19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert...

download 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

of 8

Transcript of 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert...

  • 8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

    1/8

    A new approach to Diagnosis of Power Quality

    Problems using Expert System

    A.N.Malleswara Rao Dr. K. Ramesh Reddy Dr. B. V. Sanker RamResearch Scholar Dean & HoD, EEE Dept. Professor, EEE Dept.,

    JNTUH, Hyderabad GNITS, Hyderabad JNTUH, [email protected] [email protected]

    Abstract: In this paper, a new approach is presented to identify

    power quality disturbances using fuzzy logic systems. Distributed

    single phase power electronic loads are usually treated as fixed

    harmonic current injectors in distribution system. Their current

    harmonics are characterized by normalized phasors |Ih/I1|angle h,

    where the fundamental current component I1 is varied

    proportionally with load power. Fixed harmonic current injection

    lead to an over estimation of resulting voltage harmonics because it

    neglects phase angle, dispersion of individual current harmonics.

    Harmonic currents generated by single phase power electronicloads too small to cause any appraisable distribution feeders.

    However as the number of these loads increases and as larger

    nonlinear loads the cumulative harmonics becomes very significant.

    Fuzzy logic is used to diagnose all these problems. Detailed digital

    simulation results involving various types of transient power

    quality disturbances are presented to prove the ability of the new

    approach in classifying these disturbances..

    Index TermsFuzzy logic, power system harmonics, Power

    quality, Fault analysis

    I. INTRODUCTION

    Harmonic is a core issue regarding Power Quality. It is

    not only pollutes the power system but also have negative effects

    on electrical equipments. With increasing use of power

    electronics in industrial, commercial, and residential consumers,

    the issue of harmonics and their effects on performance of

    electrical installation and electronic equipment increases [1].

    The objective of the electric utility is to deliver sinusoidal

    voltage at fairly constant magnitude throughout their system.

    This objective is complicated by the fact that there are loads on

    the system that produce harmonic currents. These currents

    results in distorted voltage and current that can adversely impact

    the system performance in different ways. A number of

    harmonic producing loads have increased over the years, it has become increased necessary to address their influence when

    making any additional or changes to an installation.

    The fundamental or basic power frequency is 50 Hertz. This

    means the waveform of the electricity repeats itself 50 times

    every second. The characteristic harmonics are based on number

    of rectifiers (pulse number) used in a circuit &can be determined

    by the following equation

    h= (n*p) 1 ---- (1)

    where n=an integer (1, 2, 3, 4, 5.)

    p=number of pulse or rectifiers

    A pure AC sine wave is ideal, such as shown in figure 1(a), and

    is obtained if the load is an incandescent light bulb.

    Fig 1(a) Ideal AC sine wave

    In a three phase system, three sine waves are generated120

    degrees apart, as shown in figure 1(b)

    Fig1(b).Three phase system

    Harmonic frequencies are multiples of the fundamenta

    frequency. Any distorted voltage or current wave is the sum of

    the fundamental frequency and a number of the above

    harmonics. Figure 2(a) shows the fundamental and the third

    harmonic. Figure 2(b) demonstrates the addition of the harmonic

    and the fundamental frequency.

    A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297

    ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 290

    mailto:[email protected]:[email protected]
  • 8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

    2/8

    Fig 2(a).Fundamental and the third harmonic wave forms

    Fig 2(b).Combined waveform of fundamental and third

    harmonic component.

    II. BACKGROUND HISTORY

    The voltage pushing that current through the load

    circuit is described in terms of frequency and amplitude. The

    frequency of the current will be identical to the frequency of the

    voltage as long as the load impedance does not change. In a

    linear load, like a resistor, capacitor or inductor, current and

    voltage will have the same frequency. As long as the

    characteristics of the load components do not change, the

    frequency component of the current will not change. But in case

    of non-linear loads such as switching power supplies, saturated

    transformers, charged capacitors, and converters used in drives,

    the characteristics of the load are dynamic. As the amplitude of

    the voltage changes and the load impedance changes, the

    frequency of the current will change. The changing current and

    resulting complex waveform is a result of these load changes.

    The complex current waveform can be described by defining

    each component of the waveform. The frequencies that are

    normally dealt with using drives are 50 or 60 Hz. By definition,

    these frequencies are termed fundamental in their respective

    distribution systems.

