2012 Lik KaiPacific Sense
March 2012
![Page 2: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/2.jpg)
PACIFIC SENSE
• Company Intro
![Page 3: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/3.jpg)
PACIFIC SENSE
3
![Page 4: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/4.jpg)
Comparison of FM200 system against room volume
Room Volume
Cylinder c/w its associated accessories (such as valve, solenoid, pressure sw. & etc…) HKD
Detection equipment (such as panel, detector, safety barrier & etc…) HKD
Installation HKD
100 cu m 35,000 12,000 23,000
150 cu m 43,000 12,000 23,000
200 cu m 51,000 12,000 28,000
250 cu m 59,000 12,000 28,000
300 cu m 67,000 16,000 32,000
350 cu m 74,000 16,000 35,000
400 cu m 81,000 16,000 38,000
4
![Page 5: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/5.jpg)
Suppression Solutions
• The latest technology in suppression system suitable for Hospital BuildingSelection criteriaTypes of productDesign and installationMaintenanceQuality
![Page 6: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/6.jpg)
Selection criteria
• Physical dimensions
• Occupant
• Weight / space limitations
• Fire fighting performance
• Environmental
• Life cycle cost
![Page 7: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/7.jpg)
Types of product
• Fixed gaseous fire suppression systemChemical gasesInert gasesCarbon Dioxide
• Fixed water systemWater mistSprinklerWater spay system
![Page 8: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/8.jpg)
Fixed gaseous fire suppression systems
• Chemical gases
Designation Chemical formula Chemical name Trade Name
HFC 23 CHF3Trifloromethane FE-13
HFC 125 CF3CHF2Pentafloroethane FE-25
HFC 227ea CF3CHFCF3Heptafluoropropane FM200 ,
FE-227
FK-5-1-12mmy2 CF3CF2C(0)CF(CF3)2Dodecafluro-2-methylpentan-2-one
Novec 1230
![Page 9: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/9.jpg)
Fixed gaseous fire suppression systems
• Inert gases
Designation Gas blend Trade name
IG-01 100% argon Various
IG-100 100% nitrogen Various
IG-55 50% nitrogen , 50% argon Argonite
IG-541 50% nitrogen , 42 % argon , 8% carbon dioxide
Inergen
![Page 10: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/10.jpg)
Fluid Safety and Use Concentration Comparison
Properties NOVEC 1230
Halon 1301
HFC-125 HFC-227ea
Inert Gas Carbon dioxide
Temperature to change from Liquid to gas form
49.2 -57.8 -48.5 -16.4 -196 Sublimes at low temps
Use Concentration
4-6% 5% 8.7-12.1%
7.5-8.7%
38-40% 30-75%
NOAEL 10% 5% 7.5% 9% 43% NA
Safety Margin
67-150%
Nil Nil 3-20% 7-13% Lethal at Use
Conc.
![Page 11: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/11.jpg)
Fire Protection Fluid Environmental Properties Comparison
Properties NOVEC 1230 (FK-
5-1-12)
Halon 1301
HFC-125 IG-55 (Argonite
)
IG-541 (Inergen)
HFC-227ea
Ozone Deletion Potential (ODP)
0.0 12 0.0 0.0 0.0 0.0
Globe Warming Potential - IPCC
1 6900 3400 0.0 0.0 3500
Atmospheric Lifetime (years)
0.014 65 29 0.0 0.0 33
SNAP Yes N/A Yes Yes Yes Yes
![Page 12: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/12.jpg)
Fixed gaseous fire suppression systems
• Carbon dioxideOver eighty yearsExtinguishes the fire primarily by reducer the oxygen
concentration and provides localized coolingLocal application and total flooding application
![Page 13: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/13.jpg)
Fixed water system
• Water mist90% droplets less than 1 mm in diameter To cool the fire source by removing the heat and
suppressing the fireDisplaces oxygen in the atmosphere
![Page 14: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/14.jpg)
Design and installation
• Complex and various of size
• Type of fuel
• High value asset
• Temperature
• Downtown
• Integration
• Safety
![Page 15: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/15.jpg)
Maintenance
• Regular maintenance by competent , third party certified person
• Manufacturer instruction
• Charges to protection area
• Enclosure integrity
• Nozzles position
![Page 16: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro.](https://reader036.fdocuments.us/reader036/viewer/2022062519/5697bfda1a28abf838cb014f/html5/thumbnails/16.jpg)
Quality
• Design : Factory trained and certified engineer
• Component : US DOT , EU TPEP and PED
• System : UL , FM Global , LPCB and Vds
• Installation : NFPA 2001 , ISO 14520 and the manufacturer instruction