: ! , COVER SHEET 1RE04 INSERVICE INSPECTION SUMMARY REPORT ; FOR SYSTEM PRESSURE TESTS i (CLASS 1 AND 2) : AT TIIE e SOUTII TEXAS PROJECT ELECTRIC GENERATING STATION UNIT 1 ' ; P. O. Box 289 Wadsworth, Texas 77483 USNRC DOCKET NO.: 50-498 , OPERATING LICENSE NO.: NPF-76 ' COMMERCIAL OPERATION DATE: August 25,1988 j 1 Prepared by: 80 /b4' 3 2S c73 A. P. PathaxfConsulting Engineer - Codes & Standards i ! Reviewed by: w' }M 93 S. Timmaraju, Sr. Consulting Engineer - Codes & Standards ! ( Approved by: [ RQ .3 ' F> ~ 93 , i M. Pacy, Manager ( esign Engineering Departmer . ! , f f ! L ' MB4AC8.AP ! 9304060252 930331 ! PDR ADOCK 05000498 ' G PDR ,

Transcript of '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT...

Page 1: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

:

!,

COVER SHEET

1RE04 INSERVICE INSPECTION SUMMARY REPORT ;

FOR SYSTEM PRESSURE TESTS i

(CLASS 1 AND 2):

AT TIIEe

SOUTII TEXAS PROJECT ELECTRIC GENERATING STATION UNIT 1';

P. O. Box 289Wadsworth, Texas 77483

USNRC DOCKET NO.: 50-498,!

OPERATING LICENSE NO.: NPF-76'

COMMERCIAL OPERATION DATE: August 25,1988 j

1

Prepared by: 80 /b4' 3 2S c73A. P. PathaxfConsulting Engineer - Codes & Standards

i

!

Reviewed by: w' }M 93S. Timmaraju, Sr. Consulting Engineer - Codes & Standards !

(Approved by: [ RQ .3 ' F> ~ 93

,

i

M. Pacy, Manager ( esign Engineering Departmer .

!

,

f

f

!L

'MB4AC8.AP

!

9304060252 930331 !PDR ADOCK 05000498 '

G PDR,

Page 2: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

. . . . . ... -- _ _ . -

. .

.

.

.

SCOPE

1RE04 SYSTEM PRESSURE TESTS

The examinations summarized in this report were performed in accordance with the 1983Edition through Summer 1983 Addenda of the ASME Code, Section XI which isapplicable to the South Texas Project Electric Generating Station Unit 1. This reportcovers selected ASME Code Class 1 and 2 Systems / Components. Examinations and testsrequired by the Codt are scheduled in accordance with ' Inspection Program B" as _defined in IWB-2412 and IWC-2412 for ASME Code Class 1 and 2 Systems / Components.All ASME Code Class 1 components were examined as prescribed by' Table IWB-2500-1,

outage. The ASM. ory B-P which established the examination frequency at each refuelingE Code Class 2 Systems / Components were selected on a random basis.Examination Cate:

!

| This random selection process will continue until all ASME Code Class 2| Systems /Commonents are examined in accordance with Table IWC-2500-1, ExaminationI dategory C-E. This examination category for ASME Code Class 2 Systems / ComponentsI established the examination frequency at each inspection period. The remaining second

period examinations are anticipated to be completed by the end (8-25-95) of the secondmspection period.

1 conducted on Class 1 Systems / Components inThe System Leakage Test [IWA-5211(a)U-P also satisfied the system pressure testaccordance with Examination Categoryrequired by IWA-5214(e) subsequent to the disassembly and reassembly of mechanicaljoints in ASME Code Class 1 Systems / Components.

!

I

!

