INSPECTION REPORT
For the Property at:
207 EAST LOWELL STREETLE ROY, MN 55951
Prepared for: SUSAN MEYERInspection Date: Thursday, August 13, 2020
Prepared by: David Shipler
Home Run Home Inspections LLC5175 Ridgeway Road Northwest
Rochester, MN 55901507-438-9825507-440-8040
homerunaustin.com [email protected]
WE COVER ALL THE BASES!!
INVOICE
August 15, 2020
Client: Susan Meyer
Report No. 2872For inspection at:207 East Lowell StreetLe Roy, MN55951on: Thursday, August 13, 2020
Home Inspection Only - Rochester And Surrounding Areas $350.00
Total $350.00
PAID IN FULL - THANK YOU!
Home Run Home Inspections LLC5175 Ridgeway Road Northwest
Rochester, MN 55901507-438-9825507-440-8040
homerunaustin.com [email protected]
ROOFING
Description
The home is considered to face: West
Sloped roofing material: Composition shingles
Sloped roof flashing material: Metal
Probability of leakage: Medium
Approximate age: 16 years
Typical life expectancy: 20-25 years
Roof Shape: Gable
Limitations
Inspection performed: By walking on roof
Age determined by: Reported by seller
Not included as part of a building inspection: Not readiliy accessible interiors of vent systems, flues, and chimneys
Recommendations
SLOPED ROOFING \ Composition shingles1. Condition: Granule lossImplication(s): Shortened life expectancy of materialLocation: Various Exterior RoofTask: MonitorTime: Ongoing
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 1 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ROOFING
1. Granule loss 2. Granule loss
2. Condition: PatchedImplication(s): Shortened life expectancy of materialLocation: North garage porch
3. Patched
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 2 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
EXTERIOR
Description
Gutter & downspout material: Aluminum
Gutter & downspout type: Eave mounted
Gutter & downspout discharge: Above grade
Lot slope: Away from building
Soffit (underside of eaves) and fascia (front edge of eaves): Aluminum
Wall surfaces and trim: Metal siding
Retaining wall: Masonry
Driveway:BlacktopConcrete
Approach
Exterior steps: Wood
Patio: Concrete
Garage: Attached Detached
Recommendations
ROOF DRAINAGE \ Gutters and Downspouts3. Condition: MissingLocation: East Exterior WallTask: ProvideTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 3 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
EXTERIOR
4. Missing
ROOF DRAINAGE \ Downspouts4. Condition: MissingImplication(s): Chance of water damage to contents, finishes and/or structureLocation: East Exterior Wall GarageTask: ProvideTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 4 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
EXTERIOR
5. Missing
WALLS \ Metal siding5. Condition: Discolored
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 5 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
EXTERIOR
The paint is starting to peel on the steel siding in a few placesImplication(s): Shortened life expectancy of material | Material deteriorationLocation: Various Exterior WallTask: ImproveTime: When necessary
6. Discolored
PORCHES, DECKS, STAIRS, PATIOS AND BALCONIES \ Floors6. Condition: Paint or stain neededImplication(s): Shortened life expectancy of materialLocation: South ExteriorTask: ImproveTime: Regular maintenance
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 6 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
EXTERIOR
7. Paint or stain needed
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 7 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
STRUCTURE
Description
Configuration:BasementCrawlspace
8. Crawlspace 9. Crawlspace
Foundation material: Poured concrete Masonry block
Floor construction: Joists Subfloor - plank Subfloor - OSB (Oriented Strand Board)
Exterior wall construction: Wood frame
Roof and ceiling framing: Trusses Oriented Strand Board (OSB) sheathing
Recommendations
WALLS \ Solid masonry walls7. Condition: Masonry deterioratedImplication(s): Weakened structure | Chance of structural movementLocation: North Exterior WallTask: ImproveTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 8 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
STRUCTURE
10. Masonry deteriorated
11. Masonry deteriorated
8. Condition: EfflorescenceImplication(s): Weakened structureLocation: Various BasementTask: ImproveTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 9 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
STRUCTURE
12. Efflorescence 13. Efflorescence
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 10 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ELECTRICAL
Description
Service entrance cable and location:Underground - cable material not visible
14. Underground - cable material not visible
Service size:200 Amps (240 Volts)
4/0 Aluminum
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 11 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ELECTRICAL
15. 200 Amps (240 Volts) 16. 200 Amps (240 Volts)
Main disconnect/service box rating:200 Amps
17. 200 Amps
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 12 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ELECTRICAL
Main disconnect/service box type and location:Breakers - utility room
18. Breakers - utility room 19. Breakers - utility room
Breakers - garage
System grounding material and type: Copper - water pipe
Electrical panel manufacturers: Eaton/Cutler-Hammer
Auxiliary panel (subpanel) type and location:Breakers - garage
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 13 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ELECTRICAL
20. Breakers - garage 21. Breakers - garage
Number of circuits installed: 24
Distribution wire (conductor) material and type: Copper - non-metallic sheathed
Type and number of outlets (receptacles): Grounded - typical
Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI):GFCI - bathroomGFCI - garageGFCI - kitchenGFCI - panel
Detached garage panelThe outlets did not trip to the breaker.