    The drawing shown indicates how current follows the

    frequency when the load is linear only a phase angle change isshown in Fig 3.

    Fig 3. Current follows the frequency when the load is linear and

    phase angle change.

    When the load become non-linear, the current is not continuous

    and will contain many frequencies. Figure 4 shows how the

    current might look like in a non-linear circuit.

    Fig 4.Line current in non-linear circuit

    A. Source of Harmonics

    Harmonic load currents are generated by all non-linear loads

    These include single phase loads, e.g.

    Switched mode power supplies (SMPS) Electronic fluorescent lighting ballasts Small uninterruptible power supplies (UPS) units

    Three phase loads, e.g.

    Variable speed drives Large UPS units Highly Fluxed Iron Cores

    B.Problems caused by harmonics

    Harmonic currents cause problems both on the supply and

    within the installation. The effects and the solutions are very

    different and need to be addressed separately; the measures that

    are appropriate to controlling the effects of harmonics within the

    installation may not necessarily reduce the distortion caused on

    the supply and vice versa [2]. There are several common

    problem areas caused by harmonics:

    1) Overloading of neutrals

    In a three-phase system the voltage waveform from each phase

    to the neutral star point is displaced by 120so that, when each

    phase is equally loaded, the combined current in the neutral is

    zero. In the past, installers have taken advantage of this fact by

    installing half-sized neutral conductors. However, although the

    fundamental currents cancel out, the harmonic currents do not -

    A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297

    ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 291

  • 8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

    3/8

    in fact those that are an odd multiple of three times the

    fundamental, the triple-N harmonics, add in the neutral.

    2) Overheating of transformers

    Transformers are affected in two ways by harmonics. Firstly, the

    eddy current losses, normally about 10 % of the loss at full load,

    increase with the square of the harmonic number. This results in

    a much higher operating temperature and a shorter life. The

    second effect concerns the triple-N harmonics. When reflected back to a delta winding they are all in phase, so the triple-N

    harmonic currents circulate in the winding. The triple-N

    harmonics are effectively absorbed in the winding and do not

    propagate onto the supply, so delta wound transformers are

    useful as isolating transformers.

    3) False tripping of circuit breakers

    Residual current circuit breakers (RCCB) operate by summing

    the current in the phase and neutral conductors and, if the result

    is not within the rated limit, disconnecting the power from the

    load. False tripping can occur in the presence of harmonics for

    two reasons. Firstly, the RCCB, being an electromechanical

    device, may not sum the higher frequency components correctly

    and therefore trips erroneously. Secondly, the kind of equipment

    that generates harmonics also generates switching noise that

    must be filtered at the equipment power connection.

    4) Over-stressing of power factor correction capacitors

    Power factor correction capacitors are provided in order to draw

    a current with a leading phase angle to offset lagging current

    drawn by an inductive load such as induction motors. The

    impedance of the PFC capacitor reduces as frequency rises,

    while the source impedance is generally inductive and increases

    with frequency. The capacitor is therefore likely to carry quite

    high harmonic currents and, unless it has been specificallydesigned to handle them, damage can result. A potentially more

    serious problem is that the capacitor and the stray inductance of

    the supply system can resonate at or near one of the harmonic

    frequencies when it occurred, very large voltages and currents

    can be generated, often leading to the catastrophic failure of the

    capacitor system [4].

    C.Problems caused by harmonic voltages:

    1) Voltage distortion:

    Because the supply has source impedance, harmonic load

    currents give rise to harmonic voltage distortion on the voltage

    waveform (this is the origin of flat topping). There are two

    elements to the impedance: that of the internal cabling from the

    point of common coupling (PCC), and that inherent in the

    supply at the PCC, e.g. the local supply transformer. The

    distorted load current drawn by the non-linear load causes a

    distorted voltage drop in the cable impedance. The resultant

    distorted voltage waveform is applied to all other loads

    connected to the same circuit, causing harmonic currents to flow

    in them - even if they are linear loads. Here separate circuits

    feed the linear and non-linear loads from the point of common

    coupling, so that the voltage distortion caused by the non-linear

    load does not affect the linear load.

    2) Induction motorsHarmonic voltage distortion causes increased eddy

    current losses in motors in the same way as in transformers

    However, additional losses arise due to the generation of

    harmonic fields in the stator, each of which is trying to rotate the

    motor at a different speed either forwards or backwards. High

    frequency currents induced in the rotor further increase losses.

