INPUT_DATA
Page 1
Please change only the data written in BLUE color
Name of SubstationContract No.ProtectionRelay FunctionTypeSerial No.Rated VoltageRated transformerLowside VoltagePercentage of Phase Current SetPercentage of Ground Current SetCT Ratio Primary
Secondary
SLG Fault Current at 115 KVPhase Operating Time
Ground Operating Time
Instanteneous Settings ( for Ground Fault)
Instanteneous Time
SET I>> = 1 * MAX FAULT 22KV
SET IE>> = 1 * MAX FAULT 22KV
22kV 3 PHASE FAULT = 34944.4 AINST. FAULT SETTING = BLOCK22kV SLG FAULT = 9831.8 AINST. FAULT SETTING =1872
tI>> = 0.25
SLG Fault Current at 115 KV
Instanteneous Time
3f Fault Current at 115 KV
Instanteneous Settings ( for 3f Overcurrent)
3f Fault Current at 115 KV
INPUT_DATA
Page 2
22kV 3 PHASE FAULT = 6685.02 A
INST. FAULT SETTING = 7362 A
22kV SLG FAULT = 1880.87 A
INST. FAULT SETTING = 7362 A
tI>> = 0.6
Relay Function
Type
Percentage of Overloading
Relay Operating Time
Rate Current
Time Delay
U< 3 sec
U<< 1.5 sec
U> 2 sec
U>> 1 sec
Formula
ST 0.05 0.04
SI 0.14 0.02
IN 9.4 0.7
VI 13.5 1
EI 80 2
LT 120 1
2
2
K IF
I> 0.14 3.714
Ie> 0.14 1.045
INPUT_DATA
Page 3
ROT CHANA
PEA - TSD.6.1.P-3.7/2550
22 kV BUS SECTION FEEDER50 / 51 & 50/51G 50BF set I<AREVA P142
primary
115 kV 115000 V
50 MVA22 kV
125 %25 %
1800 A 1800
1 A34,944.40 A 6685.02 A9,831.80 A 1880.87 A
0.6 Second
0.6 Second xIn
34,944.40 6685.01565217391 3.71
9831.8 1880.86608695652 1.04
0.25 Second
1
1
For LV coordinate
34,944.40 A9,831.80 A
0.6 Second
INPUT_DATA
Page 4
For HV coordinate
50 / 62BF
MICOM P127
10 %
0.3 Sec
3,156.00
Short Time Inverse
Standard Inverse
Inverse
Very Inverse
Extremely Inverse
Long Time Inverse
IS α
0.92 0.02
0.19 0.02
INPUT_DATA
Page 5
secondary115 V 66.4
pri sec ratio300 1 300600 1 600
Through fault to high sideThrough fault to high side
Through fault to Low side
1.04 1872
INPUT_DATA
Page 6
SUBSTATION : ROT CHANA CONTRACT NO. :
PROTECTION : 22 kV BUS SECTION FEEDER
RELAY Fn. : 50 / 51 & 50/51G TYPE :
CALCULATED BY : DATE :
APPROVED BY : DATE :
REMARKS :
Capacity of Transformer line = (50 MVA / SQ.RT.3 * 22 kV )
= 1312.16
Rated Current = 1312.16
Select CT RATIO = 1800
For Phase Fault SettingsMinimum Pick up current at 125% of Full Load Current of Transformer
= 1640.20
= 0.911
= 0.911
Relay setting value I> = 0.920
= 6,685.02
= 3.714
= 3.714
= 4.037
Select Standard Inverse Curve (SI)
= 4.037
Time , T = 0.14 * ( TMS ) / [ ((IF / Is)^0.02)-1]
= 4.9465 * (TMS)
Required Operating Time = 0.6
TMS = 0.121
Choose TMS I> Setting = 0.125
Ins. Setting I>> = 4.09
Ins. Setting Time = 0.25
Actual Operating Time I> = 0.618
For Ground Fault SettingsMinimum Pick up current at 25% of Full Load Current of Transformer
= 328.040
= 0.182
= 0.182
Relay setting value Ie> = 0.190
Maximum SLG Fault current = 1,880.87
= 1.045
= 1.05
= 5.50
Select Standard Inverse Curve (SI)
= 5.50
Time , T = 0.14 * ( TMS ) / [ ((IF / Is)^0.02)-1]
= 4.0366 * (TMS)
Required Operating Time = 0.6
TMS = 0.149
Choose TMS I> Setting = 0.125
Maximum 3 f Fault current
