200 A METER FITTING OVERHEAD INSTALLATION 120/208 VOLT …

24
200 A METER FITTING OVERHEAD INSTALLATION 225 A MAXIMUM SERVICE 120/208 VOLT 3 PHASE 4 WIRE 120/240 VOLT 3 PHASE 4 WIRE GB3-012

Transcript of 200 A METER FITTING OVERHEAD INSTALLATION 120/208 VOLT …

200 A METER FITTINGOVERHEAD INSTALLATION

225 A MAXIMUM SERVICE

120/208 VOLT 3 PHASE 4 WIRE120/240 VOLT 3 PHASE 4 WIRE

GB3-012

200 A METER FITTINGOVERHEAD INSTALLATION

225 A MAXIMUM SERVICE277/480 VOLT 3 PHASE 4 WIRE

SERVICEEQUIPMENT

GB3-013

200 A METER FITTINGINSTALLED AFTER MAIN SERVICE EQUIPMENT

225 A MAXIMUM SERVICE120/240 VOLT 3 PHASE 4 WIRE120/208 VOLT 3 PHASE 4 WIRE

GB3-015

200A METER FITTING, TWO GANGOVERHEAD OR UNDERGROUND INSTALLATION

120/208 OR 120/240 VOLT, 3 PHASE, 4 WIRE225A MAXIMUM SERVICE PER POSITION

GB3-017

AutoCAD SHX Text
LINE TERMINAL
AutoCAD SHX Text
COMPARTMENT
AutoCAD SHX Text
ONLY
AutoCAD SHX Text
SEE NOTES 2 & 3
AutoCAD SHX Text
6'-0" MAX.
AutoCAD SHX Text
5'-0" MIN.
AutoCAD SHX Text
GRADE
AutoCAD SHX Text
REV
AutoCAD SHX Text
NEW 6-8-18
AutoCAD SHX Text
NOTES: 1. MORE THAN TWO GANGED METER FITTINGS IN ONE CABINET SHALL NOT BE PERMITTED. MORE THAN TWO GANGED METER FITTINGS IN ONE CABINET SHALL NOT BE PERMITTED. 2. GANGED METER FITTINGS WILL BE PERMITTED TO SUPPLY 120/208 VOLT AND GANGED METER FITTINGS WILL BE PERMITTED TO SUPPLY 120/208 VOLT AND 120/240 VOLT 3 PHASE SERVICES. 3. FOR UNDERGROUND SERVICE CABLE, MINIMUM 4" RIGID METALLIC CONDUIT OR GRAY FOR UNDERGROUND SERVICE CABLE, MINIMUM 4" RIGID METALLIC CONDUIT OR GRAY SCHEDULE 80 PVC INSTALLED BY CONTRACTOR. 4. IF UNDERGROUND, LINE CONDUIT SHALL HAVE A BUSHING FOR COMPANY CABLE; IF IF UNDERGROUND, LINE CONDUIT SHALL HAVE A BUSHING FOR COMPANY CABLE; IF METALLIC CONDUIT, THE INSULATED GROUNDING BUSHING SHALL BE U.L. LISTED. 5. BONDING WIRES SHALL BE INSULATED. BONDING WIRES SHALL BE INSULATED. 6. THE METER FITTING SHALL MEET THE REQUIREMENTS SHOWN ON DRAWING GB1-005 THE METER FITTING SHALL MEET THE REQUIREMENTS SHOWN ON DRAWING GB1-005 FOR 320 AMPERE, 600 VOLT EXCEPT THE RATING SHALL BE A MINIMUM OF 200 AMPERES. 7. CONTRACTORS SHALL PERMANENTLY IDENTIFY HIGH PHASE FOR FOUR WIRE DELTA CONTRACTORS SHALL PERMANENTLY IDENTIFY HIGH PHASE FOR FOUR WIRE DELTA SERVICE IN ACCORDANCE WITH SECTION 560I. (RIGHT PHASE IN METER FITTING)
AutoCAD SHX Text
METER FITTING FURNISHED AND INSTALLED BY CONTRACTOR.
AutoCAD SHX Text
LOAD
AutoCAD SHX Text
LINE
AutoCAD SHX Text
LOAD

