    Mobile Panel 277F IWLAN V2-Upgrading to Roaming-

    WinCC flexible 2008 SP2 + HSP

    Application description February 2011

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    2/45

    2Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    Industry Automation and Drives Technologies Service & Support Portal

    This article is taken from the Service Portal of Siemens AG, Industry Automationand Drives Technologies. The following link takes you directly to the downloadpage of this document.

    http://support.automation.siemens.com/WW/view/en/25702331

    If you have any questions about this document, please contact us at the followinge-mail address:

    [email protected]

    http://support.automation.siemens.com/WW/view/en/25702331mailto:[email protected]:[email protected]://support.automation.siemens.com/WW/view/en/25702331
  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    3/45

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 3

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    sSIMATIC

    Mobile Panel 277F IWLAN V2

    Roaming

    Automation Task 1

    Automation Solution 2

    Basics 3

    Configuration Process 4

    Configuration Process 5

    Links & Literature 6

    History 7

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    4/45

    Warranty and Liability

    4Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    Warranty and LiabilityNote The application examples are not binding and do not claim to be complete

    regarding configuration, equipment and any eventuality. The applicationexamples do not represent customer-specific solutions. They are only intended

    to provide support for typical applications. You are responsible for ensuring thatthe described products are used correctly. These application examples do notrelieve you of the responsibility to use sound practices in application, installation,operation and maintenance. When using these Application Examples, yourecognize that we cannot be made liable for any damage/claims beyond theliability clause described. We reserve the right to make changes to theseApplication Examples at any time without prior notice. If there are any deviationsbetween the recommendations provided in this application example and otherSiemens publications e.g. Catalogs the contents of the other documentshave priority.

    We accept no liability for information contained in this document.

    Any claims against us based on whatever legal reason resulting from the use ofthe examples, information, programs, engineering and performance data etc.,described in this Application Example shall be excluded. Such an exclusion shallnot apply in the case of mandatory liability, e.g. under the German Product LiabilityAct (Produkthaftungsgesetz), in case of intent, gross negligence, or injury of life,body or health, guarantee for the quality of a product, fraudulent concealment of adeficiency or breach of a condition which goes to the root of the contract(wesentliche Vertragspflichten). However, claims arising from a breach of acondition which goes to the root of the contract shall be limited to the foreseeabledamage which is intrinsic to the contract, unless caused by intent or grossnegligence or based on mandatory liability for injury of life, body or health. Theabove provisions do not imply a change in the burden of proof to your detriment.

    It is not permissible to transfer or copy these Application Examples or excerptsthereof without express authorization from Siemens Industry Sector.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    5/45

    Table of contents

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 5

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    Table of contentsWarranty and Liability ................................................................................................. 4

    1 Automation Task................................................................................................ 6

    1.1 Introduction........................................................................................... 61.2 Overview of the automation task.......................................................... 61.3 Description of the automation task....................................................... 71.4 Requirements ....................................................................................... 7

    2 Automation Solution ......................................................................................... 8

    2.1 Overview of the overall solution ........................................................... 82.2 Description of the core functionality ..................................................... 92.3 Hardware and software components used......................................... 10

    3 Basics ...............................................................................................................11

    3.1 iPCF-MC concept............................................................................... 113.2 Applicable WLAN standards for the mobile panel.............................. 15

    4 Configuration Process.................................................................................... 16

    4.1 Preparatory measures for the configuration....................................... 164.1.1 IP addresses ...................................................................................... 164.2 SCALANCE W788-2RR configuration ............................................... 164.2.1 Assigning the IP address for the SCALANCE W788-2RR................. 174.2.2 Configuring the SCALANCE W788-2RR via the WEB....................... 184.2.3 Backing up data the SCALANCE W788-2RR.................................... 304.2.4 Adjusting other access points ............................................................ 314.3 Configuring the mobile panel ............................................................. 344.3.1 Hardware settings .............................................................................. 344.3.2 WLAN configuration ........................................................................... 38

    5 Startup of the Application............................................................................... 446 Links & Literature ............................................................................................ 45

    7 History............................................................................................................... 45

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    6/45

    1 Automation Task-

    1.1 Introduction

    6Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    1 Automation Task

    1.1 Introduction

    The application is based on the Configuration and Use of the Mobile Panel 277FIWLAN application description. This is where you have already been introduced tothe individual configuration steps for creating a Mobile Panel 277F IWLAN project.

    It is the aim of this application to get familiar with the Roaming function and itsapplication.

    Note Whenever the mobile panel is mentioned in this document it relates to the MobilePanel 277F IWLAN V2.

    1.2 Overview of the automation task

    The figure below provides an overview of the automation task.

    The figure below shows Plant section 1 of a packing station.

    Figure 1-1

    Converyor belt 1 of 3

    Conveyor belt 2 of 3

    Conveyor belt 3 of 3

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    7/45

    1 Automation Task

    1.3 Description of the automation task

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 7

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    1.3 Description of the automation task

    A plant section (packing station) consists of several

    stations (conveyor belts 1 to 3), that are spatially far apart.Via a Mobile Panel 277F IWLAN all stations are to be operated and monitored.Smooth and secure operation of the individual stations through the Mobile Panel277F IWLAN has to be guaranteed.

    1.4 Requirements

    Requirements of the automation task

    Standard communication

    PROFIsafe communication via WLAN

    Uninterrupted roaming to other access points (iPCF-MC)

    Requirements for the HMI:

    the complete operation of the plant is performed via the HMI operator panel.

