2 Earthing Grounding

70
This document is the exclusive property of Alstom Grid and s hall not be transmitted by any means, copied, reproduced or modified without the prior written consent of Alstom Grid Technical Institute. All rights reserved. GRID Technical Institute Syst em E art hing

Transcript of 2 Earthing Grounding

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 1/70

This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior 

written consent of Alstom Grid Technical Institute. All rights reserved.

GRID

Technical Institute

System Earthing

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 2/70

> System Earthing 2 

System Earthing

Earth faults :- 70

90% of all faults.

IF 

E A 

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 3/70

> System Earthing 3

System Earthing

Earthing method determines :-

Fault current IF 

Damage caused

Steady state overvoltages

Transient overvoltages

Insulation requirements

Quantities available to detect faults

Type of Protection

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 4/70

> System Earthing 4

Earthing Method

Solid / Low Z High Z

IF High Low

Overvoltages in Low High

Sound Phases

Damage High Low

Cost of Insulation Low High

Low Voltage Systems For Safety

Medium Voltage Systems To limit currentcost of insulation

acceptable

High Voltage & To limit cost

EHV Systems of insulation

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 5/70

> System Earthing 5 

Methods of Earthing In Common Use

Solid or Direct Earthing

Resistance Earthing

Reactance Earthing

Resonant or Petersen Coil Earthing

Insulated Earth

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 6/70

> System Earthing 6 

System Earthing

Solid

Lowest System Z0 

IF High

- Damage

- Easy E/F Protn.

No Arcing Grounds IF >> ICHARGE 

Lowest Overvoltages

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 7/70> System Earthing 7 

System Earthing

Reactance

Lower IF 

Higher Transient Overvoltages

Cheaper than resistance at high volts

Overvoltages during E/Fs

0.8 1 x VØ/Ø 

Not often used except as tuned reactor 

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 8/70> System Earthing 8 

System Earthing

Petersen Coil

XE    XCHARGING 

Arcing faults self extinguishing

- Good for transient faults

XE needs changing if XC alters

Overvoltages during E/Fs VØ/Ø 

Insulation important

Restricts use of auto-transformersDiscriminative E/F protection difficult

Tuned

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 9/70> System Earthing 9

System Earthing

Resistance

Reduced IF 

Reduced transient overvoltages

Not self extinguishing but E/F easier todetect

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 10/70> System Earthing 10 

System Earthing

Unearthed

Insulated

IF Capacitive

Can be self extinguishing if IF small

Overvoltages during E/Fs = VØ/Ø 

Arcing faults likely - high transientovervoltages

Insulation important

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 11/70> System Earthing 11

System Earthing

660 V Solid - Safety

Insulated - Special cases where continuityof supply required

660 V 33 kV Resistance or reactance normally used

Solid - When IF is low

Resistance - IF limited to IFL 

Reactance - IF(E/F) limited to IF(3Ø)

Petersen - Overhead lines. LightningCoil

> 33 kV SolidOvervoltages more important (insulation)

Directly Coupled Resistance - Most common

Generators Solid and - Not recommended

Reactance (High IF

)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 12/70> System Earthing 12 

System Earthing

Generator - Transformer Units

IF ~ 200 300 A

IF ~ 10 15 A

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 13/70> System Earthing 13

Low Voltage System Earthing

Safety :-

Power system neutral solidly earthed at transformer.

Metallic tools and appliances solidly earthed.

Sensitive protection by :-

RCD’s :- Residual current devices

ELCB’s :- Earth leakage circuit breakers

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 14/70> System Earthing 14

Earth Fault Hazard

ZF = Fault impedance

ZP = Human body impedance

ZE = Environmental impedance

VP = Case / earth potential

ZF 

ZE 

VP

 

Z

Unearthed

 Appliance

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 15/70> System Earthing 15 

Earth Fault Hazard

ZF = Fault impedance

ZP = Human body impedance

ZE = Environmental impedance

VP = Case / earth potential

EFP

P/NH

ZZZ

Z . E V

-:earthprotectiveWithout

ZF 

ZE 

VP 

Z

Unearthed

 Appliance

IF 

VH 

RCD for High ZF 

Fuses for 

High IF 

Protective Earth Conductor 

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 16/70> System Earthing 16 

Unearthed L.V. Winding

NormalConditions

H.V.

