7/22/2019 20001969 http://slidepdf.com/reader/full/20001969 1/76 Micro Motion TM UL-D-IS Installation Instructions, 9-Wire For installations approved for intrinsic safety by Underwriters Laboratories Installation Instructions P/N 20001969, Rev. B January 2005

Transcript of 20001969

Page 1: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 1/76

Micro MotionTM

UL-D-IS Installation

Instructions,

9-Wire

For installations approved forintrinsic safety by

Underwriters Laboratories

Installation InstructionsP/N 20001969, Rev. BJanuary 2005

Page 2: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 2/76

Page 3: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 3/76

UL-D-IS InstallationInstructions,9-Wire

For installations approved for

intrinsic safety by

Underwriters Laboratories

For online technical support, refer to the EXPERT2™ tool atwww.expert2.com. To speak to a customer servicerepresentative, call the support center nearest you:

• In U.S.A., phone 1-800-522-MASS (1-800-522-6277)

• In Canada and Latin America, phone (303) 527-5700

• In Asia, phone (65) 6770-8155

• In the U.K., phone 0800 - 966 180 (toll-free)

• Outside the U.K., phone +31 (0) 318 495 670

 ©2005, Micro Motion, Inc. All rights reserved. Micro Motion is a registered trademarkof Micro Motion, Inc. The Micro Motion and Emerson logos are trademarks ofEmerson Electric Co. All other trademarks are property of their respective owners.

Page 4: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 4/76

Page 5: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 5/76

i

Contents

Model 1700/27009-Wire Installation to Junction Box

Transmitter with integrally mounted core processor to sensor junction

box for:CMF (except CMF300A and CMF400), F, T,

D (except D600 and DT), and DL sensors. . . . . . . . . . . . . 1CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

CMF400 sensor with booster amplifier. . . . . . . . . . . . . . . . . . . 3DT sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4D600 sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Transmitter to remote core processor to:CMF (except CMF300A and CMF400), F, T,

D (except D600 and DT), and DL sensors. . . . . . . . . . . . . 6CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

CMF400 sensor with booster amplifier . . . . . . . . . . . . . . . . . . 8DT sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9D600 sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Transmitter Output InstallationAnalog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Intrinsically safe outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Configurable inputs and outputs. . . . . . . . . . . . . . . . . . . . . . . . . . 13FOUNDATION™ fieldbus outputs . . . . . . . . . . . . . . . . . . . . . . . . . 14

Profibus-PA outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Model 3300Nonincendive parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Model 3350Nonincendive parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Model 35009-Wire Installation to Junction Box

Transmitter to sensor junction box for:CMF, F, and T sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22CMF400 sensor with booster amplifier. . . . . . . . . . . . . . . . . . 23

D (except D600 and DT) and DL sensors . . . . . . . . . . . . . . . 24D600 sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

DT sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Page 6: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 6/76

ii

Contents continued 

Model 37009-Wire Installation to Junction Box

Transmitter to sensor junction box for:

CMF, F, and T sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28CMF400 sensor with booster amplifier . . . . . . . . . . . . . . . . . . 29D (except D600 and DT) and DL sensors. . . . . . . . . . . . . . . . 30

D600 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31DT sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

RFT9739 Field-MountGrounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

9-Wire Installation to Junction BoxTransmitter to sensor junction box for:

CMF and F sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35CMF400 sensor with booster amplifier . . . . . . . . . . . . . . . . . . 36

D (except D600 and DT) and DL sensors. . . . . . . . . . . . . . . . 37D600 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

DT sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

RFT9739 Rack-MountGrounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

9-Wire Installation to Junction BoxTransmitter to sensor junction box for:

CMF and F sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

CMF400 sensor with booster amplifier . . . . . . . . . . . . . . . . . . 44D (except D600 and DT) and DL sensors. . . . . . . . . . . . . . . . 45D600 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

DT sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

IFT97019-Wire Installation to Junction Box

Transmitter to sensor junction box for:CMF and F sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50CMF400 sensor with booster amplifier . . . . . . . . . . . . . . . . . . 51D (except D600 and DT) and DL sensors. . . . . . . . . . . . . . . . 52

Page 7: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 7/76

iii

Contents continued 

Model 35009-Wire Installation to Junction Box

Transmitter to remote core processor to 9-wire junction box for:

