to start
RESETTYPE
Automatic
Automatic
Faulty Sensor,wiring error or failed
main base board
Configuration error
Faulty Sensor,wiring error or failed
main base board
Faulty Sensor,wiring error, failedEXV or CPM board
Configuration error
Faulty Sensor, wiringerror, failed EMM
board
Configuration error
Faulty Sensor,wiring error, failed
EXV board
Faulty transducer,wiring error, failed
main base board orfan board
Configuration error
Faulty transducer,wiring error, failed
CPM board
68
Table 39 -- Alarm Codes (cont)
PREFIX SUFFIX ALARM ACTION TAKEN RESETCODE CODE NUMBER ALARM DESCRIPTION BY CONTROL TYPE PROBABLE CAUSE
Pr 15 37 Circuit C Economizer Circuit shut down or AutomaticPressure Transducer not allowed to start
Co A1 38
B1 39
C1 40
E1 41
E2 42
E3 43
F1 44
Loss of communication withCompressor Board ALoss of communication withCompressor Board BLoss of communication withCompressor Board CLoss of communication withEXV Board ALoss of communication withEXV Board BLoss of communication withEXV Board CLoss of communication withFan Board 1
REASON FOR ALARM
Measured voltage is0 dc
No communicationwith CPM board
No communication withEXV board
Affectedcompressor shut
down
Affectedcompressorshut down
Automatic
Automatic
Faulty transducer,wiring error, failed CPM
boardWrong CPM address,wrong unit configura-
tion, wiring error, powerloss, failed
CPM board
Wrong EXV boardaddress, wrong unitconfiguration, wiring
error, power loss,failed EXV board
No communication with Circuit A/B shut Automatic Wrong board address,fan board down or not allowed wrong unit configura-
to start (080-120 tion, wiring error, losston), Circuit A shut of power, failed board
down or not allowedto start
(130-500 ton)
F2 45 Loss of communication with No communication with Circuit B shut down Automatic Wrong board address,Fan Board 2 fan board or not allowed to wrong unit configura-
start (130-500 ton) tion, wiring error, lossof power, failed board
F3 46 Loss of communication with No communication with Circuit C shut down Automatic Wrong board address,Fan Board 3 fan board or not allowed to wrong unit configura-
start (400-500 ton) tion, wiring error, lossof power, failed board
No communication with None Automatic Configuration errorfree cooling board
No communication withEMM board
01
O2
O3
Loss of communication with
Free Cooling Board 1
Loss of communication withFree Cooling Board 2
Loss of communication with
Energy ManagementNRCP2* Board
Disable or not allowEMM functions
3 step and 4-20 mAand space tempera-
ture reset, occu-pancy override and
ice build)
NoneLoss of communication withHeat Reclaim Board
Loss of communication withAUX Board 6
Cooler Freeze Protection
47
48
49 Automatic
AutomaticO4 5O
05 51
01 52
No communication
with Free Cooling Board
Wrong moduleaddress, wrong unitconfiguration, wiringerror, power loss to
module, failed module
Configuration error
P Entering or leaving ther- Unit shut down or Automatic, first Faulty thermistor, faultymistor sensed a tempera- not allowed to start occurrence in wiring, low water flow,
ture at or below freeze 24 hours; low loop volume, fouledpoint manual if cooler, or freeze
multiple alarms conditionswithin 24 hours
-- None Automatic Configuration error
Low saturated suction
temperatures detected fora period of time
EXV>98%,suction superheat > 30 F,and SST<MOP for more
than 5 minutes
02 53
03 54
04 55
05 56
06 57
07 58
08 59
09 60
10 61
Condenser Freeze ProtectionCircuit A
Condenser Freeze ProtectionCircuit B
Condenser Freeze ProtectionCircuit C
Circuit A Low Suction
Temperature
Circuit B Low SuctionTemperature
Circuit C Low Suction
Temperature
Circuit A High SuctionSuperheat
Circuit B High SuctionSuperheat
Circuit C High SuctionSuperheat
LEGEND
Automatic, firstoccurrence in
24 hours;manual if
multiple alarmswithin 24 hours
Manual
CON -- Carrier Comfort Network®
CPM -- Compressor Protection ModuleEMM -- Energy Management ModuleEXV -- Electronic Expansion ValveMOP -- Maximum Operating Pressure
MTA -- Must Trip AmpsOAT -- Outdoor Air TemperatureSST -- Saturated Suction TemperatureUL -- Underwriters' Laboratories
*NRCP2 is the Energy Management Board.
Circuit shut down
Circuit shut down
Faulty thermistor, faultywiring, low water flow,
low loop volume, fouledcooler, or freeze
conditions
Faulty transducer,faulty wiring, faulty
thermistor, faulty EXV,low refrigerant charge,plugged or restricted
liquid line
69
Table 39 -- Alarm Codes (cont)
PREFIXCODE
P
SUFFIXCODE
11
12
13
14
28
29
ALARMNUMBER
62
63
64
65
66
67
ALARM DESCRIPTION
Circuit A Low SuctionSuperheatCircuit B Low SuctionSuperheatCircuit C Low SuctionSuperheat
Interlock Failure
REASON FOR ALARM PROBABLE CAUSE
EXV<5% and either thesuction superheat is lessthan the set point by atleast 5 F or the suctiontemperature is greaterthan MOP set point formore than 5 minutes
Lockout Switch Closes
ACTION TAKENBY CONTROL
Circuit shut down
RESETTYPE
Manual Faulty transducer,faulty wiring, faulty
thermistor, faulty EXV,or incorrect
configuration
Unit shut down or Automatic Lock Switch Closednot allowed to start
Electrical Box Thermostat Not supported -- -- --Failure/Reverse Rotation
Loss of communication with Loss of communication Unit change to AutomaticSystem Manager with an external control stand-alone
device for more than operation2 minutes
30 68 Master/Slave communication Communication between Unit change to AutomaticFailure the master and slave stand-alone
machines lost operation
Circuit shut down67
68
69
69
7O
71
Oil pressure and suctionpressure differential isless than the set point
Difference between dis-charge pressure and oilpressure is greater than
50 psi for more than30 seconds
Difference between dis-charge pressure and oilpressure is greater than
30 psi for more than5 minutes
Oil level switch open
7O 72
71 73
72 74
84 75
85 76
86 77
75 78
76 79
77 80
Circuit shut down
Alarm tripped
Circuit shut down ornot allowed to start
Circuit A Low Oil PressureCircuit B Low Oil PressureCircuit C Low Oil Pressure
Automatic, firstoccurrence in
24 hours;manual if
multiple alarmswithin 24 hours
Manual
Manual
Automatic, firstoccurrence in
24 hours;manual if
multiple alarmswithin 24 hours
Automatic
Circuit A Max Oil Filter Differ-ential Pressure
Circuit B Max Oil Filter Differ-ential Pressure
Circuit C Max Oil Filter Differ-ential Pressure
Circuit A High Oil Filter DropPressure
Circuit B High Oil Filter DropPressure
Circuit C High Oil Filter DropPressure
Circuit A Low Oil Level
Circuit B Low Oil Level
Circuit C Low Oil Level
Faul!y communicationwiring, no power
supply to the externalcontroller
Faulty communicationwiring, no power orcontrol power to themain base board of
either module
Plugged oil filter, faultyoil transducer, oil checkvalve stuck, plugged oil
strainer
Plugged oil filter,closed oil valve, bad oil
solenoid, oil checkvalve stuck, faulty oil
transducer
Plugged filter
Low oil level, faultyswitch, wiring error,failed CPM board
MC nn 81 Master chiller configuration Wrong or incompatible Unit not allowed to Configuration errorerror Number 01 to nn configuration data start in Master-slave
control
FC nO 82 No factory configuration No Configuration Unit not allowed to Automatic Configuration errorstart
nn 83 Illegal factory configuration Wrong or incompatible Unit not allowed to AutomaticNumber 01 to 04 configuration data start
P 31 84 Unit is in CCN emergency Emergency stop com- Unit shut down or Automaticstop mand has been received not allowed to start
ManualPump interlock statusdoes not match pump
status
Unit shuts down, ifavailable, another
pump will start
-- None Manual
-- None Manual Configuration error
Cooler pump #1 fault
Cooler pump #2 fault
Circuit shut down
Condenser Flow SwitchFailure
Circuit A Reclaim OperationFailure
Circuit B Reclaim OperationFailure
Circuit A -- Repeated highdischarge gas overrides
Circuit B -- Repeated highdischarge gas overrides
Circuit C -- Repeated highdischarge gas overrides
Automatic
32 85
33 86
15 87
34 88
35 89
37 90
38 91
39 92
CON i Carrier Comfort Network®CPM i Compressor Protection ModuleEMM -- Energy Management ModuleEXV -- Electronic Expansion ValveMOP -- Maximum Operating Pressure
*NRCP2 is the Energy Management Board.
Multiple capacity over-rides due to high
saturated dischargetemperature
LEGEND
MTA i Must Trip AmpsOAT i Outdoor Air TemperatureSST i Saturated Suction TemperatureUL i Underwriters' Laboratories
Configuration error(see Table 40)
Carrier ComfortNetwork® Emergency
Stop commandreceived
Faulty contacts, wiringerror or low control
voltage. Configurationerror.
Configuration error
Condenser airrecirculation, dirty orplugged condenser
coils, inaccuratedischarge transducer,faulty condenser fan
70
PREFIXCODE
P
SUFFIXCODE
4O
41
42
43
73
74
78
79
8O
81
82
83
87
88
89
9O
91
ALARMNUMBER
93
94
95
96
97
98
99
100
101
1O2
1O3
1O4
1O5
1O6
1O7
1O8
1O9
Table 39 -- Alarm Codes (cont)
ALARM DESCRIPTION
Circuit A -- Repeated lowsuction temp overrides
Circuit B -- Repeated lowsuction temp overrides
Circuit C -- Repeated lowsuction temp overrides
Low entering water tempera-ture in heating
Condenser pump #1 default
Condenser pump #2 default
Circuit A High DischargeTemperature
Circuit B High DischargeTemperature
Circuit C High DischargeTemperature
Circuit A Low EconomizerPressure
Circuit B Low EconomizerPressure
Circuit C Low EconomizerPressure
Circuit A Slide Valve ControlUnverifiable
Circuit B Slide Valve ControlUnverifiable
Circuit C Slide Valve ControlUnverifiable
Cooler flow switch set pointconfiguration failure
Cooler flow switch failure
REASON FOR ALARM
Multiple capacityoverrides due to low satu-rated suction temperature
ACTION TAKENBY CONTROL
Circuit shut down
RESETTYPE
Automatic
PROBABLE CAUSE
Inaccurate
transducer, faulty EXV,low refrigerant charge,plugged or restrictedliquid line filter drier.
Not supported
-- Configuration errorNone
Circuit shut down
Circuit shut down
Discharge gas tempera-ture is higher than 212 F
for more than 90 seconds
Alarm tripped
Manual
Manual
Manual
Manual
The economizer pressureis below the suction pres-sure more than 14.5 psi
for more than 10 seconds
If 100% load current isless than 1.3 times of 30%load current, or 30% load
current is greater than0.78 times of expected
100% load current
Faulty transducer/highpressure switch, low/restricted condenser
flow
Faulty transducer,faulty main base board,
faulty wiring, closedsuction service valve,
faulty EXV
CPM board detects cur-
rent unbalance greaterthan 65% for more than
1 second
Slide valve stuck, inac-curate initial current
reading
-- None Manual Configuration error
Flow switch open Unit shut down Manual if unit Faulty flow switch, lowis running, cooler flow, faultyautomatic wiring, faulty coolerotherwise pump, faulty main base
board
Sr nn 110 Service maintenance alert Field programmed None Manual Maintenance requiredNumber # nn elapsed time has expired
for maintenance time
A1, B1, Cl 01 111-01, Compressor Motor tempera- Compressor temperature Circuit shut down Manual Motor cooling solenoid112-01, ture too high higher than 232 F for or economizer113-01 more than 90 seconds EXV failure, faulty
CPM board, lowrefrigerant charge
02 111-02, Compressor Motor tempera- Compressor temperature Circuit shut down Manual Faulty thermistor, faulty112-02, ture out of range reading out of the range of wiring, faulty CPM113-02 -40 F to 245 F board
03 111-03, Compressor High pressure HPS input on CPM board Circuit shut down Manual Loss of condenser air112-03, switch protection open flow, operation beyond113-03 compressor envelope,
faulty high pressureswitch, faulty wiring,
faulty CPM board
04 111-04, Compressor Over current CPM board detects high Circuit shut down Manual Operating beyond112-04, motor current compared chiller envelope, incor-113-04 with MTA setting rect configuration
05 111-05, Compressor Locked rotor CPM board detects locked Circuit shut down Manual Compressor motor fail-112-05, rotor current compared ure, unloader slide113-05 with MTA setting valve failure, compres-
sor mechanical failure
Circuit shut down Manual Blown fuse, wiringerror, loose terminals
06 111-06,112-06,113-06
07 111-07,112-07,113-07
08 111-08,112-08,113-08
09 111-09,112-09,113-09
Compressor Phase loss L1
Compressor Phase loss L2
Compressor Phase loss L3
Compressor Low current CPM detects motor cur- Circuit shut down Manual Power supply discon-alarm rent less than a certain nected, blown fuse,
percentage of the MTA wiring error, contactsetting deenergized, faulty
current toroid.
-- Must Trip Amps-- Outdoor Air Temperature-- Saturated Suction Temperature-- Underwriters' Laboratories
LEGENDCON i Carrier Comfort Network® MTACPM -- Compressor Protection Module OATEMM -- Energy Management Module SSTEXV -- Electronic Expansion Valve ULMOP -- Maximum Operating Pressure
*NRCP2 is the Energy Management Board.
71
Table 39 -- Alarm Codes (cont)
PREFIX SUFFIX ALARM ALARM DESCRIPTION REASON FOR ALARM ACTION TAKEN RESET PROBABLE CAUSECODE CODE NUMBER BY CONTROL TYPE
A1, B1, C1 10 111-10, Compressor Y delta starter If the delta mode current Circuit shut down Manual Power supply to delta112-10, 3urrent increase failure alarm is not 25% greater than contactor not113-10 the current in Y mode connected, faulty delta
contactor or wiring,faulty CPM board
11 111-11, Compressor Contactor failure CPM board detects Circuit shut down Manual Faulty contactor, con-112-11, greater than 15% of MTA tactor welded, wiring113-11 current for 10 seconds error
after shutting off the com-pressor contactor. Oilsolenoid is energized.
12 111-12, Compressor Unable to stop CPM board detects Circuit shut down Manual Faulty contactor,112-12, motor greater than 15% of MTA contactor welded,113-12 current for 10 seconds wiring error
after three attempts
13 111-13, Compressor Phase reversal CPM board detects phase Circuit shut down Manual Terminal block power112-13, reversal from current supply lead not in113-13 toroid correct phase. Power
supply leads goingthrough toroid crossed
14 111-14, Compressor MTA configura- MTA setting is out of the Circuit shut down Manual Incorrect MTA setting,112-14, tion fault allowed MTA range faulty CPM board113-14
15 111-15, Compressor Configuration CPM board MTA setting Circuit shut down Manual Incorrect CPM112-15, switch mismatch do not match factory dipswitch setting,113-15 configuration incorrect factory MTA
setting, faulty CPMboard
16 111-16, Compressor Unexpected CPM board dipswitch Sl Circuit shut down Manual Incorrect CPM112-16, switch setting change setting changed dipswitch setting, faulty113-16 CPM board
17 111-17, Compressor Power on reset CPM board detects a Circuit shut down Manual Power supply112-17, power failure interruption113-17
18 111-18, Compressor UL 1998 critical Software error Circuit shut down Manual Electric noise, faulty112-18, section software error CPM board113-18
19 111-19, Compressor UL 1998 current Software error Circuit shut down Manual Electric noise, faulty112-19, measure dual channel CPM board113-19 mismatch
LEGEND
CCN -- Carrier Comfort Network@CPM -- Compressor Protection ModuleEMM -- Energy Management ModuleEXV -- Electronic Expansion ValveMOP -- Maximum Operating Pressure
MTA -- Must TripAmpsOAT -- Outdoor Air TemperatureSST -- Saturated Suction TemperatureUL -- Underwriters' Laboratories
*NRCP2 is the Energy Management Board.
DIAGNOSTIC ALARM CODES AND POSSIBLECAUSES
Thermistor Failure
Alarln 1 -- Cooler Fluid Entering (th.01 )Alarm 2 -- Cooler Fluid Leaving (th.02)
Criwriafbr Trip -- This _flarm criterion is tested whether theunit is on or off if the temperature as measured by the ther-mistor is outside of the range -40 to 245 F (-40 to 118.3 C).
Action to be Taken -- The unit shuts down normally, or is notallowed to start.
Reset Method -- Automatic, the alarm will reset once the ther-mistor reading is within the expected range.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to the Main Base Board• sensor accuracy
See the Thermistol.s section on page 52 for thermistor de-scription, identifiers and connections.Defrost Thermistor Failure
Alarm 3 -- Circuit A (th.03)Alarm 4 -- Circuit B (th.04)
NOTE: These _flmms me not used or supported. If this condi-tion is encountered, confirm machine configuration.Thermistor Failure
Alarm 5 -- Condenser Entering Fluid (th.06)
Akum 6 -- Condenser Leaving Fluid (th.07)
NOTE: These alarlns are not used or supported. [f this condi-tion is encountered, confirm machine configuration.Condenser Reclaim Thermistor
Aimin 7-- Reclaim Entering Fluid (th.08)
Almm 8 -- Reclaim Leaving Fluid (th.09)
NOTE: Alarms 7 and 8 are not used or supported. If this condi-tion is encountered, confirm machine configuration.
Alarm 9 -- Outdoor Air Temperature Thermistor Failure
CriWriajbr Trip -- This aku'm criterion is tested whether theunit is ON or OFF. The alarm is tripped if the temperaturemeasured by the outdoor air thermistor sensor is outside therange of_40 to 245 F (_4-0 to 118.3 C).
Action to be Taken -- The unit shuts down normally, or is notallowed to st_ut.
Reset Method -- Automatic, the alarm will reset once the ther-mistor reading is within the expected range.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to the Main Base Board• a faulty thermistor
See the Thermistors section on page 52 for thermistor de-scripfion, identifiers and connections.
72
Alarm 10 -- Master/Slave Common Fluid Thermistor
CriWriafbr Trip -- This almm criterion is tested whether theunit is ON or OFF. Tile alarm will be tripped if the unit isconfigured as a master or a slave (MSSL), leaving temperaturecontrol is selected (EWTO), and if the temperature measuredby the CHWS (chilled water sensor) fluid sensor is outside therange of-40 to 245 F (-40 to 118.3 C).
A_Tion to be Taken -- Master/slave operation is disabled andthe chiller returns to stand alone mode.
Reset Method-- Reset is automatic when the thermistor mad-ing is inside the range of-40 to 245 F (-40 to 118.3 C).
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to the Main Base Board• a faulty thermistor
See the Thermistors section on page 52 for themristor de-scription, identifiers and connections.
Suction Gas Thermistor
Almm 11 -- Circuit A (th. 12)Almm 12 -- Circuit B (th. 13)Akum 13 -- Circuit C (th. 14)
CriWriafi_r Trip -- This aku'm criterion is tested whether theunit is ON or OFE [f the suction gas temperatme as measuredby the thermistor is outside of the range -40 to 245 F (-40 to118.3 C).
Action to be Taken -- The affected circuit shuts down
norln_dly.
Reset Method -- Automatic, once the thermistor reading iswithin the expected range. The affected circuit will restart oncethe alarm has cleared.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to the EXV board• board for a faulty channel• a faulty thermistor
See the Thermistors section on page 52 for themristor de-scription, identifiers and connections.
Circuit Discharge Gas Thermistor Sensor Failure
Almm 14 -- Circuit A (th. 15)Almm 15 -- Circuit B (th. 16)Almm 16 -- Circuit C (th. 17)
Criteria fi_r Trip -- This almm criterion is tested whether theunit is ON or OFF. The alarm is tripped if the temperaturemeasured by the Outdoor Air Thermistor sensor is outside therange of-40 to 245 F (-40 to 118.3 C).
Action to be Taken -- The unit shuts down normally, or is notallowed to st_ut.
Reset Method -- Automatic, the alarm will leset once the ther-mistor leading is within the expected range.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to the CPM board• a faulty thermistor• a faulty channel on the board
See the Thermistors section on page 52 for thermistor descrip-tion, identifiers and connections.
Condenser Subcooling Liquid Thermistor
Alarln 17 -- Circuit A (th. 18)Almm 18 -- Circuit B (th. 19)
NOTE: Alarms 17 and 18 are not used or supported. If thiscondition is encountered, confirm machine configuration.
Alarm 19 -- Space Temperature Sensor Failure (th.21)
Criteriafi_r Trip -- This alarm criterion is checked whether theunit is ON or OFF and if Space Temperature Reset has beenenabled. This alarm is generated if the outdoor-air temperatureas measured by the thermistor is outside of the range -40 to245 F (-40 to 118.3 C).
Action to be Taken -- Unit operates under norm_fl control.Temperature Reset based on Space Temperature is disabled.
Reset Method -- Automatic, once the thermistor reading iswithin the expected range. The Space Temperature Reset willresume once the alarm has clemed.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to the Energy Management Module• board for a faulty channel• a faulty thermistor
For themristor descriptions, identifiers and connections, seethe Thermistors section.
Alarm 20 -- Cooler Heater Feedback Sensor Thermistor
NOTE: Alarm 20 is not used or supported. If this condition isencountered, confirm machine configuration.
Economizer Gas Thermistor
Alarm 21 --Circuit A (th.24)Alarm 22 -- Circuit B (th.25)Alarm 23 -- Circuit C (th.26)
CriWria .for Trip -- This alarm criterion is tested whether theunit is ON or OFF. The akum is tripped if the Economizer gasreading is outside the range of M-0 to 245 F (-40 to 118.3 C).
Action to be Taken -- The unit shuts down normally, or is notallowed to start.
Reset Method -- Automatic, the alarm will reset once the ther-mistor reading is within the expected range.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to the EXV board• a faulty thermistor• a faulty channel on the board
See the Thermistol_ section on page 52 for thermistor descrip-tion, identifiers and connections.
Discharge Transducer
Alarm 24 -- Circuit A (Pl:01)Alarm 25 -- Circuit B (Pc02)Alarm 26 -- Circuit C (Pl:03)
Criteriafi_r Trip -- The criterion is tested whether the circuit isON or OFF. This alarm is generated if the voltage as sensed bythe MBB or Fan Bomd C (FBC) is 0 vdc, which conespondsto the NavigatoF TM display of-7 psi (-48.3 kPa).
Action to be Taken -- The circuit is shut down normally, or not_fllowed to start.
Reset Method -- Automatic, once the transducer voltage isgreater than 0 vdc, which corresponds to the Navigator displayof a value greater than -7 psi (-48.3 kPa).
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to Main Base Board (Alarms 24 and 25)• sensor wiring to Fan Board C (Alarm 26)• board for a faulty channel• for a faulty transducer• confirm unit configuration
73
Suction Pressure Transducer Failure
Alarln 27 -- Cimuit A (Pl:04)Alarm 28 -- Circuit B (171.05)Alarm 29 -- Circuit C (1'1.06)
Criteria fsr Trip -- The criteria are tested whether the circuit isON or OFE The akum is generated if one of the followingcriteria is met:
1. If the voltage as sensed by the MBB or Fan Board C is0 vdc, which corresponds to the Navigato( r_'l display of-7 psi (-48.3 kPa).
2. The circuit is ON in cooling mode and the SaturatedSuction Temperature (SST) for the circuit is greaterthan the Entering Water Temperature for more than60 seconds.
Action to be Taken -- The circuit is shut down immediately, ornot allowed to start.
Reset Method
1. Automatic, once the transducer voltage is greater than0 vdc, which corresponds to the Navigator display of avalue greater than -7 psi (-48.3 kPa).
2. Automatic once the circuit's saturated suction tempera-ture is lower than the Leaving Water Temperature by 3° F(1.6 ° C). If this criterion trips the alarm 3 times within a24-hour period, the alarm changes to a manual reset.
Pos_ffble Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to Main Base Board (Alarms 27 and 28)• sensor wiring to Fan Board C (Alarm 29)• board for a faulty channel• faulty transducer• faulty leaving water temperature sensor• unit configuration
Reclaim Pumpdown Pressure Transducer
Alarm 30 -- Circuit A (Pr07)Alarm 31 -- Circuit B (Pl:08)
NOTE: Alarms 30 and 31 me not used or supported. If thiscondition is encountered, confirm machine configuration.
Oil Pressure Transducer
Alarm 32 -- Circuit A (Pl: 10)Alarm 33 -- Circuit B (Pl: 11)Alarm 34 -- Circuit C (Pl: 12)
Criteiqafi_r Trip -- The criteria are tested whether the circuit isON or OFE The alarm is generated if one of the following cri-teria is met:
1. If the voltage as sensed by the MBB or Fan Board C is0 vdc, which corresponds to the Navigator display of-7 psi (-48.3 kPa).
2. The circuit is OFF and outside air temperature is below35.6 F (2 C).
3. The circuit is OFF and the fluid type is brine.
Action to be Taken -- The circuit is shut down immediately, ornot allowed to start.
Reset Method -- Automatic, once the transducer voltage isgreater than 0 vdc.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to CPM board• board for a faulty channel• faulty transducer• plugged oil filter• faulty oil solenoid valve coil• stuckoil solenoid valve
• confirm unit configuration
Economizer Pressure Transducer Failure
Altuln 35 -- Circuit A (Pl: 13)Altmn 36 -- Circuit B (1'1. 14)Akum 37 -- Circuit C (Pl: 15)
Cl4wriafi_r Trip -- The criteria are tested whether the circuit isON or OFF. The alarln is generated if the voltage as sensed bythe MBB or Fan Board C is 0 vdc, which corresponds to theNavigator display of-7 psi (-48.3 kPa).
Action to be Taken -- The circuit is shut down immediately, ornot allowed to start.
Reset Method -- Automatic, once the transducer voltage isgreater than 0 vdc, which conesponds to the Navigator displayof a value greater than -7 psi (-48.3 kPa).
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to EXV Board• EXV board for a faulty channel• faulty transducer• faulty economizer EXV or EXV wiring• faulty economizer EXV channel on the board• closed or partially closed suction service valve• confirm unit configuration
Loss of Communication with Compressor BoardAl_u'ln 38 -- Complessor Board A (Co.AI)Al+uln 39 -- Compressor Board B (Co.B 1)Al+um 40 -- Compressor Board C (Co.C 1)CriWria fi+r Trip -- The +flarm criterion is tested whether theunit is ON or OFF. If communication with the CompressorProtection Module Board (CPM) is lost for a period of 10 sec-onds, the alarm will be generated.
A++ion to be Taken -- The affected compressor will be shutdown.
Reset Method -- Automatic, if communication is established.If called for. the compressor will stmt normally.
Possible Causes -- If this condition is encountered, check thefollowing items:• power supply to the affected CPM board• address of the CPM• local equipment network (LEN) wiring• confirm unit configuration
Loss of Communication with EXV Board
Aku'm 41 -- Circuit A, EXV Board A (Co.A 1)Altum 42 -- Circuit B, EXV Board B (Co.B2)Akum 43 -- Circuit C, EXV Board C (Co.C3)
CriWria fi_r Trip -- The alarm criterion is tested whether theunit is ON or OFF. If communication with EXVA, B or C islost for a period of 10 seconds, the alarm will be triggered.
A_Tion to be Taken -- [f running, Circuit A, B or C will shutdown normally. If Circuit A, B or C is not operating, it will notbe allowed to start.
Reset Method -- Automatic, if communication is established,the unit will start normally.
Possible Causes -- If this condition is encountered, check thefollowing items:• power supply to EXVA, B or C• address of the EXV board
• local equipment network (LEN) wiring• confirm unit configuration
Alarm 44 -- Loss of Communication with Fan Board 1
CriWria._sr Trip -- The criterion is tested whether the unit isON or OFF. If communication with Fan Board A is lost for a
period of 10 seconds, the alarm will be triggered.
