Contract NE/2017/02 : Tseung Kwan O – Lam Tin Tunnel – Road P2/D4 and Associated Works
Noise Mitigation Plan
Revision Chronology
No. NMP Report No.
a. Activities No.1 to 4 remain unchanged while Activities No.5 and 6
have been re-organized into new Activities No.5, 6. 7 and 8.
b. The new Activities No.5, 6, 7 and 8 are confined within the current site
boundary demarcation in Figures 1b to 1d (with legend updated) while
Figure 1e is no longer applicable and removed.
c. Tables 2, 3, 4, 5 and 6 have been revised accordingly.
d. Plots 1 and 2 have been re-organized and expanded into Plots 1a, 1b,
1c, 2a, 2b, 2c.
2
3
4
5
6
7
8
9
10
04/12/2018
Revision Background / Reason
for RevisionRevised by
Revision
DateRevision Highlight
To go in line with the
latest site progress
and the construction
plant inventory
variation
0005/18/ED/0004k1 Fugro
Technical
Services
Ltd.
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 1 of 36
Noise Mitigation Plan for Contract NE/2017/02 Tseung Kwan O – Lam Tin Tunnel – Road P2/D4 and Associated Works
Client : Zhen Hua Engineering Company
Limited
Project : Noise Mitigation Plan for
NE/2017/02 Tseung Kwan O – Lam Tin
Tunnel – Road P2/D4 and Associated
Works
Prepared by:
__________________________
Mr. K. W. CHENG (AMIOA, MHKIOA)
Reviewed by:
__________________________
Calvin M.P. LEUNG (M239 of HKIOA)
Certified by:
__________________________
Colin K. L. YUNG Project Manager Fugro Technical Services Limited
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 2 of 36
TABLE OF CONTENTS TABLE
1. Introduction 1
2. Noise Mitigation Plan 1
2.1 Noise Sensitive Receivers & Statutory Noise Limits 1
2.2 Construction Plant Inventory 2
2.3 Construction Noise Calculations 4
2.4 Noise Mitigation Measures (Construction Noise) 14
2.5 Noise Mitigation Measures (Road Traffic Noise) 14
2.6 Construction Noise Levels & Compliance Status 15
3. Conclusion 19
4. References 19
TABLE
Table 1 Critical Noise Sensitive Receivers & Statutory Noise Limits
Table 2 Construction Plant Inventory
Table 3 Construction Noise Calculations (Mitigated)
Table 4 Predicted Monthly Construction Noise Levels (Mitigated)
Table 5 Summary of Proposed Noise Mitigation Measures
Table 6 Summary of Predicted Construction Noise Levels
FIGURE
FIGURE 1a Location Plan of the Construction Site
FIGURE 1b Location Plan of Noise Sensitive Receivers & Activity Locations (Activity No.1, 2, 4, 5 and 7)
FIGURE 1c Location Plan of Noise Sensitive Receivers & Activity Locations (Activity No.3, 6 and 8 ; NSR-1, NSR-3, NSR-5)
FIGURE 1d Location Plan of Noise Sensitive Receivers & Activity Locations (Activity No.3, 6 and 8 ; NSR-2, NSR-4, NSR-6)
FIGURE 2 Location Plan of the Noise Sensitive Receivers within the 300m Noise Study Boundary
APPENDIX
APPENDIX A Proposed Mitigation Measures
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 3 of 36
1. Introduction
1.1 Contract Requirements
This project refers to Contract No. NE/2017/02 Tseung Kwan O – Lam Tin Tunnel – Road P2/D4 and Associated Works. Fugro Technical Services Limited (FTS) has been appointed as the Environmental Consultant by Zhen Hua Engineering Company Limited to prepare a Noise Mitigation Plan (NMP) for this contract which is to be completed in fulfilment of the associated Environmental Permit No. EP-458/2013/C, Part C, Condition 2.5 as well as the Particular Specification, Section 25.13A of the Contract.
1.2 Scope
The NMP under this report applies to all the critical construction activities which are involved in a number of stages including the road construction, drainage works, footbridge construction as well as the subsequent landscaping works throughout the whole construction period. Particular attention shall be paid to the concurrent school activities during the school examination time during which the contract is to be executed.
2. Noise Mitigation Plan
2.1 Noise Sensitive Receivers & Statutory Noise Limits
A total of 6 critical noise sensitive receivers (NSRs) have been identified as shown in Figures 1b to 1d and Table 1 below. They are particularly within the 300 m distance from the site boundary as delineated in Figure 2 under the current Contract. Only NSR-5 is common with the corresponding NSR No. N7603 (as designated under the associated EIA report) which has been covered under the Noise Mitigation Plans of the other 2 neighbouring Contracts: NE/2015/02 (Revision 7, updated on 04-04-2018) and NE/2015/03. Table 1 Critical Noise Sensitive Receivers & Statutory Noise Limits
Designation PremisesNoise Limit in
Leq (30 min), dB(A)Remarks
NSR-1 Metrotown, Tower 1 75
NSR-2 Hong Kong Design Institute
Served by mechanical ventilation with curtain wall façades
instead of natural ventilation via openable windows ; offering -
10 dB(A) noise reduction
NSR-3 Hong Kong IVE (Lee Wai Lee)
NSR-4 Tiu Keng Leng Public Library 70
Served by mechanical ventilation with 'fixed window + curtain
wall' façades instead of natural ventilation via openable
windows ; offering -10 dB(A) noise reduction
NSR-5 Park Central, Tower 6 75
NSR-6 Park Central, Central Heights 75
Notes : Only NSR-5 has been covered in the Noise Mitigation Plans under the other 2 Contract : NE/2015/02 and NE/2015/03
70 or 65 (during
examination)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 4 of 36
2.2 Construction Plant Inventory
Table 2 below gives the construction plant inventory over the whole construction period to be adopted for the 8 activities corresponding to the latest site progress. Table 2 Construction Plant Inventory
Group Item ClassificationIdentification
CodeSource Description Quantity
SWL,
dB(A)
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105
2 PME CNP 082 Excavator (mini-robot mounted) 2 94
3 PME CNP 143 Light Good Vehicle (G.V.W. ≤ 5.5 tonnes) 1 101
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
5 PME CNP 185 Road Roller 2 108
1 PME CNP 072 Drilling rig (Pre-drilling) 1 110
2 PME CNP 105 Grout mixer 1 90
3 PME CNP 106 Grout pump 1 105
5 PME CNP 281 Water pump (electric) 1 88
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 8 102
2 PME CNP 164 Bored Piling - Grab & Chisel 2 115
3 PME CNP 165 Bored Piling - Oscillator 2 115
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 2 100
5 SPME BS D6/33 b Concrete lorry mixer 8 96
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105
7 PME CNP 082 Excavator (mini-robot mounted) 2 94
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100
9 PME CNP 048 Mobile / crawler crane 2 112
10 PME CNP 281 Water pump (electric) 2 88
1 PME CNP 003 a Air compressor (air flow > 30 m3/min) 8 104
2 SPME BS D6/33 b Concrete lorry mixer 8 96
3 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110
4 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105
5 PME CNP 082 Excavator (mini-robot mounted) 2 94
6 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100
7 PME CNP 048 Mobile / crawler crane 2 112
8 PME CNP 281 Water pump (electric) 2 88
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115
3 PME CNP 165 Bored Piling - Oscillator 1 115
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100
5 SPME BS D6/33 b Concrete lorry mixer 4 96
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
7 PME CNP 082 Excavator (mini-robot mounted) 1 94
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100
9 PME CNP 048 Mobile / crawler crane 1 112
10 PME CNP 281 Water pump (electric) 1 88
11 PME CNP 003 a Air compressor (air flow > 30 m3/min) 4 104
12 SPME BS D6/33 b Concrete lorry mixer 4 96
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
15 PME CNP 082 Excavator (mini-robot mounted) 1 94
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100
17 PME CNP 048 Mobile / crawler crane 1 112
18 PME CNP 281 Water pump (electric) 1 88
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115
3 PME CNP 165 Bored Piling - Oscillator 1 115
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100
5 SPME BS D6/33 b Concrete lorry mixer 4 96
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
7 PME CNP 082 Excavator (mini-robot mounted) 1 94
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100
9 PME CNP 048 Mobile / crawler crane 1 112
10 PME CNP 281 Water pump (electric) 1 88
11 PME CNP 003 a Air compressor (air flow > 30 m3/min) 8 104
12 SPME BS D6/33 b Concrete lorry mixer 8 96
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105
15 PME CNP 082 Excavator (mini-robot mounted) 2 94
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100
17 PME CNP 048 Mobile / crawler crane 2 112
18 PME CNP 281 Water pump (electric) 2 88
Activity Period
Powered Mechanical Equipment (PME)
4
5
1Utilities
Diversion3/2018-6/2019 1
a
a
a
a
a
2
Bored Piling /
Pre-bored
Socketed H
Pile / Pre-
drilling
a
a
a
a
a
a
8/2018-12/2019
1
2
3
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 5 of 36
Table 2 Cont'd.