    Requirements for the communication:

    communication via WLAN

    uninterrupted roaming to other access points (iPCF-MC)

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    8/45

    2 Automation Solution-

    2.1 Overview of the overall solution

    8Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    2 Automation Solution

    2.1 Overview of the overall solution

    Schematic layout

    The figure schematically shows the most important components of the solution:

    Figure 2-1

    Mobile Panel 277F IWLAN V2

    S7-CPU 317F

    )))

    )))

    ))))))

    IndustrialEthenet

    Industrial

    Wireless LAN

    Schutztr

    PositionsschalterNot-HaltIM151-3

    mit Peripherie

    SCALANCE

    Switch X208W788 -2RRW788 -2RR

    Part of the

    "Configuration and Use of Mobile

    Panel 277F IWLAN" application

    ))))))

    ))))))

    Access Point 1 Access Point 2

    IM151-3

    with I/O

    Safety door

    position switch

    Emergency

    stop

    The figure shows the arrangement of the most important components in the directindustrial environment.

    Figure 2-2

    Mobile Panel 277F IWLAN V2

    SCALANCEW788-2RR

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    9/45

    2 Automation Solution

    2.2 Description of the core functionality

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 9

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    Classification

    For better overview, the application will only give information necessary for thereproduction of this application.

    Where necessary, the document provides references to related links and manuals. This application does not include information on the following topics:

    Safety Notices and Standards

    Directives and Approvals

    Operational Safety, etc.

    For these topics, please refer to the Operating Manual for the Mobile Panel 277FIWLAN V2.

    This application does not include a description of the SIMATIC WinCC flexibleengineering tool.

    It only describes the settings of the used hardware and software componentsthat are necessary for the application.(SCALANCE W788-2RR and Mobile Panel 277F IWLAN V2)

    Basic knowledge of the above-listed topics is assumed. For detailed information,please refer to the associated manuals.

    Required knowledge

    The basic knowledge of the Configuration and Use of the Mobile Panel 277FIWLAN application description is assumed.

    2.2 Description of the core functionality

    The core functionality is the communication between the mobile panel and severalaccess points that are in a network.It is possible to change from one access point to another access point withoutprevious logoff or new logon.

    The mobile panel communicates is expanded byiPCF-MC (industrial Point Coordination Function with Management Channel)WLAN access procedure also called Rapid Roaming.

    Rapid Roaming is used for interruption-free transfer of radio signals and providesrapid transfer of radio signals between the access points and the mobile panel abasic requirement for mobile solutions for operating and monitoring in safety-relevant areas where enabling and emergency stop buttons are used.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    10/45

    2 Automation Solution-

    2.3 Hardware and software components used

    10Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    2.3 Hardware and software components used

    The application was created with the following components:

    Hardware components

    Table 2-1

    Component Qty. MLFB/order number Note

    SCALANCE W788-2RR 2 6GK5 788-2AA60-6AA0 Alternatively, otherversions of theSCALANCE W 2RRaccess points can beused.

    Mobile Panel 277FIWLAN V2

    1 6AV6645-0EC01-0AX1 Alternatively, otherversions of the MobilePanel 277F IWLAN

    V2 can also be used.

    Standard software components

    Table 2-2

    Component Qty. MLFB/order number Note

    WinCC flexible 2008standard

    1 6AV6612-0AA51-3CA5 Alternatively, WinCCflexible 2008Advanced can also beused.

    WinCC flexible 2008SP2

    1 See Customer Supportpages

    http://support.automation.siemens.com

    SP2 is available fordownload.

    WinCC flexible 2008SP2 HSP

    1 See Customer Supportpages

    http://support.automation.siemens.com

    HSP is available fordownload.

    Sample files and projects

    The following list contains all files and projects used in this example.

    Table 2-3

    Component Note

    25702331_Standard_Project_V2_Roaming.zip Standardconfiguration

    (STEP7 andWinCC flexible)

    25702331_MobilePanel277F_IWLAN_V2_Roaming_de.doc.pdf This document

    http://support.automation.siemens.com/http://support.automation.siemens.com/http://support.automation.siemens.com/http://support.automation.siemens.com/http://support.automation.siemens.com/http://support.automation.siemens.com/http://support.automation.siemens.com/http://support.automation.siemens.com/
  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    11/45

    3 Basics

    3.1 iPCF-MC concept

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 11

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    3 BasicsThis chapter contains information regarding Roaming with iPCF-MC andapplicable WLAN standards.

    3.1 iPCF-MC concept

    For failsafe applications the mobile panel communicates through the expandedWLAN access procedure iPCF-MC(industrial Point Coordination Function with Management Channel).

    The data communication is performed on the so called data channel (in PCFmethod).The coordination of the communication is performed on the so calledmanagement channel.

    The figures below are to illustrate the iPCF-MC concept.

    Figure 3-1

    Each access point has a different "Data Channel"

    Each access point has the same "Management Channel" (here channel 48)

    AP3 W788-2RR

    AP2 W788-2RR

    AP1 W788-2RR

    36

    Industrial Ethernet/PROFINET

    40

    44

    48

    48

    48

    AP: Access Point

    There are as many data channels (here 36; 40; 44) as there are access pointsand one joint management channel (here 48).

    Each access point (AP) sends so called beacons (approx. every 5ms) to themanagement channel.The clients (in this application the mobile panel) receive information regarding the

    reception quality and the number of the data channel to all the access points ofthe network in reach within a very short time.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    12/45

    3 Basics-

    3.1 iPCF-MC concept

    12Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    iPCF-MC, data channel

    Figure 3-2

    AP2W78x-2RR

    AP1W78x-2RRAP3W78x-2RR

    Industrial Ethernet/PROFINET

    36

    Mobile Panel

    Data transfer

    AP: Access Point

    The data transfer takes places through cyclic polling (just like iPCF).Each mobile panel has a reserved data transfer window.

    iPCF-MC, management channel

    Figure 3-3

    AP2 W78x-2RR

    AP1 W78x-2RRAP3W78x-2RR

    Industrial Ethernet/PROFINET

    Mobile Panel

    48

    48

    48

    AP: Access Point

    An access point (AP) sends a beacon at regular intervals. This beacon containsinformation regarding the signal strength, SSID of the access point and the channelsettings of the data channel.

