3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The...

16
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: [email protected] Web: www.ashidaelectronics.com Ref.: ADR145A Issue : 05 09.06.07 Page 1 / 6 Type: ADR145A (ADITYA Series) (Preliminary) Features: 4 Element (3 Phase + EF) Over current IDMT with instant trip. Programmable (Non- Volatile) Setting By local keys as well as remote setting by communication port. Back - lit LCD display for settings. Display of fault current. / Load current. Selection of Curve: Five selectable curves, Normal Inverse1 (C1), Normal Inverse2, (C2) Very inverse (C3), Extremely inverse (C4), Long time inverse (C5). Design using DSP technology Latching of fault current. Direction OC/EF Characteristic. Programmable MTA +30, +45and +60 for phase and – 14, -30, -45 for EF. Pass-word protection for setting. General: The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet demand of low and medium switchgear control. The ADR145A is a Directional 3 OC and 1 EF relay with Instantaneous high set and programmable output to simplify feeder protection wiring. The ADR145A continuously monitors all 3 phase and earth current, through CT connections. The high-speed micro-controller samples this current through a 12-bit A/D converter. The micro-controller performs powerful Digital Algorithms to find out Amplitude of current signal, direction of power flow then this value is use for protection and metering function. All measurement is tuned to fundamental frequency. Each input current is also displayed on 16 x 2 LCD display for metering. The Relay is having main three functions 1) Protection 2) Self-Supervision 3) Measurement. 1. Protection Functions: The ADR145A give maximum benefit/cost ratio. The ADR145A give all the advantage of numerical relay at affordable cost. Following is summery of different protection functions provided by relay. ANSI IEC Protection Functions 50 I >> Instantaneous Over current Protection (OC-Inst.) 50N I E >> Instantaneous Earth Fault Protection (EF-Inst.) ASHIDA NUMERICAL DIRECTIONAL 3 O/C + 1E/F IDMT RELAY ‚þ¹ªþ¸þ ADR 145A LED RESET

Transcript of 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The...

Page 1: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR145AIssue : 05 09.06.07

Page 1 / 6

Type: ADR145A (ADITYA Series) (Preliminary)

Features:• 4 Element (3 Phase + EF) Over current IDMT

with instant trip.• Programmable (Non- Volatile) Setting By local

keys as well as remote setting by communicationport.

• Back - lit LCD display for settings.• Display of fault current. / Load current.• Selection of Curve: Five selectable curves,

Normal Inverse1 (C1), Normal Inverse2, (C2)Very inverse (C3), Extremely inverse (C4), Longtime inverse (C5).

• Design using DSP technology• Latching of fault current.• Direction OC/EF Characteristic.• Programmable MTA +30, +45and +60 for phase

and – 14, -30, -45 for EF.• Pass-word protection for setting.General:The ADR145A is member of Ashida Numerical Relayfamily (Aditya Series) design to meet demand of lowand medium switchgear control. The ADR145A is aDirectional 3 OC and 1 EF relay with Instantaneoushigh set and programmable output to simplify feederprotection wiring. The ADR145A continuouslymonitors all 3 phase and earth current, through CTconnections. The high-speed micro-controllersamples this current through a 12-bit A/D converter.

The micro-controller performs powerful Digital Algorithms to find out Amplitude of current signal,direction of power flow then this value is use for protection and metering function. All measurement istuned to fundamental frequency. Each input current is also displayed on 16 x 2 LCD display formetering. The Relay is having main three functions 1) Protection 2) Self-Supervision 3) Measurement.

1. Protection Functions:The ADR145A give maximum benefit/cost ratio. The ADR145A give all the advantage of numericalrelay at affordable cost. Following is summery of different protection functions provided by relay.

ANSI IEC Protection Functions50 I >> Instantaneous Over current Protection (OC-Inst.)

50N IE>> Instantaneous Earth Fault Protection (EF-Inst.)

