Manual Switches(Two position)
OPERATOR`S MANUAL
(630A~1600A)This device can only professional installation, commissioning and maintenance.
Not require manual operation of all the caused losses , the manufacturers will not be held
responsible.
a) the device can only professional installation, commissioning and maintenance
b) installation, commissioning and maintenance of the device to be cut off the two-way
power (active fire control signals can cause electric shock, but also to confirm disconnect)
c) must use the Voltmeter testing to confirm the power has been disconnected
d) devices, as required reliable grounding
e) devices and power before cabinet door and interrupter cover reset
f) operated in violation of regulations could lead to electric shocks, burning or explosion!
Suggest send the instruction to final user
Technical & Service: [email protected]
Ⅵ、Common Faults and ruled out
#Read the users manual carefully before using your Manual Switches.
!Dangerous Warning
Manual switch no or unusual action, first check the following:
① switchbody and controller if in good connections,or loose ?Is correct?
② power is open ?
③ controller is in a state of manual ?
④ voltage is normal ?
⑤ switchbody and controller, main and backup power input is contrary ?
⑥ fuse is intact ?
⑦ debugging, debugging line is too long ?wire diameter is too small?
⑧ debugging, Neutral N line, phase wire and PE connect earth line is distinction ?
#Keep the users manual for your future reference.
01
General Working Conditions
04
Ⅳ.Installation and wiring
Manual switch the installation and commissioning of all the work should be professional and
understand the switching equipment staff, must consider the appropriate protective and preventive
measures, the switch of main circuit wiring without any pressure or strong power. Commissioning
should be do before installed the switch without damage identification or any other harmful envi
-ronmental impact, should check whether the transport process in the line head Loose; remove dirt
,in particular the insulation pieces of dirt, a loop linking should be paid attention Main and Backup
power in same phase, to connect the second control loop should be in strict compliance with
the wiring diagram, while paying attention to control power supply voltage; switches must be
installed a good grounding.
Ⅴ.Running before Debugging
Taking into account the physical security and the rapid switch. Commissioning handle only for
debugging purposes,user Do not use debugging handle in load operation. Before installed interrupter
device also not allowed to load operation. Try to debug handle operations at the switch. Observation
of the main contact closed, if not unusual, power-operation, to switch to observe the operation, no
abnormal after a formal operation.
630A~1600A With ACU538 controller Wiring Diagram I. General PC-class dual-supply automatically switch (Manual switch) is the latest
company Technology development of high-tech products. It is in line with
IEC60947-4 superscript , And also with "high-rise
buildings fire norms" and "Architectural Design fire norms", "emergency Lighting
Design Guide, "" civil electrical design specifications. " Product components, parts
after martial law Screening of the aging grid, finished a continuous 168 hours of
electricity a dry run, the final pass through the test load Before the factory. This is
to ensure the product's reliability and security.
Manual switch apply to AC415V, rated frequency of 50 Hz/60Hz. 250 volts DC
and the following Occasions.
The products are mainly used for the state of a load, widely applicable to the
fire, postal communications, hospitals, hotels, Urban rail transport and high-rise
buildings, industrial assembly line, television stations need electricity for the important
parts.Main power、Emergency Power can be power grids, with Self-excitation
generator sets, battery, and so on.Ge
ne
rato
r
battery+
battery-
Remote start
A1 B1 B2 A2 C0 C1 C2 a1 b1 a2 b2
LOADL1 L2 L3 N
1#voltage input
R1S1T1N1
R2S2T2N2
CONTROL MODULE
10
A
10
A
20
A
10
A
10
A
20
A
8
14 13 12 11 5 9 6 1 2 3 4
I C
lose
GN
D 1
9
1# C
lose
inpu
t
2# C
lose
inpu
t21
22 7 15
16
17
18
10
I C
lose
I 201927
28
II.Working Conditions2.1 Ambient air temperature
Ambient air temperature of -5 ℃ to +40 ℃, and a 24-hour average temperature does not
exceed +35 ℃. Around +40 ℃air temperature is above or below -5 ℃ users should consult
with the manufacturers.
