2 Unbalanced Faults

download 2 Unbalanced Faults

of 87

Transcript of 2 Unbalanced Faults

  • 8/22/2019 2 Unbalanced Faults

    1/87

    This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior

    written consent of Alstom Grid Technical Institute. All rights reserved.

    GRID

    Technical Institute

    Analysis o f Unbalanced Faults

  • 8/22/2019 2 Unbalanced Faults

    2/87

    > Analysis of Unbalanced Fults2

    Fault Types

    Line - Ground (65 - 70%)

    Line - Line - Ground (10 - 20%)

    Line - Line (10 - 15%)

    Line - Line - Line (5%)

    Statistics published in 1967 CEGB Report, but are similar todayall over the world.

  • 8/22/2019 2 Unbalanced Faults

    3/87

    > Analysis of Unbalanced Fults3

    Fault Inc idence

    85% of faults are overhead line faults.

    50% of these due to lightning strikes.

  • 8/22/2019 2 Unbalanced Faults

    4/87

    > Analysis of Unbalanced Fults4

    Unbalanced Faults (1)

    In three phase fault calculations, a single phase

    representation is adopted

    3 phase faults are rare

    Majority of faults are unbalanced faults

    UNBALANCED FAULTS may be classified into

    SHUNT FAULTS and SERIES FAULTS SHUNT FAULTS

    Line to Ground Line to Line Line to Line to Ground

    SERIES FAULTS

    Single Phase Open Circuit Double Phase Open Circuit

  • 8/22/2019 2 Unbalanced Faults

    5/87

    > Analysis of Unbalanced Fults5

    Unbalanced Faults (2)

    LINE TO GROUND

    LINE TO LINE

    LINE TO LINE TO GROUND

    Causes :

    1) Insulation Breakdown

    2) Lightning Discharges and other Overvoltages

    3) Mechanical Damage

  • 8/22/2019 2 Unbalanced Faults

    6/87

    > Analysis of Unbalanced Fults6

    Unbalanced Faults (3)

    OPEN CIRCUIT OR SERIES FAULTS

    Causes :

    1) Broken Conductor2) Operation of Fuses

    3) Maloperation of Single Phase Circuit Breakers

    DURING UNBALANCED FAULTS, SYMMETRY OF SYSTEMIS LOST

    SINGLE PHASE REPRESENTATION IS NO LONGER VALID

  • 8/22/2019 2 Unbalanced Faults

    7/87> Analysis of Unbalanced Fults7

    Unbalanced Faults (4)

    Analysed using :-

    Symmetrical Components

    Equivalent Sequence Networks of Power System

    Connection of Sequence Networks appropriate to Typeof Fault

  • 8/22/2019 2 Unbalanced Faults

    8/87> Analysis of Unbalanced Fults8

    Symmetr ica l Components

    Fortescue discovered a property of unbalanced phasors

    n phasors may be resolved into :-

    (n-1) sets of balanced n-phase systems of phasors, each sethaving a different phase sequence

    plus

    1 set of zero phase sequence or unidirectional phasors

    VA = VA1 + VA2 + VA3 + VA4 - - - - - VA(n-1) + VAn

    VB = VB1 + VB2 + VB3 + VB4 - - - - - VB(n-1) + VBn

    VC = VC1 + VC2 + VC3 + VC4 - - - - - VC(n-1) + VCn

    VD = VD1 + VD2 + VD3 + VD4 - - - - - VD(n-1) + VDn- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    Vn = Vn1 + Vn2 + Vn3 + Vn4 - - - - - Vn(n-1) + Vnn

    (n-1) x Balanced 1 x ZeroSequence

  • 8/22/2019 2 Unbalanced Faults

    9/87> Analysis of Unbalanced Fults9

    Unbalanced 5-Phase Sys tem of Vo ltages (1)

    This can be resolved into :-

    First Set of Balanced Second Set ofPhasors Balanced Phasors

    VA1

    2VE1

    VD1 VC1

    VB1

    VA2

    VC2

    VE2 VB2

    VD2

  • 8/22/2019 2 Unbalanced Faults

    10/87> Analysis of Unbalanced Fults10

    Unbalanced 5-Phase Sys tem of Vo ltages (2)

    Third Set of Balanced Fourth Set of

    Phasors Balanced Phasors

    4

    3

    VA4

    VB4

    VC4 VD4

    VE4

    VA3

    VD

    3

    VB3 VE3

    VC3

  • 8/22/2019 2 Unbalanced Faults

    11/87> Analysis of Unbalanced Fults11

    Unbalanced 5-Phase Sys tem of Vo ltages (3)

    Fifth Set of Zero

    Sequence Phasors VA5

    VB5

    VD5

    VE5

    VC5

  • 8/22/2019 2 Unbalanced Faults

    12/87> Analysis of Unbalanced Fults12

    Unbalanced 3-Phase Sys tem of Vo ltages (1)

    This can be resolved into :-

    First Set of Balanced Second Set of

    Phasors Balanced Phasors

    VA1

    VC1

    120

    VB1

    VA2

    VB2 VC2

    240

  • 8/22/2019 2 Unbalanced Faults

    13/87> Analysis of Unbalanced Fults13

    Unbalanced 3-Phase Sys tem of Vo ltages (2)