IF / Is
IF / Is
Ins. Setting Ie>> = 4.09
Ins. Setting Time = 0.25
Actual Operating Time Ie> = 0.505
PEA - TSD.6.1.P-3.7/2550
AREVA P142
(50 MVA / SQ.RT.3 * 22 kV )
A
/ 1 A
A Primary
A Secondary
A (SEE ANNEX)
A Secondary
0.14 * ( TMS ) / [ ((IF / Is)^0.02)-1]
Second
(~ 110% Max. Fault)
Second
Second
A Primary
A Secondary
A (SEE ANNEX)
A Secondary
0.14 * ( TMS ) / [ ((IF / Is)^0.02)-1]
Second
IN
IN
IN
Is
IN
IN
IN
Is
(~ 110% Max. Fault)
Second
Second
SUBSTATION : ROT CHANA CONTRACT NO. :
PROTECTION : 22 kV BUS SECTION FEEDER
RELAY Fn. : 50BF set I< TYPE :
CALCULATED BY : DATE :
APPROVED BY : DATE :
REMARKS :
Capacity of Transformer line = (50 MVA / SQ.RT.3 * 22 kV )
= 1312.16
Rated Current = 1312.16
Select CT RATIO = 1800
For Breaker Failure SettingsPick up under current at 10% of CT Rating
= 180.00
= 0.100
= 0.100
Relay setting value I< = 0.100
= 6,685.02
= 3.714
Breaker Failure I< < 3.714
Breaker Failure is operated at Phase Fault
Maximum SLG Fault current = 1,880.87
= 1.045
Breaker Failure I< < 1.045
Breaker Failure is operated at Earth Fault
Time of BF Tbf = 300
Maximum 3 f Fault current
PEA - TSD.6.1.P-3.7/2550
AREVA P142
(50 MVA / SQ.RT.3 * 22 kV )
A
/ 1 A
A Primary
A Secondary
A (SEE ANNEX)
A Secondary
A Secondary
A (SEE ANNEX)
A Secondary
A Secondary
ms
IN
IN
SUBSTATION : ROT CHANA CONTRACT NO. :
PROTECTION : 22 kV BUS SECTION FEEDER
RELAY FUNCTION : 50 / 51 & 50/51G TYPE :
SETTING FOR AREVA : P142 RELAY
Setting
SYSTEM DATA Language English Sys Fn Lonks 0
Description MiCOM P142Plant Reference MiCOMFrequency 50 Hz
CB CONTROL CB Control by Opto+Local
Close Pulse Time 500 ms Trip Pulse Time 500 ms Man Close Delay 10 s
CB Healthy Time 5 s Reset Lockout by CB Close Man Close RstDly 5 s CB Status Input None
DATE AND TIME Battery Alarm Disabled,Enabled
CONFIGURATION Setting Group Select via Menu Active Settings Group 1 Setting Group 1 Enabled Setting Group 2 Disabled
Setting Group 3 Disabled Setting Group 4 Disabled System Confic Invisible Overcurrent Enabled Neg Sequence O/C Disabled Broken Conductor Disabled Earth Fault 1 Enabled Earth Fault 2 Disabled SEF/REF Prot'n Disabled Residual O/V NVD Disabled Thermal Overload Disabled Neg Sequence O/V Disabled System Check Enabled Cold Load Pickup Disabled Selective Logic Disabled Admit Protection Disabled Volt Protection Disabled Freq Protection Disabled df/dt Protection Disabled CB Fail Enabled Supervision Enabled Fault Locator Enabled System Checks Disabled
Auto-Reclose Disabled Input Labels Visible Output Labels Visible CT & VT Ratios Visible Recorder Control Invisible Disturb Recorder Invisible Measure 't Setup Invisible
Comms Settings Visible Commission Tests Visible
Setting Values Secondary Control Inputs Visible Ctrl I/P Config Visible Ctrl I/p Labels Visible LCD Contrast 11
CT AND VT RATIOS Main VT Primary 115 kV Main VT Sec'y 115 V Phase CT Primary 115 kV Phase CT Sec'y 115 V E/F CT Primary A E/F CT Secondary A SEF CT Primary 1800 A SEF CT Secondary 1 A
