19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert...
-
Upload
helpdesk9532 -
Category
Documents
-
view
218 -
download
0
Transcript of 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert...
-
8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297
1/8
A new approach to Diagnosis of Power Quality
Problems using Expert System
A.N.Malleswara Rao Dr. K. Ramesh Reddy Dr. B. V. Sanker RamResearch Scholar Dean & HoD, EEE Dept. Professor, EEE Dept.,
JNTUH, Hyderabad GNITS, Hyderabad JNTUH, [email protected] [email protected]
Abstract: In this paper, a new approach is presented to identify
power quality disturbances using fuzzy logic systems. Distributed
single phase power electronic loads are usually treated as fixed
harmonic current injectors in distribution system. Their current
harmonics are characterized by normalized phasors |Ih/I1|angle h,
where the fundamental current component I1 is varied
proportionally with load power. Fixed harmonic current injection
lead to an over estimation of resulting voltage harmonics because it
neglects phase angle, dispersion of individual current harmonics.
Harmonic currents generated by single phase power electronicloads too small to cause any appraisable distribution feeders.
However as the number of these loads increases and as larger
nonlinear loads the cumulative harmonics becomes very significant.
Fuzzy logic is used to diagnose all these problems. Detailed digital
simulation results involving various types of transient power
quality disturbances are presented to prove the ability of the new
approach in classifying these disturbances..
Index TermsFuzzy logic, power system harmonics, Power
quality, Fault analysis
I. INTRODUCTION
Harmonic is a core issue regarding Power Quality. It is
not only pollutes the power system but also have negative effects
on electrical equipments. With increasing use of power
electronics in industrial, commercial, and residential consumers,
the issue of harmonics and their effects on performance of
electrical installation and electronic equipment increases [1].
The objective of the electric utility is to deliver sinusoidal
voltage at fairly constant magnitude throughout their system.
This objective is complicated by the fact that there are loads on
the system that produce harmonic currents. These currents
results in distorted voltage and current that can adversely impact
the system performance in different ways. A number of
harmonic producing loads have increased over the years, it has become increased necessary to address their influence when
making any additional or changes to an installation.
The fundamental or basic power frequency is 50 Hertz. This
means the waveform of the electricity repeats itself 50 times
every second. The characteristic harmonics are based on number
of rectifiers (pulse number) used in a circuit &can be determined
by the following equation
h= (n*p) 1 ---- (1)
where n=an integer (1, 2, 3, 4, 5.)
p=number of pulse or rectifiers
A pure AC sine wave is ideal, such as shown in figure 1(a), and
is obtained if the load is an incandescent light bulb.
Fig 1(a) Ideal AC sine wave
In a three phase system, three sine waves are generated120
degrees apart, as shown in figure 1(b)
Fig1(b).Three phase system
Harmonic frequencies are multiples of the fundamenta
frequency. Any distorted voltage or current wave is the sum of
the fundamental frequency and a number of the above
harmonics. Figure 2(a) shows the fundamental and the third
harmonic. Figure 2(b) demonstrates the addition of the harmonic
and the fundamental frequency.
A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297
ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 290
mailto:[email protected]:[email protected] -
8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297
2/8
Fig 2(a).Fundamental and the third harmonic wave forms
Fig 2(b).Combined waveform of fundamental and third
harmonic component.
II. BACKGROUND HISTORY
The voltage pushing that current through the load
circuit is described in terms of frequency and amplitude. The
frequency of the current will be identical to the frequency of the
voltage as long as the load impedance does not change. In a
linear load, like a resistor, capacitor or inductor, current and
voltage will have the same frequency. As long as the
characteristics of the load components do not change, the
frequency component of the current will not change. But in case
of non-linear loads such as switching power supplies, saturated
transformers, charged capacitors, and converters used in drives,
the characteristics of the load are dynamic. As the amplitude of
the voltage changes and the load impedance changes, the
frequency of the current will change. The changing current and
resulting complex waveform is a result of these load changes.
The complex current waveform can be described by defining
each component of the waveform. The frequencies that are
normally dealt with using drives are 50 or 60 Hz. By definition,
these frequencies are termed fundamental in their respective
distribution systems.
