Electrical arc short circuits in metal clad switchgear may occur for many different reasons.

defective or ageing insulating materials

poor bus or cable connections

poor maintenance

human error

ingress of moisture, dust or vermin

abnormal service conditions

Page 4: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Arc FaultEffects and Consequences

ENERGY RELEASED BY ARC FAULTENERGY RELEASED BY ARC FAULT

PRESSURE

RISE

TEMPERATURE

RISE

VISUAL & ACCOUSTIC PHENOMENA

EFFECTS OF FAULT ARC

CONSEQUENCES FOR PLANT

MECHANICAL STRESSING OF ENCLOSURES

THERMAL STRESSING, MELTING, FIRE

VAPOURISATION

CONSEQUENCES FOR PERSONNEL

SHOCK WAVE, FLYING DEBRIS,

OPENING PANELS

U/V BURNS & EJECTION OF

FLAMES & HOT GASES & SMOKE

Page 5: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Switchgear FailureEffects and Consequences

Page 6: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Switchgear Internal FaultExample

FAULT TIME

PROTECTION

TRANSFORMER

2 secs

OC-relay

110/22 kV

30 MVA

Page 7: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Switchgear Internal FaultExample

FAULT TIME

PROTECTION

TRANSFORMER

0.07 secs

Arc protection

110/22 kV

30 MVA

Page 8: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Variable Speed DriveFault Example

PROTECTION

TRANSFORMER

Earth leakage

22 kV / 690V

Water CorporationWestern Australia

At approximately 0800 hrs on 25/2/07  No.2 VSD failed at Tamworth Pumping Station WA. The PSN electrician was called out to the fault later that same morning and found the main switch

compartment of the drive badly damaged.

The extent of damage is quite severe and was contained to the main switch compartment of the

variable speed drive.

The majority of damage appears to have been originated from the VSD main switch, then

spreading upon explosion to the upper and rear of the drive and also externally through the

ventilation ducts.

Page 9: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Variable Speed DriveFault Example

The earth leakage protection on the #2 VSD 22kV / 690V feeder tripped.

The O/C protection also detected a phase fault condition.

#2 22kV / 690V  Transformer circuit breaker was found to be in the OFF position.

Judging by the extent of the damage the protection clearly did not respond quickly

enough.

Page 10: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Variable Speed DriveFault Example

Page 11: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Variable Speed DriveFault Example

OPERATOR HAZARD IN ADJACENT CORRIDOR

Page 12: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Variable Speed DriveFault Example

1S20 ARC FAULT PROTECTION INSTALLED AFTER EARLIER FAULT

Page 13: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Variable Speed DriveFault Example

SUBSEQUENT FAULT

As a result of this incident, RMS 1S20 Arc Fault Monitors and 1S30 Arc Flash Sensors

were installed.

Subsequently several months later another incident occurred, this time due to the failure

of the IGBT board.

As a consequence, the arc sensors were triggered by tripping the 22kV circuit breaker

and as can be seen by the photos the damage was insignificant.

1S30 ARC SENSOR

ARC FAULT

Page 14: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Variable Speed DriveFault Example

SUBSEQUENT FAULT

ARC FAULT

Page 15: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Arc Fault Monitor

For moderate arc fault currents the trip

time of the over-current stage will be too slow:

For very low arc fault currents the

instantaneous trip stage of a standard

over-current relay cannot be set low

enough.

Page 16: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Arc Fault Monitor

The degree of damage caused by arcing

depends principally on the duration of the arc.

~100ms Arc Fault Duration

The switchgear needs to be checked & the

insulation resistance measured before power

can be re-established.

~200ms Arc Fault Duration

The power supply will be interrupted; the

switchgear must be checked; power is re-

established only after minor repairs.

Page 17: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Arc Fault Monitor

~100ms Arc Fault Duration

Page 18: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Arc Fault Monitor

The degree of damage caused by arcing

depends principally on the duration of the arc.