    Third Set of Zero

    Sequence Phasors

    VA3

    VB3

    VC3

  • 8/22/2019 2 Unbalanced Faults

    14/87> Analysis of Unbalanced Fults14

    Unbalanced 3-Phase System (1)

    VA = VA1 + VA2 + VA0

    VB = VB1 + VB2 + VB0

    VC = VC1 + VC2 + VC0

    Positive Sequence Negative Sequence

    VA1

    VC1

    120

    VB1

    VA2

    VB2 VC2

    240

  • 8/22/2019 2 Unbalanced Faults

    15/87> Analysis of Unbalanced Fults15

    Unbalanced 3-Phase System (2)

    Zero Sequence

    VA0

    VB0

    VC0

  • 8/22/2019 2 Unbalanced Faults

    16/87> Analysis of Unbalanced Fults16

    Symmetr ica l Components

    Phase Positive + Negative + Zero

    VA VA1 + VA2 + VA0

    VB VB1 + VB2 + VB0

    VC VC1 + VC2 + VC0

    VA

    VB

    VC

    ++

    VB1VC1

    VA1

    VB2

    VC2

    VC0VB0VA0VA2

    VB1 = a2 VA1 VB2 = a VA2 VB0 = VA0

    VC1 = a VA1 VC2 = a2

    VA2 VC0 = VA0

    =

    =

    =

  • 8/22/2019 2 Unbalanced Faults

    17/87> Analysis of Unbalanced Fults17

    Conver ting from Sequence Componentsto Phase Values

    VA = VA1 + VA2 + VA0

    VB = VB1 + VB2 + VB0 = a2VA1 + a VA2 + VA0

    VC = VC1 + VC2 + VC0 = a VA1 + a2VA2 + VA0

    VA0

    VC1

    VC

    VA2

    VA1

    VA

    VC0

    VC2

    VB2

    VB0VB1

    VB

  • 8/22/2019 2 Unbalanced Faults

    18/87> Analysis of Unbalanced Fults18

    Convert ing from Phase Valuesto Sequence Components

    VA1 = 1/3 {VA + a VB + a2

    VC}VA2 = 1/3 {VA + a

    2VB + a VC}

    VA0 = 1/3 {VA + VB + VC}

    VC3VA0

    VB

    VA0

    VA

  • 8/22/2019 2 Unbalanced Faults

    19/87> Analysis of Unbalanced Fults19

    Add VA, VB, VC vectorially

    VA = VA1 + VA2 + VA0

    VB

    = a2VA1

    + a VA2

    + VA0

    VC = a VA1 + a2VA2 + VA0

    VA + VB + VC = 0 + 0 + 3VA0

    VA0 = 1/3 (VA + VB + VC )Add VA, aVB and a

    2VC vectorially

    VA = VA1 + VA2 + VA0

    a VB = VA1 + a2VA2 + a VA0

    a2VC = VA1 + a VA2 + a2VA0

    VA + aVB + a2VC = 3VA1 + 0 + 0

    VA1 = 1/3 (VA + a VB + a2 VC )

  • 8/22/2019 2 Unbalanced Faults

    20/87> Analysis of Unbalanced Fults20

    Add VA, a2VB and aVC vectorially

    VA = VA1 + VA2 + VA0

    a2VB = a VA1 + VA2 + a2VA0

    a VC = a2VA1 + VA2 + a VA0

    VA + a2VB + VC = 0 + 3VA2 + 0

    VA2 = 1/3 (VA + a2VB + aVC )

  • 8/22/2019 2 Unbalanced Faults

    21/87> Analysis of Unbalanced Fults21

    VA = VA1 + VA2 + VA0

    VB = a2 VA1 + a VA2 + VA0

    VC = a VA1 + a2 VA2 + VA0

    IA = IA1 + IA2 + IA0

    IB = a2 IA1 + a IA2 + IA0

    IC = a IA1 + a2 IA2 + IA0

    VA1 = 1/3 {VA + a VB + a2 VC }

    VA2 = 1/3 {VA + a2 VB + a VC }

    VA0 = 1/3 {VA + VB + VC }

    IA1 = 1/3 { IA + a IB + a2 IC }

    IA2 = 1/3 { IA + a2 IB + a IC }

    IA0 + 1/3 { IA + IB + IC }

  • 8/22/2019 2 Unbalanced Faults

    22/87> Analysis of Unbalanced Fults22

    Residu al Current

    Used to detect earth faults

    *IRESIDUAL is zero for :- *IRESIDUAL is present for :-

    Balanced Load /E Faults

    3 Faults //E Faults

    / Faults

    IA

    IRESIDUAL = IA + IB +

    IC

    = 3I0

    IB

    IC

    E/F

  • 8/22/2019 2 Unbalanced Faults

    23/87

    > Analysis of Unbalanced Fults23

    Residual Voltage

    Used to detect earth faults

    Residual voltage is measured fromOpen Delta or Broken Delta VT

    secondary windings.