CB MONITOR SETUP Broken I^ 2 I^ Maintenance Alarm Disabled I^ Maintenance - A I^ Lockout Alarm Disabled I^ Lockout - A No. CB Ops Maint Alarm Disabled No. CB Ops Maint - A No. CB Ops Lock Alarm Disabled No. CB Ops Lock - A CB Time Maint Alarm Disabled CB Time Maint - ms CB Time Lockout Alarm Disabled CB Time Lockout - ms Fault Freq Lock Alarm Disabled Fault Freq Count - Fault Freq Time 3600 s Reset Lockout By CB Close Man Close RstDly 5 s
OPTO CONFIG Global Nominal V 110/125V Opto Filter Cntl 0000 0001 Characteristic Standard 60%-80%
Group1 Overcurrent I>1 Function IEC S Inverse I>1 Directional Non-Directional km I>1 Current Set 0.92 I>1 TMS 0.1 I>1 DT Adder 0.0 I>1 tRESET 0 I>2 Function DT
I>2 Direction Non-Directional I>2 Current 4.09 I>2 Time Delay 0.25 s I>2 tRESET 0.00 s I>3 Status Disable I>4 Status Disable I> Blocking 00000000 I> Char Angle 1.32 Deg VCO Status Disable
Group1 Earth Fault 1 : In1>1 Function IEC S Inverse In1>1 Direction Non-Directional In1>1 Current 0.19 In1>1 TMS 0.125 In1>1 DT Adder 0.00 s In1>1 tRESET 0.00 s In1>2 Function DT In1>2 Direction Non-Directional In1>2 Current 4.09 In1>2 Time Delay 0.25 s In1>2 tRESET 0.00 s In1>3 Status Disable In1>4 Status Disable In1> Blocking 000000 In1> Char Angle 0.00 Deg In1> Pol Zero Sequence In1> Vnpol Set 20.00 V
Group1 CB Fail & I< : CB Fail 1 Status Enable CB Fail 1 Timer 300.0 ms CB Fail 2 Status Disable Volt Prot Reset CB Open & I< Ext Prot Reset CB Open & I< I< Current Set 100 mA In< Current Set 100 mA ISEF< Current 20 mA Remove I> start Disable s Remove IN> start Disable
Group 1 Supervision VTS Status DT VTS Reset Mode Manual VTS Time Delay 2.000 s VTS I> Inhibit 0.00 A VTS I2> Inhibit 0.00 ms CTS Status Disable
GROUP 1 Fault Locator Line Length 0.000 mi Line Impedance 0.00 Ohm Line Angle 0.00 Deg KZN Residual 0.000 KZN Res Angle 0.00 Deg
GROUP 1 Input Labels
Opto Input 1 Input L1 Opto Input 2 Input L2 Opto Input 3 Input L3 Opto Input 4 Input L4 Opto Input 5 Input L5 Opto Input 6 Input L6 Opto Input 7 Input L7 Opto Input 8 Input L8
GROUP 1 Output Labels Relay 1 Output R1 Relay 2 Output R2 Relay 3 Output R3 Relay 4 Output R4 Relay 5 Output R5 Relay 6 Output R6 Relay 7 Output R7 Relay 8 Output R8 Relay 9 Output R9 Relay 10 Output R10 Relay 11 Output R11
AREVA P142
Setting Range
Min Max Step
English, Franais0=Trip LED, 1=Reset
MiCOM P142
50Hz 60Hz 10Hz
Disabled,Local,RemoteLocal+RemoteOpto,Opto+Local,Opto+Remote
Opto+Rem+Local100 ms 10 s 10 ms100 ms 5 s 10 ms100 ms 600 s 10 ms100 ms 999 s 10 ms
User Interface, CB Close100 ms 999 s 10 ms
None,52A,52B,Bolt 52A AND 52B
Select via Menu,Select via OptoGroup 1-4
Disabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledInvisible,VisibleDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,EnabledDisabled,Enabled
Disabled,EnabledInvisible,VisibleInvisible,VisibleInvisible,VisibleInvisible,VisibleInvisible,VisibleInvisible,VisibleInvisible,VisibleInvisible,Visible
Primary,SecondaryInvisible,VisibleInvisible,VisibleInvisible,Visible 0.01s
0 31 1
0.04s 100s 0.01sNo or Yes or Dir
