1 About this document
Maschinenfabrik Reinhausen 2011 2332837/01 EN DEETAP AR 3
1 About this document
1.1 Validity of this quick reference guide
This document cannot take the place of the operating instructions provided upon delivery.
Always note the safety instructions and information provided in the operating instructions.
Always follow the directions in the operating instructions if the delivery is damaged or incomplete or if you are not sure how to handle the delivery.
-
2 Fastening off-circuit tap-changer to active part
Maschinenfabrik Reinhausen 2011 2332837/01 EN DEETAP AR 5
2 Fastening off-circuit tap-changer to active part
When fastening the off-circuit tap-changer to the active part, ensure that the off-circuit tap-changer has the correct installation dimension if it is to be driven via an insulating drive shaft of the standard length. The installation dimension varies depending on the off-circuit tap-changer model and is either the dis-tance between the top edge of the mounting flange and center of the top sup-porting link or the distance between the center of the bottom supporting link and bottom edge of the step-by-step gear (see table below).
Highest voltage for equipment Um
Installation dimension I1 for upwards insulat-
ing drive shaft
Installation dimension I1 for downwards in-sulating drive shaft
72.5 kV 981 mm 1105 mm 170 kV 1281 mm 1405 mm 245 kV 1781 mm 1905 mm
Table 1 Installation dimension I1 of off-circuit tap-changer
Figure 1 Installation dimension I1 of off-circuit tap-changer
-
2 Fastening off-circuit tap-changer to active part
6 DEETAP AR 2332837/01 EN Maschinenfabrik Reinhausen 2011
NOTE
Damage to property!
Danger of damage to the off-circuit tap-changer and transformer due to incorrectly measured attachment points!
Fasten off-circuit tap-changer in transformer in isolating manner.
Measure attachment points according to the loads caused by the mass of the off-circuit tap-changer and torques when undertaking switch operation. The mass of the off-circuit tap-changer should be taken from the dimen-sional drawings in the appendix. The switching torques required should be taken from the table below.
Rated through current Switching torque
1000 A 30 Nm 2000 A 60 Nm 3000 A 90 Nm
Table 2 Switching torque
Secure off-circuit tap-changer to active part with 4 screws. The screws are not included in the scope of supply.
Figure 2 Fastening off-circuit tap-changer to active part
-
3 Connecting off-circuit tap-changer to transformer winding
Maschinenfabrik Reinhausen 2011 2332837/01 EN DEETAP AR 7
3 Connecting off-circuit tap-changer to transformer winding
NOTE
Mechanical load will damage the off-circuit tap-changer!
Connection leads which place the off-circuit tap-changer under mechan-ical load will damage the off-circuit tap-changer!
Establish and secure connections with care.
Install the connection leads so that the application of force on the off-circuit tap-changer is minimal during all operational, testing and malfunction con-ditions (e. g. short circuit).
Connect connecting leads without warping or deforming.
The cable diameter is 20 mm at current levels of up to 1000 A and 32 mm at current levels above 1000 A.
1. Remove safety caps from top and bottom flexible connecting leads.
Figure 3 Safety caps
-
3 Connecting off-circuit tap-changer to transformer winding
8 DEETAP AR 2332837/01 EN Maschinenfabrik Reinhausen 2011
NOTE
Damage to off-circuit tap-changer and transformer!
Damage to off-circuit tap-changer and transformer resulting from short circuit/flashover!
Connect connecting leads to transformer winding such that they do not protrude by an impermissible distance into the ground insulation clear-ance.
Figure 4 Grounding insulation distance
1 Insulating drive shaft 2 Connecting lead 3 Grounding insulation distance
Highest voltage for equipment Um Grounding insulation dis-tance
72.5 kV 175 mm 170 kV 420 mm 245 kV 700 mm
Table 3 Grounding insulation distance
-
3 Connecting off-circuit tap-changer to transformer winding
Maschinenfabrik Reinhausen 2011 2332837/01 EN DEETAP AR 9
2. Connect off-circuit tap-changer's flexible connecting leads with ferrules to transformer winding following the detailed connection diagram supplied with the delivery. The ferrules are not included in the scope of supply.