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105
2 PME CNP 081 Excavator 1 112
3 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
5 PME CNP 186 Roller (vibratory) 1 108
6 PME CNP 283 Water pump (submersible, electric) 4 85
1 SPME CNP 025 a Breaker (hand-held, 20 kg ≤ mass ≤ 35 kg) 1 111
2 SPME BS D6/33 b Concrete lorry mixer 1 96
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
4 PME CNP 081 Excavator 1 112
5 PME CNP 107 Generator (portable) - Welding set 1 100
6 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102
7 PME CNP 186 Roller (vibratory) 1 108
8 PME CNP 283 Water pump (submersible, electric) 4 85
1 PME CNP 021 a Bar Bender and Cutter (electric) 1 90
2 SPME BS D6/33 b Concrete lorry mixer 3 96
3 PME CNP 048 Crawler Crane 1 112
4 PME CNP 056 Cutter (circular, steel, electric) 1 112
5 PME CNP 081 Excavator 1 112
6 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
7 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102
8 PME CNP 168 Power Pack for Hand-held Items 1 100
2 1 PME CNP 068 a Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105
Activities 5 to 6 being mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110
3 PME CNP 081 Excavator 1 112
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100
5 PME CNP 048 Mobile / crawler crane 1 112
1 PME CNP 003 a Air compressor (air flow > 30 m3/min) 2 104
2 SPME BS D6/33 b Concrete lorry mixer 2 96
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
4 PME CNP 081 Excavator 1 112
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100
6 PME CNP 048 Mobile / crawler crane 1 112
6Concrete
Breaking8/2018-11/2020 1 1 PME CNP 028 a Breaker (excavator mounted, hydraulic) 1 122
Activities 7 to 8 being mutually exclusive (not occurring concurrently with) from Activities 1 to 6
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110
3 PME CNP 081 Excavator 1 112
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100
5 PME CNP 048 Mobile / crawler crane 1 112
1 PME CNP 003 a Air compressor (air flow > 30 m3/min) 2 104
2 SPME BS D6/33 b Concrete lorry mixer 2 96
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
4 PME CNP 081 Excavator 1 112
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100
6 PME CNP 048 Mobile / crawler crane 1 112
1 PME CNP 004 Asphalt Paver 1 109
2 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105
3 PME CNP 168 Power Pack for Hand-held Items 1 100
4 PME CNP 184 Road Planer 1 111
5 PME CNP 185 Road Roller (Pneumatic Tyred Roller) 1 108
6 PME CNP 186 Roller (vibratory) 1 108
Notes : 1. SPME = Specified Powered Mechanical Equipment ; SWL = Sound Power Level
2. Source from 'a' EPD's Technical Memorandum GW-TM [1] or DA-TM [2] ; 'b' British Standard BS 5229-1 (2009) [3]
8Flexible
Pavement8/2018-11/2020 1
a
a
a
a
a
7
Bored Piling /
Pre-bored
Socketed H
Pile / Pre-
drilling
8/2018-12/2019 1
Bored Piling /
Pre-bored
Socketed H
Pile / Pre-
drilling
8/2018-12/2019 2
5
Bored Piling /
Pre-bored
Socketed H
Pile / Pre-
drilling
8/2018-12/2019 1
Bored Piling /
Pre-bored
Socketed H
Pile / Pre-
drilling
8/2018-12/2019 2
1
3
Drainage,
Sewerage and
Water Mains
8/2018-11/2020
4
Footbridge
Segment
Installation /
Staircase and
Lift Shaft
Construction
7/2019-11/2020
1
2
a
a
a
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 6 of 36
2.3 Construction Noise Calculations
Construction noise calculations based on the latest proposed plant inventory have been carried out to give the Corrected Noise Levels (CNLs) for the 6 most critical NSRs as tabulated in Table 3 below. All CNLs are derived from the selected Sound Power Levels (SWLs) of the respective Powered Mechanical Equipments (PMEs) as well as corrections including those for PME % On-time (both the plant inventory and PME % On-time have been reviewed and confirmed to be appropriate estimates by the Resident Engineer of the project team), noise screening (e.g. noise barrier), distance attenuation (source-to-receiver slant distance ‘R’ where the source is taken as the notional source position) and façade reflection. Details of the combined CNL time variation over the whole construction period from 2018 to 2020 (with relevant noise mitigation measures) and the noise compliance status are summarized in Table 4. In particular the cumulative CNLs at the common NSR-5 from all the noise contribution under the current Contract NE/2017/02 as well as the other Contract NE/2015/02 + NE/2015/03 are given in Table 4 (NSR-5 only) as well.
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 7 of 36
Table 3 Construction Noise Calculations (Mitigated)
NSR-1 : Metrotown, Tower 1 (Mitigated) Updated : 27-11-2018
Group Item ClassificationIdentification
CodeDescription Quantity
SWL,
dB(A)
Combined
SWL, dB(A)Individual Overall
Non-restricted Hours
(07:00-19:00)
Compliance
(CNL ≤ Noise Limit)
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 247 52
2 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 50 0 247 41
3 PME CNP 143 Light Good Vehicle (G.V.W. ≤ 5.5 tonnes) 1 101 101 50 0 247 45
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 247 47
5 PME CNP 185 Road Roller 2 108 111 50 0 247 55
1 PME CNP 072 Drilling rig (Pre-drilling) 1 110 110 60 0 271 54
2 PME CNP 105 Grout mixer 1 90 90 40 0 271 32
3 PME CNP 106 Grout pump 1 105 105 40 0 271 47
5 PME CNP 281 Water pump (electric) 1 88 88 60 0 271 32
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 8 102 111 35 0 271 53
2 PME CNP 164 Bored Piling - Grab & Chisel 2 115 118 60 0 271 62
3 PME CNP 165 Bored Piling - Oscillator 2 115 118 60 0 271 62
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 2 100 103 60 0 271 47
5 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 271 49
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 271 47
7 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 271 39
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 271 49
9 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 271 57
10 PME CNP 281 Water pump (electric) 2 88 91 60 0 271 35
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 271 55
2 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 271 49
3 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 271 57
4 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 271 47
5 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 271 39
6 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 271 49
7 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 271 57
8 PME CNP 281 Water pump (electric) 2 88 91 60 0 271 35
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 271 50
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 0 271 59
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 0 271 59
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 271 44
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 271 46
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 271 44
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 271 36
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 271 46
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 271 54
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 271 32
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 4 104 110 35 0 271 52
12 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 271 46
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 60 0 271 54
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 271 44
15 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 271 36
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 271 46
17 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 271 54
18 PME CNP 281 Water pump (electric) 1 88 88 60 0 271 32
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 271 50
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 0 271 59
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 0 271 59
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 271 44
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 271 46
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 271 44
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 271 36
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 271 46
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 271 54
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 271 32
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 271 55
12 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 271 49
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 271 57
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 271 47
15 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 271 39
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 271 49
17 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 271 57
18 PME CNP 281 Water pump (electric) 2 88 91 60 0 271 35
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 25 0 122 55
2 PME CNP 081 Excavator 1 112 112 30 0 122 60
3 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 122 56
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 25 0 122 52
5 PME CNP 186 Roller (vibratory) 1 108 108 25 0 122 55
6 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 122 44
1 SPME CNP 025 Breaker (hand-held, 20 kg ≤ mass ≤ 35 kg) 1 111 111 25 0 122 58
2 SPME BS D6/33 Concrete lorry mixer 1 96 96 70 0 122 48
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 122 53
4 PME CNP 081 Excavator 1 112 112 25 0 122 59
5 PME CNP 107 Generator (portable) - Welding set 1 100 100 50 0 122 50
6 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 35 0 122 51
7 PME CNP 186 Roller (vibratory) 1 108 108 25 0 122 55
8 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 122 44
1 PME CNP 021 Bar Bender and Cutter (electric) 1 90 90 100 0 271 36
2 SPME BS D6/33 Concrete lorry mixer 3 96 101 50 0 271 44
3 PME CNP 048 Crawler Crane 1 112 112 80 0 271 57
4 PME CNP 056 Cutter (circular, steel, electric) 1 112 112 60 0 271 56
5 PME CNP 081 Excavator 1 112 112 80 0 271 57
6 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 271 48
7 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 50 0 271 45
8 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 271 43
2 1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 271 51 51 75 Complied
Activities 5 to 6 being mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 271 53
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 271 56
3 PME CNP 081 Excavator 1 112 112 40 0 271 54
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 271 46
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 271 54
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 271 53
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 271 42
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 271 46
4 PME CNP 081 Excavator 1 112 112 40 0 271 54
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 271 46
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 271 55
6 Concrete Breaking 8/2018-11/2020 1 1 PME CNP 028 Breaker (excavator mounted, hydraulic) 1 122 122 39 0 122 71 71 75 Complied
Activities 7 to 8 being mutually exclusive (not occurring concurrently with) from Activities 1 to 6
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 271 53
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 271 56
3 PME CNP 081 Excavator 1 112 112 40 0 271 54
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 271 46
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 271 54
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 271 53
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 271 42
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 271 46
4 PME CNP 081 Excavator 1 112 112 40 0 271 54
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 271 46
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 271 55
1 PME CNP 004 Asphalt Paver 1 109 109 50 0 122 59
2 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 122 55
3 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 122 50
4 PME CNP 184 Road Planer 1 111 111 50 0 122 61
5 PME CNP 185 Road Roller (Pneumatic Tyred Roller) 1 108 108 50 0 122 58
6 PME CNP 186 Roller (vibratory) 1 108 108 50 0 122 58