V

v

L.V.

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 17/70> System Earthing 17 

Unearthed L.V. Winding

H.V.

xV

yv

L.V.

VF 

VF = xV + (1 - y)v

Inter-winding fault ‘F’

causes dangerous risein L.V. voltage 

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 18/70> System Earthing 18 

Breakdown Between HV and LV Windings

1730V

A2 

B2 C2 

N

c2  b2 

a2 254V

n

3000 / 440 V Transformer 

Normal voltage conditionsNeutrals earthed or unearthed

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 19/70> System Earthing 19

Breakdown Between HV and LV Windings

Voltage conditions with breakdownbetween HV and LV at point X on phaseLV neutral unearthed

1730V

850V

A2 

B2 C2 

xH x

n

c2  b2 

a2 

xL

755V

254V

1009V

95V

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 20/70> System Earthing 20 

Hand to Hand Resistance of Living Body50Hz AC (Freiburger 1933)

6000

5000

4000

3000

2000

1000 

0 100 200 300 400 500 600

Volts 

   R  e  s   i  s   t  a  n  c  e  -   O   h  m  s

Very Dry Skin 

Very Moist Skin 

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 21/70> System Earthing 21

Effects of Body Current

1mA Can be felt

> 9mA Cannot let go

15mA Threshold of cramp

30mA Breathing difficultRise in blood pressure

50mA Heart misses odd beat

50 200mA Heavy shock

Unconsciousness

> 200mA Reversible cardiac arrest

Current marks

Burns

Eff f V i V l f B d C

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 22/70> System Earthing 22 

Current at 50Hz Duration Physiological effects on humans

to 60Hz r.m.s. of shock

value mA

0-1 not Range up to threshold of perception.critical Electrocution not felt.

1-15 not Range up to threshold of cramp.

Critical Independent release of hands from object gripped no longer possible. Possibly

powerful and sometimes painful effects on muscles of fingers and arms.

15-30 minutes Cramp-like contraction of arms. Difficulty in breathing. Rise in blood pressure.

Limit of tolerability.

30-50 seconds Heart irregularities. Rise in blood pressure. Powerful cramp-effect. to minutes

Unconsciousness. Ventricular fibrillation if long shock at upper limit of range.

less than No ventricular fibrillation. Heavy shock.

50 to a cardiac cycle

few hundred

above one Ventricular fibrillation. Beginning of electrocution in relation to heart phase not

cardiac cycle important. (Disturbance of stimulus conducting system?)Unconsciousness. Current marks.

less than Ventricular fibrillation. Beginning of electrocution in relation to heart phase

cardiac cycle Important Initiation of fibrillation only in the sensitive phase.

Above (Direct stimulatory effect on heart muscle?) Unconsciousness. Current marks

few hundred

over one Reversible cardiac arrest. Range of electrical defibrillation. Unconsciousness.

cardiac cycle Current marks. Burns

Effects of Various Values of Body Current

B d C / Ti d S i

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 23/70

> System Earthing 23

Body Current / Time and Security

10,000

1,000

100

10 0.1 1.0 10 100 1000

Current (mA) 

Time

(mS) 

Thresholdof 

Perception 

Thresholdof 

Let Go 

Let Go Hold On 

IEC SecurityCurve 

Thresholdof 

Fibrillation 

E thi I d Aff t T h & St P t ti l

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 24/70

> System Earthing 25 

Earthing Impedance Affects Touch & Step Potentials

Don’t forget

communicationscables etc.entering S/S ! 

Surface

True

Earth

RE Touch

VH VH 

Step

E

RF IF 

RG 

IF 

IF 

True EarthRG 

RG' = f(Distance)

d

!