    3) Zero-crossing noise

    Many electronic controllers detect the point at which the supply

    voltage crosses zero volts to determine when loads should be

    turned on. This is done because switching reactive loads at zero

    voltage does not generate transients, so reducing electromagnetic

    interference (EMI) and stress on the semiconductor switching

    devices. When harmonics or transients are present on the supply

    the rate of change of voltage at the crossing becomes faster and

    more difficult to identify, leading to erratic operation. There may

    in fact be several zero-crossings per half cycle.

    D.Problems caused when harmonic currents reach the supply

    When a harmonic current is drawn from the supply it gives rise

    to a harmonic voltage drop proportional to the source impedance

    at the point of common coupling (PCC) and the current. Since

    the supply network is generally inductive, the source impedance

    is higher at higher frequencies[5]. Of course, the voltage at the

    PCC is already distorted by the harmonic currents drawn byother consumers and by the distortion inherent in transformers,

    and each consumer makes an additional contribution.

    III. ELECTRICAL EQUIVALENT OF POWER

    SYSYTEMS:

    The equivalent circuit of a non-linear load is shown in Figure 5

    It can be modeled as a linear load in parallel with a number of

    current sources, one source for each harmonic frequency. The

    harmonic currents generated by the load or more accurately

    converted by the load from fundamental to harmonic current

    have to flow around the circuit via the source impedance and all

    other parallel paths. As a result, harmonic voltages appear across

    the supply impedance and are present throughout the

    installation. Source impedances influence the harmonic voltage

    distortion resulting from a harmonic current.

    A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297

    ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 292

  • 8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

    4/8

    Fig 5. Equivalent circuit of Non-linear load

    Whenever harmonics are suspected, or when trying to verify

    their absence, the current must be measured.

    The Fourier series represents an effective way to study

    and analyze harmonic distortion. It allows inspecting the various

    constituents of distorted waveform through decomposition.

    Generally, any periodic wave form can be expanded in the form

    of a Fourier series

    ----(2)

    Measures of Harmonic distortion:

    A distorted periodic current or voltage waveform expanded into

    a Fourier series is expressed as follows

    ------ (3)

    Accordingly, the following relationship for active power andreactive power supply are

    ----- (4)

    Reactive power is defined as

    ----- (5)

    Voltage distortion factor VDF, also known as voltage total

    harmonic distortion is defined as

    ------ (6)

    Analogously, Current distortion factor CDF, further known as

    Current total harmonic distortion is defined as

    ------(7)

    Where V1, I1 represent the fundamental peak voltage and curren

    respectively. With

    ------ (8)

    A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297

    ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 293

  • 8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

    5/8

    the apparent power is

    ----(9)

    Where S1 is the apparent power at fundamental frequency and

    the power factor is

    ----(10)

    A.Harmonic phase sequences

    The phase sequences of harmonic waveforms at

    different frequencies are compared with the fundamental

    waveform and are classified as positive, zero and negative

    sequence harmonics. Harmonics such as the 7th, which "rotate"

    with the same sequence as the fundamental, are called positive

    sequence. Harmonics such as the 5th, which "rotate" in the

    opposite sequence as the fundamental, are called negative

    sequence. Triplen harmonics which don't "rotate" at all because

    they're in phase with each other are called zero sequence.

    In a balanced three-phase power system, the currents in phases

    a-b-c are shifted in time by +/-120 degrees of fundamental.

    Therefore, since

    ----- (11)

    then the currents in phases b and c lag and lead by 2/3 radians,

    respectively. Thus

    -----(12)

    Expanding the above series,

    By examining the current equations, it can be seen that

    i) The first harmonic (i.e., the fundamental) is positive sequence

    (a-b-c) because phase b lags phase a by 120, and phase c leads

    phase a by 120,

    ii) The second harmonic is negative sequence (a-c-b) because

    phase b leads phase a by 120, and phase c lags phase a by 120,iii) The third harmonic is zero sequence because all three phases

    have the same phase angle.

    All harmonic multiples of three (i.e., the triplens) are zero

    sequence. The next harmonic above a triplen is positive

    sequence; the next harmonic below a triplen is negative

    sequence[5],[6],[7].