Notes : 1. SPME = Specified Powered Mechanical Equipment ; SWL = Sound Power Level ; CNL = Corrected Noise Level 3. * Noise Mitigation Measures = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction]
2. Combined SWL = SWL + 10 log (Quantity) ; Predicted CNL (Individual) = Combined SWL + 10 log (PME % On-time) + Correction (Measures) - 20 log (R) - 8 + Facade Reflection [where Facade Reflection = 3] ; Predicted CNL (Overall) = 10 log [∑10(Predicted CNL (Individual) /10)
]
75 Complied8 Flexible Pavement 8/2018-11/2020 1 66
75 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 60 75 Complied
7
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 61
75 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 60 75 Complied
5
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 61
75 Complied4
Footbridge
Segment
Installation /
Staircase and Lift
Shaft Construction
7/2019-11/20201 62
Complied
3
Drainage,
Sewerage and
Water Mains
8/2018-11/2020
1 64 75 Complied
2 64 75 Complied
Predicted CNL, dB(A) Statutory Noise Limit, dB(A)
Complied75
2
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019
1 55
5 66 75
4 65 75 Complied
1 Utilities Diversion 3/2018-6/2019 1 58
3 62
75 Complied
2 66 75 Complied
75 Complied
Activity Period
Powered Mechanical Equipment (PME)PME %
On-time
Distance 'R'
(Source to Critical
NSR), m
Correction
(Noise Mitigation
Measures)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 8 of 36
NSR-2 : Hong Kong Design Institute (Mitigated) Updated : 27-11-2018
Group Item ClassificationIdentification
CodeDescription Quantity
SWL,
dB(A)
Combined
SWL, dB(A)Individual Overall
Non-restricted Hours
(07:00-19:00)
Compliance
(CNL ≤ Noise Limit)
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 118 49
2 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 50 0 118 38
3 PME CNP 143 Light Good Vehicle (G.V.W. ≤ 5.5 tonnes) 1 101 101 50 0 118 42
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 118 43
5 PME CNP 185 Road Roller 2 108 111 50 0 118 52
1 PME CNP 072 Drilling rig (Pre-drilling) 1 110 110 60 0 143 50
2 PME CNP 105 Grout mixer 1 90 90 40 0 143 28
3 PME CNP 106 Grout pump 1 105 105 40 0 143 43
5 PME CNP 281 Water pump (electric) 1 88 88 60 0 143 28
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 8 102 111 35 0 143 48
2 PME CNP 164 Bored Piling - Grab & Chisel 2 115 118 60 0 143 58
3 PME CNP 165 Bored Piling - Oscillator 2 115 118 60 0 143 58
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 2 100 103 60 0 143 43
5 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 143 45
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 143 43
7 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 143 35
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 143 45
9 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 143 52
10 PME CNP 281 Water pump (electric) 2 88 91 60 0 143 31
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 143 50
2 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 143 45
3 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 143 53
4 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 143 43
5 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 143 35
6 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 143 45
7 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 143 52
8 PME CNP 281 Water pump (electric) 2 88 91 60 0 143 31
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 143 45
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 0 143 55
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 0 143 55
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 143 40
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 143 42
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 143 40
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 143 32
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 143 42
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 143 49
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 143 28
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 4 104 110 35 0 143 47
12 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 143 42
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 60 0 143 50
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 143 40
15 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 143 32
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 143 42
17 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 143 49
18 PME CNP 281 Water pump (electric) 1 88 88 60 0 143 28
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 143 45
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 0 143 55
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 0 143 55
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 143 40
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 143 42
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 143 40
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 143 32
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 143 42
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 143 49
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 143 28
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 143 50
12 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 143 45
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 143 53
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 143 43
15 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 143 35
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 143 45
17 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 143 52
18 PME CNP 281 Water pump (electric) 2 88 91 60 0 143 31
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 25 0 57 52
2 PME CNP 081 Excavator 1 112 112 30 0 57 57
3 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 57 53
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 25 0 57 49
5 PME CNP 186 Roller (vibratory) 1 108 108 25 0 57 52
6 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 57 41
1 SPME CNP 025 Breaker (hand-held, 20 kg ≤ mass ≤ 35 kg) 1 111 111 25 0 57 55
2 SPME BS D6/33 Concrete lorry mixer 1 96 96 70 0 57 44
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 57 50
4 PME CNP 081 Excavator 1 112 112 25 0 57 56
5 PME CNP 107 Generator (portable) - Welding set 1 100 100 50 0 57 47
6 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 35 0 57 47
7 PME CNP 186 Roller (vibratory) 1 108 108 25 0 57 52
8 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 57 41
1 PME CNP 021 Bar Bender and Cutter (electric) 1 90 90 100 0 143 32
2 SPME BS D6/33 Concrete lorry mixer 3 96 101 50 0 143 40
3 PME CNP 048 Crawler Crane 1 112 112 80 0 143 53
4 PME CNP 056 Cutter (circular, steel, electric) 1 112 112 60 0 143 52
5 PME CNP 081 Excavator 1 112 112 80 0 143 53
6 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 143 44
7 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 50 0 143 41
8 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 143 39
2 1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 143 47 47 70 Complied
Activities 5 to 6 being mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 143 49
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 143 52
3 PME CNP 081 Excavator 1 112 112 40 0 143 50
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 143 42
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 143 50
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 143 49
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 143 38
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 143 42
4 PME CNP 081 Excavator 1 112 112 40 0 143 50
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 143 42
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 143 51
6 Concrete Breaking 8/2018-11/2020 1 1 PME CNP 028 Breaker (excavator mounted, hydraulic) 1 122 122 39 0 57 68 68 70 Complied
Activities 7 to 8 being mutually exclusive (not occurring concurrently with) from Activities 1 to 6
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 143 49
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 143 52
3 PME CNP 081 Excavator 1 112 112 40 0 143 50
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 143 42
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 143 50
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 143 49
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 143 38
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 143 42
4 PME CNP 081 Excavator 1 112 112 40 0 143 50
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 143 42
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 143 51
1 PME CNP 004 Asphalt Paver 1 109 109 50 0 57 56
2 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 57 52
3 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 57 47
4 PME CNP 184 Road Planer 1 111 111 50 0 57 58
5 PME CNP 185 Road Roller (Pneumatic Tyred Roller) 1 108 108 50 0 57 55
6 PME CNP 186 Roller (vibratory) 1 108 108 50 0 57 55
Notes : 1. SPME = Specified Powered Mechanical Equipment ; SWL = Sound Power Level ; CNL = Corrected Noise Level 3. * Noise Mitigation Measures = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction]
2. Combined SWL = SWL + 10 log (Quantity) ; Predicted CNL (Individual) = Combined SWL + 10 log (PME % On-time) + Correction (Measures) - 20 log (R) - 8 + Facade Reflection - 10 [where Facade Reflection = 3] ; Predicted CNL (Overall) = 10 log [∑10(Predicted CNL (Individual) /10)
]
70 Complied8 Flexible Pavement 8/2018-11/2020 1 63
70 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 55 70 Complied
7
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 56
70 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 55 70 Complied
5
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 56
70 Complied4
Footbridge
Segment
Installation /
Staircase and Lift
Shaft Construction
7/2019-11/20201 58
Complied
3
Drainage,
Sewerage and
Water Mains
8/2018-11/2020
1 60 70 Complied
2 60 70 Complied
Predicted CNL, dB(A) Statutory Noise Limit, dB(A)
Complied70
2
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019
1 51
5 61 70
4 60 70 Complied
1 Utilities Diversion 3/2018-6/2019 1 54
3 57
70 Complied
2 62 70 Complied
70 Complied
Activity Period
Powered Mechanical Equipment (PME)PME %
On-time
Distance 'R'
(Source to Critical
NSR), m
Correction
(Noise Mitigation
Measures)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 9 of 36
NSR-3 : Hong Kong IVE (Lee Wai Lee) (Mitigated) Updated : 27-11-2018
Group Item ClassificationIdentification
CodeDescription Quantity
SWL,
dB(A)
Combined
SWL, dB(A)Individual Overall
Non-restricted Hours
(07:00-19:00)
Compliance
(CNL ≤ Noise Limit)
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 117 59
2 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 50 0 117 48
3 PME CNP 143 Light Good Vehicle (G.V.W. ≤ 5.5 tonnes) 1 101 101 50 0 117 52
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 117 53
5 PME CNP 185 Road Roller 2 108 111 50 0 117 62
1 PME CNP 072 Drilling rig (Pre-drilling) 1 110 110 60 0 141 60
2 PME CNP 105 Grout mixer 1 90 90 40 0 141 38
3 PME CNP 106 Grout pump 1 105 105 40 0 141 53
5 PME CNP 281 Water pump (electric) 1 88 88 60 0 141 38
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 8 102 111 35 -5 141 53
2 PME CNP 164 Bored Piling - Grab & Chisel 2 115 118 60 -5 141 63
3 PME CNP 165 Bored Piling - Oscillator 2 115 118 60 -5 141 63
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 2 100 103 60 0 141 53
5 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 141 55
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 141 53
7 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 141 45
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 -5 141 50
9 PME CNP 048 Mobile / crawler crane 2 112 115 35 -5 141 57
10 PME CNP 281 Water pump (electric) 2 88 91 60 0 141 41
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 141 60
2 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 141 55
3 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 141 63
4 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 141 53
5 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 141 45
6 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 -5 141 50
