29 Ultra High Voltage
-
Upload
wilber-lucas -
Category
Documents
-
view
215 -
download
0
Transcript of 29 Ultra High Voltage
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 1/88
2.9 ULTRA HIGH-VOLT
R
Wednesday, 14th Sep(11.00 - 12.45)Chm: Aki AmetaniRpt: Jinliang He
291 Availability of different transmission systems for long distanC. Neumann B. Rusek U. Sundermann T. Benz N. Christl
292 Experimental study on corona environment effects of 1000-transmission lines - J.L. He, J. Tang, B. Zhang, R. Zeng
293 Desi n stud for 1000 kV UVH-AC - Com osite insulatin st
J.M. Seifert, D. Stefanini, F. Lehretz294 Lightning strike characteristics of +/- 800-kV DC UHV transJ.L. He, R. Zeng
295 Considerations for the standardization of high-speed earthisecondary arc extinction on transmission lines - M. Toyoda, Y. Y
R. Jaenicke, H. Heiermeier, A. Lathouwers, K. Edwards, I.M. Kim
Marquezin, M. Kosa a a
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 2/88
q ,
Availability of different long distance
transmission systems
C. Neumann, B. Rusek, U. Sundermann, Amprion, Germany
T. Benz, ABB, Germany
N. Christl, Siemens, Germany
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 3/88
Availability of long distance transmission systems| CIGRE Bologna 20112
Content
1 Introduction
2 Considered long distance transmission systems
3 Definitions
4 Approach to define the availability of components
Extra high voltage equipment
Transformers
LCC & VSC & SLC
Overhead lines
Cables
5 Results
6 Conclusions
Availability of long distance transmission systems| CIGRE C4 Bologna 20112
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 4/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 5/88
Considered transmission systems (500km, 3GW)
Availability of long distance transmission systems| CIGRE Bologna 20114
D e s c r i p t i o n (AC1a) (AC1b) (AC2) (DC1) (DC2a) (DC2b) (DC2c)
AC
2x380-
kV D
AC 2x380-
kV D with
SC
AC 1x750-kV
F* 2T
HVDC LCC
1Bx500-kV
D*
HVDC VSC 3Bx320-kV
cable
HVDC VSC 2x500-
kV D*
HVDC VSC
1x500-kV D*
P o
w e r
3600 3600 4000 4000 3000 3600 2720
X L P E c a b l e s
O H L
O H L + S e r i e s
c o m p e n s a t i o n
O H L
O H L
O H L
O H L
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 6/88
Definitions
Unavailability derived from forced energy unavailability FEU
If no exact data are available
Thereby :
MDT - mean down time
MTBF – Mean time between failures
λ – failure rate
Availability of long distance transmission systems| CIGRE Bologna 20115
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 7/88
Availability of EHV equipment
Reliability of the EHV equipment
the worst failure rate value from the past CIGRE surveys and Amprion
database.
The assessment of outage time due to failure
according Amprion service experience
The unavailability is strongly affected by minor failures.
