CONTROL PANELSRANGE OF PANELS FOR CONTROL ANDPROTECTION OF LOWARA ELECTRIC PUMPS
50/60 Hz50/60 Hz50/60 Hz50/60 Hz50/60 Hz
CCCCCod.od.od.od.od. 191007691 R 191007691 R 191007691 R 191007691 R 191007691 Revevevevev.A.A.A.A.A Ed.12/2011 Ed.12/2011 Ed.12/2011 Ed.12/2011 Ed.12/2011
3
QSMQSMQSMQSMQSM Series ..........................................................................................................................................55555QPCQPCQPCQPCQPC Series ...........................................................................................................................................66666QPCQPCQPCQPCQPCSSSSS Series .........................................................................................................................................77777QSCQSCQSCQSCQSC Series ...........................................................................................................................................88888QSCQSCQSCQSCQSC Series (60 Hz) ...............................................................................................................................99999QSCQSCQSCQSCQSCSSSSS Series ...................................................................................................................................1010101010QSCQSCQSCQSCQSCSSSSS Series (60 Hz) .......................................................................................................................1111111111QMQMQMQMQM Series .......................................................................................................................................1212121212QTDQTDQTDQTDQTD Series ......................................................................................................................................1313131313Q3DQ3DQ3DQ3DQ3D Series ......................................................................................................................................1414141414Q3YQ3YQ3YQ3YQ3Y Series ......................................................................................................................................1515151515Q3IQ3IQ3IQ3IQ3I Series .......................................................................................................................................1616161616Q3AQ3AQ3AQ3AQ3A Series ......................................................................................................................................1717171717Q3SFQ3SFQ3SFQ3SFQ3SF Series ....................................................................................................................................1818181818
CONTENTSCONTENTSCONTENTSCONTENTSCONTENTS
4
QDRMQDRMQDRMQDRMQDRM Series .................................................................................................................................1919191919QDRMCQDRMCQDRMCQDRMCQDRMC Series ...............................................................................................................................2020202020QDRQDRQDRQDRQDR Series .....................................................................................................................................2121212121QGMCQGMCQGMCQGMCQGMC Series .................................................................................................................................2222222222QDRM2QDRM2QDRM2QDRM2QDRM2 Series ...............................................................................................................................2323232323QYRQYRQYRQYRQYR Series .....................................................................................................................................2424242424QDRMC2QDRMC2QDRMC2QDRMC2QDRMC2 Series ............................................................................................................................2626262626QDR2QDR2QDR2QDR2QDR2 Series ..................................................................................................................................2727272727QYR2QYR2QYR2QYR2QYR2 Series ..................................................................................................................................2828282828QXR20QXR20QXR20QXR20QXR20 Series ................................................................................................................................3030303030QCL5QCL5QCL5QCL5QCL5 Series ...................................................................................................................................3131313131QCL10QCL10QCL10QCL10QCL10 Series .................................................................................................................................3232323232QCLP10QCLP10QCLP10QCLP10QCLP10 Series ...............................................................................................................................3333333333KSLKSLKSLKSLKSL Series ......................................................................................................................................3434343434DPFDPFDPFDPFDPF, VR, VR, VR, VR, VR, SCA3, SCA3, SCA3, SCA3, SCA3 Series ..................................................................................................................3535353535KIT RILS20KIT RILS20KIT RILS20KIT RILS20KIT RILS20 Series .........................................................................................................................3636363636
5
QSM SeriesQSM SeriesQSM SeriesQSM SeriesQSM Series
Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a single-phase submersible electric pump for 4” wells
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALFEAFEAFEAFEAFEATURESTURESTURESTURESTURES• QSM PF version with overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Main switch for manual control.• Supply voltage: 1 x 220-240 V ±5%.• Frequency: 50 Hz.• Power: 0,25 to 1,1 kW.• Direct motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Incorporated capacitor.• Thermal protection with motor protector inside the panel.
SERIE QSM
MODEL RATED RATED CAPACITOR WEIGHT
VOLTAGE CURRENT 450V A B C
V kW HP A uF mm mm mm Kg
QSM 02 220-240 0,25 0,33 2,6 12,5 80 210 65 0,45
QSM 03 220-240 0,37 0,5 3,4 16 80 210 65 0,45
QSM 05 220-240 0,55 0,75 4,8 20 80 210 65 0,45
QSM 07 220-240 0,75 1 6,5 30 80 210 65 0,45
QSM 11 220-240 1,1 1,5 8,3 40 80 210 65 0,45
CB-QSM-en_c_te
RATED
POWER
DIMENSIONS
I
0
A
B
C
6
Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
QPC SeriesQPC SeriesQPC SeriesQPC SeriesQPC Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a single-phase submersible electric pump for 4” wells.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• DPF single-phase module for overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Main switch for manual control.• Supply voltage: 1 x 230 V ±10%.• Frequency: 50 Hz.• Power: 0,25 to 2,2 kW.• Direct motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted with fins.• Plastic enclosure.• Incorporated capacitor.• Main switch with manual-reset thermal protection and power indicator light.
SERIE QPC
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QPC/02 1 x 230 V ± 10 % 0,25 0,33 3 170 170 75 1,1
QPC/03 1 x 230 V ± 10 % 0,37 0,5 4 170 170 75 1,1
QPC/05 1 x 230 V ± 10 % 0,55 0,75 5 170 170 75 1,1
QPC/07 1 x 230 V ± 10 % 0,75 1 6 170 170 75 1,1
QPC/11 1 x 230 V ± 10 % 1,1 1,5 9 170 170 75 1,1
QPC/15 1 x 230 V ± 10 % 1,5 2 11 170 170 75 1,1
QPC/22 1 x 230 V ± 10 % 2,2 3 16 170 170 127 1,2
CB-QPC-en_a_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
CAPACITOR
µF/450V
12,5
16
70
20
30
40
50
ATTENZIONE !
TOGLIERE TENSIONE PRIMA DI APRIRE
DISCONNECT THE POWER BEFORE OPENING
VOR DEM OFFNEN NETZSTECKER ABSCHALTEN
DEBRANCHER LA LIGNE AVANT OUVRIR LE COFFRET
DANGER!
ACHTUNG GEFAHR!
DANGER!
DESCONETAR TENSION ANTES DE ABRIR
ATENCION!
I
0
A
B
C
7
Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
QPCQPCQPCQPCQPCS SeriesS SeriesS SeriesS SeriesS Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a single-phase submersible electric pump for 4” wells.
• Main switch with manual-reset thermal protection and power indicator light.• Power, pump running, level control LED.• Overvoltage discharges.• Dry running control through probes or float or minimum pressure switch.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Set of 3 electrodes (probes) without cable.• Float.• Pressure switch.
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through an external enable contact.• Supply voltage: 1 x 230 V ±10%.• Frequency: 50 Hz.• Power: 0,25 to 2,2 kW.• 12 V AC low-voltage auxiliary circuit.• Direct motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted with fins.• Plastic enclosure with transparent cover.• Incorporated capacitor.
SERIE QPCS
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QPCS/02 1 x 230 V ± 10 % 0,25 0,33 3 200 150 80 1,3
QPCS/03 1 x 230 V ± 10 % 0,37 0,5 4 200 150 80 1,3
QPCS/05 1 x 230 V ± 10 % 0,55 0,75 5 200 150 80 1,3
QPCS/07 1 x 230 V ± 10 % 0,75 1 6 200 150 80 1,3
QPCS/11 1 x 230 V ± 10 % 1,1 1,5 9 200 150 80 1,3
QPCS/15 1 x 230 V ± 10 % 1,5 2 11 200 150 80 1,3
QPCS/22 1 x 230 V ± 10 % 2,2 3 16 200 150 80 1,3
CB-QPCS-en_a_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
CAPACITOR
µF/450V
12,5
16
70
20
30
40
50
Elektroden Empfindlikeit
ElectrodesSensibilitè
ProbesSensitivity
SondeSensibilità
Temporizzatore Timer Temporisation Zeiteinstellung
Marcia Run Marche Betriebe
Blocco livello Lack of water Manque d'eau Wassermangel
Linea Main supply Tension Stromversorgung
I GB F D
InterruttoreGeneraleProtezioneTermica
MainSwitchThermalOverload
InterrupteurGeneralProtectionMoteur
Attenzione : togliere tensione prima di aprire !Danger : disconnect power before opening !Danger : debrancher la ligne avant ouvrir le coffret !Achtung Gefahr : vor dem offnen Netzstecker abshalten!
