Standar PDE STP Chair PM PM Email NEC Reference
429
Jeff
DesJarlais
Diana
Pappas
Jordan Alan McGrath [email protected]
430.102(A), Exception 3. An exception permits
valve actuator motors to be provided with a
warning marking and provision for locking if the
valve will not be installed in sight of field
disconnect means.
429
Jeff
DesJarlais
Diana
Pappas
Jordan Alan McGrath [email protected] 430.2. Defines Valve Actuator Motors.
486
Jake
Killinger
Bradley
Schmidt
Marcia
Kawate [email protected]
250.8. Establishes basic requirements for
terminal connectors and means to connect
equipment for grounding and bonding.
489
Jeff
Hidaka
Bradley
Schmidt Patricia Sena [email protected]
610.31. Section 610.31 (Runway Conductor
Disconnecting Means) was revised to require
the The provision for locking or adding a lock
to the disconnecting means shall be installedon or at the switch or circuit breaker used as
the disconnecting means and shall remain in
place with or without the lock installed. Portable
means for adding a lock to the switch or circuit
breaker shall not be permitted as the means
required to be installed at and remain with the
equipment.
mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected] -
7/31/2019 2008 NEC Changes - Copy
2/22
-
7/31/2019 2008 NEC Changes - Copy
3/22
-
7/31/2019 2008 NEC Changes - Copy
4/22
Standar PDE STP Chair PM PM Email NEC Reference
639
Lou
Chavez
Sarah
Brooks Megan Cahill [email protected]
725,130(B) exception 3. Listing of intrusion
protection systems with bare, class 2
conductors
845
Jeff
Hidaka
Bradley
Schmidt Valara Davis [email protected]
200.2(B). Requires that a neutral (grounded)
system conductor be connected through
terminals and not to use the enclosure as part
of the current carrying path.
891
Robert
Osborne
Bradley
Schmidt Tim Corder [email protected]
110.20. Movement of enclosure environmental
types from Article 430 to Article 110. Inclusion
of switchboards, panelboards, industrial control
panels, motor control centers and meter
sockets.
At the January 2006 ROP Meetings, UL staff
and NEMA staff verified that Type 1 ratings had
been required in practice, although the wording
in some of the affected standards is not precise
in stating this.
891
Robert
Osborne
Bradley
Schmidt Tim Corder [email protected]
200.2(B). Requires that a neutral (grounded)
system conductor be connected throughterminals and not to use the enclosure as part
of the current carrying path.
891
Robert
Osborne
Bradley
Schmidt Tim Corder [email protected]
519 (new section). New Article 519, "Control
Systems for Permanent Amusement
Attractions", was accepted by Panel 15 which
opens the door for new categories of industrial
control devices such as control panels for
these systems.
891
Robert
Osborne
Bradley
Schmidt Tim Corder [email protected]. Expanded requirements for capacity and
Ratings of optional standby systems.
mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected] -
7/31/2019 2008 NEC Changes - Copy
5/22
Standar PDE STP Chair PM PM Email NEC Reference
1008
Paul
Barnhart
Bradley
Schmidt
Esther
Espinoza [email protected]
700.9(D)(3). Added clause regarding control
conductors between transfer equipment and
the emergency generator.
1008
Paul
Barnhart
Bradley
Schmidt Tim Corder [email protected]. Expanded requirements for capacity and
Ratings of optional standby systems.
1042
Robert
Wozniak Joe Musso Mitch Gold [email protected]
406.11 Requires use of tamper resistant
receptacles
1042
Robert
Wozniak Joe Musso Mitch Gold [email protected]. Requires disconnecting means to be
rated 125% of total of disconnected loads.
1047
Joe
Murnane
Bradley
Schmidt Susan Malohn [email protected]
517.18(B) and 517.19(B)(2). In critical care
areas receptacles shall have an integral light
indicating the receptacle is powered or be part
of a listed headwall assembly that provides
indication of power to each receptacle.
1072
Tom
Cybula
Diana
Pappas
Jordan Camille Alma [email protected]
300.40. The change to the second paragraph
of 300.40 provides a more defined connection
requirement for shielding components to a
grounding conductor, to a grounding busbar, or
to a grounding electrode for shielded
conductors in excess of 600 volts, rather than
just that the shield be grounded.
1072
Tom
Cybula
Diana
Pappas
Jordan Camille Alma [email protected]
310.13. Three additional, larger sizes ofconductors were added to Table 310.13D.
Those sizes are as follows:1001 1250
kcmil1251 1500 kcmil1501 2000 kcmil.