~500ms Arc Fault Duration

The supply is interrupted, metal parts of the

switchgear are destroyed & poisonous gases

are emitted.

~1s Arc Fault Duration

Destroys most of the switchgear & may cause a

fire, injury to personnel & damage to property.

Page 19: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Arc Fault Monitor

~500ms Arc Fault Duration

Page 20: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Arc Fault Monitor

Arguably the greatest risk of arc fault damage

exists at the CB cable termination & in the CB

chamber itself due to the slow clearance times

of the IDMT feeder protection.

The problem of arc faults is most prevalent in

older metal clad switchgear, which already has

operational protection systems.

The CB cable termination is particularly at risk to

ingress of moisture & rodent damage.

Page 21: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Low Voltage Protection

Trip on arc fault <10ms

1S 25

HEALTH Y

Z ONE 2

Z ONE 3

Z ONE 4

Z ONE 1

Cus tom te xt

Cus tom te xt

Cus tom te xt

Cus tom te xt

FAIL

FAIL

FAIL

FAIL

T RIP

T RIP

T RIP

T RIP

RESET/T EST

CO MMO N TRIP

ALARMO UTPUTS

Page 22: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

System Integration

With current check using high speed starter element

A R C FA U LT TR IP IN IT IATE

CB ARC FAULT

M O NITORSENSOR

OVER-CURRENT RELAY3 P o le O C + E F

H E A LT H Y

Z O N E 2

Z O N E 3

Z O N E 4

Z O N E 1

C u s to m te x t

C u s to m te x t

C u s to m te x t

C u s to m te x t

F A IL

F A IL

F A IL

F A IL

T R IP

T R IP

T R IP

T R IP

R E S E T/T E S T

Page 23: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Single Line DiagramCable box only