    These beacons are evaluated by the mobile panel.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    13/45

    3 Basics

    3.1 iPCF-MC concept

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 13

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    Roaming with iPCF-MC, sequence description

    The mobile panel regularly changes from the data channel to the managementchannel and evaluates the received beacons.

    In this case the beacon of access point 1 (AP1) is the strongest=> no roaming.

    Figure 3-4

    Industrial Ethernet/PROFINET

    36

    AP2 W78x-2RR

    AP1 W78x-2RRAP3W78x-2RR

    48

    48

    AP: Access Point

    40 48

    44

    36

    The mobile panel is now closer to access point 2 (AP2).With the next change to the management channel the beacon of

    access point 2 is stronger. => roaming on access point 2.

    Figure 3-5

    Industrial Ethernet/PROFINET

    AP2 W78x-2RR

    AP1 W78x-2RR AP3W78x-2RR48

    48

    AP: Access Point

    40 48

    44

    40

    36

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    14/45

    3 Basics-

    3.1 iPCF-MC concept

    14Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    iPCF-MC general conditions

    For the operation of iPCF-MC the following general conditions are required:

    at least three unused non-overlapping channels are required

    the management channel must not be operated on 802.11h (radar detection!)

    management channel and data channel must be precisely overlapped:

    both must either be in 2.4 GHz band or in 5 GHz band

    with the access point, WLAN1 and WLAN2 have to be equipped with thesame antennas

    Channel assignment for extensive plants

    When configuring the data channel, ensure that the addresses of neighboring datachannels do not overlap.

    Figure 3-6

    Industrial Ethernet/PROFINET

    AP2W78x-2RR

    AP1 W78x-2RR

    48

    48

    AP: Access Point

    36

    AP3 W78x-2RR

    48

    44

    40

    AP4 W78x-2RR

    48

    36

    Same address possible

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    15/45

    3 Basics

    3.2 Applicable WLAN standards for the mobile panel

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 15

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    3.2 Applicable WLAN standards for the mobile panel

    Table 3-1

    Mobile Panel277 IWLAN

    Mobile Panel277F IWLAN

    Mobile Panel277F RFID

    *)

    IEEE 802.11a 5 GHz Yes Yes Yes

    IEEE 802.11b 2.4 GHz

    Yes

    Only, if no zoneconfigured

    No Yes

    IEEE 802.11g 2.4 GHz

    Yes

    Only, if no zoneconfigured

    No Yes

    IEEE 802.11h 5 GHz Yes Yes Yes

    *) Only Mobile Panel 277F IWLAN V2

    Supported protocols:

    DCF (standard WLAN without roaming)

    iPCF (only Mobile Panel 277F IWLAN V2 without roaming)

    iPCF-MC (only Mobile Panel 277F IWLAN V2)

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    16/45

    4 Configuration Process-

    4.1 Preparatory measures for the configuration

    16Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    4 Configuration ProcessThe chapters that follow describe the required settings and configurations for thecommunication between the access points and the mobile panel.

    4.1 Preparatory measures for the configuration

    Before you start with the configuration, determine the addresses of the individualhardware components.

    4.1.1 IP addresses

    Define the IP addresses of the individual Ethernet nodes.The following table lists the IP addresses and the MAC addresses used for theapplication.

    Table 4-1

    IP Address Mac Address Device name

    Mobile Panel 277F IWLAN 172.16.34.210 2-34-56-78-9a-bc Mobile277fiwlan

    SCALANCE 788W-2RR 172.16.34.200 00-0E-8C-D3-1E-43 CS3-Network-011

    SCALANCE 788W-2RR 172.16.34.202 00-0E-8C-D3-1D-3B CS3-Network-012

    4.2 SCALANCE W788-2RR configuration

    The settings are necessary for each configuration. Only the respective addresseshave to be adjusted (see chapter4.2.4).

    Note Please note that the SCALANCE W788-2RR has numerous parameter andsetting options.This document describes only the points that are necessary for this application.For detailed information on the individual parameters, please refer to theSCALANCE W78-2RR configuration manual, under entry ID: 42784493.

    http://support.automation.siemens.com/WW/view/en/42784493http://support.automation.siemens.com/WW/view/en/42784493
  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    17/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 17

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    4.2.1 Assigning the IP address for the SCALANCE W788-2RR

    If you have not yet assigned an IP address to the SCALANCE W788-2RR, follow

    the instructions listed in the table below.Table 4-2

    No. Action Additional information

    1. Use an Ethernet cable to connect theSCALANCE W788-2RR to your PC.

    2. Open the SIMATIC Manager.

    3. Setting the PG/PC interface:

    Select theOptions > Set PG/PC Interface menucommand and set the PG/PC interface toEthernet.

    4. Editing the Ethernet node:

    Select thePLC > Edit Ethernet Node... menu command.

    TheEdit Ethernet Node dialog box opens.

    5. Select the Browse button. The Browse Network dialog box opens.

    Now all available nodes on the Ethernetnetwork are displayed.

    6. Select the MAC address of your SCALANCEW788-2RR and confirm it by selecting OK.

    7. Select the MAC address of your SCALANCEW788-2RR and confirm it by selecting OK.

    The Browse Network dialog box closes andthe Edit Ethernet Node dialog box opens.

    8. In Set IP Configuration, you can now specifythe IP address and the subnet mask.

    In this example172.16.34.200255.255.0.0

    9. Then click on the Assign IP Configurationbutton.

    The data is transferred.