1277
Tom
Cybula
Diana
Pappas
Jordan Camille Alma [email protected]
336.104. Added additional language which
permits Type TC to be provided with nickel or
nickel coated copper conductors.
mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected] -
7/31/2019 2008 NEC Changes - Copy
6/22
Standar PDE STP Chair PM PM Email NEC Reference
1569
Tom
Cybula
Diana
Pappas
Jordan Camille Alma [email protected]
330.104. Added additional language which
permits Type MC to be provided with nickel or
nickel coated copper conductors.
1598 Ed Joseph
Diana
Pappas
Jordan
Heather
Sakellariou [email protected]
410.16(A)(3). Permits LED or fluorescent
luminaires that qualify and are identified to be
installed within the defined storage space of a
clothes closet.
1684
George
Walbrecht
Diana
Pappas
Jordan Paul Lloret [email protected]
300.7(B), FPN. Information on new Table
355.44 for expansion characteristics for
reinforced thermosetting resin conduit (RTRC)
has been added.
An expansion and contraction formula has
been added to this FPN for aluminum conduit
and aluminum electrical metallic tubing.
1703
Tim
Zgonena
Bradley
Schmidt Susan Malohn [email protected]
690.31(B). (B) Single-Conductor Cable. Single-
conductor cable typeUSE-2, and single-
conductor cable listed and labeled
asphotovoltaic (PV) wire shall be permitted in
exposed outdoorlocations in photovoltaicsource circuits for photovoltaicmodule
interconnections within the photovoltaic
array.Exception: Raceways shall be used when
required by 690.31(A).
1703
Tim
Zgonena
Bradley
Schmidt Susan Malohn [email protected]
690.31(F). (F) Flexible, Fine-Stranded Cables.
Flexible, fine strandedcables shall be
terminated only with terminals,lugs, devices, or
connectors that are identified and listed forsuch
use.
1703
Tim
Zgonena
Bradley
Schmidt Susan Malohn [email protected]
690.33. (C) Type. The connectors shall be of
the latching or lockingtype. Connectors that are
readily accessible and that are used in circuits
operating at over 30 volts, nominal, maximum
system voltage for dc circuits, or 30 volts for
accircuits, shall require a tool for opening
mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected] -
7/31/2019 2008 NEC Changes - Copy
7/22
Standar PDE STP Chair PM PM Email NEC Reference
1703
Tim
Zgonena
Bradley
Schmidt Susan Malohn [email protected]
690.33. (E) Interruption of Circuit. Connectors
shall be either (1)or (2): (1) Be rated for
interrupting current without hazard to the
operator.(2) Be a type that requires the use of
a tool to open and marked Do Not Disconnect
Under Load or Not for Current Interrupting.
1703
Tim
Zgonena
Bradley
Schmidt Susan Malohn
690.35. (C) Ground-Fault Protection. All
photovoltaic source and output circuits shall be
provided with a ground-fault protection device
or system that complies with (1) through (3):(1)
Detects a ground fault.(2) Indicates that a
ground fault has occurred(3) Automatically
disconnects all conductors or causes the
inverter or charge controller connected to thefaulted circuit to automatically cease supplying
power to output circuits.(D) The photovoltaic
source conductors shall consist of the
following:(1) Nonmetallic jacketed
multiconductor cables(2) Conductors installed
in raceways, or (3) Conductors listed and
identified as Photovoltaic (PV)Wire installed as
exposed, single conductors. (F) The
photovoltaic power source shall be labeled with
the following warning at each junction box,
combiner box, disconnect disconnect, anddevice where energized, ungrounded circuits
may be exposed during service:WARNING
ELECTRIC SHOCK HAZARD. THE DC
CONDUCTORS OF THIS PHOTOVOLTAIC
SYSTEM ARE UNGROUNDED AND MAY BE
ENERGIZED.(G) The inverters or charge
controllers used in systems with
ungrounded photovoltaic source.
1741
Tim
Zgonena
Bradley
Schmidt Susan Malohn [email protected]
690.31(F). (F) Flexible, Fine-Stranded Cables.
Flexible, fine strandedcables shall be
terminated only with terminals,lugs, devices, or
connectors that are identified and listed forsuch
use.
mailto:[email protected]:[email protected]:[email protected]:[email protected] -
7/31/2019 2008 NEC Changes - Copy
8/22
-
7/31/2019 2008 NEC Changes - Copy
9/22
Standar PDE STP Chair PM PM Email NEC Reference
2021
Robert
Wozniak Joe Musso Mitchell Gold [email protected]. Requires disconnecting means to be
rated 125% of total of disconnected loads.