HauptshalterUberlastungThermischerShutz
I
0
A
B
C
8
SERIE QSC
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QSC/02 1 x 230 V ± 10 % 0,25 0,33 2,5 ÷ 4 205 220 160 1,7
QSC/03 1 x 230 V ± 10 % 0,37 0,5 4 ÷ 6,3 205 220 160 1,7
QSC/05 1 x 230 V ± 10 % 0,55 0,75 4 ÷ 6,3 205 220 160 1,7
QSC/07 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 205 220 160 1,7
QSC/11 1 x 230 V ± 10 % 1,1 1,5 6,3 ÷ 10 205 220 160 1,7
QSC/15 1 x 230 V ± 10 % 1,5 2 10 ÷ 16 205 220 160 1,7
QSC/22 1 x 230 V ± 10 % 2,2 3 16 ÷ 20 205 220 160 2,7
QSC/40 1 x 230 V ± 10 % 4 5,5 25 ÷ 32 280 220 160 3
CB-QSC-en_d_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
CAPACITOR
µF/450V
12,5
30
20
90
16
40
50
70
Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
QSC SeriesQSC SeriesQSC SeriesQSC SeriesQSC Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a single-phase submersible electric pump for 4” wells.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• DPF single-phase module for overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Main switch for manual control.• Supply voltage: 1 x 230 V ±10%.• Frequency: 50 Hz.• Power: 0,25 to 4 kW.• Direct motor start.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Incorporated capacitor.• Main switch with manual-reset thermal protection.
9
SERIE QSC..6
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QSC/036 1 x 230 V ± 10 % 0,37 0,5 4 ÷ 6,3 205 220 160 1,7
QSC/056 1 x 230 V ± 10 % 0,55 0,75 4 ÷ 6,3 205 220 160 1,7
QSC/056A 1 x 230 V ± 10 % 0,55 0,75 6,3 ÷ 10 205 220 160 1,7
QSC/076 1 x 230 V ± 10 % 0,75 1 6,3 ÷ 10 205 220 160 1,7
QSC/116 1 x 230 V ± 10 % 1,1 1,5 6,3 ÷ 10 205 220 160 1,7
QSC/116A 1 x 230 V ± 10 % 1,1 1,5 10 ÷ 16 205 220 160 1,7
QSC/156 1 x 230 V ± 10 % 1,5 2 10 ÷ 16 205 220 160 1,7
QSC/226 1 x 230 V ± 10 % 2,2 3 16 ÷ 20 205 220 160 2,7
QSC/406 1 x 230 V ± 10 % 4 5,5 25 ÷ 32 280 220 160 3
CB-QSC6-en_c_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
CAPACITOR
µF/450V
20
35
25
75
50
25
40
40
50
Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
QSC SeriesQSC SeriesQSC SeriesQSC SeriesQSC Series(60 Hz)(60 Hz)(60 Hz)(60 Hz)(60 Hz)
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a single-phase submersible electric pump for 4” wells.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• DPF single-phase module for overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Main switch for manual control.• Supply voltage: 1 x 230 V ±10%.• Frequency: 60 Hz.• Power: 0,37 to 4 kW.• Direct motor start.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Incorporated capacitor.• Main switch with thermal protection.
10
Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
QSCQSCQSCQSCQSCS SeriesS SeriesS SeriesS SeriesS Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a single-phase submersible electric pump for 4” wells.
• Main switch with manual-reset thermal protection.• Dry running control with float or minimum pressure switch (available separately).
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• DPF single-phase module for overvoltage protection (lightning protector).• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through an external enable contact.• Supply voltage: 1 x 230 V ±10%.• Frequency: 50 Hz.• Power: 0,25 to 2,2 kW.• Direct motor start.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Incorporated capacitor.
SERIE QSCS
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QSCS/02 1 x 230 V ± 10 % 0,25 0,33 2,5 ÷ 4 280 370 160 3,7
QSCS/03 1 x 230 V ± 10 % 0,37 0,5 4 ÷ 6,3 280 370 160 3,7
QSCS/05 1 x 230 V ± 10 % 0,55 0,75 4 ÷ 6,3 280 370 160 3,7
QSCS/07 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 280 370 160 3,7
QSCS/11 1 x 230 V ± 10 % 1,1 1,5 6,3 ÷ 10 280 370 160 3,7
QSCS/15 1 x 230 V ± 10 % 1,5 2 10 ÷ 16 280 370 160 3,7
QSCS/22 1 x 230 V ± 10 % 2,2 3 16 ÷ 20 280 370 160 3,7
QSCS/40 1 x 230 V ± 10 % 4 5,5 25 ÷ 32 280 370 160 4
CB-QSCS-en_c_te
90
70
16
40
50
CAPACITOR
µF/450V
12,5
30
20
A
RATED
POWER
DIMENSIONSRATED
CURRENT
11
Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
QSCQSCQSCQSCQSCS SeriesS SeriesS SeriesS SeriesS Series(60 Hz)(60 Hz)(60 Hz)(60 Hz)(60 Hz)
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a single-phase submersible electric pump for 4” wells.
• Main switch with thermal protection.• Dry running control with float or minimum pressure switch (available separately).
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• DPF single-phase module for overvoltage protection (lightning protector).• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through an external enable contact.• Supply voltage: 1 x 230 V ±10%.• Frequency: 60 Hz.• Power: 0,37 to 2,2 kW.• Direct motor start.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Incorporated capacitor.
SERIE QSCS..6
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QSCS/036 1 x 230 V ± 10 % 0,37 0,5 4 ÷ 6,3 280 370 160 3,7
QSCS/056 1 x 230 V ± 10 % 0,55 0,75 4 ÷ 6,3 280 370 160 3,7
QSCS/056A 1 x 230 V ± 10 % 0,55 0,75 6,3 ÷ 10 280 370 160 3,7
QSCS/076 1 x 230 V ± 10 % 0,75 1 6,3 ÷ 10 280 370 160 3,7
QSCS/116 1 x 230 V ± 10 % 1,1 1,5 6,3 ÷ 10 280 370 160 3,7
QSCS/116A 1 x 230 V ± 10 % 1,1 1,5 10 ÷ 16 280 370 160 3,7
QSCS/156 1 x 230 V ± 10 % 1,5 2 10 ÷ 16 280 370 160 3,7
QSCS/226 1 x 230 V ± 10 % 2,2 3 16 ÷ 20 280 370 160 3,7
QSCS/406 1 x 230 V ± 10 % 4 5,5 25 ÷ 32 280 370 160 4
CB-QSCS6-en_d_te
75
A
RATED
POWER
DIMENSIONSRATED
CURRENT
CAPACITOR
µF/450V
20
35
50
50
25
40
40
25
12
Single-phaseSingle-phaseSingle-phaseSingle-phaseSingle-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
QM SeriesQM SeriesQM SeriesQM SeriesQM Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a single-phase surface electric pump.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• VR1 single-phase varistor module overvoltage protection (lightning protector).• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through an external enable contact.• Supply voltage: 1 x 230 V ±10%.• Frequency: 50/60 Hz.• Power: 0,25 to 2,2 kW.• Direct motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Ready for installation of dry running control float or pressure switch (to be ordered separately).• Power and thermal overload indicator lights
SERIE QM
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QM/02 1 x 230 V ± 10 % 0,25 0,33 1 ÷ 1,6 235 265 150 5,8
QM/03 1 x 230 V ± 10 % 0,37 0,5 1,6 ÷ 2,5 235 265 150 5,8
QM/05 1 x 230 V ± 10 % 0,55 0,75 2,5 ÷ 4 235 265 150 5,8
QM/07 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 235 265 150 5,8
QM/15 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 235 265 150 5,8
QM/22 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 235 265 150 5,8
CB-QM-en_b_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
A
B
C
0
1
LINEA
POWER
TERMICO
OVERLOAD
13
Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
QTD SeriesQTD SeriesQTD SeriesQTD SeriesQTD Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a three-phase surface or submersible electric pump.
SERIE QTD
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QTD/02-03 3 x 400 V ± 10 % 0,25-0,37 0,33-0,50 0,63 ÷ 1 235 265 150 5,8
QTD/03-05 3 x 400 V ± 10 % 0,37-0,55 0,55-0,75 1 ÷ 1,6 235 265 150 5,8
QTD/05-07 3 x 400 V ± 10 % 0,55-0,75 0,75-1 1,6 2,5 235 265 150 5,8
QTD/07-15 3 x 400 V ± 10 % 0,75-1,5 1-2 2,5 4 235 265 150 5,8
QTD/15-22 3 x 400 V ± 10 % 1,5-2,2 2-3 4 ÷ 6,3 235 265 150 5,8
QTD/22-40 3 x 400 V ± 10 % 2,2-4 3-5,5 6,3 ÷ 10 235 265 150 5,8
QTD/40-75 3 x 400 V ± 10 % 4-7,5 5,5-10 10 ÷ 16 235 265 150 5,8
QTD/75-92 3 x 400 V ± 10 % 7,5-9,2 10-12,5 16 ÷ 20 235 265 150 5,8
CB-QTD-en_c_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• VR3 three-phase module for overvoltage protection (lightning protector).• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).