'RRR

'R E V

GFE

GH

I t t d St (Zi Z ) E thi T f

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 25/70

> System Earthing 26 

Interconnected Star (Zig-Zag) Earthing TransformerSingle Earthing Resistor

I

2I 

I

3I

3I Earth

Fault

I IITransformer Insulated

for Line Voltage

Resistor Insulated

For System Phase

Voltage

3I2II

I II

I t t d St E thi T f

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 26/70

> System Earthing 27 

Interconnected Star Earthing Transformer Three Earthing Resistors

2I 

I

I

3I

3IEarth

Fault

I II

3I2II

I II

I IIResistors

3I

Note:- Resistors tobe insulated for linevoltage and to have 3times the ohmic valueof a single neutralresistor  

Di l t f N t l f E th

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 27/70

> System Earthing 28 

Displacement of Neutral from Earthduring an Earth Fault

Va 

Vb Vc 

ZE 

N

Z

G

Z

Z

IF 

Va 

Vb Vc 

G

NZZ

Z . V Z V

E

EaNEFGN

E th F lt S t ith I l t d E th

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 28/70

> System Earthing 29

Earth Fault on System with Insulated Earth

Va 

IF 

Ic 

Ib Vb Vc N 

-jXc 

-jXc  -jXc 

c

ab

 jX-V

c

ac

 jX-

V

c

ac

 jX-

V

c

ab

 jX-

V

E th F lt S t ith I l t d E th

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 29/70

> System Earthing 30 

Earth Fault on System with Insulated Earth

Vab Vac 

Va 

Vb Vc N 

IF 30 30 

bc

ab -  jX-

Vc

ac

 jX-

V

cc

ac -  jX-

V

currentchargingnormalx3  jX-

3V 

 jX-

 jX-

c

aNc

ac

c

abF

currentchargingnormalx3 

X

V . 3 

 jX-

 jX-

V - 

currentchargingnormalx3 XV . 3 

 jX-V 

 jX-V - 

c

cc

c

ca

c

acc

cbb

cac

cabb

Earth Fault on System

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 30/70

> System Earthing 31

Earth Fault on Systemwith Resistance Earthed System

Va 

IF 

Vb Vc 

-jXc 

G a 

-jXc  -jXc RE 

a, G  a, G 

c

ac

 jX-

V

c

ab

 jX-

V

E

aN

R

V

Earth Fault on System

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 31/70

> System Earthing 32 

Earth Fault on Systemwith Resistance Earthed System

Vab Vac Va 

Vb 

Vc 

-Ib -Ic 

IF 

bc

ab -  jX-

V

cc

ac -  jX-

V

E

aNR

V

normalx3 X

V 3 

normalx3 X

V

 3 

c

cc

c

bb

charging current 

charging current 

Earth Fault on System with Resonant

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 32/70

> System Earthing 33

Earth Fault on System with Resonantor Petersen Coil Earthing

Va 

IF 

Vb Vc 

-jXc 

a,G 

-jXc  -jXc 

a, G  a, G 

-jXL c

ac jX-V

c

ab jX-V

LaN jXV

c

abb

 jX-

V -

Earth Fault on System with Resonant or Petersen

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 33/70

> System Earthing 34

Earth Fault on System with Resonant or PetersenCoil Earthing

Vab Vac 

Va 

Vb Vc N  -I

-Ib c

c

ac -  jX-

V

b

c

ab -  jX-

V

L

aN jX

V

L

aN jX

V

cbL

aNL

aN 

cbF

  jX

V if  0 

 jX

V - - 

3

X X 

2jX

3.3 

2jX

3.3 

 jX

V tuningperfectFor  c

L

ccL

/N

Sequence Impedances

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 34/70

> System Earthing 35 

Sequence Impedances

ZL1 X1 

X

ZT1 ZG1 P

-jX'C1 -jXC1 Ea 

N1 

Generator 

Generator 

Transformer 

Transmission Line

Fault

Capacitance of 

the transmission

system

C'C

ZE  Z'E 

Positive Phase-Sequence Network :-

Sequence Impedances

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 35/70

> System Earthing 36 

Sequence Impedances

Negative Phase-Sequence Network :-

X2  ZL2 ZT2 ZG2 P2 

-jX'C2 -jXC2 

N2 

ZL0

 X0 

ZT0 ZG0 

3ZE 

P0 

3Z'E  -jX'C0 -jXC0 

N0 

Zero Phase-Sequence Network :-

Fault Currents and Voltages Analysis of Single

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 36/70

> System Earthing 37 

Fault Currents and Voltages Analysis of SinglePhase to Earth and Double Phase to Earth Faults

The following analysis relates to the system shown in Figure 7.