2024
George
Walbrecht
Diana
Pappas
Jordan Paul Lloret [email protected]
725.154(B) and (C) with changes in the 2005
NEC in 725.179(I), (J), and (K). General-
Purpose-signaling raceways, riser-signalingraceways, and plenum-signaling raceways
have been added in the last and in this Code
cycle.
2200
Tim
Zgonena
Diana
Pappas
Jordan
Elizabeth
Sheppard [email protected]
250.35. Establishes requirements for a
bonding jumper between the generator and the
first disconnecting means.
2200
Tim
Zgonena
Diana
Pappas
Jordan
Elizabeth
Sheppard [email protected] 445.18. Added lockable in the open position
2200
Tim
Zgonena
Diana
Pappas
Jordan
Elizabeth
Sheppard [email protected]
590.6, last sentence. A new last sentence has
been added to 590.6 stating that ground fault
protection for personnel shall apply to power
derived from an electric utility company or from
an on-site-generated power source.
2200
Tim
Zgonena
Diana
Pappas
Jordan
Elizabeth
Sheppard [email protected]
700.12(B)(6). Added reference to the
disconnecting means requirements for outdoor
generator sets.
2200
Tim
Zgonena
Diana
Pappas
Jordan
Elizabeth
Sheppard [email protected]
700.9(D)(3). Added clause regarding control
conductors between transfer equipment and
the emergency generator.
mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected] -
7/31/2019 2008 NEC Changes - Copy
10/22
Standar PDE STP Chair PM PM Email NEC Reference
2200
Tim
Zgonena
Diana
Pappas
Jordan
Elizabeth
Sheppard [email protected]
701.11(B)(5). Added reference to the
disconnecting means requirements for outdoor
generator sets.
2200
Tim
Zgonena
Diana
Pappas
Jordan
Elizabeth
Sheppard [email protected]
702.11. Added reference to the disconnecting
means requirements for outdoor generator
sets.
508A
John
Kovacik
Bradley
Schmidt Megan Cahill [email protected]
200.2(B). Requires that a neutral (grounded)
system conductor be connected through
terminals and not to use the enclosure as part
of the current carrying path.
508A
John
Kovacik
Bradley
Schmidt Megan Cahill [email protected]
250.122(D)(2). Sets the sizing for the
equipment grounding conductor for motor
starter equipment with an instantaneous trip
circuit breaker or motor circuit protector.
508A
John
Kovacik
Bradley
Schmidt Megan Cahill [email protected]
519 (new section). New Article 519, "Control
Systems for Permanent Amusement
Attractions", was accepted by Panel 15 which
opens the door for new categories of industrial
control devices such as control panels for
these systems.
514A
George
Walbrecht
Bradley
Schmidt Susan Malohn [email protected]
250.146(A). Sets requirements for when wiring
device yoke is grounded by connection to anexposed work cover and a bonding jumper is
not required. Two fastners that provide good
security and the flat metal to metal cover
corner connection to the box.
mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected] -
7/31/2019 2008 NEC Changes - Copy
11/22
Standar PDE STP Chair PM PM Email NEC Reference
514A
George
Walbrecht
Bradley
Schmidt Susan Malohn [email protected]
250.8(A)(6) Requires that thread forming
machine screw-type fasteners engage not less
than two threads
514D
George
Walbrecht
Bradley
Schmidt Beth Northcott [email protected]
406.4(D) Ex 2. This removes any material that
would hinder the complete seating of an
attachment plug of the type, intended for use
with the receptacle.
60601-1
Joe
Murnane
Bradley
Schmidt Barbara Davis [email protected]
517.160(A)(5). The isolated power systems
conductor identification colors for isolated
conductors 1, 2 and 3 (3 for 3-phase only) have
changed to the below:Isolated conductor no. 1
Orange with a distinctive colored stripe other
than white, green or gray.Isolated conductorno. 2 Brown with a distinctive colored stripe
other than white, green or gray.Isolatedconductor no. 1 Yellow with a distinctive
colored stripe other than white, green or gray.
6A
George
Walbrecht
Diana
Pappas
Jordan Paul Lloret [email protected]
300.7(B), FPN. Information on new Table
355.44 for expansion characteristics for
reinforced thermosetting resin conduit (RTRC)
has been added.