CMF (except CMF300A and CMF400), F, T,

D (except D600 and DT), and DL sensors. . . . . . . . . . . . 53CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54CMF400 sensor with booster amplifier. . . . . . . . . . . . . . . . . . 55

D600 sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56DT sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Model 37009-Wire Installation to Junction Box

Transmitter to remote core processor to 9-wire junction box for:CMF (except CMF300A and CMF400), F, T,

D (except D600 and DT), and DL sensors. . . . . . . . . . . . 59CMF300A sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60CMF400 sensor with booster amplifier. . . . . . . . . . . . . . . . . . 61

D600 sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62DT sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Remote Booster Amplifier InstallationCMF400 Booster amplifier with junction box remotely

mounted from sensor and transmitter . . . . . . . . . . . . . . . . . . 65D600 Booster amplifier with junction box remotely

mounted from sensor and transmitter . . . . . . . . . . . . . . . . . . 66

Page 8: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 8/76

iv

Page 9: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 9/76

1

UL-D-IS Installation Instructions, 9-WireModel 1700/2700

9-Wire Installation to Junction BoxTransmitter with integrally mounted core processor to sensor junction box for CMF(except CMF300A and CMF400), F, T, D (except D600 and DT), and DL sensors

Page 10: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 10/76

2

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter with integrally mounted core processor to sensor junction box forCMF300A sensor

- 5

Page 11: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 11/76

3

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter with integrally mounted core processor to sensor junction box forCMF400 sensor with booster amplifier

EB-3600533

Page 12: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 12/76

4

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter with integrally mounted core processor to sensor junction box forDT sensor

- 5

Page 13: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 13/76

5

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter with integrally mounted core processor to sensor junction box forD600 sensor

Page 14: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 14/76

6

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to CMF (except CMF300A and CMF400), F, T, D(except D600 and DT), and DL sensors

Page 15: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 15/76

7

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to CMF300A sensor

Page 16: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 16/76

8

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to CMF400 sensor with booster amplifier

Page 17: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 17/76

9

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to DT sensor

Page 18: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 18/76

10

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to D600 sensor

Page 19: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 19/76

11

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

Transmitter Output InstallationAnalog outputs

Page 20: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 20/76

12

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

Transmitter Output InstallationIntrinsically safe outputs

E

Page 21: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 21/76

13

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

Transmitter Output InstallationConfigurable inputs and outputs

C

Page 22: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 22/76

14

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

Transmitter Output InstallationFOUNDATION

™ fieldbus outputs

G

Page 23: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 23/76

15

Model 1700/2700 UL-D-IS Installation Instructions, 9-Wire

Transmitter Output InstallationProfibus-PA outputs

EB-3600472

G

Page 24: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 24/76

16

Page 25: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 25/76

17

UL-D-IS Installation Instructions, 9-WireModel 3300

Nonincendive parameters

EB-3300491

Page 26: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 26/76

18

Page 27: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 27/76

19

UL-D-IS Installation Instructions, 9-WireModel 3350

Nonincendive parameters

EB-3300817

Page 28: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 28/76

20

Page 29: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 29/76

21

UL-D-IS Installation Instructions, 9-WireModel 3500

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF, F, and T sensorsFor CMF300A, see 3002933, page 22For CMF400, see 3005807, page 23

EB-3300529

Page 30: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 30/76

22

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF300A sensor

3002933

Page 31: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 31/76

23

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF400 sensor with booster amplifier

3005807

Page 32: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 32/76

24

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D (except D600 and DT) and DL sensors(For D600, see 1005073, page 25)(For DT, see 3300554, page 26)

EB-3300553

Page 33: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 33/76

25

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D600 sensor

1005073

Page 34: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 34/76

26

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for DT sensor

3300554

Page 35: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 35/76

27

UL-D-IS Installation Instructions, 9-WireModel 3700

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF, F, and T sensorsFor CMF300A, see 3002935, page 28For CMF400, see 3005808, page 29

EB-3300564

Page 36: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 36/76

28

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF300A sensor

3002935

Page 37: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 37/76

29

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF400 sensor with booster amplifier

3005808

Page 38: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 38/76

30

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D (except D600 and DT) and DL sensorsFor D600, see 1005074, page 31For DT, see 3300574, page 32