74
Action to be Taken -- If file number of fans per circuit isgreater than four fans per cimuit, Cimuit A will shut down nor-m_flly if they am running. Cimuit B will continue to run. If thecircuit or cimuits conholled by the board am not running, thenthey will not be allowed to start.
Reset Method -- Automatic, if communication is established,the unit will stmt normally.
Possible Causes -- If this condition is encountered, check thefollowing items:• power supply to Fan Board A• address of the Fan Board A• local equipment network (LEN) wiring• confirm unit configuration
Alarm 45 -- Loss of Communication with Fan Board 2
Criteriafi_r Trip -- The criterion is tested whether the unit isON or OFE and only if Cimuit A or B has morn than four fansper cimuit.NOTE: Fan Board B controls Cimuit B only.
A_Hon to be Taken -- If communication with Fan Board B islost for a period of 10 seconds, the alarm will be triggered. Ifrunning, Cimuit B will shut down normally. If Cimuit B is notrunning, then it will not be allowed to start.
Reset Method -- Automatic, if communication is established,the unit will stmt normally.
Possible Causes -- If this condition is encountered, check thefollowing items:• power supply to Fan Board B• address of the Fan Board B
• local equipment network (LEN) wiring• confirm unit configuration
Alarm 46 -- Loss of Communication with Fan Board 3
Criteria /or Trip -- The criterion is tested whether the unit isON or OFF. and on units with three cimuits only. [f communi-cation with Fan Bomd C is lost for a period of 10 seconds, thealarm will be triggered.
A_Hon to be Taken -- [f running, Cimuit C will shut down nor-mally. If the cimuit is not running, then it will not be allowed tostart.
Reset Method -- Automatic, if communication is established,the unit will stmt normally.
Possible Causes -- If this condition is encountered, check thefollowing items:• power supply to Fan Board C• address of the Fan Board C• local equipment network (LEN) wiring• confirm unit configuration
Loss of Communication with Free Cooling Board
Almm 47 --Bom'd 1 (Co.01)Almm 48 -- Bomd 2 (Co.02)
NOTE: Alarms 47 and 48 are not used or supported. If thiscondition is encountered, confirm machine configuration.
Alarm 49 -- Loss of Communication with Energy Manage-ment Module Board (Co.03)
Criwria/or Trip -- The criterion is tested whether the unit isON or OFF and when a fimction that requires the EnergyManagement Module (EMM) is configured. If communicationwith the EMM is lost for a period of 10 seconds, the alarm willbe triggered.
Action to be _iken -- If any function controlled by the EMM(3-Step and 4-20 mA Demand Limit, 4-20 mA and SpaceTemperature Reset, Occupancy Ovemde, and Ice Build) is
active, that fimction will be terminated. If an EMM function isprogrammed, and communication is lost, the function will notbe allowed to start.
Reset Method -- Automatic, if communication is established,the functions will be enabled.
Possible Causes -- If this condition is encountered, check thefollowing items:
• The EMM is installed, (Configuration-+UNIT-+EMM).If (EMM=YES), check for a control option that requiresthe EMM that may be enabled (correct configuration ifnot correct).
• power supply to EMM• address of the EMM• local equipment network (LEN) wiring• confirm unit configuration to be sure that no options that
require the EMM are enabledAlarm 50 -- Loss of Communication with Heat Reclaim
Board (Co.O4)
NOTE: Almm 50 is not used or supported. If this condition isencountered, confirm machine configuration.Alarm 51 -- Loss of Communication with AUX Board 6
NOTE: Almm 51 is not used or supported. If this condition isencountered, confirm machine configuration.
Alarm 52 -- Cooler Freeze Protection (P.01 )
Criteria /or Trip -- The _darm criteria me checked whether theunit is ON or OFE If the entering or leaving water thermistorsenses a temperature at the freeze point or less, the almm willbe generated. For a fresh water system (Configuration---_$'ERV--+FLUD=I), the freeze point is 34 F (1.1 C).For medium temperature brine systems (Col_guration---_ERV--cFLUD=2), the freeze point is Brine Freeze SetPoint (Configuration --_ER V--_LOSP).
Action to be Taken -- Unit shut down or not allowed to start.
Chilled water pump will be started.
Reset Method -- Automatic, first occunence in 24 hours ifLWT rises to 6° F (3 ° C) above set point. Manual, if more thanone occurrence in 24 hours.
Possible Causes -- If this condition is encountered, check thefollowing items:• entering and leaving fluid thermistors for accuracy• water flow rate
• loop volume -- low loop volume at nominal flow ratescan in extreme cases bypass cold water to the cooler
• freezing conditions• heater tape and other freeze protection items for proper
operation• glycol concentration and adjust LOSP accordingly• If the Leaving W_tter Set Point is above 40 F (4.4 C) and
there is glycol in the loop, consider using the MediumTemperature Brine option (Configuration--÷SERV--÷FLUD=2) to utilize the brine freeze point instead of 34 F(l.l C)
Condenser Freeze Protection
Alarm 53 -- Circuit A (R02)Alarm 54 -- Circuit B (R03)Alarm 55 -- Circuit C (R04)
NOTE: Alarms 53-55 me not used or supported. If this condi-tion is encountered, confirm machine configuration.
Low Saturated Suction Temperature
Alarm 56 -- Circuit A (R05)Alarm 57 -- Circuit B (R06)Alarm 58 -- Circuit C (R07)
75
Criteria for Trip -- The criteria are tested only when thecircuit is ON. This alarm is generated if one of the followingcriteria is met:
• If the circuit Saturated Suction Temperature is below-13 F (-25 C) for more than 30 seconds.
• If the circuit Saturated Suction Temperature is below-22 F (-30 C) for more than 8 seconds.
• If the circuit Saturated Suction Temperature is below-40 F (-40 C) for more than 3 seconds.
Action to be _tken -- The circuit is shut down immediately.
Prior to the ahum trip, the control will take action to avoidthe alarm. See Operating Modes 21,22 and 23 on page 51.
Reset Method -- Automatic, first occurrence in 24 hours.Manual, if more than one occurrence in 24 hours.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to Main Base Board (Alarm 56 and 57) or
Fan Board C (Alarm 58)• board for a faulty channel• faulty suction transducer• cooler water/low• loop volume• EXV operation• liquid line refrigerant restriction, filter drier, service
valve, etc• refrigerant charge• If the Leaving Water Set Point is above 40 F (4.4 C)
and there is glycol in the loop, consider using theMedium Temperature Brine option (Conflguration--€SERV--+FLUD=2) to utilize the brine freeze pointinstead of 34 F (1.1 C).
High Suction SuperheatAlarm 59 -- Circuit A (1:'.08)Alarm 60 -- Circuit B (R09)Alarm 61 --Circuit C (RI0)
Criteria for Trip -- The criteria are tested only when the cir-cuit is ON. This ahum is generated if all of the following crite-ria are met:• The EXV position is equal to or greater than 98%.• The circuit's Suction Superheat (Suction Gas Tempera-
ture - Saturated Suction Temperature) is greater than thesuperheat control set point.
• The circuit's Saturated Suction Temperature is less thanMaximum Operating Pressure (MOP) set point (Config-uration ---_SERV--+MOP) for more than 5 minutes.
Action to be _tken -- The circuit is shut down normally.Reset Method -- Manual.
Possible Causes -- If this condition is encountered, check thefollowing items:• suction pressure transducer wiring to Main Base Board
(Alarm 59 and 60) or Fan Board C (Alarm 61 )• board for a faulty channel• a faulty suction transducer• suction gas thermistor wiring to EXV Board 1 (Alarm
41) otto EXV Board 2 (Alarm 43)• suction gas thermistor sensor for accuracy• for EXV Board 1 (Alarm 41) or EXV Board 2 (Alarm
42) faulty channel• EXV operation• a liquid line refrigerant restriction, filter drier, service
valve, etc• refrigerant charge
Low Suction Superheat
Alarln 62 --Circuit A (P.I 1)Alarm 63 -- Circuit B (P. 12)Alarm 64 -- Circuit C (P. 13)
Cdwda.fi_r Trip -- The criteria are tested when the circuit isON. This alarm is generated if the following criterion is met:
The EXV position is equal to or less than 5% and the cir-cuit's Suction Supeflleat (Suction Gas Temperature - SaturatedSuction Temperature) is less than the Suction Supeflleat SetPoint (Configuration--)SERV--)SHP.A, Cotlfiguration --€SERV--_S'HP.B, or (2btlfiguration--AS'ERV--_S'HP.C) by atleast 5° F (2.8 ° C) or the circuit Saturated Suction Temperatureis greater than Maximum Operating Pressure (MOP) set point(Cotlfiguration _SERV---_MOP) for more than 5 minutes.
A_Tion W be Taken -- The circuit is shut down normally.
Reset Method -- Automatic, first occurrence in 24 hours.Manu_d, if more than one occurrence in 24 hours.
Possible Causes -- If this condition is encountered, check thefollowing items:• suction pressure transducer wiring to Main Base Board
(Alarln 62 and 63) or Fan Board C (Alarm 64)• board for a faulty channel• faulty suction transducer• suction gas thermistor wiring to EXV Board 1 (Alarm
41) or to EXV Board 2 (Alarm 42)• suction gas thermistor sensor for accuracy• EXV Board 1 (Alarm 41) or EXV Board 2 (Alarm 42)
faulty channel• EXV operation• confirm maximum operating pressure set point• refiigerant chargelevel
Alarm 65 -- Interlock Failure (RI4)
Cdwria for Trip -- The criteria gue tested whether the unit isON or OFE This alarm is generated if the lockout switch(located in the Energy Management Module) is closed duringnormal operation.
Action to be Taken -- All compressors are shut down immedi-ately without going through pumpdown, and is not allowed tostart.
Reset Method -- Automatic, first occurrence in 24 hours.Manu_d, if more than one occunence in 24 hours.
Possible Causes -- If this condition is encountered, check thefollowing items:• chilled water flow switch operation• water flow. Be sure all water isolation valves are open
and check water strainer for a restriction• interlock wiring circuit• power supply to the pump• control signal to the pump controller• chilled water pump operation• cooler pump contactor for proper operation
Alarm 66 -- Electrical Box Thermostat Failure/ReverseRotation (R28)
NOTE: Ahum 66 is not used or supported. If this condition isencountered, confirm machine configuration.
Alarm 67 -- Loss of Communication with System Manager
Cdwria for Trip -- The criterion is tested whether the unit isON or OFF. This _darm is generated if the System Managerhad established communications with the machine and is thenlost for more than 2 minutes.
Action to be _tken -- The action to be taken by the controldepends on the configuration. If Auto St:ut when SM lost isenabled, (Configuration---)SERV---)AU.SM=YES), then theunit will force the CCN Chiller Start Stop to ENBL and clearall forced points from the System Managel: The unit will revertto stand-alone operation.
76
Reset Method -- Automatic, once communication isre-established.
Possible Causes -- If this condition is encountered, check thefollowing items:• communication wiring• power supply to the System Manager and unit controls
Alarm 68 -- Master/Slave Communication Failure (R30)
Criteriafl_r Trip -- The criterion is tested whether the units areON or OFF and a Master and Slave machine has been config-ured, (Configuration---)RSET---)MSSL=l and Cottfiguration--+RSET--+MSSL=2). If communication is lost for more than3 minutes, this alfum is generated.
Action to be Taken -- Dual chiller control will be disabled andeach unit will operate in Stand-Alone mode.
Reset Method -- Automatic, once communication isre-established.
Possib& Causes -- If this condition is encountered, check thefollowing items:• CCN wiring• control power to each Main Base Board, master and
slave
• confirm correct configurationLow Oil Pressure
Akum 69 -- Circuit A (E67)Alfuln 70 -- Circuit B (R68)Alfum 71 -- Circuit C (R69)
Criteriafl)r Tril? -- The criteria are tested only when the com-pressor is ON. The fdarm is generated if one of the followingOccurs, where:
oil = oil plessure transducer reading for the appropriate com-pressor
sl) = suction pressure reading for the affected circuit
dp= discharge pressure reading for the affected circuit
oil_spl = 0.7 x (dp-sp) + sp
oil sp2 = sp + 7.2 psi (15 seconds 'after slarl)
oil sp2 = sp + 14.5 psi (45 seconds after start)• ff the compressor starts with the ambient temperature
(OAT less than 3.6 ° F [2 ° C] the oil pressure monitoringis delayed by 30 seconds.
A_Tion to be Taken -- The affected compressor will bestopped. The other compressors will continue to operate.Reset Method -- Manual.
Possible Causes -- If this condition is encountered, check thefollowing items:• sensor wiring to the CPM Board• board for a faulty channel• faulty transducer• plugged oil filter• faulty oil solenoid valve coil• stuck oil solenoid valve• stuck check valve
• manual shut off valve to ensure it is not fully open• confirm unit configuration
Max Oil Filter Differential Pressure Failure
Alfum 72 -- Circuit A (R70)Alfum 73 -- Circuit B (R71)Akum 74 -- Circuit C (R72)
CriWriafi)r Trip -- The criterion is tested when the compres-sor has been operating for fit least 5 seconds. The alarm isgenerated if the difference between the Circuit Dischalge Pies-sure and the Complessor Oil Pressure is greater than 50 psi(345 kPa) for more than 30 seconds.
Action to be Taken -- The affected compressor will be turnedoff.
Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• check the discharge and oil sensor wiring to the Main
Base Board and CPM board• boards for a faulty channel• faulty transducer• plugged oil tilter• faulty oil solenoid valve coil• stuck oil solenoid valve• stuck check valve• manual shut off valve to ensure it is not fully open
Check the power supply to the System Manager and unitcontrols.
High Oil Filter Pressure Drop
Alarm 75 -- Circuit A (R84)Alarm 76 -- Circuit B (R85)Alarm 77 -- Circuit C (R84)
Criteria._br Trip -- The criterion is tested when the compres-sor has been operating for fit least 5 seconds. The alarm is gen-erated if the diffelence between the Circuit Dischmge Plessurefind the Compressor Oil Plessure is greater than 30 psi formore than 5 minutes.
Action to be _tken -- The complessor will continue to run.
Reset Method-- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• discharge and oil sensor wiring to the Main Base Board
and CPM board• boards for a faulty channel• faulty transducer• plugged oil filter• faulty oil solenoid valve coil• stuck oil solenoid valve• stuck check valve
• manual shut off valve to ensure it is not fully open
Check the power supply to the System Manager and unitcontrols.
Low Oil Level Failure
Alarm 78 -- Circuit A (R75)Alarm 79 -- Circuit B (R76)Alarm 80 -- Circuit C (R77)
Criteria ._br Trip -- The criteria are tested whether the com-pressor is on or off. The almm is generated if:• The compressor is not running and an increase in capac-
ity is required and the compressor is not started.• The compressor is running and the oil level switch is
open for more than 45 seconds.
Action to be Taken -- The affected compressor will be turnedoff.
Reset Method -- Automatic, when the oil level is elevated,first three times the alarm is tripped in a 24-hour period. Mfm-ual if alarm is tripped mole than three times in a 24-hourperiod.
Possible Causes -- If this condition is encountered, check thefollowing items:• oil level in the oil separator• oil level switch wiring to the CPM board• CPM board for a faulty channel• faulty oil level switch
Alarm 81 -- Master Chiller Configuration Error (MC.nn)
Criteria fi)r Trip -- The criterion is tested whether flae unit isON or OFF. The units must be configured as a Master andSlave machine (Configuration --)RSET--cMSSL=I and Con-figuration_RSET--+MSSL=2), find one of the followingconfiguration enors has been found. The "nn" refers to theerror code listed in Table 40.
77
Table 40 -- Master/Slave Alarm Code
MCERROR MASTER SLAVE DESCRIPTIONCODE
The master or slave water pump is not configured while the control of the lag unit pump is required01 X X (lag_pump = I)02 X Master and slave units have the same network address.
03 X There is no slave configured at the slave address
04 X Slave pumpseq incorrect configuration
There is a conflict between the master and the slave LWT option: the master is configured for EWT control05 X while the slave is configured for LWT control.
There is a conflict between the master and the slave LWT option: the master is configured for LWT control06 X while the slave is configured for EWT control.
There is a conflict between the master and the slave pump option: the master is configured for lag pump07 X control while the slave is not configured for lag pump control.
There is a conflict between the master and the slave pump option: the master is not configured for lag pump08 control while the slave is configured for lag pump control.
09 X The slave chiller is in local or remote control (chilstat = 3)
10 X The slave chiller is down clue to fault (chilstat = 5)
11 The master chiller operating type is not Master: masteropertyp12 X No communication with slave.
13 Master and slave heat cool status are not the same.
EWT =LWT =
X
X
X
X
X
X
LEGEND
Entering Water TemperatureLeaving Water Temperature
Action to be Taken -- Unit not _dlowed to stmt in Master Slavecontrol.
Reset Method -- Automatic
Possible Causes -- If this condition is encountered, check thefollowing:• CCN wiring.• Control power to each Main Base Board, master and
slave.• Move to first position.• Confirm unit configuration.
Alarm 82 -- Initial Factoly Configuration Required (FC.n0)
CriteHa.fbr Trip -- The criterion is tested whether the unit isON or OFF. The alarm will be generated if the Configuration_UNIT -¢TONS=O.
Action to be Taken -- The unit is not allowed to stmt.
Reset Method- Automatic after factoly configuration is com-plete. The configuration must be manually completed.
Possible Causes -- If tiffs condition is encountered, confirmthe unit configuration.
Alarm 83 --Illegal Configuration IFC.nn)
Cr#eriafi,r Trip -- The criterion is tested whether the unit isON or OFF. The alarm will be generated if file one of thefollowing configuration errors is detected by the control. The"nn" refers to the error code listed in Table 41.
Table 41 -- Illegal Configuration Alarm Code
FCERROR DESCRIPTIONCODE
01 Unit size is unknown.
02 Reclaim option selected for Heat Pump machine.
03 Hot Gas Bypass configured for a Heat Pump machine.
Number of Fans controlled by low ambient temperature04 head pressure control is greater than expected.
Action to be _tken -- The unit is not allowed to stm't.
Reset Method-- Automatic after reconfiguration is completed.
Possible Causes -- If tiffs condition is encountered, confirmthe unit configuration (Configuration --)UNIT).
Alarm 84 -- Unit is in Emergency Stop (R31)
Cfiteriafi_r Trip -- The criterion is tested whether the units areON or OFF and when the machine receives a C_urier ComfortNetwork® (CCN) command for an Emergency Stop.
Action to be Taken -- Unit will stop, or will not _dlowed tostart.
Reset Method -- Automatic, once a return to normal commandis received.
Possible Causes -- If this condition is encountered, check forCCN Emergency Stop command.
Cooler Pump Fault
Almm 85 -- Pump 1 Fault (R32)Aku'm 86 -- Pump 2 Fault (R33)
Cfiteriafi_r Trip -- The criterion is tested whether the units areON or OFF. This almm will be generated if the cooler pumpinterlock opens. When starting the pump, the control mustread an open circuit for 3 consecutive reads. If the pump isoperating and file circuit opens, the alarm will be generatedimmediately.
Action to be Taken -- The pump and machine will be shutdown. If there is another pump available, the control will startthat pump, restart the machine and clear the alarm. If no otherpump is available, the unit will remain OFF.Reset Method -- Manu_d.
Possible Causes -- ff this condition is encountered, check thefollowing items:
• interlock wiring circuit• control signal to the pump controller• cooler pump contactor for proper operation• control voltage for proper voltage (on 208-volt systems,
be sure the proper tap on TRANI is utilized)
Alarm 87 -- Condenser Flow Switch Failure (El5)
NOTE: Almm 87 is not used or supported. If this condition isencountered, confirm machine configuration.
Reclaim Operation Failure
Aku'lll g8- Circuit A (R34)Alm'm 89 -- Circuit B (R35)
78
Repeated High Discharge Gas Overrides
Aimin 90 -- Circuit A (R37)Almm 91 -- Circuit B (R38)Akum 92 -- Circuit C (R39)
Cdwriafor Trip -- The criterion is tested when file circuit isON. This _flarm will be tripped if the circuit capacity is reducedmore than 8 times in 30 minutes due to high discharge gas tem-peratures. If no override occurs in a 30-minute period, thecounter is reset.
A_Tion to be Taken -- The affected circuit will be shut down.
Reset Method -- Automatic, after 30 minutes. If file alann iscleared via the Manual method, the counter will be reset tozero.
Possible Causes -- If this condition is encountered, check thefollowing items:
• Maximum Condensing Temperature (MCT) for theproper setting
• noncondensables in the refrigerant circuit• condenser air re-circulation• proper refrigerant charge (overcharged)• operation beyond the limit of the machine• condenser coils for debris or restriction• condenser fans and motors for proper rotation and
operation• discharge service valve to be sure that it is open. Check
the discharge pressure transducer for accuracy• confirm unit configuration
Repeated Low Suction Temperature Protection
Aimin 93 -- Circuit A (R40)Almm 94 -- Circuit B (R41)Akum 95 -- Circuit C (R42)
CriWriafbr Trip -- The criterion is tested when file circuit isON. If the circuit operates and if more than 8 successive circuitcapacity decreases (stop the compressor) have occurredbecause of low suction temperature protection ovemdes, thecircuit almm will be tripped. If no override has occurred formore fllan 30 minutes, the override counter will be reset to zero(LOSP).
Action to be Taken -- ALARM_LED will be set to blinking.Alert rekiy will be energized.
Reset Method -- Automatic, when the override counter returnsto zero. If the almm is clemed via file Manual method, thecounter will be forced to zero.
Possible Causes -- If this condition is encountered, check thefollowing items:• suction transducer for accuracy
• suction transducer wiring
• EXV operation• proper refrigerant charge (undercharged)
• evaporator loop for low water flow
• evaporator leaving water temperature• suction service valve to be sure it is open. Discharge
pressure transducer for accuracy• confirm unit configuration
Alarm 96 -- Low Entering Water Temperature in Heating
NOTE: Alarm 96 is not used or supported. If this condition isencountered, confirm machine configuration.
Condenser Default
Alm'm 97 -- Pump 1 (R73)Aku'm 98 -- Pump 2 (R74)
NOTE: Alarms 97 and 98 are not used or supported. If thiscondition is encountered, confirm machine configuration.
High Discharge Temperature
Alarm 99 -- Circuit A (R78)Alarm 100 -- Circuit B (R79)Alarm 101 -- Circuit C (R80)
Criteria for Trip -- Tile criterion is tested when file compressoris operating. This almm will be tripped if the dischmge gas tem-perature is higher than 212 F (100 C) for more than 90 seconds.
Action to be Taken -- The affected compressor will bestopped.
Reset Method-- Manual.
Possible Causes -- If tiffs condition is encountered, check thefollowing items:
• Maximum Condensing Temperature (MCT) for theproper setting
• noncondensables in the refrigerant circuit• condenser air re-circulation• proper refrigerant charge (overcharged)• operation beyond the limit of the machine• condenser coils for debris or restriction• condenser fans and motors for proper rotation and operation• the discharge service valve to be sure that it is open,
check the discharge pressure transducer for accuracy• confirm unit configuration
Low Economizer Pressure
Alarm 102 -- Circuit A (R81 )Alarm 103 -- Circuit B (E82)Alarm 104 -- Circuit C (R83)
Criwria.for Tril) -- The criterion is tested when the compres-sor is operating to prevent pumpdown conditions when thesuction service valve is closed. This alarm will be tripped if theeconomizer pressure is below the suction pressure more than1 bar (14.5 psi) for more than 10 seconds.
Action to be Taken -- The affected compressor will bestopped.Reset Method-- Manual.
Possible Causes -- If fills condition is encountered, check thefollowing items:• suction service valve is closed
• sensor wiring to the EXV boards
• boards for faulty channels• faulty transducer
• economizer EXV operation
Slide Valve Control Unverifiable
Alarm 105 -- Circuit A (R87)Alarm 106 -- Circuit B (E88)Alarm 107 -- Circuit C (R89)
Criwria.for TriF -- The criteria are tested when the compres-sor is operating. This alarm will be tripped if:• The circuit is operating at 100% of capacity and the mea-
sured current is less than 1.15 times the current at fullyunloaded 30% for more than one minute.
• The circuit is operating and is at a minimum load (30%of capacity) and the measured current is greater than 0.78expected current at 100% of capacity.
Action to be Taken -- The affected compressor will continue tolain.
Reset Method-- Manual.
Possible Causes -- If tiffs condition is encountered, check thefollowing items:
• faulty unloader solenoid valves• faulty unloader solenoid coils
• wiring of the unloader solenoid valves• CPM board for faulty channels
• current transformer reading for accuracy
79
Alarm 108 -- Cooler Flow Switch Setpoint ConfigurationFailure _R90)
NOTE: Almm 108 is not used or supported. If this condition isencountered, confirm machine configuration.
Alarm 109 -- Cooler Flow Switch Failure (R91 )
Criteria for Trip -- The criteria are tested when the unit is onor off. This alann will be tripped when the unit is on if:• The flow switch fails to close after the Off/On delay.• If the master/slave control is active, the unit is the lag
chiller and if the cooler flow switch fails to close within
one minute after the cooler pump was restarted. Thealarm is ignored if the lag cooler pump is stopped as aresult of master/slave control.
• The flow switch is opened during normal operation.
The alarm will be tripped when the unit is off if:• The cooler pump control is enabled (PUMP=0) and the
cooler flow switch is checked when the pump is enabled(RLOC) and the cooler flow switch is closed after file coolerpump is commended OFF for more than 2 minutes.
• The flow switch fails to close after the Off/On delay afterthe cooler pump has been turned off to protect the coolerfrom freezing (PUMP=0).
Action to be Taken -- For criteria for trip AI and A2, the com-pressors will not be st_uted.
For criteria for trip A3, all compressors will be stopped wiflloutgoing through pumpdown. Cooler pump will be stopped withno delay.
For criteria for trip BI, the unit will not start.
Reset Method -- Manual if at least one compressor is operat-ing. Automatic if no compressors are operating.
Possible Causes -- If this condition is encountered, check thefollowing items:
• a faulty flow switch
• flow switch wiring• Main Base Board for a faulty channel
Alarm 110 -- Service Maintenance Alert (Sl:nn)
CriWriafor Trip -- This alert is tested whether the unit is ONor OFF and when file Servicing Alert decisions listed underTime Clock--)MCFG have been enabled. The almm will be
generated if the one of the following configuration errors isdetected by the control. The "nn" refers to the error code listedin Table 42.
Table 42 -- Service Maintenance Alert Codes
CODE DESCRIPTION
Sr-01 Circuit A Loss of Refrigerant Charge
Sr-02 Circuit B Loss of Refrigerant Charge
Sr-03 Circuit C Loss of Refrigerant Charge
Sr-04 Water Loop Size Warning
Sr-05 Air Exchanger Cleanliness Warning
Sr-06 Cooler Pump 1 Servicing Required
Sr-07 Cooler Pump 2 Servicing Required
Sr-08 Condenser Pump 1 Servicing Required
Sr-09 Condenser Pump 2 Servicing Required
Sr-10 Water Filter Servicing Required
Sr-11 Compressor A Oil Filter Servicing Required
Sr-12 Compressor B Oil Filter Servicing Required
Sr-13 Compressor C Oil Filter Servicing Required
Action m be Taken -- None.
Reset Method-- Manual, after the service has been completed.
Possible Causes -- If the Sr-01, 02, or 03 conditions meencountered, check the following items:• sensor wiring to the Main Base Board
• sensor for accuracy
Compressor Motor Temperature Too High
Almm 111-01 -- Circuit A (A1.01 )Almm 112-01 -- Circuit B (B 1.01 )Almm 113-01 --Circuit C (CI.01)
CriWria .for Trip -- The alarm criteria me checked when thecompressor is ON. This alarm will be generated if:• The temperature is greater than 250 F (121 C) and it has
been greater than 212 F (100 C) for 10 consecutiveseconds.
• The compressor temperature is greater than 232 F(111 C) for 90 seconds (but less than 250 F [121 C]).
Action to be _iken -- The circuit shuts down immediately.
Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• faulty wiring and loose plugs• faulty CPM board
Compressor Motor Temperature Out of Range
Alarm 111-02 -- Circuit A (A1.027Almm 112-02 --Circuit B (BI.02)Almm 113-02- Circuit C (C 1.027
Criteria .for Trip -- The alarm criterion is checked when thecompressor is ON. This alarm will be generated if: the temper-ature is greater than 250 F (121 C) and it has NOT been greaterthan 212 F (100 C) for 10 consecutive seconds.
Action to be _ken -- The compressor will be stopped.
Reset Method -- Manual
Possible Causes -- ff this condition is encountered, check thefollowing items:• faulty compressor temperature thermistor• faulty wiring and loose plugs• faulty CPM board
Compressor High Pressure Switch Protection
Almm 111-03 -- Circuit A (A1.03)Almm 112-03 --Circuit B (BI.03)Almm 113-03 --Circuit C (C 1.03)
Criteria.for Trip -- The alarm criterion is checked when thecompressor is ON. This alarm will be generated if the circuithigh-pressure switch (HPS) opens for more than 200 ms (milli-seconds). The CPM board monitors the HPS switch.
A_Tion to be _ken -- The compressor will be stopped.
Reset Method -- Manu_fl
Possible Causes -- ff this condition is encountered, check thefollowing items:• condenser fan or contactor failure of loss of condenser air
flow
• compressor operating beyond the operation envelope• faulty high pressure switch or wiring• faulty CPM board
Compressor Overcurrent
Almm 111-04 -- Circuit A (A1.04)Almm 112-04 --Circuit B (BI.04)Almm 112-04 -- Circuit C (C 1.04)
CriWria.for Trip -- The alarm criterion is checked when thecompressor is ON. This _flmm will be generated if the CPMbomd detects a high motor current compared with the MTA(must trip amps) setting for more than 1.7 seconds.
A_tion to be Taken -- The compressor will be stopped.
Reset Method -- Manu_d
80
Possible Causes -- If this condition is encountered, check thefollowing items:• Compressor operating beyond the operation envelope.• Incorrect MTA setting.
Compressor Locked Rotor
Almm 111-05 -- Circuit A (A1.05)Almm 112-05 --Circuit B (B 1.05)Almm 113-05 -- Circuit C (C1.05)
Criteria .fbr Trip -- The _flmm criterion is checked duringstall-up when the compressor is ON. This tdarm will be gener-ated if the CPM board detects a high motor current comparedwith the MTA (must trip alnps) setting for more than 450 ms.
Action to be _iken -- The compressor will be stopped.
Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• compressor mechanical f:filure• unloader slide valve failure• compressor motor failure
Compressor Phase LossAlmm 111-06 -- Circuit AAlmm 112-06- Circuit BAlmm 113-06 -- Circuit CAlmm 111-07 -- Circuit AAlmm 112-07 -- Circuit BAlmm 113-07- Circuit CAlmm 111-08 -- Circuit AAlmm 112-08- Circuit BAlmm 113-08- Circuit C
LI (AI.06)LI (BI.06)LI (C1.06)L2 (A 1.07)L2 (B1.07)L2 (C1.07)L3 (A 1.08)L3 (BI.08)L3 (C1.08)
CriWria .fbr Trip -- The alarm criteria are checked duringstartup when the compressor is ON. This _darm will be gener-ated if:• The current unbalance on any of the 3 phases is greater than
65% for more than 1 second continuously during start-up.• The current unbalance on any of the 3 phases is greater
than 65% for more than 200 ms continuously duringruntime.
Action to be _iken -- The compressor will be stopped.
Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• power failure• blown fuse or tripped circuit breaker• power wiring errol_ or loose termin_fls
Compressor Low Current
Almm 111-09 -- Circuit A (A1.09)Almm 112-09- Circuit B (B 1.09)Almm 113-09 -- Circuit C (C1.09)
Cl4wria ._br Trip -- The alarm criteria me checked when thecompressor is ON. This alarm will be generated if:• The current is less than 15% MTA on all three legs for
more than 450 ms for Wye-Delta start units.• If the current is less than 15% of MTA on all three legs
for more than 1 second for direct start units.
Action to be _ken -- The compressor will be stopped.Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• power failure• blown fuse or tripped circuit breaker• deenergized contactor• faulty current toroid
Compressor Wve-Delta Starter Current Increase Failure
Almm 111-10 -- Circuit A (AI. 10)Almm 112-10 -- Circuit B (B 1.10)Almm 113-10 -- Circuit C (CI.10)
Criteria ._br Trip -- The almm criterion is checked duringcompressor start-up. This almm will be generated if the currentin Delta mode is not more than 25% greater than the cunent inY mode within 550 ms.
Action to be _ken -- The compressor will be stopped.
Reset Method-- Manual
Pos,ffble Causes -- If this condition is encountered, check thefollowing items:• power supply failure to the delta contactor• faulty wiring to the delta contactor• faulty CPM board• faulty current toroid
Compressor Contactor Failure
Alarm 111- 11 -- Circuit A (A 1.11 )Alarm 112-11 -- Circuit B (B 1.11 )Alarm 113-11 -- Circuit C (C 1.11 )
CriWria ._br Trip -- The almm criterion is checked duringcompressor shut-down. This alarm will be generated if the cur-rent is greater than 15% of the MTA on at least one phase for10 continuous seconds.
Action to be _ken -- The compressor will be stopped.
Reset Method-- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• faulty or welded contactor• faulty wiring• faulty CPM board
Compressor Unable to Stop Motor
Alarm 111-12 -- Circuit A (A 1.12)Alarm 112-12-- Circuit B (131.12)Alarm 113-12 -- Circuit C (C 1.12)
Criwria ._br Trip -- The almm criterion is checked duringcompressor shut-down. This alarm will be generated if allerthree attempts to turn off the compressor outputs and the cur-rent is still greater than 15% of the MTA on at least one phasefor 10 continuous seconds.
Action to be _ken -- The compressor will be stopped.Reset Method-- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• faulty or welded contactor• faulty wiring
Compressor Phase Reversal
Alarm 111-13 -- Circuit A (A 1.13)Alarm 112-13- Circuit B (BI.13)Alarm 113-13 -- Circuit C (C 1.13)
CriWria ,fbr Trip -- The almm criterion is checked duringcompressor st_ut-up. This alarm will be generated if the CPMboard detects a phase reversed from the cunent toroid.
Action to be _ken -- The compressor will be stopped.Reset Method-- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• if power supply lead at the terminal block is not operating at
the correct phase• if power supply is crossed when going through the current
toroid
Compressor MTA Configuration Fault
Alarm 111-14 -- Circuit A (A 1.14)Alarm 112-14 -- Circuit B (131.14)Alarm 113-14 -- Circuit C (C 1.14)
C;4teria_sr Trip -- The _dmm criterion is checked whether thecompressor is ON or OFF. This alarm will be generated if theMTA setting is out of the allowed MTA range.
81
Action to be Taken -- The compressor will be stopped.
Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• incorrect MTA settings• faulty CPM bomd
Compressor Configuration Switch Mismatch
Alarm 111-15 -- Circuit A (A 1.15)Alarm 112-15 --Circuit B (BI.15)Alarm 113-15 -- Circuit C (C1.15)
CriWriafi_r Trip -- The almm criterion is checked whether thecompressor is ON or OFF. This alarm will be generated ifthe CPM board SI and $2 setting does not match softwareconfiguration.
Action to be _ken -- The compressor will be stopped.Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• incorrect CPM board settings• faulty CPM bom'd
Compressor Unexpected Switch Setting Change
Alarm 111-16 -- Circuit A (AI. 16)Alarm 112-16--Circuit B (BI.16)Alarm 113-16 -- Circuit C (C 1.16)
Cdteria fi_r Trip -- The alarm criterion is checked when thecompressor is ON. This alarm will be generated if the CPMboard $1 setting has changed.
Action to be _ken -- The compressor will be stopped.Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• incorrect CPM board settings• faulty CPM bomd
Compressor Power on Reset
Alarm 111-17 -- Circuit A (AI.17)Alarm 112-17 -- Circuit B (B1.17)Alarm 113-17 -- Circuit C (C1.17)
CriWriafi_r Trip -- The alarm criterion is checked when thecompressor is ON. This alarm will be generated if the CPMboard detects a power failure.
Action to be _ken -- The compressor will be stopped.Reset Method -- Manual
Possible Causes -- If this condition is encountered, check forpower interruptions.
Compressor UL 1998 Critical Section Software Error
Alarm 111-18 -- Circuit A (AI. 18)Alarm 112-18--Circuit B (BI.18)Alarm 113-18 -- Circuit C (C1.18)
CriWriafi_r Trip -- The alarm criterion is checked when thecompressor is ON. This alarm will be generated if the CPMboard detects a software errol:
Action to be _ken -- The compressor will be stopped.
Reset Method -- Manual
Possible Causes -- If this condition is encountered, check thefollowing items:• electric_d noise• faulty CPM bomd
Compressor UL 1998 Current Measure Dual Channel Mis-match
Alarm 111-19 -- Circuit A (AI. 19)Alarm 112-19--Circuit B (BI.19)Alarm 113-19 -- Circuit C (C 1.19)
Cdteria.fi_r Trip -- The alarm criterion is checked when thecompressor is ON. This altum will be generated if the CPMbomd detects a software errol:
Action to be _iken -- The compressor will be stopped.
Reset Method -- Manu_d
Possible Causes -- If this condition is encountered, check thefollowing items:• electrical noise• faulty CPM board
Service Test- Main power and control circuit powermust be on for Service Test.
The Service Test function is used to verify proper operationof various devices within the chillen such as condenser fan(s),compressol,s, minimum load valve solenoid (if installed),cooler pump(s) and remote alarm relay. Tiffs is helpful duringthe start-up procedure to determine if devices are installedcorrectly. See Fig. 42-44 for 30XA wiring diagrams.
To use the Service Test mode, the Enable/Off/Remote Con-tact switch must be in the OFF position. Use the display keys tomove to the Service Test mode. The items are described in theService Test table. There are two sub-modes available. Service
Test--+ZREQ allows for manual control of the compressorsand minimum load control. In this mode the compressol,s willoperate only on command. The capacity control and head pres-sure control algorithms will be active. The condenser fans willoperate along with the EXVs. There must be a load on thechiller to operate for an extended period of time. All circuitsafeties will be honored during the test. Service Test-cQUICallows for test of EXVs, condenser fans, pumps, low ambienthead pressure control speed control, oil sepmatol; cooler heat-ers, oil solenoids, unloader solenoids and status points (alarmrelays, running status and chiller capacity). This mode allowsfor the testing of non-refligeration items. If there are no keyspressed for 5 minutes, flle active test mode will be disabled.
To enter the Manual Control mode, the Enable/Off/Remote
Contact switch must be in the OFF position. Move the LED tothe Service Test mode. Press _ to access TEST. Press
to access ZREQ. Press _ and the display
will show OFF. Press _ and OFF will flash. Enter the
password if required. Use either arrow key to change the
T.REQ v:due to ON and press _. Place the Enble/Off/
Remote Switch in the enable position. Mtmual Control mode is
now active. Press the _urow keys to move to the appropriate
item. To activate an item locate the item, press _ andthe display will show OFF. Press _ and OFF will
flash. Use either rerow key to change the value to ON and_. The item should be active. To turn the itempress
off, locate the item, press _ and the display will show
ON. The chiller must be enabled by turning the Enable/Off/
Remote Contact switch to Enable. Press _ and ON will
flash. Use either arrow key to change the value to OFF and
_. The item should be inactive.press
To enter the Quick Test mode, the Enable/Off/Remote
Contact switch must be in the OFF position. Move the LED tothe Service Test mode. Press _ to access TEST. Use
the _ key until the display reads QUIC. Press _ to
Q.REQ. Press _ and the display will show OFF.access
Press _ and OFF will flash. Enter the password if
required. Use either _urow key to change the QUIC v_due to
ON and press _. Quick Test mode is now active. Fol-low the same instructions for the Manual Control mode to acti-
vate a component.
82
Example -- Test the condenser tim AI (see Table 43).
Power must be applied to the unit. Enable/Off/RemoteContact switch must be in the OFF position.
Test the condenser fans, cooler pump(s) and alarm relay bychanging the item values fiom OFF to ON. These discreteoutputs me then turned off if there is no keypad activity for10minutes. Test the compressor and minimum load valve sole-noid (if installed) outputs in a similar mannel: Tile minimumload valve solenoids will be turned off if there is no keypadactivity for 10 minutes. Compressors will stay on until theoperator turns them off. The Service Test mode will remain
enabled for as long as them is one or more compressorsrunning. All safeties am monitored during this test and willturn a compressor, cimuit or the machine off if required. Anyother mode or sub-mode can be accessed, viewed, or changedduring the Manual Control mode only. Tile STAT item (RunStatus --)VIEW) will display "0" as long as the Service mode isenabled. Tile TEST sub-mode value must be changed back toOFF befom the chiller can be switched to Enable or Remotecontact for normal operation.
NOTE: Them may be up to a one-minute delay before theselected item is energized.
Table 43 -- Testing Circuit A Oil Solenoid
MODE SUB-MODE KEYPAD ITEM DISPLAY VALUEDESCRIPTION COMMENT(Red LED) ENTRY EXPANSION (Units)
SERVICE TEST [] Service Test Mode
TEST [] Manual Sequence
QUIC [] Q.REQ
PASS WORD Password may be required
] 0111
[] Each [] will lock in the next
] digit. If 0111 is not the password,use the arrow keys to change the
[] _assword digit and press []
] when correct.
] Q.REQ Returns to the original field
] OFF
] OFF OFF will flash
The Enable/Off/Remote Contact] ON switch must be in the OFF
_osition.
Q.REQ
] EXV.A
] Press 15 times.
] OLG.A Oil Solenoid cir.A
] OFF
] OFF OFF will flash
[] oN
] ON OLS.A will turn on.
] ON 1 will flash
] OFF
] OFF OLS.A will turn off.
LEGEND FOR FIG. 42-44
ALM -- IsolationCB -- Circuit BreakerCPM -- Compressor Protection ModuleCWFS -- Chilled Water Flow SwitchEMM -- Energy Management ModuleEXV -- Electronic Expansion ValveFlOP -- Factory-Installed OptionHTR -- Heater
ISO --MBB --MLV --MM --PMP --SGT --TB --
IsolationMain Base BoardMinimum Load ValueLow Ambient Temperature Head Pressure ControlPumpSaturated Gas TemperatureTerminal Block
83
TO FROMCPM-B CPM-A
JI2 J12
TB3 JgB
TOCPM-A
J12
J3
,_, ROUTE TO E_M COM_ PLUG
FOR E_ OPTION ONLYROUT[ TO FAR BOARD J9COrM PLUG FOR ALLOTHER OPT IORS
JgB J9AJTB
EMM J7ABOARD
FlOP/ACCESSORY _="
d6--
g_
"'1
I
J3 J4 J5 <:_>>,_,"17;II ? I ? I_,;I,_,",I _>'
Fig. 42 -- 30XA080 Low Voltage Control Schematic
84
TB3
FROMMBBJgC
!
MAIN BASEBOARD
J12j7 D
J7C
jJ7B
JTA
J3
TOCPM.B
TOCPM-B
.112(090-1201
TOFAN
BOARD-BJ9
(H.0-350)
FROMCPM-A
J12
FROMCPM-B
J12
TOCPM-A
JI2
ECT
ROUTE TO RAN BOARD J9 . _ _ ; _ _COM_ PLUG FOR ALLOTHER OPTIONS
I
I
I
: J9B J9A
I
J8
EMM J7ABOARD
FlOP/ACCESSORY
J5 _>,J4 <_->>,: J3
: 1_;11_;;;_/ -_
I
I
I
I
I
Fig. 43 -- 30XA090-350 Low Voltage Control Schematic
85
TB3
MAIN BASEBOARD
TOFAN
BOARD-CJ9
TOFAN
BOARD-BJ9
FROMCPM-A
J12
FROMCPM-B
JI2
;GTA ECT,
J12j7 D
J3
TOCPM-A
JI2
ROUTE TO E_M COMW PLUG ' "
FOR E_ OPTION ONLY _ I FJ_ FJ_ROUTE TO FAN _OARD J9 - _ _ _ _ _CONN PLUG FOR ALL " = _ _ = _ =OTHER OPTIONS
J8
1
I
I
FROMMBBJ9C
I
TOCPM-B
]
Fig. 44 -- 30XA400-500 Low Voltage Control Schematic
86
ITEM
VIEW-_EWT
-_LWT
-_SETP
-_CTPT
-_STAT
-_OCC-_CTRL
-_CAP-_CAP. A-_CAP. B-_CAP. C-_CAP. S-_LIM-_CURR-_CUR.L-_ALRM
-_HC.ST
-_RC.ST-_TIME-_MNTH
-_DA TE-_ YEAR
RUN-_HRS. U-_STR.U-_HR.P1-_HR.P2-_HR.P3-_HR.P4
HOUR-_HR.A-_HR.B-_HR. C
STRT-_ST.A-_ST.B-_ST.C
FAN-_FR.A1-_FR.A2-_FR.A3-_FR.A4-_FR.A5-_FR.A6-_FR.A7-_FR.A8-_FR.A9-_F.A I O-_FR.B1-_FR.B2-_FR.B3-_FR.B4-_FR.B5-_FR.B6-_FR.B7-_FR.B8-_FR.B9-_F.BIO-_FR.C1-_FR.C2-_FR.C3-_FR.C4-_FR.C5-_FR.C6-_FR.C7-_FR.C8-_FR.C9-_F.CIO
APPENDIX A -- LOCAL DISPLAY TABLES
MODE -- RUN STATUS
EXPANSION
AUTO DISPLAYEntering Fluid Ternp
Leaving Fluid Temp
Active Setpoint
Control Point
Unit Run Status
OccupiedStatus Unit Control Type
Percent Total CapacityPercent Capacity Cir APercent Capacity Cir BPercent Capacity Cir CCapacity IndicatorActive Demand Limit ValActual Chiller CurrentChiller Current LimitAlarm State
Heat Cool Status
Reclaim Select StatusTime of DayMonth of Year
Day of Month XXYear of Century XXMACHINE STARTS/HOURSMachine Operating HoursMachine StartsWater Pump 1 Run HoursWater Pump 2 Run HoursCondenser Pump 1 HoursCondenser Pump 2 HoursCOMPRESSOR RUN HOURSCompressor A Run HoursCompressor B Run HoursCompressor C Run HoursCOMPRESSOR STARTSCompressor A StartsCompressor B StartsCompressor C StartsFAN RUN HOURSFan 1 Run Hours Cir AFan 2 Run Hours Cir AFan 3 Run Hours Cir AFan 4 Run Hours Cir AFan 5 Run Hours Cir AFan 6 Run Hours Cir AFan 7 Run Hours Cir AFan 8 Run Hours Cir AFan 9 Run Hours Cir AFan 10 Run Hours Cir AFan 1 Run Hours Cir BFan 2 Run Hours Cir BFan 3 Run Hours Cir BFan 4 Run Hours Cir BFan 5 Run Hours Cir BFan 6 Run Hours Cir BFan 7 Run Hours Cir BFan 8 Run Hours Cir BFan 9 Run Hours Cir BFan 10 Run Hours Cir BFan 1 Run Hours Cir CFan 2 Run Hours Cir CFan 3 Run Hours Cir CFan 4 Run Hours Cir CFan 5 Run Hours Cir CFan 6 Run Hours Cir CFan 7 Run Hours Cir CFan 8 Run Hours Cir CFan 9 Run Hours Cir CFan 10 Run Hours Cir C
UNITS
XXXX.X(deg F/deg C)XXX.X(deg F/deg C)XXX.X(deg F/deg C)XXX.X(deg F/deg C)
xxx(%)xxx(%)xxx(%)xxx(%)xxxxx(%)XXX(amps)XXX(amps)
XX.XX
XXXX (hours)XXXXXXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)
XXXX (hours)XXXX (hours)XXXX (hours)
XXXXXXXXXXXX
XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)XXXX (hours)
RANGE
0-100
0-100
0-100
0-100
OffRunningStoppingDelayNO/YESLocal OffLocal OnCCNRemote0-1000-1000-1000-1000-320-1000-40000-40000=Normal1=Partial2=Shutdown0-Cooling1-Heating2=StandbyNO/YES00:00-23:591=January2=February3=March4-April6=May6=June7=July8=August9-September10-October11=November12=December1-3100-99
0-999000*0-9999*0-999000*0-999000*0-999999*0-999999*
0-999000*0-999000*0-999000*
0-999000*0-999000*0-999000*
0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*0-999999*
WRITECOMMENT STATUS
Heating andStandby notsupported.Not supported.
forcibleforcible
Not supported, forcibleNot supported, forcibleNot supported, forcibleNot supported, forcible
forcibleforcibleforcible
forcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
CCN TABLE
STATEGEN
STATEGEN
GENUNIT
GENUNIT
GENUNIT
GENUNITGENUNIT
GENUNITGENUNITGENUNITGENUNITMAINTGENUNITGENUNITGENUNITGENUNIT
GENUNIT
GENUNITN/AN/A
N/AN/A
STRTHOURFANHOURSFANHOURSFANHOURSFANHOURS
STRTHOURSTRTHOURSTRTHOUR
STRTHOURSTRTHOURSTRTHOUR
FANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURSFANHOURS
CCN POINT
COOLEWT
COOLLWT
SP
CTRL PNT
STATUS
CHIL OCCctr type
CAP TCAPATCAPBTCAPCTOVER CAPDEM-LIMTOT CURRCURR LIMALM
HEATCOOL
reclaim selTIMEmoy
dora
yoc
hrmachst roachhrcpumlhr cpum2hr hpumplhr hpump2
hr cp ahr cp bhr cp c
st cp ast cp bst cp c
hr fanalhrfana2hrfana3hrfana4hrfana5hrfana6hrfana7hrfana8hrfana9hrfanal0hr fanblhrfanb2hrfanb3hrfanb4hrfanb5hrfanb6hrfanb7hrfanb8hrfanb9hrfanbl0hr fanclhrfanc2hrfanc3hrfanc4hrfanc5hrfanc6hrfanc7hrfanc8hrfanc9hrfancl 0
PAGENO.
8320
20
50, 51
20, 42,5O29, 30
2929
205O
21
87
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- RUN STATUS (cont)
WRITE CCN TABLE CCN POINT PAGEITEM EXPANSION UNITS RANGE COMMENT STATUS NO.
NO/YES forcible CP UNABL un cp aNO/YES forcible CP UNABL un cp bNO/YES forcible CP UNABL un cp c
CA UN-_A.UN-_B. UN-_C.UN
MAIN-_CHRG-_WATE-_PM P.1-_PMP.2-_PMP.3-_PMP.4-_W.FIL-_A.FIL-_B.FIL-_C.FIL
VERS-_A PPL-_MARQ-_NAVI-_EXVA-_EXVB-_EXVC-_AUXl-_AUX2-_AUX3-_AUX4-_AUX5-_AUX6-_CPMA-_CPMB-_CPMC-_EMM-_R.BRD
COMPRESSOR DISABLECompressor A DisableCompressor B DisableCompressor C DisablePREDICTIVE MAINTENANCERefrigerant ChargeWater Loop SizePump 1 (Days)Pump 2 (Days)Cond Pump 1 (Days)Cond Pump 1 (Days)Water FilterComp A OII Filter (days)Comp B Oil Filter (days)Comp C Oil Filter (days)SOFTWARE VERSIONSCSA-XXXXXXXXXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XXXXXXXX-XX-XX
(days)(days)
(days)
NO/YESNO/YES
Not supported.
Press ENTERand ESCAPE
SERMAINTSERMAINTSERMAINTSERMAINTSERMAINTSERMAINTSERMAINTSERMAINTSERMAINTSERMAINT
simultaneouslyto read versioninformation
*As data in all of these categories can exceed 9999 the following display strategy is used;From 0-9999 display as 4 digits.From 9999-99999 display xx.xKFrom 99900-999999 display as xxxK.
charge mwloop mcpumpl mcpump2 mhpumpl mhpump2 mwfilte mofilta mofiltb mofiltc m
PD5 APPLSTDUNavigatorEXV BRDAEXVBRDBEXVBRDCAUXBRD1AUXBRD2AUXBRD3AUXBRD4AUXBRD5AUXBRD6SPM CPASPM CPBSPM CPCEMM NRCPREC NRCP
88
ITEM
TEST-_T.REQ-_CP.A
-_SLI.A
-_CP.B-_SLI.B
-_CP.C-_SLI.C
QUIC-_Q.REQ-_EXVA-_EXVB-_EXVC-_ECO.A-_ECO.B-_ECO.C-_FAN.A-_FAN.B-_FAN.C-_SPD.A-_SPD.B-_SPD. C-_HT.A-_SL 1.A-_SL2.A-_OLS.A-_DGT.A-_HT.B-_SL1.B-_SL2.B-_OLS.B-_DGT.B-_HT.C-_SL1.C-_SL2.C-_OLS.C-_DGT.C-_FRVA-_FRP.A-_FRVB-_FRP.B-_FRVC-_FRP.C-_RVA-_RVB-_HR1 .A-_HR2.A-_HR3.A-_HR4.A-_HR1.B-_HR2.B-_HR3.B-_HR4.B-_PM P.1-_PMP.2-_PMP.3-_PMP.4-_CL.HT-_BVL.A-_BVL.B-_BVL.C-_CP..HT-_Q.RDY-_Q.RUN-_SHUT-_CATO-_ALRM-_ALRT
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- SERVICE TEST
WRITE PAGEEXPANSION UNITS COMMENT STATUS NO,
MANUAL TEST MODEManual SequenceCompressor A Output
Slide Valve Capacity A
Compressor B OutputSlide Valve Capacity B
Compressor C OutputSlide Valve Capacity C
QUICK TEST MODE
Circuit A EXV % OpenCircuit B EXV % OpenCircuit C EXV % OpenCirc A ECO EXV %Circ B ECO EXV %Circ C ECO EXV %Circuit A Fan StagesCircuit B Fan StagesCircuit C Fan StagesCir A Varifan positionCir B Varifan positionCir C Varifan positionOil Heater Circuit ASlide Valve 1 Cir ASlide Valve 2 Cir BOil Solenoid Cir ADGT Cool Solenoid AOil Heater Circuit BSlide Valve 1 Cir BSlide Valve 2 Cir BOil Solenoid Cir ADGT Cool Solenoid BOil Heater Circuit CSlide Valve 1 Cir CSlide Valve 2 Cir COil Solenoid Cir ADGT Cool Solenoid C
Free Cooling Heater ARefrigerant Pump AFree Cooling Heater BRefrigerant Pump BFree Cooling Heater CRefrigerant Pump C4 Way Valve Circuit A4 Way Valve Circuit BAir Cond Enter Valve AAir Cond Leaving Valv AWater Cond Enter Valv AWater Cond Leav Valve AAir Cond Enter Valve B
Air Cond Leaving Valv BWater Cond Enter Valv BWater Cond Leav Valve BWater Exchanger Pump 1Water Exchanger Pump 2Condenser Pump 1Condenser Pump 2Cooler Heater OutputBall Valve Position ABall Valve Position BBall Valve Position CCondenser Heater OutputChiller Ready StatusChiller Running StatusCustomer Shutdown StatChiller Capacity in 0-10vAlarm RelayAlert Relay
xxx(%)xxx(%)xxx(%)xxx(%)xxx(%)xxx(%)XXXXXX(%)XXX(%)XXX(%)
XX.X (vdc)
RANGE
OFF/ON
OFF/ONunchangedincreasedecreaseOFF/ONunchangedincreasedecreaseOFF/ONunchangedincreasedecrease
OFF/ON0-1000-1000-1000-1000-1000-1000-80-80-80-1000-1000-100OFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOPEN/CLSEOFF/ONOPEN/CLSEOFF/ONOPEN/CLSEOFF/ONOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOPEN/CLSEOPEN/CLSEOPEN/CLSEOFF/ONOFF/ONOFF/ONOFF/ON
OFF/ONOFF/ON
Remote-Off-Enable Switchmust be set toOFF Position
Remote-Off-Enable Switchmust be set toENABLEPosition
Remote-Off-Enable Switchmust be set toOFF Position
Not supported.Not supported.Not supported.Not supported.
Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.
