2009 Eaton Corporation. All rights reserved.
1
Wiring of Communication ModulesmMINT, PMINT, MCAM and PCAM
22009 Eaton Corporation. All rights reserved.
202.Jul.2009
mMINT Communication Wiring
ATx/Rx +
Tx/Rx -B
Modbus RTU NetworkMaster
GND*
RS-485Modbus
SHD*) Connect shield to ground at master device end only. Interconnect shielding where devices are daisy-chained.
SW1 should be moved to the ON position only when it is the last device in a chain of devices or if it is a single device.
Baudrate SW2-2 SW2-3
1200 On On
9600 Off On
19200 On Off
SW2-1
Addr. 247or 248** Off
Normal On
(Fo
r d
iag
no
stic
s)
**) for diagnostic mode, to configure the mMINT
SW3 should be moved to the ON position only when it is the last device in a chain of devices or if it is a single device.
INCOM
IZM26
Terminal B1Terminal B2
Terminal A14
Terminal A15
+, P
Feed control voltage to A14 and A15 for breaker remote control and for Trip Unit operation without current flow.
0V, N
0V
, N
+,
P
Integrated-Status (on/off) sensors-Shunt trip and spring release control only available with Digitrip models 1150x
32009 Eaton Corporation. All rights reserved.
302.Jul.2009
PMINT Communication Wiring
PROFIBUS DPMaster
RS-485PROFIBUS DP
SW2-1
Remote disable Open
Remote enable Close
123456
INC
OM
Connect the INCOM Shield wire to ground at master device (PMINT) end only.SHIELD
IZM-CS in position C
CBSW1
CBSW2
GND
IZM-CS in position D
NO NO CC
0V
, N
+,
PPosition of breaker in drawer
IZM26
Terminal B1Terminal B2
Terminal A14
Terminal A15
+, P
Feed control voltage to A14 and A15 for breaker remote control and for Trip Unit operation without current flow.
0V, N
Integrated-Status (on/off) sensors-Shunt trip and spring release control only available with Digitrip models 1150x
42009 Eaton Corporation. All rights reserved.
402.Jul.2009
MCAM Communication Wiring*
5
4
3
2
1
4
3
2
1
Close
Open
COM - R
24 Vdc-
24 Vdc+
Shield
COM - C
A (Tx/Rx-)
B (Tx/Rx+)
1 17 19 21 23 25 27 35
2 18 20 22 24 26 28 36
ST
1
SG
F2
+24V
CM
M1
CM
M3
SR
1
ST
2
SG
F1
AG
ND
CM
M2
CM
M4
SR
2
53
54
0V
24 Vdc+
MCAM
(Top View of a mounted MCAM on IZM)
ModbusControl
Source Ground
(Front View of MCAM)
Enable
Disable
ModbusCommunicationsAdapter ModuleCat. MCAM
Tx/Rx+
Tx/Rx-
Modbus RTU Master
GND**
RS-485Modbus
IntegratedStatus (on/off) sensors in breaker
wiring for remote control (Shunt trip and spring release)
inverting
non-inverting
52009 Eaton Corporation. All rights reserved.
502.Jul.2009
PCAM Communication Wiring*
5
4
3
2
1
Close
Open
COM - R
24 Vdc-
24 Vdc+
1 17 19 21 23 25 27 35
2 18 20 22 24 26 28 36
ST
1
SG
F2
+24V
CM
M1
CM
M3
SR
1
ST
2
SG
F1
AG
ND
CM
M2
CM
M4
SR
2
53
54
0V
24 Vdc+
PCAM
(Top View of a mounted PCAM on IZM )
PROFIBUSControl
Source Ground
(Front View of PCAM)
Enable
Disable
Series NRXPROFIBUSCommunicationsAdapter ModuleCat. PCAM
PROFIBUS DPMaster
RS-485PROFIBUS DP
IntegratedStatus (on/off) sensors in breaker
wiring for remote control (Shunt trip and spring release)
62009 Eaton Corporation. All rights reserved.
602.Jul.2009
ECAM Communication Wiring*
5
4
3
2
1
Close
Open
COM - R
24 Vdc-
24 Vdc+
1 17 19 21 23 25 27 35
2 18 20 22 24 26 28 36
ST
1
SG
F2
+24V
CM
M1
CM
M3
SR
1
ST
2
SG
F1
AG
ND
CM
M2
CM
M4
SR
2
53
54
0V
24 Vdc+
ECAM
(Top View of a mounted ECAM on IZMX)
EthernetControl
Source Ground
(Front View of ECAM)
Enable
Disable
Series NRXEthernetCommunicationsAdapter ModuleCat. ECAM
IntegratedStatus (on/off) sensors in breaker
wiring for remote control (Shunt trip and spring release)
Ethernet Network,Switch, or PCConnection
72009 Eaton Corporation. All rights reserved.
702.Jul.2009
Remote Control Possibilities through Network
Circuit Breaker IZM16 Circuit Breaker IZM26
MCAM PCAM mMINT PMINT
Digitrip 520
Digitrip 1150
Digitrip 520
Digitrip 1150
Digitrip 520
Digitrip 1150
Digitrip 520
Digitrip 1150
remote controlling
yes yes yes yes NA Yes NA Yes
82009 Eaton Corporation. All rights reserved.
802.Jul.2009
Modbus RTU Network RS-485
XV-102
RS485
Pin 3 A
Pin 7 B
Pin 3
B
TB2-1 B
Pin 2
ATB2-2 A
XC200XIOC-SER
Tx/Rx-
Tx/Rx+
Modbus RTU
USB-RS 485 Converter
+ -
B A
92009 Eaton Corporation. All rights reserved.
902.Jul.2009