ITD Inline Tension Disconnect Switch
15-38 kV Hookstick SwitchesProduct Bulletin 1VAG201901-DB
-
7/31/2019 1VAG201901-DB_ITD
2/4
ApplicationThe ABB ITD Inline Tension Disconnect Switch is a single-phase,hookstick-operated switch used to manually switch de-energized orparallel circuits of overhead distribution lines rated 15 through 38 kV,150/200 kV BIL. The ITDs are installed directly in the line and are
used to sectionalize the circuit. Switches are selected by continuouscurrent and voltage ratings.
OperationAll ABB ITD disconnect switches include loadbreak hooks. Use theappropriate loadbreak device to open the switch under load. The pull-ring can be utilized for easy opening and ice breaking. The hook por-tion of the contact-casting matches the blade latch for positive closure.
Design Features
Insulators
Silicone insulator provides extra leakage dis-tance and BIL ratings to ensure inline
switches are not the flashover point
Blade Design
Copper blades with stainless steel shoulder
pins. Standard blade opening is 90; 160with stop pin removed
Loadbreak Hooks
Galvanized steel for corrosion protection,to be used with loadbreak tool
Terminal Options
1. Standard two-hole NEMA tin-plated pad2. Optional two-piece parallel groove
terminal
Mounting
Inline
Ordering Instructions
- 2 -
Description Code Definition
SWITCH TYPE T Type ITD Switch
MAX kV, BIL3 38 kV, 200 kV BIL Non-Loadbreak
5 27 kV, 150 kV BIL Non-Loadbreak
BLADE STOP
N No stop
A 90 stop
B 160 stop
C 90 latch *** Not yet available, Call factory
TERMINAL CONNECTORS
C Two-piece tinned parallel groove clamshell (#2-500 MCM)
D Double eyebolt terminal (#2-350 MCM)
N Two-hole NEMA pad - standard
UNUSED N Space holder for future options
UNUSED N Space holder for future options
CONTINUOUS CURRENT6 600 amperes
9 900 amperes
DESIGN SUB 000 First Design
Choose one character from each description. There should be a total of 10 characters.
Example: To purchase a standard non-loadbreak ITD Inline Tension Disconnect Switch, the catalog code would be: T1NNNN6000
-
7/31/2019 1VAG201901-DB_ITD
3/4
- 3 -
Description
AVAILABLE RATINGS
Maximum
Voltage
BIL
(kV)
Continuous
Current
Peak Withstand
Current
Non-loadbreak 15 38 kV 150/200 600, 900 A 65 kA
DescriptionMaximum
Voltage
BIL
(kV)
Creep
(in)
Strike
(in)
Non-loadbreak 15 kV 150 23.2 10.5
Non-loadbreak 27 kV 150 23.2 10.5
Non-loadbreak 38 kV 200 33.5 15.0
.63[16]
.63[16]
1.75[44]
1.25[32]
ACCEPTS 1/2" BOLTS
.56[14]
INSULATOR SHEDDESIGN WILL VARY,SHED MAX DIA WILLBE 3.75
.630 DIACLEVIS PIN
COTTERKEY
.690 DIA HOLE3.16[80]
.62[16]
kV
Class
BIL
(kV)
Unit Dimensions (in)
Dry ArcA B C D
15 & 27 150 17.0 12.5 17.0 28.0 11.4 min
15 & 27 200 21.7 17.2 21.7 32.7 15.2 min
38 200 21.7 17.2 21.7 32.7 15.2 min
kV
Class
BIL
(kV)
Metric Unit Dimensions (mm)
Dry ArcA B C D
15 & 27 150 432 318 432 711 11.4 min
15 & 27 200 551 437 551 831 15.2 min
38 200 551 437 551 831 15.2 min
Type ITD Unit Dimensions
-
7/31/2019 1VAG201901-DB_ITD
4/4
1VAG201901-DB
Rev.B
October2005
Copyright20
05ABB.Allrightsreserved.
ABB Inc.406 Banner Ave.Greensboro, NC 27401Tel: +1-336-275-7310www.abb.com/mediumvoltage