Availability of long distance transmission systems| CIGRE Bologna 20116
17%
33%
20%
13%17% Circuit-breaker
instrumment transformer
pantograph disconnector
center-break disconnector
earthing switch
Forced EnergyUnavailability
of a 380-kV-bay
1,4 hour / year
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 8/88
Availability of transformers
Data source
different CIGRE Surveys and Amprion experience
Reliability LCC Transformers MTBF = 50 years per unit
VSC (AC) Transformers MTBF = 100 years per unit
Mean Down Time Time to replace a transformer = 48 hours
Availability of long distance transmission systems| CIGRE Bologna 20117
FEU of transformer
0.48 … 0.96 hour / year
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 9/88
Availability of VSC and LCC poles and SC
Power electronics
MTBF = 5 years / pole
MDT = 7 hours
Availability of long distance transmission systems| CIGRE Bologna 20118
FEU of power electronics
1.4 hour / year
Share in unavailability for typical LCC and VSC 1-pole stations
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 10/88
Availability of
overhead lines
Availability of long distance transmission systems| CIGRE Bologna 20119
Interpretation of FNN dataoutages due to galloping conductors
probable less probable
(included) (excluded)
FEU of OHL
3.1 hour / year
Typical towersin FNN
DC towers
Data source FNN - German Forumfor Network technology and Network
operation
90% of single mode failures
fault clearing with auto reclosing
similar behaviour of DC systems
10% of common mode failures
fault end-ups usually with an outage
(except galloping conductors)
MTBF 3.86 years / 100 cct. km
MDT 12h
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 11/88
Availability of DC cables
No data for on-land DC XLPE
Use of data for AC XLPE (CIGRE, TB 379)
λ adjustments: AC 3 phases DC 2 poles
J oint every 0.8 km per cable 2.5 joints per cct. km
MTBF = 8.06 year / 100 cct. km
MDT = 120 h (4 - 5 days) !!
Availability of long distance transmission systems| CIGRE Bologna 201110
FEU of DC cable
14.8 hours / year
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 12/88
Forced energy unavailability – comparison of
different long distance transmission systems
Availability of long distance transmission systems| CIGRE Bologna 201111
0,0
0,2
0,4
0,6
0,8
1,0
1,2
(AC1a) (AC1b) (AC2) (DC2b) (DC2c) (DC2a) (DC1)
F o r
c e d E n e r g y U n a v a i l a b i l i t y % Transmission lines (OHL/cables)
EHV switchyard
UHV switchyard
Transformer
Converter stations (VSC,LCC, SLC)
73%
27%
82%
8%
19%
10%
52%
9%
20%
8%
58%
34%
11%
41%
48%
28%
42%
30%
12%
88%
2,5 2.48
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 13/88
Conclusions
Comparable forced energy unavailability of AC & DCsystems with overhead lines⇒ 1.7 - 3.3 days/year
Availability of the transmission lines is crucial
Slightly worse availability of VSC systems caused by higher
number of components and some power restrictions
VSC option using cables as transmission system is stronglyaffected by the presumed availability of the XLPE cables
Since many new LCC and VSC systems are going to beinstalled, the service performance should thoroughly beobserved
Availability of long distance transmission systems| CIGRE Bologna 201112
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 14/88
DESIGN STUDY FOR 1000/1200 kV
UHV-AC COMPOSITE INSULATOR STRINGDr. J. M. Seifert; Ing. D. Stefanini
Ing. Fabian Lehretz
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 15/88
„Technology Survey“
Transmission Distance in km
C a p a c i t y i n
G W
0.01
0.1
1
10
100
0.001
1 10 100 1000 10000
UHV
1200kV
HVDC
765kV
400/500kV
Subtransmission
„Smartgrids“HVDC - Smart
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 16/88
Tab. 1: Insulation coordination for 1000/1200 kV
Composite Insulator - 1100kV
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 17/88
Tab. 2: Maximum electrical design field stresses at the composite insulator
Location Evaluation Criterion (EPRI)
Insulator
shank
Path length on which Etg > 4.2
kV/cm shorter than 10 mm
Triple point Etg
< 3.5 kV/cm
Composite Insulator - 1100kV Field Control
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 18/88
Fig. 3: Tangential Field distribution along the insulator axis and field plot of HV region
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 19/88
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
0 10 20 30 40 50 60 70 80 90 100
ATH content (by weight)
P e r f o r
m a n c e
HTM
Tracking & Erosion Resistance
Outdoor performance
p.u.