Let Z1, Z2 and Z0 be the system sequence impedances in the fault path.

Let Z2 = K2Z1 and Z0 = K0Z1.

For a phase to earth fault :

I1 = I2 = I0 = Ea/Z1 + Z2 + Z0 

= Ea/Z1 (1 + K2 + K0)

Fault Currents and Voltages Analysis of Single

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 37/70

> System Earthing 38 

Fault Currents and Voltages Analysis of SinglePhase to Earth and Double Phase to Earth Faults

For a phase to phase to earth fault :

)KKK(KZ

K.E- 

ZZ

Z . 

)KKK(KZ

K.E- 

ZZ

Z . 

KK

KK

 1Z

ZZ

ZZ Z

02021

2a

02

210

02021

0a

02

012

02

02

1

a

02

02

1

a1

 

 

 

 

Fault Currents and Voltages Analysis of Single

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 38/70

> System Earthing 39

Fault Currents and Voltages Analysis of SinglePhase to Earth and Double Phase to Earth Faults

Also :

V1 = Ea - I1Z1; V2 = -I2Z2 = -I2K2Z1; V0 = -I0Z0 = -I0K0Z1

Ia = I1 + I2 + I0; Va = V1 + V2 + V0 

Ib = a2I1 + aI2 + I0; Vb = a2V1 + aV2 + V0 

Ic = aI1 + a2I2 + I0; Vc = aV1 + a2V2 + V0

From all these equations it is possible to calculate the faultcurrents and voltages at the fault location in terms of the phasesequence impedances of the system. The values of these

currents and voltages are shown in Table 2.Currents have been expressed in terms of the three phase faultcurrent where I3Ø = Ea/Z1

Sequence Connections for Phase to Earth Fault

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 39/70

> System Earthing 40 

-jX'C0 

X0  3Z'E ZT0 ZL0 

Sequence Connections for Phase to Earth Fault

P2 N1 

P1 

Z0 Z2 

Z1 

-jX'C1 -jXC1 Ea 

X1 ZL1 ZT1 ZG1 

-jX'C2 

-jXC2 

X2  ZG2 ZT2 ZL2  P0 N2 N0 

I2  I0 

I1 

Phase to Earth Fault

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 40/70

> System Earthing 41

Phase to Earth Fault

302

a1

3

0211a

101100000

121122222

111

02110121021021

 . )KK(1

Z

-:pointsametheatfaultaFor 

KK1Z

3E 3 

ZK- ZK- Z- V

ZK- ZK- Z- V

Z-E V

KK1ZE 

ZKZKZE 

ZZZE 

Phase to Earth Fault

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 41/70

> System Earthing 42 

Phase to Earth Fault

a02

022

cc

a02

022

b

0221021

ab

022

11a2

10112111a2

0212

b

E . K K 1

K Ka a

 - E V

E . K K 1

K aK a

 - E 

K aK a Z . )KK(1Z

E - E 

K aK aZ - Ea 

ZK - ZK-a Z - Ea 

V aV Va V

Phase to Earth Fault

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 42/70

> System Earthing 43

Phase to Earth Fault

a02

0

a02

0acb

02

02acb

a

02

022

022

cb

caRES

E . )K K 1(

K3 

E . )K K 1(

K3 - E E E 

K K 1

2K K 1 E E E 

E . K K 1

K Ka a K aK a

 - E E 

V Vb V V

Sequence Connections for Phase

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 43/70

> System Earthing 44

Sequence Connections for Phaseto Phase to Earth Fault

P2 

N1 

P1 

Z0 

Z2 Z

-jX'C1 -jXC1 Ea 

X1 ZL1 ZT1 ZG1 

-jX'C2 

-jXC2 

X2  ZG2 ZT2 ZL2 

P0 

N2 

-jX'C0 

X0  3Z'E ZT0 ZL0  N0 

I

I0 

I1 

Steady-state Fault Currents and Voltages for

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 44/70

> System Earthing 45 

Steady state Fault Currents and Voltages forPhase-to-Earth and Double-Phase to Earth Faults