MB4408.AP

- - _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ - _ _ _ _ _ _ _ _ _ _ _ _ . __

Page 3: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

-

. PAGE 1 of 3.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAs required by the Provisions of the ASME Code Rules

i

i

1. Owner Ibuston Lighting & Pcuer Ccrpany Electric hr, P. O. Box 1700, Ibustm, 'DC 77001 j(Name and /ddress of Omer) |

2. Plant South Texas Project Electric Cenerating Station P. O. Bax 289, Wadsworth, 'DC 77483 1

!(Nme and /ddress of Plant)3. Plant Unit 1 4. Omer C <*ificate of Authorization (if required) N/A

|

5. Camercial Service Date 08/25/88 6. National Board itznber for Ihlt N/A

7. ''r:panents Inspected A9E CODE CLASS 1 PIPDG #0 (I2iEC24ENIS,

,

Manufacturer I

Ccrpanent or Manufacturer or Installer State or National i

Appurtenance or Installer Serial No. Prwince No. Board No. ,

RFJCKR \N CIHSUSTICN BCD4EERDG/'

1R10D4RV101A VESTDGOUSE (M) 11073 N/A 22190

SDi. @SAIG1R121NSG101A WESTDG0USE (M) 2131 N/A W18691

SDi. G SAIm1R121HSG101B VfSrDG00SE (M) 2132 N/A W18692 :

SDi. OS/JG1R121NSG101C WESTDGOUSE (M) 2133 N/A W18693

SIM. GEN m KIm1R1211G101D WESTDGOUSE (M) 2134 N/A V18694

PRESSURIZIR

1R11D4PZ101A WESTDG00 sit (M) 2141 N/A V18590

RcIueIR131NPP101A kTSrDODUSE (M) 1-115E580G)1 N/A 28 !

IC IUfIR131NPP101B kTSrDG00SE (M) 2-115E580CD1 N/A 29

RC IUT1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30

Tc IufIR131NPP101D WESrDGOUSE (M) 4-115E580311 N/A 31

CLASS 1

PIPDG EPASCD (I) N/A N/A N/A '

CIASS 1VALVES VARICUS N/A N/A N/A

,

I

!

ICIE: Su;plenental sheets in form of lists, sketches, or drawings may be used, prwided (1)size is 81/2 in. X 11 in., (2) information in itens I through 6 on this report is incitded oneach sheet, and (3) each sheet is rnznbered and tre ntruber of steets is recorded at the top ofthis form.

i

NIS1 CLI.1RE04

i__

Page 4: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

PAGE 2 of 3. . ,

FORM NIS-1 (Back)'

8. Lcanination Dates Of./05/91 to 01/01/93 9. Inspectim Interval frcen 08/25/88 to 08/25/98i

10. Abstract of Exaninations. Inchde a list of == intime and a stataaent conceming status of work

regaired for current interval. Refer to Supplanental Sheet Page 3 of 3.

11. Abstract of Corditions IbtedIb relevant conditions affecting pressure retaining bcxxndaries were noted.

12. Abstract of Corrective & asures R + - . %ei and TakenRefer to Supplemental Sheet Page 3 of 3.

We certify that the statamnts made in this report are correct and the exaninations ard correctiveceasures taken cmform to the rules of the ASE Code, Section XI.

Certificate of Aathorization Ib.-(if applicable) N/A Dcpiratim Date }{/A

Byh b &Date M deC b I2, 19 '8 Signed mustm Ughting Wr Co.Owner D.Aj/. azar

Plant Engirreering Manager

OREIFICKIE & INSER71CE DGPICIIQi *

I, the undersigned, holding a valid cmmission issued by the National Board of Boiler and Pressure VesselInspectors ard the State or Province of Texas and mployed by Arkwright fixtual Insurance Co. of

Ibrwood, MASS. have inspected the cups.nts described in thisomer's Retnrt during the period /A9-qa to 3 - a ' - 9.3 and state,

that to the test of ray knowledge and belief, the Deer has perforxted exaninations ard taken correctiveneesures described in this Owner's Report in accordance with tie inspection plan ard as required by the ASECode, Section XI. !

By signing this certificate neither tie Inspector nor his enployer makes any warranty, expressedor inplied, concerning the exaninatims ard corrective neasures described in this Owner's Report. Furthernere,

.

',

neither the Inspector nor his er:ployer shall be liable in any manner for any personal injury or property ;

danage or a loss of any kird arising fran or connected with this inspection.

FACIGN IU1UAL SYSIIM

A Ccxunissions 'IX-826B. R. Russell, Inspector's Signature National Board, State, Province, ard Endorsements ,

,

Date 3-2.2- 19 16 ,

!,

1

|

|

!

l,

NISI.CLI.1RE04

_ _ . - _ . - _ _ - _ _ _ _ _ _ _ _ _ - - _ _ _ _ _ _ _ - - - _ - .