SELECTIONSELECTIONSELECTIONSELECTIONSELECTION• For a suitable choice of control panel, be sure the electrical input of the motor (Ampere) is included in the rated current value mentioned in the table below.
A
B
C
0
1
LINEA
POWER
TERMICO
OVERLOAD
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Control through an external enable contact.• Supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• Power: 0,25 to 9,2 kW.• Direct motor start.• Short-circuit and overload protection.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Ready for installation of dry running control float or pressure switch (to be ordered separately).• Power and thermal overload indicator lights.
14
• Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).• Float.• Pressure switch.• VR3/SCA3 three-phase module for overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Manual control through an Auto/Man selector switch.• Automatic control through an external enable contact.• Supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• 24 V AC low voltage auxiliary circuit.• Power: 0,25 to 37 kW.• Direct motor start.• Short-circuit and overload protection.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Power, pump running, thermal overload and dry running indicator lights.
Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a three-phase surface or submersible electric pump.
SERIE Q3D
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
Q3D/02-03 3 x 400 V ± 10 % 0,25-0,37 0,33-0,50 0,63 ÷ 1 300 400 200 15
Q3D/03-05 3 x 400 V ± 10 % 0,37-0,55 0,5-0,75 1 ÷ 1,6 300 400 200 15
Q3D/05-07 3 x 400 V ± 10 % 0,55-0,75 0,75-1 1,6 ÷ 2,5 300 400 200 15
Q3D/07-15 3 x 400 V ± 10 % 0,75-1,5 1-2 2,5 ÷ 4 300 400 200 15
Q3D/15-22 3 x 400 V ± 10 % 1,5-2,2 2-3 4 ÷ 6,3 300 400 200 15
Q3D/22-40 3 x 400 V ± 10 % 2,2-4 3-5,5 6,3 ÷ 10 300 400 200 15
Q3D/40-75 3 x 400 V ± 10 % 4-7,5 5,5-10 10 ÷ 16 300 400 200 15
Q3D/75-92 3 x 400 V ± 10 % 7,5-9,2 10-12,5 16 ÷ 20 300 400 200 15
Q3D/92-110 3 x 400 V ± 10 % 9,2-11 12,5-15 20 ÷ 25 300 400 200 20
Q3D/110-150 3 x 400 V ± 10 % 11-15 15-20 22 ÷ 32 400 500 200 20
Q3D/150-185 3 x 400 V ± 10 % 15-18,5 20-25 28 ÷ 40 400 500 200 20
Q3D/185-220 3 x 400 V ± 10 % 18,5-22 25-30 36 ÷ 50 400 600 200 27
Q3D/220-300 3 x 400 V ± 10 % 22-30 30-40 45 ÷ 63 400 600 200 27
Q3D/300-370 3 x 400 V ± 10 % 30-37 40-50 57 ÷ 75 400 600 200 27
CB-Q3D-en_a_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
Q3D SeriesQ3D SeriesQ3D SeriesQ3D SeriesQ3D Series
0
200
150A
25
0
V 500
300
50 0
L1-L2
L2-L3
L3-L1
0M A
A
B
C
15
Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
Q3Y SeriesQ3Y SeriesQ3Y SeriesQ3Y SeriesQ3Y Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a three-phase surface or submersible electric pump.
SERIE Q3Y
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
Q3Y/40-75 3 x 400 V ± 10 % 4-7,5 5,5-10 10 ÷ 16 400 600 200 23
Q3Y/75-92 3 x 400 V ± 10 % 7,5-9,2 10-12,5 16 ÷ 20 400 600 200 23
Q3Y/92-110 3 x 400 V ± 10 % 9,2-11 12,5-15 20 ÷ 25 400 600 200 23
Q3Y/110-150 3 x 400 V ± 10 % 11-15 15-20 22 ÷ 32 400 600 200 23
Q3Y/150-185 3 x 400 V ± 10 % 15-18,5 20-25 28 ÷ 40 400 600 200 23
Q3Y/185-220 3 x 400 V ± 10 % 18,5-22 25-30 36 ÷ 50 500 700 200 32
Q3Y/220-300 3 x 400 V ± 10 % 22-30 30-40 45 ÷ 63 500 700 200 32
Q3Y/300-370 3 x 400 V ± 10 % 30-37 40-50 57 ÷ 75 600 800 250 68
Q3Y/370-450 3 x 400 V ± 10 % 37-45 50-60 70 ÷ 90 600 800 250 80
Q3Y/450-550 3 x 400 V ± 10 % 45-55 60-75 80 ÷ 108 600 900 250 80
Q3Y/550-750 3 x 400 V ± 10 % 55-75 75-100 105 ÷ 138 600p 1300p 300p 109
Q3Y/750-900 3 x 400 V ± 10 % 75-90 100-125 138 ÷ 185 600p 1300p 300p 109
Q3Y/900-1100 3 x 400 V ± 10 % 90-110 125-150 175 ÷ 210 600p 1500p 300p 120
Q3Y/1100-1320 3 x 400 V ± 10 % 110-132 150-180 210 ÷ 260 800p 1700p 400p 130
Q3Y/1320-1600 3 x 400 V ± 10 % 132-160 180-218 250 ÷ 305 800p 1700p 400p 130
Q3Y/1600-2000 3 x 400 V ± 10 % 160-200 218-273 290 ÷ 400 800p 1900p 400p 140
Q3Y/2000-2500 3 x 400 V ± 10 % 200-250 273-340 400 ÷ 460 1000p 1900p 400p 180
Q3Y/2500-3150 3 x 400 V ± 10 % 250-315 340-430 450 ÷ 580 1000p 1900p 400p 180
Dimensions note : P indicates floor mounted control panel. CB-Q3Y-en_c_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
• Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).• Float.• Pressure switch.• VR3/SCA3 three-phase module for overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Manual control through an Auto/Man selector switch.• Automatic control through an external enable contact.• Supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• 24 V AC low voltage auxiliary circuit.• Power: 4 to 315 kW.• Star-delta starting.• Short-circuit and overload protection.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Power, pump running, thermal overload and dry running indicator lights.
0
200
150A
25
0
V 500
300
50 0
L1-L2
L2-L3
L3-L1
0M A
A
B
C
16
Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
Q3I SeriesQ3I SeriesQ3I SeriesQ3I SeriesQ3I Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a three-phase surface or submersible electric pump.
SERIE Q3I
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
Q3I/40-75 3 x 400 V ± 10 % 4-7,5 5,5-10 10 ÷ 16 400 600 250 35
Q3I/75-92 3 x 400 V ± 10 % 7,5-9,2 10-12,5 16 ÷ 20 400 600 250 35
Q3I/92-110 3 x 400 V ± 10 % 9,2-11 12,5-15 20 ÷ 25 400 600 250 35
Q3I/110-150 3 x 400 V ± 10 % 11-15 15-20 22 ÷ 32 500 700 250 50
Q3I/150-185 3 x 400 V ± 10 % 15-18,5 20-25 28 ÷ 40 500 700 250 50
Q3I/185-220 3 x 400 V ± 10 % 18,5-22 25-30 36 ÷ 50 500 700 250 50
Q3I/220-300 3 x 400 V ± 10 % 22-30 30-40 45 ÷ 63 500 700 250 65
Q3I/300-370 3 x 400 V ± 10 % 30-37 40-50 57 ÷ 75 500 700 250 65
Q3I/370-450 3 x 400 V ± 10 % 37-45 50-60 70 ÷ 90 600 900 250 65
Q3I/450-550 3 x 400 V ± 10 % 45-55 60-75 80 ÷ 108 600p 1300p 300p 100
Q3I/550-750 3 x 400 V ± 10 % 55-75 75-100 105 ÷ 138 600p 1300p 300p 100
Q3I/750-900 3 x 400 V ± 10 % 75-90 100-125 138 ÷ 185 600p 1500p 300p 100
Q3I/900-1100 3 x 400 V ± 10 % 90-110 125-150 175 ÷ 210 800p 1700p 400p 100
Q3I/1100-1320 3 x 400 V ± 10 % 110-132 150-180 210 ÷ 260 800p 1700p 400p 150
Q3I/1320-1600 3 x 400 V ± 10 % 132-160 180-218 250 ÷ 305 800p 1700p 400p 150
Q3I/1600-2000 3 x 400 V ± 10 % 160-200 218-273 290 ÷ 400 800p 1900p 400p 160
Q3I/2000-2500 3 x 400 V ± 10 % 200-250 273-340 400 ÷ 460 1000p 1900p 400p 180
Q3I/2500-3150 3 x 400 V ± 10 % 250-315 340-430 450 ÷ 580 1000p 1900p 400p 200
Dimensions note : P indicates floor mounted control panel. CB-Q3I-en_c_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
• Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).• Float.• Pressure switch.• VR3/SCA3 three-phase module for overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Manual control through an Auto/Man selector switch.• Automatic control through an external enable contact.• Supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• 24 V AC low voltage auxiliary circuit.• Power: 4 to 315 kW.• Impedance start.• Short-circuit and overload protection.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Power, pump running, thermal overload and dry running indicator lights.