Trip only if over current starter picked up

ZONE 1ARC PROTECTION

COMMONALARM

OUTPUT

1S2550/51

Page 24: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Single Line Diagram

Cable box and CT chamber

ZONE 1ARC PROTECTION

CO MMO NALARM

O UTPUT

1S 2550/51

HEALTH Y

Z ONE 2

Z ONE 3

Z ONE 4

Z ONE 1

Cus tom te xt

Cus tom te xt

Cus tom te xt

Cus tom te xt

FAIL

FAIL

FAIL

FAIL

T RIP

T RIP

T RIP

T RIP

RESET/T EST

Page 25: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Single Line Diagram

Protect multiple breakers with a single 1S25

ZONE 1ARC PROTEC TIO N

COMMO NALARM

O UTPUT

1S 2550/51

HEALTH Y

Z ONE 2

Z ONE 3

Z ONE 4

Z ONE 1

Cus tom te xt

Cus tom te xt

Cus tom te xt

Cus tom te xt

FAIL

FAIL

FAIL

FAIL

T RIP

T RIP

T RIP

T RIP

RESET/T EST

TRIP

Page 26: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Single Line Diagram

Cable box, CT and CB chamber

ZONE 1ARC PROTECTION

CO MMO NALARM

O UTPUT

1S 2550/51

HEALTH Y

Z ONE 2

Z ONE 3

Z ONE 4

Z ONE 1

Cus tom te xt

Cus tom te xt

Cus tom te xt

Cus tom te xt

FAIL

FAIL

FAIL

FAIL

T RIP

T RIP

T RIP

T RIP

RESET/T EST

ZONE 2 TR IPUP STREAM

BREAKERZONE 2

ARC PROTECTION

ZONE 1 TR IP

Page 27: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Single Line Diagram

Cable box, CB and BUS chamber

ZONE 1

ZONE 2ARC PROTECTION

ZONE 3ARC PROTECTION

ZONE 2, 3 & 4 TRIPUP STREAM BR EAKER

ZONE 4ARC PROTECTION

CO MMO N ALARM O UTPUT

1S 25

HEALTH Y

Z ONE 2

Z ONE 3

Z ONE 4

Z ONE 1

Cus tom te xt

Cus tom te xt

Cus tom te xt

Cus tom te xt

FAIL

FAIL

FAIL

FAIL

T RIP

T RIP

T RIP

T RIP

RESET/T EST

50/51

Page 28: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Single Line Diagram

BUS chamber

ZONE 1 & 3TRIP CO MMO N

ALARMO UTPUT

50/51 1S 25

HEALTH Y

ZONE 2

ZONE 3

ZONE 4

ZONE 1

Cus tom te xt

Cus tom te xt

Cus tom te xt

Cus tom te xt

FAIL

FAIL

FAIL

FAIL

TRIP

TRIP

TRIP

TRIP

RESET/TEST

ZONE 2 & 3TRIP

50/51ZONE 1

TRIP

ZONE 3TRIP

ZONE 2TRIP

ZONE 3TRIP

ZONE 1 ZONE 3 ZONE 2

ZONE 1TRIP

ZONE 2TRIP

Page 29: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30 Optical Sensors

Page 30: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor

Mounted in each segregated switchgear chamber

Sensitivity linear in forward direction through 180º

Detects reflected arc light - mounting position not critical

Burden 2.5mA (quiescent)

Optional rear facing sensor

Page 31: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor Installation

Mounting position of the Sensor is not critical.

High sensitivity in direction of ‘View’

Page 32: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25 System Testing

Use camera flash to check operation of arc sensor and pick up of 1S25 trip contact.

Typical operating range of flash to arc sensor is 50 to 300mm

Page 33: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25 System Testing

CRO trace showing nominal operation time of the trip contacts. First contact touch at 6.25ms and fully closed by 7.25ms.

Page 34: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor Installation

1S30 shown mounted on the outside of a switchgear panelDetector oriented to ‘look’ through a hole into the switchgear

S w itchgearpanel

2 x M 4self th read ing

m oun ting sc rew s(S upp lied )

S ea led cab les tress re lie f

O p tica l detec torp ro trud ing th rough

ho le in pane l

Page 35: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor Installation

1S30 shown mounted on the inside of a switchgear panelDetector oriented to ‘look’ out into the switchgear compartment

2 x M 4self th reading

m ounting screw s(S upp lied )

O p tica l de tec to rfac ing aw ayfrom panel

Page 36: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor Installation

The dual optical detector version can be panel mountedto monitor two adjacent switchgear compartments simultaneously.

In terna l pa rtitionbe tw een sw itchgea r

com partm en ts

O p tica l de tec to rp ro trud ing th rough

com partm en t d iv ide rin to ad jacent

sw itchgea r cham ber

O p tica l de tec to rw indow fac ing aw ayfrom com partm en t

d iv ide r

Page 37: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor Installation

Right angle mounting off a surfaceMount off floor or walls within switchgear / BUS bar chamber

R igh t ang lem ountingb racke t

O p tica l de tec to rw indow fac ing aw ay

from right anglem ounting b racke t

S ing leop tica l de tec to r

D ua lop tica l de tec to r

Page 38: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor Installation

Flush mount reinforcing plate1.2mm zinc plated mild steel

2 x M 4self th read ing

m ounting screw s(S upp lied )

F lush m oun tre inforc ing

p la te

Page 39: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor Installation

SENSOR LOCATIONS

Page 40: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Cable Box Arc Fault

13.1kA (50mS)

Fault created in Cable Box by connecting three bushing connectors with fuse wire.

Sensor fitted to side of box.

Cover after testCover as new

Page 41: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Cable Box Arc Fault

Lower portion of Coverstrengthened

Page 42: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Cable Box Arc Fault

Sensor location

Page 43: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

CB Chamber Arc Fault

CB chamber fault at 13.1kA (50mS)

Fault initiated by connecting 3 phases of circuit side of CB with fuse wire

- typical of test leads used during maintenance.

One ARC sensor fitted.