    VRESIDUAL is zero for:-

    Healthy unfaulted systems

    3 Faults

    / Faults

    VRESIDUAL is present for:-

    /E Faults//E Faults

    Open Circuits (on supply

    side of VT with earthed source)

    VRESIDUAL= VA+ VB+VC

    = 3V0

  • 8/22/2019 2 Unbalanced Faults

    24/87

    > Analysis of Unbalanced Fults24

    Example

    Evaluate the positive, negative and zero sequence components

    for the unbalanced phase vectors :

    VA = 10VB = 1.5 -90

    VC = 0.5 120

    VC

    VA

    VB

  • 8/22/2019 2 Unbalanced Faults

    25/87

    > Analysis of Unbalanced Fults25

    Solut ion

    VA1 = 1/3 (VA + aVB + a2VC)

    = 1/3 1 + (1 120) (1.5 -90)+ (1 240) (0.5 120)

    = 0.965 15

    VA2 = 1/3 (VA + a2

    VB + aVC)= 1/3 1 + (1 240) (1.5 -90)

    + (1 120) (0.5 120) = 0.211 150

    VA0 = 1/3 (VA + VB + VC)

    = 1/3 (1 + 1.5 -90 + 0.5 120)= 0.434 -55

    S

  • 8/22/2019 2 Unbalanced Faults

    26/87

    > Analysis of Unbalanced Fults26

    Pos it ive Sequence Voltages

    VC1 = aVA1

    15

    VA1 =

    0.96515

    VB1 =

    a2VA1

  • 8/22/2019 2 Unbalanced Faults

    27/87

    > Analysis of Unbalanced Fults27

    Zero SequenceVoltagesNegative Sequence

    Voltages

    VA0 = 0.434-

    55VB0 = -

    VC0 = -

    -55VC2 = a2 VA2150

    VB2 = a VA2

    VA2 =0.211150

    S t i l C t

  • 8/22/2019 2 Unbalanced Faults

    28/87

    > Analysis of Unbalanced Fults28

    Symmetr ica l Components

    VC1

    VA1

    VB1

    VC2

    VA2

    VB2

    VC0

    VA0

    VB0

    VA2VC2

    VB2

    VC

    VA

    V0

    VB

    E l (1)

  • 8/22/2019 2 Unbalanced Faults

    29/87

    > Analysis of Unbalanced Fults29

    Examp le (1)

    Evaluate the phase quantities IA, IB and IC from the

    sequence componentsIA1 = 0.6 0IA2 = -0.4 0IA0 = -0.2 0

    Solution

    IA = IA1 + IA2 + IA0 = 0

    IB = a2IA1 + aIA1 + IA0

    = 0.6240 - 0.4120 - 0.20 = 0.91-109IC = aIA1 + a

    2IA2 + IA0

    = 0.6120 - 0.4240 - 0.20 = 0.91+109

    E l (2)

  • 8/22/2019 2 Unbalanced Faults

    30/87

    > Analysis of Unbalanced Fults30

    Examp le (2)

    IC

    IB

    109

    109

  • 8/22/2019 2 Unbalanced Faults

    31/87

    > Analysis of Unbalanced Fults31

    POSITIVE

    IA1

    NEGATIVE

    IB1

    IC1

    IA2

    IB2

    IC2

    IC1

    IB1

    IA1

    IA2

    IB2

    IC2

  • 8/22/2019 2 Unbalanced Faults

    32/87

    > Analysis of Unbalanced Fults32

    PHASE

    ZERO

    IA0

    IB0IC0

    IB

    IC

    IC

    IB

    IA0IB0IC0

    Sequence Components (1)

  • 8/22/2019 2 Unbalanced Faults

    33/87

    > Analysis of Unbalanced Fults33

    Sequence Components (1)

    Any 3 phase system of vectors may be represented as the sum of3 sets of symmetrical vectors :-

    3 PHASE

    VECTORS

    EQUIVALENT SYMMETRICAL COMPONENTS

    POSITIVE PHASE

    SEQUENCE (PPS)

    ZERO PHASE

    SEQUENCE

    I2

    BALANCED LOADOR 3-PHASE FAULT

    /IA/ = /IB/ = /IC/ = IFI0 = 0I2 = 0I1 = IF

    NEGATIVE PHASE

    SEQUENCE (NPS)

    I1

    IA

    IC IB

    I0

    IA1

    IC1 IB1

    Sequence Components (2)

  • 8/22/2019 2 Unbalanced Faults

    34/87

    > Analysis of Unbalanced Fults34

    Sequence Components (2)

    PHASE-PHASE

    FAULT /IA/=/IB/ = IF

    IA

    IB

    I0 = 0

    IA1

    IC1

    IB1

    IA2

    IC2

    IB2

    I1 = IF

    3

    I2 = IF

    3

    Sequence Components (3)

  • 8/22/2019 2 Unbalanced Faults

    35/87

    > Analysis of Unbalanced Fults35

    Sequence Components (3)

    PHASE-EARTH

    FAULTS

    /IA/ OR /IC/ = IF

    IA

    IC

    I

    B2

    IC2 IA2

    IA0 IC0IB0IA1

    IC1 IB1

    IA2

    IB2 IC2

    IA1

    IC1 IB1

    I1 = IF

    3

    I2 = IF

    3

    I0 = IF

    3

    IA0 IC0IB0

    Sequence Networks

  • 8/22/2019 2 Unbalanced Faults

    36/87

    > Analysis of Unbalanced Fults36

    Sequence Networks

    It can be shown that providing the system impedances arebalanced from the points of generation right up to the fault, eachsequence current causes voltage drop of its own sequence only.