Page 5: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

PAGE 3 of 3. .

'

SUPPLEMDITAL..

FOR

ASME CODE CLASS 1 PIPING AND COMPONDITS-

1. Owner Ibusten Li@ti= & Power Ccrpany Electric Tower, P. O. Bar 1700, Ikustxm, 'IX 77001(Nme arxi Ackiress of Owner)

2. Plant South Texas Project Electric Generating Station P. O. Bar 289. Wadsworth, TX 77483

(Name and Address of Plant)3. Plant thit 1 4 Owner Certificate of Authorization (if required) N/A

5. Camercial Service Date 08/25/88 6. National Board Nanber for thit N/A

10. ABSTRACT OF EXAMINATIONS

A System Leakage Test as prescribed by IWA-5211(a) for all ASME CodeClass 1 Pressure Retaining Components was conducted in accordance withTable IVB-2500-1, Examination Category B-P, Item Nos. B15.10, B15.20,

B15. 30, B15.40, Bl.5. 50, B15. 60 and B15. 70. t

t

The Pressure Test and VT-2 visual examinations were conducted in accordancewith Plant Surveillance Pressure Test Procedure, OPSP15-RC-0001, ReactorCoolant System Leakage Pressure Test (Rev. O) at the conclusion of the-fourth refueling outage. ASME Code Class 1 piping and valves arespecifically identified in the above referenced procedure.

t

In addition, the above System Leakage Test also satisfied the requirement i

for a System Pressure Test subsequent to the disassembly and reassembly of i

mechanical joints in ASME Code Class 1 components as prescribed byIWA-5214(e). 3

i

Also, System Pressure Tests subsequent to the disassembly and reassembly ofmechanical joints in ASME Code Class 1 components as p'rescribed byIWA-5214(e) were conducted in accordance with OPGP03-ZE-0027, ASMESection XI Post-Maintenance Pressure Tests (Rev. 3) for individual workitems performed outside the scope of the fourth refueling outage, f

12. ABSTRACT OF CORRECTIVE MEASURES RECOMMENDED AND TAKEN !

The Visual Examinations (VT-2) performed during these Pressure Tests found ,

minor leakage at mechanical joints such as valve stems and flanged i

connections. These leaks were evaluated and determined acceptable for i

continued system operation. Appropriate corrective action was initiated to [correct these leaks. A leak was found at the control rod drive mechanismat the top of the reactor vessel. This leak was from a seal weld and ,

although not a Class I boundary the reactor coolant system was ,

depressurized. The leak was repaired and retested satisfactorily.,

I|

'

'1

|!

l

|.

NISI.CLI.1RE04

Page 6: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

. .

'

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS Page 1 Cf 4 ,,

As required by the Provisions of the ASME Code Rulm

__

1. Owner Houston Llahtina & Power Company Electric Tower. P.O. Box 1700. Houston. TX 77001(Name and Address of Owner)

2. Plant South Texas Project Electric Generatino Station P.O. Box 289, Wadsworth, TX 77483

(Name and Address of Owner)3. Plant Unit 1 4. Owner Certificate of Authorization (if required) N/A -

5. Commercial Service Date 08/25/88 6. National Board Number for Unit N/A,

P

7. Components inspected ASME CODE CLASS 2 PIPING AND COMPONENTS

ManufacturerComponent or Manufacturer or Installer State or National ,

Appurtenance or Installer Serial No. Province No. Board No.