%
HTV - Composite Insulator - Pollution Performance
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 20/88
0
20
40
60
80
100
120
140
0 4 8 12 16
Transfer Time
S t a t i c C o n
t a c t A n g l e
RTV-2
RTV-1
HTV-Gen III/IV
HTV-Gen II
HTV-Gen I
LSR
Generation III/IV HTV-
PDMS² / ATH filled
°
d
HTV Composite Insulator - Pollution Performance
RODURFLEX®
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 21/88
Pollution Severity: 2% ESDD Level (mg/cm²)
0,001 0,01 0,1 1
I n s u l a t i o n L e n g t h ( m )
11,0
10,5
10,0
9,5
9,0
8,5
8,0
7,5
7,0
6,5
6,0
5,5
5,0
4,5
U n i f i e d S p e c i f i c C r e e p a g e D i s t a n c e ( m m / k V i n s u l a t o r )
56
54
52
50
48
46
44
42
40
38
36
34
32
30
28
26
2422
Fig. 6: Insulation Length in m and USCD in mm/kV in dependence on ESDD 2% site pollution.
The IST sensitivity analysis in Fig. 3 for the “study” insulator will result in a 2%-ESDD pollution performance of 0.22 mg/cm² (“heavy pollution”). More performancecan be reached if more underrib sheds will be added (up to CF of 4.0). At samelength 2%-ESDD of 0.6…0.8 mg/cm² can be achieved with silicone rubberinsulators of this design.
Very Light Light Medium Heavy Very Heavy
IEC 60815
0,22 mg/cm²
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 22/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 23/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 24/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 25/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 26/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 27/88
600 / 800 kV HVDC
533 kV 600 kV 800 kV
Glass / Porcelain 9.8m 12.6m 15.1m
Silicone Rubber Composite
6.4m 7.3m 9.6m
Required Insulation Length:
HEAVY (IEC 60815): ESDD=0.1mg/cm² - NSDD=0.3mg/cm²
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 28/88
2011 BOLOGNA SYMPOSIUMThe Electric Power S stem of the F
Integrating Supergrids
and
Microg
13‐15 September 2011, Bologna, Ita
Lightning Strike
Characteristic
800‐kV DC UHV Transmission
Jinliang He and
R.
Zeng
g o age esearc ns
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 29/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 30/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 31/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 32/88
2. Fractal Model
Lightning current magnitude Q=f(I m ),
charges are assumed uniformly distributedin the fractal channels
without with fractal channels
6 2/3
16.5 10I
6 2 / 3
43 10 I
Upward leader inception
Local field criterion
enera groun e o ec :
Transmission line:
mc
/03.013000 r m E c “Hot‐spot” concept
Hot‐spots distribute every several meters
along the
line
edges,
corners
and
tips
of the tower
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 33/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 34/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 35/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 36/88
4. Application in +/‐800kV DC UHV
Distribution of the initiating point and falling point
EGM and LPM develop vertically or near vertically, this property leads to
But the fractal model has scattered distribution of the initiating point and
leader. This
means
downward
leader
initiating
from
far
place
can
still
hav
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 37/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 38/88
4. Application in +/‐800kV DC UHV
Shielding failure is most probable to occur in middle part of transmiss
Our statistical results lead to the ratio between numbers of shieldin fof (+) and (‐) conductors (~8:1), very close to the operation data (8~10:1)lines of China Southern Power Grid
+/ ‐800kV DC line
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 39/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 40/88
Cigrè International Symposium
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 41/88
P-2
HSESs (HSGSs)
HSES for 550kV system in BPA
13-15 September 2011 – Bologna (Italy)
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 42/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 43/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 44/88
Cigrè International Symposium13-15 September 2011 – Bologna (Italy)
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 45/88
P-6
Direct lightning strokes to phase lines
Direct lightning stroke to the
upper phase line
Direct lightning stroke to the
middle phase line and flashover
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 46/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 47/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 48/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 49/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 50/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 51/88
Cigrè International Symposium13-15 September 2011 – Bologna (Italy)
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 52/88
P-13
Comparison between four-legged reactor and HSES four-legged reactor HSES
Secondaryarcextinction
- Effective for single-phase fault that
hold the majority of the faults.- Difficult to choose a reactance value
of reactors that effectively reducethe secondary arc current for allfault modes.