7 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 141 62
8 PME CNP 281 Water pump (electric) 2 88 91 60 0 141 41
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 141 55
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 -5 141 60
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 -5 141 60
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 141 50
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 141 52
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 141 50
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 141 42
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 141 52
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 141 59
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 141 38
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 4 104 110 35 -5 141 52
12 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 141 52
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 60 -5 141 55
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 141 50
15 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 141 42
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 141 52
17 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 141 59
18 PME CNP 281 Water pump (electric) 1 88 88 60 0 141 38
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 141 55
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 -5 141 60
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 -5 141 60
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 141 50
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 141 52
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 141 50
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 141 42
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 141 52
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 -5 141 54
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 141 38
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 -5 141 55
12 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 141 55
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 -5 141 58
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 141 53
15 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 141 45
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 141 55
17 PME CNP 048 Mobile / crawler crane 2 112 115 35 -5 141 57
18 PME CNP 281 Water pump (electric) 2 88 91 60 0 141 41
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 25 0 84 59
2 PME CNP 081 Excavator 1 112 112 30 -5 84 58
3 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 -5 84 55
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 25 0 84 55
5 PME CNP 186 Roller (vibratory) 1 108 108 25 0 84 58
6 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 84 48
1 SPME CNP 025 Breaker (hand-held, 20 kg ≤ mass ≤ 35 kg) 1 111 111 25 -5 84 56
2 SPME BS D6/33 Concrete lorry mixer 1 96 96 70 0 84 51
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 84 56
4 PME CNP 081 Excavator 1 112 112 25 -5 84 57
5 PME CNP 107 Generator (portable) - Welding set 1 100 100 50 0 84 54
6 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 35 0 84 54
7 PME CNP 186 Roller (vibratory) 1 108 108 25 0 84 58
8 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 84 48
1 PME CNP 021 Bar Bender and Cutter (electric) 1 90 90 100 0 141 42
2 SPME BS D6/33 Concrete lorry mixer 3 96 101 50 0 141 50
3 PME CNP 048 Crawler Crane 1 112 112 80 -5 141 58
4 PME CNP 056 Cutter (circular, steel, electric) 1 112 112 60 -5 141 57
5 PME CNP 081 Excavator 1 112 112 80 -5 141 58
6 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 141 54
7 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 50 0 141 51
8 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 141 49
2 1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 141 57 57 70 Complied
Activities 5 to 6 being mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 141 59
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 -5 141 57
3 PME CNP 081 Excavator 1 112 112 40 0 141 60
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 141 52
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 141 60
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 141 59
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 141 48
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 141 52
4 PME CNP 081 Excavator 1 112 112 40 0 141 60
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 141 52
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 141 61
6 Concrete Breaking 8/2018-11/2020 1 1 PME CNP 028 Breaker (excavator mounted, hydraulic) 1 122 122 39 -5 84 69 69 70 Complied
Activities 7 to 8 being mutually exclusive (not occurring concurrently with) from Activities 1 to 6
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 141 59
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 -5 141 57
3 PME CNP 081 Excavator 1 112 112 40 0 141 60
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 141 52
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 141 60
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 141 59
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 141 48
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 141 52
4 PME CNP 081 Excavator 1 112 112 40 0 141 60
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 141 52
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 141 61
1 PME CNP 004 Asphalt Paver 1 109 109 50 0 84 63
2 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 84 59
3 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 84 54
4 PME CNP 184 Road Planer 1 111 111 50 0 84 65
5 PME CNP 185 Road Roller (Pneumatic Tyred Roller) 1 108 108 50 0 84 62
6 PME CNP 186 Roller (vibratory) 1 108 108 50 0 84 62
Notes : 1. SPME = Specified Powered Mechanical Equipment ; SWL = Sound Power Level ; CNL = Corrected Noise Level 3. * Noise Mitigation Measures = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction]
2. Combined SWL = SWL + 10 log (Quantity) ; Predicted CNL (Individual) = Combined SWL + 10 log (PME % On-time) + Correction (Measures) - 20 log (R) - 8 + Facade Reflection [where Facade Reflection = 3] ; Predicted CNL (Overall) = 10 log [∑10(Predicted CNL (Individual) /10)
]
70 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 65 70 Complied
7
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 65
70 Complied
5
28/2018-12/2019
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 65 70 Complied
70 Complied
8 Flexible Pavement 8/2018-11/2020 1 69 70 Complied
4
Footbridge
Segment
Installation /
Staircase and Lift
Shaft Construction
7/2019-11/20201 64
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
65
Complied
3
Drainage,
Sewerage and
Water Mains
8/2018-11/2020
1 64 70 Complied
2 64 70 Complied
Predicted CNL, dB(A) Statutory Noise Limit, dB(A)
Complied70
2
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019
1 61
5 67 70
4 67 70 Complied
1 Utilities Diversion 3/2018-6/2019 1 64
3 67
70 Complied
2 67 70 Complied
70 Complied
Activity Period
Powered Mechanical Equipment (PME)PME %
On-time
Distance 'R'
(Source to Critical
NSR), m
Correction
(Noise Mitigation
Measures)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 10 of 36
NSR-4 : Tiu Keng Leng Public Library (Mitigated) Updated : 27-11-2018
Group Item ClassificationIdentification
CodeDescription Quantity
SWL,
dB(A)
Combined
SWL, dB(A)Individual Overall
Non-restricted Hours
(07:00-19:00)
Compliance
(CNL ≤ Noise Limit)
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 99 50
2 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 50 0 99 39
3 PME CNP 143 Light Good Vehicle (G.V.W. ≤ 5.5 tonnes) 1 101 101 50 0 99 43
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 99 45
5 PME CNP 185 Road Roller 2 108 111 50 0 99 53
1 PME CNP 072 Drilling rig (Pre-drilling) 1 110 110 60 0 121 51
2 PME CNP 105 Grout mixer 1 90 90 40 0 121 29
3 PME CNP 106 Grout pump 1 105 105 40 0 121 44
5 PME CNP 281 Water pump (electric) 1 88 88 60 0 121 29
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 8 102 111 35 0 121 50
2 PME CNP 164 Bored Piling - Grab & Chisel 2 115 118 60 0 121 59
3 PME CNP 165 Bored Piling - Oscillator 2 115 118 60 0 121 59
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 2 100 103 60 0 121 44
5 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 121 46
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 121 44
7 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 121 36
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 121 46
9 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 121 54
10 PME CNP 281 Water pump (electric) 2 88 91 60 0 121 32
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 121 52
2 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 121 46
3 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 121 54
4 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 121 44
5 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 121 36
6 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 121 46
7 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 121 54
8 PME CNP 281 Water pump (electric) 2 88 91 60 0 121 32
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 121 47
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 0 121 56
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 0 121 56
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 121 41
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 121 43
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 121 41
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 121 33
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 121 43
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 121 51
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 121 29
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 4 104 110 35 0 121 49
12 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 121 43
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 60 0 121 51
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 121 41
15 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 121 33
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 121 43
17 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 121 51
18 PME CNP 281 Water pump (electric) 1 88 88 60 0 121 29
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 121 47
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 0 121 56
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 0 121 56
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 121 41
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 121 43
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 121 41
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 121 33
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 121 43
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 121 51
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 121 29
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 121 52
12 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 121 46
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 121 54
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 121 44
15 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 121 36
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 121 46
17 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 121 54
18 PME CNP 281 Water pump (electric) 2 88 91 60 0 121 32
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 25 0 88 48
2 PME CNP 081 Excavator 1 112 112 30 0 88 53
3 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 88 49
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 25 0 88 45
5 PME CNP 186 Roller (vibratory) 1 108 108 25 0 88 48
6 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 88 37
1 SPME CNP 025 Breaker (hand-held, 20 kg ≤ mass ≤ 35 kg) 1 111 111 25 0 88 51
2 SPME BS D6/33 Concrete lorry mixer 1 96 96 70 0 88 41
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 88 46
4 PME CNP 081 Excavator 1 112 112 25 0 88 52
5 PME CNP 107 Generator (portable) - Welding set 1 100 100 50 0 88 43
6 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 35 0 88 44
