3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks...

12
8/19/2015 1 STORAGE TANK FIRES Dr Jeanne van Buren sr. consultant MARSH CONE ROOF TANKS 1 August 19, 2015 https://www.icheme.org/communities/subject_groups/safety%20and%20loss%20prevention/resourc es/hazards%20archive/~/media/Documents/Subject%20Groups/Safety_Loss_Prevention/Hazards %20Archive/XIX/XIX-Paper-63.pdf MARSH TANK DESIGN (1) • Cone roof tank Diameter <3 meter (no weak seam no ERV) Roof stays on tank – rocketing tank (video) Fixed system Diameter 3 meter but <18 meter Weak seam, no ERV and no Nitrogen supply Roof can separate from tank – mobile response and fixed system are both possible Diameter 3 meter but <18 meter With innerfloater – no mobile response 2 August 19, 2015

Transcript of 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks...

Page 1: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

1

STORAGE TANK FIRES

Dr Jeanne van Burensr. consultant

MARSH

CONE ROOF TANKS

1August 19, 2015

https://www.icheme.org/communities/subject_groups/safety%20and%20loss%20prevention/resources/hazards%20archive/~/media/Documents/Subject%20Groups/Safety_Loss_Prevention/Hazards

%20Archive/XIX/XIX-Paper-63.pdf

MARSH

TANK DESIGN (1)

• Cone roof tank

Diameter <3 meter (no weak seam no ERV)Roof stays on tank – rocketing tank (video)Fixed system

Diameter ≥3 meter but <18 meterWeak seam, no ERV and no Nitrogen supplyRoof can separate from tank – mobile response and fixed system are both possible

Diameter ≥3 meter but <18 meterWith innerfloater – no mobile response

2August 19, 2015

Page 2: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

2

MARSH

TANK DESIGN (2)

• Cone roof tank (continued)

Diameter > 18 meter with innerfloaterFixed system for rim seal fire or escalation scenario full surface fire

3August 19, 2015

MARSH

TANK DESIGN (3)

• Cone roof tank (continued)

Diameter max 60 meter (also with innerfloater)Secure Nitrogen BlanketingNO FIRE

PFB Design – JOIFFGuideline

Tank venting requirementsAPI 2000 venting design

4August 19, 2015

MARSH 5August 19, 2015

http://vapoloctemp.dynaglass.com/wp-content/uploads/2012/04/Brief-Information.pdf

http://vapoloctemp.dynaglass.com/wp-content/uploads/2012/04/Brief-Information.pdf

EFFECT FLOATING ROOF

Page 3: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

3

MARSH 6August 19, 2015

EEMUA 159: 2003, vol.1, p.15

SINGLE DECK PONTOON FLOATING ROOF

MARSH 7August 19, 2015

EEMUA 159 2003, vol.1, p.15

DOUBLE DECK FLOATING ROOF TANK

MARSH 8August 19, 2015

EEMUA 159 2003, vol.1, p.15

ROOF POSITION

Page 4: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

4

MARSH 9August 19, 2015

http://www.atecotank.com/product/floating_roof/alumax_ultimate_internal_floating_roof.html

ALUMINIUM FLOATING ROOF

MARSH 10August 19, 2015

FULL CONTACT GRE FLOATING ROOF TANK

http://vapoloctemp.dynaglass.com/wp-content/uploads/2012/04/Brief-Information.pdf

MARSH

TANK DESIGN (4)

• Floating roof tank

Rim seal fire – fixed system

Escalation scenario – full surface fireFixed or mobile systemDiameter > 60 meter – consider mutual aid

11August 19, 2015

Page 5: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

5

MARSH

TANK DESIGN (5)

• Floating roof tank with Aluminum geodesic dome rooffelted and non felted

Fixed system for full surface fire for single full contact Aluminum deck and full contact GRE floating roof (may changein next version NFPA 11)

Fixed system for rim sealfire for other floating roofs

12August 19, 2015

MARSH

DESIGN OF TANK (6)

• Tank height

Very large tanks used to have L/D ratios of 0.5 or less with max height of 23 meter(API 650). Space limitations can dictate a larger height up to 44 meter – cylinder stiffening(API 620)