The drawing shown indicates how current follows the
frequency when the load is linear only a phase angle change isshown in Fig 3.
Fig 3. Current follows the frequency when the load is linear and
phase angle change.
When the load become non-linear, the current is not continuous
and will contain many frequencies. Figure 4 shows how the
current might look like in a non-linear circuit.
Fig 4.Line current in non-linear circuit
A. Source of Harmonics
Harmonic load currents are generated by all non-linear loads
These include single phase loads, e.g.
Switched mode power supplies (SMPS) Electronic fluorescent lighting ballasts Small uninterruptible power supplies (UPS) units
Three phase loads, e.g.
Variable speed drives Large UPS units Highly Fluxed Iron Cores
B.Problems caused by harmonics
Harmonic currents cause problems both on the supply and
within the installation. The effects and the solutions are very
different and need to be addressed separately; the measures that
are appropriate to controlling the effects of harmonics within the
installation may not necessarily reduce the distortion caused on
the supply and vice versa [2]. There are several common
problem areas caused by harmonics:
1) Overloading of neutrals
In a three-phase system the voltage waveform from each phase
to the neutral star point is displaced by 120so that, when each
phase is equally loaded, the combined current in the neutral is
zero. In the past, installers have taken advantage of this fact by
installing half-sized neutral conductors. However, although the
fundamental currents cancel out, the harmonic currents do not -
A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297
ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 291
-
8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297
3/8
in fact those that are an odd multiple of three times the
fundamental, the triple-N harmonics, add in the neutral.
2) Overheating of transformers
Transformers are affected in two ways by harmonics. Firstly, the
eddy current losses, normally about 10 % of the loss at full load,
increase with the square of the harmonic number. This results in
a much higher operating temperature and a shorter life. The
second effect concerns the triple-N harmonics. When reflected back to a delta winding they are all in phase, so the triple-N
harmonic currents circulate in the winding. The triple-N
harmonics are effectively absorbed in the winding and do not
propagate onto the supply, so delta wound transformers are
useful as isolating transformers.
3) False tripping of circuit breakers
Residual current circuit breakers (RCCB) operate by summing
the current in the phase and neutral conductors and, if the result
is not within the rated limit, disconnecting the power from the
load. False tripping can occur in the presence of harmonics for
two reasons. Firstly, the RCCB, being an electromechanical
device, may not sum the higher frequency components correctly
and therefore trips erroneously. Secondly, the kind of equipment
that generates harmonics also generates switching noise that
must be filtered at the equipment power connection.
4) Over-stressing of power factor correction capacitors
Power factor correction capacitors are provided in order to draw
a current with a leading phase angle to offset lagging current
drawn by an inductive load such as induction motors. The
impedance of the PFC capacitor reduces as frequency rises,
while the source impedance is generally inductive and increases
with frequency. The capacitor is therefore likely to carry quite
high harmonic currents and, unless it has been specificallydesigned to handle them, damage can result. A potentially more
serious problem is that the capacitor and the stray inductance of
the supply system can resonate at or near one of the harmonic
frequencies when it occurred, very large voltages and currents
can be generated, often leading to the catastrophic failure of the
capacitor system [4].
C.Problems caused by harmonic voltages:
1) Voltage distortion:
Because the supply has source impedance, harmonic load
currents give rise to harmonic voltage distortion on the voltage
waveform (this is the origin of flat topping). There are two
elements to the impedance: that of the internal cabling from the
point of common coupling (PCC), and that inherent in the
supply at the PCC, e.g. the local supply transformer. The
distorted load current drawn by the non-linear load causes a
distorted voltage drop in the cable impedance. The resultant
distorted voltage waveform is applied to all other loads
connected to the same circuit, causing harmonic currents to flow
in them - even if they are linear loads. Here separate circuits
feed the linear and non-linear loads from the point of common
coupling, so that the voltage distortion caused by the non-linear
load does not affect the linear load.
2) Induction motorsHarmonic voltage distortion causes increased eddy
current losses in motors in the same way as in transformers
However, additional losses arise due to the generation of
harmonic fields in the stator, each of which is trying to rotate the
motor at a different speed either forwards or backwards. High
frequency currents induced in the rotor further increase losses.