7 PME CNP 186 Roller (vibratory) 1 108 108 25 0 88 48
8 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 88 37
1 PME CNP 021 Bar Bender and Cutter (electric) 1 90 90 100 0 121 33
2 SPME BS D6/33 Concrete lorry mixer 3 96 101 50 0 121 41
3 PME CNP 048 Crawler Crane 1 112 112 80 0 121 54
4 PME CNP 056 Cutter (circular, steel, electric) 1 112 112 60 0 121 53
5 PME CNP 081 Excavator 1 112 112 80 0 121 54
6 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 121 45
7 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 50 0 121 42
8 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 121 40
2 1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 121 48 48 70 Complied
Activities 5 to 6 being mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 121 50
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 121 53
3 PME CNP 081 Excavator 1 112 112 40 0 121 51
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 121 43
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 121 51
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 121 50
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 121 39
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 121 43
4 PME CNP 081 Excavator 1 112 112 40 0 121 51
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 121 43
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 121 52
6 Concrete Breaking 8/2018-11/2020 1 1 PME CNP 028 Breaker (excavator mounted, hydraulic) 1 122 122 39 0 88 64 64 70 Complied
Activities 7 to 8 being mutually exclusive (not occurring concurrently with) from Activities 1 to 6
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 121 50
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 121 53
3 PME CNP 081 Excavator 1 112 112 40 0 121 51
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 121 43
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 121 51
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 121 50
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 121 39
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 121 43
4 PME CNP 081 Excavator 1 112 112 40 0 121 51
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 121 43
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 121 52
1 PME CNP 004 Asphalt Paver 1 109 109 50 0 88 52
2 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 88 48
3 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 88 43
4 PME CNP 184 Road Planer 1 111 111 50 0 88 54
5 PME CNP 185 Road Roller (Pneumatic Tyred Roller) 1 108 108 50 0 88 51
6 PME CNP 186 Roller (vibratory) 1 108 108 50 0 88 51
Notes : 1. SPME = Specified Powered Mechanical Equipment ; SWL = Sound Power Level ; CNL = Corrected Noise Level 3. * Noise Mitigation Measures = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction]
2. Combined SWL = SWL + 10 log (Quantity) ; Predicted CNL (Individual) = Combined SWL + 10 log (PME % On-time) + Correction (Measures) - 20 log (R) - 8 + Facade Reflection - 10 [where Facade Reflection = 3] ; Predicted CNL (Overall) = 10 log [∑10(Predicted CNL (Individual) /10)
]
70 Complied8 Flexible Pavement 8/2018-11/2020 1 59
70 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 57 70 Complied
7
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 58
70 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 57 70 Complied
5
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 58
2
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
70 Complied4
Footbridge
Segment
Installation /
Staircase and Lift
Shaft Construction
7/2019-11/20201 59
70 Complied
2 57 70 Complied
3
Drainage,
Sewerage and
Water Mains
8/2018-11/2020
1 56
Predicted CNL, dB(A)
8/2018-12/2019
1
2
3
5
4 62
63
52
Statutory Noise Limit, dB(A)
1
Distance 'R'
(Source to Critical
NSR), m
PME %
On-time
Correction
(Noise Mitigation
Measures)
Complied56 70
Activity Period
Powered Mechanical Equipment (PME)
Utilities Diversion 3/2018-6/2019 1
70 Complied
70 Complied
59 70 Complied
70 Complied
63 70 Complied
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 11 of 36
NSR-5 (i.e. N7603 under the associated EIA Report & CM8 under the Noise Mitigation Plan by Contract : NE/2015/02) : Park Central, Tower 6 (Mitigated) Updated : 27-11-2018
Group Item ClassificationIdentification
CodeDescription Quantity
SWL,
dB(A)
Combined
SWL, dB(A)Individual Overall
Non-restricted Hours
(07:00-19:00)
Compliance
(CNL ≤ Noise Limit)
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 110 59
2 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 50 0 110 48
3 PME CNP 143 Light Good Vehicle (G.V.W. ≤ 5.5 tonnes) 1 101 101 50 0 110 52
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 110 54
5 PME CNP 185 Road Roller 2 108 111 50 0 110 62
1 PME CNP 072 Drilling rig (Pre-drilling) 1 110 110 60 0 109 62
2 PME CNP 105 Grout mixer 1 90 90 40 0 109 40
3 PME CNP 106 Grout pump 1 105 105 40 0 109 55
5 PME CNP 281 Water pump (electric) 1 88 88 60 0 109 40
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 8 102 111 35 0 109 61
2 PME CNP 164 Bored Piling - Grab & Chisel 2 115 118 60 -5 109 65
3 PME CNP 165 Bored Piling - Oscillator 2 115 118 60 -5 109 65
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 2 100 103 60 0 109 55
5 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 109 57
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 109 55
7 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 109 47
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 109 57
9 PME CNP 048 Mobile / crawler crane 2 112 115 35 -5 109 60
10 PME CNP 281 Water pump (electric) 2 88 91 60 0 109 43
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 109 63
2 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 109 57
3 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 109 65
4 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 109 55
5 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 109 47
6 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 109 57
7 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 109 65
8 PME CNP 281 Water pump (electric) 2 88 91 60 0 109 43
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 109 58
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 -5 109 62
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 -5 109 62
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 109 52
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 109 54
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 109 52
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 109 44
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 109 54
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 109 62
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 109 40
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 4 104 110 35 0 109 60
12 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 109 54
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 60 0 109 62
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 109 52
15 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 109 44
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 109 54
17 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 109 62
18 PME CNP 281 Water pump (electric) 1 88 88 60 0 109 40
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 109 58
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 -5 109 62
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 -5 109 62
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 109 52
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 109 54
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 109 52
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 109 44
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 109 54
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 109 62
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 109 40
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 109 63
12 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 109 57
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 -5 109 60
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 109 55
15 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 109 47
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 -5 109 52
17 PME CNP 048 Mobile / crawler crane 2 112 115 35 -5 109 60
18 PME CNP 281 Water pump (electric) 2 88 91 60 0 109 43
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 25 0 61 61
2 PME CNP 081 Excavator 1 112 112 30 0 61 66
3 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 -5 61 57
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 25 0 61 58
5 PME CNP 186 Roller (vibratory) 1 108 108 25 0 61 61
6 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 61 50
1 SPME CNP 025 Breaker (hand-held, 20 kg ≤ mass ≤ 35 kg) 1 111 111 25 -5 61 59
2 SPME BS D6/33 Concrete lorry mixer 1 96 96 70 0 61 54
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 61 59
4 PME CNP 081 Excavator 1 112 112 25 0 61 65
5 PME CNP 107 Generator (portable) - Welding set 1 100 100 50 0 61 56
6 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 35 0 61 57
7 PME CNP 186 Roller (vibratory) 1 108 108 25 0 61 61
8 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 61 50
1 PME CNP 021 Bar Bender and Cutter (electric) 1 90 90 100 0 109 44
2 SPME BS D6/33 Concrete lorry mixer 3 96 101 50 0 109 52
3 PME CNP 048 Crawler Crane 1 112 112 80 0 109 65
4 PME CNP 056 Cutter (circular, steel, electric) 1 112 112 60 0 109 64
5 PME CNP 081 Excavator 1 112 112 80 0 109 65
6 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 109 56
7 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 50 0 109 53
8 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 109 51
2 1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 109 59 59 75 Complied
Activities 5 to 6 being mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 109 61
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 109 64
3 PME CNP 081 Excavator 1 112 112 40 0 109 62
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 109 54
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 109 62
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 109 61
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 109 50
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 109 54
4 PME CNP 081 Excavator 1 112 112 40 0 109 62
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 109 54
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 109 63
6 Concrete Breaking 8/2018-11/2020 1 1 PME CNP 028 Breaker (excavator mounted, hydraulic) 1 122 122 39 -5 61 72 72 75 Complied
Activities 7 to 8 being mutually exclusive (not occurring concurrently with) from Activities 1 to 6
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 109 61
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 109 64
3 PME CNP 081 Excavator 1 112 112 40 0 109 62
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 109 54
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 109 62
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 109 61
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 109 50
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 109 54
4 PME CNP 081 Excavator 1 112 112 40 0 109 62
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 109 54
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 109 63
1 PME CNP 004 Asphalt Paver 1 109 109 50 0 61 65
2 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 61 61
3 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 61 56
4 PME CNP 184 Road Planer 1 111 111 50 0 61 67
5 PME CNP 185 Road Roller (Pneumatic Tyred Roller) 1 108 108 50 0 61 64
6 PME CNP 186 Roller (vibratory) 1 108 108 50 0 61 64
Notes : 1. SPME = Specified Powered Mechanical Equipment ; SWL = Sound Power Level ; CNL = Corrected Noise Level 3. * Noise Mitigation Measures = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction]
2. Combined SWL = SWL + 10 log (Quantity) ; Predicted CNL (Individual) = Combined SWL + 10 log (PME % On-time) + Correction (Measures) - 20 log (R) - 8 + Facade Reflection [where Facade Reflection = 3] ; Predicted CNL (Overall) = 10 log [∑10(Predicted CNL (Individual) /10)
]