ASHIDA NUMERICAL DIRECTIONAL3 O/C + 1E/F IDMT RELAY

‚þ¹ªþ¸þ

ADR 145A

LEDRESET

Page 2: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR145AIssue : 05 09.06.07

Page 2 / 6

Type: ADR145A (ADITYA Series) (Preliminary)

51 I>t, Ip Time Over current Protection (Phase) (OC-IDMT.)51N IE>t, IEP Time Over current Protection (Earth) (EF-IDMT.)67 Idir >, Idir >> Ipdir Directional Time over current protection, Phase

67N IEdir >, IEdir >> IEdir Directional Time over current protection, EF

1.1. Over current / EF protection:The ADR145A has 4 sensing element 3 OC and 1 EF. The tripping current can be set from 50% to200% for phase and 5% to 80% for Earth fault in steps of 1% by Keys switch provided on frontpanel. The unit has got selection of IDMT characteristic of international IEC standard Very inverse /Extremely Inverse / Long Inverse and Standard inverse (both 3.0 sec and 1.3sec at 10 times). Theunit also has Time Multiplier Setting (TMS) from x0.01 to x1.0 for IDMT delay multiplication. Theinstantaneous tripping function is having range of 100% - 3000% for phase and 100% - 1200% forEF and can be set in steps of 100%. The high speed CPU continuously monitor the all four currentinputs and compare with IDMT as well as instantaneous setting. If any one current is aboveinstantaneous setting the relay provide immediate trip command bypassing IDMT delay. If is inputcurrent is less than instantaneous setting but more than IDMT setting, CPU calculate IDMT delay asper selected IDMT characteristic multiply it with TMS setting and provide trip command if fault ispersist even after this time delay. All the 4 elements are voltage polarised. That means theIDMT elements can be made directional or non-directional via. Key board setting.All the settings are password protected to prevent unauthorised change.

1.2. Extra Alarm Contact:Any Protection panel required extra contacts for provide visual ALARM and ANNUNCIATIONindication for operator. Also some status contacts for SCADA or remote indications. Usuallyseparate electromechanical relay used for contact multiplication of protection relay contacts. Thisadded extra wiring and extra hardware. The ADR141A provide separate programmable ALARMcontact for such application. Maximum 4 nos. of extra contacts can be provided. These contacts canbe programmed as follows

Function ANN1 ANN2 ANN3 ANN4Type 1 OC1 OC2 EF OC3Type 2 OC–IDMT OC-Inst. EF-IDMT EF-Inst.

2. Supervision Function:2.1. Self-supervision:

The continuously keeping track on its internal hardware and the movement it detect any failure ofany component, it give message on LCD display, This feature is very useful to give pre informationto avoid any mall - operation. In such situation it use some default setting and remain in protectionmode.

Page 3: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR145AIssue : 05 09.06.07

Page 3 / 6

Type: ADR145A (ADITYA Series) (Preliminary)

3. Measurement Function:In normal condition this display shows all settings. Via keyboard the display can be program to showthe actual current flowing through the relay. If current excesses set value the relay gives tripcommand. The type of fault is displayed on LCD display. During the fault condition the relaymeasure the fault current and store in non-volatile memory. The fault current can be read viakeyboard on LCD display Last 3 fault values along with tripping counter can be view via key-board. All settings are save in Electrically erasable read only memory and remain.

Ordering Information:

While Order ing Specify the fol lowing Information for ADR145A Relay

Order ing informat ion :

A D R 1 4 5 A - A M - X X X - X X - X - X - X X - X

ExampleADR145A – AM-001-02-3-0-02-0Type : ADR145ABack Termina l Layout : Relay with extra contact - - -Cabinet Type : CSD-150 non DrawoutCT sec : 5 Amp. Aux i l ia ry Supply : 77 - 250 V dc

D e f i n i t i o n o f M o d e l N o o f A d i t y a S e r i e s o f R e l a y s

A M X X X – X X – X – X – X X – X

Auxiliary Supply01 = 18 – 52 V dc 06 = 110 V dc02 = 77 – 250 V dc 07 = 220 V dc03 = 24 V dc04 = 30 V dc05 = 48 V dc