3) Zero-crossing noise
Many electronic controllers detect the point at which the supply
voltage crosses zero volts to determine when loads should be
turned on. This is done because switching reactive loads at zero
voltage does not generate transients, so reducing electromagnetic
interference (EMI) and stress on the semiconductor switching
devices. When harmonics or transients are present on the supply
the rate of change of voltage at the crossing becomes faster and
more difficult to identify, leading to erratic operation. There may
in fact be several zero-crossings per half cycle.
D.Problems caused when harmonic currents reach the supply
When a harmonic current is drawn from the supply it gives rise
to a harmonic voltage drop proportional to the source impedance
at the point of common coupling (PCC) and the current. Since
the supply network is generally inductive, the source impedance
is higher at higher frequencies[5]. Of course, the voltage at the
PCC is already distorted by the harmonic currents drawn byother consumers and by the distortion inherent in transformers,
and each consumer makes an additional contribution.
III. ELECTRICAL EQUIVALENT OF POWER
SYSYTEMS:
The equivalent circuit of a non-linear load is shown in Figure 5
It can be modeled as a linear load in parallel with a number of
current sources, one source for each harmonic frequency. The
harmonic currents generated by the load or more accurately
converted by the load from fundamental to harmonic current
have to flow around the circuit via the source impedance and all
other parallel paths. As a result, harmonic voltages appear across
the supply impedance and are present throughout the
installation. Source impedances influence the harmonic voltage
distortion resulting from a harmonic current.
A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297
ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 292
-
8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297
4/8
Fig 5. Equivalent circuit of Non-linear load
Whenever harmonics are suspected, or when trying to verify
their absence, the current must be measured.
The Fourier series represents an effective way to study
and analyze harmonic distortion. It allows inspecting the various
constituents of distorted waveform through decomposition.
Generally, any periodic wave form can be expanded in the form
of a Fourier series
----(2)
Measures of Harmonic distortion:
A distorted periodic current or voltage waveform expanded into
a Fourier series is expressed as follows
------ (3)
Accordingly, the following relationship for active power andreactive power supply are
----- (4)
Reactive power is defined as
----- (5)
Voltage distortion factor VDF, also known as voltage total
harmonic distortion is defined as
------ (6)
Analogously, Current distortion factor CDF, further known as
Current total harmonic distortion is defined as
------(7)
Where V1, I1 represent the fundamental peak voltage and curren
respectively. With
------ (8)
A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297
ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 293
-
8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297
5/8
the apparent power is
----(9)
Where S1 is the apparent power at fundamental frequency and
the power factor is
----(10)
A.Harmonic phase sequences
The phase sequences of harmonic waveforms at
different frequencies are compared with the fundamental
waveform and are classified as positive, zero and negative
sequence harmonics. Harmonics such as the 7th, which "rotate"
with the same sequence as the fundamental, are called positive
sequence. Harmonics such as the 5th, which "rotate" in the
opposite sequence as the fundamental, are called negative
sequence. Triplen harmonics which don't "rotate" at all because
they're in phase with each other are called zero sequence.
In a balanced three-phase power system, the currents in phases
a-b-c are shifted in time by +/-120 degrees of fundamental.
Therefore, since
----- (11)
then the currents in phases b and c lag and lead by 2/3 radians,
respectively. Thus
-----(12)
Expanding the above series,
By examining the current equations, it can be seen that
i) The first harmonic (i.e., the fundamental) is positive sequence
(a-b-c) because phase b lags phase a by 120, and phase c leads
phase a by 120,
ii) The second harmonic is negative sequence (a-c-b) because
phase b leads phase a by 120, and phase c lags phase a by 120,iii) The third harmonic is zero sequence because all three phases
have the same phase angle.
All harmonic multiples of three (i.e., the triplens) are zero
sequence. The next harmonic above a triplen is positive
sequence; the next harmonic below a triplen is negative
sequence[5],[6],[7].
IV. FUZZY BASED CLASSIFICATION
Fuzzy logic (FL) can be defined as a problem-solving
control system methodology that lends itself to implementation
in systems ranging from simple, small, embedded micro-controllers to large, networked, multi-channel PC or
workstation-based data acquisition and control systems. Fuzzy
based classification technique employs a simple, rule-based IF X
AND Y THEN Z approach to a solving control problem rather
than attempting to model a system mathematically.