0.5 In 40 In 0.01 InDMT or IDMT or RI
CRUVE0.025 1.5 0.025
0s 150s 0.01sNo or Yes or Dir
1 2 0.1Alarm Enabled, Alarm Disabled
1A 25kA 1AAlarm Enabled, Alarm Disabled
1A 25kA 1AAlarm Enabled, Alarm Disabled
1 10000 1Alarm Enabled, Alarm Disabled
1 10000 1Alarm Enabled, Alarm Disabled
5 ms 500 ms 1 msAlarm Enabled, Alarm Disabled
5 ms 500 ms 1 msAlarm Enabled, Alarm Disabled
0 9999 10 s 9999 s 1 s
CB Close ,User interface10 ms 600 s 10 ms
30/34V,48/54V,110/125V,220/250V,CustumInput L1-L8
Standard 60%-80%,50%-70%
IEC S,V,E Inverse, UK LT Inverse, UK RectifierNon-Directional, Directional Fwd,Rev
0.08 4 0.010.025 A 1.2 A 0.005 A
0s 100 s 10 ms0 s 100 s 10 ms
Disable,IEC S,V,E Inverse,UK LT Inverse,UK Rectifier
Non-Directional, Directional Fwd,Rev80 mA 4 A 10 mA
0 s 200 s 0.01 s0 s 100 s 11 ms
Disable,EnableDisable,Enable
VTS Blocks I>1-4, AR Blocks I>3-4(-95) 95 1 Deg
Disable,I>1,I>2,Bolt I>1& I>2
IEC S,V,E Inverse, UK LT Inverse, UK RectifierNon-Directional, Directional Fwd,Rev
80 mA 4 A 10 mA0.025 1.2 0.005
0 s 100 s 10 ms0 s 100 s 11 ms
Disable,IEC S,V,E Inverse,UK LT Inverse,UK RectifierNon-Directional, Directional Fwd,Rev
80 mA 4 A 10 mA0 s 200 s 0.01 s0 s 100 s 11 ms
Disable,EnableDisable,Enable
VTS Blocks I>1-4, AR Blocks I>3-4(-95) 95 1 Deg
Zero Sequence, Neg Sequence2 V 320 V 2 V
Disable,Enable0 s 10 s 10 ms
Disabled,EnabledI<Only,CB Open & I<,Prot Reset & I<I<Only,CB Open & I<,Prot Reset & I<
0.02 A 3.2 A 0.01 A0.02 A 3.2 A 0.01 A1 mA 800 mA 500 uA
Disabled,EnabledDisabled,Enabled
Blocking,IndicationManual,Auto
1 s 10 s 0.1 s80 mA 32 A 0.01 A50 mA 500 mA 10 mA
Disable,Enable
0.005 mi 621 mi 0.005mi0.4 Ohm 1000 Ohm 0.04 Ohm
20 85 1 Deg0 7 0.01
(-90) 90 1 Deg
GRAPH_DATA
Page 21
t = 0.14 x (TMS)/((IF/IS)^0.02-1)
t t
PH O/C E/F O/C
through phase o/c
side A
1792.9545 343
2054.3182 393
2315.6818 443
2577.0455 493
2838.4091 543
3099.7727 593
3361.1364 643
3622.5 693
3883.8636 743
4406.5909 843
4929.3182 943
5452.0455 1043
5974.7727 1143
6497.5 1243
IF
GRAPH_DATA
Page 22
7020.2273 1343
7542.9545 1443
8065.6818 1543
8745.2482 1673.004 85.6432
9111.1573 1743.004 17.0794
9477.0664 1813.004 9.6512
9842.9755 1883.004 6.8025
10208.885 1953.004 5.2955
10574.794 2023.004 4.3624
10940.703 2093.004 3.7275
11306.612 2163.004 3.2673
11672.521 2233.004 2.9182
12038.43 2303.004 2.6443
12404.339 2373.004 2.4235
12770.248 2443.004 2.2416
13136.157 2513.004 2.0892
13502.066 2583.004 1.9596
13867.975 2653.004 1.8479
14233.885 2723.004 1.7507
14599.794 2793.004 1.6652
GRAPH_DATA
Page 23
14965.703 2863.004 1.5895
15331.612 2933.004 1.5220
15697.521 3003.004 1.4613
16063.43 3073.004 1.4066
16429.339 3143.004 1.3568
16795.248 3213.004 1.3114
17161.157 3283.004 1.2698
18729.339 3583.004 1.1250
20297.521 3883.004 1.0180
21865.703 4183.004 0.9356
23433.885 4483.004 0.8699
25002.066 4783.004 0.8162
26570.248 5083.004 0.7715
28138.43 5383.004 0.7335
29706.612 5683.004 0.7009
31274.794 5983.004 0.6725
32842.975 6283.004 0.6475
33365.703 6383.004 0.6398
33888.43 6483.004 0.6324