0
200
150A
25
0
V 500
300
50 0
L1-L2
L2-L3
L3-L1
0M A
A
B
C
17
Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
Q3A SeriesQ3A SeriesQ3A SeriesQ3A SeriesQ3A Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a three-phase surface or submersible electric pump.
SERIE Q3A
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
Q3A/40-75 3 x 400 V ± 10 % 4-7,5 5,5-10 10 ÷ 16 500 700 250 50
Q3A/75-92 3 x 400 V ± 10 % 7,5-9,2 10-12,5 16 ÷ 20 500 700 250 50
Q3A/92-110 3 x 400 V ± 10 % 9,2-11 12,5-15 20 ÷ 25 500 700 250 50
Q3A/110-150 3 x 400 V ± 10 % 11-15 15-20 22 ÷ 32 500 700 250 50
Q3A/150-185 3 x 400 V ± 10 % 15-18,5 20-25 28 ÷ 40 500 700 250 50
Q3A/185-220 3 x 400 V ± 10 % 18,5-22 25-30 36 ÷ 50 500 700 250 50
Q3A/220-300 3 x 400 V ± 10 % 22-30 30-40 45 ÷ 63 600 900 300 80
Q3A/300-370 3 x 400 V ± 10 % 30-37 40-50 57 ÷ 75 600 900 300 80
Q3A/370-450 3 x 400 V ± 10 % 37-45 50-60 70 ÷ 90 600p 1300p 300p 90
Q3A/450-550 3 x 400 V ± 10 % 45-55 60-75 80 ÷ 108 600p 1500p 300p 120
Q3A/550-750 3 x 400 V ± 10 % 55-75 75-100 105 ÷ 138 600p 1500p 300p 120
Q3A/750-900 3 x 400 V ± 10 % 75-90 100-125 138 ÷ 185 600p 1700p 400p 150
Q3A/900-1100 3 x 400 V ± 10 % 90-110 125-150 175 ÷ 210 800p 1900p 400p 150
Q3A/1100-1320 3 x 400 V ± 10 % 110-132 150-180 210 ÷ 260 800p 1900p 400p 200
Q3A/1320-1600 3 x 400 V ± 10 % 132-160 180-218 250 ÷ 305 800p 1900p 400p 200
Q3A/1600-2000 3 x 400 V ± 10 % 160-200 218-273 290 ÷ 400 800p 1900p 400p 230
Q3A/2000-2500 3 x 400 V ± 10 % 200-250 273-340 400 ÷ 460 1000p 1900p 400p 230
Q3A/2500-3150 3 x 400 V ± 10 % 250-315 340-430 450 ÷ 580 1000p 1900p 400p 250
Dimensions note : P indicates floor mounted control panel. CB-Q3A-en_c_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
• Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).• Float.• Pressure switch.• VR3/SCA3 three-phase module for overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Manual control through an Auto/Man selector switch.• Automatic control through an external enable contact.• Supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• 24 V AC low voltage auxiliary circuit.• Power: 4 to 315 kW.• Starting autotransformer.• Short-circuit and overload protection.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Power, pump running, thermal overload and dry running indicator lights.
0
200
150A
25
0
V 500
300
50 0
L1-L2
L2-L3
L3-L1
0M A
A
B
C
18
Three-phaseThree-phaseThree-phaseThree-phaseThree-phaseElectricElectricElectricElectricElectricPPPPPanelanelanelanelanel
Q3SF SeriesQ3SF SeriesQ3SF SeriesQ3SF SeriesQ3SF Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of a three-phase surface or submersible electric pump.
SERIE Q3SF
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
Q3SF 75 3 x 400 V ± 10 % 5,5 - 7,5 7,5 -10 8,5 ÷ 17 400 600 250 35
Q3SF 150 3 x 400 V ± 10 % 9,2 - 15 12,5 - 20 15 ÷ 30 500 700 250 40
Q3SF 220 3 x 400 V ± 10 % 18,5 - 22 25 - 30 28 ÷ 45 500 700 250 40
Q3SF 300 3 x 400 V ± 10 % 30 40 42 ÷ 60 600 900 300 90
Q3SF 370 3 x 400 V ± 10 % 37 50 55 ÷ 75 600 900 300 90
Q3SF 450 3 x 400 V ± 10 % 45 60 70 ÷ 85 600 900 300 90
Q3SF 550 3 x 400 V ± 10 % 55 75 80 ÷ 110 600 900 300 90
Q3SF 590 3 x 400 V ± 10 % 59 80 105 ÷ 125 600 900 300 90
Q3SF 750 3 x 400 V ± 10 % 75 100 120 ÷ 142 600p 1700p 400p 120
Q3SF 900 3 x 400 V ± 10 % 90 125 135 ÷ 190 600p 1700p 400p 120
Q3SF 1100 3 x 400 V ± 10 % 110 150 185 ÷ 245 600p 1700p 400p 120
Dimensions note : P indicates floor mounted control panel. CB-Q3SF-en_b_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
Protections against phase failure / phase sequence / frequency out of limits on power supply line. Low-voltage protection on auxiliary circuits. Protection against starter overtemperature / overload / malfunction. Protection against overload / locked rotor / current asymmetry on motor side. Short-circuit protection on inputs and outputs. RS232 interface for remote control and RS485 for use of remote keypanel. Incorporated by-pass contactor.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• KSL series 24 V level kit. Probe module for protection against dry running (set of three electrodes included in the supply).• Float.• Pressure switch.• VR3/SCA3 three-phase module for overvoltage protection (lightning protector).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Manual control through an Auto/Man selector switch.• Automatic control through an external enable contact.• Supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• 24 V AC low voltage auxiliary circuit.• Power: 5,5 to 110 kW.• Softstart with torque control.• Protection class: IP54.• Ambient temperature: -5 to +40 °C• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Dry running indicator light.• Power - pump running - malfunction LEDs on starter keypanel.• ON/OFF selector switch for activation of by-pass contactor.• Ready for installation of dry running control float or pressure switch (to be ordered separately). Can be equipped with electronic protection module with electrodes.
STSTSTSTSTAAAAATIC STTIC STTIC STTIC STTIC STARTERARTERARTERARTERARTERCHARACTERISTICCHARACTERISTICCHARACTERISTICCHARACTERISTICCHARACTERISTICSSSSS• Static starter for gradual start-up/ shutdown, featuring: keypanel with liquid crystal display showing voltage, absorbed current, cos ϕ, operating hours, number of starts, last twenty messages on system status (events / alarms).
0M A
A
B
C
19
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QDRM SeriesQDRM SeriesQDRM SeriesQDRM SeriesQDRM Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of one single-phase drainage pump.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Audible or visual signalling device, 12 Vdc 0.3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. − VR1 single-phase module (for QDRM) for overvoltage protection (lightning protector).
SERIE QDRM
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QDRM/02 1 x 230 V ± 10 % 0,25 0,33 1 ÷ 1,6 280 220 160 2,2
QDRM/03 1 x 230 V ± 10 % 0,37 0,5 1,6 ÷ 2,5 280 220 160 2,2
QDRM/05 1 x 230 V ± 10 % 0,55 0,75 2,5 ÷ 4 280 220 160 2,2
QDRM/07 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 280 220 160 2,2
QDRM/15 1 x 230 V ± 10 % 1,1 ÷ 1,5 1,5 ÷ 2 6,3 ÷ 10 280 220 160 2,2
QDRM/22 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 280 370 160 4,1
CB-QDRM-en_c_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 1 x 230 V ±10%.• Frequency: 50/60 Hz.• Power: 0,25 to 2,2 kW.• Direct motor start.• Protection class: IP55• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Electronic control module with test and alarm reset buttons, and power-on, pump running and high level alarm indicator LED’s.• Alarm silencing button.
20
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QDRMC SeriesQDRMC SeriesQDRMC SeriesQDRMC SeriesQDRMC Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of one single-phase drainage pump with external capacitor.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. − VR1 single-phase module (for QDRM) for overvoltage protection (lightning protector).