120/240 VOLT, 3 PHASE, 4 WIRE120/208 VOLT, 3 PHASE, 4 WIRE

OVERHEAD OR TROUGH INSTALLATIONSOUTDOOR METERING,

250 A TO 400 A SERVICEGB3-020

120/240 VOLT, 3 PHASE, 4 WIRE120/208 VOLT, 3 PHASE, 4 WIRE

INSTALLED AFTER MAIN SERVICE EQUIPMENTOUTDOOR METERING,

250 A TO 400 A SERVICEGB3-021

120/240 VOLT, 3 PHASE, 4 WIRE120/208 VOLT, 3 PHASE, 4 WIREUNDERGROUND INSTALLATION

OUTDOOR METERING,

250 A TO 400 A SERVICEGB3-022

250 A TO 400 A SERVICE277/480 VOLT, 3 PHASE, 4 WIRE

OVERHEAD OR TROUGH INSTALLATIONSOUTDOOR METERING,

GB3-024

250 A TO 400 A SERVICE277/480 VOLT, 3 PHASE, 4 WIREUNDERGROUND INSTALLATION

OUTDOOR METERING,

GB3-026

OUTDOOR METERINGOVERHEAD INSTALLATION

0 A TO 400 A SERVICE277/480 VOLT, 1 PHASE, 3 WIRE

GB3-028

WALL MOUNTED

277/480 VOLT, 3 PHASE, 4 WIRE120/240 VOLT, 3 PHASE, 4 WIRE120/208 VOLT, 3 PHASE, 4 WIRE120/240 VOLT, 1 PHASE, 3 WIRE

GB3-028

120/240 VOLT, 1 PHASE, 3 WIRE120/208 VOLT, 3 PHASE, 4 WIRE120/240 VOLT, 3 PHASE, 4 WIRE277/480 VOLT, 3 PHASE, 4 WIRE

WALL MOUNTED

277/480 VOLT, 1 PHASE, 3 WIRE401 A TO 1600 A SERVICE

OVERHEAD INSTALLATIONOUTDOOR METERING

GB3-029

OUTDOOR METERINGOVERHEAD INSTALLATION

277/480 VOLT, 3 PHASE, 4 WIRE1601 A TO 3000 A SERVICE

WALL MOUNTED

120/240 VOLT, 3 PHASE, 4 WIRE120/208 VOLT, 3 PHASE, 4 WIRE

GB3-030

OVERHEAD INSTALLATIONTRANSFORMER RATED

OUTDOOR METERING CABINET

GB3-032

PT'S IN THE METER FITTING

OUTDOOR METERING,OVERHEAD INSTALLATION,

GB3-033

120/208 VOLT, 3 PHASE, 4 WIRE120/240 VOLT, 3 PHASE, 4 WIRE

225 A MAXIMUM SERVICE

UNDERGROUND INSTALLATION200 A METER FITTING

GB3-042

277/480 VOLT, 3 PHASE, 4 WIRE

225 A MAXIMUM SERVICE

UNDERGROUND INSTALLATION

200 A METER FITTING

SERVICE

EQUIPMENT

GB3-044

OUTDOOR METERINGUNDERGROUND INSTALLATION

120/208, or 120/240 VOLT, 3 PHASE, 4 WIRE500 A TO 1200 A SERVICE GB3-060

UNDERGROUND INSTALLATION120/208 or 120/240 VOLT, 3 PHASE, 4 WIRE

500 A TO 1200 A SERVICE

MAXIMUM SIZE MULTIPLE SERVICES

OUTDOOR METERING,

GB3-070

UNDERGROUND INSTALLATION277/480 VOLT 3 PHASE, 4 WIRE

250 A TO 1200 A SERVICE

OUTDOOR METERING,

GB3-085

TRANSFORMER MOUNTED CT's ONLY277/480 VOLT, 3 PHASE, 4 WIRE

OUTDOOR METERING,UNDERGROUND INSTALLATION,

450 A TO 3000 A SERVICEGB3-095

TRANSFORMER MOUNTED CT's ONLY120/208 VOLT, 3 PHASE, 4 WIRE

OUTDOOR METERING,UNDERGROUND INSTALLATION,

450 A TO 3000 A SERVICEGB3-096

277/480 VOLT, 3 PHASE, 4 WIRE

INDOOR METERING120/208 OR 120/240 VOLT, 3 PHASE, 4 WIRE

250 A TO 1200 A SERVICE GB3-100

277/480 VOLT, 3 PHASE, 4 WIRE

INDOOR METERING120/208 OR 120/240 VOLT, 3 PHASE, 4 WIRE

250 A TO 1200 A SERVICE GB3-100