Not supported.
forcibleforcible
forcible
forcibleforcible
forcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcible
CCN TABLE
N/AN/AN/A
N/A
N/A
N/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
N/A
N/AN/AN/AN/AN/AN/AN/A
CCN POINT
service test
comp serv a
comp ser sid a
comp serv bcomp ser sid b
comp serv ccomp ser sidc
58, 8258
58
58
82
57, 5857, 5857, 58
89
ITEM
UNIT-;,CEWT
-_CLWT
-_CD.LT
-_CD.ET
-_OAT
_CHWS
_HEWT
_HLWT
_SPT
-_THHR
ClR.A-_SCT.A
-_SST.A
-_DGT.A
-_SGT.A
-_SUP.A-_ECT.A
-_ESN.A
-_C TP.A
-_DEF.A
ClR.B_SCT.B
_SST.B
-_DGT.B
_SGT.B
_SUP.B_ECT.B
_ESH.B
_C TP.B
_DEF.B
CIR.C_SCT.C
_SST.C
-_DGT.C
_SGT.C
_SUP.C
-_ECT.C
-eESH.C
-_CTP.C
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- TEMPERATURE
EXPANSION
UNIT TEMPERATURESCooler Entering Fluid
Cooler Leaving Fluid
Condenser Entering Fluid
Condenser Leaving Fluid
Outside Air Temperature
Lead/Lag Leaving Fluid
Heat Reclaim Entering
Heat Reclaim Leaving
Optional Space Temp
Cooler Heater Temp
CIRCUIT A TEMPERATURESSat Cond Temp Circ A
Sat Suction Temp Circ A
Discharge Gas Temp Cir A
Suction Gas Temp Circ A
Superheat Temp Cim AEconomizer Gas Temp A
Economizer Superheat A
Motor Temperature Cir A
Defrost Temp Circ A
CIRCUIT B TEMPERATURESSat Cond Temp Circ B
Sat Suction Temp Circ B
Discharge Gas Temp Cir B
Suction Gas Temp Circ B
Superheat Temp Cim BEconomizer Gas Temp B
Economizer Superheat B
Motor Temperature Cir B
Defrost Temp Circ B
CIRCUIT C TEMPERATURESSat Cond Temp Circ C
Sat Suction Temp Circ C
Discharge Gas Temp Cir C
Suction Gas Temp Circ C
Superheat Temp Cim CEconomizer Gas Temp C
Economizer Superheat C
Motor Temperature Cir C
WRITE CCN POINT PAGEUNITS RANGE COMMENT STATUS NO.
XXXIX
(deg F/deg C)XXX.X(deg F/deg C)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg c)
XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XXXIX (AF/AC)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)
XXX.X(deg F/deg C)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XXX.X (AF/AC)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XXX.X(deg F/deg C)
XXX.X(deg F/deg C)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XXXIX (AF/AC)XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)
-40-245 F
(-40-118 C)40-245 F
(-40-118 C)-40-245 F(-40-118 C)-40-245 F
(-40-118 C)-40-245 F(-40-118 C)-40-245 F
(-40-118 C)-40-245 F(-40-118 C)
40-245 F(-40-118 C)
40-245 F
(-40-118 C)-40-245 F(-40-118 C)
40-245 F
(-40-118 C)-40-245 F(-40-118 C)-40-245 F
(-40-118 C)-40-245 F( 40-118 C)
-40-245 F(-40-118 C)-40-245 F
(-40-118 C)40-245 F
(-40-118 C)-40-245 F(-40-118 C)
40-245 F(-40-118 C)-40-245 F(-40-118 C)-40-245 F
(-40-118 C)-40-245 F(-40-118 C)
40-245 F(-40-118 C)
40-245 F
(-40-118 C)-40-245 F(-40-118 C)-40-245 F( 40-118 C)
-45-245 F(-43-118 C)-45-245 F(-43-118 C)-40-245 F
(-40-118 C)-45-245 F(-43-118 C)
Not supported.Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
CCN TABLE
STATEGEN
STATEG EN
GENUNIT
STATEGEN
RECLAIM
RECLAIM
STATEGEN
CIRCA AN
CIRCA AN
CIRCA AN
CIRCA AN
N/A
CIRCB AN
CIRCB AN
CIRCB AN
CIRCB AN
N/A
CIRCCANCIRCCAN
ClRCCAN
CIRCC AN
CIRCC AN
COOLEWT
COOLLWT
COND LWT
COND EWT
OAT
CHWS
HR EWT
HR LWT
SPACETMP
TH HEATER
SCT A
SST A
DGTA
SUCTT A
SH AEC© TP A
EC© SH A
CP TMP A
DEFRTA
SCT B
SST B
DGT B
SUCTT B
SH BECO TP B
ECO SH B
CP TMP B
DEFRT B
SCT C
SST C
DGT C
SUCTT C
SH CECO TP C
ECO SH C
CP TMP C
5, 50
5, 50
5, 50
5
14
8
10
10
8
10
10
88
10
9O
ITEM
PRC.A-_DP.A
-_SP.A
-_OP.A
-_DOP.A
-_ECRA
-_PDRA
PRC.B-_DP.B
-_SP.B
_OP.B
-_DOP.B
-_ECP. B
-_PDP. B
PRC. C-_DP. C
_SP. C
_OP.C
-eDOR C
-_ECP. C
-_PDP. C
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE--PRESSURE
EXPANSION
CIRCUIT A PRESSURESDischarge Pressure Cir A
Suction Pressure Circ A
Oil Pressure Circ A
Oil Pressure Diff A
Economizer Pressure A
Reclaim Pressure A
CIRCUIT B PRESSURES
Discharge Pressure Cir B
Suction Pressure Circ B
Oil Pressure Circ B
Oil Pressure Diff B
Economizer Pressure B
Reclaim Pressure B
CIRCUIT A PRESSURESDischarge Pressure Cir C
Suction Pressure Circ C
Oil Pressure Circ C
Oil Pressure Diff C
Economizer Pressure C
Reclaim Pressure C
WRITE CCN POINTUNITS RANGE COMMENT STATUS
XXX.X
(psig/kPa)XXX.X(psig/kPa)XXX.X(psig/kPa)XXX.X
(psig/kPa)XXX.X(psig/kPa)XXX.X
(psig/kPa)
XXX.X(psig/kPa)XXX.X
(psig/kPa)XXX.X(psig/kPa)XXX.X(psig/kPa)XXX.X
(psig/kPa)XXX.X(psig/kPa)
XXX.X(psig/kPa)XXX.X(psig/kPa)XXX.X
(psig/kPa)XXX.X(psig/kPa)XXX.X(psig/kPa)XXX.X
(peig/kPa)
Not supported.
Not supported.
Not supported.
CCN TABLE
CIRCAAN
CIRCAAN
CIRCBAN
CIRCBAN
CIRCCAN
CIRCCAN
DPA
SPA
OP A
DOPA
ECON PA
PMPD PA
DP B
SP B
OP B
DOP B
ECON P B
PMPD P B
DP C
SPC
OP C
DOP C
ECON P C
PMPD P C
PAG ENO.
52
5
8
52
5
8
13, 52
13
8
9]
ITEM
COOL-_,CSP.1
-_CSP.2
-_CSP.3
-_CRV1
-_CRV2
-_CRT1
-_CRT2
-_CR01
-_CR02
-_CRS1
-_CRS2
-_DGRC
-_CAUT
-_CRMP
HEAT-_HSP. 1
-_HSP.2
-_HRV1-_HRV2-_HRT1-_HRT2-_HR01
-_HR02
-_DGRH-_HAUT
-eHRMP
MISC-_DLS1
-_DLS2
-_DLS3
-_W.SCT
-_RSP
-_RDB
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- SET POINTS
EXPANSION
COOLING SETPOINTSCooling Setpoint 1
Cooing Setpoint 2
Ice Setpoint
Current No Reset Val
Current Full Reset Val
Delta T No Reset Temp
Delta T Full Reset Temp
OAT No Reset Temp
OAT Full Reset Temp
Space T No Reset Temp
Space T Full Reset Temp
Degrees Cool Reset
Cool Changeover Setpt
Cool Ramp Loading
HEATING SETPOINTS
Heating Setpoint 1
Heating Setpoint 2
Current to Reset ValCurrent Full Reset Val
Delta T No Reset TempDelta T Full Reset TempOAT No Reset Temp
OAT Full Reset Temp
Degrees Heat ResetHeat Changeover Setpt
Heat Ramp LoadingMISC SETPOINTS
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
Water Val Cond Stp
Heat Reclaim Setpoint
Reclaim Deadband
UNITS RANGE COMMENT
XXXX.X
(deg F/deg C)
XXXX.X
(deg F/deg C)
XXXX.X
(deg F/deg C)
XX.X (mA)
XX.X (mA)
XXX.X (AF/AC)
xxx.x (AF/AC)
XXX.X
(deg F/deg C)
XXX.X(deg F/deg C)
XXX.X(deg F/deg C)
XXX.X(deg F/deg C)
XX.X (A F/AC)
XX.X(deg F/deg C)X.X
XXX.X(deg F/deg C)XXX.X
(deg F/deg C)XX.X (mA)XX.X (mA)XXX.X (AF/AC)XXX.X (AF/AC)XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XX.X (AF/AC)XX.X(deg F/deg C)X.X
xxx (%)
xxx (%)
xxx (%)
XXX.X
(deg F/deg C)XXX.X(deg F/deg C)XX.X (AF/AC)
-20-70 F
(-29-21 C),Default = 44.020-70 F
(-29-21 C),Default = 44.0-20-70 F
( 29-21 C),Default = 44.00-20,Default = 00-20,Default - 00-125 F
(0-69.4 C),Default = 00-125 F
(0-69.4 C),Default - 00-125 F
(-18-52 C),Default = 14.00-25 F( 18-52 C),Default = 14.00-125 F(-18-52 C),Default- 14.00-125 F(-18-52 C),Default = 14.0-30-30 F-16.7-16.7 C),Default - 0Default = 75.0
0.2-2.0 AF
(0.1-1.1 AC),Default = 1.0
Default = 100
Default = 100
Default = 0Default = 0Default - 0Default - 0Default - 14.0
Default = 14.0
Default = 0Default = 64
Default = 1.0
0-100,Default- 1000-100,Default- 1000-100,Default = 10080-140 F
(26.7-60 C)Default - 122
Default = 9.0
Not supported.
Not supported.
Not supported.
Not supported.Not supported.Not supported.Not supported.Not supported.
Not supported.
Not supported.Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
WRITESTATUS
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcibleforcibleforcibleforcibleforcible
forcible
forcibleforcible
forcible
forcible
forcible
forcible
forcible
forcible
CCN TABLE
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINTSETPOINTSETPOINTSETPOINTSETPOINT
SETPOINT
SETPOINTSETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
CCN POINT
cspl
csp2
ice sp
v cr no
v crfu
dt cr no
dt crfu
oatcr no
oatcrfu
spacr no
spacr fu
cr deg
cauto sp
cramp sp
HSR1
HSR2
v hr nov hr fudt hr nodt hrfuoathr no
oathrfu
DGRHhautosp
hramp sp
lira spl
lira sp2
lira sp3
w sct sp
rsp
hrdeadb
PAG ENO.
30, 42
30, 50
30, 50.51
32
32
31
31
31
31
31
31
31
15, 20,5O
32
32
92
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- INPUTS
WRITE CCN TABLE CCN POINT PAGEITEM EXPANSION UNITS RANGE COMMENT STATUS NO,
GEN.I-_ONOF-_LOCK-_COND-_DLS1-_DLS2-_ICE.D-_DUAL-_ELEC-_PUMP-_OCCS-_RECL-_HC.SW-_RLOC-_OIL.A-_OIL.B-_OIL.C-_CUR.A-_CUR.B-_CUR.C-_DMND-_RSET
GENERAL INPUTSOn Off SwitchCooler InterlockCondenser Flow SwitchDemand Limit Switch 1Demand Limit Switch 2Ice DoneDual Setpoint SwitchElectrical Box SafetyPump Run FeedbackOccupancy Override SwitHeat Reclaim SwitchHeat Cool Switch StatusRemote Interlock SwitchOil Level Circuit AOil Level Circuit BOil Level Circuit CMotor Current Circuit AMotor Current Circuit BMotor Current Circuit C4-20 mA Demand Signal4-20 mA Reset/Setpoint
XXX.X (amps)XXX.X (amps)XXX.X (amps)XXX.X (mA)XXX.X (mA)
OPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOFF/ONOFF/ONOPEN/CLSEOPEN/CLSEOFF/ONOFF/ONOFF/ONOPEN/CLSELOW/HIGHLOW/HIGHLOW/HIGH0-6000-6000-6004 to 204 to 20
Not supported.
Not supported.Not supported.
Not supported.Not supported.
STATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGENSTATEGEN
ONOFLOCK 1CONFLOWLIM SW1LIM SW2ICE SWSETP SWELEC BOXPUMP DEFOCC OVSWRECL SWHC SWREM-LOCKOILLAOILLBOILLCCURR ACURR BCURR CLIM ANALSPRESET
55, 20
514145
14
14
8881414
93
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- OUTPUTS
WRITE CCN POINT PAGEITEM EXPANSION UNITS RANGE COMMENT STATUS NO.
ClR.A-_CRA-_HT.A-_SL1.A-_SL2.A-_OLS.A-_FAN.A-_SPD.A-_EXV.A-_ECO.A-_DGT.A-_FRP.A-_FRH.A-_HR1 .A-_HR2.A-_HR3.A-_HR4.A-_RV.A
ClR.B-_CP.B-_HT.B-_SL1.B-_SL2.B-_OLS.B-_FAN.B-_SPD.B-_EXV.B-_ECO.B-_DGT.B-_FRP.B-_FRH.B-_HR1.B-_HR2.B-_HR3.B-_HR4.B-_RV.B
ClR.C-_CP.C-_HT.C-_SL I.C-_SL2. C-_OLS.C-_FAN.C-_SPD.C-_EXVC-_ECO.C-_DGT.C-_FRP.C-_FRHC
GEN.O-_PM P.1-_PMP.2-_PMP.3-_PMP..4-_CO.HT-_BVL.A-_BVL.B-_BVL.C-_CN.HT-_REDY-_RUN-_SHUT-_CATO-_ALRM-_,ALRT
CIRCUIT A OUTPUTSCompressor A RelayOil Heater Circuit ASlide Valve 1 Cir ASlide Valve 2 Cir AOil Solenoid Cir ACircuit A Fan StagesCirc A Varifan Position
Circuit A EXV % OpenCirc A EXV ECO % OpenDGT Cool Solenoid ARefrigerant Pump Out AFree Cooling Heater AAir Cond Enter Valve AAir Cond Leaving Valv AWater Cond Enter Valv AWater Cond Leav Valve A4 Way Valve Circuit A
CIRCUIT B OUTPUTSCompressor B RelayOil Heater Circuit BSlide Valve 1 Cir BSlide Valve 2 Cir BOil Solenoid Cir BCircuit B Fan StagesCirc B Varifan PositionCircuit B EXV % OpenCirc B EXV ECO % OpenDGT Cool Solenoid BRefrigerant Pump Out BFree Cooling Heater BAir Cond Enter Valve BAir Cond Leaving Valv BWater Cond Enter Valv BWater Cond Leav Valve B4 Way Valve Circuit B
CIRCUIT C OUTPUTSCompressor C RelayOil Heater Circuit CSlide Valve 1 Cir CSlide Valve 2 Cir COil Solenoid Cir C
Circuit C Fan StagesCirc C Varifan PositionCircuit C EXV % OpenCirc C EXV ECO % OpenDGT Cool Solenoid CRefrigerant Pump Out CFree Cooling Heater C
XXXX (%)XXX (%)XXX (%)
XXXX (%)XXX (%)XXX (%)
OFF/ON
OFF/ON
X
XXX (%)xxx (%)xxx (%)
OFF/ON
OFF/ON
OFF/ONOFF/ONOFF/ONOFF/ONOFF/ON0-60-1000-1000-100OFF/ONOFF/ONOFF/ONOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSE
OFF/ONOFF/ONOFF/ONOFF/ONOFF/ON0-60-1000-1000-100OFF/ONOFF-ONOFF-ONOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSEOPEN/CLSE
OFF/ONOFF/ONOFF/ON0-60-1000-1000-100OFF/ON
Not supported,Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.
Not supported,Not supported.Not supported.Not supported.Not supported.Not supported.Not supported.
Not supported.Not supported.
CCN TABLE
CIRCA D
CIRCA DCIRCA ANCIRCA AN
CIRCADCIRCA DRECLAIMRECLAIMRECLAIMRECLAIMCIRCAD
CIRCB DCIRCB D
CIRCB DCIRCB ANCIRCB AN
CIRCB DCIRCA DRECLAIMRECLAIMRECLAIMRECLAIMCIRCB D
CIRCC DCIRCC D
CIRCC DCIRCC ANCIRCC AN
CIRCC DCIRCC D
GENERAL OUTPUTS
Water Exchanger Pump 1Water Exchanger Pump 2Condenser Pump 1Condenser Pump 2Cooler Heater OutputBall Valve Position ABall Valve Position BBall Valve Position CCondenser Heat OutputChiller Ready StatusChiller Running StatusCustomer Shutdown StatChiller Capacity 0-10 vAlarm RelayAlert Relay
XX.X
OFF/ONOFF/ONOFF/ONOFF/ONOFF/ONOPEN/CLOSEOPEN/CLOSEOPEN/CLOSEOFF/ONOFF/ONOFF/ONOFF/ON
OFF/ONOFF/ON
Not supported,Not supported,
Not supported.forcibleforcibleforcibleforcible
STATEGENSTATEGEN
STATEGEN
RECLAIMRECLAIMSTATEGENSTATEGENSTATEGENSTATEGENSTATEGEN
CP AOIL HTASLID1ASLID2 AOIL SLAFAN STAhd pos aEXV AEXVEC Adgt gascool aFR PMP AFR HEATAhr ca ahrla ahren ahr Iw aRVA
CP BOIL HT BSLID1 BSLID2 BOIL SL BFAN ST Bhd pos bEXV BEXVEC Bdgt gascool bFR PMP BFR HEATBhr ca bhrla bhren bhr Iw bRV B
CP COIL HTCSLID1 CSLID2 COIL SL CFAN ST Chd pos cEXV CEXVEC Cdgt gascool cFR PMP CFR HEATC
CPUMP 1CPUMP 2HPUMP 1HPUMP 2COOLHEATref iso aref iso bref iso ccond htrREADYRUNNINGSHUTDOWNCAPT 010ALARMALERT
85,8888
1210108
85,8888
121010
88888
13
I0
5555
14141455
94
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- CONFIGURATION
CCN CCN PAGEITEM EXPANSION UNITS RANGE COMMENT DEFAULT TABLE POINT NO.
DISP DISPLAY CONFIGURATION_TEST Test Display LEDs OFF/ON OFF N/A displa_test_METR Metric Display US/METR US DISPCONF DISPUNIT_LANG Language Selection English English DISPCONF LANGUAGE
EspanolFrancaisPortuguesTranslated
UNIT UNIT CONFIGURATION-_TYPE Unit Type Air Cooled Air cooled
Heat Pump
-_TONS
-_ VAR.A
-WAR.B
-WAR.C
-_VOLT-_60HZ-_STAR-_ Y.D.-_MTA.A-_R.MT.A-_MTA.B-_R.MT.B-_MTA.C-_R.MT.C-_C.SW.A-_R. CSA-_C.SW.B-_R. CSB-_C.SW.C-_R.CSC-_RECL-_EHS-_EMM-_PAS.E-_PASS-_CO.HT-_CON. V-_FREE-_HI. TI
SERV-_FLUD
_CFLU
-_MOP
-_HP.TH
-_SHP.A
-_SHP.B
-_SHP. C
-_,HTR
_EWTO_AU.SM_LOSP
-_HD.PG-_HD.DG-_HD.IG-_HR.MI-_HR.MA-_HGBP-_MCHX-_FL.SP
Unit Size
Nb Fan on Varifan Cir A
Nb Fan on Varifan Cir B
Nb Fan on Varifan Cir C
Power Supply Voltage60 Hz FrequencySoft Starter SelectWye Delta T Start SelectMust Trip Amps cir ARead Must Trip Amps AMust Trip Amps cir BRead Must Trip Amps BMust Trip Amps cir CRead Must Trip Amps C$1 Config switch cir ARead $1 Config switch A$1 Config switch cir BRead $1 Config switch B$1 Config switch cir CRead $1 Config switch CHeat Reclaim Select
Electrical Heater StageEMM Module InstalledPassword EnableFactory PasswordCooler Heater SelectCondenser Valve SelectFree Cooling SelectHigh Tiers display SelectSERVICE CONFIGURATIONS
Cooler Fluid Type
Condenser Fluid Type
EXV MOP Setpoint
High Pressure Threshold
Cir A Superheat Setp
Cir B Superheat Setp
Cir C Superheat Setp
Cooler Heater DT Setp
Entering Water ControlAuto Start When SM LostBrine Freeze Setpoint
Varifan Proportion GainVarifan Derivative Gain
Varifan Integral GainReclaim Water Valve MinReclaim Water Valve MaxHot Gas Bypass SelectMCHX Exchanger SelectBrine Flow Switch Setp
XXX
X
XXX (volt)
XXX (amps)XXX (amps)XXX (amps)XXX (amps)XXX (amps)XXX (amps)XXX (amps)XXX (amps)XXX (amps)XXX (amps)XXX (amps)XXX (amps)
XXX
XX.X(deg F/deg C)XXX.X (psi/kPa)
XX.X (AF/AC)
XX.X (AF/AC)
XX.X (AF/AC)
XX.X (AF/AC)
XXIX
(deg F/degC)XXIXXXIXXXIX
XXXIX (%)xxxIx (%)
0 to 1800nominal size)
0-8
0-8
0-8
200-690NO/YESNO/YESNO/YES0 to 15000 to 15000 to 15000 to 15000 to 15000 to 15000 to 2550 to 2550 to 2550 to 2550 to 2550 to 255NO/YES0-4NO/YESENBL/DSBL1 to 0150NO/YESNO/YESNO/YESNO/YES
WaterBrineWATERBRINE40-60 F(4.4-15.6 C)250-280 psi(1724-1930 kPa)3-14 F(1.7-7.8 C)3-14 F(1.7-7.8 C)3-14 F
(1.7-7.8 C)0.5-9 F(0.3-5.0 C)
NO/YESNO/YES-20-50 F
(-20-10 C)-10-10-10-10-10-10
NO/YESNO/YES10-60
Heat pump andheat machine
not supported
Not supported.Not supported
Not supported.Not supported.Not supported.
Not supported.
21.6
Not supported.Not supported.Not supported.Not supported.Not supported.
0: No low ambienttemperature head)ressure control
1 :low ambienttemperature head)ressure control
0: No low ambienttemperature head)ressure control
1 : low ambienttemperature head)ressure control
0: No low ambient
temperature head)ressure control
1 : low ambient
temperature head)ressure control
YES
NO0NO
0111
NO
Water
55
290
21.6
7.2
21.6
2.0Number of
degreesadded tobrine freezeset point toenablecoolerheater,)NONO14
2.00.40.22O100NONO55
FACTORY
FACTORY
FACTORY
FACTORY
FACTORY
FACTORYFACTORY
FACTORYFACTORYFACTORYFACTORYFACTORY
FACTORY
SERVICE1
SERVICE1
SERVICE1
SERVICE1
SERVICE1
SERVICE1
SERVICE1
SERVICE1SERVICE1SERVICE1
SERVICE1SERVICE1SERVICE1SERVICE1SERVICE1FACTORYFACTORYSERVICE
unit typ
unitsize
varfan a
varfan b
varfan c
voltagefreq 60Hsoftstarwye deltcpa mtaccpa mtamcpb mtaccpb mtamcpc mtaccpb mtamcpa sl ccpa sl mcpb sl ccpb sl mcpc sl ccpc sl mrecl optehs sel
emm nrcp9ass enbfac passheat selcond valfreecool
highdisp
flui typ
cond typ
mop sp
hp th
sh spa
sh sp b
sh sp c
heatersp
ewt optauto smIowestsp
hd pghd dghd igmin 3wmax3whgbp selmchx selflow sp
78
78
8
8
8
75
20,21,30,50,51, 75, 76
76
52
76
76
76
50, 62
307620,21,30,50,51, 62, 75
9.5
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- CONFIGURATION (cont)
ITEM EXPANSION RANGE COMMENT DEFAULT PAGENO.
OPTN-_CCNA-_CCNB-_BAUD
-_LOAD
-_LLCS
-_RL.S-_DELY-_ICE.M-_HPUM
_PUMP
-_ROT.P-_PM.PS-_PSBY-_P.LOC-_LS.ST-_LS.ND-_LS.LT-_RV.AL-_OATH
-_FREE
_CUR.S_CUR.F_EHST
_EHSB_EDEF_EHSP_AUTO
RSET_CRST
_HRST
_DMDC
_DMMX_DMZE_MSSL
-_SLVA-_LLBL
-_LLBD-_LLDY-_LL.ER
-_LAG.M
-_LAGP
-_LPUL-_SER1
OPTIONS CONFIGURATIONCCN AddressCCN Bus NumberCCN Baud Rate
Loading Sequence Select
Lead/Lag Circuit Select
Ramp Load SelectMinutes Off TimeIce Mode EnableCondenser Pumps Sequence
Cooler Pumps Sequence
Pump Rotation DelayPeriodic Pump StartStop Pump In StandbyFlow Checked if Prop OffNight Low Noise StartNight Low Noise EndLow Noise Capacity LiraReverse Alarms RelayHeat Mode OAT Threshold
Free Cooling OAT Limit
Current Limit SelectCurrent Limit at 100%
Elec Stag OAT Threshold
Last Heat Elec BackupQuick EHS in DefrostElec Heating PulldownAuto Changeover Select
UNITS
XXXXXX
Lead/Lag Balance DeltaLead/Lag DelayStart if Error Higher
Lag Minimum Running Time
Lag Unit Pump Select
Lead Pulldown TimeChillers in Series
XX (Minutes)
X
XXXX (hours)
XX.XXXX.XXXXX(%)
XX.X(deg F/deg C)XX.X
(deg F/deg C)
XXXXXX.XX(deg F/deg C)
XX (rain)
RESET, DEMAND LIMIT, MASTER/SLAVECooling Reset Type
Heating Reset Type
Demand Limit Select
mA for 100% Demand Limit XX.X (mA)mA for 0% Demand Limit XX.X (mA)Master/Slave Select
Slave Address XXX
Lead/Lag Balance Select
XXX (hours)XX (minutes)XX.X
(deg F/deg C)XXX(rain)
XX (minutes)
1-2390-2392400480096001920038400EqualStagedAutomaticCir A LeadsCir B LeadsCir C LeadsENBL/DSBL1 to 15ENBL/DSBLNo Pump1 Pump Only2 Pumps AutoPMP 1 ManualPMP 2 Manual
No Pump1 Pump Only2 Pumps AutoPMP 1 ManualPMP 2 Manual24 to 3000NO-YESNO-YESNO-YES00.00-23.5900-00-23.590-100NO-YES
NO/YES0 to 500023 -70 F(-5-21 C)NO-YESNO-YES
NO-YES
No Reset
Out Air TempDelta T Temp4-20 mA InputSpace TempNo ResetOut Air TempDelta T Temp4-20 mA InputNoneSwitch
4-20 mA Input
DisableMasterSlave1-236
Always LeadLag if FailRuntime Sel40-4002-303-18
0-150
OFF if U stpON if U stp0-60NO/YES
Not supported.
Not supported.Not supported.Not supported.Not supported.
Not supported.
Not supported.
Not supported.Not supported.
Not supported.
