1CF00eng
Transcript of 1CF00eng
![Page 1: 1CF00eng](https://reader030.fdocuments.us/reader030/viewer/2022021213/577d27141a28ab4e1ea2ffaa/html5/thumbnails/1.jpg)
8/6/2019 1CF00eng
http://slidepdf.com/reader/full/1cf00eng 1/4
Copyright 2003 by Siemens Energy & Automation, Inc.A5E00262196--01
Product Information
SIMATIC S7--300
Digi tal Outp ut Modu le SM 322; DO 8 X 48--125 VDC/1.5A
New Digital Output Module Available
The S7--300 Digital Output Module SM 322; DO 8 X 48--125 VDC/1.5A has been
added to the S7--300 family. The order number for this module is6ES7 322-1CF00-0AA0.
This product information includes details about the characteristics and technical
specifications of the SM 322; DO 8 X 48--125 VDC/1.5A Module. Refer to the
S7-300 Installation and Hardware Manual for more information about the S7-300
product family.
Additional Assistance
For assistance in answering technical questions, for training on this product, or for
ordering, contact your Siemens distributor or sales office.
X 23Release 4
![Page 2: 1CF00eng](https://reader030.fdocuments.us/reader030/viewer/2022021213/577d27141a28ab4e1ea2ffaa/html5/thumbnails/2.jpg)
8/6/2019 1CF00eng
http://slidepdf.com/reader/full/1cf00eng 2/4
2Product Information S7--300 Digital Output Module SM 322 DO 8 x 48--125 VDC/1.5 A
A5E00262196--01
Digital Output Module SM 322; DO 8 X 48-125 VDC/1.5A
Order Number
6ES7 322-1CF00--0AA0
Characteristics
The SM 322; DO 8 ¢ 48--125 VDC/1.5A features the following characteristics:
! 8 outputs, reverse polarity protection and isolated in groups of 4
! 1.5 A output current
! Rated load voltage 48 to 125 VDC
! Suitable for solenoid valves, DC contactors and indicator lights
! Group error display
Using the module with high-speed counters
Please take note of the following information on the use of the module in
connection with high-speed counters:
Note
When connecting the power supply via a mechanical contact, the outputs of theSM 322; DO 8 × 48-125 VDC/1.5 A carry a ”1” signal for approximately 50 !s forreasons associated with the circuitry.
![Page 3: 1CF00eng](https://reader030.fdocuments.us/reader030/viewer/2022021213/577d27141a28ab4e1ea2ffaa/html5/thumbnails/3.jpg)
8/6/2019 1CF00eng
http://slidepdf.com/reader/full/1cf00eng 3/4
3Product Information S7--300 Digital Output Module SM 322 DO 32 x 48--125 VDC/1.5 AA5E00262196--01
Terminal Assignment and Block Diagram of the SM 322; DO 8 X 48-125 VDC/1.5A
Channel number
Status display -- green
1M
48 to125 V
1 L+
2M
48 to125 V
2 L+
SF
1
3
5
7
9
10Backplane bus
interface
+ 5 V
+ 5 V 11
13
15
17
19
20
SF
Fault indicator -- red
Figure 1 Module View and Block Diagram of the SM 322; D0 8¢ 48--125 VDC/1.5 A
![Page 4: 1CF00eng](https://reader030.fdocuments.us/reader030/viewer/2022021213/577d27141a28ab4e1ea2ffaa/html5/thumbnails/4.jpg)
8/6/2019 1CF00eng
http://slidepdf.com/reader/full/1cf00eng 4/4
4Product Information S7--300 Digital Output Module SM 322 DO 8 x 48--125 VDC/1.5 A
A5E00262196--01
Technical specifications of the SM 322; DO 8 × 48-125 VDC/1.5 A
Dimensions and Weight
Dimensions W × H × D(in millimeters)
40¢!125¢!117
Weight Approx. 250 g
Data for Specific Module
Supports clockedoperation
No
Number of outputs 8
Length of cable
! Unshielded
! Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L+ 48 VDC to 125 VDC
! Reverse polarity protection Yes, by means offuse1)
Total current of the outputs(per group)
! Horizontal configuration
Up to 40 "C
Up to 50 "C
Up to 60 "C
max. 6 A
max. 4 A
max. 3 A
! Vertical configuration
Up to 40 "C max. 4 A
Isolation
! Between channels andbackplane bus
Yes
! Between the channels
In groups of
Yes
4
Permitted potential difference
! Between the differentcircuits
146 VDC / 132 VAC
Insulation tested with 1500 VAC
Current consumption
! From the backplane bus
! From the load voltage L+(no load)
max. 100 mA
max. 2 mA
Power dissipation of the module typ. 7.2 W
Status, Interrupts, Diagnostics
Status display Green LED per channel
Interrupts None
Diagnostic functions
! Group error display Red LED (SF)2)
Data for Selecting an Actuator
Output voltage
! At ” 1” signal min. L + (--1.2 V)
Output current
!At ” 1” signalRated value
Permitted range
1.5 A
10 mA to 1.5 A
! Permitted surge current max. 3 A for 10 ms
! For ”0” signal(leakage current)
max. 0.5 mA
Output delay (for resistive load)
! At ”0” to ”1”
! At ”1” to ”0”
max. 2 ms
max. 15 ms
Lamp load max. 15 W at 48 Vmax. 40 W at 125 V
Parallel connection of 2 outputs! For redundant actuation of
a loadPossible (only outputsof the same group)
! To increase performance Not possible
Triggering a digital input Possible
Switch rate
! For resistive load
! For inductive load
! For lamp load
max. 25 Hz
max. 0.5 Hz
max. 10 Hz
Limit (internal) of the inductive circuit interruptionvoltage up
typ. M (--1V)
Short-circuit protection of theoutput
! Threshold on
Yes, electronic3)
typ. 4.4 A
Replacement fuses Fuse 6.3 A/250 V, quickblow, 5 x 20 mm
! Schurter
! Wickmann
SP0001.1012
194-1630-0
Fuse carrier
! Wickman 653 0000 040
1) The fuses on this module are merely supplementaryfuses. External overcurrent protection (suitable forbranch circuits conforming to the local regulations for
electrical engineering) is required in the supply cables ofthe load circuit.
2) Potential errors are:- No load voltage- Fuse defective- Output overloaded
3) If an overload condition is detected, the output isinhibited for approximately 2.4 s.