GFCI - panelGarage
Smoke alarms (detectors): Present
Carbon monoxide (CO) alarms (detectors): None noted
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 14 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ELECTRICAL
Limitations
System ground: Continuity not verified
Circuit labels: The accuracy of the circuit index (labels) was not verified.
Not included as part of a building inspection: Low voltage wiring systems and components Determination of theage of smoke and carbon monoxide alarms
Recommendations
SERVICE BOX, GROUNDING AND PANEL \ Distribution fuses/breakers9. Condition: Double tapsImplication(s): Fire hazardLocation: North Basement Utility RoomTask: Further evaluation CorrectTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 15 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ELECTRICAL
22. Double taps 23. Double taps
DISTRIBUTION SYSTEM \ Wiring - installation10. Condition: Extension cord used as permanent wiringImplication(s): Electric shock | Fire hazardLocation: Middle GarageTask: RemoveTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 16 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ELECTRICAL
24. Extension cord used as permanent wiring 25. Extension cord used as permanent wiring
11. Condition: Extension cord used as permanent wiringImplication(s): Electric shock | Fire hazardLocation: Northeast ExteriorTask: RemoveTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 17 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
ELECTRICAL
26. Extension cord used as permanent wiring
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 18 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
HEATING
Description
System type: Furnace
Fuel/energy source: Gas
Furnace manufacturer: Airquest
27. 28.
Heat distribution: Ducts and registers
Approximate capacity: 125,000 BTU/hr
Efficiency: Conventional
Exhaust venting method: Induced draft
Combustion air source: Interior of building
Approximate age: 28 years
Typical life expectancy: Furnace (conventional or mid-efficiency) 18 to 25 years
Main fuel shut off at:BasementUtility room
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 19 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
HEATING
29. Utility room
Main fuel shut off at: Lap Tank
30.
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 20 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
HEATING
Failure probability: Medium
Air filter:Disposable
31. Disposable
20" x 25"4" thick
Auxiliary heat:Gas space heater
Detached garageWas not tested as the thermostat goes to 75 and the temperature was 83°
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 21 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
HEATING
32. Gas space heater 33. Gas space heater
Gas space heaterAttached garageOperatedGas was off and it was unplugged
34. Gas space heater
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 22 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
HEATING
Fireplace/stove:Gas fireplace
35. Gas fireplace
Chimney/vent: PVC plastic Sidewall venting
Mechanical ventilation system for building:Heat recovery ventilator (HRV)
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 23 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
HEATING
36. Heat recovery ventilator (HRV) 37. Heat recovery ventilator (HRV)
Location of the thermostat for the heating system: Dining Room
Limitations
Heat loss calculations: Not done as part of a building inspection
Heat exchanger: Only a small portion visible
Not included as part of a building inspection: Interiors of vent systems, flues, and chimneys Heat exchangers
Recommendations
FURNACE \ General notes12. Condition: Service FurnaceLocation: Southeast Basement Utility RoomTask: Service annuallyTime: Regular maintenance
HEAT RECOVERY VENTILATOR \ Filters13. Condition: DirtyImplication(s): Equipment ineffectiveLocation: Northeast Basement Utility RoomTask: CleanTime: Regular maintenance
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 24 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
HEATING
38. Dirty
HEAT RECOVERY VENTILATOR \ Ducts and grilles14. Condition: Obstructed
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 25 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
HEATING
Implication(s): Equipment ineffectiveLocation: North Exterior WallTask: CleanTime: Regular maintenance
39. Obstructed
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 26 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
COOLING & HEAT PUMP
Description
Air conditioning type: Air cooled
Manufacturer: Tempstar
40. 41.