    Regard each sequence current flowing within its own networkthro impedances of its own sequence only, with no

    interconnection between the sequence networks right up to thepoint of fault.

    Unbalanced Voltages and Currents act ing on

  • 8/22/2019 2 Unbalanced Faults

    37/87

    > Analysis of Unbalanced Fults37

    Unbalanced Voltages and Currents act ing onBalanced Impedances

    ZSIAVA

    ZMZMZSIBVB

    ZMZSICVC

    VA = IAZS + IBZM + ICZM

    VB = IAZM + IBZS + ICZM

    VC = IAZM + IBZM + ICZS

    In matrix form

    VA ZS ZM ZM IA

    VB = ZM ZS ZM IB

    VC ZM ZM ZS IC

  • 8/22/2019 2 Unbalanced Faults

    38/87

    > Analysis of Unbalanced Fults38

    Resolve V & I phasors into symmetrical components

    1 1 1 V0 ZS ZM ZM 1 1 1 I0

    1 a2 a V1 = ZM ZS ZM 1 a2 a I1

    1 a a2 V2 ZM ZM ZS 1 a a2 I2

    Multiply by [A]-1

    V0 1 1 1 ZS ZM ZM 1 1 1 I0

    V1 = 1 a2 a ZM ZS ZM 1 a

    2 a I1

    V2 1 a a2 ZM ZM ZS 1 a a

    2 I2

    V0 1 1 1 ZS ZM ZM 1 1 1 I0

    V1 = 1/3 1 a a2 ZM ZS ZM 1 a

    2 a I1

    V2 1 a2 a ZM ZM ZS 1 a a

    2 I2

    V0 ZS + 2ZM ZS + 2ZM ZS + 2ZM

    V1 = 1/3 ZS - ZM ZM + a ZS + a2 ZM ZM + aZM + a

    2 ZS

    V2 ZS - ZM ZM + a2 ZS + a ZM ZM + a

    2 ZM + a ZS

    1 1 1 I0

    1 a2 a I1

    1 a a2

    I2

    -1

  • 8/22/2019 2 Unbalanced Faults

    39/87

    > Analysis of Unbalanced Fults39

    V0 ZS + 2ZM 0 0 I0

    V1 = 0 ZS - ZM 0 I1

    V2 0 0 ZS - ZM I2

    V0 Z0 0 0 I0

    V1 = 0 Z1 0 I1

    V2 0 0 Z2 I2

    The symmetrical component impedance matrix is adiagonal matrix if system is symmetrical.

    The sequence networks are independent of each other.

    The three isolated sequence networks are

    interconnected when an unbalance such as a fault orunbalanced loading is introduced.

    Phase Sequence Equ ivalent Circuits (1)

  • 8/22/2019 2 Unbalanced Faults

    40/87

    > Analysis of Unbalanced Fults40

    Phase Sequence Equ ivalent Circuits (1)

    Positive Sequence Impedance

    E

    QPa2E

    aE

    Z1 = E/I

    Q1P1

    I

    a2 I

    aI

    Phase Sequence Equ ivalent Circuits (2)

  • 8/22/2019 2 Unbalanced Faults

    41/87

    > Analysis of Unbalanced Fults41

    Phase Sequence Equ ivalent Circuits (2)

    Negative Sequence Impedance

    For static non-rotating plant :- Z2 = Z1

    E

    QP

    a2E

    aE

    Z2 = E/I

    Q2P2

    I

    a2 I

    aI

    Phase Sequence Equ ivalent Circuits (3)

  • 8/22/2019 2 Unbalanced Faults

    42/87

    > Analysis of Unbalanced Fults42

    Phase Sequence Equ ivalent Circuits (3)

    Zero Sequence Impedance

    I

    I

    I3I

    E QP

    Z0 = E/IP0 Q0

    Sequence Networks

  • 8/22/2019 2 Unbalanced Faults

    43/87

    > Analysis of Unbalanced Fults43

    Sequence Networks

    +ve, -ve and zero sequence networks are drawn for areference phase. This is usually taken as the A phase.

    Faults are selected to be balanced relative to the referenceA phase.

    e.g. For /E faults consider an A-E fault

    For / faults consider a B-C fault

    Sequence network interconnection is the simplest for thereference phase.

    Pos it ive Sequence Diagram

  • 8/22/2019 2 Unbalanced Faults

    44/87

    > Analysis of Unbalanced Fults44

    Pos it ive Sequence Diagram

    1. Start with neutral point N1

    - All generator and load neutrals are connected to N1

    2. Include all source EMFs

    - Phase-neutral voltage

    3. Impedance network

    - Positive sequence impedance per phase

    4. Diagram finishes at fault point F1

    Z1N1E1

    F1

    Example

  • 8/22/2019 2 Unbalanced Faults

    45/87

    > Analysis of Unbalanced Fults45

    Example

    V1 = Positive sequence /N voltage at fault point

    I1 = Positive sequence phase current flowing into F1

    V1 = E1 - I1 (ZG1 + ZT1 + ZL1)

    E1F1I1

    ZL1ZG1 ZT1N1

    (N1)

    V1

    Line

    FN

    E

    R

    Generator Transformer

    Negative Sequence Diagram

  • 8/22/2019 2 Unbalanced Faults

    46/87

    > Analysis of Unbalanced Fults46

    Negative Sequence Diagram

    1. Start with neutral point N2

    - All generator and load neutrals are connected to N2

    2. No EMFs included

    - No negative sequence voltage is generated!

