2018 International Energy Conservation Code Updates
02.28.2018
![Page 2: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/2.jpg)
We assist buildings and communities in achieving energy efficiency, saving money, and becoming more sustainable.
We are an applied research program at University of Illinois, working in collaboration with 360 Energy Group.
Our goal: Reduce the energy footprint of Illinois.
2
Who we are
![Page 3: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/3.jpg)
SEDAC is the Illinois Energy Conservation Code Training Provider
This training program is sponsored by Illinois EPA
![Page 4: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/4.jpg)
Energy Code Assistance
• Technical support • 800.214.7954• [email protected]
• Online resources at sedac.org/energy-code
• Workshops• Webinars• Online on-demand training
modules
4
![Page 5: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/5.jpg)
www.sedac.org/energy-code
5
![Page 6: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/6.jpg)
https://codes.iccsafe.org/public/document/iecc2018
6
Access to 2018 IECC
![Page 7: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/7.jpg)
8
History of Model Codes ImprovementResidential
Commercial
![Page 8: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/8.jpg)
• Commercial• No significant energy efficiency improvement (initial estimate of 2-5%
improvement)
• Mechanical Section (C 403): Reorganized, so all provisions for a type of equipment or system are in one place
• More detailed requirements for lighting controls: Change from “be capable of” to “be configured”)
• Appendix CA Solar-Ready Zone
• Definition of “Approved”: Change from “Approval by the code official as a result of investigation and tests conducted by him or her, or by nationally recognized organizations” to “Acceptable to the code official”
• ASHRAE 90.1-2016 • New climate zone map (6 counties in Illinois – Calhoun, Clark, Coles,
Cumberland, Greene, Jersey: from 4A to 5A)• New performance-based compliance path (Appendix G)
9
2018 IECC Commercial Changes Highlights
![Page 9: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/9.jpg)
• Residential• No significant energy efficiency improvement (initial estimate of 0%
improvement)
• Definition of “Approved”
• Inspection: Change from construction or work shall remain “accessible and exposed” to “visible and able to accessed” for inspection”
10
2018 IECC Residential Changes Highlights
![Page 10: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/10.jpg)
• Commercial• Envelope• HVAC• Service Water Heating• Lighting• Performance• Maintenance & Commissioning
• Residential• Envelope• HVAC• Lighting• Performance
• IL Amendment Process
11
2018 IECC Updates
![Page 11: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/11.jpg)
Commercial
![Page 12: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/12.jpg)
Heated Slab Insulation
R-5 continuous insulation required under heated slabs for both commercial and residential
13
Envelope [C402.1.3]
Image courtesy of DOE
![Page 13: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/13.jpg)
Isolating Combustion Appliances
• Specifies minimum construction methods for rooms containing open combustion appliances (Water heaters, furnaces, etc.)
• This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms.
• Alternative is to install sealed combustion (higher efficiency) appliances
14
HVAC [C402.5.3]
Images courtesy of DOE
![Page 14: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/14.jpg)
Expanded VFDs
•Pumps and fans with 2hp and larger now required•Increased allowance for DDC controlled systems
15
HVAC [C403.4.4]
![Page 15: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/15.jpg)
Improved HVAC Turndown
Reduced minimum airflow from 30% to 20% of maximum
16
HVAC [C403.6.1]
Heating Cooling
Cooling & Reheat
Heating Cooling
Cooling & Reheat
2015 IECC
2018 IECC
![Page 16: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/16.jpg)
Guestroom Automatic Controls
Automatic HVAC control now required for buildings with over 50 guestrooms
17
HVAC [C403.7.6]
Image courtesy of Wattstopper
![Page 17: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/17.jpg)
Water Storage Tank Heat Traps
Heat Traps now required for hot water storage tanks, not just water heaters
18
SWH [C404.3]
![Page 18: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/18.jpg)
Luminaire Level Lighting Controls
•Allows for luminaire lighting controls to take the place of centralized controls
•Must include occupancy sensor and ambient light sensor
19
Lighting [C405.2]
Image courtesy of Cree
![Page 19: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/19.jpg)