a0202

02a

30202

2ares

30202

202

c

30202

20

22b

302

a

E . KK K K

KK3 0 V

 KK K K

3K- toEqual 

. KK K K

)a-a(K )1(aK 0 

. KK K K

a)-a(K )1(aK 0 

0 . K K 1

e)-c-(bfaultearthtophaseDouble e)-(afaultearthtoPhase 

Steady-state Fault Currents and Voltages for

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 45/70

> System Earthing 46 

Steady state Fault Currents and Voltages forPhase-to-Earth and Double-Phase to Earth Faults

E .. K K 1

K3 V

VtoEqual VtoEqual V

0 E K K 1

1 K E V

VtoEqual V-toEqual V

0 E K K 1

K Ka a - E V

0 E K K 1

K Ka a - E V

a02

0res

acca

bc02

2bcbc

ababa02

022

cc

a02

022

bb

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 46/70

> System Earthing 47 

122 Z

Z K

 

Independent of earthing method

Normally K2 = 1

Close to power stations with synchronousgenerators :-

K2  up to 1.4

X2 for cylindrical rotors = Xd"

for salient poles = Xd" to 1.4 Xd"

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 47/70

> System Earthing 48 

1

00

Z

Z K

 

Depends on method of earthing

Relative values of transformer, generator and line impedances

Transformer winding arrangement

Amount and angle of ZLINE 

K0 has an angle

K0 ranges from for unearthed system to 0.2 for solid earthing andfault close to a power station.

Line

XS1 = 25%

XS2 = 25%

XT1

= XT2

= XT0

=

7%

0.219 

32

7 25

X

X

1

0

Variation of Healthy Phase Voltages Due to

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 48/70

> System Earthing 49

Variation of Healthy Phase Voltages Due toDifferent System Earthing for an A-E Fault

abab

a/2ba

2

b

ba

2

b

a/5ba

2

b

a/2ba

2

b

2

B0

E E E - E 

E E E 411

4aa - E 4

E E 111

1aa - E 1

E E E 0.5110.50a - E 0.5

E E E 11

aa - E 0

1K 2Tableinformula 

fromcalculatedVK

Variation of Healthy Phase Voltages Due to

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 49/70

> System Earthing 50 

Variation of Healthy Phase Voltages Due toDifferent System Earthing for an A-E Fault

Ea 

G

V'b 

Eb 

V"b 

V'c 

Ec 

V"c 

Effectively earthed systems

K = 0

K = 0.5

K = 1

K = 4

K =  

Non-effectively earthed

systems

Healthy Phase Voltages during Earth Faults

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 50/70

> System Earthing 51

Healthy Phase Voltages during Earth Faults

a0

02

bb

122

a02

022

bb

E K2

Kaa E V

01 /ZZ K  Assuming

E KK1

KaKa

 - E V

K0 = 0.5

Solid earthing; Fault near power station

VS.P. < VØ/N rated (- 0.95 VØ/N)

K0 = 1.0

Solid earthing; Fault remote from power station VS.P. = VØ/N rated

Healthy Phase Voltages during Earth Faults

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 51/70

> System Earthing 52 

ea y ase o ages du g a au s

K0  4.5

- Solid earthing; Remote fault; Long line

ZL0 /ZL1 can be 4.5

- Also possible with low reactance earthing

- VS.P. = 0.75 VØ/Ø rated with K0. = 4

K0 > 1.0

VS.P.

> VØ/N

rated

Healthy Phase Voltages during Earth Faults

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 52/70

> System Earthing 53

y g g

Effectively Earthed Systems

British definition (BS 162 : 1961) :-

VS.P. > 80% of VØ/Ø rated

Note :- VS.P. > 0.8 VØ/Ø rated

is possible on solidly earthed systems

Overvoltage relays should not be connectedØ/N or may operate for earth faults.