Compressor type: Electric
Compressor approximate age: 9 years
Typical life expectancy: 12 to15 years
Failure probability: Medium
Refrigerant type: R-410A
Location of the thermostat for the cooling system: Dining Room
Limitations
Heat gain calculations: Not done as part of a building inspection
Not part of a home inspection: Home inspectors cannot typically access or inspect the indoor coil Home inspectorsdo not verify that the size of the indoor coil matches the outdoor coil
Not included as part of a building inspection: Cooling system adequacy Cooling system distribution balance
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 27 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
COOLING & HEAT PUMP
Recommendations
AIR CONDITIONING \ General notes15. Condition: Service air conditionerImplication(s): Reduced system life expectancy | Increased cooling costs | Reduced comfortLocation: North ExteriorTask: Service annuallyTime: Regular maintenance
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 28 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
INSULATION AND VENTILATION
Description
Attic/roof insulation material:Glass fiber
Garage
42. Glass fiber
Cellulose
43. Cellulose
44. Cellulose
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 29 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
INSULATION AND VENTILATION
45. Cellulose
Attic/roof insulation amount/value:R-20
GarageR-40
House
Attic/roof air/vapor barrier:Kraft paper
GarageNot visible
Attic/roof ventilation: Roof vent Gable vent
Limitations
Attic inspection performed: From access hatch
Air/vapor barrier system: Continuity not verified
Mechanical ventilation effectiveness: Not verified
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 30 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
PLUMBING
Description
Water supply source (based on observed evidence):PublicPrivate
46. Private
Service piping into building: Plastic Galvanized steel
Supply piping in building: Copper PEX (cross-linked Polyethylene)
Main water shut off valve at the:BasementUtility room
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 31 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
PLUMBING
47. Utility room
Water flow and pressure: Typical for neighborhood
Water heater type: Conventional
Water heater location: Basement Utility room
Water heater fuel/energy source: Electric
Water heater manufacturer: Richmond
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 32 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
PLUMBING
48. 49.
Water heater tank capacity: 50 gallons
Water heater approximate age: 14 years
Water heater typical life expectancy: 10 to 20 years
Water heater failure probability: Medium
Waste disposal system:PrivateSeptic system
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 33 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
PLUMBING
50. Septic system
Waste and vent piping in building: Plastic PVC plastic
Floor drain location: Center of basement
Water treatment system:Water softener
The reservoir is low on salt
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 34 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
PLUMBING
51. Water softener
Gas piping: Steel CSST (Corrugated Stainless Steel Tubing)
Exterior hose bibb (outdoor faucet): Present
Limitations
Items excluded from a building inspection: Well Water quality Septic system Isolating/relief valves & main shut-off valve Concealed plumbing Tub/sink overflows Water treatment equipment Water heater relief valvesare not tested The performance of floor drains or clothes washing machine drains Water features
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 35 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
INTERIOR
Description
Major floor finishes: Carpet Hardwood Tile
Major ceiling finishes: Suspended tile
Major wall and ceiling finishes: Plaster/drywall
Windows: Awning Vinyl
Glazing: Triple
Exterior doors - type/material: Hinged Metal Garage door - metal
Doors: Inspected
Oven type: Conventional
Range fuel: Electricity
Appliances: Refrigerator Dishwasher Waste disposal Door bell Microwave/Exhaust Fan Combo Range
Laundry facilities: Laundry tub Hot/cold water supply Vented to outside 120-Volt outlet 240-Volt outlet Wastestandpipe
Kitchen ventilation:Range hood - recirculating type