    10. In Assign Device Name, you can specify adevice name.

    In this example"CS3-Network-011"

    11. Then click on the Assign name button. The data is transferred.

    Note Instead of the SIMATIC Manager, you can also use PST (Primary Setup Tool).

    Detailed information on PST is available on the Customer Support pages, IDnumber: 19440762.

    http://support.automation.siemens.com/WW/view/en/19440762http://support.automation.siemens.com/WW/view/en/19440762
  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    18/45

    4 Configuration Process-

    4.2 SCALANCE W788-2RR configuration

    18Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    4.2.2 Configuring the SCALANCE W788-2RR via the WEB

    Once you have assigned an IP address to the SCALANCE W788-2RR, you can

    access the home page of the W788-2RR (Web Based Management) using a webbrowser and perform the parameterization.

    If you do not know the username or the current password, it is recommendedthat the SCALANCE W788-2RR is initially reset to factory settings. For this reset,please note the information in the SCALANCE W788-2RR (Link) configurationmanual.

    Note The configuration of the individual access points are essentially the same.What parameters have to be adjusted accordingly can be found under thefollowing Link.

    Logon via Web Based Management

    Table 4-3

    No. Action Screens

    1. In the address bar of the web browser, enterthe IP address or the URL of the SCALANCEW788-2RR.Once a connection to the SCALANCE W788-2RR has been established, the logon screenof Web Based Management is displayed.

    In this example:IP address: http://172.16.34.200

    Note:if you have already configured the securitysettings with the aid of the Wizard, enter thisIP address in the address bar of the webbrowser:https://172.16.34.200.

    2. In the User namedrop-down list, select Admin(read and write access).

    3. Enter your password. If you have not yetdefined a password, the default passwordsapply.

    Enter admin.

    4. Click on the Log On button to start thelogon.

    http://support.automation.siemens.com/WW/view/en/42784493http://support.automation.siemens.com/WW/view/en/42784493
  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    19/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 19

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    5. After successful logon, an explorer view isdisplayed that shows the different subfoldersfor parameterizing the SCALANCE W788-

    2RR.

    Configuring the basic functionality with the aid of the wizard

    Table 4-4

    No. Action Screens

    1. The Web based management offers severalwizards.

    First, use the Basic Wizard.(Wizard for general settings to ensure thebasic functionality of the device).

    Then use theSecurity Wizard.(The wizard supports you when setting failsafeparameters).

    2. Basic Wizard, IP Settings:

    on this page, enter the IP address and thesubnet mask.

    Make sure that the address is unique withinyour network.

    In this example:Specified IP address: selectedIP address: 172.16.34.200

    Subnet: 255.255.0.0

    Select the Next>> button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    20/45

    4 Configuration Process-

    4.2 SCALANCE W788-2RR configuration

    20Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    3. Basic Wizard, System Name:

    The system name (device name) identifies anode.

    In this example:

    System name: CS3-Network-011

    Select the Next>> button.

    4. Basic Wizard, Country code:

    Select the country code from the drop-downlist.

    In this example:

    Country code: GERMANY

    Select the Next>> button.

    5. Basic Wizard, Wireless Settings forWLAN 1:

    The configuration of the WLAN 1 (1) networkis defined on this page. This includes network

    name and transmission mode.

    In this example:SSID: CS3_Mobile_PanelWireless mode: 5 GHz 54Mbps (802.11a)

    Select the Next>> button.

    Notes:

    SSID name: When starting the mobilepanel, the mobile panel attempts toconnect to this wireless network.

    The Wireless Mode assigned here,

    should match the Wireless Mode forWLAN 2 (Link). The same is the case forthe mobile panel (Link).

    Wireless Mode 802.11b or802.11g onlyfor

    Mobile Panel 277F IWLAN (RFID)

    Mobile Panel 277 IWLAN (withoutsafety), if no transponders are used.

    1

    2

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    21/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 21

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    6. Basic Wizard, Channel Settings forWLAN 1:

    For the communication, an access point usesa specific channel of a frequency band.

    When assigning the Radio channel, ensurethat the neighboring channels are notoverlapped by the access points (Link).

    In this example:Auto channel select: disabledRadio channel: 36 (5180MHz)Antenna Type: ANT795-4MRAntenna cable length (in meters): 0

    Select the Next>> button.

    7. Basic Wizard, Wireless Settings forWLAN 2:

    The configuration of the WLAN 2 (1) networkis defined on this page. This includes networkname and transmission mode.

    In this example:SSID: Mobile_Panel_MC

    *)

    Wireless Mode: 5 GHz 54Mbps (802.11a)

    *) The SSID name between WLAN 1and WLAN 2 must be different.

    Select the Next>> button.

    Note:

    No 802.11h for Management Channel(Radar)

    Wireless Mode 802.11b or802.11g onlyfor

    Mobile Panel 277F IWLAN (RFID)

    Mobile Panel 277 IWLAN (withoutsafety), if no transponders are used.

    1

    2

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    22/45

    4 Configuration Process-

    4.2 SCALANCE W788-2RR configuration

    22Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    8. Basic Wizard, Channel Settings forWLAN 2:

    For the communication, an access point usesa specific channel of a frequency band.

    When assigning the Radio channel, ensurethat the neighboring channels are notoverlapped by the access points (Link).

    In this example:Outdoor AP mode: not selelectedRadio channel: 48 (5240MHz)Antenna Type: ANT795-4MRAntenna cable length (in meters): 0

    Select the Next>> button.

    9. Basic wizard, Summary Basic Wizard:

    After you have made all settings for the basicconfiguration, this page displays your selectedparameters.

    Select the Finish button to exit the BasicWizard.