METERING COMPARTMENTFOR SWITCHGEAR

120/240 or 120/208V or 277/480V GB3-120

AutoCAD SHX Text
36" MIN.
AutoCAD SHX Text
36" MIN.
AutoCAD SHX Text
REMOVABLE BUS
AutoCAD SHX Text
12" TO 20"
AutoCAD SHX Text
4"
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
DRILL & TAP FOR
AutoCAD SHX Text
LUG
AutoCAD SHX Text
A0
AutoCAD SHX Text
B0
AutoCAD SHX Text
C0
AutoCAD SHX Text
N
AutoCAD SHX Text
CT
AutoCAD SHX Text
CT
AutoCAD SHX Text
CT
AutoCAD SHX Text
PT
AutoCAD SHX Text
PT
AutoCAD SHX Text
PT
AutoCAD SHX Text
1/4" - 20 BOLT
AutoCAD SHX Text
SEE NOTE 6
AutoCAD SHX Text
#12 WIRE W/LUG
AutoCAD SHX Text
ON SIDE OF C.T./P.T.
AutoCAD SHX Text
COMPARTMENT MIN.
AutoCAD SHX Text
(SEE NOTE 5)
AutoCAD SHX Text
CONTACT THE
AutoCAD SHX Text
ON SERVICE SIZE,
AutoCAD SHX Text
SIZE IS DEPENDENT
AutoCAD SHX Text
COMPANY.
AutoCAD SHX Text
TEST SWITCH
AutoCAD SHX Text
18"
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
NOTES: 1. CT, PT AND CODED CONTROL CABLE FURNISHED BY THE COMPANY AND INSTALLED BY CT, PT AND CODED CONTROL CABLE FURNISHED BY THE COMPANY AND INSTALLED BY ELECTRICAL CONTRACTOR. 2. METERING CABINET FURNISHED BY THE COMPANY AND INSTALLED BY ELECTRICAL METERING CABINET FURNISHED BY THE COMPANY AND INSTALLED BY ELECTRICAL CONTRACTOR WITH A 1-1/4" CONTINUOUS CONDUIT FROM C.T./P.T. COMPARTMENT TO METER CABINET. METERING CABINET SHALL BE INSTALLED AT A REMOTE POINT IN A LOCATION AGREEABLE TO THE CUSTOMER AND THE COMPANY. 3. IDENTIFY C.T./P.T. COMPARTMENT WITH NAME PLATE OR STENCIL. IDENTIFY C.T./P.T. COMPARTMENT WITH NAME PLATE OR STENCIL. 4. 480 VOLT SERVICES, FLOOR OF COMPARTMENT TO BE CAPABLE OF SUPPORTING 60 480 VOLT SERVICES, FLOOR OF COMPARTMENT TO BE CAPABLE OF SUPPORTING 60 LBS. INDEFINITELY. 5. A NEUTRAL TAP MAY BE USED IN PLACE OF A NEUTRAL BUS USING #12 COPPER A NEUTRAL TAP MAY BE USED IN PLACE OF A NEUTRAL BUS USING #12 COPPER WIRE W/LUG FOR TERMINATION. 6. INSTALL P.T.'s WITH PRIMARY TO REAR AND SECONDARY TO THE FRONT. INSTALL P.T.'s WITH PRIMARY TO REAR AND SECONDARY TO THE FRONT. 7. METER COMPARTMENT DIMENSIONS MAY BE CHANGED ONLY UPON WRITTEN APPROVAL METER COMPARTMENT DIMENSIONS MAY BE CHANGED ONLY UPON WRITTEN APPROVAL FROM THE COMPANY'S METER DEPARTMENT. 8. CONTRACTOR SHALL PERMANENTLY IDENTIFY HIGH PHASE FOR FOUR WIRE DELTA CONTRACTOR SHALL PERMANENTLY IDENTIFY HIGH PHASE FOR FOUR WIRE DELTA SERVICE IN ACCORDANCE WITH SECTION 560. 9. THE USE OF CONDUIT BODIES (CONDULETS) WITH REMOVABLE COVERS IS PROHIBITED THE USE OF CONDUIT BODIES (CONDULETS) WITH REMOVABLE COVERS IS PROHIBITED FOR METERING CABLE.
AutoCAD SHX Text
REV
AutoCAD SHX Text
5-23-17