SERIE QDRMC
MODEL RATED WEIGHT C Cs
VOLTAGE A B C
V kW HP mm mm mm Kg uF uF
QDRMC/07 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 280 370 160 3,1 20 40
QDRMC/15 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 280 370 160 3,1 35 60
QDRMC/22 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 280 370 160 3,1 35 60
QDRMC/07/TS 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 280 370 160 3,5 20 40
QDRMC/15/TS 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 280 370 160 3,5 35 60
QDRMC/22/TS 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 280 370 160 3,5 35 60
QDRMC/07/WD 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 280 370 160 4 20 40
QDRMC/15/WD 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 280 370 160 4 35 60
QDRMC/22/WD 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 280 370 160 4 35 60
QDRMC/15/TS/GL 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 280 370 160 4 35 100
C= Run capacitor; Cs= Start capacitor CB-QDRMC-en_e_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 1 x 230 V ±10%.• Frequency: 50/60 Hz.• Power: 0,75 to 2,2 kW.• Direct motor start.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Electronic control module with test and alarm reset buttons, and power-on, pump running, high level alarm, thermal probe (versions /TS and /WD) and water in oil chamber (version /WD) indicator LED’s.• Alarm silencing button.• Start and run capacitor incorporated in the control panel.• /TS version equipped with stator thermal protection circuit.• /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.• /TS/GL versions for electropumps GLS/GLV series.
21
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QDR SeriesQDR SeriesQDR SeriesQDR SeriesQDR Seriesthree-phasethree-phasethree-phasethree-phasethree-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of one three-phase drainage pump.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. − VR3 three-phase module (for QDR) for overvoltage protection (lightning protector).
SERIE QDR
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QDR/03 3 x 400 V ± 10 % 0,37 0,5 0,63 ÷ 1 280 370 150 4,1
QDR/05 3 x 400 V ± 10 % 0,55 0,75 1 ÷ 1,6 280 370 150 4,1
QDR/07 3 x 400 V ± 10 % 0,75 1 1,6 ÷ 2,5 280 370 150 4,1
QDR/15 3 x 400 V ± 10 % 1,1 ÷ 1,5 1,5 ÷ 2 2,5 ÷ 4 280 370 150 4,1
QDR/22 3 x 400 V ± 10 % 2,2 3 4 ÷ 6,3 280 370 150 4,1
QDR/40 3 x 400 V ± 10 % 3 ÷ 4 4 ÷ 5,5 6,3 ÷ 10 280 370 150 4,1
QDR/75 3 x 400 V ± 10 % 5,5 ÷ 7,5 7,5 ÷ 10 10 ÷ 16 280 370 150 4,1
QDR/07/TS 3 x 400 V ± 10 % 0,75 1 1,6 ÷ 2,5 280 370 150 4,5
QDR/15/TS 3 x 400 V ± 10 % 1,5 2 2,5 ÷ 4 280 370 150 4,5
QDR/22/TS 3 x 400 V ± 10 % 2,2 3 4 ÷ 6,3 280 370 150 4,5
QDR/07/WD 3 x 400 V ± 10 % 0,75 1 1,6 ÷ 2,5 280 370 150 5
QDR/15/WD 3 x 400 V ± 10 % 1,5 2 2,5 ÷ 4 280 370 150 5
QDR/22/WD 3 x 400 V ± 10 % 2,2 3 4 ÷ 6,3 280 370 150 5
The /WD option also includes the /TS option. CB-QDR-en_c_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• Power: 0,37 to 9,2 kW.• Direct motor start.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Power, thermal overload, high level indicator lights.• Alarm silencing button.• /TS version equipped with stator thermal protection circuit.• /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.
22
QGMC SeriesQGMC SeriesQGMC SeriesQGMC SeriesQGMC Series
SERIE QGMC
MODEL RATED WEIGHT C Cs
VOLTAGE A B C
V kW HP mm mm mm Kg uF uF
QGMC/07 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 280 370 160 3 20 40
QGMC/15 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 280 370 160 3 35 60
QGMC/22 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 280 370 160 3 35 60
C = Run capacitor; Cs = Start capacitor. CB-QGMC-en_a_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of one single-phase drainage pump with external capacitor.
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control via external contact.• Supply voltage: 1 x 230 V ±10%.• Frequency: 50 Hz.• Power: 0,75 to 2,2 kW.• Direct motor start.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Run capacitor.• Start capacitor.• Starter.• Main switch with thermal protection.
23
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QDRM2 SeriesQDRM2 SeriesQDRM2 SeriesQDRM2 SeriesQDRM2 Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of two single-phase drainage pumps.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. − VR1 single-phase module for overvoltage protection (lightning protector). − Signal relay board kit (power, auto/ man, start/stop, thermal overload, high level).
SERIE QDRM2
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QDRM2/02 1 x 230 V ± 10 % 0,25 0,33 1 ÷ 1,6 260 380 150 9,4
QDRM2/03 1 x 230 V ± 10 % 0,37 0,5 1,6 ÷ 2,5 260 380 150 9,4
QDRM2/05 1 x 230 V ± 10 % 0,55 0,75 2,5 ÷ 4 260 380 150 9,4
QDRM2/07 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 260 380 150 9,4
QDRM2/15 1 x 230 V ± 10 % 1,1 ÷ 1,5 1,5 ÷ 2 6,3 ÷ 10 260 380 150 9,4
QDRM2/22 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 260 380 150 9,4
CB-QDRM2-en_a_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 1 x 230 V ±10%.• Frequency: 50/60 Hz.• Power: 0,25 to 2,2 kW.• Direct motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs.• Alarm silencing button.
Control box
0 O
FF
1 ON
LINEA
POWER
BLOCCO
TERMICO
ALLARME
OVER
LOAD
ALARM
RESET
ALLARME
ALARM
AUT MAN
AUT MAN
OFF ON
P1
OFF ON
P2
COD.168276440
A
B
C
24
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QYR SeriesQYR SeriesQYR SeriesQYR SeriesQYR Seriesthree-phasethree-phasethree-phasethree-phasethree-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of one three-phase drainage pump with star-delta start.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. − VR3 three-phase module (for QDR) for overvoltage protection (lightning protector). − Signal relay board kit (power, auto/ man, start/stop, thermal overload, high level).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• Power: 3 to 75 kW.• Star-delta motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs.• Alarm silencing button.• /TS version equipped with stator thermal protection circuit.• /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.