    10. Wizards, Status:

    After clicking the Finish button, you getback to the Start page.

    First of all, carry out a restart and continue thesettings with the Security Wizard.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    23/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 23

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    11. System Restart:

    After completing the Wizard, perform arestart.

    The changes you have made becomeeffective after restarting the SCALANCE.

    In the System > Restart folder, you canuse the Restart button to restart thesystem.

    Configuring the security settings with the aid of the wizard

    Table 4-5

    No. Action Screens

    1. The security wizard enables a specification ofthe safety-relevant parameters.

    Note:for the use of PROFIsafe via WLAN, it is

    mandatory that specific security settings aremade.

    2. Security wizard, Security Settings:

    The password must comprise at least 20characters and consist of upper and lowercase letters, digits and special characters.

    In this example:

    Current Admin Password: adminNew Password: MobilePanel277F_IWLAN

    Select the Next>> button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    24/45

    4 Configuration Process-

    4.2 SCALANCE W788-2RR configuration

    24Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    3. Security wizard, Security Settings forManagement Interfaces:

    Security Settings for Management Interfaces.

    On this page, you define the protocols viawhich you access the configuration of theIWLAN device, for example, to be able tomake parameter changes.

    All protocols whose the checkbox was tickedcan be used for the configuration.

    Select only protocols that you actually use.

    In this example:the Allow management only from wiredinterface option must be selected.

    All other options can be selected.

    Select the Next>> button.

    4. Security wizard, Security Settings forSNMP Protocol:

    On this page you can apply the standardsettings.

    In this example:SNMPv1/v2 read only:: selected

    Select the Next>> button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    25/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 25

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    5. Security wizard, Security Settings forWLAN 1:

    Specifying access rights for WLAN 1

    In this example:SSID: CS3_Mobile_PanelEnable Suppress SSID broadcasting featurefor WLAN 1 disabledEnable Inter SSID communication forWLAN 1: selected

    Enable Intracell communication: Allowed

    Select the Next>> button.

    Note:the SSID name will be stored in theconfiguration and for the mobile panel.

    When starting the mobile panel, the mobilepanel attempts to connect to this wirelessnetwork.

    6. Security wizard, Security Settings forWLAN 1:

    Authentication and encryption to secure anetwork for WLAN 2.

    In this example:

    Security level for WLAN 1:None (open System)

    Select the Next>> button.

    Note:the encryption is configured later (Link).

    7. Security wizard, Security Settings forWLAN 2:

    Specifying access rights for WLAN 2

    In this example:SSID: Mobile_Panel_MCEnable Suppress SSID broadcasting featurefor WLAN 2 selectedEnable Inter SSID communication forWLAN 2: selected

    Enable Intracell communication: Allowed

    Select the Next>> button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    26/45

    4 Configuration Process-

    4.2 SCALANCE W788-2RR configuration

    26Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    8. Security wizard, Security Settings forWLAN 2:

    Authentication and encryption to secure anetwork for WLAN 2.

    In this example:Security level for WLAN 2:

    None (open System)

    Select the Next>> button.

    Note:the encryption is configured later (Link).

    9. Security wizard, Summary I:

    Once you have made all settings for thesecurity wizard, this page displays yourselected parameters.

    Select the Next>> button.

    10. Security wizard, Summary II:

    You have completed the first part of the safetysettings.

    Select the Finish button to exit the securitywizard.

    11. Wizards, Status:

    After clicking the Finish button, you getback to the Start page.

    First of all, carry out a restart and continue thesettings with the second part of the securitysettings.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    27/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 27

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    12. System Restart:

    After completing the Wizard, perform arestart.

    The changes you have made becomeeffective after restarting the SCALANCE.

    In the System > Restart folder, you canuse the Restart button to restart thesystem.

    13. Other necessary settings:

    The following menu options are not triggered through the WIZARD and must be selected throughthe menu tree.

    14. Services menu option:

    In the System > Services menu tree, callthe Services menu.

    Select the HTTPS only option.

    The other options can be used.

    Then click on the Set Values button.

    Once you have made the settings, theSCALANCE W788-2RR has to be restarted.

    Note:

    After the restart you have to enterhttps://172.16.34.200/ instead ofhttp://172.16.34.200/, to call the Homepageof SCALANCE.

    15. Security settings for iPCF-MC,Key table for Wireless Interface 1:

    Security > Keys > WLAN1

    Enter a key forData Channel. The key has to be made up of16 ASCII characters.

    In this example:Public key 1: PROFISAFE_Mobile

    Then click on the Set Values button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    28/45

    4 Configuration Process-

    4.2 SCALANCE W788-2RR configuration

    28Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    16. Security settings for iPCF-MC,Key table for Wireless Interface 2:

    Security > Keys > WLAN2

    Enter a key forManagement Channel. The key has to bemade up of 16 ASCII characters.

    In this example:Public key 1: PROFISAFE_Mobile

    Then click on the Set Values button.

    17. Security settings for iPCF-MCWireless Interface 1 Security Properties:

    Security > Basic WLAN > WLAN1

    In this example:Authentication type: Open SystemEncryption: selectedDefault WEP key: Select your key through

    the dropdown list.In this case:

    Key 1 - PROFISAFE_Mobile

    Suppress SSID broadcasting: deselectedInter SSID communication: selectedEnable Intracell communication: Allowed

    Then click on the Set Values button.

    18. Security settings for iPCF-MCWireless Interface 2 Security Properties:

    Security > Basic WLAN > WLAN2

    In this example:Authentication type: Open SystemEncryption: selectedDefault WEP key: Select your key through

    the dropdown list.In this case:

    Key 1 - PROFISAFE_MobileSuppress SSID broadcasting: deselectedInter SSID communication: selectedEnable Intracell communication: Allowed

    Then click on the Set Values button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    29/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 29

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    19. iPCF-MC

    I-Features > iPCF-MC"

    Enable iPCF-MC and assign which channelis intended for the Data Channel orManagement Channel.