- Quick extinction for all fault modes.
Flexibility to
the changeof network
- In case a substation is constructed inthe middle of a line, it might be
required to substitute a reactor thathas already installed.
- Not affect on the substation
equipment that has alreadyinstalled.
Control/Protection
- Special control is unnecessary for secondary arc extinction.
- Automatic sequential control such as“fault detection CB open HSES close HSES open CBclose” is necessary in each phase,and it can be easily realized.
Economy- Four-legged shunt reactor is appropriate for transmission lines which require
shunt reactors for voltage control, while HSES would be economical for thelines without shunt reactors.
Concern
- Detailed analysis is necessary so asnot to cause resonance betweenshunt reactor inductance and linecapacitance not only in power frequency of 50/60Hz but also inthe high frequency band.
- Highly reliable control system isrequired since a mal-function leadsto a ground fault.
C l i
Cigrè International Symposium13-15 September 2011 – Bologna (Italy)
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 53/88
P-14
Conclusion
★ PT48 in IEC SC17A works for HSES standardizationfrom 2009-1
• Effect of system parameters to the interrupting duties isstudied and 5 categories are introduced as interruptingduties
• Contacting with CIGRE WG A3.22 and A3.28
★ Principal topics discussed in this paper are…;
• coordination with CB re-closing systems
• timing coordination of HSES operation with CBs’
• consideration for successive fault on transmission line
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 54/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 55/88
1
Considerations and Recommendations
for the Specification of UHV Substation Equipment
CIGRE Symposium in Bologna, 13-14 September 2011
Hiroki Ito, Mitsubishi Electr ic
Anton Janssen, Liander Denis Dufournet, Alstom Grid
Yoshibumi Yamagata, TEPCO
Scope: Review the state-of-the-art of project specific and national technicalspecifications for all substation equipment within the scope of CIGRE Study Committee
A3 at voltages exceeding 800 kV.
Recommend future specifications and standardizations of 1100 kV and 1200 kV
equipment and provide technical backgrounds on the collected information to IEC TC17.
On behalf of CIGRE WG A3.22 / A3.28
Uwe Riechert, ABB
Paulo Fernandez, EletrobrasMasayuki Kosakada, Toshiba
David Peelo, Consultant
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 56/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 57/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 58/88
DC time constants in fault currents
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 59/88
5
Tower and conductor designs
Calculations predict a large DC time constants in fault current in UHV transmission systems due
to usage of multi sub-conductor bundles and the existence of large capacity power transformers.
16.5m
16m
15.5m
19m
7 2 . 5 m
9 0 m
1 0 7 . 5 m
1 2 0 m
810mm sq. -8 conductors
1100kV transmission lines
2 7 . 4 m 4
0 . 3 m
15.24m
42.7m
1360mm sq. -4 conductors
800kV transmission lines
3 5 ( 5 4 . 5
) m
2 2 . 6
( 4 2 . 1
) m
12m 12m
20.12m
1360mm sq. -4 conductors
800kV transmission lines
Influences of the high DC component on test-duty T100a does not show any signi ficant
difference when the constant exceeds around 120ms. Therefore, it was recommended to
use a time constant of 120 ms for rated voltages higher than 800 kV.