09600
EQUAL
AUTOMATIC
DSBL
DSBLNO PUMP
NO PUMP
48NONOYES00.0000.00100NO5F
32.0
NO200041
NONO0NO
NO RESET
NO RESET
NONE
0.00.0DISABLE
2
AlwaysLead
168104
0
OFF if U stp
CCN TABLE
N/AN/AN/A
USER
USER
USERUSERUSER
USER
USERUSERUSERUSERUSERUSERUSERUSERUSER
USER
USER
USERUSERUSERUSER
USER
USER
USER
USERUSERMaT SLV
MaT SLVMaT SLV
MaT SLVMST SLVMaT SLV
MaT SLV
MaT SLV
MaT SLV
CCN POINT
CCNACCNBBAUD
lead cir
seq typ
ramp seloff on dice cnfghpum seq
pump seq
pump delpump perpump sbypump Iocnh startnh endnh limital reverheatth
free oat
curr aelcurr fulehs th
ehsbackehsdefrehs_ullauto sel
cr sel
hr sel
lira sel
lim mxlim zems sel
sly addrhal
baldIsrt timstart dt
lag mini
lag pump
lead pulserle
49
49
16
18, 20, 5015, 30, 493O
5O
5050
505050
31,32, 50
32, 40, 50
4O4O49, 51, 77
16, 49
16, 4949
49
16, 4916
96
ITEM
TIME-_HH.MM
DATE-_MNTH
-_DOM-_DAY
-_ YEAR
SCH1-_PER. 1-_PER. 1-_OCC. 1-_PER. 1-_UNO. 1-_PER. 1-_MON. 1-_PER. 1-_ TUE. 1-_PER. I-_WED.1-_PER. 1-_ THU. 1-_PER. 1-_FRI. 1-_PER. 1-_SAT. 1-_PER. 1-_SUN. 1-_PER. 1-_HOL. 1-_PER.2-_PER.2-_OCC.2-_PER.2-_UNO.2-_PER.2-_MON.2-_PER.2-_ TUE.2-_PER.2-_WED.2-_PER.2-_ THU.2-_PER.2-_FRI.2-_PER.2-_SAT.2-_PER.2-_SUN.2-_PER.2-_HOL.2-_PER.3-_PER.3-_OCC.3-_PER.3-_UNO.3-_PER.3-_MON.3-_PER.3-_ TUE.3-_PER.3-_WED.3-_PER.3-_ THU.3-_PER.3-_FRI.3-_PER.3-_SAT.3-_PER.3-_SUN.3-_PER.3-_HOL.3-_PER.4-_PER. 4-_OCC. 4-_PER. 4-_U NO. 4-_PER.4-_MON.4-_PER.4-_TUE.4-_PER. 4-_ WED. 4-_PER.4-_THU.4-_PER. 4-_FRI. 4-_PER.4-_SAT.4-_PER.4-_SUN.4-_PER. 4-_HOL. 4-_PER.5-_PER.5-_OCC.5-_PER.5-_UNO.5-_PER.5-_MON.5-_PER.5-_ TUE.5-_PER.5-_WED.5-_PER.5-_ THU.5-_PER.5-_FRI.5-_PER.5-_SAT.5-_PER.5-_SUN.5-_PER.5-_HOL.5-_PER.6-_PER.6-_OCC.6-_PER.6-_UNO.6-_PER.6-_MON.6-_PER.6-_ TUE.6-_PER.6-_WED.6-_PER.6-_ THU.6-_PER.6-_FRI.6-_PER.6-_SAT.6-_PER.6-_SUN.6-_PER.6-_HOL.6
*Password protected.
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- TIMECLOCK
EXPANSION
TIME OF DAYHour and Minute
DAY, DATEMonth
Day of MonthDay of Week
Year of CenturySCHEDULE 1Period 10cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 20cc/Unocc SelOccupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 30cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 40cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 50cc/Unocc SelOccupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 60cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday Select
UNITS RANGE
XX.XX 00.00-23.59
WRITECOMMENT STATUS
forcible*
CCN TABLE
N/A
forcible* N/A
forcible*forcible*
forcible*
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
N/AN/A
N/A
OCClP01SOCClP01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCClP01SOCClP01SOCClP01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCClP01SOCClP01SOCClP01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCClP01S
OCClP01SOCClP01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01S
OCClP01SOCClP01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01S
OCClP01SOCClP01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01SOCC1P01S
CCN POINT
HH.MM
MNTH
DOMDAY
YEAR
OCCTOD1UNOCTOD1DOW1DOW1DOW1DOW1DOW1DOW1DOW1DOWl
OCCTOD2UNOCTOD2DOW2DOW2DOW2DOW2DOW2DOW2DOW2DOW2
OCCTOD3UNOCTOD3DOW3DOW3DOW3DOW3DOW3DOW3DOW3DOW3
OCCTOD4UNOCTOD4DOW4DOW4DOW4DOW4DOW4DOW4DOW4DOW4
OCCTOD5UNOCTOD5DOW5DOW5DOW5DOW5DOW5DOW5DOW5DOW5
1=January2=February3=March4-April5=May6=June7=July8=August9-SeptemberlO=October11=November12=December
XX 1-311=Monday2-Tuesday3=Wednesday4-Thursday5=Friday6=Saturday7=Sunday
XX 00-99
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00;00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00;00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
OCCTOD6UNOCTOD6DOW6
DOW6DOW6DOW6DOW6
DOW6DOW6DOW6
PAG ENO.
29, 30
9?
ITEM
SCH1-_PER.7-_PER.7-_OCC.7-_PER.7-_UNO.7-_PER.7-_MON. 7-_PER.7-_TUE.7-_PER.7-_WED.7-_PER.7-_THU.7-_PER.7-_FRL 7-_PER.7-_SAT. 7-_PER.7-_SUN.7-_PER.7-_HOL.7-_PER.8-_PER.8-_OCC.8-_PER.8-_UNO.8-_PER.8-_MON.8-_PER.8-_TUE.8-_PER.8-_WED.8-_PER.8-_THU.8-_PER.8-_FRL8-_PER.8-_SAT.8-_PER.8-_SUN.8-_PER.8-_HOL.8
SCH2-_PER. 1-_PER. 1-_OCC. 1-_PER. 1-_UNO. 1-_PER. 1-_MON. 1-_PER. 1-_ TUE. 1-_PER. I-_WED.1-_PER. I-_ THU.1-_PER. 1-_FRL 1-_PER. 1-_SAT. 1-_PER. 1-_SUN. 1-_PER. 1-_HOL. 1-_PER.2-_PER.2-_OCC.2-_PER.2-_UNO.2-_PER.2-_MON.2-_PER.2-_TUE.2-_PER.2-_WED.2-_PER.2-_THU.2-_PER.2-_FRL2-_PER.2-_SAT.2-_PER.2-_SUN.2-_PER.2-_HOL.2-_PER.3-_PER.3-_OCC.3-_PER.3-_UNO.3-_PER.3-_MON.3-_PER.3-_TUE.3-_PER.3-_WED.3-_PER.3-_THU.3-_PER.3-_FRL3-_PER.3-_SAT.3-_PER.3-_SUN.3-_PER.3-_HOL.3-_PER.4-_PER.4-_OCC.4-_PER.4-_UNO.4-_PER.4-_MON.4-_PER.4-_TUE.4-_PER.4-_WED.4-_PER.4-_THU.4-_PER.4-_FRL 4-_PER.4-_SAT.4-_PER.4-_SUN.4-_PER.4-_HOL.4-_PER.5-_PER.5-_OCC.5-_PER.5-_UNO.5-_PER.5-_MON.5-_PER.5-_TUE.5-_PER.5-_WED.5-_PER.5-_THU.5-_PER.5-_FRL5-_PER.5-_SAT.5-_PER.5-_SUN.5-_PER.5-_HOL.5-_PER.6-_PER.6-_OCC.6-_PER.6-_UNO.6-_PER.6-_MON.6-_PER.6-_TUE.6-_PER.6-_WED.6-_PER.6-_THU.6-_PER.6-_FRL6-_PER.6-_SAT.6-_PER.6-_SUN.6-_PER.6-_HOL.6
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- TIMECLOCK (cont)
EXPANSION UNITS RANGE
SCHEDULE 1Period 70cc/Unocc Sel
Occupied Time XX.XX 00:00-23:59Unoccupied Time XX.XX 00:00-23:59Monday Select NO/YESTuesday Select NO/YESWednesday Select NO/YESThursday Select NO/YESFriday Select NO/YESSaturday Select NO/YESSunday Select NO/YESHoliday Select NO/YESPeriod 8 ©cc/Unocc SelOccupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday Select
SCHEDULE 2Period 10cc/Unocc SelOccupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 2 ©cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 3 ©cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 4 ©cc/Unocc SelOccupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 50cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 6 ©cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday Select
XX.XX 00:00-23;59XX.XX 00:00-23;59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
XX.XX 00:00-23:59XX.XX 00:00-23:59
NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
WRITECOMMENT STATUS
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
CCN TABLE
OCCP01S©CCP01SOCCP01SOCCP01SOCCP01SOCCP01SOCCP01SOCCP01SOCCP01SOCCP01S©CCP01SOCCP01S©CCP01S©CCP01S©CCP01S©CCP01S©CCP01SOCCP01SOCCP01SOCCP01SOCCP01S
OCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02S
OCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02S
OCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02S
OCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02S
OCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02S
OCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02SOCC2P02S
CCN POINT
OCCTOD7UNOCTOD7DOW7DOW7DOW7DOW7DOW7DOW7DOW7DOW7
OCCTOD8UNOCTOD8DOW8DOW8DOW8DOW8DOW8DOW8DOW8DOW8
©CCTOD1UN©CTOD1DOW1DOW1DOW1DOW1DOW1DOW1DOW1DOW1
OCCTODUNOCTOD2DOW2DOW2DOW2DOW2DOW2DOW2DOW2DOW2
OCCTODUNOCTOD3DOW3
DOW3DOW3DOW3
DOW3DOW3DOW3
DOW3
OCCTOD4UNOCTOD4DOW4DOW4DOW4DOW4DOW4DOW4DOW4DOW4
OCCTOD5UNOCTOD5DOW5DOW5DOW5DOW5DOW5DOW5DOW5DOW5
OCCTOD6UNOCTOD6DOW6
DOW6DOW6DOW6
DOW6DOW6DOW6
DOW6
PAGENO.
29
98
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- TIMECLOCK (cont)
ITEM
-_PER. 7-_PER. 7-_0CC. 7-_PER. 7-_UNO. 7-_PER. 7-_MON.7-_PER. 7-* TUE. 7-_PER.7-_WED.7-_PER.7-_THU.7-_PER.7-_FRI.7-_PER. 7-_SAT. 7-_PER.7-_SUN.7-_PER.7-_HOL.7-_PER.8-_PER.8-_OCC.8-_PER.8-_UNO.8-_PER.8-_MON.8-_PER.8-_ TUE.8-_PER.8-_WED.8-_PER.8-_ THU.8-_PER.8-_FRI.8-_PER.8-_SAT.8-_PER.8-_SUN.8-_PER.8-_HOL.8
HOLI-_HOL. 1-_HOL. 1 -_MON. 1
-_HOL. 1 -_DAY 1-_HOL. 1 -_DUR. 1-_HOL. 1 -_HOL.2-_HOL. 1 -_MON.2
-_HOL. 16-_H0.16-_,HOL. 16-_M0.16
-_HOL. 16-_DA. 16
-_HOL. 16-_DU. 16
MCFG-_AL.SV-_CHRG-_ WA TE-_PMP. 1-_PMP.2-_PMP.3-_PMP.4-_W.FIL-_A.FIL-_B.FIL-_C.FIL-_RS.S V
EXPANSION
Period 70cc/Unocc SelOccupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectPeriod 80cc/Unocc Sel
Occupied TimeUnoccupied TimeMonday SelectTuesday SelectWednesday SelectThursday SelectFriday SelectSaturday SelectSunday SelectHoliday SelectHOLIDAYS*
Holiday 1 ConfigurationHoliday Start Month
Holiday Start DayHoliday Duration in DaysHoliday 2 ConfigurationHoliday Start Month
Holiday Start Day
Holiday Duration in Days
Holiday 16 ConfigurationHoliday Start Month
Holiday Start Day
Holiday Duration in Days
UNITS
XX.XXXX.XX
XX.XXXX.XX
XXXX
SERVICE MAINTENANCE CONFIGURATION
RANGE
00:00-23:5900:00-23:59NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
00:00-23:5900:00-23:59NO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YESNO/YES
1=January2-February3=March
4=April5=May6=June
7=July8-August9=September10-Octobe r11=November12=December1 to311 to 99
See
HOL.I-_MON.1SeeHOL.I-_DAY.1SeeHOL.I-_DUR.1
See
HOL.I_MON.1SeeHOL.I_DAY.1SeeHOL.I_DUR.1
COMMENT WRITE CCN TABLESTATUS
forcible OCC2P02Sforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcibleforcible
forcible HOLDY 01
forcible HOLDY 01forcible HOLDY 01
forcible HOLDY 02
forcible HOLDY 02
forcible HOLDY 02
forcible HOLDY 16
forcible HOLDY 16
forcible HOLDY 16
CCN POINT
OCCTOD7UNOCTOD7DOW7DOW7DOW7DOW7DOW7DOW7DOW7DOW7
OCCTOD8UNOCTOD8DOW8DOW8DOW8DOW8DOW8DOW8DOW8DOW8
HOL MON
HOLDAYHOLLEN
HOLMON
HOLDAY
HOLLEN
PAGENO,
Service Warning SelectRefrigerant ChargeWater Loop SizePump 1 (days)Pump 2 (days)Cond Pump 1 (days)Cond Pump 2 (days)Water Filter (days)Comp A Oil Filter (days)Comp B Oil Filter (days)Comp C Oil Filter (days)Servicing Alert Reset
XXXX (days)XXXX (days)XXXX (days)XXXX (days)XXXX (days)XXXX (days)XXXX (days)XXXX (days)
NO/YESNO/YESNO/YES0-65,5000-65,5000-65,5000-65,5000-65,5000-65,5000-65,5000-65,5000=Default
DEFAULT=NODEFAULT=NODEFAULT=NODEFAULT-0DEFAULT-0DEFAULT-0DEFAULT-0DEFAULT=0DEFAULT=0DEFAULT=0DEFAULT-0DEFAULT-0
forcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible MAINTCFGforcible SERMAINT
s alertchargeawloop cpumplcpump2chpumpl chpump2 cwfilte cofiltacofiltbcofiltc cs reset
8O
41
1=Refrigerant Charge2-Water loop size3=Not used4=Pump 15=Pump 26=Reclaim Pump (not used)7=Reclaim Pump (not used)8-Water Filter
9=Compressor A Oil Filter10=Compressor B Oil Filter11=Compressor C Oil Filter12=Reset All
*Holidays range from 1-16. Item has same structure, with the only difference being the two number identifier.
99
APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- OPERATING MODE
ITEM
SLCT-_OPER
-_SP.SE
_HGSE
EXPANSION*
OPERATING CONTROL TYPEOperating Control Type
Setpoint Select
Heat Cool Select
WRITE PAGEUNITS RANGE COMMENT STATUS NO.
Switch CtrlTime SchedCCN ControlSetpoint OccSetpointlSetpoint24-20mA SetpDual Setp SwCoolingHeatingAuto ChgoverHeat Cool SwNoYesSwitch Ctrl
Default - SwitchCtrl
Default =
Setpoint Occ
Default = CoolingNot supported.Not supported.Not supported.Default = NoNot supported.Not supported.
forcible
forcible
forcible
CCN TABLE
N/A
N/A
GENUNIT
CCN POINT
N/A
N/A
HC SEL
29, 49
30, 40
3O
-_RL.SE Reclaim Select forcible GENUNIT RECLSET
MODE* OPERATING MODES-eMD01 First Active Mode 0-32 MODES-eMD02 Second Active Mode 0-32 MODES-eMD03 Third Active Mode 0-32 MODES-eMD04 Fourth Active Mode 0-32 MODES-_MD05 Fifth Active Mode 0-32 MODES-_MD06 Sixth Active Mode 0-32 MODES
*Up to six current operating modes will be displayed.
NOTE: See operating modes starting on page 49.
MODE -- ALARMS
ITEM EXPANSION* UNITS RANGE COMMENT WRITE CCN TABLE CCN POINT PAGESTATUS NO.
R.ALM RESET ALL CURRENT ALARM NO/YES forcible N/A N/A
ALRMt CURRENTLY ACTIVE ALARMS 67Current Alarm 1 GENUNIT alarm 1Current Alarm 2 GENUNIT alarm 2Current Alarm 3 GENUNIT alarm 3Current Alarm 4 GENUNIT alarm4Current Alarm 5 GENUNIT alarm 5
H.ALM** ALARM HISTORYAlarm History #1 ALRMHIST aim history 01Alarm History #2 ALRMHIST aim history 02
ALRMHISTAlarm History #49 ALRMHIST aim history49Alarm History #50 ALRMHIST aim historySO
*Expanded display will be actual alarm description.tHistory of up to five past alarms will be displayed.**History of fifty past alarms will be displayed,
1O0
TABLE
ClRCAAN
CIRCA D
ClRCBAN
CIRCE D
*Not supported.
APPENDIX B -- CCN TABLES
STATUS DISPLAY TABLES
DISPLAY NAME
CIRCUIT A ANALOG VALUESPercent Total CapacityDischarge PressureSuction PressureEconomizer PressureOil PressureOII Pressure DifferenceMotor CurrentMotor TemperatureDischarge Gas TempEconomizer Gas TempSaturated Condensing TrapSaturated Suction TempCompressor Suction TempEXV PositionHead Press Actuator Pos
CIRCUIT A DISCRETECompressor OutputSlide Valve 1 OutputSlide Valve 2 OutputOil Heater OutputOil Solenoid OutputOil Level InputDGT Cooling Solenoid
FANS OUTPUTFan Output DO # 1Fan Output DO # 2Fan Output DO # 3Fan Output DO # 4Fan Output DO # 5Fan Output DO # 6Fan Output DO # 7Fan Output DO # 8Fan Staging Number
I RANGE I UN,TSI PO,NTNAMEI WR,TESTATUS0- 100nnn.nnnn.nnnn.nnnn.nnnn.nnnn.nnnnnnnnnnnnn_+nnn.n_+nnn.n_+nnn.n0- 1000- 100
ON/OFFON/OFFON/OFFON/OFFON/OFFLow/HighON/OFF
%psipsipsipsipsiAMPSoFoFoFoFoFoF%%
CAPATDPASP AECON P AOPADOP ACURREN ACPTMPADGTAECO TP ASCT ASSTASUCT T AEXV Ahd pos a
COMP ASLID 1 ASLID 2 AOIL HT AOIL SL AOIL L AGASCOOLA
FREE COOLING OUTPUTRefrigerant Pump Out*Circuit Heater Output*
MISCELLANEOUSBall Valve PositionBall Valve Closing OutBall Valve Opening Out4 Way Refrigerant Valve*
CIRCUIT B ANALOG VALUESPercent Total CapacityDischarge PressureSuction PressureEconomizer PressureOil PressureOil Pressure DifferenceMotor CurrentMotor TemperatureDischarge Gas TempEconomizer Gas TempSaturated Condensing TrapSaturated Suction TempCompressor Suction TempEXV PositionHead Press Actuator Pos
CIRCUIT B DISCRETECompressor OutputSlide Valve 1 OutputSlide Valve 2 OutputOil Heater OutputOil Solenoid OutputOil Level InputDGT Cooling Solenoid
FANS OUTPUTFan Output DO # 1Fan Output DO # 2Fan Output DO # 3Fan Output DO # 4Fan Output DO # 5Fan Output DO # 6Fan Output DO # 7Fan Output DO # 8Fan Staging Number
FREE COOLING OUTPUTRefrigerant Pump Out*Circuit Heater Output*
MISCELLANEOUSBall Valve PositionBall Valve Closing OutBall Valve Opening Out4 Way Refrigerant Valve*
ON/OFFON/OFFON/OFFON/OFFON/OFFON/OFFON/OFFON/OFF0-10
ON/OFF
ON/OFF
OPEN/CLSEON/OFFON/OFFON/OFF
0- 100nnn.nnnn.nnnn.nnnn.nnnn.nnnn.nnnnnnnnnnnnn_+nnn,n_+nnn,n_+nnn,n0-1000-100
ON/OFFON/OFFON/OFFON/OFFON/OFFLow/HighON/OFF
ON/OFFON/OFFON/OFFON/OFFON/OFFON/OFFON/OFFON/OFF0-10
ON/OFF
ON/OFF
OPEN/CLSEON/OFFON/OFFON/OFF
%psipsipsipsipsiAMPSoFoFoFoFoFoF%%
fan alfan a2fan a3fan a4fan a5fan a6fan a7fan a8FAN ST A
FR PMP A
FR HEATA
ISO REFAISO CL A
ooPACAPETDP BSP BECON P BOP BDOP BCURREN BCPTMP BDGT BECO TP BSCT BSSTBSUCT T BEXV Bhd pos b
COMP BSLID 1 BSLID 2 BOIL HT BOIL SL BOIL L BGASCOOLB
fan blfan b2fan b3fan b4fan b5fan b6fan b7fan b8FA_ST B
FR PMP B
FR HEATB
ISO REFBISO CL B
ooPB
101
TABLE
ClRCC AN
ClRCC D
APPENDIX B -- CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
I RANGE I UNITSI POINTNAMEI WRITESTATUS0-100nnn.nnnn.n
nnn,nnnn.nnnn.nnnn,nnnnnnnnnnnnn_+nnn.n_+nnn.n_+nnn.n0-1000-100
DISPLAY NAME
CIRCUIT C ANALOG VALUESPercent Total CapacityDischarge PressureSuction PressureEconomizer PressureOil PressureOil Pressure DifferenceMotor CurrentMotor TemperatureDischarge Gas TempEconomizer Gas TempSaturated Condensing TmpSaturated Suction TempCompressor Suction TempEXV PositionHead Press Actuator Pos
CIRCUIT C DISCRETECompressor OutputSlide Valve 1 OutputSlide Valve 2 OutputOil Heater OutputOil Solenoid OutputOil Level InputDGT Cooling Solenoid
FANS OUTPUTFan Output DO # 1Fan Output DO # 2Fan Output DO # 3Fan Output DO # 4Fan Output DO # 5Fan Output DO # 6Fan Output DO # 7Fan Output DO # 8Fan Staging Number
FREE COOLING OUTRefrigerant Pump Out*Circuit Heater Output*
MISCELLANEOUSBall Valve PositionBall Valve Closing OutBall Valve Opening Out4 Way Refrigerant Valve*
On/OffOn/OffOn/OffOn/OffOn/OffLow/HighOn/Off
On/OffOn/OffOn/OffOn/OffOn/OffOn/OffOn/OffOn/Off0-10
%psipsipsipsipsiAMPSoFoFoFoFoFoF%%
CAPCTDP CSP CECON P COP CDOP CCURl:tEN CCP TMP CDGT CECO TP CSCT CSST CSUCT T CEXV Chd pos c
COMP CSLID 1 CSLID 2 COIL HT COILSLCOILLCGASCOOLC
fan clfan c2fan c3fan c4fan c5fan c6fan c7fan c8FAN ST C
On/Off FR PMP COn/Off FR HEATC
OPEN/CLSE ISO REFCOn/Off ISO CL COn/Off ISO OP COn/Off RV
FAN HOURS
*Not supported.
FAN OPERATING HOURSCircuit A Fan #1 HoursCircuit A Fan #2 HoursCircuit A Fan #3 HoursCircuit A Fan #4 HoursCircuit A Fan #5 HoursCircuit A Fan #6 HoursCircuit A Fan #7 HoursCircuit A Fan #8 HoursCircuit A Fan #9 HoursCircuit A Fan #10 HoursCircuit B Fan #1 HoursCircuit B Fan #2 HoursCircuit B Fan #3 HoursCircuit B Fan #4 HoursCircuit B Fan #5 HoursCircuit B Fan #6 HoursCircuit B Fan #7 HoursCircuit B Fan #8 HoursCircuit B Fan #9 HoursCircuit B Fan #10 HoursCircuit C Fan #1 HoursCircuit C Fan #2 HoursCircuit C Fan #3 HoursCircuit C Fan #4 HoursCircuit C Fan #5 HoursCircuit C Fan #6 HoursCircuit C Fan #7 HoursCircuit C Fan #8 HoursCircuit C Fan #9 HoursCircuit C Fan #10 Hours
nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn
hours hrfanalhours hrfana2hours hrfana3hours hrfana4hours hrfana5hours hrfana6hours hrfana7hours hrfana8hours hr fana9hours hrfanal0hours hrfanblhours hrfanb2hours hrfanb3hours hrfanb4hours hrfanb5hours hrfanb6hours hrfanb7hours hrfanb8hours hr fanb9hours hrfanbl0hours hrfanclhours hrfanc2hours hrfanc3hours hrfanc4hours hrfanc5hours hrfanc6hours hrfanc7hours hrfanc8hours hrfanc9hours hrfancl0
102
APPENDIX B -- CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE
GENUNIT
DISPLAY NAME
Operating TypeControl Type
Run Status
CCN Chiller Start/StopChiller Occupied?Minutes Left for StartHeat/Cool Status
Heat/Cool Select
Heat Reclaim SelectFree Cooling SelctAlarm State
Current Alarm 1Current Alarm 2Current Alarm 3Current Alarm 4Current Alarm 5
Percent Total CapacityActive Demand Limit Val
Lag Capacity Limit ValueActual Chiller CurrentChiller Current Limit
Current SetpointSetpoint Occupied?Setpoint Control
Control Point
Controlled Water TempExternal TemperatureEmergency Stop
MODES Startup Delay in EffectSecond Setpoint in UseReset in EffectDemand Limit ActiveRamp Loading ActiveCooler Heater ActiveCooler Pumps RotationPump Periodic StartNight Low Noise ActiveSystem Manager ActiveMaster Slave ActiveAuto Changeover ActiveFree Cooling ActiveReclaim ActiveElectric Heat ActiveHeating Low EWT LockoutCondenser Pumps RotationIce Mode in EffectDefrost Active On Cir ADefrost Active On Cir BLow Suction Circuit ALow Suction Circuit BLow Suction Circuit CHigh DGT Circuit AHigh DGT Circuit BHigh DGT Circuit CHigh Pres Override Cir AHigh Pres Override Cir BHigh Pres Override Cir CLow Superheat Circuit ALow Superheat Circuit BLow Superheat Circuit C
*Not supported.tThe forced value will be used.