75 Complied8 Flexible Pavement 8/2018-11/2020 1 72
75 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 68 75 Complied
7
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 69
75 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 68 75 Complied
5
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 69
Complied5
Complied
7570
75
8/2018-12/2019
70
1 69
2 75 Complied
75
Predicted CNL, dB(A) Statutory Noise Limit, dB(A)
Complied
Complied
Complied
75
75
Complied
Complied7570
63 75
75 Complied4
Footbridge
Segment
Installation /
Staircase and Lift
Shaft Construction
7/2019-11/20201 70
65
2 70
2
69
1
4
3
3
1 Utilities Diversion 3/2018-6/2019 1
Drainage,
Sewerage and
Water Mains
8/2018-11/2020
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
Activity Period
Powered Mechanical Equipment (PME)PME %
On-time
Distance 'R'
(Source to Critical
NSR), m
Correction
(Noise Mitigation
Measures)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 12 of 36
NSR-6 (i.e. N7001 under the associated EIA Report) : Park Central, Central Heights (Mitigated) Updated : 27-11-2018
Group Item ClassificationIdentification
CodeDescription Quantity
SWL,
dB(A)
Combined
SWL, dB(A)Individual Overall
Non-restricted Hours
(07:00-19:00)
Compliance
(CNL ≤ Noise Limit)
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 300 50
2 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 50 0 300 39
3 PME CNP 143 Light Good Vehicle (G.V.W. ≤ 5.5 tonnes) 1 101 101 50 0 300 43
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 300 45
5 PME CNP 185 Road Roller 2 108 111 50 0 300 53
1 PME CNP 072 Drilling rig (Pre-drilling) 1 110 110 60 0 294 53
2 PME CNP 105 Grout mixer 1 90 90 40 0 294 32
3 PME CNP 106 Grout pump 1 105 105 40 0 294 47
5 PME CNP 281 Water pump (electric) 1 88 88 60 0 294 31
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 8 102 111 35 0 294 52
2 PME CNP 164 Bored Piling - Grab & Chisel 2 115 118 60 0 294 61
3 PME CNP 165 Bored Piling - Oscillator 2 115 118 60 0 294 61
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 2 100 103 60 0 294 46
5 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 294 48
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 294 47
7 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 294 39
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 294 49
9 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 294 56
10 PME CNP 281 Water pump (electric) 2 88 91 60 0 294 34
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 294 54
2 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 294 48
3 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 294 56
4 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 294 47
5 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 294 39
6 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 294 49
7 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 294 56
8 PME CNP 281 Water pump (electric) 2 88 91 60 0 294 34
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 294 49
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 0 294 58
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 0 294 58
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 294 43
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 294 45
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 294 44
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 294 36
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 294 46
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 294 53
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 294 31
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 4 104 110 35 0 294 51
12 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 294 45
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 60 0 294 53
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 294 44
15 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 294 36
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 294 46
17 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 294 53
18 PME CNP 281 Water pump (electric) 1 88 88 60 0 294 31
1 PME CNP 002 Air compressor (10m3/min < air flow ≤ 30m
3/min) 4 102 108 35 0 294 49
2 PME CNP 164 Bored Piling - Grab & Chisel 1 115 115 60 0 294 58
3 PME CNP 165 Bored Piling - Oscillator 1 115 115 60 0 294 58
4 PME CNP 166 Bored Piling - Reverse Circulation Drill 1 100 100 60 0 294 43
5 SPME BS D6/33 Concrete lorry mixer 4 96 102 60 0 294 45
6 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 20 0 294 44
7 PME CNP 082 Excavator (mini-robot mounted) 1 94 94 40 0 294 36
8 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 294 46
9 PME CNP 048 Mobile / crawler crane 1 112 112 35 0 294 53
10 PME CNP 281 Water pump (electric) 1 88 88 60 0 294 31
11 PME CNP 003 Air compressor (air flow > 30 m3/min) 8 104 113 35 0 294 54
12 SPME BS D6/33 Concrete lorry mixer 8 96 105 60 0 294 48
13 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 2 110 113 60 0 294 56
14 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 20 0 294 47
15 PME CNP 082 Excavator (mini-robot mounted) 2 94 97 40 0 294 39
16 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 294 49
17 PME CNP 048 Mobile / crawler crane 2 112 115 35 0 294 56
18 PME CNP 281 Water pump (electric) 2 88 91 60 0 294 34
1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 25 0 80 59
2 PME CNP 081 Excavator 1 112 112 30 0 80 64
3 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 2 100 103 100 0 80 60
4 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 25 0 80 56
5 PME CNP 186 Roller (vibratory) 1 108 108 25 0 80 59
6 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 80 48
1 SPME CNP 025 Breaker (hand-held, 20 kg ≤ mass ≤ 35 kg) 1 111 111 25 0 80 62
2 SPME BS D6/33 Concrete lorry mixer 1 96 96 70 0 80 51
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 80 57
4 PME CNP 081 Excavator 1 112 112 25 0 80 63
5 PME CNP 107 Generator (portable) - Welding set 1 100 100 50 0 80 54
6 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 35 0 80 54
7 PME CNP 186 Roller (vibratory) 1 108 108 25 0 80 59
8 PME CNP 283 Water pump (submersible, electric) 4 85 91 100 0 80 48
1 PME CNP 021 Bar Bender and Cutter (electric) 1 90 90 100 0 294 36
2 SPME BS D6/33 Concrete lorry mixer 3 96 101 50 0 294 43
3 PME CNP 048 Crawler Crane 1 112 112 80 0 294 57
4 PME CNP 056 Cutter (circular, steel, electric) 1 112 112 60 0 294 55
5 PME CNP 081 Excavator 1 112 112 80 0 294 57
6 PME CNP 145 Lorry with Crane (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 294 48
7 SPME CNP 173 Poker (vibratory, hand-held, electric) 1 102 102 50 0 294 45
8 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 294 43
2 1 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 2 105 108 50 0 294 51 51 75 Complied
Activities 5 to 6 being mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 294 53
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 294 56
3 PME CNP 081 Excavator 1 112 112 40 0 294 54
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 294 46
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 294 54
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 294 53
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 294 42
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 294 45
4 PME CNP 081 Excavator 1 112 112 40 0 294 54
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 294 46
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 294 55
6 Concrete Breaking 8/2018-11/2020 1 1 PME CNP 028 Breaker (excavator mounted, hydraulic) 1 122 122 39 0 80 75 75 75 Complied
Activities 7 to 8 being mutually exclusive (not occurring concurrently with) from Activities 1 to 6
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 294 53
2 PME CNP 072 Drilling rig (Pre-bored Sockette H Pile) 1 110 110 100 0 294 56
3 PME CNP 081 Excavator 1 112 112 40 0 294 54
4 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 294 46
5 PME CNP 048 Mobile / crawler crane 1 112 112 40 0 294 54
1 PME CNP 003 Air compressor (air flow > 30 m3/min) 2 104 107 100 0 294 53
2 SPME BS D6/33 Concrete lorry mixer 2 96 99 50 0 294 42
3 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 30 0 294 45
4 PME CNP 081 Excavator 1 112 112 40 0 294 54
5 PME CNP 102 Generator (silenced, 75 dB(A) at 7m) 1 100 100 100 0 294 46
6 PME CNP 048 Mobile / crawler crane 1 112 112 50 0 294 55
1 PME CNP 004 Asphalt Paver 1 109 109 50 0 80 63
2 PME CNP 068 Dump Truck (5.5 tonnes < G.V.W. ≤ 38 tonnes) 1 105 105 50 0 80 59
3 PME CNP 168 Power Pack for Hand-held Items 1 100 100 50 0 80 54
4 PME CNP 184 Road Planer 1 111 111 50 0 80 65
5 PME CNP 185 Road Roller (Pneumatic Tyred Roller) 1 108 108 50 0 80 62
6 PME CNP 186 Roller (vibratory) 1 108 108 50 0 80 62
Notes : 1. SPME = Specified Powered Mechanical Equipment ; SWL = Sound Power Level ; CNL = Corrected Noise Level 3. * Noise Mitigation Measures = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction]
2. Combined SWL = SWL + 10 log (Quantity) ; Predicted CNL (Individual) = Combined SWL + 10 log (PME % On-time) + Correction (Measures) - 20 log (R) - 8 + Facade Reflection [where Facade Reflection = 3] ; Predicted CNL (Overall) = 10 log [∑10(Predicted CNL (Individual) /10)
]
75 Complied8 Flexible Pavement 8/2018-11/2020 1 70
75 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 59 75 Complied
7
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 60
75 Complied
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 2 59 75 Complied
5
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019 1 60
75 Complied4
Footbridge
Segment
Installation /
Staircase and Lift
Shaft Construction
7/2019-11/20201 61
75 Complied
2 67 75 Complied
3
Drainage,
Sewerage and
Water Mains
8/2018-11/2020
1 67
Utilities Diversion 3/2018-6/2019 1 56
Predicted CNL, dB(A) Statutory Noise Limit, dB(A)
Activity Period
Powered Mechanical Equipment (PME)PME %
On-time
Distance 'R'
(Source to Critical
NSR), m
Correction
(Noise Mitigation
Measures)
Complied751
2
Bored Piling / Pre-
bored Socketed H
Pile / Pre-drilling
8/2018-12/2019
1 54
2 66
3 61
4 64
75 Complied
5 65 75 Complied
75 Complied
75 Complied
75 Complied
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 13 of 36
Table 4 Predicted Monthly Construction Noise Levels (Mitigated)
Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1 1 Utilities Diversion 58 - 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 2
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
66 - 0 0 0 0 0 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 0 0 0 0 0 0 0 0 0 0 0
3 2Drainage, Sewerage and
Water Mains64 - 0 0 0 0 0 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64
4 1
Footbridge Segment
Installation / Staircase and
Lift Shaft Construction
62 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62
58 58 58 58 58 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 66 66 66 66 66 66 66 66 66 66 66
5 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
61 - 0 0 0 0 0 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61 0 0 0 0 0 0 0 0 0 0 0
6 1 Concrete Breaking 71 - 0 0 0 0 0 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71
0 0 0 0 0 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71 71
7 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
61 - 0 0 0 0 0 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61 0 0 0 0 0 0 0 0 0 0 0
8 1 Flexible Pavement 66 - 0 0 0 0 0 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66
0 0 0 0 0 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 66 66
75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
Notes :1. CNL = Corrected Noise Level ; C = Complied ; E = Exceeded
2. For any multi-group construcction activity (with only 1 group operating at a time), only the group striking the highest Predicted CNL has been included in the calculations above.
3. * NB = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction] ; Activity groups to adopt NB are detailed in Table 3.
4. Activities 5 to 6 are mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8.
Activities 7 to 8 are mutually exclusive (not occurring concurrently with) from Activities 1 to 6.