RWST 1 A2N121NTF101 A BROWN MINNEAPOLIS (M) 1100-15 N/A N/A

HHSI PMP 1 A2N121NPA101A PACIFIC PUMPS (M) 51695 N/A 382

HHS! PMP 1B2N121NPA101B PACIFIC PUMPS (M) 51696 N/A 383

HHSI PMP 1C |

2N121NPA101C PACIFIC PUMPS (M) 51700 N/A 402

LHSI PMP 1 A2N121NPA102A PACIFIC PUMPS (M) 51701 N/A 420

LHSI PMP 182N121NPA102B PACIFIC PUMPS (M) 51702 N/A 421

LHSI PMP 1C2N121NPA102C PACIFIC PUMPS (M) 51703 N/A 422

CS PMP 1 A ;

2N101NPA101A PACIFIC PUMPS (M) 51707 N/A 441

CS PMP 1B ,

2N101NPA101B PACIFIC PUMPS (M) 51708 N/A 441 i

CS PMP 1C2N101NPA101C PACIFIC PUMPS (M) 51709 N/A 442

3

SI ACC TK 1 A2N121NRD101A SOUTHWEST FAB (M) 0043 N/A 362

,

SI ACC TK 182N121NRC101B SOUTHWEST FAB (M) 0044 N/A 363 ;

St ACC TK 1C2N121NRC101C SOUTHWEST FAB (M) 0045 N/A 364

CS EDUCTOR 1 A2N101NED101A EBASCO (I) 229 N/A N/A

CS EDUCTOR 182N101NED101D EBASCO (I) 230 N/A N/A

.

CS EDUCTOR 1C2N101NED101C EBASCO (1) 225 N/A N/A

Note: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) sie e is 81/2 in. X 11~

,

in., (2) information in items 1 through 6 on this report is included on each sheet, anc (3) each sheet is l

numbered and the number of sheets is recorded at the top of this form.

N!9 Ct218 yod

Page 7: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

-

*

PAGE 2 of M. .

/b($ ,

FORM NIS-1 (Back) 3/ rim ;,

8. Ecamination Dates O',/05/91 to 01/01/93 9. Inspection Interval frun 08/25/88 to 08/25/98 [

10. Abetract of Darninations. Incluie a list of e-inaticos and a statemnt concemirg status of woric ,

required for second period and examinations performed to cmplete the requiramnts of the first periodof the current interval. Refer to Supplamntal Sheet Page 3 of 3.

11. Abstract of Conditions IbtedIb relevant gcrxiitions affectirg pressure retaining boundaries were noted. ,

12. Abstract of <:brrective Wasures FF. < ~ %<i and Taken :

Rcfer to Supplanental Sheet Page 3 of 3. -

We certify that the statements made in this report are correct and the exaninations ad correctivemeasures taken conform to tJe rules of the ASME Code, Section XI. !

Certificate of Authorization !b. (if applicable) N/A Expiration Date vN/A ,

Date /N7/'(b /2- . 19 93 Signed Ruston 1.ighting & Power Cb. By . - m

Oaner D. ApTeazarPlant Engineering Manager

QRIIFICNIE T IIGDNIG IICE'ICEICH

I, the undersigned, holding a valid ccr.ruission issued by the National Board of Boiler and Pressure VesselInspectors and the State or Prwince of Texas axi a: ployed by Arkwright lirtual Insurance Co. of |

- Norvocd, MASS. have inspected the ccr:ponents described in this i

O mer's Report during the period 6 - 5- O- to 5-n-@ and state,

that to the best of rey knowledge and belief, the Daner has performed examinations and taken correctivemeasures described in this Oaner's Peport in accordance with the inspection plan a:xi as required by the ISE iCode, Section XI.

By signing this certificate neither the Inspector nor his a:ployer makes any warranty, expressed.

or itzplied, concerning the examinations and corrective measures described in this Or w's Report. Ibrtherraore, !

neither the Inspector nor his ecployer shall be liable in any manner for any persoual injury or propertydanage or a loss of any kird arising frun or connected with this inspection.

}FACIDIU 11ml4L SYSIDI '

.

kash Ccr missions 'JX-8261

B. R. Russell, Inspector's Signature National Board, State, Prwince, and Driorsements I

f

Dcte 3 - n - 19 e73 ,

iii

!,

,

!

,

!NISI.CL2.1RE04

Page 8: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

. _ . - - - - _

.