    In this example:iPCF-MC enabled: selectedStrong AES-CCM encryption: selectedPNIO update time: 32ms

    Data Channel: WLAN1

    Management Channel: WLAN2

    Then click on the Set Values button.20. The settings for the first access point (SCALANCE W788-2RR) are now complete.

    21. System Restart:

    after completing the settings, perform arestart.

    The changes you have made becomeeffective after restarting the SCALANCE.

    In the System > Restart folder, you canuse the Restart button to restart thesystem.

    22. Now configure the other access points.The majority of parameters can be accepted from the first access point.

    Chapter4.2.4 lists the parameters you need to adjust individually for each access point.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    30/45

    4 Configuration Process-

    4.2 SCALANCE W788-2RR configuration

    30Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    4.2.3 Backing up data the SCALANCE W788-2RR

    It is recommended to create a data backup of each access point. If a device is

    replaced, you can therefore quickly load the configuration to the new device.Table 4-6

    No. Action Screens

    1. Saving or loading the configuration:

    in the System > Load&Save > HTTPfolder, you can save the configuration on yourPC at any time or load a previously savedsetting back to the PC.

    For this purpose, select the location and thenuse the Save orLoad buttons.

    Note:alternatively use the TFTP.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    31/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 31

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    4.2.4 Adjusting other access points

    Repeat the steps, described in chapter4.2.2. Alternatively, you can create a data

    backup from an already configured access point and upload it to another accesspoint. You only have to check or adjust the steps listed below.

    Configuring further access points

    You can use the Basic wizard again for the settings.

    Table 4-7

    No. Action Screens

    1. IP Settings:

    Assign an individual IP address for eachaccess point.

    In this example:IP address: 172.16.34.202Subnet mask: 255.255.0.0

    Select the Next>> button.

    2. System Name:

    assign an individual device name for eachaccess point.

    In this example:System name: CS3-Network-012

    Select the Next>> button.

    3. Wireless Settings for WLAN 1:

    in the application, WLAN 1 is used for theData Channel.

    Make sure that for all respective access

    points, the WLAN 1 is also configured asdata channel (Link).

    In this example:SSID: CS3_Mobile_PanelWireless mode: 5 GHz 54Mbps (802.11a)

    Select the Next>> button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    32/45

    4 Configuration Process-

    4.2 SCALANCE W788-2RR configuration

    32Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    4. Channel Settings for WLAN 1:

    when assigning the Radio channel, ensurethat the neighboring channels are notoverlapped by the access points (Link).

    In this example:Radio channel: 40 (5200MHz)Antenna Type: ANT795-4MRAntenna cable length (in meters): 0

    Select the Next>> button.

    5. Wireless Settings for WLAN 2:

    In the application WLAN 2 is used for themanagement channel.

    Make sure that WLAN 2 is also configuredas management channel (Link) for allrespective access points.

    In this example:Wireless mode: 5 GHz 54Mbps (802.11a)

    Select the Next>> button.

    Note:the SSID box can not be selected due to thealready enabled iPCF-MC enabledparameter underI-Features > iPCF-MC. (The SSID name isdisplayed by WLAN 1).

    6. Channel Settings for WLAN 2:

    in the application, WLAN 2 is used for themanagement channel.

    Ensure that all respective access points atthe radio channel are set to the same

    channel (Link).

    In this example:Radio channel: 48 (5240MHz)Antenna Type: ANT795-4MRAntenna cable length (in meters): 0

    Select the Next>> button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    33/45

    4 Configuration Process

    4.2 SCALANCE W788-2RR configuration

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 33

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    7. Summary Basic Wizard:

    this page displays the parameters you haveselected under the Basic Wizard.

    Press the Finishbutton and then perform arestart.

    The settings for the second access point arecomplete.

    No changes have to be made on theSecurity settings.

    Note:the security settings correspond to those ofthe first access point.

    8. iPCF-MC

    I-Features > iPCF-MC"

    Check the assignment of thedata channel and themanagement channel.

    In this example:iPCF-MC enabled: selectedStrong AES-CCM encryption: selectedPNIO update time: 32ms

    Data Channel: WLAN1Management Channel: WLAN2

    Then click theSet Value button(once you have performed the changes).

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    34/45

    4 Configuration Process-

    4.3 Configuring the mobile panel

    34Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    4.3 Configuring the mobile panel

    4.3.1 Hardware settings

    Network and dial-up connections

    In Network and Dial-up Connections, you can change the network settings of theWLAN connections.The connection to the PLC and possible other WLAN components is establishedvia the network parameters.

    Table 4-8

    No. Action Screens

    1. Call the control panel of the mobile panel.

    2. Click on theNetwork and Dial-up Connections icon.

    A new page opens on which you can makethe WLAN settings.

    Click on the WLAN icon.

    A dialog box opens in which you can set theconnection parameters.

    Select theSpecify an IP address option and enter theIP address and subnet mask.

    Confirm the entries with OK and close thewindow using the File > Close menu bar.

    In this example:IP address: 172.16.34.210Subnet Mask: 255.255.0.0

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    35/45

    4 Configuration Process

    4.3 Configuring the mobile panel

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 35

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    PROFINET setting

    In PROFINET, you can specify the communication channel and the device name.

    Table 4-9

    No. Action Screens

    1. Call the control panel of the mobile panel.

    2.Click on the

    PROFINET icon.A dialog box opens.

    Select the following options:

    PROFINET IO enabled: selectedDevice name: Mobile277FIWLAN

    Confirm the entries with OK.