2.2 Atmospheric humidity
The maximum temperature of +40 ℃ the relative humidity of not more than 50 percent,
the largest of 90 % relative humidity, ability Humid air by the impact of the sea, at a lower
temperature may allow a higher relative humidity, Occasionally the temperature under Conqeal
Dew should take special measures.
2.3 Installation Altitude
Locations of not more than 2,000 meters above sea level. For a higher altitude, taking into
account the air Xinhua strength and cooling down, in consultation with the manufacturer.
2.4 Pollution levels
Installation on grade Ⅲ
2.5 Installation sort
Installation sort Ⅳ type
2.6 Installed tilt
Products in the cabinet fixed installation, the largest inclination to ± 22.5。.
2.7 Flash Arc-distance
In AC 415V-arc distance of 80 mm. Under 125A installation can`t consider flash arc.
Installation and wiring、Running before Debugging
2#voltage input
02
2 position type ATS (630A~1600A)
Main Function
1.ON and OFF are both by one electromagnetic winding;2.The structure is simple,maintaining covenience;3. The point has great capacity,newest move contact are stable,with strong overload capacity;4.Eliminate conducting electricity of surplus part,structure simple,span long.
III. Products Instruction
MG1 MG2
CC
CC
BD
MG
LS1,LS2,LS3
A 1 B1 C0 C 1 C 2
A2 B 2 A.T.S a1 b1
a2 a3b2 b3
MG1
LS1
MG1 MG2
LS2 LS3
MG2
BD
¢1.2×1035T
Rectifier KBPC5010
Parts NameParts No .No .
1
3
2
4
Parts Model
CJX2-1210
Limit switch LXW20-11
630
16 16 16 16 1650 50 50 50 50
2500 2500 2500 2500500 500 500 500 50015 20 25 25 25
800 1000 1250 1600
Main Power
Ba
cku
p P
ow
er
Auxiliary switch
LoadAC contactor
Closing Coil
Model
Operating Voltage
Operating Current(A)
Max Instantaneous Current(KA)
Machine
ElectricUse Life
Max operate cycle(Second/Times)
630A~1600A Internal wiring Diagram
630A~1600A Manual switch Technical character
2500
Products Brief
ModelDimension
630
510
620
600
750
470
580
560
710
280 210 245
90
90
90
90
130
30(a)
40(a)
45(a)
55(a)
75(b)
---
---
---
40
40
12
14
1600
800
1000
1250
AGFED UB R
C
3P 4P 3P 4P
630A~1600A Manual switch appearance installation dimension
630A~1600A manual adjustment, the use of special operations handle,along with closing direction
of force to promote and hear the closing lock in "ge" of a sound,can open-operation, otherwise the
closing is not in place, the main circuit Lack of phase phenomenon, check whether the main contacts
in place under up and down closing signs to determine, as shown below:
ATSE
Switchbody up closing label
Main power closing Main power
closing
Backup power closing
Backup power closing
Main
clo
sing p
ositio
n
Back
up c
losin
g p
ositio
n
Switchbody dowm closing label
Closing status Indication
Right position
Abnormity position
03
Products Brief
1
2
A
4- 14
B
4
5
6A
E1600A
=85
1600A
=75
1600/4P-25mmother -20mm
A
C
F
D
U
6- U
35
15
4- U
R
G
(b)(a)
G
2- U
3
220V 50mm
380V 80mm
*Flash arc distance 1.Control Circuit
Terminal block
2.Manual operating
handgrip faucet
3.Mechanical indicator
of switch state
4.Mechanical indicator
of switch state
5.Load Bus
6.Standby power Bus
AC220V/240V(160V~280V)
Pole
Weight(Kg)
3P 4P
37 42.5
3P 4P
39 46
3P 4P
41 48
3P 4P
48 57
3P 4P
56 67