    IV. FUZZY BASED CLASSIFICATION

    Fuzzy logic (FL) can be defined as a problem-solving

    control system methodology that lends itself to implementation

    in systems ranging from simple, small, embedded micro-controllers to large, networked, multi-channel PC or

    workstation-based data acquisition and control systems. Fuzzy

    based classification technique employs a simple, rule-based IF X

    AND Y THEN Z approach to a solving control problem rather

    than attempting to model a system mathematically.

    In the case of Neural Networks, considerable amount of

    training time under different operating conditions is required for

    good performance of the system. The fuzzy logic based fault

    classification scheme does not require training and so it is

    computationally much faster when compared to fault

    classification by Artificial Neural Network (ANN) methods

    This fuzzy logic based scheme is capable of accurately

    predicting the exact type of fault under wide range of operating

    conditions [9].

    A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297

    ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 294

  • 8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

    6/8

    The Fault Classification is based on Angular

    differences among the sequence components of the fundamental

    during fault current as well as on their relative magnitudes. The

    phasor diagram of a phase a to ground fault is shown in the

    Figure 6. The zero, positive and negative sequence components

    of the post fault currents relative to phase a are denoted as Iaof,

    Ia1f

    and Ia2f

    respectively.

    Fig 6. Phasor diagram for L-G fault

    The angles between the positive and negative sequence

    components of phase a, b and c are given as

    ---(13)

    The magnitudes of Iaof,

    Ia1f

    and Ia2f

    are related by

    Rof

    =| Iaof,

    / Ia1f

    | = 1 and R2f

    =| Ia2f,

    / Ia1f

    | = 1 ----(14)

    Similarly, the magnitudes and angle between the positive and

    negative sequence components are obtained for other types of

    asymmetric faults.

    For every type of fault, there exists a unique set of these

    five parameters. So it is possible to formulate simple logic base

    for determining the fault type from the values of the five inputs.

    The different inputs are represented by a corresponding fuzzy

    variable. Now a fuzzy rule was developed using these five

    variables to detect the type of fault.

    For example:

    If arg_A is approximately 300

    and arg_B is approximately

    1500

    and arg_C is approximately 1500

    and Rof

    is high and

    Rsf

    is high then fault type is a-g

    In this method, only 3 parameters are sufficient and it

    identifies 10 types of short-circuit faults accurately. But the main

    disadvantage with this method is that it is applicable to only

    asymmetric faults and it is not very effective if you are looking

    to classify not just by the type of fault.

    V. SIMULATION RESULTS

    A. POWER QUALITY AND POWER SYSTEM EVENTS

    The term power quality refers to a wide variety of

    electromagnetic phenomena that characterize the voltage and

    current at a given time and at a given location on the power

    system. A power system event is a recorded (or observed)

    current or voltage excursion outside the predetermined

    monitoring equipment thresholds. A power disturbance is a

    recorded (or observed) current or voltage excursion (event)

    which results in an undesirable reaction in the electrica

    environment or electronic equipment or systems. The term

    power problem refers to a set of disturbances or conditions that

    produce undesirable results for equipment, systems or a facility.

    The term event is typically used to describe significant and

    sudden deviations of voltage or current from its normal or idealwaveform (like in Fig 7.1) unlike the term variation which is

    used to describe small deviations from the nominal values. The

    monitoring of events is done using certain triggering thresholds.

    Voltage or current variations are obtained by continuous

    monitoring as shown in Fig 7.2.

    Fig 7.1: Measurement of current during a fault

    Fig 7.2: RMS voltage measurement for one day

    A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297

    ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 295

  • 8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

    7/8

    B. CASE STUDY: INDUCTION MOTOR STARTING

    Starting of large induction motors is one more cause of voltage

    dips. It has been concern for designers of industrial power

    systems. During start-up an induction motor takes current five to

    six times larger than normal. This current remains high until the

    motor reaches its nominal speed. This lasts between several

    seconds to one minute. The characteristics of the correspondingvoltage dip depend on the characteristics of the induction motor

    (size, starting method, load, etc) and the strength of the system at

    the point where the motor is connected. The magnitude of the

    dip depends strongly on the system parameters. For the system

    in Fig.8, Z0 is the source impedance and ZM the motor

    impedance during starting. The voltage experienced at PCC is

    found from the voltage divider equation:

    where E is the source voltage. The magnitude of voltage dips

    due to motor starting is rarely deeper than 0.85 pu.