An expansion and contraction formula has
been added to this FPN for aluminum conduit
and aluminum electrical metallic tubing.
mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected] -
7/31/2019 2008 NEC Changes - Copy
12/22
Comment
If UL 429 is revised to include valve
actuator motors, then additional wording
may help provide more design flexibility of
these products.
Revise the Standard to cover these
products.
No immediate change necessary but
questions have been raised about using
standard listed connectors vs. connectors
listed specifically for grounding and
bonding.
This additional requirement maypotentially affect current lock-off device
Listings within UL's Circuit Breaker
Accessories (DIHS) category and
requirements within sub-clause 14.8 of the
UL 489 standard. Some lock-off device
Listings may require review to determine
that they are not portable or removable
after installation. The Panel stated during
the meetings that they believe multiple
lock hasps are accessories and are not
affected by this requirement, i.e. thesedevices already comply with the intent of
this code change.
This wording was accepted for similar
disconnect device requirements
referenced in Articles 610, 620, 625, 647
& 665.
-
7/31/2019 2008 NEC Changes - Copy
13/22
Comment
This additional requirement may
potentially affect current lock-off device
Listings within UL's Circuit Breaker
Accessories (DIHS) category and
requirements within sub-clause 14.8 of theUL 489 standard. Some lock-off device
Listings may require review to determine
that they are not portable or removable
after installation. The Panel stated during
the meetings that they believe multiple
lock hasps are accessories and are not
affected by this requirement, i.e. these
devices already comply with the intent of
this code change.
This wording was accepted for similardisconnect device requirements
referenced in Articles 610, 620, 625, 647
& 665.
This additional requirement may
potentially affect current lock-off device
Listings within UL's Circuit Breaker
Accessories (DIHS) category and
requirements within sub-clause 14.8 of the
UL 489 standard. Some lock-off deviceListings may require review to determine
that they are not portable or removable
after installation. The Panel stated during
the meetings that they believe multiple
lock hasps are accessories and are not
affected by this requirement, i.e. these
devices already comply with the intent of
this code change.
This wording was accepted for similardisconnect device requirements
referenced in Articles 610, 620, 625, 647
& 665.
-
7/31/2019 2008 NEC Changes - Copy
14/22
Comment
This additional requirement may
potentially affect current lock-off device
Listings within UL's Circuit Breaker
Accessories (DIHS) category and
requirements within sub-clause 14.8 of theUL 489 standard. Some lock-off device
Listings may require review to determine
that they are not portable or removable
after installation. The Panel stated during
the meetings that they believe multiple
lock hasps are accessories and are not
affected by this requirement, i.e. these
devices already comply with the intent of
this code change.
This wording was accepted for similardisconnect device requirements
referenced in Articles 610, 620, 625, 647
& 665
Need to verify the when these listed
assemblies are used. The terminal for the
equipment grounding conductor is
adequate.
The Listing evaluations of these type
devices need to take this into account
from a replacement and neutral loading
(e.g. will single component faults result in
harmonics) point of view for design and
installation instructions.
Opportunity for new industrial control
devices (control panels, power
distribution equipment, etc) that are
allowed under the new section
-
7/31/2019 2008 NEC Changes - Copy
15/22
Comment
Although this has been a long standing
practice in the burglar alarm industry, it
may be helpful to incorporate this text or a
reference to it within UL 639.
These standards may need to be reviewedto ensure that when arranged for a neutral
supply that a neutral bus or terminals be
provided so that the enclosure is not used
in the neutral current carrying path.
Verify that Type I has been required to be
marked based on 49.21.1 and no action is
needed. Note the 11th Edition clearly
addresses this issue.
These standards may need to be reviewed
to ensure that when arranged for a neutral
supply that a neutral bus or terminals beprovided so that the enclosure is not used
in the neutral current carrying path.
Opportunity for certification of industrial
control devices (control panels, power
distribution equipment, etc) that are
allowed under the new section
Will require automatic optional standby
systems to either be suitable for full load
on both sources, or have load
management system. This may require
standards revision.
-
7/31/2019 2008 NEC Changes - Copy
16/22
Comment
Provisions must be made in transfer
switches for emergency and in generators
which may be used in emergency systems
to keep the generator control wiring
independent of all other wiring. This may
require standards revision.Will require automatic optional standby
systems to either be suitable for full load
on both sources, or have load
management system. This may require
standards revision.