Control box
0 O
FF
1 ON
LINEA
POWER
BLOCCO
TERMICO
ALLARME
OVER
LOAD
ALARM
RESET
ALLARME
ALARM
AUT MAN
AUT MAN
OFF ON
P1
OFF ON
P2
COD.168276440
A
B
C
25
QYR SERIES PQYR SERIES PQYR SERIES PQYR SERIES PQYR SERIES PANELSANELSANELSANELSANELSELECTRICAL DAELECTRICAL DAELECTRICAL DAELECTRICAL DAELECTRICAL DATTTTTA TA TA TA TA TABLEABLEABLEABLEABLESERIE QYR
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QYR/40 3 x 400 V ± 10 % 3 ÷ 4 4 ÷ 5,5 6,3 ÷ 10 400 500 200 25
QYR/75 3 x 400 V ± 10 % 5,5 ÷ 7,5 7.5 ÷ 10 10 ÷ 16 400 500 200 25
QYR/92 3 x 400 V ± 10 % 9,2 12,5 16 ÷ 20 400 500 200 25
QYR/110 3 x 400 V ± 10 % 11 15 20 ÷ 25 400 500 200 25
QYR/150 3 x 400 V ± 10 % 15 20 22 ÷ 32 400 600 200 27
QYR/185 3 x 400 V ± 10 % 18,5 25 28 ÷ 40 400 600 200 27
QYR/220 3 x 400 V ± 10 % 22 30 36 ÷ 50 500 700 200 32
QYR/300 3 x 400 V ± 10 % 30 40 45 ÷ 63 500 700 200 32
QYR/370 3 x 400 V ± 10 % 37 50 57 ÷ 75 600 800 250 32
QYR/450 3 x 400 V ± 10 % 45 60 70 ÷ 90 600 800 250 32
QYR/550 3 x 400 V ± 10 % 55 75 80 ÷ 108 600 900 250 37
QYR/750 3 x 400 V ± 10 % 75 100 105 ÷ 138 600p 1300p 300p 70
QYR/22/TS 3 x 400 V ± 10 % 2,2 3 4 ÷ 6,3 400 500 200 25
QYR/40/TS 3 x 400 V ± 10 % 3 ÷ 4 4 ÷ 5,5 6,3 ÷ 10 400 500 200 26
QYR/75/TS 3 x 400 V ± 10 % 5,5 ÷ 7,5 7,5 ÷ 10 10 ÷ 16 400 500 200 26
QYR/92/TS 3 x 400 V ± 10 % 9,2 12,5 16 ÷ 20 400 500 200 26
QYR/110/TS 3 x 400 V ± 10 % 11 15 20 ÷ 25 400 500 200 26
QYR/150/TS 3 x 400 V ± 10 % 15 20 22 ÷ 32 400 600 200 27
QYR/185/TS 3 x 400 V ± 10 % 18,5 25 28 ÷ 40 400 600 200 27
QYR/220/TS 3 x 400 V ± 10 % 22 30 36 ÷ 50 500 700 200 32
QYR/300/TS 3 x 400 V ± 10 % 30 40 45 ÷ 63 500 700 200 32
QYR/370/TS 3 x 400 V ± 10 % 37 50 57 ÷ 75 600 800 250 33
QYR/450/TS 3 x 400 V ± 10 % 45 60 70 ÷ 90 600 800 250 33
QYR/550/TS 3 x 400 V ± 10 % 55 75 80 ÷ 108 600 900 250 37
QYR/750/TS 3 x 400 V ± 10 % 75 100 105 ÷ 138 600p 1300p 300p 70
QYR/40/WD 3 x 400 V ± 10 % 3 ÷ 4 4 ÷ 5,5 6,3 ÷ 10 400 500 200 26
QYR/75/WD 3 x 400 V ± 10 % 5,5 ÷ 7,5 7,5 ÷ 10 10 ÷ 16 400 500 200 26
QYR/92/WD 3 x 400 V ± 10 % 9,2 12,5 16 ÷ 20 400 500 200 26
QYR/110/WD 3 x 400 V ± 10 % 11 15 20 ÷ 25 400 500 200 26
QYR/150/WD 3 x 400 V ± 10 % 15 20 22 ÷ 32 400 600 200 28
QYR/185/WD 3 x 400 V ± 10 % 18,5 25 28 ÷ 40 400 600 200 28
QYR/220/WD 3 x 400 V ± 10 % 22 30 36 ÷ 50 500 700 200 33
QYR/300/WD 3 x 400 V ± 10 % 30 40 45 ÷ 63 500 700 200 33
QYR/370/WD 3 x 400 V ± 10 % 37 50 57 ÷ 75 600 800 250 33
QYR/450/WD 3 x 400 V ± 10 % 45 60 70 ÷ 90 600 800 250 33
QYR/550/WD 3 x 400 V ± 10 % 55 75 80 ÷ 108 600 900 250 38
QYR/750/WD 3 x 400 V ± 10 % 75 100 105 ÷ 138 600p 1300p 300p 71
Dimensions: p = floor-standing cabinet. CB-QYR-en_e_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
26
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QDRMC2 SeriesQDRMC2 SeriesQDRMC2 SeriesQDRMC2 SeriesQDRMC2 Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of two single-phase drainage pumps with external capacitor.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. − VR1 single-phase module for overvoltage protection (lightning protector). − Signal relay board kit (power, auto/ man, start/stop, thermal overload, high level).
SERIE QDRMC2
MODEL RATED WEIGHT C Cs
VOLTAGE A B C
V kW HP mm mm mm Kg uF uF
QDRMC2/07 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 390 470 130 8,5 20 40
QDRMC2/15 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 390 470 130 8,5 35 60
QDRMC2/22 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 390 470 130 8,5 35 60
QDRMC2/07/TS 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 390 470 130 9 20 40
QDRMC2/15/TS 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 390 470 130 9 35 60
QDRMC2/22/TS 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 390 470 130 9 35 60
QDRMC2/07/WD 1 x 230 V ± 10 % 0,75 1 4 ÷ 6,3 390 470 130 10 20 40
QDRMC2/15/WD 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 390 470 130 10 35 60
QDRMC2/22/WD 1 x 230 V ± 10 % 2,2 3 10 ÷ 16 390 470 130 10 35 60
QDRMC2/15/TS/GL 1 x 230 V ± 10 % 1,5 2 6,3 ÷ 10 390 470 130 10 35 100
C = Run capacitor; Cs = Start capacitor. CB-QDRMC2-en_d_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
Control box
0 O
FF
1 ON
LINEA
POWER
BLOCCO
TERMICO
ALLARME
OVER
LOAD
ALARM
RESET
ALLARME
ALARM
AUT MAN
AUT MAN
OFF ON
P1
OFF ON
P2
COD.168276440
A
B
C
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 1 x 230 V ±10%.• Frequency: 50/60 Hz.• Power: 0,75 to 2,2 kW.• Direct motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs.• Start and run capacitor incorporated in the control panel.• /TS version equipped with stator thermal protection circuit.• /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.• /TS/GL versions for electropumps GLS/GLV series.
27
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QDR2 SeriesQDR2 SeriesQDR2 SeriesQDR2 SeriesQDR2 Seriesthree-phasethree-phasethree-phasethree-phasethree-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of two three-phase drainage pumps.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. − VR3 three-phase module for overvoltage protection (lightning protector). − Signal relay board kit (power, auto/ man, start/stop, thermal overload, high level).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• Power: 0,37 to 9,2 kW.• Direct motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs.• Alarm silencing button.• /TS version equipped with stator thermal protection circuit.• /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.
Control box
0 O
FF
1 ON
LINEA
POWER
BLOCCO
TERMICO
ALLARME
OVER
LOAD
ALARM
RESET
ALLARME
ALARM
AUT MAN
AUT MAN
OFF ON
P1
OFF ON
P2
COD.168276440
A
B
C
SERIE QDR2
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QDR2/03 3 x 400 V ± 10 % 0,37 0,5 0,63 ÷ 1 260 380 150 9,4
QDR2/05 3 x 400 V ± 10 % 0,55 0,75 1 ÷ 1,6 260 380 150 9,4
QDR2/07 3 x 400 V ± 10 % 0,75 1 1,6 ÷ 2,5 260 380 150 9,4
QDR2/15 3 x 400 V ± 10 % 1,1 ÷ 1,5 1,5 ÷ 2 2,5 ÷ 4 260 380 150 9,4
QDR2/22 3 x 400 V ± 10 % 2,2 3 4 ÷ 6,3 260 380 150 9,4
QDR2/40 3 x 400 V ± 10 % 3 ÷ 4 4 ÷ 5,5 6,3 ÷ 10 260 380 150 9,4
QDR2/75 3 x 400 V ± 10 % 5,5 ÷ 7,5 7,5 ÷ 10 10 ÷ 16 260 380 150 9,4
QDR2/92 3 x 400 V ± 10 % 9,2 12,5 16 ÷ 20 300 400 180 11
QDR2/07/TS 3 x 400 V ± 10 % 0,75 1 1,6 ÷ 2,5 400 400 200 14
QDR2/15/TS 3 x 400 V ± 10 % 1,1 ÷ 1,5 1,5 ÷ 2 2,5 ÷ 4 400 400 200 14
QDR2/22/TS 3 x 400 V ± 10 % 2,2 3 4 ÷ 6,3 400 400 200 14
QDR2/07/WD 3 x 400 V ± 10 % 0,75 1 1,6 ÷ 2,5 400 500 200 18
QDR2/15/WD 3 x 400 V ± 10 % 1,1 ÷ 1,5 1,5 ÷ 2 2,5 ÷ 4 400 500 200 18
QDR2/22/WD 3 x 400 V ± 10 % 2,2 3 4 ÷ 6,3 400 500 200 18
The /WD option also includes the /TS option. CB-QDR2-en_b_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
28
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QYR2 SeriesQYR2 SeriesQYR2 SeriesQYR2 SeriesQYR2 Seriesthree-phasethree-phasethree-phasethree-phasethree-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of two three-phase drainage pumps with star-delta start.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Audible or visual signalling device, 12 Vdc 0,3 A max (two connection terminals provided inside the electrical panel) for high-level alarm. − VR3 three-phase module for overvoltage protection (lightning protector). − Signal relay board kit (power, auto/ man, start/stop, thermal overload, high level).
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 3 x 400 V ±10%.• Frequency: 50/60 Hz.• Power: 3 to 75 kW.• Star-delta motor start.• Protection class: IP54.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Metal enclosure.• Electronic board with power, thermal overload, high level alarm, pump start/stop indicator LEDs.• Alarm silencing button.• /TS version equipped with stator thermal protection circuit.• /WD version equipped with oil chamber water sensor control circuit and stator thermal protection.