Built in the microwave
Bathroom ventilation: Exhaust fan
Laundry room ventilation: Clothes dryer vented to exterior
Counters and cabinets: Inspected
Stairs and railings: Inspected
Limitations
Not included as part of a building inspection: Cosmetic issues Perimeter drainage tile around foundation, if anyDecorative items Aesthetics or quality of finishes Vermin, including wood destroying organisms. Undergroundcomponents (e.g., oil tanks, septic fields, underground drainage systems) Paint, wallpaper,and other finishes Floorcoverings Window treatments
Appliances: Self-cleaning features on ovens not tested Effectiveness of dishwasher drying cycle not testedAppliances are not moved during an inspection
Recommendations
WALLS \ General notes16. Condition: StainsImplication(s): Chance of water damage to contents, finishes and/or structureLocation: Various BasementTask: Repair ImproveTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 36 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
INTERIOR
52. Stains
DOORS \ Hardware17. Condition: BrokenImplication(s): System inoperative or difficult to operateLocation: North First Floor Dining RoomTask: RepairTime: Immediate
53. Broken
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 37 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
INTERIOR
GARAGE \ Vehicle door operators18. Condition: Sensors poorly locatedImplication(s): Physical injuryLocation: Middle Middle GarageTask: CorrectTime: Immediate
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 38 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
INTERIOR
54. Sensors poorly located
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 39 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
SITE DATA
Description
Weather: Partly sunny Ground was dry Light winds
Approximate temperature: 84°
Attendees: Seller
Access to home provided by: Seller
Occupancy: The home was occupied at the time of the inspection. The home was unfurnished during the inspection.
Utilities: All utilities were on during the inspection.
Approximate inspection Start time: The inspection started at 1:00 p.m.
Approximate inspection End time: The inspection ended at 4:00 p.m.
Building type: Detached home
Number of dwelling units: Single-family
Number of stories: 2
Number of kitchens: 1
Below grade area: Basement Crawlspace
Garage, carport and outbuildings: Attached two-car garage Detached three-car garage
Area: City
Street type: Residential
Street surface: Paved
END OF REPORT
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 40 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
REFERENCE LIBRARY
The links below connect you to a series of documents that will help you understand your home and how it works. Theseare in addition to links attached to specific items in the report.
Click on any link to read about that system.
01. ROOFING, FLASHINGS AND CHIMNEYS
02. EXTERIOR
03. STRUCTURE
04. ELECTRICAL
05. HEATING
06. COOLING/HEAT PUMPS
07. INSULATION
08. PLUMBING
09. INTERIOR
10. APPLIANCES
11. LIFE CYCLES AND COSTS
12. SUPPLEMENTARY
Asbestos
Radon
Urea Formaldehyde Foam Insulation (UFFI)
Lead
Carbon Monoxide
Mold
Household Pests
Termites and Carpenter Ants
13. HOME SET-UP AND MAINTENANCE
14. MORE ABOUT HOME INSPECTIONS
207 East Lowell Street, Le Roy, MN August 13, 2020 homerunaustin.com homerunrochester.com
Providing great home inspections for every client every time
Report No. 2872
Page 41 of 41
ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR SITE DATA
REFERENCE
Aug 22,2020
RE: Inspection Report for Property at 207 East Lowell Street Leroy, MN 55951
The following are the list of items that have been corrected since the inspection on 8-13-2020.
The corrections were performed by: Roger Meyer Master Electrician MN license #AM006887
Recommendation #9: Condition: Double Taps North Basement Utility room Resolution: The double wired taps of 2 wires attached to a single breaker were changed to a single wired tap using wire nuts which meets Minnesota code. Recommendation #14: Condition: Heat recovery Ventilator/Ducts-Grilles were obstructed. Resolution: The ducts were thoroughly cleaned by using an air compressor to blow off filter and vacuuming.
Recommendation #53: Condition: Broken door handle on patio door in dining room.
Resolution: Door handle was replaced and functioning properly.