ConductorsHighest voltage(kV)
Size(mm2 ) Bundle
DC timeconstants(ms )
800Canada 686 4 75
800USA 572 6 89800
South Africa 428 6 67
800Brazil 603 4 88800
China 400 6 751200
Russia 400 8 911050Italy 520 1001100Japan 810 150
1100China 500 120
8
8
81200India 774 1008
5
UHV TRV requirements
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 60/88
6
Voltage
Uc
ti0
Ui
t2 Timet1
U1U1: First reference voltage= 0.75 x Kppx Ur 2/3
U1/ t1: Rate of rise of TRV
Uc/ t2
U1 / t1
RRRV
TRV peak
ITRV
t2 : time to TRV peak
Uc: TRV peak = Kpp x Kaf x Ur 2/3
t2 = 4 x t1for T100, t2 = 6 x t1 for T60
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Time (μs)
U ( k V )
T60, kpp=1.2, kaf =1.5, t2=3xt1
T100, kpp=1.2, kaf =1.5, t2=3xt1
T60, kpp=1.2, kaf =1.5, t2=4.5xt1
T100, kpp=1.3, kaf =1.4, t2=4xt1
T60, kpp=1.3, kaf =1.5, t2=6xt1
T60, kpp=1.2, kaf =1.5, t2=6xt1
TRV for T100 and T60 with Ur=1100 kV
q
1.2 (1.3)T100 1617
TLF
Out-of-phase
UHV
DUTY
T60
T30T10
First-pole-to-clear factor
Kpp
2.0
1.2 (1.3)
1.2 (1.3)
1.2 (1.3)
1.2 (1.5)
Amp lit udefactor
Kaf
1.5 (1.4)
1.5
1.541.76
0.9*1.7
1.25
1100 kV
TRV peak (kV)
1617
16601897
1649
2245
1764
1200 kV
TRV peak (kV)
1764
18112076
1799
2450
Rate of Rise of TRV
RRRV (kV/µs)
2
3
57
(*)
Time to TRV peak
t2
3.0*t1 (4*t1)
4.5*t1 (6*t1)
Time to TRV peak
t3
t3 (t3)
t3 (t3)
(*)
Values ( ) are standards for 800 kV and below.
1.38*t1 (2*t1)
t1 and t3 are based on Kpp=1.2
(*) : RRRV= Uc / t3 with t3 =6 * Ur / I 0.21 shown in the ANSI C37.06.1-2000 for t ransfo rmers up to 550 kV
For UHV transformers, RRRV and t3 are determined by the transformer impedance and its equivalent surgecapacitance (specified as 9 nF)
Effect of MOSA on TRV waveforms
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 61/88
7
0 4Time (ms)
1 52 3
Uc=1635kV (Kpp=1.3, Kaf=1.4)
0
500
V
o l t a g e ( k V )
1000
1500
2000 T60, Breaking current : 26.2kA
TRV for T60 with twic e TRV peak value of existi ng 550kV standard
Without MOSA
With MOSA (A type characteristic)
With MOSA (B type characteristic)
Uc=1751kV (Kpp=1.3, Kaf=1.5)
0 4Time (ms)
1 52 30
500
V
o l t a g e ( k V )
1000
1500
2000 T100, Breaking current : 33.8kA
TRV for T100 with twic e TRV peak value of existin g 550kV standards
Without MOSA
With MOSA (A type characteristic)
With MOSA (B type characteristic)
TRVpeak=1586kV
TRVpeak=1411kV
Uc=1635kV (Kpp=1.3, Kaf=1.4)TRVpeak=1502kV
TRVpeak=1380kV
The clipping or suppression level of 1400 kV would lead to a specified TRV level of
1617 kV considering a certain margin between the circui t-breaker performances and the
MOSA protection levels. This recommendation corresponds to the inherent peak value
for T100 and close to the inherent peak value for T60. 7
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 62/88
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 63/88
Publications of CIGRE WG A3.22
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 64/88
10
2007
Technical paper presented at IEC-CIGRE UHV symposium in Beijing
2-4-1 “ Technical requirements for UHV substation equipments”
2008
First Technical Brochure published in December
TB 362 “ Technical requirements for substation equipments exceeding 800 kV”
CIGRE Session paper presented at 2008 CIGRE session in Paris
A3-211 “ Technical requirements for UHV substation equipments”
2009
Technical paper presented at IEC-CIGRE UHV symposium in New Delhi
3-1 “System impacts on UHV substation equipment”
4-1 “CIGRE state of the art & prospects for equipment”
2011Second Technical Brochure publ ished in April
TB456 “Background of technical specifications of substation equipment exceeding 800 kV”
Technical paper presented at 2011 SC A3 col loquium in Vienna
A3-101 Background informat ion & study results for specifications of UHV substation equipment
> WG A3.28 will cont inue the studies on UHV / EHV switching equipment
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 65/88
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 66/88
Presentation Outline
• Introduction
• The Sardinian Power System
• Power Generation and Load Demand in Sardinia
• Renewable Energy Sources integration in Sardinia
• Scenarios in 2020 and 2030
• Results
• Remarks
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage2
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 67/88
The Sardinian AC Grid
±500 kV HVDC
200 kV HVDC
220 kV AC
380 kV AC
380 kV AC Transmission Lines [km]
Total 304,9
220 kV AC Transmission
Lines
[km]
Total 1335,1
150 kV AC Transmission [km]
Total 2064,6
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
380 kV EHV transmission network
from North to South of Sardinia
connects the two areas with the
biggest power plants.