Page 3 of 4.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAs required by the Provisions of the ASME Code Rules

,

I

1. Owner 1kuston Lighting & Ptwer Camarn Electric Tower, P. O. Bcot 1700, ibuston, TK 77001(ltras and /diress of Daner)

2. Plant South Texas Project Electric Generating Station P. O. Bax 289, Wadsworth, 'DC 77483 ;

(Naus and Address of Plant) |

3. Plant thit 1 4. Owner Certificate of Authorization (if required) N/A-

5. Cmr:creial Service Date 08/25/88 6. National Board Niler for Ibit N/A

7. Ccr:panents Inspected N2E CIE CIASS 2 PIPDG #0 O'HPOERS ,

Manufacturer .

Ccrpcnent or Manufacturer or Installer State or NationalAppartenance or Installer Serial Ib. Prwince Ib. Board Ib. *

CIASS 2 i

PIPDG EPJ&D (I) N/A N/A N/A.

iCLASS 2VALVES VARICUS N/A N/A N/A

:t

i

;

E,

[r|

!t

it

!

Ir

:!

,

I.

|

1

1 DIE: Supplanental sheets in form of lists, sketches, or drawings may be used, prcuided (1)'

size is 81/2 in. X 11 in., (2) information in iterns I through 6 on this re;crt is included oneach sheet, and (3) each sheet is mrnbered and the trJraber of Sheets iS recorded at the top ofthis fonn.,

NISI.CL2. IRE 04

. _ _ _ _ _ _ _ _ _ _ _ _ _ _ . - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Page 9: '1RE04 ISI Summary Rept for Sys Pressure Test (Class 1 & 2) at … · 2020. 4. 10. · RC IUT 1R131NPP101C WESIDUOUSE (M) 3-115E580CD1 N/A 30 Tc Iuf IR131NPP101D WESrDGOUSE (M) 4-115E580311

_ _

|- . ;

I'

Page 4 of 4,

SUPPLEMDITAL- FOR i

ASME CODE CLASS 2 PIPING AND COMPONENTS

1. Owner Ikuston Lighting & Power Cmpany Electric 'Ibwer, P. O. Bax 1700, Ibustcn, TX 77001 -

(Nane and Address of Odner) I

2. Plant South Texas Project Electric Generating Station P. O. Bax 289, Wadsworth, TX 77483 '

(Nane and Address of Plant) |

3. Plant thit 1 4. Omer Certificate of Autlerization (if required) N/A

5. Camercial Service Date 08/25/88 6. National Board Naber for Unit N/A:

10. ABSTRACT OF EXAMINATIONS -

System Inservice Tests as prescribed by IVA-5211(c) were conducted on >

'

selected ASME Code Class 2 Pressure Retaining Components in accordance with,

Table IVC-2500-1. Examination Category C-H, Item Nos. C7.30 and C7.70. ;;

The Pressure Tests and VT 2 visual examinations were conducted during thefirst period of examination in accordance with the following Plant :

Surveillance Pressure Test Procedures 1

OPSP15-CH-0001 - Containment Hydrogen Monitoring System Functional Pressure*

J Test, (Rev. 1)IPSP15-CV-0001 - Chemical and Volume Control System Inservice Pressure

Test, (Rev. 1) !

The Pressure Tests and VT-2 visual examinations were conducted during the,

second period of examination in accordance with the following Plant |'

Surveillance Pressure Test Procedures:

OPSP15-CS-0001 - CS System Functional Pressure Test, (Rev. 0)'

<

IPSP15-SI-0001 - Safety Injection System Functional Pressure Test, (Rev. 3)IPSP15-SB-0001 - Steani Generator Blowdown System Inservice Iressure Test I

(Rev. 2)IPSP15-FW-0001 - Feedwater System Inservice Pressure Test (Re'r. 2)

(inside containment portion only)IPSP15-RC-0001 - Reactor Coolant System Leakage Pressure Test (Rev. 2)

* ,

!

f

IASME Code Class 2 piping and valves are specifically identified'in theabove referenced procedures. These test procedures were conducted during :

the time period of April 5, 1991 to January 1, 1993. |I

12. ABSTRACT OF CORRECTIVE MEASURES RECOMMENDED AND TAKEN:p

The Visual Examinations (VT-2) performed during these Pressure Tests foundonly minor leakage at mechanical joints such as valve stems and flangedconnections. These leaks were evaluated and determined acceptable for

,

continued system operation. Appropriate corrective action was initiated tocorrect these leaks.

,

s

4

&

.