American definition :-

X0 /X1  3 and R0 /X1  1

K0 = high gives non effectively earthed systeme.g. For Resistance

Petersen Coil

Insulated VSP = VØ/Ørated Z0     } 

VØ/Ø during Earth Fault

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 53/70

> System Earthing 54

/ g

bc02

2bcbc E 

KK1

1 K E V

If generator AVR is not in service :-

Id"

Id'

Id 

Few Seconds 

I  Z2 and Z0 fixedZ1 varies from Xd" to Xd, i.e. increases

If K2 = Z2 /Z1 varies from 1 to 0.2

K0 = Z0 /Z1 varies from 3.0 to 0.6

Vbc = Ebc 

bc

bc

bc02

2bcc'b'

E0.556 

E0.60.21

1.0-0.2 1 

E . KK1

1 K E V

Variation of Healthy Phase Voltages for an Earth Fault due

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 54/70

> System Earthing 55 

to changes of K2 and K0 during the Fault

Vc.and Vd are the healthy phase voltages at fault instant with K2 =1.0 and K0 = 3.0.

Vc' and Vb' are the healthy phase voltages a few seconds after faultoccurs with K2. = 0.2 and K0 = 0.6.

Ea 

Vb'V

c'

Eb Ec 

Vb

 Vc

 

Figure a

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 55/70

> System Earthing 56 

Z1  Z2 

Ea  C1  C0  V0 3Z

E'

Z0 i

g

Figure b

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 56/70

> System Earthing 57 

g

Ea 

V0 arc restrikes

arc extinguishes 

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 57/70

> System Earthing 58 

VTRANSIENT 

Neutral to Earth 

Faulted Phase 

Resistor kWCharging kVA 

(% EØ/N PEAK)

Unfaulted Phase 

400

300

200

100 

.2 .4 .6 .8 1.0 2.0 

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 58/70

> System Earthing 59

Z1  Z2 

C1  C0 3RE 

Z0 i

Ea 

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 59/70

> System Earthing 60 

V0 

45º

i

0.7E pk

pk0

0E

t/-pk.e0

0e

E0.06 V

-:7.5msafter 

w1 C3R where

E0.7 V

wC

1 3RIf 

  

  

Sound Phase Currents During an Earth Fault (1)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 60/70

> System Earthing 61

IF 

Source

6

6

5

1

1

1

1

1

1

1

1

3

33

63

LoadX Y1

1

1

5

Sound Phase Currents During an Earth Fault (2)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 61/70

> System Earthing 62 

I1 

I

2

 

I0 

ZX1 

ZX2 

ZX0 

IX1 

IX2 

IX0

 

ZY1 

ZY2 

ZY0 

E

Sound Phase Currents During an Earth Fault (3)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 62/70

> System Earthing 63

I1 = I2 = I0 = IX0 + I Y0 

if ZX0 = Z Y0 then IX0 = I Y0 

IF = 3I0 = 6IX0 ; Iya = I Yb = I Yc = IX0 = I Y0 = IF/6 

IXa = IX1 + IX2 + IX0 = 5IX0 = 5IF/6 

IXb = a2IX1 + aIX2 + IX0 = -I0 + IX0 = -IF/6

IXc = -IF/6 

Parallel Generators (1)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 63/70

> System Earthing 64

G3  G4 G1  G2 

3  E/F 

Only 1 machine is earthed :- 

Parallel Generators (2)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 64/70

> System Earthing 65 

Consider the current in G1

for :- (i) Earth Fault

(ii) 3Ø Fault

Let

ZG11 = ZG21 = ZG31 = ZG41 = 0.244 p.u.

ZG12 = ZG22 = ZG32 = ZG42 = 0.124 p.u.

ZG10 = ZG20 = ZG30 = ZG40 = 0.05 p.u.

Earth Fault (1)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 65/70

> System Earthing 66 

Sequence Networks :- 

N1 EG 

ZG11 

ZG21 

ZG31 

ZG41 

IG11  IG12  IG10 ZG12  ZG10 

ZG22 

ZG32 

ZG42 F1 N2 IF1  F2 N0 IF2  F0 IF0 

0.05p.u.

IF1  IF2  F0 IF0 

0.244p.u.

0.244p.u.

0.244p.u.

0.124p.u.

0.124p.u.

0.124p.u.N1 

1p.u.

0.244p.u. 0.124p.u.