A shorter 380 kV EHV line connects
the two HVDC stations.
3
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 68/88
500 kV, 1000 MW HVDC (SAPEI)
• Connection from Sardinia to the mainland.• Two HVDC converter stations (Fiume
Santo, Latina).
• The HVDC system is a bipole of 1.000 MW.
• Each pole has a capacity of 500MW at ±500kV with 1.000 A as nominal current.
• The DC cable is laid beneath the Tyrrhenian
Sea at depths of up to 1,600 meters.
Sardinian DC Grid 200 kV, 300 MW HVDC (SACOI)
Currently the SA.CO.I. is under scheduling arevamp to increase reliability and power
capacity
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage4
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 69/88
The energy production in Sardinia on 2008 was dominated by thermal plants
which covers 72% of the total Sardinian electricity generation
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
2008 vs 2010 Power Generation Capacity
The expansion of RES power plants installed in Sardinia, especially wind
and PV power, has reduced the share of traditional power plants
12.46%
74.59%
0.41%
12.11% 0.42%
Hydro
Thermoelectric
Photovoltaic
Wind
Biomass
10.21
%
71.94
%
2.23%
13.99
%
1.63%
5
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 70/88
In the last 5 years there has
been a great increase of wind
power production that will be
doubled in the next ten
years (1750 MW on 2020).
A fast growth of the PV
integration in the power systems with reference to the
number of power plants and
power capacity
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Renewable Power Generation in Sardinia
The orography and
hydrography of the Sardinian
territory do not allow large
hydro generation capacity.
Distribution of wind capacity
6
Cigrè International Symposium Bologna 13-15 Sept. 2011
2008 L d D d d L ti
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 71/88
•Strong increasing of load in
summer
Agricolture Industry Tertiary Residential Total
Zone GWh GWh GWh GWh GWh
SS 38,6 683 449 458 1.629
Ca 37,4 2.593 927 775,6 4.333
CI 11,7 3.187,9 135,2 172 3.506
OT 11,4 128,9 351,1 289,4 780,7
NU 24,6 289,1 183,9 190,2 687,7
OR 61,7 103,4 178,7 194,4 538,2
VS 18,8 71,6 100,5 111,1 302
OG 7,2 29,6 60,9 60,5 158,2Tot 211,2 7.086,2 2.386,4 2.251,4 11.935
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
2008 Load Demand and Location
• One third of demand is concentrated in
the south
•Load is widespread with very low density7
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 72/88
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Seasonal Daily Load Profile
0
400
800
1200
1600
2000
0 2 4 6 8 10 12 14 16 18 20 22
D a i l y l o a
d [ M W ]
16/04/2008 30/07/2008 15/10/2008 02/12/2008
Hour
The 2008 peak demand in Sardinia was 1825 MW registered in August
due to the high use of air conditioners
• Maximum peak load appears around 8-9 p.m. during summer
• Minimum valley load around 3-4 a.m. during winter
• Average summer peak and winter valley load data were chosen to create
worst conditions for grid operation with high RES shares.8
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 73/88
Cigrè International Symposium Bologna 13-15 Sept. 2011
G id E i i 2030
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 74/88
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
1) HVDC monopolar connection to the
mainland (SA.CO.I) is put back intoservice with the same capacity of the
existing one (300 MW);
2) Upgrades of the existing 150 kV low