Cables must not be laid inside a circumference of 100 mm around the off-circuit tap-changer's drive shaft because otherwise the insulating drive shaft cannot connect with the off-circuit tap-changer.
Figure 5 Flexible connecting leads
3. Wrap paper around flexible connecting leads after connection to trans-former winding in order to insulate.
-
4 MR worldwirde
Maschinenfabrik Reinhausen 2011 2332837/01 EN DEETAP AR 11
4 MR worldwirde
Australia Reinhausen Australia Pty. Ltd. Ground Floor 6-10 Geeves Avenue Rockdale N. S. W. 2216 Phone: +61 2 9556 2133 Fax: +61 2 9597 1339 E-Mail: [email protected]
Italy Reinhausen Italia S.r.l. Via Alserio, 16 20159 Milano Phone: +39 02 6943471 Fax: +39 02 69434766 E-Mail: [email protected]
Russian Federation OOO MR Naberezhnaya Akademika Tupoleva 15, Bld. 2 ("Tupolev Plaza") 105005 Moscow Phone: +7 495 980 89 67 Fax: +7 495 980 89 67 E-Mail: [email protected]
Brazil MR do Brasil Indstria Mecnica Ltda. Av. Elias Yazbek, 465 CEP: 06803-000 Embu - So Paulo Phone: +55 11 4785 2150 Fax: +55 11 4785 2185 E-Mail: [email protected]
Japan MR Japan Corporation German Industry Park 1-18-2 Hakusan, Midori-ku Yokohama 226-0006 Phone: +81 45 929 5728 Fax: +81 45 929 5741
South Africa Reinhausen South Africa (Pty) Ltd. No. 15, Third Street, Booysens Reserve Johannesburg Phone: +27 11 8352077 Fax: +27 11 8353806 E-Mail: [email protected]
Canada Reinhausen Canada Inc. 1010 Sherbrooke West, Suite 1800 Montral, Qubec H3A 2R7, Canada Phone: +1 514 286 1075 Fax: +1 514 286 0520 Mobile: +49 170 7807 696 E-Mail: [email protected]
Luxembourg Reinhausen Luxembourg S.A. 72, Rue de Prs L-7333 Steinsel Phone: +352 27 3347 1 Fax: +352 27 3347 99 E-Mail: [email protected]
South Korea Reinhausen Korea Ltd. Baek Sang Bldg. Room No. 1500 197-28, Kwanhun-Dong, Chongro-Ku Seoul 110-718, Korea Phone: +82 2 767 4909 Fax: +82 2 736 0049 E-Mail: [email protected]
India Easun-MR Tap Changers Ltd. 612, CTH Road Tiruninravur, Chennai 602 024 Phone: +91 44 26300883 Fax: +91 44 26390881 E-Mail: [email protected]
Malaysia Reinhausen Asia-Pacific Sdn. Bhd Level 11 Chulan Tower No. 3 Jalan Conlay 50450 Kuala Lumpur Phone: +60 3 2142 6481 Fax: +60 3 2142 6422 E-Mail: [email protected]
U.S.A. Reinhausen Manufacturing Inc. 2549 North 9th Avenue Humboldt, TN 38343 Phone: +1 731 784 7681 Fax: +1 731 784 7682 E-Mail: [email protected]
Iran Iran Transfo After Sales Services Co. Zanjan, Industrial Township No. 1 (Aliabad) Corner of Morad Str. Postal Code 4533144551 E-Mail: [email protected]
P.R.C. (China) MR China Ltd. (MRT) 360 4E 200120 86 21 61634588 86 21 61634582 [email protected] [email protected]
United Arab Emirates Reinhausen Middle East FZE Dubai Airport Freezone Building Phase 6, 3rd floor, Office No. 6EB 341 Dubai Phone: +971 4 2368451 Fax: +971 4 2368225 E-Mail: [email protected]
-