RANGE UNITS POINT NAME
L-Off-Local Off OPERTYP(ComfortLink Controls- On/Off Switch-Opened)L-On-Local OnL-Sched-Local On/Off State based on Time SchedulesCCN-Unit is in CCN ControlRemote-On/Off Based on Remote Contact(not applied to ComfortLink Display)Master-Unit Operation in Lead/Lag and it is a MasterLocal ctr typeCCNRemote0 - Off STATUS1 - Running2 = Stopping3 = Delay4 = Tripout5 - Ready6 - Override7 - Defrost8 - Run Test9 = TestEnable/Disable CHILS SYedNo CHILOCC0-15 rain rain left0 - Cool HEATCOOL1 - Heat2 = Stand-by3 = Both0 = Cool HC SEL1 = Heat2 = AutoYedNo RECL SELYedNo FC DSBLE0 = Normal ALM1 - Partial2 - Shutdownnnnnn alarm 1nnnnn alarm 2nnnnn alarm 3nnnnn alarm4nnnnn alarm 5nnn % CAP Tnnn % DEM LIMnnn % LAG LIM
nnn amps TOT CURRnnn amps CURR LIM_+nnn.n °F SPYes/No SP OCC
Setpt 1 sp ctrlSetpt 2Ice sp4-20mAAuto_+nnn.n °F CTRL PNT_+nnn.n °F CTRLWT_+nnn.n °F OATEnable/Disable EMSTOP
Yes/No -- Mode 01Yes/No -- Mode 02Yes/No -- Mode 03Yes/No -- Mode 04YedNo -- Mode 05YedNo -- Mode 06YedNo -- Mode 07YedNo -- Mode 08Yes/No -- Mode 09Yes/No -- Mode 10Yes/No -- Mode 11Yes/No -- Mode 12Yes/No -- Mode 13Yes/No -- Mode 14Yes/No -- Mode 15Yes/No -- Mode 16Yes/No -- Mode 17Yes/No -- Mode 18YedNo -- Mode 19YedNo -- Mode20YedNo -- Mode21YedNo -- Mode22Yes/No -- Mode23Yes/No -- Mode24Yes/No -- Mode25Yes/No -- Mode26Yes/No -- Mode27Yes/No -- Mode28Yes/No -- Mode29Yes/No -- Mode 30Yes/No -- Mode 31YedNo -- Mode 32
WRITE STATUS
forcibleforcible
forcible
forcible*forcible
forcible*
forcibletforcible
forcible
forcible*
forcible
103
APPENDIX B -- CON TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE RANGE UNITS POINT NAME WRITE STATUS
RECLAIM* Yes/no RECL SELOn/Off CONDPUMPOn/Off CONDFLOWOn/Off cend htr±nnn.n °F HR EWT±nnn.n °F HR LWT±nnn.n °F RSP forcible±nnn.n % hr v_os
STATEGEN
STRTHOUR
DISPLAY NAME
Heat Reclaim SelectReclaim Condenser PumpReclaim Condenser FlowReclaim Condenser HeaterReclaim Entering FluidReclaim Leaving FluidReclaim Fluid SetpeintReclaim Valve Position
HEAT RECLAIM CIRCUIT AReclaim Status Circuit APumpdown Pressure Cir ASub Condenser Temp Cir APumpdown Saturated Trap ASubceeling Temperature AAir Cond Entering Valv AWater Cond Enter Valve AAir Cond Leaving Valve AWater Cond Leaving Val A
HEAT RECLAIM CIRCUIT BReclaim Status Circuit BPumpdown Pressure Cir BSub Condenser Temp Cir BPumpdown Saturated Trap BSubcoeling Temperature BAir Cond Entering Valv BWater Cond Enter Valve BAir Cend Leaving Valve BWater Cond Leaving Val B
UNIT DISCRETE INOn/Off - Remote SwitchRemote Heat/Cool SwitchCurrent Control
n±nnn,n±nnn,n±nnn.n±nnn.nOn/OffOn/OffOnlOffOn/Off
Remote Reclaim SwitchRemote Setpoint SwitchLimit Switch 1 StatusLimit Switch 2 StatusOccupied Override SwitchIce Done Storage SwitchCooler Flow SwitchCooler Pump Run Status*Condenser Flow Status*Remote Interlock StatusElectrical Box Interlock*
UNIT DISCRETE OUTElectrical Heat Stage*Cooler Pump #1 Command*Cooler Pump #2 Command*Rotate Cooler Pumps ?*Condenser Pump #1 Out*Condenser Pump #2 Out*Rotate Condenser Pumps?*Cooler Heater CommandShutdown Indicator StateAlarm Relay StatusAlert Relay StatusReady or Running StatusRunning Status
UNIT ANALOGCooler Flow Setpoint Out*Cooler Entering FluidCooler Leaving FluidCondenser Entering Fluid*Condenser Leaving Fluid*Cooler Heater TempOptional Space TempCHWS TemperatureReset/Setpnt 4-20mA SgnlLimit 4-20mA SignalChiller Capacity Signal
Machine Operating HoursMachine Starts NumberCompressor A HoursCompressor A StartsCompressor B HoursCompressor B StartsCompressor C HoursCompressor C Starts
WATER PUMPS*Cooler Pump #1 HoursCooler Pump #2 HoursCondenser Pump #1 HoursCondenser Pump #2 Hours
DEFROST CYCLES*Circuit A Defrost NumerCircuit B Defrost Number
n±nnn.n±nnn.n±nnn.n±nnn.nOn/OffOn/OffOnlOffOnlOff
Open/ClseOpen/ClseOff, On Cool, On Heat,On AutoOpen/ClseOpen/ClseOpen/ClseOpen/ClseOpen/ClseOpen/ClseOpen/ClseOpen/ClseOn/OffOpen/ClseOpen/Clse
0-4/OffOn/OffOn/OffYes/NoOn/OffOn/OffYes/NoOn/OffOn/OffOn/OffOn/OffOn/OffOn/Off
On/Off±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nn.n±nn.n±nn.n
nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn
psioFoF^F
psioFoF^F
oFoFoFoFoFoFoFmama
volts
hours
hours
hours
hours
hrstat aPD PAhr subtahr sat ahr subcahr ea ahr ew ahr la ahr Iw a
hrstat bPDPBhr subtbhr sat bhr subcbhr ea bhr ew bhr labhr Iw b
ONOFF SWHC SWon ctrl
RECLSWSETP SWLIM SW1LIM SW2OCC OVSWICE SWFLOW SWCPUMPDEFCONDFLOWREM LOCKELECBOX
EHS STEPCPUMP 1CPUMP2ROTCPUMPHPUMP 1HPUMP2ROTHPUMPCOOLHEATSHUTDOWNALARMOUTALERTREADYRUNNING
SET FLOWCOOL EWTCOOL LWTCOND EWTCOND LWTHEATERSPACETMPCHWSTEMPSP RESETLIM ANALCAPT 010
HR MACHst machHR CP AstcpaHR CP BstcpbHR CP Cst cp c
nnnnn hours hr cpumlnnnnn hours hr cpum2nnnnn hours hr hpumlnnnnn hours hr hpum2
nnnnn nb def annnnn nb def b
*Not supported.
forcibleforcibleforcibleforcibleforcibleforcible
104
APPENDIX B -- CON TABLES (cont)
CONFIGURATION TABLES
TABLE DISPLAY NAME RANGE DEFAULT UNITS POINT NAME
Ctrl ID Device Name 8 chars PD5 RBRQDescription 24 chars PRO-DIALOG 5
30RB&30HPLocationSoftware Part Number CSA-SR-20C4600nnModel NumberSerial NumberReference Number
ALARMDEF Alarm Routing Control 00000000 ALRM CNTAlarm Equipment Priority 4 EQP TYPComm Failure RetryTime 10 rain RETRY TMRealarm Time 30 rain RE ALARMAlarm System Name PRO RGRW ALRM NAM
BRODEFS Activate 2 -- Ccnbroad
HOLIDAY/HOLDY01 StoHOLDY16S
OCCDEFCS/OCCPC01S andOCCPC02S
OAT Broadcast
DAYLIGHT SAVING SELECTENTERINGMonthDay of week* (1=Monday)Week Number of MonthtLEAVINGMonthDay of week* (1=Monday)Week Number of Montht
Holiday Start MonthStart DayDuration (days)
Timed Override HoursPeriod 1 DOW (MTWTFSSH)Occupied FromOccupied ToPeriod 2 DOW (MTWTFSSH)Occupied FromOccupied ToPeriod 3 DOW (MTWTFSSH)Occupied FromOccupied ToPeriod 4 DOW (MTWTFSSH)Occupied FromOccupied ToPeriod 5 DOW (MTWTFSSH)Occupied FromOccupied ToPeriod 6 DOW (MTWTFSSH)Occupied FromOccupied ToPeriod 7 DOW (MTWTFSSH)Occupied FromOccupied ToPeriod 8 DOW (MTWTFSSH)Occupied FromOccupied To
24 chars16 chars20 chars12 chars24 chars
0-111111110-71-2401-2558 chars
0-Unused1-Broadcast time,date, holiday flag andOAT2=For Standalonechiller. Daylight savingstime & holiday determi-nation will be donewithout broadcastingthrough the bus.
Bus # 0 to 239
Element #0 to 239
Disable/Enable
1to 121to71to5
to 12to 7to 5
0-120-310-99
0-40/100:00-24:0000:00-24:000/100:00-24:0000:00-24:000/100:00-24:0000:00-24:000/100:00-24:0000:00-24:000/100:00-24:0000:00-24:000/100:00-24:0000:00-24:000/100:00-24:0000:00-24:000/100:00-24:0000:00-24:00
*Day of week where daylight savings time will occur in the mornim (at2:00 am). Daylight savings time occurs on Sunday (7) morning, 1 hour shallbe added when entering and 1 hour subtracted when leaving.
tDate once selected (from 1) shall occur in the week number entered. 1: If dayof week selected is 7 (Sunday) time change will occur the first Sunday (week
00
isable
10
ooo
o1111111100:0024:0011111111oo:oooo:oooooooooo00:00oo:oooooooooo00:00oo:oooooooooo00:0000:00oooooooooo:oooo:oooooooooo00:00oo:oooooooooo00:00oo:oo
Oatbusnm
Oatlocad
dayl selStartmonStartdowStartwom
StopmonStoptdow
stopwomHOL MONHOL DAYHOL LEN
©VR EXTDOWl©CCTOD1UN©CTOD1DOW1©CCTOD1UNOCTOD2DOW3©CCTOD3UN©CTOD3DOW4©CCTOD4UN©CTOD4DOW5©CCTOD5UNOCTOD5DOW6OCCTOD6UN©CTOD6DOW7OCCTOD7UN©CTOD7DOW8©CCTOD8UNOCTOD8
number 1 in the month. 5: If day of week selected is 7 (Sunday) time changewill occur the last Sunday of the month (week number 4 or 5).
NOTE: nn is software version.
105
APPENDIX B -- CON TABLES (cent)
CONFIGURATION TABLES (cent)
TABLE DISPLAY NAME RANGE
DISPCONF Metric Display on STDU Yes/No NoLanguage Selection 0=English 0
l=Espanol2-Francais3=Portugues4=Translated
NOTES:1. Enter unit size. This item allows the controls to determine capacity of each
compressor and the total number of fans on each circuit based on a com-pressor arrangement array (can be viewed in table FACTORY2). It is netnecessary to enter compressor capacity and number of fans on each cir-cuit, See Tables 1A and 1B in the 30XA Installation Instructions for moreinformation.
2. Number of fans controlled directly by a variable speed fan actuator using 0to 10 vdc signal, This will enable the controls to determine the remainingdiscrete fan staging outputs from the total fans on each circuit.
DEFAULT UNITS POINT NAME
DISPUNITLANGUAGE
3. Used for extra functions with the purpose of energy management such asoccupancy override switch, ice storage, setpoint reset, and demand limit.
4. Compressor capacity will be automatically be determined if unit sizeentered in FACTORY1 table matches the values in the unit compressorconfiguration table,
5. Total number of fans includes fans controlled by a variable speed fan. Thisvalue will be automatically populated if unit size entered in FACTORY1table matches the values in the unit compressor configuration table.
TABLE
MST SLV
DISPLAY NAME
MASTER SLAVE CONTROLMaster/Slave Select
Master Control Type
Slave AddressLead Lag Select
Lead/Lag Balance DeltaLag Start TimerLead Pulldown TimeStart if Error HigherLag Minimum Running TimeLag Unit Pump Control
Chiller in Series
RANGE DEFAULT UNITS
0=Disable1=Master2-Slave1-Local Control2-Remote Control3=CCN Control1 to 2360=Always Lead1-Lag Once
Failed Only2-Lead/Lag
Runtime Sec40 to 4002 to 300 to 60
O=Stop if Unit Stops1=Run if Unit StopsYedNo
0
1
20
1681004° AF0 min0
No
hoursminminutes
POINT NAME
ms sel
ms ctrl
slv addrlead sel
II baldIstr timlead pulstartdltlag minilag pump
II serie
106
APPENDIX B -- CON TABLES (cont)
CONFIGURATION TABLES (cont)
TABLE DEFAULT UNITS
USER 0
DISPLAY NAME
Circuit Loading Sequence
Staged Loading SequenceRamp Loading SelectUnit Off to On DelayCondenser Pumps SequenceCooler Pumps Sequence
Pump Auto Rotation Delay*Pump Sticking Protection*Stop Pump During Standby*Flow Checked if C Pump OffAuto Changeover Select*Cooling Reset SelectHeating Reset Select*
Demand Limit Type Select
mA For 100% Demand LimitmA For 0% Demand LimitCurrent Limit SelectCurrent Limit at 100%Heating OAT ThresholdBoiler OAT ThresholdFree Cooling OAT Limit*Elec Stage OAT Threshold*1 Elec Stage for backup*Electrical Pulldown Time*Quick EHS for Defrost*
NIGHT CONTROLStart HourEnd HourCapacity LimitIce Mode EnableReverse Alarms RelayPass For All User Config
RANGE
0-30=Auto,I=A Lead2-B Lead,3 =C LeadNo/YesNo/Yes1-150/1/2/3/40-40=No Pump1=One Pump Only2=Two Pumps Auto3=Pump#1 Manual4=Pump#2 Manual24-3000No/YesNo/YesNo/YesNo/Yes0-40-41 =OAT,0=None2=Delta T,3=4-20mA Control4-Space Temp0-20=None1=Switch Control2=4-20mA Control0-200-20No/Yes0 to 2000-4-325-59-4-37.423-70No/Yes0-60No/Yes
No
No100
48NoNoYesNo00
00No20005143241No0No
Min
hours
mama
ampsoFoFoFoF
minutes
00:00-24:0000:00-24:000-100No/YesNo/YesNo/Yes
POINT NAME
lead cir
NOTES: function shall be ignored. Configuration 3 (4-20mA1. Flow checked if pump off needed when a command is sent to the primary
pump to prevent cooler from freezing in winter conditions. Command willset the cooler flow switch to closed while the controls stop the coolerpump. The controls may then generate an alarm. If this decision is active,the cooler flow switch is not checked when the cooler pump is stopped.
2. If cooling reset select set point has been selected the set point based on4-20mA input signal through ComfortLink TM control, then a 4-20 mA reset
seqtypramp seloff on dhpumpseqpump seq
pump delpump perpump sbypump Iocauto selcr selhrsel
lira sel
lim mxlim zecurr selcurr fulheat thboil thfree oatehsthehs backehs pullehs defr
00:00 nh start00:00 nh end100 % nh cnfgNo ice cnfgNo al rever
No al/pass
Control) and 4 (SpaceTemperature) shall require an Energy Management Module.
3. Configuration 2 (4-20mA Control) shall require an Energy ManagementModule. Configuration 1 Switch Demand limit provides 3 step demand limitif an Energy Management Module is present. Otherwise, only one step isallowed.
4. Reverse Alarms Relay configuration will be deenergized when an alarmand alert relay is present and will be energized when no alarm is present.
107
APPENDIX B -- CCN TABLES (cont)
SETPOINT CONFIGURATION TABLES
TABLE RANGE DEFAULT UNITS POINT NAMESETPOINT
*Not supported.
DISPLAY NAME
COOLING
Cooling Setpoint 1Cooling Setpoint 2Cooling Ice SetpointOAT No Reset ValueOAT Full Reset ValueDelta T No Reset ValueDelta T Full Reset ValueCurrent No Reset ValueCurrent Full Reset ValueSpace T No Reset ValueSpaceT Full Reset ValueCooling Reset Deg. ValueCooling Ramp LoadingHEATING*
Heating Setpoint 1Heating Setpoint 2OAT No Reset ValueOAT Full Reset ValueDelta T No Reset ValueDelta T Full Reset ValueCurrent No Reset ValueCurrent Full Reset Value
Heating Reset Deg. ValueHeating Ramp Loading
AUTO CHANGEOVER*Cool Changeover Setpt
Heat Changeover SetptMISCELLANEOUS
Switch Limit Setpoint 1Switch Limit Setpoint 2Switch Limit Setpoint 3Reclaim Setpoint*Reclaim Deadband*
Water Val Condensing Stp*
-20-70-20-70-20-7014-12514-1250-250-250-200-2014-12514-125-30-300.2-2,0
80-14080-14014-12514-1250-250-250-200-20-30-300.2-2,0
39-12232-115
0-1000-1000-10095-1405-2780to 120
44.044.044.014.014.0O.OO.OO.OO.O14,014.0O.O1.0
100.0100,014.014.0O.OO.OO.OO.OO.O1.0
75.064.0
100100100122.09.086
oFoFoFoFoFAF
AF
mamaoFoFAFAF
oFoFoFoFAFAFmamaAF^F
oFoF
%%%oFoFoF
MAINTENANCE DISPLAY TABLES
cspl;sp2
mespoatcrnooatcr fudtcrnodtcr fuv crnov crfu
spacrnospacr fucr degcramp_sp
hsplhsp2oathr nooathr fudt hr nodt hr fuv hr nov hr fu
hr deghramp_sp
cauto sp
hauto_sp
limspllimsp2limsp3rsphr deadb
w_sct_sp
TABLE
BOARD PN
CUR PHASE
DEFROSTM*
DISPLAY NAME
EXV Board Circuit AEXV Board Circuit BEXV Board Circuit CAUX Board #1 Part NumberAUX Board #2 Part NumberAUX Board #3 Part NumberAUX Board #4 Part NumberAUX Board #5 Part NumberEMM NRCP2 BoardReclaim NRCP2 Board
TCPM Board Comp AMust Trip Amps
$1 Config Switch (8 to 1)TCPM Board Comp B
Must Trip Amps$1 Config Switch (8 to 1)
TCPM Board Comp CMust Trip Amps
S1 Con% Switch (8 to 1)Current Phase 1 Comp ACurrent Phase 2 Comp ACurrent Phase 3 Comp ACurrent Phase 1 Comp BCurrent Phase 2 Comp BCurrent Phase 3 Comp BCurrent Phase 1 Comp CCurrent Phase 2 Comp CCurrent Phase 3 Comp CCIR A DEFROST CONTROLExchanger Frost FactorNext Sequence Allowed inDefrost Active?
Defrost TemperatureDefrost Duration
Fan Sequence Started ?Override StateMean SST CalculationDelta: OAT - Mean SSTReference DeltaDelta - Reference Delta
Frost Integrator GainDefrost Fan Start Cal ADefrost Fan Offset Cal A
*Not supported.
CIR B DEFROST CONTROL
Exchanger Frost FactorNext Sequence Allowed inDefrost Active?Defrost TemperatureDefrost DurationFan Sequence Started?Override StateMean SST calculationDelta: OAT - Mean SSTReference DeltaDelta - Reference DeltaFrost Integrator GainDefrost Fan Start Cal BDefrost Fan Offset Cal B
RANGE
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX0-60000000000nnnn0-60000000000XXXXXXXX0-60000000000
0-6000-6000-6000-6000-6000-6000-6000-6000-600
0-100nnnTrue/False_+nnn.nnnnnnn_+nnn.n_+nnn.n_+nnn.n_+nnn.nn.n0.O00.O0
0-100nnnTrue/False_+nnn.nnnnnnn_+nnn.n_+nnn.n_+nnn.n_+nnn.nn.n0.O00.O0
NOTES: Tables for display onl_ Forcing shall not be supported on this maintenance screen.
ampsO
ampsO
ampsO
ampsampsampsampsampsampsampsampsamps
%minutes
oFminutes
AFoF
ps!psi
%minutes
oFminutes
oF
AFAF
AF
ps!psl
UNITS WRITE STATUSPOINT NAME
exv brdaexv brdbexv brdcaux brdlaux brd2aux brd3aux_brd4aux_brd5emm nrcprec nrcpcpa verscpa mtamcpasl mcpb verscpb mtamcpbsl mcpcverscpc mtam
cpc_sl_mcpacurlcpacur2cpacur3cpbcurlcpbcur2cpbcur3cpccurlcpccur2cpc_cur3
frost adef sea
mode[19]DEFRT Adeft duadef fa aover d asst dmadelt adelt r adel v afr int adef ca adef_of_a
frost bdef se b
mode[2O]DEFRT Bdeft dubdef fa bover d bsst dmbdelt bdelt r bdel v bfr int bdef ca_bdef_of_b
108
APPENDIX B -- CCN TABLES (cont)MAINTENANCE DISPLAYTABLES (cont)
TABLE WRITE STATUS
FANCTRL
LAST POR
LOADFACT
DISPLAY NAME
Cir A SCT Control PointCir A SCT CandidateCirA Fan Cycle CounterCir A Optimal Fan CountCir B SCT Control PointCir B SCT CandidateCir B Fan Cycle CounterCir B Optimal Fan CountCir C SCT Control PointCir C SCT CandidateCir C Fan Cycle CounterCirC Optimal Fan Count
Power On 1: day-men-yearPower On 1: hour-minutePowerDown 1:day-men-yearPowerDown 1:hour-minutePower On 2: day-men-yearPower On 2: hour-minutePowerDown 2:day-men-yearPowerDown 2:hour-minutePower On 3: day-men-yearPower On 3: hour-minutePowerDown 3:day-men-yearPowerDown 3:hour-minutePower On 4: day-men-yearPower On 4: hour-minutePowerDown 4:day-men-yearPowerDown 4:hour-minutePower On 5: day-men-yearPower On 5: hour-minutePowerDown 5:day-men-yearPowerDown 5:hour-minute
CAPACITY CONTROLAverage Ctrl Water TempDifferential Water TempWater Delta TControl PointReset AmountControlled Temp ErrorActual CapacityActual Capacity LimitActual Chiller CurrentChiller Current LimitCurrent At 30% Load ACurrent At 30% Load BCurrent At 30% Load C
RANGE
±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n
nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn
Current At 100% Load ACurrent At 100% Load BCurrent At 100% Load CCurrent Z Multiplier ValLoad/Unload FactorActive Capacity Override
EHS CAPACITY CONTROLEHS Ctrl OverrideRequested Electric StageElectrical Pulldown?
EXV CONTROLEXV Position Circuit ADischarge Superheat ASuction Superheat ASuction SH Control Pt ACooler Exchange DT Cir ACooler Pinch Ctl Point AEXV Override Circuit AEXV Position Circuit BDischarge Superheat BSuction Superheat BSuction SH Control Pt BCooler Exchange DT Cir BCooler Pinch Ctl Point BEXV Override Circuit BEXV Position Circuit CDischarge Superheat CSuction Superheat CSuction SH Control Pt CCooler Exchange DT Cir CCooler Pinch Ctl Point CEXV Override Circuit C
ECONOMIZER CONTROLEconomizer Position AEconomizer Superheat AEconomizer SH Setpoint AEXV Override Circuit AEconomizer Position BEconomizer Superheat BEconomizer SH Setpoint BEXV Override Circuit BEconomizer Position CEconomizer Superheat CEconomizer SH Setpoint CEXV Override Circuit C
±nnn.n±nnn.n±nnn.n±nnn.n±nnn.n±nnn.nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn±n.n±nnn.nnn
UNITS
oFoF
oFoF
oFoF
ddmmyyhhmmddmmyyhhmmddmmyyhhmmddmmyyhhmmddmmyyhhmmddmmyyhhmmddmmyyhhmmddmmyyhhmmddmmyyhhmmddmmyyhhmm
oFoF^FoF^F^F%%lamspampsampsampsampsampsampsamps
0/0
nn over ehsnn eh stageTrue/False ehspulld
EXV CTRLnnn,nnnn,nnn,nnn,nnn,nnn,nnnnnn,nnnn,nnn,nnn,nnn,nnn,nnnnnn,nnnn,nnn,nnn,nnn,nnn,nnn
nnn.nnn,nnn,nnnnnn,nnn,nnn,nnnnnn,nnn,nnn,nnn
%%^F^F^F^F
%%^F^F^F^F
%%^F^F^F^F
%^F^F
%^F^F
%^F^F
POINT NAME
sct spasct fu afancyc afancop asct sp bsct fu bfancyc bfancop bsct sp csct fu cfancyc cfancop c
date on1time on1date of 1time of 1date on2time on2date of 2time of 2date on3time on3date of 3time of 3date on4time on4date of 4time of 4date on5time on5date of 5time of 5
ctrl avgdiff wtdelta tCTRL PNTresettp errorcap tcap limTOT CURRCURR LIMcur 30 acur 30 bcur 30 ccurl00 acurl00 bcurl00 czm
smz
overcap
EXVADSH ASHAsh spa_inch a
pinch spaov exv aEXV BDSH BSH Bshsp b_inch b
pinch spbov exv bEXV CDSH CSH Cshsp c_inch c
pinch spcOV exvc
EXV ECAeco shaecsh spaov eco aEXV EC Beco shbecsh spbov eco bEXV EC Ceco shc
ecsh spcOV eco C
109
APPENDIX B -- CON TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE RANGE UNITS POINT NAME WRITE STATUSMSTSLAVE
DISPLAY NAME
MASTER/SLAVE CONTROLUnit is Master or Slave
Master Control Type*Master/Slave Ctrl ActiveLead Unit is the:Slave Chiller Statet
Slave Chiller Total CapLag Start Delay**Lead/Lag Hours Delta*Lead/Lag Changeover?**Lead Pulldown?Master/Slave ErrorMax Available Capacity?l-tSlave Lagstat
Disable/Master/SlaveLocal/Remote/CCNTrue/FalseMaster/Slave0=Chiller is off1=Valid Run State in
CCN Mode2=Unused for this control3=Chiller is in local mode4=Power fail restart in
progress5=Shudown due to fault6=Communication failure0-1001-30_+nnnnnYes/NoYes/NonnTrue/False
0=Unit not configuredas a slave chiller
1=Slave pumpconfiguration error
ins error=l)2=Un t conf gured as
slave chiller withIwt opt=no (enteringwater control) with
ump controlag pump=0)
3=Unit configured as slavechillerwith Iwt opt=yes
leaving water controlwth pump centre(lag pump=0)
4=Unit Configured as slavechiller with Iwt opt=noentering water control
wth no pump centre(lag pump=l)
5=Unit configured as slavechiller with Iwt opt=yes
leaving water controlwth no pump centre(lag_pump=l)
*Always CCN for the slave chiller.1-Slave chiller chillstat value
**This decision is consistent for Master chiller only. It shall be set by default to 0 for the slave chiller.tl-This item is true when chiller has loaded its total available capacity tonnage.
%minuteshours
mstslvms ctrlms activlead selslv_stat
slv captstrt d
II hr d
II changII pullms error
cap maxlagstat
TABLE WRITE STATUSOCCMAINT
DISPLAY NAME
Current Mode (l=occup.)Current Occp Period #Timed-Override in EffectTimed-Override DurationCurrent Occupied TimeCurrent Unoccupied TimeNext Occupied DayNext Occupied TimeNext Unoccupied DayNext Unoccupied TimePrev Unoccupied DayPrev Unoccupied Time
RANGE
0/11 to8Yes/No0-400:00-23:5900:00-23:59Men-Sun00:00-23:59Men-Sun00:00-23:59Men-Sun00:00-23:59
UNITS
hours
POINT NAME
MODEPER NOOVERLASTOVR HRSSTRTTIMEENDTIMENXTOCDAYNXTOCTIMNXTUNDAYNXTUNTIMPRVUNDAYPRVUNTIM
TABLE DISPLAY NAME
PR LIMIT Discharge A Ternp Average _+nnn.nDischarge A Temp Rate _+nnn.nDischarge A Gas Limit _+nnn.nSuction A Temp Average _+nnn.nDischarge B Temp Average _+nnn.nDischarge B Temp Rate _+nnn.nDischarge B Gas Limit _+nnn.nSuction B Temp Average _+nnn.nDischarge C Temp Average _+nnn.nDischarge C Temp Rate _+nnn.nDischarge C Gas Limit _+nnn.nSuction C Temp Average _+nnn.n
NOTE: Table for display only. Used for Cooling and Heat Pump Compressor Envelope.
RANGE UNITS WRITE STATUS
oFAF
oFoFoFAF
oFoFoFAF
oFoF
POINT NAME
sdt rnasdt mrasdtlim asstmasdt m bsdt mrbsdtlim bsstm bsdt mcsdt mr csdtlimcsst m c
TABLE DISPLAY NAME nn RANGE UNITS POINT NAME forcWRelTE STATUSSERMAINT Reset Maintenance Alert SRESET1 to 11: reset individually12: reset all
OPERATION WARNINGS
1 -- Refrigerant Charge Normal/Low/Disable I charge m I2 -- Water Loop Size Norma/Low/D sab e I w oop_m IGENERAL SERVICING DELAYS3--Cooler Pump 1 (days)* 0-1000/Alert/Disable cpumpl m4 -- Cooler Pump 2 (days)* 0-1000/Alert/Disable cpump2 m
5-- Condenser Pump 1 (days)* 0-1000/Alert hpumpl m6 -- Condenser Pump 2 (days)* 0-1000/Alert hpump2_m7 -- Water Filter (days)* 0-1000/Alert/Disable wfilte m8 -- Cp A Oil Filter (days) 0-1000/Alert oilfa m9 -- Cp B Oil Filter (days) 0-1000/alert oilfilb m
10 -- CRC Oil Filter (days) 0-1000/Alert o c_m
*Not supported.