Earth Fault (2)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 66/70

> System Earthing 67 

N1 

0.061

1p.u.0.031 0.05

F1 N2 IF1  F2 N0 IF2  F0 IF0 

IF1 = IF2 = IF0 = 1 = 1 = 7.04 p.u.0.061 + 0.031 + 0.05 .142

IF = 3IF1 = 21.12 p.u.

IG11 = IF1 = 1.76 p.u. IG12 = IF2 = 1.76 p.u. IG10 = 7.04 p.u.4 4

  IG1 = IG11 + IG12 + IG10 = 1.76 + 1.76 + 7.04 = 10.56 p.u.

3Ø Fault

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 67/70

> System Earthing 68 

1p.u. 

ZG11 = .244

IF1  F1 

IG11 

ZG21 = .244

ZG31 = .244

ZG41 = .244

N1 

IG11 = 1 = 4.1 p.u.

.244

  IG1 = 4.1 p.u.

 Thermal Stress

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 68/70

> System Earthing 69

Stress3x6.55 

Stress3x4.1

10.56

 StressE/F 

StressThermal

p.u.4.1 

p.u.10.56 

2

2

)(3G1

(E/F)G1

 

Methods of Neutral Earthing (1)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 69/70

> System Earthing 70 

Aspect Solid Resistance Resistance & High value Low value Tuned Insulated

reactance reactor reactor reactor 

Normal Suitable for Suitable for Suitable for phase Suitable for Suitable for If used for Suitable for line

insulation phase voltage phase voltage voltage line voltage for phase voltage operation with voltage for longcontinuously continuously continuously long periods continuously one line earthed

for long periods

insulation must

be suitable for 

line voltage

Over voltages:

(a) Initiated by Not excessive Not excessive Not excessive provi- Can be very high Not excessive Not excessive if Arcing ground

faults, ding all three phases e.g. neutral no mutual coup- can give very

switching, etc are made or broken inversion ling between zero high voltagessimultaneously & positive seq-

uence networks

(b) Travelling Negative In general, “ Full reflection at Full reflection at Full reflection at Full reflection

waves reflection negative neutral neutral neutral at neutral

reflection at

neutral

Protection:(a) Automatic No difficulty No difficulty No difficulty, normal Extremely diffi- No difficulty By using special Extremely

segregation normal methods normal methods methods can be cult if more than normal methods technique can be difficult

of faulty zone can be used can be used used one zone can be used done satisfac-

involved torily

(b) Travelling Diverters rated In general, In general, diverters Diverters rated In general, Diverter rated Diverters rated

waves for phase volts diverters rated rated for line volts for line volts are diverters rated for for line volts are for line volts

are suitable for line voltage are essential essential line volts are essential are essential

are essential essential

Methods of Neutral Earthing (2)

7/29/2019 2 Earthing Grounding

http://slidepdf.com/reader/full/2-earthing-grounding 70/70

Aspect Solid Resistance Resistance & High value Low value Tuned Insulated

reactance reactor reactor reactor 

Earth-fault

Current

(a) Value Highest value High value High value Negligible High value Negligible Capacitive if 

small may be

self exting-uished

(b) Duration Few seconds Few seconds Few seconds Long time Few seconds Few seconds or In general long

continuous, time

depending on

method of 

application

(c) Effect on Electromagnetic Electromagnetic Electromagnetic Electrostatic Electromagnetic If used for Electrostatic

communica- interference interference interference interference interference may running contin- interference

tion circuits may necessi- depending on depending on necessitate current uously with one

tate current degree of degree of limitation limitation line earthed

limitation limitation requires partic-

ular consideration

Harmonic No limitation Partial limitations Partial limitation of Limits all Appreciably limits Appreciably limits -

currents in of harmonic of harmonic harmonic currents harmonic all harmonic all harmonic

neutral currents currents currents currents currents

Time rating of 30 sec. 30 sec. 30 sec. Continuous 30 sec. 30 sec. or -

neutral apparatus continuous

General remarks Maximum In general use In general use where Confined mainly Cheaper than Best continuity Some applica-

disturbance to a source neutral is to protection of resistor at very of supply. Can tions on short

system not available generator on high voltages be a danger to feeders in