Page 44: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

CB Chamber Arc Fault

General views after test

Page 45: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Does it Work

WILL IT OPERATE UNDER DYNAMIC CONDITIONS? --- YES

HOW FAST DOES IT REMOVE AN INTERNAL FAULT? --- 50-75ms

IS IT EFFECTIVE IN ALL SWITCHGEAR CHAMBERS? --- YES

HOW MUCH DAMAGE IS CAUSED TO THE SWITCHGEAR? --- Minimal

DOES IT IMPROVE SAFETY? --- YES, Significantly

Page 46: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30Arc Sensor

measured current( increase 1*In ==> 10*In)

arc detection

overcurrent detection

trip output contact

Page 47: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Up to 8 arc sensors in 4 independent zones

5 high speed tripping duty arc sense output contacts

<10ms arc fault tripping time

Self supervision with fail alarm contact

Push button reset & self test

1S30 Arc sensor continuous supervision

Compact, economic design

Simple panel mounting for retrofit applications

1S25 Summary

Page 48: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Front Panel Indication

HE ALT HY

ZO NE 2

ZO NE 3

ZO NE 4

ZO NE 1

Custom text 1

Custom text 2

Custom text 3

Custom text 4

S ENS OR FA IL

S ENS OR FA IL

S ENS OR FA IL

S ENS OR FA IL

TRIP

TRIP

TRIP

TRIP

RE SE T/TE S T

Page 49: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

Mounting

Front v iew15

2 ho les o f 3 .7

Ind icativepos ition

S ide v iew

S ize 2M 28-Sdraw out case

D raw ing un its : m m

Term ina l layout P ane l cut out

S uits flush pane l m ounting &4U h igh 19 inch rack fram e

14

1 2

27 28

Page 50: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Configuration Settings

Switch ON OFF

C1 Latching trip contacts Self reset trip contacts

C2 Segregated trip outputs Common trip outputs

C3 Apply volts to BLOCK Remove volts to BLOCK

C4 DC only status inputs AC/DC status inputs

O NO NO NO N

O FFO FFO FFO FF

S w itch 1S w itch 2S w itch 3S w itch 4

B A N K

A

Bank A & B configuration switches are used to set the number of 1S30 arc sensors connected.

Page 51: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Wiring Termination

1

3V x P ow er sup p ly ,C PU & se nso r

fa il a larm

R em o te re set

A rc fau lt BL O C K in pu t

Configuration sw itches(Primary PCB)

Z one 1A rc s ens or inp ut

1S 30A rc F au lt Se nso rs

Z one 2A rc s ens or inp ut

Z one 3A rc s ens or inp ut

Z one 4A rc s ens or inp ut

2

Z one 1 T rip

Z one 2 T rip

Z one 3 T rip

Z one 4 T rip

C om m o n Trip

Switch 1Switch 2Switch 3Switch 4

B AN K

AB AN K

BB AN K

C

27

25

23F ail

H ea lthy

A la rm c om m o n

S igna l p rocess ingand log icfunc tions

O N O N O N

A rc s ens or fa u lt s igna l

Page 52: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25 Ordering Code

ORDER CODE The order code determines the production build in the factory & cannot be changed in the field.

Generate the required order code as follows: e.g. 1S25 BA

Order

Code General Type 1 2

1S25 -

1 AUXILIARY SUPPLY RANGE

A 20 - 70V DC B 40 - 300V DC & 40 – 275V AC

2 CUSTOM ENGRAVED TEXT

A Not required No engraving - factory default B Required Complete the custom text details at left

Page 53: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S30 Ordering Code

Generate the required ordering code as follows: e.g. 1S30 A

1 DETECTORS

A Single through hole panel detector B Dual detectors

2 SPECIFY OPTIONS (Only if required)

F Flush mount reinforcing plate required L 20m shielded cable required

1 2

1S30

Page 54: 1S25 Arc Fault Monitor. 1S25 Arc Fault Monitor 1S25 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear may occur for many different.

1S25Additional Information

Technical Bulletin User Guide Price & Availability