Revise standard to indicate that if a
baseboard heater is provided with a
receptacle the receptacle shall be
tamperproof when the heater is installed in
a residential application.
Standards need to be revised to reflect
increased ampacity requirement for unit
switches serving as disconnecting means.
For KEWV, KEZR and KEXS equipment
the receptacles in critical care areas will
need to have power on indicators.
This change would provide a better
defined connection point for the ground
shield for high voltage cable and we may
want to incorporate
UL 1072, Table 1.1 will need to be revised
to reflect the larger size conductors now
allowed by the NEC. Specifically, the first
row, second column needs to be revised
to allow conductors up to 2000 kcmil.
Presently, UL 1277 requirements do not
address nickel or nickel coated copper
conductors. A standards change is
needed to allow this option.
-
7/31/2019 2008 NEC Changes - Copy
17/22
Comment
Presently, UL 1569 requirements do not
address nickel or nickel coated copper
conductors. A standards change is
needed to allow this option.
Will require new performance, marking
requirements, Guide card and markingguide revisions. Due to the delay getting
revisions processed in this Trinational
Standard a CRD will be issued first so that
by end of first quarter 2008 certification
requirements will be in place.
Provides expansion and contraction
formulas for both raceway types.
UL should only allow use of PV wire,
USE2 cable or equivalent for general
outdoor PV modules.
Connectors need to be rated for the wire
type.
Since we have no control over installation
locations all PV connectors need to be
built such that they can only be opened
via the use of a tool.
-
7/31/2019 2008 NEC Changes - Copy
18/22
Comment
Since we have no control over installation
locations all PV connectors need to be
built such that they can only be opened
via the use of a tool.
Need marking no disconnect under loadunless evaluated for disconnect under
load.
PV modules used in ungrounded arrays
need UL PV wire to comply.
Connectors need to be rated for the wire
type.
-
7/31/2019 2008 NEC Changes - Copy
19/22
Comment
PV modules used in ungrounded arrays
need UL PV wire to comply.
May need to revise/ provide guidance on
minimum sizing of combined AC and DC
grounging.
This could require either OCP or product
evaluation for current limitation on both
sides of conductors between energy
storage and inverter / charger circuits.
Inverters with charger circuit may need
equalization voltage marking.
-
7/31/2019 2008 NEC Changes - Copy
20/22
Comment
Standards need to be revised to reflect
increased ampacity requirement for unit
switches serving as disconnecting means.
These raceways are being used toenclose not only optical fiber cables but
also Class 2 and Class 3 cables of the
appropriate rating.
Where a listed generator is supplied with
a disconnecting means the bonding
jumper sized according to NEC would be
required.
Where a generator is not provided with an
integral disconnect, the disconnect isinstalled in the field and this clause
applies the field installation rather than the
generator itself. Generators provided with
integral disconnects shall have provisions
for locking the disconnect in the open
position. Possible revisions necessary to
standard.
This change helps bolster therequirements that GFCI protection for
personnel is required even for generator-
derived power.
Integral disconnecting means shall be
suitable for use as service equipment
when the generator is used in emergency
systems. This may require standards
revision
Provisions must be made in transfer
switches for emergency and in generators
which may be used in emergency systems
to keep the generator control wiring
independent of all other wiring. This may
require standards revision.
-
7/31/2019 2008 NEC Changes - Copy
21/22
Comment
Integral disconnecting means shall be
suitable for use as service equipment
when the generator is used in legally
required standby systems. This may
require standards revision
Integral disconnecting means shall besuitable for use as service equipment
when the generator is used in emergency
systems. This may require standards
revision.
These standards may need to be reviewed
to ensure that when arranged for a neutral
supply that a neutral bus or terminals be
provided so that the enclosure is not used
in the neutral current carrying path.Need to verify the when these listed
assemblies are used, the terminal for the
equipment grounding conductor is
adequate.
Opportunity for new industrial control
devices (control panels, power
distribution equipment, etc) that are
allowed under the new section
Confirm that covers meet these
requirements and that assemblies of
devices in these covers are correct.
-
7/31/2019 2008 NEC Changes - Copy
22/22
Comment
Revise Clause 8.1.1( C)
Presently, UL 514D, para. 4.1.1 prohibits
a cover plate or outlet box hood that is
used with a receptacle shall not hinder the
complete seating of an attachment plug of
the type intended for use with the
receptacle.
For KEWV, KEYQ2 and KEXS equipment
the conductor identification colors will
need to change to those indicated.
Provides expansion and contraction
formulas for both raceway types.