In the case of Neural Networks, considerable amount of
training time under different operating conditions is required for
good performance of the system. The fuzzy logic based fault
classification scheme does not require training and so it is
computationally much faster when compared to fault
classification by Artificial Neural Network (ANN) methods
This fuzzy logic based scheme is capable of accurately
predicting the exact type of fault under wide range of operating
conditions [9].
A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297
ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 294
-
8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297
6/8
The Fault Classification is based on Angular
differences among the sequence components of the fundamental
during fault current as well as on their relative magnitudes. The
phasor diagram of a phase a to ground fault is shown in the
Figure 6. The zero, positive and negative sequence components
of the post fault currents relative to phase a are denoted as Iaof,
Ia1f
and Ia2f
respectively.
Fig 6. Phasor diagram for L-G fault
The angles between the positive and negative sequence
components of phase a, b and c are given as
---(13)
The magnitudes of Iaof,
Ia1f
and Ia2f
are related by
Rof
=| Iaof,
/ Ia1f
| = 1 and R2f
=| Ia2f,
/ Ia1f
| = 1 ----(14)
Similarly, the magnitudes and angle between the positive and
negative sequence components are obtained for other types of
asymmetric faults.
For every type of fault, there exists a unique set of these
five parameters. So it is possible to formulate simple logic base
for determining the fault type from the values of the five inputs.
The different inputs are represented by a corresponding fuzzy
variable. Now a fuzzy rule was developed using these five
variables to detect the type of fault.
For example:
If arg_A is approximately 300
and arg_B is approximately
1500
and arg_C is approximately 1500
and Rof
is high and
Rsf
is high then fault type is a-g
In this method, only 3 parameters are sufficient and it
identifies 10 types of short-circuit faults accurately. But the main
disadvantage with this method is that it is applicable to only
asymmetric faults and it is not very effective if you are looking
to classify not just by the type of fault.
V. SIMULATION RESULTS
A. POWER QUALITY AND POWER SYSTEM EVENTS
The term power quality refers to a wide variety of
electromagnetic phenomena that characterize the voltage and
current at a given time and at a given location on the power
system. A power system event is a recorded (or observed)
current or voltage excursion outside the predetermined
monitoring equipment thresholds. A power disturbance is a
recorded (or observed) current or voltage excursion (event)
which results in an undesirable reaction in the electrica
environment or electronic equipment or systems. The term
power problem refers to a set of disturbances or conditions that
produce undesirable results for equipment, systems or a facility.
The term event is typically used to describe significant and
sudden deviations of voltage or current from its normal or idealwaveform (like in Fig 7.1) unlike the term variation which is
used to describe small deviations from the nominal values. The
monitoring of events is done using certain triggering thresholds.
Voltage or current variations are obtained by continuous
monitoring as shown in Fig 7.2.
Fig 7.1: Measurement of current during a fault
Fig 7.2: RMS voltage measurement for one day
A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297
ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 295
-
8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297
7/8
B. CASE STUDY: INDUCTION MOTOR STARTING
Starting of large induction motors is one more cause of voltage
dips. It has been concern for designers of industrial power
systems. During start-up an induction motor takes current five to
six times larger than normal. This current remains high until the
motor reaches its nominal speed. This lasts between several
seconds to one minute. The characteristics of the correspondingvoltage dip depend on the characteristics of the induction motor
(size, starting method, load, etc) and the strength of the system at
the point where the motor is connected. The magnitude of the
dip depends strongly on the system parameters. For the system
in Fig.8, Z0 is the source impedance and ZM the motor
impedance during starting. The voltage experienced at PCC is
found from the voltage divider equation:
where E is the source voltage. The magnitude of voltage dips
due to motor starting is rarely deeper than 0.85 pu.
Fig. 8: Voltage divider model for the calculation of voltage dip
during motor starting
The duration of the voltage dip due to motor starting
depends on a number of motor parameters. The most important
of them is the motor inertia. The duration of the dip is prolonged
if other motor loads are connected to the same bus bar, as they
will further keep the voltage down. Fig.9(a) and 9(b) shows the
fundamental frequency magnitude of the three phases during the
connection of a 500 HP induction motor on a 480 V bus as
simulated in MATLAB.