110
APPENDIX B -- CON TABLES (cont)
SERVICE CONFIGURATION TABLES
TABLE I DISPLAY NAMEm
TABLE USED FOR DISABLE COMPRESSORS
CP UNABL CompressorA DisableCompressor B DisableCompressor C Disable
FACTORY Unit Type
MCHX Exchanger SelectHigh Tiers Display Selec
FACTORY2
I RANGE I DEFAULT I UNITS I POINT NAME I WRITE STATUS
No un cp aNo un cp bNo un cp c
1 unittyp
Unit Capacity ModelNB Fans on Varifan Cir ANB Fans on Varifan Cir BNB Fans on Varifan Cir CSoft Starter SelectWye Delta Start SelectAir Cooled Reclaim SelFree Cooling SelectElectrical Heat Stages*Boiler Command SelectPower Frequence 60HZ SelPower Supply VoltageEnergy Management ModuleCooler heater selectCondenser Water Val Sel*Hot Gas Bypass Select
Factory Password
Compressor A ConfigMust Trip Amps$1 Config Switch (8 to 1)
Compressor B ConfigMust Trip Amps$1 Config Switch (8 to 1)
Compressor C ConfigMust Trip Amps$1 Config Switch (8 to 1)
No/YesNo/YesNo/Yes
1 (Cooling Only),2 (Heat Pump)3 (Water Cooled)4 (Heat Machine)0 to 18000to60to60to6Yes/NoYes/NoYes/NoYes/No0to4Yes/NoYes/No200 to 660Yes/NoYes/NoYes/No0-Hot gas bypassvalve (not used)1-Used for Startuponly2=Close Control3=High Ambient (ifHigh pressure modeis active, close con-trol shall be active)Yes/NoNo - Use Com-fortLink TM display asuser interface (fac-tory installed)Yes = Use HighTiers Display asuser interface (fac-tory installed)0 to 9999
0 to 60000000000 (8 posi-tion dip switch con-figuration)
0 to 60000000000 (8 posi-tion dip switch con-figuration)
0 to 60000000000 (8 posi-tion dip switch con-figuration)
0000NoNoNoNo0NoNovoltNoNoNo0
NoYes
113
00
tons unitsizevarfan avarfan bvarfan csoftstarwye deltrecl optfreecoolehs selboil selfre_60Hvoltageernm nrcpheatselcond valhgbp sel
mchx selhighdisp
fac pass
cpa mtaccpa sl c
cpb mtaccpb sl c
cpc mtaccpc sl c
Circuit A Total Fans NBCircuit B Total Fans NBCircuit C Total Fans NBEXV A Maximum StepsNumbEXV B Maximum StepsNumbEXV C Maximum StepsNumbEconomizer A Steps NumbEconomizer B Steps NumbEconomizer C Steps Numb
2to82to80to80/15000
0/15000
0/15000
0/150000/150000/15000
0000-EXV not used
369036903690
nb fan anb fan bnb fan cexva max
exvb max
exvc max
eco cn_eco cnfbeco cnfc
NOTES: 2. All data will be re-initialized to NO" at Power on reset on units using1. Table used to disable compressors for maintenance purposes. The capac- pro dialog display. For Comfortt_ink TM display, data shall be saved.
ity control will consider that these compressors (once set to YES) are failedmanually (no alarm will appear).
TABLE
MAINTCFG
*Not supported.
DISPLAY NAME
MAINTENANCE CONFIGServicing AlertRefrigerant Charge CtrlWater Loop ControlCPump 1 Ctl Delay (days)*CPump 2 Ctl Delay (days)*HPump 1 Ctrl Delay (days) *HPump 2 Ctrl Delay (days)*Water Filter Ctrl (days)*Oil Filter A Ctrl (days)Oil Filter B Ctrl (days)Oil Filter C Ctrl (days)
RANGE
Enable/DisableEnable/DisableEnable/Disable0-10000-10000-10000-10000-10000to 10000to 10000to 1000
DEFAULT
DisableDisableDisable00000000
UNITS POINT NAME
s alertcharge cwloopccpumplccpump2chpumpl chpump2 cwfilte coilfia coilfib coilfic c
WRITE STATUS
111
APPENDIX B -- CON TABLES (cont)
SERVICE CONFIGURATION TABLES
TABLE DEFAULT WRITE STATUS
SERVICE
DISPLAY NAME
Cooler Fluid TypeBrine Flow Switch SPBrine Freeze SetpointCondenser Fluid TypeEntering Fluid ControlProp PID Gain VarifanInt PID Gain VarifanDeri PID Gain VarifanEXV A Superheat SetpointEXV B Superheat SetpointEXV C Superheat SetpointPinch offset circuit APinch offset circuit BPinch offset circuit CEXV MOP SetpointHigh Pressure ThresholdCooler Heater Delta SptAuto Start When SM LostRecl Valve Min Position*Recl Valve Max Position*Economizer SH Setpoint AEconomizer SH Setpoint BEconomizer SH Setpoint CUser Password
RANGE
1-3 11014
1/2 1Yes/No No-20.0-20,0 2.0-5.0-5,0 0,220.0-20,0 0.45-15 7,25-15 7,25-15 7.2-3.0-3.0 0-3.0-3,0 0-3.0-3,0 040-55 55500-640 6091-6 2Enable/Disable Disable0-50 2020-100 1005-15 7,25-15 7,25-15 7,20-150 11
UNITS
°FAF
^F^F^F^F^F^F°Fpsi^F
%%^F^F^F
POINT NAME
flui typflowspIowestspcond typewt opthd pghd ighd dgsh spash sp bsh sp c)inoff a)inoff b)inoff cmop sphpthheaterspauto smrain 3wmax 3wesh_p aesh sp besh sp cuse pass
*Not supported.
NOTE: This table shall be downloadable at any time. However, modified value shall not be used by tasks until the unit is in OFF state. This shall not apply to the Varifangains that shall be modified at any time and used immediately by the head pressure control tasks even if the unit is in operation.
TABLE I DISPLAY NAME I RANGE I UNITS I POINT NAME I WRITE STATUSTABLE TO BE USED FOR RUN TIMES UPDATE IN CASE OF CONTROL RETROFIT
UPDHRFAN FAN Operating HoursCircuit A Fan #1 HoursCircuit A Fan #2 HoursCircuit A Fan #3 HoursCircuit A Fan #4 HoursCircuit A Fan #5 HoursCircuit A Fan #6 HoursCircuit A Fan #7 HoursCircuit A Fan #8 HoursCircuit A Fan #9 HoursCircuit A Fan #10 HoursCircuit B Fan #1 HoursCircuit B Fan #2 HoursCircuit B Fan #3 HoursCircuit B Fan #4 HoursCircuit B Fan #5 HoursCircuit B Fan #6 HoursCircuit B Fan #7 HoursCircuit B Fan #8 HoursCircuit B Fan #9 HoursCircuit B Fan #10 HoursCircuit C Fan #1 HoursCircuit C Fan #2 HoursCircuit C Fan #3 HoursCircuit C Fan #4 HoursCircuit C Fan #5 HoursCircuit C Fan #6 HoursCircuit C Fan #7 HoursCircuit C Fan #8 HoursCircuit C Fan #9 HoursCircuit C Fan #10 HoursWATER PUMP #1 Hours*WATER PUMP #2 Hours*
nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn
hours hr fanalhours hr fana2hours hr fana3hours hr fana4hours hr fana5hours hr fana6hours hr fana7hours hr fana8hours hr fana9hours hrfanal 0hours hr fanblhours hr fanb2hours hr fanb3hours hr fanb4hours hr fanb5hours hr fanb6hours hr fanb7hours hr fanb8hours hr fanb9hours hrfanbl 0hours hr fanclhours hr fanc2hours hr fanc3hours hr fanc4hours hr fanc5hours hr fanc6hours hr fanc7hours hr fanc8hours hr fanc9hours hrfancl0hours hr cpurnlhours hr cpurn2
*Not supported.
NOTE: This table shall be used for purposes of transplanting the devices on time in the event of a module hardware failure or software upgrade via downloading. It shallbe usable only if all items are still null. Afterwards, its access shall be denied.
TABLE I DISPLAY NAME I RANGE I UNITS I POINT NAME I WRITE STATUSTABLE TO BE USED FOR RUN TIMES UPDATE IN CASE OF CONTROL RETROFIT
UPDTHOUR Machine Operating Hours nnnnnMachine StartsCompressor A HoursCompressor A StartsCompressor B HoursCompressor B StartsCompressor C HoursCompressor C StartsCircuit A Defrost Number*Circuit B Defrost Number*
nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn
hours
hours
hours
hours
hr machst roachhr cp ast cp ahr cp bst cp bhr cp cst cp cnb defanb defb
*Not supported.
NOTE: This table shall be used for purposes of transplanting the devices on time in the event of a module hardware failure or software upgrade via downloading. It shallbe usable only if all items are still null. Afterwards, its access shall be denied.
112
APPENDIX C -- 30XA080-500 CPM DIP SWITCH ADDRESSES
ACROSS-THE-LINE START
30XA VOLTAGE CIRCUIT A CIRCUIT B CIRCUIT C
UNiZ,sp.CPOOlP IIIIIIISIZE 60 Hz) SWITCHES 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
31 DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF575
$2 ON ON ON ON OFF OFF OFF OFF ON ON ON ON DFF OFF OFF OFF
$1 DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF460
$2 OFF ON OFF ON ON OFF OFF OFF OFF ON OFF ON ON OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF080* 380
$2 ON OFF OFF OFF DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF230
$2 DFF OFF OFF ON DFF OFF ON OFF DFF OFF OFF ON DFF OFF ON OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF200
$2 DFF ON OFF OFF ON OFF ON OFF DFF ON OFF OFF ON OFF ON OFF
$1 DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF575
$2 DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF
$1 DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF460
$2 ON ON OFF ON ON OFF OFF OFF ON ON OFF ON ON OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF090 380
$2 ON ON OFF OFF DFF ON OFF OFF ON ON OFF OFF DFF ON OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF230
$2 ON ON OFF ON OFF OFF ON OFF ON ON OFF ON DFF OFF ON OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF2OO
$2 DFF OFF ON OFF ON OFF ON OFF DFF OFF ON OFF ON OFF ON OFF
$1 DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF575
$2 DFF OFF ON OFF ON OFF OFF OFF DFF OFF ON OFF ON OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF460
$2 DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF100 380
$2 ON OFF OFF ON OFF ON OFF OFF ON OFF OFF ON DFF ON OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF230
$2 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF2OO
$2 DFF OFF OFF OFF DFF ON ON OFF DFF OFF OFF OFF DFF ON ON OFF
$1 DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF575
$2 ON OFF ON ON ON OFF OFF OFF DFF OFF ON OFF ON OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF460
$2 DFF OFF ON ON DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF110 380
$2 DFF ON ON OFF ON ON OFF OFF ON OFF OFF ON DFF ON OFF OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF230
$2 DFF ON OFF OFF DFF OFF OFF OFF ON OFF ON OFF ON OFF ON OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF200
$2 DFF OFF OFF ON DFF OFF OFF OFF DFF OFF OFF OFF DFF ON ON OFF
$1 DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF575
$2 ON OFF ON ON ON OFF OFF OFF ON OFF ON ON ON OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF460
$2 DFF OFF ON ON DFF ON OFF OFF DFF OFF ON ON DFF ON OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF120 380
$2 DFF ON ON OFF ON ON OFF OFF DFF ON ON OFF ON ON OFF OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF OFF ON OFF OFF OFF230
$2 DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF OFF ON OFF OFF OFF200
$2 DFF OFF OFF ON DFF OFF OFF OFF DFF OFF OFF ON DFF OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF575
$2 OFF OFF OFF ON ON ON OFF OFF OFF OFF ON OFF ON OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF460
$2 ON ON ON ON DFF OFF ON OFF DFF OFF OFF OFF DFF ON OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF140 380
$2 ON ON ON ON ON OFF ON OFF ON OFF OFF ON DFF ON OFF OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF230
$2 ON OFF ON OFF DFF ON OFF OFF ON OFF ON OFF ON OFF ON OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF200
$2 ON ON ON ON DFF ON OFF OFF DFF OFF OFF OFF DFF ON ON OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF575
$2 DFF OFF ON OFF DFF OFF ON OFF ON OFF ON ON ON OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF460
$2 ON ON ON ON ON OFF ON OFF DFF OFF ON ON DFF ON OFF OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF160 380
$2 DFF OFF ON OFF DFF OFF OFF OFF DFF ON ON OFF ON ON OFF OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF OFF ON OFF OFF OFF230
$2 DFF OFF OFF OFF DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF OFF ON OFF OFF OFF20O
$2 DFF OFF OFF OFF DFF OFF ON OFF DFF OFF OFF ON DFF OFF OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF575
$2 DFF OFF OFF ON ON ON OFF OFF DFF OFF OFF ON ON ON OFF OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF460
$2 ON ON ON ON DFF OFF ON OFF ON ON ON ON DFF OFF ON OFF
$1 DFF ON OFF ON DFF OFF OFF OFF DFF ON OFF ON DFF OFF OFF OFF180 380
$2 ON ON ON ON ON OFF ON OFF ON ON ON ON ON OFF ON OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF OFF ON OFF OFF OFF230
$2 ON OFF ON OFF DFF ON OFF OFF ON OFF ON OFF DFF ON OFF OFF
$1 DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF OFF ON OFF OFF OFF200
$2 ON ON ON ON DFF ON OFF OFF ON ON ON ON DFF ON OFF OFF
MTA MTA MTASETTING SETTING SETTING
CIRCUIT CIRCUIT CIRCUIT
70 70 --
92 92 --
106 106 --
184 184 --
204 204 --
72 72 --
94 94 --
110 110 --
190 190 --
208 208 --
80 80 --
104 104 --
122 122 --
210 210 --
232 232 --
98 80 --
128 104 --
148 122 --
254 210 --
282 232 --
98 98 --
128 128 --
148 148 --
254 254 --
282 282 --
152 80 --
198 104 --
230 122 --
398 210 --
438 232 --
176 98 --
230 128 --
266 148 --
462 254 --
506 282 --
152 152 --
198 198 --
230 230 --
398 398 --
438 438 --
113
APPENDIX C -- 30XA080 500 CPM DIP SWITCH ADDRESSES (cont)
ACROSSTHELINE START (cont)
30XA VOLTAGE CIRCUIT A CIRCUIT B CIRCUIT C MTA MTA MTA
UN,T 3ph, CPM D,P I I I I I I I SETi'NG SETi'NG SETi'NGSIZE 60Hz SWITCHES 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CIR UIT CIR UIT CIR UIT
$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF575 176 176 --
$2 OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF
460 230 230 --$2 ON ON ON ON ON OFF ON OFF ON ON ON ON ON OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
200 380 266 266 --$2 OFF OFF ON OFF OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
230 462 462 --$2 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
200 506 506 --$2 OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF ON OFF$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF
575 210 176 --$2 ON OFF ON OFF ON OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF
460 274 230 --$2 OFF ON ON OFF OFF OFF OFF OFF ON ON ON ON ON OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
220 380 318 266 --$2 ON OFF OFF OFF ON OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
230 550 462 --$2 ON ON OFF ON OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
200 602 506 --$2 OFF OFF OFF ON ON OFF ON OFF OFF OFF OFF OFF OFF OFF ON OFF$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF
575 210 210 --$2 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
460 274 274 --$2 OFF ON ON OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
240 380 318 318 --$2 ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
230 550 550 --$2 ON ON OFF ON OFF OFF ON OFF ON ON OFF ON OFF OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
200 602 602 --$2 OFF OFF OFF ON ON OFF ON OFF OFF OFF OFF ON ON OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF
575 286 176 --$2 ON OFF OFF ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF
260 460 374 230 --$2 ON ON ON ON ON OFF OFF OFF ON ON ON ON ON OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
380 434 266 --$2 OFF ON ON ON OFF ON OFF OFF OFF OFF ON OFF OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF
575 286 210 --$2 ON OFF OFF ON OFF OFF OFF OFF ON OFF ON OFF ON OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
280 460 374 274 --$2 ON ON ON ON ON OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
380 434 318 --$2 OFF ON ON ON OFF ON OFF OFF ON OFF OFF OFF ON OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF
575 338 210 --$2 OFF ON ON OFF ON OFF OFF OFF ON OFF ON OFF ON OFF ON OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
300 460 446 274 --$2 ON OFF OFF OFF ON ON OFF OFF OFF ON ON OFF OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
380 514 318 --$2 OFF ON OFF OFF OFF OFF ON OFF ON OFF OFF OFF ON OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
575 286 286 --$2 ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
325 460 374 374 --$2 ON ON ON ON ON OFF OFF OFF ON ON ON ON ON OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
380 434 434 --$2 OFF ON ON ON OFF ON OFF OFF OFF ON ON ON OFF ON OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
575 338 286 --$2 OFF ON ON OFF ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
350 460 446 374 --$2 ON OFF OFF OFF ON ON OFF OFF ON ON ON ON ON OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
380 514 434 --$2 OFF ON OFF OFF OFF OFF ON OFF OFF ON ON ON OFF ON OFF OFF$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
575 210 210 286$2 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF OFF ON OFF OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
400 460 274 274 374$2 OFF ON ON OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF ON ON ON ON ON OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
380 318 318 434$2 ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF OFF ON ON ON OFF ON OFF OFF$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
575 338 152 338$2 OFF OFF OFF ON ON ON OFF OFF OFF ON ON OFF ON OFF OFF OFF OFF ON ON OFF ON OFF OFF OFF$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
450 460 446 198 446$2 ON ON ON ON OFF OFF ON OFF ON OFF OFF OFF ON ON OFF OFF ON OFF OFF OFF ON ON OFF OFF$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
380 514 230 514$2 ON ON ON ON ON OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF$1 OFF ON OFF ON OFF OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
575 338 210 338$2 ON OFF ON OFF ON OFF ON OFF OFF ON ON OFF ON OFF OFF OFF OFF ON ON OFF ON OFF OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
500 460 446 274 446$2 OFF ON ON OFF OFF OFF OFF OFF ON OFF OFF OFF ON ON OFF OFF ON OFF OFF OFF ON ON OFF OFF$1 OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF
380 514 318 514$2 ON OFF OFF OFF ON OFF OFF OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF
LEGEND
CPM -- Compressor Protection ModuleMTA -- MustTdpAmps
*The 30XA080 unit does not have an additional economizer.
114
APPENDIX C -- 30XA080-500 CPM DIP SWITCH ADDRESSES (cont)
WYE DELTA START
30XA VOLTAGE CPM DIPUNIT 3 Ph,SIZE 60 Hz 3WITCH ES
$1575
$2$1
400$2$1
080* 380$231
230$231
200$231
575$231
460$231
090 380$231
23O$231
2O0$231
575$231
460$231
100 380$2$1
23O$2$1
200$2$1
575$2$1
460$2$1
110 380$2$1
23O$2$1
200$2S1
575$2$1
460$2$1
120 380$2$1
23O$2$1
200$2$1
575$2$1
460$2$1
140 380$2$1
23O$2$1
200$2$1
575$2$1
400$2$1
160 380$2$1
230$2$1
200$2$1
575$2$1
400$2$1
180 380$2$1
230$2$1
200$2
CIRCUIT A CIRCUIT B CIRCUIT C MTA MTA MTA
I I I I I I I EWq'N°q'RG1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CIR UIT CIR UIT CIR UIT
ON ON OFF OFF DFF OFF OFF OFF ON ON OFF OFF DFF OFF OFF OFF70 70 --
ON ON ON ON DFF OFF OFF OFF ON ON ON ON DFF OFF OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
92 92 --DFF ON OFF ON ON OFF OFF OFF DFF ON OFF ON ON OFF OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
106 106 --ON OFF OFF OFF DFF ON OFF OFF ON OFF OFF OFF DFF ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
184 184 --DFF OFF OFF ON DFF OFF ON OFF DFF OFF OFF ON DFF OFF ON OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
2_ 204 --DFF ON OFF OFF ON OFF ON OFF DFF ON OFF OFF ON OFF ON OFFON ON OFF OFF DFF OFF OFF OFF ON ON OFF OFF DFF OFF OFF OFF
72 72 --DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
94 94 --ON ON OFF ON ON OFF OFF OFF ON ON OFF ON ON OFF OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
110 110 --ON ON OFF OFF DFF ON OFF OFF ON ON OFF OFF DFF ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
190 190 --ON ON OFF ON DFF OFF ON OFF ON ON OFF ON DFF OFF ON OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
208 208 --DFF OFF ON OFF ON OFF ON OFF DFF OFF ON OFF ON OFF ON OFFON ON OFF OFF DFF OFF OFF OFF ON ON OFF OFF DFF OFF OFF OFF
80 80 --DFF OFF ON OFF ON OFF OFF OFF DFF OFF ON OFF ON OFF OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
1_ 104 --DFF OFF OFF OFF DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
122 122 --ON OFF OFF ON DFF ON OFF OFF ON OFF OFF ON DFF ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
210 210 --ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
232 232 --DFF OFF OFF OFF DFF ON ON OFF DFF OFF OFF OFF DFF ON ON OFFON ON OFF OFF DFF OFF OFF OFF ON ON OFF OFF DFF OFF OFF OFF
98 80 --ON OFF ON ON ON OFF OFF OFF DFF OFF ON OFF ON OFF OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
128 104 --DFF OFF ON ON DFF ON OFF OFF DFF OFF OFF OFF DFF ON OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
148 122 --DFF ON ON OFF ON ON OFF OFF ON OFF OFF ON DFF ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
254 210 --ON ON OFF ON DFF ON ON OFF ON OFF ON OFF ON OFF ON OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
282 232 --ON OFF OFF ON ON ON ON OFF DFF OFF OFF OFF DFF ON ON OFFON ON OFF OFF DFF OFF OFF OFF ON ON OFF OFF DFF OFF OFF OFF
98 98 --ON OFF ON ON ON OFF OFF OFF ON OFF ON ON ON OFF OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
128 128 --DFF OFF ON ON DFF ON OFF OFF DFF OFF ON ON DFF ON OFF OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
148 148 --DFF ON ON OFF ON ON OFF OFF DFF ON ON OFF ON ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
254 254 --ON ON OFF ON DFF ON ON OFF ON ON OFF ON DFF ON ON OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
282 282 --ON OFF OFF ON ON ON ON OFF ON OFF OFF ON ON ON ON OFFON OFF OFF OFF DFF OFF OFF OFF ON ON OFF OFF DFF OFF OFF OFF
152 80 --DFF OFF OFF ON ON ON OFF OFF DFF OFF ON OFF ON OFF OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
198 104 --ON ON ON ON DFF OFF ON OFF DFF OFF OFF OFF DFF ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
230 122 --ON ON ON ON ON OFF ON OFF ON OFF OFF ON DFF ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
398 210 --ON ON OFF OFF ON ON OFF ON ON OFF ON OFF ON OFF ON OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
438 232 --ON ON ON ON DFF ON OFF OFF DFF OFF OFF OFF DFF ON ON OFFON OFF OFF ON DFF OFF OFF OFF ON ON OFF OFF DFF OFF OFF OFF
176 98 --DFF OFF ON OFF DFF OFF ON OFF ON OFF ON ON ON OFF OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
230 128 --ON ON ON ON ON OFF ON OFF DFF OFF ON ON DFF ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
266 148 --ON OFF OFF OFF ON ON ON OFF DFF ON ON OFF ON ON OFF OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
462 254 --ON OFF ON OFF ON ON OFF OFF ON ON OFF ON DFF ON ON OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
506 282 --OFF OFF OFF OFF OFF OFF ON OFF ON OFF OFF ON ON ON ON OFFON OFF OFF OFF DFF OFF OFF OFF ON OFF OFF OFF DFF OFF OFF OFF
152 152 --DFF OFF OFF ON ON ON OFF OFF DFF OFF OFF ON ON ON OFF OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
198 198 --ON ON ON ON DFF OFF ON OFF ON ON ON ON DFF OFF ON OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
230 230 --ON ON ON ON ON OFF ON OFF ON ON ON ON ON OFF ON OFFON OFF OFF ON DFF OFF OFF OFF ON OFF OFF ON DFF OFF OFF OFF
398 398 --ON ON OFF OFF ON ON OFF ON ON ON OFF OFF ON ON OFF ONON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
438 438 --ON ON ON ON DFF ON OFF OFF ON ON ON ON DFF ON OFF OFF
LEGEND
CPM -- Conlp_ssor P_tection ModuleMTA -- Must TdpAmps
*The 30XA080 unit does not have an additional economizer.
115
APPENDIX C -- 30XA080-500 CPM DIP SWITCH ADDRESSES (cont)
WYE DELTA START (cont)
30XA VOLTAGE
UNIT 3 Ph_SIZE 60 Hz
575
46O
200 380
23O
200
575
460
220 380
230
200
575
460
240 380
230
200
575
260 460
380
575
280 460
380
575
300 460
380
575
325 460
380
575
350 460
380
575
400 460
38O
575
450 460
38O
575
500 460
380
CPM DIPSWITCHES
$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2$1
$2
CIRCUIT A CIRCUIT B CIRCUIT C MTA MTA MTA
IIIIIII s ETilNG SETiING SETilNG1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CIR UIT CIR UIT CIR UIT
ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF176 176 --
OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
230 230 --ON ON ON ON ON OFF ON OFF ON ON ON ON ON OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
266 266 --ON OFF OFF OFF ON ON ON OFF ON OFF OFF OFF ON ON ON OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
462 462 --ON OFF ON OFF ON ON OFF OFF ON OFF ON OFF ON ON OFF OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
506 506 --OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
210 176 --ON OFF ON OFF ON OFF ON OFF OFF OFF ON OFF OFF OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
274 230 --ON OFF ON OFF ON ON ON OFF ON ON ON ON ON OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
318 266 --ON ON OFF ON OFF OFF OFF ON ON OFF OFF OFF ON ON ON OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
550 462 --ON ON OFF ON OFF OFF ON OFF ON OFF ON OFF ON ON OFF OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
602 506 --OFF OFF OFF ON ON OFF ON OFF OFF OFF OFF OFF OFF OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
210 210 --ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
274 274 --ON OFF ON OFF ON ON ON OFF ON OFF ON OFF ON ON ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
318 318 --ON ON OFF ON OFF OFF OFF ON ON ON OFF ON OFF OFF OFF ONON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
550 550 --ON ON OFF ON OFF OFF ON OFF ON ON OFF ON OFF OFF ON OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
602 602 --OFF OFF OFF ON ON OFF ON OFF OFF OFF OFF ON ON OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
286 176 --ON ON OFF ON ON ON ON OFF OFF OFF ON OFF OFF OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
374 230 --ON ON ON OFF OFF ON OFF ON ON ON ON ON ON OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
434 266 --ON OFF ON OFF OFF OFF ON ON ON OFF OFF OFF ON ON ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
286 210 --ON ON OFF ON ON ON ON OFF ON OFF ON OFF ON OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
374 274 --ON ON ON OFF OFF ON OFF ON ON OFF ON OFF ON ON ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
434 318 --ON OFF ON OFF OFF OFF ON ON ON ON OFF ON OFF OFF OFF ONON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
338 210 --ON OFF ON OFF ON OFF OFF ON ON OFF ON OFF ON OFF ON OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
446 274 --ON OFF OFF OFF ON ON OFF OFF ON OFF ON OFF ON ON ON OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
514 318 --OFF ON OFF OFF OFF OFF ON OFF ON ON OFF ON OFF OFF OFF ONON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
286 286 --ON ON OFF ON ON ON ON OFF ON ON OFF ON ON ON ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
374 374 --ON ON ON OFF OFF ON OFF ON ON ON ON OFF OFF ON OFF ONON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
434 434 --ON OFF ON OFF OFF OFF ON ON ON OFF ON OFF OFF OFF ON ONON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
338 286 --ON OFF ON OFF ON OFF OFF ON ON ON OFF ON ON ON ON OFFON OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
446 374 --ON OFF OFF OFF ON ON OFF OFF ON ON ON OFF OFF ON OFF ONON OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
514 434 --OFF ON OFF OFF OFF OFF ON OFF ON OFF ON OFF OFF OFF ON ONON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
210 210 286ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON ON OFF ON ON ON ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
274 274 374ON OFF ON OFF ON ON ON OFF ON OFF ON OFF ON ON ON OFF ON ON ON OFF OFF ON OFF ONON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
318 318 434ON ON OFF ON OFF OFF OFF ON ON ON OFF ON OFF OFF OFF ON ON OFF ON OFF OFF OFF ON ONON OFF OFF OFF OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
152 338 338OFF OFF OFF ON ON ON OFF OFF ON OFF ON OFF ON OFF OFF ON ON OFF ON OFF ON OFF OFF ONON OFF OFF ON OFF OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
198 446 446ON ON ON ON OFF OFF ON OFF ON OFF OFF OFF ON ON OFF OFF ON OFF OFF OFF ON ON OFF OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
230 514 514ON ON ON ON ON OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF
210 338 338ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF OFF ON ON OFF ON OFF ON OFF OFF ONON OFF OFF ON OFF OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
274 446 446ON OFF ON OFF ON ON ON OFF ON OFF OFF OFF ON ON OFF OFF ON OFF OFF OFF ON ON OFF OFFON OFF OFF ON OFF OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF
318 514 514ON ON OFF ON OFF OFF OFF ON OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF
LEGEND
CPM -- Compressor Protection ModuleMTA -- MustTdpAmps
*The 30XA080 unit does not have an additional economizer.