    Note:

    in the STEP 7 hardware manager, an IOdevice has been configured for the mobilepanel. In the object properties of this IOdevice, a device name is entered in General.

    This name must be applied here.Please note that the name is case sensitive.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    36/45

    4 Configuration Process-

    4.3 Configuring the mobile panel

    36Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    PROFIsafe setting

    In PROFIsafe, you set the PROFIsafe address.

    Table 4-10

    No. Action Screens

    3. Call the control panel of the mobile panel.

    4.Click on the

    PROFIsafe icon.A dialog box opens.

    In this dialog box, enter the PROFIsafeaddress.

    In this example:Address: 300

    Note:

    in the STEP 7 hardware manager, an IOdevice has been configured for the mobilepanel.

    Use the PROFIsafe > F_Dest_Add menu

    command to access an address in the objectproperties of the Mobile277Failsafe_IOmodule. This address must be applied here.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    37/45

    4 Configuration Process

    4.3 Configuring the mobile panel

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 37

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    Selecting frequency range for the transponder

    In the control panel under the OP Properties dialog, Transponder tab, you canspecify through which channel (frequency range) the operator panel communicates

    with the transponders.Table 4-11

    No. Action Screens

    1. Call the control panel of the mobile panel.

    2. Click on the OP icon.

    The OP Properties dialog box opens.

    Select the Transponder tab.

    Select the required WLAN channel throughthe dropdown list.

    The following options are available:

    Auto (all channels):the frequency hopping method searchesan unused frequency range within the 2.4GHz band.A free channel is selected automatically.

    List with several frequency rangeswithin the 2.4 GHz band:you can select a discrete frequency rangefrom this list.This enables you to determine whatchannel is used, and not the operatorpanel.

    The entry is saved by clicking the OK buttonand the dialog is closed.

    Note:setting the channel ensures the coexistence

    with other radio system. A possible error ofother networks can therefore be prevented.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    38/45

    4 Configuration Process-

    4.3 Configuring the mobile panel

    38Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    4.3.2 WLAN configuration

    A software assistant for the WLAN configuration is available via web interface.

    The settings below ensure secure data exchange between the SCALANCE W788-2RR and the mobile panel.

    The settings are always necessary for each configuration.

    Table 4-12

    No. Action Screens

    1. Call the control panel of the mobile panel.

    2. Click on the WLAN V2 Config icon.

    The following context menu opens.

    3. In the User namedrop-down list, select Admin(read and write access).

    4.Enter your password.If you have not yet defined a password, thedefault passwords apply.

    Enteradmin.

    5. Click on the Log On button to start thelogon.

    6. Note:

    if you do not know the password, the system has to be bootstrapped (reset the operating systemto the factory settings).How to bootstrap can be found under entry ID: 19701610

    7. After successful logon, a start page withvarious subfolders for the configuration of theWLAN configuration appears.

    http://support.automation.siemens.com/WW/view/en/19701610http://support.automation.siemens.com/WW/view/en/19701610
  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    39/45

    4 Configuration Process

    4.3 Configuring the mobile panel

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 39

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    Configuring the basic functionality with the aid of the wizard

    Table 4-13

    No. Action Screens

    1. The Web based management offers severalwizards.

    Basic

    Security

    iPCF

    In the status overview you can see whichwizards you have already completed.

    First of all, start with the Basic Wizard.

    2. Basic Wizard, Country code:

    Select the country code from the drop-down

    list.

    In this example:Country code: GERMANY

    Select the Next>> button.

    3. Basic Wizard, Wireless Settings:

    The configuration of the wireless network isdefined on this page. This includes networkname and transmission mode.

    In this example:Connect to ANY SSID: disabledSSID: CS3_Mobile_PanelWireless mode: 5 GHz 54Mbps (802.11a)

    Select the Next>> button.

    Notes:

    the SSID name will also be stored in theconfiguration of the mobile panel.When starting the mobile panel, themobile panel attempts to connect to this

    wireless network. the selected wireless mode should

    match the selected wireless mode ofSCALANCE W788-2RR (Link).

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    40/45

    4 Configuration Process-

    4.3 Configuring the mobile panel

    40Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    4. Basic Wizard, Channel Settings:

    due to the previously selected settings underWireless Mode you cannot make anysettings on this page.(In any case, the setting would not benecessary).

    Select the Next>> button.

    5. Basic Wizard, Summary Basic Wizard:

    after you have made all settings for the basicconfiguration, this page displays your selectedparameters.

    Select the Finish button to exit the Basic

    Wizard.

    6. Wizards, Status:

    After clicking the Finish button, you getback to the start page.

    First of all, carry out a restart and continue thesettings with theSecurity Wizard.

    7. System Restart:

    In the System > Restart folder, you canuse the Restart WLAN button to restart thesystem.

    The changes you have made becomeeffective after a restart.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    41/45

    4 Configuration Process

    4.3 Configuring the mobile panel

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 41

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    Configuring the security settings with the aid of the wizard

    Table 4-14

    No. Action Screens

    1. The security wizard enables a specification ofthe safety-relevant parameters.

    Note:for the use of PROFIsafe via WLAN, it ismandatory that specific security settings aremade.

    2. Security wizard, Security Settings:

    the password must comprise at least 20

    characters and consist of upper and lowercase letters, digits and special characters.

    In this example:Current Admin Password: adminNew Password: MobilePanel277F_IWLAN

    Select the Next>> button.

    3. Security wizard, Security Settings forWLAN:

    authentication and encryption.

    In this example:Security level: None (Open System)

    Select the Next>> button.

    4. Security wizard, Summary I:

    You cannot make any settings on this page.

    (Due to the previously selected setting underSecurity level).