Statutory Noise Limit (07:00-19:00), dB(A)
Compliance (Combined CNLs for 'Activities 1 to 4 ; 5 to 6 ; 7 to 8' ≤ Statutory Noise Limit)
Construction Activity 2019 2020Noise
Mitigation
MeasuresNo. Group Description
Contract : NE/2017/02 ; Activities 5 to 6
Contract : NE/2017/02 ; Activities 7 to 8
Combined CNL, dB(A)
Combined CNL, dB(A)
Predicted CNL Allocation, dB(A)
2018Predicted CNL
(Mitigated),
dB(A)
Contract : NE/2017/02 ; Activities 1 to 4 Combined CNL, dB(A)
NSR-1 : Metrotown, Tower 1
Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1 1 Utilities Diversion 54 - 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 2
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
62 - 0 0 0 0 0 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62 0 0 0 0 0 0 0 0 0 0 0
3 2Drainage, Sewerage and
Water Mains60 - 0 0 0 0 0 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
4 1
Footbridge Segment
Installation / Staircase and
Lift Shaft Construction
58 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58
54 54 54 54 54 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 62 62 62 62 62 62 62 62 62 62 62
5 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
56 - 0 0 0 0 0 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 0 0 0 0 0 0 0 0 0 0 0
6 1 Concrete Breaking 68 - 0 0 0 0 0 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68
0 0 0 0 0 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68 68
7 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
56 - 0 0 0 0 0 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 0 0 0 0 0 0 0 0 0 0 0
8 1 Flexible Pavement 63 - 0 0 0 0 0 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
0 0 0 0 0 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 63 63 63 63 63 63 63 63 63 63 63
70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70
C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
Notes :1. CNL = Corrected Noise Level ; C = Complied ; E = Exceeded
2. For any multi-group construcction activity (with only 1 group operating at a time), only the group striking the highest Predicted CNL has been included in the calculations above.
3. * NB = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction] ; Activity groups to adopt NB are detailed in Table 3.
4. Activities 5 to 6 are mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8.
Activities 7 to 8 are mutually exclusive (not occurring concurrently with) from Activities 1 to 6.
Statutory Noise Limit (07:00-19:00), dB(A)
Compliance (Combined CNLs for 'Activities 1 to 4 ; 5 to 6 ; 7 to 8' ≤ Statutory Noise Limit)
Construction Activity 2019 2020Noise
Mitigation
MeasuresNo. Group Description
Contract : NE/2017/02 ; Activities 5 to 6
Contract : NE/2017/02 ; Activities 7 to 8
Combined CNL, dB(A)
Combined CNL, dB(A)
Predicted CNL Allocation, dB(A)
2018Predicted CNL
(Mitigated),
dB(A)
Contract : NE/2017/02 ; Activities 1 to 4 Combined CNL, dB(A)
NSR-2 : Hong Kong Design Institute
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 14 of 36
Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1 1 Utilities Diversion 64 - 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 2
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
67 NB * 0 0 0 0 0 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 0 0 0 0 0 0 0 0 0 0 0
3 2Drainage, Sewerage and
Water Mains64 NB * 0 0 0 0 0 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64
4 1
Footbridge Segment
Installation / Staircase and
Lift Shaft Construction
64 NB * 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64
64 64 64 64 64 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 67 67 67 67 67 67 67 67 67 67 67
5 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
65 NB * 0 0 0 0 0 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 0 0 0 0 0 0 0 0 0 0 0
6 1 Concrete Breaking 69 NB * 0 0 0 0 0 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69
0 0 0 0 0 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 69 69 69 69 69 69 69 69 69 69 69
7 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
65 NB * 0 0 0 0 0 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 0 0 0 0 0 0 0 0 0 0 0
8 1 Flexible Pavement 69 - 0 0 0 0 0 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69
0 0 0 0 0 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 69 69 69 69 69 69 69 69 69 69 69
70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70
C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
Notes :1. CNL = Corrected Noise Level ; C = Complied ; E = Exceeded
2. For any multi-group construcction activity (with only 1 group operating at a time), only the group striking the highest Predicted CNL has been included in the calculations above.
3. * NB = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction] ; Activity groups to adopt NB are detailed in Table 3.
4. Activities 5 to 6 are mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8.
Activities 7 to 8 are mutually exclusive (not occurring concurrently with) from Activities 1 to 6.
Predicted CNL Allocation, dB(A)
2018Predicted CNL
(Mitigated),
dB(A)
Contract : NE/2017/02 ; Activities 1 to 4 Combined CNL, dB(A)
NSR-3 : Hong Kong IVE (Lee Wai Lee)
Statutory Noise Limit (07:00-19:00), dB(A)
Compliance (Combined CNLs for 'Activities 1 to 4 ; 5 to 6 ; 7 to 8' ≤ Statutory Noise Limit)
Construction Activity 2019 2020Noise
Mitigation
MeasuresNo. Group Description
Contract : NE/2017/02 ; Activities 5 to 6 Combined CNL, dB(A)
Contract : NE/2017/02 ; Activities 7 to 8 Combined CNL, dB(A)
Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1 1 Utilities Diversion 56 - 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 2
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
63 - 0 0 0 0 0 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 0 0 0 0 0 0 0 0 0 0 0
3 2Drainage, Sewerage and
Water Mains57 - 0 0 0 0 0 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57 57
4 1
Footbridge Segment
Installation / Staircase and
Lift Shaft Construction
59 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59
56 56 56 56 56 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 61 61 61 61 61 61 61 61 61 61 61
5 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
58 - 0 0 0 0 0 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 0 0 0 0 0 0 0 0 0 0 0
6 1 Concrete Breaking 64 - 0 0 0 0 0 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64
0 0 0 0 0 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 64 64 64 64 64 64 64 64 64 64 64
7 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
58 - 0 0 0 0 0 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 0 0 0 0 0 0 0 0 0 0 0
8 1 Flexible Pavement 59 - 0 0 0 0 0 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59
0 0 0 0 0 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62 62 59 59 59 59 59 59 59 59 59 59 59
70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70
C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
Notes :1. CNL = Corrected Noise Level ; C = Complied ; E = Exceeded
2. For any multi-group construcction activity (with only 1 group operating at a time), only the group striking the highest Predicted CNL has been included in the calculations above.
3. * NB = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction] ; Activity groups to adopt NB are detailed in Table 3.
4. Activities 5 to 6 are mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8.
Activities 7 to 8 are mutually exclusive (not occurring concurrently with) from Activities 1 to 6.
Predicted CNL Allocation, dB(A)
2018Predicted CNL
(Mitigated),
dB(A)
Contract : NE/2017/02 ; Activities 1 to 4 Combined CNL, dB(A)
NSR-4 : Tiu Keng Leng Public Library
Statutory Noise Limit (07:00-19:00), dB(A)
Compliance (Combined CNLs for 'Activities 1 to 4 ; 5 to 6 ; 7 to 8' ≤ Statutory Noise Limit)
Construction Activity 2019 2020Noise
Mitigation
MeasuresNo. Group Description
Contract : NE/2017/02 ; Activities 5 to 6
Contract : NE/2017/02 ; Activities 7 to 8
Combined CNL, dB(A)
Combined CNL, dB(A)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 15 of 36
Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1 1 Utilities Diversion 65 - 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 2
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
70 NB * 0 0 0 0 0 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 0 0 0 0 0 0 0 0 0 0 0
3 2Drainage, Sewerage and
Water Mains69 NB * 0 0 0 0 0 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69
4 1
Footbridge Segment
Installation / Staircase and
Lift Shaft Construction
70 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70
65 65 65 65 65 73 73 73 73 73 73 73 73 73 73 73 74 74 74 74 74 74 73 73 73 73 73 73 73 73 73 73 73
5 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
69 - 0 0 0 0 0 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 0 0 0 0 0 0 0 0 0 0 0
6 1 Concrete Breaking 72 NB * 0 0 0 0 0 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72
0 0 0 0 0 74 74 74 74 74 74 74 74 74 74 74 74 74 74 74 74 74 72 72 72 72 72 72 72 72 72 72 72
7 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
69 - 0 0 0 0 0 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 69 0 0 0 0 0 0 0 0 0 0 0
8 1 Flexible Pavement 72 - 0 0 0 0 0 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72
0 0 0 0 0 74 74 74 74 74 74 74 74 74 74 74 74 74 74 74 74 74 72 72 72 72 72 72 72 72 72 72 72
75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
(NE/2015/02 + NE/2015/03) 71 71 71 71 72 70 70 70 70 70 70 70 70 70 61 61 61 61 61 61 - - - - - - - - - - - - -
72 72 72 72 73 75 75 75 75 75 75 75 75 75 74 74 74 74 74 74 74 74 73 73 73 73 73 73 73 73 73 73 73
C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
Notes :1. CNL = Corrected Noise Level ; C = Complied ; E = Exceeded
2. For any multi-group construcction activity (with only 1 group operating at a time), only the group striking the highest Predicted CNL has been included in the calculations above.
3. * NB = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction] ; Activity groups to adopt NB are detailed in Table 3.
4. Activities 5 to 6 are mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8.
Activities 7 to 8 are mutually exclusive (not occurring concurrently with) from Activities 1 to 6.