The short circuit level of the bus bar is 30 MVA. The
initial drop in voltage is 0.09 pu and it takes approximately 400
msec for voltage to reach its steady state value. This voltage dipis symmetrical, all three phases drop equally and then recover
gradually in a similar way because the starting current of the
motor is the same for all three phases. A measurement of a
voltage dip due to induction motor starting is shown in Fig10(a)
and 10.(b). The measurement comes from a low voltage
network. The three phases present exactly the same
characteristics. The voltage recovers within 7-8 cycles
Summarizing, voltage dips due to induction motor starting are:
Non-rectangular: voltage recovers gradually.
Symmetrical: all phases present the same behavior.
Figure 9 (a)
Figure 9 (b)
Fig. 9: Induction motor starting (a) Voltage waveforms (b)
Voltage magnitude (measurement in a 400 V network)
Figure 10(a)
A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297
ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 296
-
8/6/2019 19.IJAEST Vol No 7 Issue No 2 a New Approach to Diagnosis of Power Quality Problems Using Expert System 290 297
8/8
Figure 10 (b)
Fig. 10: Influence of induction motor load during a fault (a)
Non-rectangular (b) Symmetrical
V. CONCLUSION
This paper gives an overall view to diagnose the of power
quality problem. A brief discussion on the harmonic distortion
and their impacts on electric power quality are mentioned.
Harmonic distortion has a harmful effect on both distribution
system equipment and on loads. Because of this, harmonic
distortion is a main cause of supply quality degradation. If
harmonic distortion exceeds some limits, then equipment is
needed for its suppression. Equipment for harmonic suppression
should also compensate the reactive current thereby improving
both power factor and supply quality.
The main idea of this approach is to map the power quality
disturbance features in to real valued number though extended
fuzzy reasoning, in terms of which the PQ disturbance
waveforms are identified according to boundary values.
A study was conducted using MATLAB to investigate
the response of induction motor to voltage dips. Motor response
to the applied voltage dips show that the motor can support most
commonly encountered voltage dips. It has been demonstratedthat the dynamic behavior of induction motors is sensitive to the
values of the motor parameters.
VI. REFERENCES
[1] L. M. Tolbert, Harmonic Analysis of Electrical Distribution
Systems, Oak Ridge National Laboratory, ORNL-6887, March
1996.
[2] L. M. Tolbert, H. Hollis, P. S. Hale, Survey of Harmonics
Measurements in Electrical Distribution Systems, Conf. Record
of the 1996 IAS Annual Meeting.
[3] IEEE Task Force, Effects of harmonics on equipment,
IEEE Trans. Power Delivery, vol. 8, pp. 672-680, Apr. 1993.
[4] IEEE Emerald Book, IEEE Recommended Practice for
Powering and Grounding Sensitive Electronic Equipment, IEEE
Std 1100-1992.
[5] National Electrical Code, NFPA Std 70-1996.
[6] IEEE Recommended Practice for Establishing Transformer
Capability When Supplying Non sinusoidal Load Currents
ANSI/IEEE Std. C57.110-1986.
[7] Arrillaga.J., Bradley, D.A., and Bodger, P.S.: Power System
Harmonics, John Wiley,1985
[8] Guideline on Electrical Power for ADP Installations, Federa
Information Processing Standard Publications 94, NationalBureau of Standards, 1983.
[9] P.K.Dash, M.M.A.Salama, S.Mishra, and A.C. Liew
Classification of power system disturbances using a fuzzy
expert system and a Fourier linear combiner, IEEE
Transactions on Power Delivery, vol. 15, no. 2, pp. 472
477,April 2000.
A.N.Malleswara Rao* et al. / (IJAEST) INTERNATIONAL JOURNAL OF ADVANCED ENGINEERING SCIENCES AND TECHNOLOGIESVol No. 7, Issue No. 2, 290 - 297
ISSN: 2230-7818 @ 2011 http://www.ijaest.iserp.org. All rights Reserved. Page 297