8 October, 2012 Emerson Process Management(India) Private Limited
Plot A-145/4, TTC Industrial Area
MIDC Pawane
Calibration Data Sheet Consistent with ISO 10474 3.1B or EN 10204 3.1
Navi Mumbai 400 705. India
Tel : (91) 22 66736000, 66736001
FAX: (91) 22 66736005
Customer Information Manufacturer Information
Name: Sales Order:
PO: Line:
Device Information Calibration Information
Device Type: Pressure Transmitter Factory: INDIATag No: Station Name:
Serial No: Operator ID:
Model No: Calibration Date:
Module Serial No:Output:
08230004
PROLIFIC SYSTEMS AND TECHNOLOGIES PVT LT
PST/JMK/12-13/060A
2051TG3A2B21AB4M5D4Q4
11032397
MRK-2
1038
10/8/2012 12:12:04PM
18383723
1
Linear
Calibration Data
% of Range Analog Output (mA) Pass/FailApplied Pressure Requested Applied Pressure % Span Error
Range: 0.0000 TO 20.0000 bar
2000.000 kPa 20.0000 bar 20.0044 0.0275 PASS100.000
1600.000 kPa 16.0000 bar 16.8038 0.0238 PASS80.000
1200.000 kPa 12.0000 bar 13.6026 0.0163 PASS60.000
800.000 kPa 8.0000 bar 10.4018 0.0113
PASS40.000
400.000 kPa 4.0000 bar 7.1972 -0.0175 PASS20.000
0.000 kPa 0.0000 bar 3.9998 -0.0012 PASS0.000
This is to certify that the listed product meets the applicable Rosemount Specifications.
Measuring and test equipment used in the manufacture and inspection of the listed product are
traceable to the National Institute of Standards and Technology. The calibration system was
designed to meet the intent of ANSI Z540-1-1994.
HEMANT SHIRSAT
ROSEMOUNT REPRESENTATIVE
1708230004_Q4-PRESSURE_IMMC_1Page 1 of 1