EB-3300572

Page 39: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 39/76

31

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D600 sensor

1005074

Page 40: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 40/76

32

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for DT sensors

3300574

Page 41: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 41/76

33

UL-D-IS Installation Instructions, 9-WireRFT9739 Field-Mount

Grounding

3001547

Page 42: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 42/76

34

9739 Field-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF and F sensorsFor CMF300A, see 3002929, page 35For CMF400, see 3005802, page 36

3002205

Page 43: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 43/76

35

9739 Field-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF300A sensor

3002929

Page 44: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 44/76

36

9739 Field-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF400 sensor with booster amplifier

3005802

Page 45: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 45/76

37

9739 Field-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D (except D600 and DT) and DL sensorsFor D600, see 1005069, page 38For DT, see 3002208, page 39

EB-3002206

Page 46: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 46/76

38

9739 Field-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D600 sensor

1005069

Page 47: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 47/76

39

9739 Field-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for DT sensor

3002208

Page 48: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 48/76

40

Page 49: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 49/76

41

UL-D-IS Installation Instructions, 9-WireRFT9739 Rack-Mount

Grounding

3002535

Page 50: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 50/76

42

9739 Rack-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF and F sensorsFor CMF300A, see 3002931, page 43For CMF400, see 5005803, page 44

3002519

Page 51: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 51/76

43

9739 Rack-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF300A sensor

3002931

Page 52: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 52/76

44

9739 Rack-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF400 sensor with booster amplifier

5005803

Page 53: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 53/76

45

9739 Rack-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D (except D600 and DT) and DL sensorsFor D600, see 1005070, page 46For D600, see 3005606, page 47

3002520

Page 54: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 54/76

46

9739 Rack-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D600 sensor

1005070

Page 55: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 55/76

47

9739 Rack-Mount UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for DT sensors

3005606

Page 56: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 56/76

48

Page 57: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 57/76

49

UL-D-IS Installation Instructions, 9-WireIFT9701

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF and F sensorsFor CMF300A, see 3003299, page 50For CMF400, see 3005805, page 51

EB-3100714

Page 58: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 58/76

50

IFT9701 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF300A sensor

3003299

Page 59: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 59/76

51

IFT9701 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for CMF400 sensor with booster amplifier

3005805

Page 60: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 60/76

52

IFT9701 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to sensor junction box for D (except D600 and DT) and DL sensors

3100715

Page 61: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 61/76

53

UL-D-IS Installation Instructions, 9-WireModel 3500

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box for CMF (exceptCMF300A and CMF400), F, T, D (except D600 and DT), and DL sensors

EB-3300529

Page 62: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 62/76

54

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box for CMF300A sensor

3002933

Page 63: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 63/76

55

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box forCMF400 sensor with booster amplifier

EB-20000228

Page 64: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 64/76

56

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box for D600 sensor

3005807

Page 65: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 65/76

57

Model 3500 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box for DT sensor

3300554

Page 66: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 66/76

58

Page 67: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 67/76

59

UL-D-IS Installation Instructions, 9-WireModel 3700

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box for CMF (exceptCMF300A and CMF400), F, T, D (except D600 and DT), and DL sensors

EB-3300529

Page 68: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 68/76

60

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box for CMF300A sensor

3002933

Page 69: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 69/76

61

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box forCMF400 sensor with booster amplifier

EB-20000202

Page 70: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 70/76

62

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box for D600 sensor

3005807

Page 71: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 71/76

63

Model 3700 UL-D-IS Installation Instructions, 9-Wire

9-Wire Installation to Junction BoxTransmitter to remote core processor to 9-wire junction box for DT sensor

3300554

Page 72: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 72/76

64

Page 73: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 73/76

65

UL-D-IS Installation Instructions, 9-WireRemote Booster Amplifier Installation

CMF400 Booster amplifier with junction boxremotely mounted from sensor and transmitter

Page 74: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 74/76

66

Remote Booster Amplifier Installation UL-D-IS Installation Instructions, 9-Wire

D600 Booster amplifier with junction box remotelymounted from sensor and transmitter

Page 75: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 75/76

Page 76: 20001969

7/22/2019 20001969

http://slidepdf.com/reader/full/20001969 76/76

©2005, Micro Motion, Inc. All rights reserved. P/N 20001969, Rev. B

*20001969*

For the latest Micro Motion product specifications, view the

PRODUCTS section of our Web site at www.micromotion.com

Micro Motion Inc. USAWorldwide Headquarters7070 Winchester Circle

Boulder, Colorado 80301T (303) 527-5200

(800) 522-6277