    3. Impedance network

    - Negative sequence impedance per phase

    4. Diagram finishes at fault point F2

    Z2N2 F

    2

    Example

  • 8/22/2019 2 Unbalanced Faults

    47/87

    > Analysis of Unbalanced Fults47

    Example

    V2 = Negative sequence /N voltage at fault point

    I2 = Negative sequence phase current flowing into F2

    V2 = -I2 (ZG2 + ZT2 + ZL2)

    F2I2ZL2ZG2 ZT2N2

    (N2)

    V2

    Line F

    N

    E

    R

    Generator Transformer

    System Single LineDiagram

    Negative Sequence Diagram

    Zero Sequence Diagram (1)

  • 8/22/2019 2 Unbalanced Faults

    48/87

    > Analysis of Unbalanced Fults48

    Zero Sequence Diagram (1)

    For In Phase (Zero Phase Sequence) currents to flow in each

    phase of the system, there must be a fourth connection (this istypically the neutral or earth connection).

    IA0 + IB0 + IC0 = 3IA0

    IA0N

    IB0

    I

    C0

    Zero Sequence Diagram (2)

  • 8/22/2019 2 Unbalanced Faults

    49/87

    > Analysis of Unbalanced Fults49

    Zero Sequence Diagram (2)

    Resistance Earthed System :-

    3IA0

    N

    E

    R

    Zero sequence voltage between N & E given by

    V0 = -3IA0. RZero sequence impedance of neutral to earth path

    Z0 = V0 = 3R

    -IA0

    Trans form er Zero Sequence Impedance

  • 8/22/2019 2 Unbalanced Faults

    50/87

    > Analysis of Unbalanced Fults50

    Trans form er Zero Sequence Impedance

    QP

    ZT0

    aaQP

    bb

    N0

    General Zero Sequence Equ ivalent Circu it

  • 8/22/2019 2 Unbalanced Faults

    51/87

    > Analysis of Unbalanced Fults51

    q qfor Two Wind ing Transfo rmer

    Secondary

    Terminal'a' 'a'

    Primary

    Terminal

    'b' 'b'

    N0

    ZT0

    On appropriate side of transformer :

    Earthed Star Winding - Close link a

    Open link b

    Delta Winding - Open link a

    Close link b

    Unearthed Star Winding - Both links open

    Zero Sequence Equ ivalent

  • 8/22/2019 2 Unbalanced Faults

    52/87

    > Analysis of Unbalanced Fults52

    q qDy Tx (1)

    3I0

    No zero sequence

    in line connection

    on side

    I0

    I0

    I0

    Zero Sequence Equ ivalent

  • 8/22/2019 2 Unbalanced Faults

    53/87

    > Analysis of Unbalanced Fults53

    q qDy Transfo rmer (2)

    side

    terminal

    side

    terminal

    ZT0

    N0

    (E0)

    I

    0

    Thus, equivalent single phase zero sequence diagram :-

    Zero Sequence Equ ivalent Circu its (1)

  • 8/22/2019 2 Unbalanced Faults

    54/87

    > Analysis of Unbalanced Fults54

    q q ( )

    S0ZT0

    N0

    P0

    P S

    aa

    b b

    Zero Sequence Equ ivalent Circu its (2)

  • 8/22/2019 2 Unbalanced Faults

    55/87

    > Analysis of Unbalanced Fults55

    q q ( )

    S0ZT0

    N0

    P0

    P S

    aa

    b b

    Zero Sequence Equ ivalent Circu its (3)

  • 8/22/2019 2 Unbalanced Faults

    56/87

    > Analysis of Unbalanced Fults56

    q q ( )

    S0ZT0

    N0

    P0

    P S

    aa

    b b

    Zero Sequence Equ ivalent Circu its (4)

  • 8/22/2019 2 Unbalanced Faults

    57/87

    > Analysis of Unbalanced Fults57

    q q ( )

    S0ZT0

    N0

    P0

    P S

    aa

    b b

    Zero Sequence Diagram

  • 8/22/2019 2 Unbalanced Faults

    58/87

    > Analysis of Unbalanced Fults58

    V0 = Zero sequence PH-E voltage at fault point

    I0 = Zero sequence current flowing into F0

    V0 = -I0 (ZT0 + ZL0 + 3RT)

    F0I0ZL0ZG0 ZT0N0

    N0

    V0

    LineF

    N

    E

    R

    Generator Transformer

    System Single LineDiagram

    Zero Sequence Network

    3R

    E0

    3RT

    RT

    Zig-Zag Earthing Trans formers (1)

  • 8/22/2019 2 Unbalanced Faults

    59/87

    > Analysis of Unbalanced Fults59

    Positive (and negative) sequence impedance is very high.