Reserved for Future Use

PT Secondary1 = 63.5V ac2 = 110V ac3 = 230V ac

CT Secondary1 = 1 Amp.2 = 5 Amp.3 = 1 Amp. / 5 Amp. Selectable

AM XXX XX X3OC + 1EF Relays

001 01 Relay without extra contacts, With site selectable CT. CSD – 150 302 Relay with 4 extra contacts, two contact for LBB & site

selectable CT.CSD – 150 3

Page 4: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR145AIssue : 05 09.06.07

Page 4 / 6

Type: ADR145A (ADITYA Series) (Preliminary)

Technical Specifications:Sr. No. Specification Particulars

I. CT Inputs : Suitable for CT secondary 1.0 Amp or 5.0 Amp. (To be specified.) II. PT Input : Suitable for PT secondary of 110Vac

: For Phase - 50 - 200 % in step of 1%.: For EF - 5 - 80 % in step of 1%: Phase Instantaneous: - 100 - 3000% in steps of 100% and bypass

Protection Relay SettingRange

: EF Instantaneous: - 100 to 1200% in steps of 100%.: Phase - +30 , +45 & +60 or non directional III. MTA setting: EF - -10 , +30 ,-45 ,–60 or non directional

IV. Pickup Current : Within 1.1 times of set current value. V. Resetting Current : Within 90% of set value. VI. Operating Time : Time: 5 selectable IDMT curve C1, to C5.

: Instantaneous Time < 40ms on 2 times current of setting. VII. Time Accuracy : Within class 2.5 As per IS: 3231. VIII. Burden on CTs : Less than 0.2VA. IX. Aux. Supply : 18 - 52VDC or 77 - 250VDC. To be specified while ordering. X. Burden on Aux. Supply : Less than 10VA on any supply. XI. Control Contacts : 2 NO contacts (SR ) are given for Trip & Annunciation. - Trip Duty XII. Contact Rating Trip Duty : Make and carry for 3sec. – 7500VA with max. 30A & 660VAC/DC

: Make and carry for continuous - 1250VA with max. 5A & 660VAC/DC: Break AC - 1250 VA DC - 100 W resistive 50W inductive.

XIII. Operational Indicators (Flags)ON : Green LED indicates Relay OK

: In case of following condition led become off1. Problem in relay Hardware.2. Auxiliary supply is not sufficient for relay operation.

FAULT : Red LED’s indicates the OC/EF relay trip, Hand Reset (HR) Type.PKP : Red LED indicates OC/EF relay Pickup.TRIP : Indicates that Trip pulse is being executed. When BYPASS P.B. is

pressed, actual trip is not executed. XIV. Thermal Withstand

Capacity: x40 times the normal current for 3sec.: x2 Continuous

XV. High Voltage Test : IEC 60255-5: Except DC Voltage – 2.0 kV (RMS), 50Hz: Only DC voltage - 2.8 kV DC: Between Open contact of TRIP / CLOSE 1.5kV (RSM) 50Hz: Between Open contact of ALARM – 1kV (RSM) 50Hz

Page 5: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR145AIssue : 05 09.06.07

Page 5 / 6

Type: ADR145A (ADITYA Series) (Preliminary)

XVI. Impulse Voltage Test (allcircuit class – III)

: IEC60255-5: 5kV (peak) 1.2 / 50us, 0.5 J, 3 positive and 3 negative impulse at interval of5 sec

XVII. High Frequency test : IEC 60255-22-1, Class III: 2.5 kV (peak) 1MHz , τ = 15µs 400 surges / s duration 2 s

XVIII. Electro static Discharge : IEC 60255-22-2 Class III and IEC 61000-4-2 class III: 4kV/6kV contact discharge, 8kV air discharge, both polarities 150pF, Ri 330Ω

XIX. Irradiation with radiofrequency field, pulse-modulated,

: IEC 60255-22-3 and IEC 61000-4-2 class III: 10V/m; 80 to 1000MHz; 80%; 1kHz AM

XX. Fast transientinterference/bursts

: IEC 60255-22-3 and IEC 61000-4-3, class III: 4kV; 5/50ns; 5kHz burst duration = 15ms;: Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.