Small diameter tall tanks for vapourcontrol like heated tarmac

Never use fixed system on tanksheated > 100 oC

13August 19, 2015

MARSH

DESIGN OF TANK (7)

• Insulated tanks

Type of insulation and weather shield

Insulation – no credits heat exposure

Program – Corrosion Under Insulation (CUI) in place

• Heated tanks

Hot water coil

Steam coil

Electrical coil

14August 19, 2015

Page 6: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

6

MARSH

DESIGN OF TANK (8)

• Temperature measurement/control liquid in tank

• Mixers

• Vapor control system

• Venting provisions

Inbreathing

Outbreathing

Standard calculation sheet JOIFF website

15August 19, 2015

MARSH

DESIGN OF TANK (9)

• Practical life of carbon steel storage tanks

Whatever comes first:

30 years, or

1,300 full empty movements

EEMUA 159 – keeping tank fit for purpose, life can be extended to 100 years

16August 19, 2015

MARSH

TANK FIRE SCENARIO (1)

• Cone roof tank full surface fire

Roof separates from cylinder – intense fire

Functional weak seam but did not fully seperatefrom roof of tank – roof will partially lift from cylinder at intervals (video)

ERV with contra weight – mild fire

ERV without contra weight – more intense fire

With innerfloater and ventilation opening at top of cylinder – roof will partially lift from cylinder at intervals

17August 19, 2015

Page 7: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

7

MARSH

TANK FIRE SCENARIO (2)

• Floating roofs

Rim seal fire

Full surface fire when floating capacity of floating roof is compromised

Pontoon chamber fire/explosion

18August 19, 2015

MARSH

TANK FIRE SCENARIO (3)

• Floating roofs with geodesic Aluminum dome roof –felted and non felted

Rim seal fire

Full surface fire

Tank failure when Aluminum roof crashes in cylinder

19August 19, 2015

MARSH

FOAM EXTINGHUISMENT OPTIONS (1)

• Monitors – radiant heat exposure responders

• Foam chamber (various foam chambers available)

20August 19, 2015

Page 8: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

8

MARSH

FOAM EXTINGHUISMENT OPTIONS (2)

• Sub-surface injection

21August 19, 2015

MARSH

FOAM EXTINGHUISMENT OPTIONS (3)

• Semi sub-surface injection

22August 19, 2015

MARSH

FOAM EXTINGHUISMENT OPTIONS (4)

• Top foam pourers with foam dam foam delivered by either top foam pourer or flexible hose in tank (video)

23August 19, 2015

Page 9: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

9

MARSH

FOAM EXTINGHUISMENT OPTIONS (5)

• Foam between or below the seals

24August 19, 2015

MARSH

FIXED FOAM SYSTEM – NUMBER OF POURERS (1)

25August 19, 2015

MARSH

FIXED FOAM SYSTEM – NUMBER OF POURERS (1)

26August 19, 2015

Page 10: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

10

MARSH

APPLICATION RATE & TIME NFPA RECOMMANDATION (1)

27August 19, 2015

MARSH

APPLICATION RATE & TIME NFPA RECOMMANDATION (2)

28August 19, 2015

MARSH

APPLICATION RATE & TIME NFPA RECOMMANDATION (3)

29August 19, 2015

Page 11: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

11

MARSH

APPLICATION RATE & TIME NFPA RECOMMANDATION (4)

30August 19, 2015

MARSH

APPLICATION RATE & TIME NFPA RECOMMANDATION (5)

31August 19, 2015

MARSH

APPLICATION RATE & TIME NFPA RECOMMANDATION (6)

32August 19, 2015

Page 12: 3-3- TANK FIRES (1) - KappetijnDESIGN OF TANK (9) • Practical life of carbon steel storage tanks Whatever comes first: 30 years, or 1,300 full empty movements EEMUA 159 – keeping

8/19/2015

12

MARSH

CONTROLLED BURN

Controlled burn can be considered for very toxic products when safe discharge after the incident

from primary containment might be compromised.

Controlled burn for crude is not recommended

RISK OF BOILOVER(video)

33August 19, 2015

MARSH

QUESTIONS

34August 19, 2015