    Equivalent Circuit :

    P

    N

    E

    R

    P1

    N1

    Zig-Zag Earthing Trans formers (2)

  • 8/22/2019 2 Unbalanced Faults

    60/87

    > Analysis of Unbalanced Fults60

    Zero sequence impedance is very low.

    Equivalent Circuit P0

    ZT0

    3R

    N0

    (E0)

    Summary o f Sequence Diagrams (1)

  • 8/22/2019 2 Unbalanced Faults

    61/87

    > Analysis of Unbalanced Fults61

    System Single Line Diagram

    R

    E

    N

    GENERATOR TRANSFORMERLINE F

    Summary o f Sequence Diagrams (2)

  • 8/22/2019 2 Unbalanced Faults

    62/87

    > Analysis of Unbalanced Fults62

    Positive Sequence

    (N1)

    V1

    F1ZL1ZT1ZG1

    E1N1 I1

    Summary o f Sequence Diagrams (3)

  • 8/22/2019 2 Unbalanced Faults

    63/87

    > Analysis of Unbalanced Fults63

    Negative Sequence

    (N2)

    V2

    F2ZL2ZT2ZG2N2 I2

    Summary o f Sequence Diagrams (4)

  • 8/22/2019 2 Unbalanced Faults

    64/87

    > Analysis of Unbalanced Fults64

    Zero Sequence

    E0(N0)

    V0

    F0ZL0ZT0ZG0

    3R

    N0 I0

    Interconnect ion o f Sequence Netwo rks

  • 8/22/2019 2 Unbalanced Faults

    65/87

    > Analysis of Unbalanced Fults65

    Consider sequence networks as blocks with fault terminals F & N forexternal connections.

    F1

    POSITIVE

    SEQUENCE

    NETWORK

    N1

    F2

    NEGATIVE

    SEQUENCE

    NETWORK

    N2

    F0

    ZERO

    SEQUENCE

    NETWORK

    N0

    I2

    V2

    I0

    V0

    I1

    V1

    Interconnect ion o f Sequence Netwo rks

  • 8/22/2019 2 Unbalanced Faults

    66/87

    > Analysis of Unbalanced Fults66

    For any given fault there are 6 quantities to be considered at the fault point

    i.e. VA VB VC IA IB IC

    Relationships between these for any type of fault can be converted into anequivalent relationship between sequence components

    V1, V2, V0 and I1,I2 ,I0

    This is possible if :-

    1) Any 3 phase quantities are known (provided they are not all

    voltages or all currents)

    or 2) 2 are known and 2 others are known to have a specific

    relationship.

    From the relationship between sequence Vs and Is, the manner inwhich the isolation sequence networks are connected can be determined.

    The connection of the sequence networks provides a single phase

    representation (in sequence terms) of the fault.

  • 8/22/2019 2 Unbalanced Faults

    67/87

    > Analysis of Unbalanced Fults67

    To derive the system constraints at the fault terminals :-

    IA

    VA

    IB IC

    VB VC

    F

    Terminals are connected to represent the fault.

    A

    B

    C

    Phase to Earth Fault on Phase A

  • 8/22/2019 2 Unbalanced Faults

    68/87

    > Analysis of Unbalanced Fults68

    IA

    VA

    IB IC

    VB VC

    At fault point :-

    VA = 0

    VB = ?

    VC = ?

    IA = ?

    IB = 0

    IC = 0

    A

    B

    C

    Phase to Earth Fault on Phase A

  • 8/22/2019 2 Unbalanced Faults

    69/87

    > Analysis of Unbalanced Fults69

    At fault point

    VA = 0; IB = 0 ; IC = 0

    but VA = V1 + V2 + V0 V1 + V2 + V0 = 0 ------------------------- (1)I0 = 1/3 (IA + IB + IC ) = 1/3 IA

    I1 = 1/3 (IA + aIB + a2IC) = 1/3 IA

    I2 = 1/3 (IA + a2IB + aIC) = 1/3 IA

    I1 = I2 = I0 = 1/3 IA ------------------------- (2)To comply with (1) & (2) the sequence networks must be connected in series :-

    I1 F1

    N1

    V1+veSeqN/W

    I

    2

    F2

    N2

    V2-veSeqN/W

    I0F0

    N0

    V0ZeroSeqN/W

    Example : Phase to Earth Fault

  • 8/22/2019 2 Unbalanced Faults

    70/87

    > Analysis of Unbalanced Fults70

    SOURCE LINE F

    132 kV

    2000 MVA

    ZS1 = 8.7

    ZS0 = 8.7

    A - GFAULTZL1 = 10

    ZL0 = 35

    Total impedance = 81.1I1 = I2 = I0 = 132000 = 940 Amps3 x 81.1IF = IA = I1 + I2 + I0 = 3I0 = 2820 Amps

    IF

    8.7 10 I1 F1

    N1

    8.7 10 I2 F2

    N2

    8.7 35 I0 F0

    N0

    Earth Fault with Fault Resistance

  • 8/22/2019 2 Unbalanced Faults

    71/87

    > Analysis of Unbalanced Fults71

    IA

    VA

    IB IC

    VB VC

    At fault point :-

    VA = IAZF

    VB = ?

    VC = ?

    IA = ?