5. Cumulative CNL = Logarithmic sum of [The highest Combined CNL among Activities 1 to 4, 5 to 6, 7 to 8 (in Green)] and [Combined CNL (in Pale Blue)]
Contract : NE/2017/02 ; Activities 5 to 6
Contract : NE/2017/02 ; Activities 7 to 8
Combined CNL, dB(A)
Combined CNL, dB(A)
Compliance (Cumulative
CNL ≤ Statutory Noise Limit)
Predicted CNL Allocation, dB(A)
2018Predicted CNL
(Mitigated),
dB(A)
Cumulative CNL, dB(A)
Combined CNL, dB(A)
Combined CNL, dB(A)Contract :
Statutory Noise Limit (07:00-19:00), dB(A)
Compliance (Combined CNLs for 'Activities 1 to 4 ; 5 to 6 ; 7 to 8' ≤ Statutory Noise Limit)
Construction Activity 2019
Contract :NE/2017/02 + (NE/2015/02
+ NE/2015/03)
Contract : NE/2017/02 ; Activities 1 to 4
2020
NSR-5 (i.e. N7603, EIA Report) : Park Central, Tower 6
Noise
Mitigation
MeasuresNo. Group Description
Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov Dec J an Feb Mar Ap r May J u n J u l Au g S ep Oct Nov
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1 1 Utilities Diversion 56 - 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 2
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
66 - 0 0 0 0 0 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 0 0 0 0 0 0 0 0 0 0 0
3 2Drainage, Sewerage and
Water Mains67 - 0 0 0 0 0 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67
4 1
Footbridge Segment
Installation / Staircase and
Lift Shaft Construction
61 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61 61
56 56 56 56 56 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 68 68 68 68 68 68 68 68 68 68 68
5 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
60 - 0 0 0 0 0 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 0 0 0 0 0 0 0 0 0 0 0
6 1 Concrete Breaking 75 - 0 0 0 0 0 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
0 0 0 0 0 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
7 1
Bored Piling / Pre-bored
Socketed H Pile / Pre-
drilling
60 - 0 0 0 0 0 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 0 0 0 0 0 0 0 0 0 0 0
8 1 Flexible Pavement 70 - 0 0 0 0 0 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70
0 0 0 0 0 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70
75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
Notes :1. CNL = Corrected Noise Level ; C = Complied ; E = Exceeded
2. For any multi-group construcction activity (with only 1 group operating at a time), only the group striking the highest Predicted CNL has been included in the calculations above.
3. * NB = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction] ; Activity groups to adopt NB are detailed in Table 3.
4. Activities 5 to 6 are mutually exclusive (not occurring concurrently with) from Activities 1 to 4, 7 to 8.
Activities 7 to 8 are mutually exclusive (not occurring concurrently with) from Activities 1 to 6.
Statutory Noise Limit (07:00-19:00), dB(A)
Compliance (Combined CNLs for 'Activities 1 to 4 ; 5 to 6 ; 7 to 8' ≤ Statutory Noise Limit)
2019
Contract : NE/2017/02 ; Activities 1 to 4 Combined CNL, dB(A)
Contract : NE/2017/02 ; Activities 5 to 6
Contract : NE/2017/02 ; Activities 7 to 8
Combined CNL, dB(A)
Combined CNL, dB(A)
2020Noise
Mitigation
Measures
NSR-6 (i.e. N7001, EIA Report) : Park Central, Central Heights
Description
Construction Activity
No. Group
Predicted CNL Allocation, dB(A)
2018Predicted CNL
(Mitigated),
dB(A)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 16 of 36
2.4 Noise Mitigation Measures (Construction Noise)
A summary of the proposed noise mitigation measures for this NMP is shown in Table 5 below. Specific assignment of the noise mitigation measures (noise barriers) to particular PMEs is included in Table 3 above. Table 5 Summary of Proposed Noise Mitigation Measures
Detailed selection and design of the engineering noise mitigation measures (e.g. greater setback distance, screening structures like noise barriers or noise enclosures etc.) are to be reviewed upon further refinement of the plants and site constraints with the project team for future NMP revision(s) and incorporation in the associated EM&A monitoring report(s). Other than these engineering noise mitigation measures, some practicable but administrative means can be like rescheduling the works program to prevent noisy construction activities during the examination periods as well as further restriction on PME % On-time. Alternatives such as installing acoustic mat covers or the like for major engine noise sources can be considered but are subject to other engineering limitations (e.g. engine cooling).
2.5 Noise Mitigation Measures (Road Traffic Noise)
Other than construction noise, specific direct and permanent noise mitigation measures for road traffic noise (operation phase) have been assigned under the associated EIA report in fulfilment of the relevant EIAO requirements. Those applicable for this Contract (within 300 m from the site boundary) are as follows.
NSR-1 NSR-2 NSR-3 NSR-4 NSR-5 NSR-6
Metrotown,
Tower 1
HK Design
Institute
HK IVE (Lee
Wai Lee)
Tiu Keng Leng
Public Library
Park Central,
Tower 6
Park Central,
Central Heights
1 Utilities Diversion - - - - - -
2Bored Piling / Pre-bored Socketed H Pile / Pre-
drilling- - NB * - NB * -
3 Drainage, Sewerage and Water Mains - - NB * - NB * -
4Footbridge Segment Installation / Staircase and
Lift Shaft Construction- - NB * - - -
5Bored Piling / Pre-bored Socketed H Pile / Pre-
drilling- - NB * - - -
6 Concrete Breaking - - NB * - NB * -
7Bored Piling / Pre-bored Socketed H Pile / Pre-
drilling- - NB * - - -
8 Flexible Pavement - - - - - -
75 70 70 70 75 75
Notes : 1. * NB = Noise barrier [with geometrical coverage blocking the line of sight to the subject NSR - offering 5 dB(A) noise reduction]
2. Activity groups to adopt NB are detailed in Table 3.
3. All noisy activities during the examination periods at NSR-2 and NSR-3 shall be suspended so as to meet the more stringent limit of 65 dB(A).
Noise Mitigation Measures
Statutory Noise Limit (07:00-19:00), dB(A)
No. Description
Construction Activity
LNS1 About 190m of Low Noise Surfacing on North and South Bound P2 Road
LNS2 About 240m of Low Noise Surfacing on East and West Bound Po Yap Road
LNS3 About 200m of Low Noise Surfacing on East and West Bound Po Yap Road
Noise Mitigation Measures (Low Noise Surfacing as shown in Figure 4, EP below)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 17 of 36
2.6 Construction Noise Levels & Compliance Status
A summary of the predicted combined CNLs and their noise compliance status is given in Table 6 below. Table 6 Summary of Predicted Construction Noise Levels
58 to 69 54 to 65 64 to 70 56 to 65 65 to 74 56 to 70
71 to 71 68 to 68 69 to 70 64 to 65 72 to 74 75 to 75
66 to 67 63 to 64 69 to 70 59 to 62 72 to 74 70 to 70
Statutory Noise Limit (07:00-19:00), dB(A)
Compliance
(Combined CNLs for 'Activities 1 to 4 ; 5 to 6 ; 7 to 8' ≤
Statutory Noise Limit)
Plot 2b
Plot 2c
Combined CNL Range (Activities 5 to 6), dB(A)
Combined CNL Range (Activities 7 to 8), dB(A)Plot 1c
Plot 1b Plot 1b
Plot 1c
Complied
7575 70 70 70 75
Complied Complied Complied Complied Complied
Park Central,
Central Heights
NSR-1 NSR-2 NSR-3 NSR-4 NSR-5 NSR-6
Metrotown,
Tower 1
HK Design
Institute
HK IVE (Lee
Wai Lee)
Plot 1aPlot 2a
Noise Sensitive Receivers
Combined CNL Range (Activities 1 to 4), dB(A)
Tiu Keng Leng
Public Library
Park Central,
Tower 6
Plot 1a
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 18 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 19 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 20 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 21 of 36
3. Conclusion
This Noise Mitigation Plan is prepared with respect to a number of stages involving some critical construction activities throughout the whole construction period such as the road construction, drainage works, footbridge construction as well as the subsequent landscaping works. Some practicable noise mitigation measures, both engineering and administrative, have been proposed and included into the construction noise level estimation. Results indicate that noise compliance (mitigated) with the statutory noise limit(s) has been struck at the selected NSR positions (i.e. The Combined CNLs at NSR-1 to NSR-6 would comply with the respective noise limits in Table 1 above while the Cumulative CNL at NSR-5 complies with the 75 dB(A) noise limit). Any excessive noise, if occurred, can be tackled by program rescheduling (e.g. during examination periods), further limiting the operation time (PME % On-time) and setbacks as well as installing screening covers (e.g. acoustic mats) onto major engine noise sources wherever appropriate.
4. References
1. Technical Memorandum on Noise from Construction Work other than Percussive Piling, 2nd Ed., Environmental Protection Department, 1996.
2. Technical Memorandum on Noise from Construction Work in Designated Areas, 2nd Ed., Environmental Protection Department, 2001.
3. British Standards BS 5229-1 (2009) : Code of Practice for Noise and Vibration Control on Construction and Open Sites – Part 1 : Noise, British Standards Institution.
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 22 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 23 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 24 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 25 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 26 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 27 of 36
Appendix A
Proposed Mitigation Measures
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 28 of 36
Proposed Mitigation Measures
Noise Barrier Mat Model No. CK2009
Noise Barrier Mat Model No. CK2009
(Laboratory Sound insulation Test Performance Rw = 15 dB)
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 29 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 30 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 31 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 32 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 33 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 34 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 35 of 36
FUGRO TECHNICAL SERVICES LIMITED
Fugro Development Centre, Tel : +852 2450 8233 5 Lok Yi Street, Tai Lam, Fax : +852 2450 6138 Tuen Mun, N.T., E-mail : [email protected] Hong Kong. Website : www.fugro.com
Report No.: 0005/18/ED/0004k
The copyright of this document is owned by Fugro Technical Services Limited. It may not be reproduced except with prior written approval from the Company.
A Fugro Group Company
Page 36 of 36