    Fig. 8: Voltage divider model for the calculation of voltage dip

    during motor starting

    The duration of the voltage dip due to motor starting

    depends on a number of motor parameters. The most important

    of them is the motor inertia. The duration of the dip is prolonged

    if other motor loads are connected to the same bus bar, as they

    will further keep the voltage down. Fig.9(a) and 9(b) shows the

    fundamental frequency magnitude of the three phases during the

    connection of a 500 HP induction motor on a 480 V bus as

    simulated in MATLAB.

    The short circuit level of the bus bar is 30 MVA. The

    initial drop in voltage is 0.09 pu and it takes approximately 400

    msec for voltage to reach its steady state value. This voltage dipis symmetrical, all three phases drop equally and then recover

    gradually in a similar way because the starting current of the

    motor is the same for all three phases. A measurement of a

    voltage dip due to induction motor starting is shown in Fig10(a)

    and 10.(b). The measurement comes from a low voltage

    network. The three phases present exactly the same

    characteristics. The voltage recovers within 7-8 cycles

    Summarizing, voltage dips due to induction motor starting are:

    Non-rectangular: voltage recovers gradually.

    Symmetrical: all phases present the same behavior.

    Figure 9 (a)

    Figure 9 (b)

    Fig. 9: Induction motor starting (a) Voltage waveforms (b)

    Voltage magnitude (measurement in a 400 V network)

    Figure 10(a)

    A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297

    ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 296

  • 8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297

    8/8

    Figure 10 (b)

    Fig. 10: Influence of induction motor load during a fault (a)

    Non-rectangular (b) Symmetrical

    V. CONCLUSION

    This paper gives an overall view to diagnose the of power

    quality problem. A brief discussion on the harmonic distortion

    and their impacts on electric power quality are mentioned.

    Harmonic distortion has a harmful effect on both distribution

    system equipment and on loads. Because of this, harmonic

    distortion is a main cause of supply quality degradation. If

    harmonic distortion exceeds some limits, then equipment is

    needed for its suppression. Equipment for harmonic suppression

    should also compensate the reactive current thereby improving

    both power factor and supply quality.

    The main idea of this approach is to map the power quality

    disturbance features in to real valued number though extended

    fuzzy reasoning, in terms of which the PQ disturbance

    waveforms are identified according to boundary values.

    A study was conducted using MATLAB to investigate

    the response of induction motor to voltage dips. Motor response

    to the applied voltage dips show that the motor can support most

    commonly encountered voltage dips. It has been demonstratedthat the dynamic behavior of induction motors is sensitive to the

    values of the motor parameters.

    VI. REFERENCES

    [1] L. M. Tolbert, Harmonic Analysis of Electrical Distribution

    Systems, Oak Ridge National Laboratory, ORNL-6887, March

    1996.

    [2] L. M. Tolbert, H. Hollis, P. S. Hale, Survey of Harmonics

    Measurements in Electrical Distribution Systems, Conf. Record

    of the 1996 IAS Annual Meeting.

    [3] IEEE Task Force, Effects of harmonics on equipment,

    IEEE Trans. Power Delivery, vol. 8, pp. 672-680, Apr. 1993.

    [4] IEEE Emerald Book, IEEE Recommended Practice for

    Powering and Grounding Sensitive Electronic Equipment, IEEE

    Std 1100-1992.

    [5] National Electrical Code, NFPA Std 70-1996.

    [6] IEEE Recommended Practice for Establishing Transformer

    Capability When Supplying Non sinusoidal Load Currents

    ANSI/IEEE Std. C57.110-1986.

    [7] Arrillaga.J., Bradley, D.A., and Bodger, P.S.: Power System

    Harmonics, John Wiley,1985

    [8] Guideline on Electrical Power for ADP Installations, Federa

    Information Processing Standard Publications 94, NationalBureau of Standards, 1983.

    [9] P.K.Dash, M.M.A.Salama, S.Mishra, and A.C. Liew

    Classification of power system disturbances using a fuzzy

    expert system and a Fourier linear combiner, IEEE

    Transactions on Power Delivery, vol. 15, no. 2, pp. 472

    477,April 2000.

    A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297

    ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 297