XXI. Shock Test : IEC 60255-21-2 class 1: Semi-Sinusoidal: 5g acceleration, duration 11ms,: Each 3 shocks in both direction of the 3 axes

XXII. Vibration Test : IEC 60255-21-1 class 1 / IEC 60068-2-6: Sinusoidal 10 to 60Hz ±0.035 mm: Amplitude, 60 to 150Hz, 0.5g acceleration: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal

XXIII. Seismic Test : IEC 60255-21-3: In single axis sine sweep in X-axis1. sweep (@a sweep rate of 1 octave/minute) vibration in the frequency

range (5-40 Hz) at amplitude of 3.5mm or 1.0gn (whichever is less): In single axis sine sweep in Y-axis1. - weep (@a sweep rate of 1 octave/minute) vibration in the frequency

range (5-40 Hz) at amplitude of 1.5mm or 0.5gn (whichever is less) XXIV. Bump Test : IEC 60255-21-2 Class-1

: 1000 bumps of 10gn peak acceleration and 16ms pulse duration in each ofthe two opposite direction per axis as per IEC60255-21-2 class 1 No. ofaxes . 3.

XXV. Shock Withstand : IEC 60255-21-2 Clas-1: 3 shocks of 15gn peak acceleration and 11ms pulse in each of two opposite

direction . No. of axis : 3 XXVI. Shock Response Test : IEC 60255-21-2 Clas-1

: 3 shocks of 1gn peak acceleration and 11ms pulse in each of two oppositedirection . No. of axis : 3

XXVII. Vibration Endurance Test : IEC60255-21-120-sweeps (@ a sweep rate of 1octave / minutes) vibration in the frequencyrange (10-150Hz) at 1 gn (9,8m/s2) acceleration in each of the 3 mutuallyperpendicular axes

Page 6: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may varyslightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.Plot No. A-308, Road No. 21,

Wagle Industrial Estate,Thane (W)-400 604. INDIA.

E-mail: [email protected]: www.ashidaelectronics.com

Ref.: ADR145AIssue : 05 09.06.07

Page 6 / 6

Type: ADR145A (ADITYA Series) (Preliminary)

XXVIII. Environmental withstand(cold, Dry heat & steadystate Damp Heat)

: IEC60068-2Cold – 2 hours operational condition at –(40 +/- 3) deg C as per IEC60068-2-

1Dry – 2 Hours dry heat operational condition at(55+/2 2 deg. C as per

IEC60068-2-2Steady state damp heat - 2 hours steady sate damp heat operational

condition at temperature at (55 +/- 2) deg. C & humidity 95% RH as perIEC60068-2-78

Drawing References : For Cabinet Type CSD -150 (MAC00402): For Operating Characteristics C1 - APR02201

C2 - APR01801C3 - APR05101C4 - APR05201C5 - APR05301

XXIX.

: For Electrical Connection & Back TerminalAM00101

- APD01602

: For Electrical Connection AM00102 - APD01604 : For Back Terminal AM00102 - APD01606 : Directional Characteristics - APR01901

• Datasheet Change Log for ADR145AIssue No.(Revision)

Date Description /Changes

01 24.12.04 Original Revision02 15.01.06 Colour Front added03 23.03.06 Electrical Connection Revised04 15.04.06 Ordering Information added

04A 09.03.07 Reset value change from 80% ….to 90%

05 09.06-07 IEC Test addedSeismic TestBump TestShock WithstandShock Response TestVibration Endurance TestEnvironmental withstand (cold, Dry heat & steady state Damp Heat)

Page 7: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 8: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 9: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 10: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 11: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 12: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 13: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 14: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 15: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet
Page 16: 3 O/C + 1E/F IDMT RELAY (Preliminary)imghost.indiamart.com/data/2/M/MY-675743/ADR145A_05.pdf · The ADR145A is member of Ashida Numerical Relay family (Aditya Series) design to meet