    Select the Next>> button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    42/45

    4 Configuration Process-

    4.3 Configuring the mobile panel

    42Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    5. Security wizard, Summary II:

    The security settings through theSecurity Wizard are complete.

    Select the Finish button to exit the securitywizard.

    6. iPCF-MC settings, Key table for WirelessInterface:

    Security > Keys

    A key has to be entered in the key table, sothat the encryption is enabled during theOpen System authentication method.

    The key has to be made up of 16 ASCIIcharacters.

    In this example:Public key 1: PROFISAFE_Mobile

    Click the Set Values button.

    7. iPCF-MC Settings, Wireless SecurityProperties:

    Security > Basic WLAN

    Enable encryption

    In this example:Encryption: selectedDefault WEP key: Select the

    previously storedkey from thedrop-down list.In this case:

    PROFISAFE_Mobile

    Click the Set Values button.8. iPCF-MC settings, iPCF-MC:

    I-Features > iPCF-MC"

    In this example:iPCF-MC enabled: selectedStrong AES-CCM encryption: selectedBackground scan interval: 1

    Click the Set Values button.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    43/45

    4 Configuration Process

    4.3 Configuring the mobile panel

    Mobile Panel 277F IWLAN V2Version 1.0, Entry D: 25702331 43

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    No. Action Screens

    9. System Restart:

    In the System > Restart folder, you canuse the Restart WLAN button to restart thesystem.

    The changes you have made becomeeffective after a restart.

    The WLAN configuration of the mobile panel277F IWLAN V2 is complete.

    10. Saving or loading the configuration:

    In the System > Load&Save > HTTPfolder, you can save the configuration on your

    mobile panel or on a USB stick at any time orload a previously saved setting back.

    For this purpose, select the location and thenuse the Save orLoad buttons.

    What USB storage media are released can befound in the following entry ID: 21847868

    http://support.automation.siemens.com/WW/view/en/21847868http://support.automation.siemens.com/WW/view/en/21847868
  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    44/45

    5 Startup of the Application-

    4.3 Configuring the mobile panel

    44Mobile Panel 277F IWLAN V2

    Version 1.0, Entry D: 25702331

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    5 Startup of the Application

    Commissioning

    Table 5-1

    No. Action Screens

    1. Make sure that all access points (SCALANCEW788-2RR) have been configured.

    2. Make sure that the WLAN configuration of themobile panel 277F IWLAN is complete.

    3. Check the LEDs on the mobile panel.

    Once all WLAN settings are ok, the COMLED on the mobile panel has to light uppermanently.

    If this is not the case, check the WLANsettings on the SCALANCE W788-2RR or the

    mobile panel.

    4. Make sure that the STEP 7 configuration(standard and F program) was transferred andthe PLC is in RUN mode.

    5. The SAFE LED lights up when the mobilepanel is integrated in the safety program of

    the F-CPU.

    Continue with the operation of the mobilepanel.

  • 7/30/2019 25702331 MobilePanel277F IWLAN V2 Roaming En

    45/45

    6 Links & Literature

    CopyrightS

    ie

    mensAG2

    011Allrightsreserved

    6 Links & Literature

    Internet links

    The following list is by no means complete and only provides a selection ofappropriate sources.

    Table 6-1

    Topic Title

    /1/ STEP 7 Automating with STEP 7 in STL and SCL

    Hans Berger

    Wiley VCH

    ISBN-10: 3895782955 ISBN-13: 978-3895782954

    /2/ Operatinginstructions

    Operator Panel Mobile Panel 277F IWLAN V2http://support.automation.siemens.com/WW/view/en/41916038

    /3/ Safety: S7fcotia.xls spreadsheethttp://support.automation.siemens.com/WW/view/en/25412441

    /4/ IWLAN Execution times of the F blocks for the Mobile Panel 277FIWLAN

    http://support.automation.siemens.com/WW/view/en/27097159

    /5/ IWLAN Setup of an Industrial Wireless LAN

    http://support.automation.siemens.com/WW/view/en/22681042

    /6/ ConfigurationManual

    SCALANCE W-700

    http://support.automation.siemens.com/WW/view/en/42784

    493/7/ Configuration

    ManualS7 Distributed Safety, configuring and programming

    http://support.automation.siemens.com/WW/view/en/22099875

    7 History

    Table 7-1

    Version Date Changes

    V1.0 07.01.2011 First issue

    http://support.automation.siemens.com/WW/view/en/41916038http://support.automation.siemens.com/WW/view/en/41916038http://support.automation.siemens.com/WW/view/en/25412441http://support.automation.siemens.com/WW/view/en/25412441http://support.automation.siemens.com/WW/view/en/27097159http://support.automation.siemens.com/WW/view/en/27097159http://support.automation.siemens.com/WW/view/en/22681042http://support.automation.siemens.com/WW/view/en/22681042http://support.automation.siemens.com/WW/view/en/42784493http://support.automation.siemens.com/WW/view/en/42784493http://support.automation.siemens.com/WW/view/en/22099875http://support.automation.siemens.com/WW/view/en/22099875http://support.automation.siemens.com/WW/view/en/22099875http://support.automation.siemens.com/WW/view/en/22099875http://support.automation.siemens.com/WW/view/en/42784493http://support.automation.siemens.com/WW/view/en/42784493http://support.automation.siemens.com/WW/view/en/22681042http://support.automation.siemens.com/WW/view/en/22681042http://support.automation.siemens.com/WW/view/en/27097159http://support.automation.siemens.com/WW/view/en/27097159http://support.automation.siemens.com/WW/view/en/25412441http://support.automation.siemens.com/WW/view/en/25412441http://support.automation.siemens.com/WW/view/en/41916038http://support.automation.siemens.com/WW/view/en/41916038