Control box
0 O
FF
1 ON
LINEA
POWER
BLOCCO
TERMICO
ALLARME
OVER
LOAD
ALARM
RESET
ALLARME
ALARM
AUT MAN
AUT MAN
OFF ON
P1
OFF ON
P2
COD.168276440
A
B
C
29
SERIE QYR2
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QYR2/40 3 x 400 V ± 10 % 3 ÷ 4 4 ÷ 5,5 6,3 ÷ 10 500 700 200 55
QYR2/75 3 x 400 V ± 10 % 5,5 ÷ 7,5 7,5 ÷ 10 10 ÷ 16 500 700 200 55
QYR2/92 3 x 400 V ± 10 % 9,2 12,5 16 ÷ 20 500 700 200 55
QYR2/110 3 x 400 V ± 10 % 11 15 20 ÷ 25 500 700 200 55
QYR2/150 3 x 400 V ± 10 % 15 20 22 ÷ 32 600 800 250 68
QYR2/185 3 x 400 V ± 10 % 18,5 25 28 ÷ 40 600 800 250 68
QYR2/220 3 x 400 V ± 10 % 22 30 36 ÷ 50 600 900 250 75
QYR2/300 3 x 400 V ± 10 % 30 40 45 ÷ 63 600 900 250 75
QYR2/370 3 x 400 V ± 10 % 37 50 57 ÷ 75 600p 1300p 300p 92
QYR2/450 3 x 400 V ± 10 % 45 60 70 ÷ 90 800p 1700p 300p 125
QYR2/550 3 x 400 V ± 10 % 55 75 80 ÷ 108 800p 1700p 300p 125
QYR2/750 3 x 400 V ± 10 % 75 100 105 ÷ 138 800p 1900p 300p 148
QYR2/22/TS 3 x 400 V ± 10 % 2,2 3 4 ÷ 6,3 500 700 200 55
QYR2/40/TS 3 x 400 V ± 10 % 3 ÷ 4 4 ÷ 5,5 6,3 ÷ 10 500 700 200 55
QYR2/75/TS 3 x 400 V ± 10 % 5,5 ÷ 7,5 7,5 ÷ 10 10 ÷ 16 500 700 200 55
QYR2/92/TS 3 x 400 V ± 10 % 9,2 12,5 16 ÷ 20 500 700 200 55
QYR2/110/TS 3 x 400 V ± 10 % 11 15 20 ÷ 25 500 700 200 55
QYR2/150/TS 3 x 400 V ± 10 % 15 20 22 ÷ 32 600 800 250 68
QYR2/185/TS 3 x 400 V ± 10 % 18,5 25 28 ÷ 40 600 800 250 68
QYR2/220/TS 3 x 400 V ± 10 % 22 30 36 ÷ 50 600 900 250 75
QYR2/300/TS 3 x 400 V ± 10 % 30 40 45 ÷ 63 600 900 250 75
QYR2/370/TS 3 x 400 V ± 10 % 37 50 57 ÷ 75 600p 1300p 300p 92
QYR2/450/TS 3 x 400 V ± 10 % 45 60 70 ÷ 90 800p 1700p 300p 125
QYR2/550/TS 3 x 400 V ± 10 % 55 75 80 ÷ 108 800p 1700p 300p 125
QYR2/750/TS 3 x 400 V ± 10 % 75 100 105 ÷ 138 800p 1900p 300p 148
QYR2/40/WD 3 x 400 V ± 10 % 3 ÷ 4 4 ÷ 5,5 6,3 ÷ 10 500 700 200 55
QYR2/75/WD 3 x 400 V ± 10 % 5,5 ÷7,5 7,5 ÷ 10 10 ÷ 16 500 700 200 55
QYR2/92/WD 3 x 400 V ± 10 % 9,2 12,5 16 ÷ 20 500 700 200 55
QYR2/110/WD 3 x 400 V ± 10 % 11 15 20 ÷ 25 500 700 200 55
QYR2/150/WD 3 x 400 V ± 10 % 15 20 22 ÷ 32 600 800 250 68
QYR2/185/WD 3 x 400 V ± 10 % 18,5 25 28 ÷ 40 600 800 250 68
QYR2/220/WD 3 x 400 V ± 10 % 22 30 36 ÷ 50 600 900 250 75
QYR2/300/WD 3 x 400 V ± 10 % 30 40 45 ÷ 63 600 900 250 75
QYR2/370/WD 3 x 400 V ± 10 % 37 50 57 ÷ 75 600p 1300p 300p 92
QYR2/450/WD 3 x 400 V ± 10 % 45 60 70 ÷ 90 800p 1700p 300p 125
QYR2/550/WD 3 x 400 V ± 10 % 55 75 80 ÷ 108 800p 1700p 300p 125
QYR2/750/WD 3 x 400 V ± 10 % 75 100 105 ÷ 138 800p 1900p 300p 148
Dimensions: p = floor-standing cabinet. CB-QYR2-en_b_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
QYR2 SERIES PQYR2 SERIES PQYR2 SERIES PQYR2 SERIES PQYR2 SERIES PANELSANELSANELSANELSANELSELECTRIC DAELECTRIC DAELECTRIC DAELECTRIC DAELECTRIC DATTTTTA TA TA TA TA TABLEABLEABLEABLEABLE
30
ElectricalElectricalElectricalElectricalElectricalpanel forpanel forpanel forpanel forpanel fordrainagedrainagedrainagedrainagedrainagepumpspumpspumpspumpspumps
QXR20 SeriesQXR20 SeriesQXR20 SeriesQXR20 SeriesQXR20 Seriessingle-phasesingle-phasesingle-phasesingle-phasesingle-phase
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Protection and control of two single-phase drainage pumps.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Signal relay board kit (power, auto man, start/stop, thermal overload, high level).
SERIE QXR20
MODEL RATED WEIGHT
VOLTAGE A B C
V kW HP mm mm mm Kg
QXR20 1 x 230 V ± 10 % 0,25 ÷ 1,5 0,33 ÷ 2 1 ÷ 10 205 220 160 1,5
CB-QXR20-en_a_te
A
RATED
POWER
DIMENSIONSRATED
CURRENT
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through electromechanical floats.• Power supply voltage: 1 x 230 V ±10%.• Frequency: 50/60 Hz.• Power: 0,25 to 1,5 kW.• Direct motor start.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Electronic board with power, thermal overload, acustic alarm of high level, pump, start/stop indicator LEDs.• Alarm silencing button.• Cyclic exchange starting pumps.• Aut-0-Man selector (1 for each pump).• One pump is controlled by the closing of internal contact that is inside the control card.
31
For connection of the electrodes to thepanel we recommend the followingcross sections:
Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.
LevelLevelLevelLevelLevelControlControlControlControlControlPPPPPanelanelanelanelanel
QCL5 SeriesQCL5 SeriesQCL5 SeriesQCL5 SeriesQCL5 Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Accessory for electric pump control panels, suitable for tank filling or drainage applications or for activation of audible or visual alarms.
SERIE QCL5
TYPE POWER SUPPLY DIMENSIONS WEIGHT
VOLTAGE FREQUENCY POWER TYPE A x B x C
V Hz W V A mm Kg
QCL5/24 1 x 24 50/60 2
QCL5/230 1 x 230 50/60 2
CB-QCL5-en_a_te
CONTACT
0,5
RANGE
90 x 130 x 60NO-C-NC 48 3
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Drop cable with circular cross section.
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through probes.• Supply voltage: 1 x 230 V ±10% or 1 x 24 V ±10%.• Frequency: 50/60 Hz.• Voltage to probes: 15 V AC at 0,5 mA max.• Switch contact 48 V AC at 3 A max (250 W max).• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Electrodes suitable for water at a maximum temperature of 40°C.• Set of three electrodes included in the supply.
TABELLA CAVI
CABLE SECTION
mm2
0 50 0,5
50 100 0,75
100 200 1,0
200 400 2,5
CB-CASEL-en_b_te
LENGHT
m
Control box
A
B
C
32
QCL10 SeriesQCL10 SeriesQCL10 SeriesQCL10 SeriesQCL10 Series
For connection of the electrodes to thepanel we recommend the followingcross sections:
Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.
LevelLevelLevelLevelLevelControlControlControlControlControlPPPPPanelanelanelanelanel
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Accessory for electric pump control panels, suitable for tank filling or drainage applications or for activation of audible or visual alarms.
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Drop cable with circular cross section.
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through probes.• Supply voltage: 1 x 230 V ±10% or 1 x 24 V ±10%.• Frequency: 50/60 Hz.• Voltage to probes: 7,5 V AC at 0,4 mA max.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Plastic enclosure.• Electrodes suitable for water at a maximum temperature of 60°C.• Set of three electrodes included in the supply.