34411.157 6583.004 0.6253
GRAPH_DATA
Page 24
34672.521 6633.004 0.6219
34933.885 6683.004 0.6185
35195.248 6733.004 0.6151
35456.612 6783.004 0.6119
35717.975 6833.004 0.6086
35979.339 6883.004 0.6055
36240.703 6933.004 0.6024
36502.066 6983.004 0.5993
36554.339 6993.004 0.5987
36815.703 7043.004 0.5957
37077.066 7093.004 0.5928
37338.43 7143.004 0.5899
37599.794 7193.004 0.5871
37704.339 7213.004 0.5859
37808.885 7233.004 0.5848
37913.43 7253.004 0.5837
38017.975 7273.004 0.5826
38122.521 7293.004 0.5815
38227.066 7313.004 0.5804
38331.612 7333.004 0.5793
GRAPH_DATA
Page 25
38436.157 7353.004 0.5783
38483.182 7362 0.2500
38535.455 7372 0.2500
38587.727 7382 0.2500
38640 7392 0.2500
38692.273 7402 0.2500
38744.545 7412 0.2500
38796.818 7422 0.2500
38849.091 7432 0.2500
38901.364 7442 0.2500
39946.818 7642 0.2500
40992.273 7842 0.2500
42037.727 8042 0.2500
43083.182 8242 0.2500
44128.636 8442 0.2500
45174.091 8642 0.2500
46219.545 8842 0.2500
47265 9042 0.2500
48310.455 9242 0.2500
52492.273 10042 0.2500
GRAPH_DATA
Page 26
56674.091 10842 0.2500
60855.909 11642 0.2500
65037.727 12442 0.2500
69219.545 13242 0.2500
73401.364 14042 0.2500
77583.182 14842 0.2500
81765 15642 0.2500
85946.818 16442 0.2500
90128.636 17242 0.2500
94310.455 18042 0.2500
99537.727 19042 0.2500
104765 20042 0.2500
109992.27 21042 0.2500
115219.55 22042 0.2500
120446.82 23042 0.2500
125674.09 24042 0.2500
130901.36 25042 0.2500
136128.64 26042 0.2500
141355.91 27042 0.2500
146583.18 28042 0.2500
GRAPH_DATA
Page 27
151810.45 29042 0.2500
156818.18 30000 0.2500
GRAPH_DATA
Page 28
GROUND o/c
299.6785
6.2863
3.3728
2.3839
1.8840
1.5811
1.3772
1.2303
1.1190
0.9612
0.8540
0.7760
0.7165
0.6693
GRAPH_DATA
Page 29
0.6310
0.5991
0.5720
0.5425
0.5286
0.5159
0.5043
0.4935
0.4836
0.4743
0.4657
0.4576
0.4501
0.4430
0.4363
0.4300
0.4241
0.4184
0.4131
0.4080
GRAPH_DATA
Page 30
0.4031
0.3985
0.3941
0.3898
0.3858
0.3819
0.3782
0.3638
0.3515
0.3408
0.3314
0.3230
0.3155
0.3088
0.3027
0.2971
0.2919
0.2903
0.2887
0.2872
GRAPH_DATA
Page 31
0.2864
0.2857
0.2850
0.2842
0.2835
0.2828
0.2821
0.2814
0.2813
0.2806
0.2799
0.2793
0.2786
0.2783
0.2781
0.2778
0.2776
0.2773
0.2770
0.2768
GRAPH_DATA
Page 32
0.2765
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
GRAPH_DATA
Page 33
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
0.2500
GRAPH_DATA
Page 34
0.2500
0.2500
GRAPH_DATA
Page 35
360.8
10 100 1000 10000 1000000.01
0.10
1.00
10.00
100.00TIME COORDINATION OF OVERCURRENT PROTECTION
( 22kV HIGH SIDE )
FAULT CURRENT(A)
OP
ER
AT
ING
TIM
E (S
)
22kV 3 PHASE FAULT = 6685.02 A
INST. FAULT SETTING = 7362 A
3 PHASE FAULT
- - - - - SLG FAULT
22kV SLG FAULT = 1880.87 A
INST. FAULT SETTING = 7362 A
100 1000 10000 1000000.01
0.10
1.00
10.00
100.00TIME COORDINATION OF OVERCURRENT PROTECTION
( 115kV HIGH SIDE )TRANSFER TO 22kV
FAULT CURRENT THROUGH 22kV SIDE(A)
OP
ER
AT
ING
TIM
E (
S)
115kV HIGH SIDE O/C PHASE
22kV 3 PHASE FAULT = 34944.4 A
INST. FAULT SETTING = BLOCK
3 PHASE FAULT
- - - - - SLG FAULT