    IB = 0

    IC = 0

    ZF

    Earth Fault with Fault Resistance

  • 8/22/2019 2 Unbalanced Faults

    72/87

    > Analysis of Unbalanced Fults72

    At fault point

    VA = IAZF ; IB = 0 ; IC = 0

    I0 = 1/3 (IA + IB + IC) = 1/3 IA

    I1 = 1/3 (IA + aIB + a2IC) = 1/3 IA

    I2 = 1/3 (IA + a2IB + aIC) = 1/3 IA

    I1 = I2 = I0 ------------------------- (1)Since VA = IAZF :-

    V1 + V2 + V0 = (I1 + I2 + I0) ZF

    = 3I0ZF

    V1 + V2 + V0 = 3I0ZF ------------ (2)

    F1

    POSITIVE

    SEQUENCE

    NETWORK

    N1

    F2

    NEGATIVE

    SEQUENCE

    NETWORK

    N2

    F0

    ZERO

    SEQUENCE

    NETWORK

    N0

    I2

    V2

    I0

    V0

    I1

    V1

    3ZF

    Phase to Phase Fault :- B -C Phase

  • 8/22/2019 2 Unbalanced Faults

    73/87

    > Analysis of Unbalanced Fults73

    IA

    VA

    IB IC

    VB VC

    At fault point :-

    VA = ?

    VB = VC

    IA = 0

    IB + IC = 0

    Phase to Phase Fault :- B -C Phase

  • 8/22/2019 2 Unbalanced Faults

    74/87

    > Analysis of Unbalanced Fults74

    At fault point

    VB = VC ; IA = 0; IB + IC = 0

    I0 = 1/3 (IA + IB + IC ) = 0

    I0 = 0 ---- (1)I1 = 1/3 (IA + aIB + a

    2IC ) = 1/3 (a - a2)IB

    I2 = 1/3 (IA + a2IB + aIC) = -1/3 (a - a

    2)IB

    I1 + I2 = 0 ------- (2)V1 = 1/3 (VA + aVB + a

    2

    VC ) = 1/3 (VA - VB)V2 = 1/3 (VA + a

    2VB + aVC ) = 1/3 (VA - VB)

    V1 = V2 ------------------------ (3)From equations (1), (2) and (3) the positive and negative sequence networks areconnected in parallel and the zero sequence network is unconnected.

    I1F1

    N1V1

    +veSeqN/W

    I2F2

    N2

    V2-veSeqN/W

    I0F0

    N0V0

    ZeroSeqN/W

    Phase to Phase Fault Current Level

  • 8/22/2019 2 Unbalanced Faults

    75/87

    > Analysis of Unbalanced Fults75

    For a / Fault ,assuming Z1 = Z2 :-

    I1 = -I2 = E

    2Z1IA = I1 + I2 + I0 = 0

    IB = a2I1 + aI2 + I0 = (a

    2 - a)I1 = -j3 . E

    2 Z1

    IC = aI1 + a2I2 + I0 = (a - a

    2)I1 = j3 . E2 Z1 IF(/) = 0.866 IF(3)

    E

    I1

    I2

    Z1

    Z2

    A

    B

    C

    I

    BIC

    EC

    EB

    EA

    Example : Phase to Phase Fault

  • 8/22/2019 2 Unbalanced Faults

    76/87

    > Analysis of Unbalanced Fults76

    SOURCE LINE F

    132 kV

    2000 MVA

    ZS1 = ZS2 = 8.7

    B - CFAULTZL1 = ZL2 = 10

    8.7 10

    8.7 10

    I1

    I2

    F1

    N1

    F2

    N2

    132000

    3

    Total impedance = 37.4 IB = a2I1 + aI2I1 = 132000 = 2037 Amps = a

    2I1 - aI13 x 37.4 = (a2- a) I1I2 = -2037 Amps = (-j) . 3 x 2037

    = 3529 Amps

    Phase to Phase Fault with Resistance

  • 8/22/2019 2 Unbalanced Faults

    77/87

    > Analysis of Unbalanced Fults77

    IA

    VA

    IB

    IC

    VB VC

    At fault point :-

    VA = ?

    VB - VC = IBZF

    IA = 0

    IB + IC = 0

    ZF

    Phase to Phase Fault w ith Resistance

  • 8/22/2019 2 Unbalanced Faults

    78/87

    > Analysis of Unbalanced Fults78

    At fault point

    IA = 0; IB + IC = 0 ; VB - VC = IBZF

    I0 = 1/3 (IA + IB + IC ) = 0

    I1 = 1/3 (IA + aIB + a2IC) = 1/3 (a - a

    2) IB

    I2 = 1/3 (IA + a2IB + aIC) = - 1/3 (a - a

    2) IB

    I0 = 0 ----------- (1)I1 + I2 = 0

    IB = a2I1 + aI2 + I0 = (a

    2 - a) I1

    VB - VC = (a2V1 + aV2 + V0) - (aV1 + a

    2V2 + V0)

    = (a2- a) V1 - (a2- a) V2

    but VB - VC = IBZF = (a2- a) I1ZF

    (a2- a) I1ZF = (a2- a) V1 - (a2- a) V2 V1 - V2 = I1ZF ------------ (2)

    I1F1

    N1V1

    +veSeqN/W

    I2F2

    N2

    V2-veSeqN/W

    I0F0

    N0

    V0ZeroSeqN/W

    ZF

    Phase to Phase to Earth Fau lt :- B -C-E

  • 8/22/2019 2 Unbalanced Faults

    79/87

    > Analysis of Unbalanced Fults79

    IA

    VA

    IB IC

    VB VC

    At fault point :-

    VA = ?