TABELLA CAVI
CABLE SECTION
mm2
0 50 0,5
50 100 0,75
100 200 1,0
200 400 2,5
CB-CASEL-en_b_te
LENGHT
m
SERIE QCL10
TYPE DIMENSIONS WEIGHT
MAIN SECONDARY CLASS A x B x C
V V V A mm Kg
QCL10/24 1x230 50/60 Hz 1x 24 50/60 Hz
QCL10/230 1x230 50/60 Hz -
CB-QCL10-en_a_te
POWER SUPPLY CONTACTOR
1
RANGE
170 x 170 x 130AC3 230 9
ATTENZIONE !
TOGLIERE TENSIONE PRIMA DI APRIRE
DISCONNECT THE POWER BEFORE OPENING
VOR DEM OFFNEN NETZSTECKER ABSCHALTEN
DEBRANCHER LA LIGNE
AVANT OUVRIR LE COFFRET
DANGER!
ACHTUNG GEFAHR!
DANGER!
DESCONETAR TENSION ANTES DE ABRIR
ATENCION!
A
B
C
33
QCLP10 SeriesQCLP10 SeriesQCLP10 SeriesQCLP10 SeriesQCLP10 Series
For connection of the electrodes to thepanel we recommend the followingcross sections:
Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.
LevelLevelLevelLevelLevelControlControlControlControlControlPPPPPanelanelanelanelanel
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Accessory for electric pump control panels, suitable for tank filling or drainage applications or for activation of audible or visual alarms
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Drop cable with circular cross section.
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Automatic control through probes.• Supply voltage: 1 x 230 V ±10% or 1 x 24 V ±10%.• Frequency: 50/60 Hz.• Voltage to probes: 7,5 V AC at 0,4 mA max.• Protection class: IP55.• Ambient temperature: -5 to +40 °C (according to EN 60439-1).• Maximum relative humidity: 50% at +40°C, provided that no condensation occurs (according to EN 60439-1).• Wall mounted.• Enclosure made of plastic material, with clear door enabling access to the magnetothermal switch.• Electrodes suitable for water at a maximum temperature of 60°C.• Set of three electrodes included in the supply.
TABELLA CAVI
CABLE SECTION
mm2
0 50 0,5
50 100 0,75
100 200 1,0
200 400 2,5
CB-CASEL-en_b_te
LENGHT
m
SERIE QCLP10
TYPE MAGNETO- DIMENSIONS WEIGHT
MAIN SECONDARY CLASS THERMAL SWITCH A x B x C
V V V A mm Kg
QCLP10/24 1x230 50/60 Hz 1x 24 50/60 Hz
QCLP10/230 1x230 50/60 Hz -
CB-QCLP10-en_b_te
POWER SUPPLY
C 10A Icn 6 KA
CONTACTOR
1,5
RANGE
205 x 220 x 160AC3 230 9
34
For connection of the electrodes to thepanel we recommend the followingcross sections:
Three-pole cables can be used for shortlenghts.Otherwise we recommend the use ofunipolar cables placed at suitabledistance from each other to preventthe capacitive effect of the cable frominterfering with the proper operationof the electronic module.
KitKitKitKitKit24 V Level24 V Level24 V Level24 V Level24 V LevelProbeProbeProbeProbeProbe
KSL SeriesKSL SeriesKSL SeriesKSL SeriesKSL Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Accessory for electric panels.
SERIE SLD
TYPE DIMENSIONS WEIGHT PANELS
MAIN POWER TYPE A x B x C
V VA V~ A mm Kg
KIT KSL/24 1x24 50/60 Hz 3,5 N0-C-NC 250 8 90 x 36 x 60 0,5QSCS-QM-QTD-Q3D-Q3Y-
Q3A-Q3I-Q3SF
CB-SLD-en_b_te
POWER SUPPLY CONTACT
RANGE
OPTIONALOPTIONALOPTIONALOPTIONALOPTIONALACCESACCESACCESACCESACCESSORIESSORIESSORIESSORIESSORIES• Drop cable with circular cross section.
TABELLA CAVI
CABLE SECTION
mm2
0 50 0,5
50 100 0,75
100 200 1,0
200 400 2,5
CB-CASEL-en_b_te
LENGHT
m
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Electronic module for use of probes as protection against dry running.• Supply voltage: 1 x 24 V ±10% for model SLD/24.• Frequency: 50/60 Hz.• Absorbed power: 3,5 VA max.• Voltage to probes: 7,5 V AC at 0,4 mA max.• Switch contact 24 V AC at 5 A max (250 W max).• Designed for installation on Lowara electric panels featuring DIN bar.• Electrodes suitable for water at a maximum temperature of 60°C.
CONSTRUCTIONCONSTRUCTIONCONSTRUCTIONCONSTRUCTIONCONSTRUCTIONCHARACTERISTICCHARACTERISTICCHARACTERISTICCHARACTERISTICCHARACTERISTICSSSSS• Module made of plastic material with DIN bar attachment.• Cables with quick plug-in connectors.• Set of three electrodes included in the supply.• Electrodes with nylon 6 body, stainless steel sensitive element brass washer and nitrile rubber seal.
35
LightningLightningLightningLightningLightningProtectionProtectionProtectionProtectionProtection
DPF SeriesDPF SeriesDPF SeriesDPF SeriesDPF Series
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Accessory for electric panels.
SERIE VR
TYPE VOLTAGE PANELS
V
DPF 1 x 220-240 50/60 Hz QSM - QSC - QSCS - QPC
KIT VR1 1 x 220-230 50/60 Hz QM - QDRM - QDRM2 - QDRMC - QDRMC2
KIT VR3 3 x 400 50/60 Hz QTD - QDR - QDR2 - Q3D
KIT SCA 3 3 x 400 50/60 Hz Q3Y-Q3A-Q3I-Q3SF-Q3D
CB-VR-en_c_te
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Varistors for overvoltage protection of three-phase lines.• To be connected between the phases (VR3 model).• Operating voltage: 460 V AC.• Maximum varistor voltage: 750 V with 100 A peak current.• Designed for installation on Lowara electric panels featuring DIN bar.
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Lightning arresters for overvoltage protection of three-phase lines. To be connected between the phases and the heart conductor,• Operating voltage: 500 V AC.• Maximum varistor voltage: 2,5 kW with 40 kA peak current.• Designed for installation on Lowara electric panels featuring DIN bar.
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• Varistor for overvoltage protection of single-phase lines. To be connected between the phase and neutral conductor.• Operating voltage: 460 V AC.• Maximum varistor voltage: 750 V with 100 A peak current.
VR SeriesVR SeriesVR SeriesVR SeriesVR Series
SCA3 SeriesSCA3 SeriesSCA3 SeriesSCA3 SeriesSCA3 Series
36
ElectronicElectronicElectronicElectronicElectronicboardboardboardboardboard
KIT RILS20KIT RILS20KIT RILS20KIT RILS20KIT RILS20SeriesSeriesSeriesSeriesSeries
APPLICAAPPLICAAPPLICAAPPLICAAPPLICATIONSTIONSTIONSTIONSTIONS• Applicable to Lowara electronic boards series SM20C and SDR20B.
SPECIFICASPECIFICASPECIFICASPECIFICASPECIFICATIONSTIONSTIONSTIONSTIONS• 12 Vdc power input from motherboard.• Six low profile 12 Vdc relays with 1A 230 Vac exchange contact.• Indicator LED’s available for each relay.• Available signals: power-on, manual/automatic mode, pump 1 running, pump 2 running, thermal overload, level alarm.• Assembly: with board guides as well as 4 holes for flat-mounting on uprights.• Customer-side output connections: removable clamp.• Maximum dimensions: A=112 mm, B=80 mm, C=22 mm.
PRODUCTPRODUCTPRODUCTPRODUCTPRODUCTFEAFEAFEAFEAFEATURESTURESTURESTURESTURESComplete electronic board providing cleansystem status contacts. Can be connected,via an 8-way serial cable with sealed plug,to boards SM20C, SDR20B (1000 mm longcable supplied). 1500 mm long cableavailable on request.
A
B
C
37
38
Xylem1) The tissue in plants that brings water upward from the roots; 2) a leading global water technology company.
We’re 12,000 people unifi ed in a common purpose: creating innovative solutions to meet our world’s water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water effi ciently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to xyleminc.com.
Headquarters
LOWARA S.r.l. UnipersonaleVia Lombardi 1436075 Montecchio Maggiore - Vicenza - ItalyTel.(+39) 0444 707111 - Fax(+39) 0444 492166e-mail: [email protected]: www.lowara.com - www.completewatersystems.comLOWARA reserves the right to make modifi cation without prior notice.LOWARA is a trademark of Xylem Inc. or one of its subsidiaries.