Office Area Occupancy Sensors
Open office areas now must have occupancy sensors
20
Lighting [C405.2.1.3]
![Page 20: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/20.jpg)
Daylight Responsive Exception
•Does not require daylight-responsive controls If 40% lower than wattage allowance
•Office Allowance – 0.79 w/sf•Threshold for Daylight-responsive controls – 0.47 w/sf
21
Lighting [C405.2.3]
![Page 21: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/21.jpg)
Increased Exterior Lighting Controls
•Daylight shutoff•Decorative lighting shut off during non-business hours
•Lighting setback – 30% watts minimum•Time switch control functionality
22
Lighting [C405.2.6]
![Page 22: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/22.jpg)
Track Lighting Demand Reduction
Reduces demand from 30W/ft to 8W/ft
23
Lighting [C405.3.1]
![Page 23: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/23.jpg)
Reduced Lighting Power Allowances
•Office 0.82 to 0.79 – 4% reduction•Library 1.19 to 0.78 – 34% reduction
24
Lighting [C405.3.2]
![Page 24: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/24.jpg)
Increased Efficiencies
Dry-type transformers & Motors
25
HVAC [C405.6‐7]
Images courtesy of Schneider Electric Image courtesy of Baldor
![Page 25: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/25.jpg)
Renewable Energy Credit Limits
•Limits on-site renewable credits to 5%•Allows Code Official to request documentation on renewables used for credit
26
Performance [C407.3]
Image courtesy of: solartrader.ca
![Page 26: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/26.jpg)
Operations and Maintenance
Building O&M must be provided to building owner
27
Maintenance & Commissioning [C408.1.1]
Image courtesy of Berkeley
![Page 27: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/27.jpg)
Residential
![Page 28: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/28.jpg)
Window U-Factors
Modest improvement in window U-factors
29
Envelope [R402.1.2]
Climate Zone
2015 U-Factor
2018 U-Factor
4 U-0.35 U-0.325 U-0.32 U-0.30
![Page 29: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/29.jpg)
Ducts Buried in Ceiling Insulation
Provides allowance for duct insulation in buried duct work (for simulated energy performance analysis)
30
Envelope [R403.3.6]
![Page 30: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/30.jpg)
Ducts in Conditioned Space
Provides criteria to determine if ducts are inside conditioned space or not.
•Completely inside air barrier OR•Buried in the ceiling insulation AND
•Air handler within air & thermal barrier•Duct leakage <1.5 cfm per 100 sf•Full depth insulation above duct
31
Envelope [R403.3.7]
![Page 31: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/31.jpg)
HRV / ERV Fan Efficiency
•Minimum fan efficiency of 1.2 cfm/w is added for Heat Recovery Ventilator and Energy Recovery Ventilator for whole house mechanical ventilation system.
32
HVAC [R403.6.1]
Image courtesy of Calcs Plus
![Page 32: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/32.jpg)
High Efficiency Lighting
• Increases high efficiency lighting to 90% from 75%•Eliminates the low-voltage exception
33
Lighting [R404.1]
![Page 33: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/33.jpg)
Multifamily Unit Modeling
Batch sampling is allowed for stacked multifamily units
34
Performance[R405.4.2]
![Page 34: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/34.jpg)
Energy Rating Index
• Increase of Max. ERI score
35
ERI [R406]
Climate Zone
2015 ERI Score
2018 ERI Score
4 54 625 55 61
Image courtesy of Energy IQ
![Page 35: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/35.jpg)
IL Code Amendment Process: What changes would
you recommend?
![Page 36: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/36.jpg)
Fill out code change proposal form•Contact info•Sections impacted•Proposed revisions•Reason•Cost impact
https://www2.illinois.gov/cdb/business/codes/Pages/2018-IECC-Announcement.aspx
37
IL Code Amendments
![Page 37: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/37.jpg)
![Page 38: 2018 International Energy Conservation Code Updates · •This was amended out in 2015 IL Energy Conservation Code due to increased cost of building these isolated rooms. •Alternative](https://reader034.fdocuments.us/reader034/viewer/2022042107/5e86b0f8c4544f17682b3a3d/html5/thumbnails/38.jpg)
•Don’t submit multiple amendments to a single code section
• If multiple code sections affected, multiple amendments need to be submitted
•Text should be presented as proposed new text, not deleted text
•Cost impact: based on construction cost impact•Supporting documentation needed
Amendment Proposals
39