116
Liquid LineService Valve
Filter Drier
Economizer EXV
SightglassDry Eye
Econo. Serv. _ ('_Valve v(SSV
Option)
Condenser Fans
Condenser Coil
©
Economizer
EXV
Sightglaee_ Flow
Dry Eye I
©Relief Valve
Suction Service Valve (Option)
Minimum LoadControl Valve
(Option)
Cooler Heater
(option)2
Condenser Fans
Oil Filter
(_) (_)Econo. Serv.
Valve(SSV
Option)
®Relief Valve
K_
Suction Service Valve (Option)
Cooler Heater
(option)
LEGEND
Refrigerant Access Fitting
High Flow Shrader Valve
Refrigerant Access FittingSSV -- Suction Service Valve
l Device Connection1 -- Suction Pressure2 -- Discharge Pressure
Liquid Line 3 -- Economizer PressureService Valve 4 -- Oil Pressure
5 -- High Pressure Switch6 -- Discharge Gas Thermistor7 -- Entering Water Thermistor
Filter Drier 8 -- Leaving Water Thermistor9 -- Return Gas Thermistor
10 -- Economizer Gas Thermistor11 -- OutsideAirThermistor
Economizer EXV
SightglassDry Eye
Economizer
EXV
SightglassDry Eye
APPENDIX D -- PIPING AND INSTRUMENTATION
Actual start-up 42Alarms and alerts 67
Alarm codes 68-72Alarm descriptors 72-_'_2
Capacity control 16Capacity control overrides 20Compressor stages and circuit cycling 16Compressor starts and run hours 16
CCNCon{fi*rtLinkTM CCN communication
wiring 15Interface 15
CCN control 29CCN global schedule 29CCN tables 101-112Condenser coils
Cleaning E-coated coils 64Condenser fans 65Configuration set point limits 30Control methods 29
CCN control 29CCN global schedule 29Switch control 29Time schedule 29Unit run status 30
Controls 4-41Board addresses 14Capacity control 16Carrier Comfort Network@ interface 15(km{#,rtLink display menu structure 4Configuring the master chiller 17Configuring the slave chiller 18Control methods 29Control module communication 14Demand limit .;2Dual chiller control 15Electronic expansion valve (EXV) Board 9Emergency on/off switch 13Enable-off-remote contact switch 13Energy management module (EMM) 13,14
inputs and outputs 14EXV board inputs and outputs 10Fan board A outputs 12Fan board C inputs and outputs 13Fan board X outputs 12Fan boards 11Local equipment network 14Low ambient temperature head pressure
control 22Machine control 29Main Base Bo:trd 4Main Base Board inputs and outputs 5Navigator TM module 3Ramp loading 15Remote alarm and alert relays 40Temperature reset 31
Cooler heat boltsTightening 63
Cooler protection 66Chilled water flow switch 64Freeze protection 62Loss of fluid flow protection 62Low fluid temperature 62Plug components 63Tightening cooler heat bolts 63Tube plugging 62
INDEX
Cooling set point selection SO4 to 20mA input 30Configuration set point limits 30
Control methods and cooling set pointstable, 30
Dual switch 30Ice mode 30
Set point 1 30Set point 2 30Set point occupancy 30
Denmnd limit $2
2-step switch controlled 322-step switch controlled configuration
table 39CCN loadshed controlled 40
Demand limit signal 41Externally powered 40Externally powered den]and limit
configuration table 40
Electronic expansion valve 56Cutaway view of 57Filter drier 59
Inspecting/opening .58
Installing motor .5;_Liquid line service valve 59Moisture liquid indicator .5_'_Troubleshooting procedure 57
Freeze protection 62Head pressure control. See low ambient
temperature head pressure controlLoss of fluid flow protection 62
Low ambient head pressure control 22Fan Staging 23, 24Operating instructions 22
Low fluid temperature 62Machine control 29Maintenance 66Minimum and nmximum cooler flow rotes 43
Minimum fluid loop volume 42Navigator display
Con_fl,rtLink alarms mode 4, 100O*mfl*rtLink configuration mode 4, 9.5,96
Comfl*rtLink inputs mode 4, 93()m_fl*rtLink operating mode 4, 100Comfl*rtLink outputs mode 4, 94C>n_ibrtLink pressure mode 4, 91
Cbn_fl*rtLink rnn status mode 4, 8Z &_¢O,mfl,rtLink service test mode 4, 82, 89()m_fl*rtLink set points mode 4, 92O*mfl*rtLink temperature mode 4, 90
Om_tortLink time clock mode 4, 97-99Navigator module 3
Adjusting the backlight brightness 3Adjusting the contrast 3
Co11_fi,rtLink display menu structure 4Operating linfitations 42
Flow rote requirements 42Minimum and nmximum cooler
flow rates 43
Minimum fluid loop volume 42Voltage 42
Plug components 63Recommended maintenance schedule 66
Every 12 months (.¢_Every 3 months (.¢_Monthly 66Routine 66
Refrigerant circuit 65Refrigerant feed components
Electronic expansion valve 56Relief devices 66
Safety considerations 2Safety devices 66
Compressor protection 66Service 56-r'.¢_
Coil maintenance and cleaning 64Compressors 59Condenser fans 65
Cooler protection 61Electronic expansion valve (EXV) 56Refrigerant circuit 65Relief devices 66
Safety devices 66Start-up 42-48
Actual start-up 42Operating limitations 42
Pre-start-up 41System check 41
Start-up and operation. See Start-up ChecklistStart-up checklist CL- I m C1-8Switch control 29
System check 41Temperature linfits
Low ambient operation 22
Temperature reset 314to 20mA temperature reset 364 to 20mA temperature reset configuration
table 38
Chilled water tempemturecontrol 34Outdoor air temperature reset 34Outdoor air temperature reset configuration
table 35
Return water reset configuration 33Space ten]perature reset 36
Space ten]perature reset configuration $7Thermistors .52
Compressor return gas temperature 52Cooler entering fluid sensor .52Cooler leaving fluid sensor .52Dual chiller LWT 53
Outdoor air temperature 52Remote space temperature .52Typical space temperature sensor
wiring 53Time schedule 29
Transducers 53, .5.5Troubleshooting 66-86
Service test 82
Tube plugging 62
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 533-00069 Printed in U.S.A. Form 30XA-1T Pg 118 12-05 Replaces: New
START-UP CHECKLIST FOR 30XA LIQUID CHILLERS
A. PROJECT INFORMATION
Job Nante Installing ContractorAd&'ess Sales Office
City State Zip Start-up Perfonned By
Design Information
Cooler
Unit
Model
CompressorsContpressor A
Model
Compressor BModel
Compressor CModel
Cooler
} 0APA0'T FL0'0T PEt FLOWOA'ESerkd
AMBIENT
Serkd
Seri_d
Seri_d
Model Serkd
B. PRELIMINARY EQUIPMENT CHECK (This section to be completed by installing contractor)
I. Is there any physical datnage? [] Yes [] No
Will this prevent start-up? [] Yes [] No
Description
2. Unit is installed level as pet the installation instructions.
3. Power supply agrees with the unit nameplate.4. Correct control voltage vac.
5. Electric_fl power wiring is installed properly.
6. Unit is properly grounded.7. Electric_fl circuit protection has been sized and installed properly.
8. All termimds are tight.
9. All plug assemblies are tight.10. All cables, thermistors and ttansducers have been inspected for cross wires.
11. All thermistot:s are fully inserted into wells.
12. Oil separator heaters energized for 24 hours befote start-up.13. Relief valve vent piping per local codes.
Chilled Water System Check
1. All chilled water valves ate open.
2. All piping is connected properly.
3. All air has been purged from the system.4. Chilled water pump is operating with the correct rotation.
5. Chilled water pump stmter interlocked wiflt chillet:
6. Chilled water flow switch operatiomfl.7. Inlet piping to cooler includes a 20 mesh strainer
8. Water loop volume greater than 3 gal/ton for air conditioningor 6 gal/ton for process cooling and low ambient operation.
9. Proper loop freeze protection provided to __ °F (°C).
Antifreeze type Concentration %.(If antifreeze solution is not utilized on 30XA machines and theminimum outdoor ambient is below 32 F (0 ° C) then items 10 and 11have to be completed to provide cooler freeze protection to -20 ERefer to Installation Instructions for proper cooler winterization procedure.)
10. Outdoor piping wrapped with electric heater tape.
11. Cooler heatet:s inst_flled and opemtion_d.
12. Is file Unit equipped with low ambient head pressure control?a. If yes, are wind baffles installed'?
Book
_b
[] Yes [] No
[] Yes [] No[] Yes [] No
[] Yes [] No
[] Yes [] No[] Yes [] No
[] Yes [] No
[] Yes [] No[] Yes [] No
[] Yes [] No
[] Yes [] No[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No[] Yes [] No
[] Yes [] No
[] Yes [] No[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No[] Yes [] No
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
5_c Catalog No, 533-00069 Printed in U.S,A, Form 30XA-1T Pg CL-1 12-05 Replaces: New
C. UNIT START-UP
I. All liquid line service v_dves are open.
2. Velil_ actuated ball valve (ABV) operation.
3. All suction service valves are open.
4. Economizer service valves open.
5. Oil service v_dves open.
6. Leak check unit. Ix_cate, repair and report any refi'igerant leaks.
7. Voltage fit terminal block is within unit nmneplate range.
Check voltage imbalance: A-B A-C B-C
Avelage voltage = (A-B + A-C + B-C)/3Maximum deviation from average voltage = __Voltage imbalance = % (max. deviation / average voltage) X 100
Is voltage imbalance less than 2%.
(DO NOT st_ut chiller if voltage imb_dance is greater than 2%.Contact local utility for assistance.)
8. Veri_ coolerflow rote
Pressure entering cooler
Pressure leaving cooler
Cooler pressure drop
Psig x 2.31 ft./psi =
Kpa x 0.334 m/psi =
Cooler flow rate
__ psig
__ psig
__ psigft of water
mm of water
__ gpm (l/s) (See Cooler Pressure Drop Curve)
Start and operate machine
I. Complete colnponent test utilizing Quick Test Mode (Service Test--)Quie)
2. Check refrigerant and oil chm'ge. Record charge information.
3. Record compressor and condenser fan motor current.
4. Record operating data.
5. Provide operating instructions to owner's personnel.
Circuit A Circuit B
Refrigerant Charge
Additional chm'ge required
Oil Charge
Additional charge required
[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No
[] Yes [] No
Circuit C
Record Software Versions
MODE -- RUN STATUS
SUB-MODEVERS t APPLITEM t DISPLAY + CSA-SR-ITEM EXPANSION
(Press ENTER & ESCAPE simultaneously to obt_dn software versions)
CL-2
kU
zm
ku
C3
(9Z
o,<
o
kUzm
C3kU
(9Z
o,<
o
Record Configuration Information
MODE -- CONFIGURATION
SUB-MODE ITEM ITEM EXPANSION
DISP TEST Test Display LED's
METR Metric Display
LANG Language
UNIT TYPE Unit TypeTONS Unit Size
VAR.A NB Fans on Varifan Cir A
SERV
VAR.B NB Fans on Varifan Cir B
VAR.C NB Fans on Varifan Cir C
VOLT Power Supply Voltage
60HZ 60HZ frequencySTAR Soft Starter Select
Y.D Wye Delta Start Select
MTA.A Must Trip Amps cir A
R.MT.A Read Must Trip Amps A
MTA.B Must Trip Amps cir B
R.MT.B Read Must Trip Amps B
MTA.C Must Trip Amps cir C
RMT.C Read Must Trip Amps C
C.SW.A $1 Config switch cir A
R.CS.A Read $1 Config switch A
C.SW.B $1 Config switch cir B
R.CS.B Read $1 Config switch B
C.SW.C $1 Config switch cir C
R.CS.C Read $1 Config switch CRECL Heat Reclaim Select
EHS Electrical Heater StageEMM EMM module installed
PAS.E Password Enable
PASS Factory Password
CO.HT Cooler Heater Select
CON.V Condenser Valve Select
FREE Free cooling Select
HGBP Hot Gas Bypass Select
MCHX MCHX Exchanger Select
HI.TI High Tiers display Selec
FLUD Cooler Fluid Type
CFLU Condenser Fluid Type
MOP EXV MOP Setpoint
HRTH High Pressure Threshold
SHRA Cir A Superheat Setp
SHRB Cir B Superheat Setp
SHRC Cir C Superheat Setp
HTR Cooler Heater DT Setp
EWTO Entering water controlAU.SM Auto Start when SM lost
LOSP Brine Freeze Setpoint
FL.SP Brine Flow Switch Setp
HD.PG Varifan Proportion GainHD.DG Varifan Derivative Gain
HD.IG Varifan Integral GainHR.MI Reclaim Water Valve Min
HR.MA Reclaim Water Valve Max
DISPLAY
ON/OFF
US-METR
X
X
XXX
0-6
0-6
0-6
XXX
NO-YES
NO-YES
NO-YES
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
NO-YES
0-4
NO-YES
ENBL/DSBL
XXX
NO-YES
NO-YES
NO-YES
NO-YES
NO-YES
NO-YES
WATER-BRINE
WATER-BRINE
XX.X
XXX.X
XX.X
XX.X
XX.X
XX.X
NO-YES
NO-YES
XX.X
XX.X
XX.X
XX.X
XX.X
XXX.X
XXX.X
DEFAULT
OFF
US
EnglishAir-Cooled
0: No low ambient
temperature head)ressure control1:low ambient
temperature head)ressure controlinstalled
0: No low ambienttemperature head)ressure control1: low ambienttemperature head)ressure controlinstalled
0: No low ambienttemperature head)ressure control1: low ambienttemperature head)ressure controlinstalled
YES
NO
NO*
0*
NO
ENBL
0111
YES
NO*
NO*
NO
NO
NO
WATER
WATER
55
290
21.6
21.6
21.6
2.0Number of
degrees addedto brine freezeset point to enablecooler heater.)
NO
NO
14
55*
2.0
0.4
0.2
20*
100"
*Not supported.
ENTRY
ON/OFF
US/METR
Air-Cooled
YES
NO/YES
NO/YES
NO
0
NO/YES
ENBL/DSBL
YES
NO
NO/YES
NO/YES
NO/YES
YES/NO
WATER/BRINE
WATER/BRINE
55 F
21.6 F
21.6 F
21,6 F
2F
NO/YES
NO/YES
55*
2.0
0.4
0.2
2O%
100%
CL-3
MODE -- CONFIGURATION (cont)
SUB-MODE ITEM ITEM EXPANSION DISPLAY DEFAULT ENTRYOPTN CCNA CCN ADDRESS XXX 1
CCNB CCN BUS NUMBER XXX 0
BAUD CCN BAUD RATE X 3
LOAD Loading Sequence Select X EQUAL [] Equal [] Staged
LLCS Lead/Lag Circuit Select X AUTOMATIC
RL, S Ramp Load Select ENBL-DSBL DSBL [] Enable [] DisableDELY Minutes Off Time XX 1 1 min
ICE.M Ice Mode Enable ENBL-DSBL DSBL [] Enable [] Disable
HPUM Condenser Pumps Sequence* X 0
PUMP Cooler Pumps Sequence* X 0 0/1/2/3/4
ROT.P Pump Rotation delay* XX 48 48 Hours
PMPS Periodic Pump Start* NO-YES NO NO
PSBY Stop Pump In Standby* NO-YES NO NO
RLOC Flow checked if Pmp Off NO-YES NO YES
LS.ST Night Low Noise Start XX.XX 00.00 00:00
LS.ND Night Low noise End XX.XX 00.00 00:00
LS.LT Low noise Capacity Lim XXX 100 100%
RV.AL Reverse Alarms Relay NO-YES NO/YESOATH Heat Mode OAT Threshold* XX.X 5 F 5 F
FREE Free Cooling OAT Limit* XX.X 32.0 32 FCUR.S Current Limit Select NO-YES NO NOCUR,F Current Limit at 100% XXXX 2000
EHST Elec Stag OAT Threshold* XX.XX 41 41F
EHSB Last Heat Elec Backup* NO-YES NO NOE,DEF Quick EHS in Defrost* NO-YES NO NO
EHSP Elec Heating pulldown* XX 0 0 min
AUTO Auto Changeover Select* NO-YES NO NO
RSET CRST Cooling Reset Type X 0 [] NO RESET[] OUT AIR TEMP[] DELTA T TEMP[] 4-20mA INPUT[] SPACE TEMP
HRST Heating Reset Type* X 0 0Demand Limit Select [] NONE
DMDC X 0 [] SWITCH[] 4-20mA INPUT
DMMX mA for 100% demand lim XX.X 0.0 0 mA
DMZE mA for 0% demand limit XX.X 0.0 10 mA
MSSL Master/Slave Select X 0 0SLVA Slave Address XXX 2 2
LLBL Lead/Lag Balance Select X DSBL [] Enable [] Disable
LLBD Lead/Lag Balance Delta XXX 168 168 Hours
LLDY Lag Start Delay XX 10 10 min
LEER Start If Error Higher XX.X 4 F
LAGM Lag Minimum Running Tim XXX 0 min
LAGP Lag Unit Pump Select X 0 0LPUL Lead Pulldewn Time XX 0 0 min
SERI Chillers in series NO-YES NO/YES
*Not supported.
CL-4
U3
zu
c_U3
c_
z
q<I-
o
LUzu
C3LUI--
£3
Z
o,<I-
o
SUB-MODE
COOL
MODE -- SETPOINT
ENTRYITEM
CSR1
CSR2
CSR3
CRV1
CRV2
CRT1
CRT2
CRO1
CRO2
CRSl
CRS2
DGRC
CAUT
CRMP
HSR1
HSR2
HRVl
HRV2
HRT1
HRT2
HRO1
HRO2
DGRH
HAUT
HRMP
DLSl
DLS2
DLS3
W.SCT
RSP
RDB
ITEM EXPANSION
Cooling Setpoint 1Cooling Setpoint 2
Ice SetpointCurrent no Reset Val
Current Full Reset Val
Delta T No Reset Temp
Delta T Full Reset Temp
OAT No Reset Temp
OAT Full Reset Temp
Space T No Reset TempSpace T Full Reset Temp
Degrees Cool Reset
Cool Changeover Setpt*
Cool Ramp Loading
Heating Setpoint 1"
Heating Setpoint 2*Current No Reset Val*
Current Full Reset Val*
Delta T No Reset Temp*
Delta T Full Reset Temp*
OAT T No Reset Temp*OAT Full Reset Temp*
Degrees Heat Reset*
Heat Changeover Setpt*
Heat Ramp Loading*
Switch Limit Setpoint 1Switch Limit Setpoint 2
Switch Limit Setpoint 3
Water Val Condensing Stp
Head Reclaim Setpoint*
Reclaim deadband*
DISPLAY
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XX.X
XXX.X
X.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XX.X
XX.X
X.X
XXX
XXX
XXX
XXX.X
XXX.X
XXX.X
DEFAULT
44.0
44.0
44.0
0
0
0
0
14.0
14.0
14.0
14.0
0
75
1.0
100.0
100.0
0
0
0
0
14.0
14.0
0
64.0
1.0
100
100
100
122
9.0
HEAT
MISC
*Not supported.
MODE -- OPERATING MODE
SUB-MODE ITEM ITEM EXPANSION DISPLAY DEFAULT ENTRY
SLCT OPER Operating Control Type X -- [] SWITCH CTRL[] TIME SCHED[] CCN CONTROL
SRSE Setpoint Select X -- [] SETPOINTOCC[] SETPOINT1[] SETPOINT2
HC.SE Heat Cool Select* X COOLING COOLING
RLSE Reclaim Select* X NO NO
*Not supported.
CL-5
Component Test -- Complete the following tests to make sure all peripheral components areoperational before the compressors are started.
MODE -- SERVICE TEST
To Enable Service Test Mode, move Enable/Off/Remote Contact Switch to OFF.Configure TEST to ON. Move Switch to ENABLE.
SUB-MODE ITEM ITEM EXPANSION
TEST* T.REQ Manual Sequence
CRA Compressor A Output
SLI.A Slide Valve Capacity A
CRB Compressor B Output
SLI.B Slide Valve Capacity B
CRC Compressor C Output
SLI.C Slide Valve Capacity CQUICt Q.REQ QUICK TEST MODE
EXV.A Circuit A EXV % Open
EXV.B Circuit B EXV % Open
EXV.C Circuit C EXV % Open
ECO.A CircAeco EXV % Open
ECO.B Circ B eco EXV % Open
ECO.C Circ Ceco EXV% Open
FAN.A Circuit A Fan Stages
FAN.B Circuit B Fan Stages
FAN.C Circuit C Fan Stages
SPD.A Cir A Head Press Speed
SPD.B Cir B Varifan position
SPD.C Cir C Varifan positionHT.A Oil Heater Circuit A
SL1 .A Slide Valve 1 Cir A
SL2.A Slide Valve 2 Cir A
HGRA Hot Gas Bypass A OutputOLS.A Oil Solenoid Cir A
DGT.A DGT Cool Solenoid A
HT.B Oil Heater Circuit B
SL1 .B Slide Valve 1 Cir B
SL2.B Slide Valve 2 Cir B
HGRB Hot Gas Bypass B OutputOLS.B Oil Solenoid Cir B
DGT.B DGT Cool Solenoid B
HT.C Oil Heater Circuit C
SL1 .C Slide Valve 1 Cir C
SL2.C Slide Valve 2 Cir C
HGRC Hot Gas Bypass C OutputOLS.C Oil Solenoid Cir C
DGT.C DGT Cool Solenoid C
FRV.A Free Cooling Heater A
FRRA Refrigerant Pump A
FRV.B Free Cooling Heater B
FRRB Refrigerant Pump B
FRV.C Free Cooling Heater C
FRRC Refrigerant Pump C
RV.A 4 Way Valve Circuit A
RV.B 4 Way Valve Circuit B
*Place the Enable/Off/Remote Contact switch to the Off position
DISPLAY CHECK WHEN COMPLETE
OFF-ON
OFF-ON
0-2OFF-ON
0-2OFF-ON
0-2OFF-ON
XXXXXX
XXX
XXX
XXX
XXX
X
X
X
XXX
XXX
XXX
OFF-ON
OFF-ON
OFF-ON
OFF-ONOFF-ON
OFF-ON
OFF-ON
OFF-ON
OFF-ON
OFF-ONOFF-ON
OFF-ON
OFF-ON
OFF-ON
OFF-ONOFF-ON
OFF-ON
OFF-ON
OPEN-CLSE
OFF-ON
OPEN-CLSE
OFF-ON
OPEN-CLSE
OFF-ON
OPEN-CLSEOPEN-CLSE
)rior to configuring T.REQ to ON. Configure the desired itemto ON, then place the Enable/Off/Remote Contact switch to the Enable position.
1-Place the Enable/Off/Remote Contact switch to the Off position prior to configuring (2.RE(2 to ON. The switch should be in theOff position to perform Quick Test.
CL-6
LU
2:
C_LUI--
rm
Z
o,<I-
(p
LU2:
rmLUI-
c_
Z
o,<I-
(p
MODE -- SERVICE TEST (cont)
To Enable Service Test Mode, move Enable/Off/Remote Contact Switch to OFF.Configure TEST to ON. Move Switch to ENABLE.
ITEM ITEM EXPANSION
HR1 .A Air Cond Enter Valve A
HR2.A Air Cond Leaving Valv AHR3.A Water Cond Enter Valv A
HR4.A Water Cond Lear Valve A
HR1.B Air Cond Enter Valve B
HR2.B Air Cond Leaving Valv BHR3.B Water Cond Enter Valv B
HR4.B Water Cond Lear Valve B
PMP.1 Water Exchanger Pump 1
PMP.2 Water Exchanger Pump 2
PMP.3 Condenser Pump 1
PMP.4 Condenser Pump 2
CL.HT Cooler heater OutputBVL.A Ball Valve Position ABVL.B Ball Valve Position B
BVL.C Ball Valve Position C
CP.HT Condenser Heater Output
Q.RDY Chiller Ready status
Q.RUN Chiller Running statusSHUT Customer Shutdown Stat
CATO Chiller capacity in 0-10v
ALRM Alarm Relay
ALRT Alert Relay
SUB-MODE
OUICI" (cont)
DISPLAY
OPEN-CLSE
OPEN-CLSE
OPEN-CLSE
OPEN-CLSE
OPEN-CLSE
OPEN-CLSE
OPEN-CLSE
OPEN-CLSE
OFF-ON
OFF-ON
OFF-ON
OFF-ON
OFF-ON
OPEN-CLSEOPEN-CLSE
OPEN-CLSE
OFF-ON
OFF-ON
OFF-ON
OFF-ON
nn.nOFF-ON
OFF-ON
CHECK WHEN COMPLETE
*Place the Enable/Off/Remote Contact switch to the Off position prior to configuring T.REQ to ON. Configure the desired itemto ON, then place the Enable/Off/Remote Contact switch to the Enable position.
1-Place the Enable/Off/Remote Contact switch to the Off position prior to configuring Q.REQ to ON. The switch should be in theOff position to perform Quick Test.
Operating Data:Record the following information from the Run Status, Temperatures and Outputs Modes when machine is in a
stable operating condition.
TEMPERATURES
COOLER ENTERING FLUID EWT
COOLER LEAVING FLUID LWT
CONTROL POINT CTPT
CAPACITY CAP
OUTSIDE AIR TEMPERATURE OAT
LEAD/LAG LEAVING FLUID CHWS
CIRCUIT A CIRCUIT B
SCT.A SCT.B
SST.A SST.B
DGT.A DGT.B
SGF.A SGT.B
SURA SURB
ECT.A ECT.B
ESH.A ESH.B
CTP.A CTRB
EXV.A EXV.B
ECO.A ECO.B
NOTE: EXV A,B,C positions are found in file output mode.
COMPRESSOR MOTOR CURRENTLI
COMPRESSOR A 1COMPRESSOR B1COMPRESSOR C1
L2 L3
(Dual Chiller Control Only)
CIRCUIT CSCT.CSST.CDGT.CSGT.CSURCECT.CESH.CCTRCEXV.CECO.C
CL-7
CONDENSERFANMOTORCURRENTLI L2
FANFANFANFANFANFANFANFANFANFANFANFANFANFANFANFANFANFANFANFANFANFAN
MOTOR 1
MOTOR 2
MOTOR 3
MOTOR 4
MOTOR 5
MOTOR 6
MOTOR 7
MOTOR 8
MOTOR 9
MOTOR 10
MOTOR 11
MOTOR 12
MOTOR 13
MOTOR 14
MOTOR 15
MOTOR 16
MOTOR 17
MOTOR 18
MOTOR 19
MOTOR 20
MOTOR 21
MOTOR 22
L3
COMMENTS:
SIGNATURES:
Start-upTechnician Date
CustomerRepresentative Date
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 212 Catalog No. 533-00069 Printed in U.S.A. Form 30XA-1T Pg CL-8 12-05 Replaces: New