    VB = 0

    VC = 0

    IA = 0

    IB = ?

    IC = ?

    Phase to Phase to Earth Fau lt :- B -C-E

  • 8/22/2019 2 Unbalanced Faults

    80/87

    > Analysis of Unbalanced Fults80

    At fault point

    VB = 0; VC = 0 ; IA = 0

    V1 = 1/3 (VA + aVB + a2VC ) = 1/3 VA

    V2 = 1/3 (VA + a2VB + aVC ) = 1/3 VA

    V0 = 1/3 (VA + VB + VC ) = 1/3 VA

    V1 = V2 = V0 = 1/3 VA -------------------- (1)IA = I1 + I2 + I0 = 0 ------------------------------- (2)

    From equations (1) & (2) the sequence networks are connected in parallel.

    I1F1

    N1

    V1+veSeqN/W

    I2F2

    N2

    V2-veSeqN/W

    I0F0

    N0V0

    ZeroSeqN/W

    Phase to Phase to Earth FaultB C E with Fault Resistance

  • 8/22/2019 2 Unbalanced Faults

    81/87

    > Analysis of Unbalanced Fults81

    IA

    VA

    IB IC

    VB VC

    B-C-E with Fault Resistance

    At fault point :-

    VA = ?

    VB = (IB +IC) ZF

    VC = (IB +IC) ZF

    IA = 0

    IB = ?IC = ?IB+ IC

    ZF

    Phase to Phase to Earth FaultB -C-E with Resis tance

  • 8/22/2019 2 Unbalanced Faults

    82/87

    > Analysis of Unbalanced Fults82

    B-C-E with Resis tanceAt fault point

    IA = 0 ; VB = VC = (IB + IC)ZF

    IA = I1 + I2 + I0 = 0 --------------------- (1)

    I0 = 1/3 (IA + IB + IC) = 1/3 (IB + IC)

    IB + IC = 3I0V1 = 1/3 (VA + aVB + a

    2VC ) = 1/3 [VA + (a2 + a)VB] = 1/3 (VA - VB)

    V2 = 1/3 (VA + a2VB + aVC ) = 1/3 [VA + (a

    2 + a)VB] = 1/3 (VA - VB)

    V1 = V2 --------------------- (2)V0 = 1/3 (VA + VB + VC ) = 1/3 (VA + 2VB)

    V0 - V1 = 1/3 (VA + 2VB ) - 1/3 (VA - VB)

    = VB = (IB + IC)ZF = 3I0ZF

    V1 = V0 - I0 (3ZF) --------------------- (3)I1

    F1

    N1

    V1+veSeqN/W

    I2F2

    N2

    V2-veSeqN/W

    I0F0

    N0

    V0ZeroSeqN/W

    3ZF

    4-w ire Representat ion of/E Fau lt (1)

  • 8/22/2019 2 Unbalanced Faults

    83/87

    > Analysis of Unbalanced Fults83

    /E Fau lt (1)

    Consider an earthed source.

    Total sequence impedances to fault

    = Z1, Z2, Z0 i.e. Source + line

    EA

    EB

    EC

    C

    B

    A

    Z1, Z2, Z0

    4-w ire Rep resentation o f /E Faul t (2)

  • 8/22/2019 2 Unbalanced Faults

    84/87

    > Analysis of Unbalanced Fults84

    Sequence Networks

    I1Z1

    I2

    I0

    Z2

    Z0

    E

    3

    ZZZ

    E

    3ZZZ

    3

    Z2Z

    3

    ZZZE

    3

    )ZZ(ZE

    101

    A

    101A

    01A

    021A

    1021A

    0211

    I

    I

    I

    I

    IIIII

    I

    4 Wire Equivalent Circuit

    EA

    EB

    EC

    Z1

    Z1

    Z1

    ZN = Z0 - Z13

    10

    N

    N1

    AF

    3

    Z-ZZ

    where

    ZZ

    EII

    3 Versus 1 Fau lt Level (1)

  • 8/22/2019 2 Unbalanced Faults

    85/87

    > Analysis of Unbalanced Fults85

    Xg

    XTE

    Xg XT

    EZ1

    IF

    3

    1TgF

    Z

    E

    XX

    E

    3 Versus 1 Fau lt Level (2)

  • 8/22/2019 2 Unbalanced Faults

    86/87

    > Analysis of Unbalanced Fults86

    Z0

    IF

    1 Xg1 XT1

    E

    Z2 = Z1

    Z1

    Xg2

    XT2

    Xg0 XT0

    I

    3EF

    2Z Z1 0

    3 Versus 1 Fau lt Level (3)

  • 8/22/2019 2 Unbalanced Faults

    87/87

    LEVELFAULT3LEVELFAULT1

    ZZIF

    Z2Z3ELEVELFAULT1

    Z2Z

    3E

    3Z

    3E

    Z

    ELEVELFAULT3

    10

    01

    1111