capacity lines in the North-West of Sardinia;
3) Refurbishment of the old 70 kV lines in
the middle of the island with 150 kV new
lines;
4) A possible new monopolar 500 MW/500
kV HVDC link between Algeria and
Sardinia to import “green” energy from
North Africa
Grid Expansion in 2030
10
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 75/88
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Load Forecast
- PEAK LOAD
- VALLEY LOAD
2008-2020 + 1,5%
2020-2030 + 1%
2020-2030 + 1%+ 0,9%2008-2020
The PV generators reduce the energy demand from power supply, the
overall yearly power supply and the number of possible congestions
caused by excessive demand11
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 76/88
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 77/88
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Methodology
The AC power flow studies have been performed using a Newton-
Raphson iterative method to characterize the steady state operation.
RES production has been dispatched with the highest priority
The dispatching of the thermal generation units has been scaled
down in accordance with their technical constraints (e.g. minimum
power production).
For the inflow of energy from Algeria two alternative assumptions:
The CSP power has always higher dispatch priority versus Sardinian
wind production: the export capacity of the Sardinian grid is practically
halved
The Sardinian wind production has higher dispatch priority versus the
Algerian power import. In this case, it has been assumed that the
import from the Algerian CSP power plants could be curtailed in order
to allow full wind production.13
Cigrè International Symposium Bologna 13-15 Sept. 2011
R lt ( i 2020)
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 78/88
0
2
4
6
8
10
12
14
16
1 2 3 4 5 6 7 8
≥ 70% ≥ 80% ≥ 90% ≥ 100%
SCENARIOS
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Results (scenario 2020)
CASE STUDIES
1 Peak Load-Wind 50%- SAR.CO. 50%-NO PV
2 Peak Load-Wind 90%- SAR.CO. 50%-NO PV
3 Peak Load-Wind 90%- SAR.CO. 100%-NO PV
4 Peak Load-Wind 90%- SAR.CO. 100%-PV
5 Peak Load-Wind 90%- SAR.CO. 100%-PV & CHP
6 Valley Load-Wind 50%- SAR.CO.100%-NO PV
7 Valley Load-Wind 90%- SAR.CO.100%-NO PV
8 Valley Load-Wind 89%- SAR.CO.100%-NO PV & CHP
Number of branches within each congestion level
Scenario with the greatest
losses:
SAR.CO. exploited up to 100% 90% wind generation
No reduction given by the PV
generation
Scenario with the smallest
losses valley load scenarios in the
same conditions.
The increased power
production causes a greater
exploitation of the 380 kV networkand HVDC connections.
The 150 and 220 kV network is
less used with a reduction of
power flows on those lines14
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 79/88
Cigrè International Symposium Bologna 13-15 Sept. 2011
R lt (S i 2030)
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 80/88
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Results (Scenario 2030)CASE STUDIES
1
Peak Load-Wind 90% - SAR.CO.0% - NO PV-Algeria
100%2 Peak Load-Wind 90% - SAR.CO.0% - PV - Algeria 47%
3Peak Load-Wind 90% - SAR.CO.0% - PV - CHP -
Algeria 6.5%
4 Peak Load-Wind 90% - SAR.CO.100% - Algeria 60%
5Peak Load-Wind 90% - SAR.CO.100% - CHP-Algeria
40%
0
1
2
3
4
5
6
7
8
9
10
1 2 3 4 5
≥ 70% ≥ 80% ≥ 90% ≥ 100%
SCENARIOS
Number of branches within each congestion level
The SA.PE.I. HVDC link
capacity available to export the
Sardinian RES power generationhas been reduced, causing the
RES generation curtailment.
The SA.CO.I. revamping
increases the export capacity to
the mainland.
The scenario with the largest
losses:
maximum wind generation
utmost import from Algeria
The balance between the
power locally produced and the
local consumption allows not
exceeding the rated capacity of
the lines 16
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 81/88
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Remarks (scenario 2030)
The HVDC connection with Algeria will significantly impact theSardinian power system with possible curtailment of the power
generation:
The generation of the conventional thermoelectric power plants
should be reduced to preserve the wind production at the evening
peak load.
Storage devices and electric vehicles are necessary to preserve
adequate reserve margin and comply with technical constraints of
thermal generation when PV generation is maxima.
At off-peak hours, the wind production has to be limited (80%) if
Algerian power gets dispatch priority. On the contrary, if the
Sardinian RES generation gets highest dispatch priority, the HVDCconnection with Algeria will be used at 60% of its capacity.
The 150 kV network is the most critical asset of the Sardinia
transmission grid.
17
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 82/88
18Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Question I
According the analysis of the paper, in order not to curtail the
wind production during the evening peak load, it is necessary to
limit the maximum generation level of the conventional
thermoelectric power plants (around 50% of the nominalinstalled capacity). What’s the suitable ratio between RES and
thermoelectric power?
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 83/88
19Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Answer I
- The suitable ratio between RES and thermoelectric power is the one
expected for 2020:
1000 / 3358 ≈ 30%
because a greater increase of wind generation, such as those planned for
2030, requires generation curtailment.
- The dramatic increasing of PV (250 MW already installed, 400 MW
expected by 2013) will probably cause wind and thermal generation
curtailment in summer windy days
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 84/88
20Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Question II
The author has been demonstrated with the study that the 150
kV network is the most critical asset of the Sardinia
transmission grid where the majority of wind farms are
connected particularly in the north-east part of the island.
Connecting the wind farms to higher voltage systems such as220 kV or 380 kV networks can alleviate network congestions,
but at very high costs for power producers and system
stakeholders. What’s the best high voltage grade for the
network with RES?
Cigrè International Symposium Bologna 13-15 Sept. 2011
A II
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 85/88
21
0
1
2
3
4
5
6
7
8
≥ 70% ≥ 80% ≥ 90% ≥ 100%
150 kV Voltage Level 220 kV voltage Level
Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Answer IINumber of branches within each congestion level
By moving wind farms to 220 kVlevel:
- A drastic reduction of congestions;
- An improvement of active power
losses (37,13 MW versus 34 MW)
The best high voltage grade for the network with RES is 220 kV level, because:
- The 380 kV network is poorly developed and the connection costs are too
high;
- the 220 kV level is the best compromise between cost and reliability of the
connection
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 86/88
22Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Question III
Large RES generation facilities are far from the main urban
consumption areas, long distance power transmission
infrastructures are required, an increase in active losses takes
place and some additional difficulties in local voltage controlmay also arise. How do the renewable energy sources affect
the structure of power transmission network? And How does the
power transmission network affect the application of RES?
Cigrè International Symposium Bologna 13-15 Sept. 2011
A III
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 87/88
23Bologna 14 Sept. 2011 - Session 2.9 Ultra High Voltage
Answer III
The structure of the transmission network of the future is affected by a high
penetration level of RES and it will be necessary a re-sizing of some
connections in order to export the RES energy to the north and then to the
mainland.
The power system affects the application of RES introducing some limits to
the distributed generation connection to the grid mainly due to the fact that
the grid has not been constituted to receive high level of RES
Cigrè International Symposium Bologna 13-15 Sept. 2011
7/29/2019 29 Ultra High Voltage
http://slidepdf.com/reader/full/29-ultra-high-voltage 88/88
THANK YOU FOR YOUR KIND ATTENTION